M E M O R A N D U M - NFPA...Apr 08, 2010  · Report on Proposals – June 2011 NFPA 90A 4.3.6.3.1...

63
M E M O R A N D U M TO: NFPA Technical Committee on Air Conditioning FROM: Linda MacKay DATE: April 8, 2010 SUBJECT: NFPA 90A A2011 ROP Letter Ballot Final Results The Final Results of the NFPA 90A ROP Letter Ballot are as follows: 28 Members Eligible to Vote 1 Ballot was not returned (Howard) Reasons for negative votes, etc. from alternate members are not included unless the ballot from the principal member was not received. All votes were affirmative on all ballot items with the exception of those noted in the attached report. According to the final ballot results, all ballot items received the necessary 2/3 required affirmative votes to pass ballot. ATTACHMENT

Transcript of M E M O R A N D U M - NFPA...Apr 08, 2010  · Report on Proposals – June 2011 NFPA 90A 4.3.6.3.1...

  • M E M O R A N D U M TO: NFPA Technical Committee on Air Conditioning FROM: Linda MacKay DATE: April 8, 2010 SUBJECT: NFPA 90A A2011 ROP Letter Ballot Final Results The Final Results of the NFPA 90A ROP Letter Ballot are as follows: 28 Members Eligible to Vote 1 Ballot was not returned (Howard) Reasons for negative votes, etc. from alternate members are not included unless the ballot from the principal member was not received. All votes were affirmative on all ballot items with the exception of those noted in the attached report. According to the final ballot results, all ballot items received the necessary 2/3 required affirmative votes to pass ballot. ATTACHMENT

  • Report on Proposals – June 2011 NFPA 90A_______________________________________________________________________________________________90A-1 Log #30

    _______________________________________________________________________________________________Marcelo M. Hirschler, GBH International / Rep. American Fire Safety Council

    Revise text to read as follows:

    1.2 Purpose.This standard shall prescribe minimum requirements for safety to life and property from fire. These requirements shall

    be intended to accomplish the following:(1) Restrict the spread of smoke through air duct systems within a building or into a building from the outside(2) Restrict the spread of fire through air duct systems from the area of fire origin, whether located within the

    building or outside(3) Maintain the fire-resistive integrity of building components and elements such as floors, partitions, roofs, walls,

    and floor- or roof-ceiling assemblies affected by the installation of air duct systems(4) Minimize the ignition sources and combustibility of the elements of the air duct systems(5) Permit the air duct systems in a building to be used for the additional purpose of emergency smoke control3.3.3* Air Connector. A conduit for transferring air between an air duct or plenum and an air terminal unit or an air

    inlet or air outlet.3.3.4 Air Distribution System. A continuous passageway for the transmission of air that, in addition to air ducts, can

    include air connectors, air duct fittings, dampers, plenums, fans, and accessory air-handling equipment but that does notinclude conditioned spaces.3.3.5 Air Duct. A conduit or passageway for conveying air to or from heating, cooling, air conditioning, or ventilating

    equipment, but not including the plenum.3.3.6 Air Duct Covering. A material such as an adhesive, insulation, banding, a coating(s), film, or a jacket used to

    cover the outside surface of an air duct, fan casing, or duct plenum.3.3.7 Air Duct Lining. A material such as an adhesive, insulation, a coating(s), or film used to line the inside surface of

    an air duct, fan casing, or duct plenum.3.3.22* Plenum. A compartment or chamber to which one or more air ducts are connected and that forms part of the

    air distribution system.4.2.4.2.2 Unlisted solar energy air distribution system components shall be accompanied by supportive information

    demonstrating that the components have flame spread and smoke developed indexes that are not in excess of those ofthe air duct system permitted by this standard.4.2.4.3.1 Mechanical refrigeration used with air duct systems shall be installed in accordance with recognized safety

    practices.4.2.4.4.1 Oil-burning heating furnaces combined with cooling units in the same air duct system shall be installed in

    accordance with NFPA 31, Standard for the Installation of Oil-Burning Equipment.4.2.4.4.2 Gas-burning heating furnaces combined with cooling units in the same air duct system shall be installed in

    accordance with NFPA 54, National Fuel Gas Code.4.2.4.5.1 Where electrical resistance or fuel-burning heaters are installed in air ducts, the air duct coverings and their

    installation shall comply with the provisions of 4.3.5.3.4.3.1 Air Ducts.4.3.1.1 Air Ducts shall be constructed of iron, steel, aluminum, copper, concrete, masonry, or clay tile, except as

    otherwise permitted in 4.3.1.2 or 4.3.1.3.4.3.1.2 Class 0 or Class 1 rigid or flexible air ducts tested in accordance with ANSI/UL 181, Standard for Safety

    Factory-Made Air Ducts and Air Connectors, and installed in conformance with the conditions of listing shall bepermitted to be used for ducts when air temperature in the ducts does not exceed 121°C (250°F) or when used asvertical ducts serving not more than two adjacent stories in height.4.3.1.3 Gypsum Board Air Ducts.4.3.1.3.2 The air temperature limits of 4.3.1.3.1 shall not apply when gypsum board material is used for emergency

    smoke exhaust air ducts.4.3.1.4 All air duct materials shall be suitable for continuous exposure to the temperature and humidity conditions of

    the environmental air in the air duct.4.3.1.5.1 Air ducts Ducts shall be considered to be in compliance with this requirement where constructed and

    installed in accordance with the ASHRAE Handbook — HVAC Systems and Equipment, and with one of the following asapplicable:

    1Printed on 4/7/2010

  • Report on Proposals – June 2011 NFPA 90A(1) NAIMA Fibrous Glass Duct Construction Standard(2) SMACNA Fibrous Glass Duct Construction Standard(3) SMACNA HVAC Duct Construction Standards — Metal and Flexible(4) SMACNA HVAC Air Duct Leakage Test Manual4.3.1.6 Where no standard exists for the construction of air ducts, the ducts shall be constructed to withstand both the

    maximum positive and negative pressures of the system at fan shutoff.4.3.2.1 Air connectors are limited-use, flexible air ducts that shall not be required to conform to the provisions for air

    ducts where they meet the requirements of 4.3.2.1.1 through 4.3.2.1.5.4.3.3.1* Pipe and duct insulation and coverings, duct linings, vapor retarder facings, adhesives, fasteners, tapes, and

    supplementary materials added to air ducts, plenums, panels, and duct silencers used in duct systems, unless otherwiseprovided for in 4.3.3.1.1 or 4.3.3.1.2, shall have, in the form in which they are used, a maximum flame spread index of25 without evidence of continued progressive combustion and a maximum smoke developed index of 50 when tested inaccordance with ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials, or withANSI/UL 723, Standard Test Method for Surface Burning Characteristics of Building Materials. Pipe and duct insulationand coverings, duct linings and their adhesives, and tapes shall use the specimen preparation and mounting proceduresof ASTM E 2231, Standard Practice for Specimen Preparation and Mounting of Pipe and Duct Insulation Materials toAssess Surface Burning Characteristics.4.3.3.1.1 The flame spread index and smoke developed index requirements of 4.3.3.1 shall not apply to air duct

    weatherproof coverings where they are located entirely outside of a building, do not penetrate a wall or roof, and do notcreate an exposure hazard.4.3.3.2 Closure systems for use with rigid and flexible air ducts tested in accordance with ANSI/UL 181, Standard for

    Safety Factory-Made Air Ducts and Air Connectors, shall have been tested, listed, and used in accordance with theconditions of their listings, in accordance with one of the following:(1) ANSI/UL 181A, Standard for Safety Closure Systems for Use with Rigid Air Ducts(2) ANSI/UL 181B, Standard for Safety Closure Systems for Use with Flexible Air Ducts and Air Connectors4.3.3.3 Coverings and linings for air ducts, pipes, plenums, and panels, including all pipe and duct insulation materials,

    shall not flame, glow, smolder, or smoke when tested in accordance with ASTM C 411, Standard Test Method forHot-Surface Performance of High-Temperature Thermal Insulation, at the temperature to which they are exposed inservice. In no case shall the test temperature be below 121°C (250°F).4.3.3.4 Air duct Duct coverings shall not extend through walls or floors that are required to be fire stopped or required

    to have a fire resistance rating, unless such coverings meet the requirements of NFPA 80, Standard for Fire Doors andOther Opening Protectives.4.3.3.5* Air duct Duct linings shall be interrupted at fire dampers to prevent interference with the operation of devices.4.3.3.6 Air duct Duct coverings shall not be installed so as to conceal or prevent the use of any service opening.4.3.4.1* Wiring shall not be installed in air ducts, except as permitted in 4.3.4.2 through 4.3.4.4.4.3.4.2 Wiring shall be permitted to be installed in air ducts, only if the wiring is directly associated with the air

    distribution system and does not exceed 1.22 m (4 ft).4.3.5 Air Duct Access and Inspection.4.3.5.1 A service opening shall be provided in air ducts adjacent to each fire damper, smoke damper, and any smoke

    detectors that need access for installation, cleaning, maintenance, inspection, and testing.4.3.5.3 Horizontal air ducts and plenums shall be provided with service openings to facilitate the removal of

    accumulations of dust and combustible materials.4.3.5.3.1 Service openings shall be located at approximately 6.1 m (20 ft) intervals along the air duct and at the base

    of each vertical riser, unless otherwise permitted in 4.3.5.3.2 through 4.3.5.3.4.4.3.5.4 Inspection windows shall be permitted in air ducts, provided they are glazed with wired glass.4.3.5.5 Openings in walls or ceilings shall be provided so that service openings in air ducts are accessible for

    maintenance and inspection needs.4.3.5.6 Where a service opening is necessary in an air duct located above the ceiling of a floor- or roof-ceiling

    assembly that has been tested and assigned a fire resistance rating in accordance with NFPA 251, Standard Methods ofTests of Fire Resistance of Building Construction and Materials, access shall be provided in the ceiling.4.3.6 Air Duct Integrity.4.3.6.1 Air ducts Ducts shall be located where they are not subject to damage or rupture, or they shall be protected to

    maintain their integrity.4.3.6.2 Where an air duct is located outdoors, the air duct, together with its covering or lining, shall be protected from

    harmful elements.4.3.6.3 Where electrical, fossil fuel, or solar energy collection heat sources are installed in air ducts, the installation

    shall avoid the creation of a fire hazard.

    2Printed on 4/7/2010

  • Report on Proposals – June 2011 NFPA 90A4.3.6.3.1 For air ducts rated as Class 1 in accordance with ANSI/UL 181, Standard for Safety Factory-Made Air Ducts

    and Air Connectors, air duct coverings and linings shall be interrupted at the immediate area of operation of such heatsources in 4.3.5.3 in order to meet the clearances specified as a condition of the equipment listing, unless otherwisepermitted in 4.3.5.3.2 or 4.3.5.3.3.4.3.11.2.6.8 Air ducts Ducts complying with 4.3.1.2 and air connectors complying with 4.3.2 shall be permitted.4.3.11.3.2 Fabricated plenum and apparatus casing shall be constructed of materials and by methods specified in

    4.3.1 and in accordance with the following:(1) The casing and plenum construction standards in SMACNA HVAC Duct Construction Standards — Metal and

    Flexible(2) ASHRAE Handbook — HVAC Systems and Equipment(3) Subsection 4.3.3 for all air duct coverings, duct lining, acoustical liner/cells, and miscellaneous materials4.3.11.5.5.7 Air ducts Ducts complying with 4.3.1.2 and air connectors complying with 4.3.2 shall be permitted.5.1.1 General. Air-handling equipment rooms shall be classified into the following three categories:(1) Those used as air plenums (usually return air)(2) Those with air ducts that open directly into a shaft(3) Other air-handling unit rooms5.1.3 Air-Handling Equipment Rooms That Have Air Ducts That Open Directly into a Shaft.5.2.1 Air Duct Clearance.5.2.1.1 The clearance from metal air ducts used for heating to assemblies constructed of combustible materials,

    including plaster on wood lath, shall be not less than 12.7 mm (½ in.), or the combustible material shall be protected withminimum 6.35 mm (¼ in.)–thick approved insulating material.5.2.2 Structural Members. The installation of air ducts, including the hangers, shall not reduce the fire resistance

    rating of structural members.5.2.3 Ceiling Assemblies. Where the installation of the hangers for the components of an air duct system penetrates

    an existing ceiling of a fire-resistive floor- or roof-ceiling assembly and necessitates removal of a portion of that ceiling,the replacement material shall be identical to that which was removed, or shall be approved as equivalent to that whichwas removed.5.2.4 As an alternative to repairing the existing ceiling, a new ceiling shall be permitted to be installed below the air

    duct system, provided the fire resistance rating of the floor- or roof-ceiling design is not reduced.5.3.1.1* Approved fire dampers shall be provided where air ducts penetrate or terminate at openings in walls or

    partitions required to have a fire resistance rating of 2 hours or more.5.3.2.1 Where air ducts extend through only one floor and serve only two adjacent stories, the air ducts shall beenclosed (see 5.3.4.1), or fire dampers shall be installed at each point where the floor is penetrated.5.3.3.1 Where air ducts and openings for air ducts are used in a floor- or roof-ceiling assembly that is required to have

    a fire resistance rating, all the materials and the construction of the assembly, including the air duct materials and thesize and protection of the openings, shall conform with the design of the fire-resistive assembly, as tested in accordancewith NFPA 251, Standard Methods of Tests of Fire Resistance of Building Construction and Materials.5.3.4.1 Air ducts Ducts that pass through the floors of buildings that require the protection of vertical openings shall be

    enclosed with partitions or walls constructed of materials as permitted by the building code of the authority havingjurisdiction, as indicated in 5.3.4.2 or 5.3.4.3, unless otherwise permitted by 5.3.4.3.1.5.3.4.2 The shaft enclosure shall have a minimum fire resistance rating (based on possible fire exposure from either

    side of the partition or wall) of 1 hour where such air ducts are located in a building less than four stories in height.5.3.4.3 The shaft enclosure shall have a minimum fire resistance rating (based on possible fire exposure from either

    side of the partition or wall) of 2 hours where such air ducts are located in a building four stories or more in height.5.3.4.3.1 Where an air duct penetrates only one floor, or one floor and an air-handling equipment penthouse floor, and

    the air duct contains a fire damper located where the duct penetrates the floor, an air duct enclosure shall not berequired.5.3.4.4 A fire-resistive enclosure used as an air duct shall conform with 4.3.1 and 5.3.4.2 through 5.3.4.3.5.3.4.5 Shafts that constitute air ducts or that enclose air ducts used for the movement of environmental air shall not

    enclose the following:(1) Exhaust ducts used for the removal of smoke- and grease-laden vapors from cooking equipment(2) Ducts used for the removal of flammable vapors(3) Ducts used for moving, conveying, or transporting stock, vapor, or dust(4) Ducts used for the removal of nonflammable corrosive fumes and vapors(5) Refuse and linen chutes(6) Piping, except for noncombustible piping conveying water or other nonhazardous or nontoxic materials(7) Combustible storage

    3Printed on 4/7/2010

  • Report on Proposals – June 2011 NFPA 90A5.3.4.6.1 A fire damper shall not be required where an air duct system serving only one story is used only for exhaust

    of air to the outside and is contained within its own dedicated shaft.5.3.5.1 Smoke dampers shall be installed at or adjacent to the point where air ducts pass through required smoke

    barriers, but in no case shall a smoke damper be installed more than 0.6 m (2 ft) from the barrier, or after the first airduct inlet or outlet, whichever is closer to the smoke barrier, unless otherwise permitted by 5.3.5.1.1 through 5.3.5.1.5.5.4.5.2.2.1* Where combination fire and smoke dampers are located within air ducts that are part of an engineered

    smoke-control system, fusible links or other approved heat-responsive devices shall have a temperature ratingapproximately 28°C (50°F) above the maximum smoke-control system designed operating temperature.5.4.5.4* Dampers shall close against the maximum calculated airflow of that portion of the air duct system in which

    they are installed.5.4.6.1 The locations and mounting arrangement of all fire dampers, smoke dampers, ceiling dampers, and fire

    protection means of a similar nature required by this standard shall be shown on the drawings of the air duct systems.5.4.6.2 Dampers required to close in airflow shall have the calculated airflow at their location shown on the drawings of

    the air duct system.6.4.4.3 Where smoke detectors required by Section 6.4 are installed in a building not equipped with an approved fire

    alarm system as specified by 6.4.4.2, the following shall occur:(1) Smoke detector activation required by Section 6.4 shall cause a visual signal and an audible signal in a

    normally occupied area.(2) Smoke detector trouble conditions shall be indicated visually or audibly in a normally occupied area and shall

    be identified as air duct detector trouble.A.1.1 An air duct system has the potential to convey smoke, hot gases, and flame from area to area and to supply air

    to aid combustion in the fire area. For these reasons, fire protection of an air duct system is essential to safety to life andthe protection of property. However, an air duct system's fire integrity also enables it to be used as part of a building'sfire protection system.Guidance for the design of smoke-control systems is provided in NFPA 92A, Standard for Smoke-Control Systems

    Utilizing Barriers and Pressure Differences.A.3.3.3 Air Connector. Some such devices are listed in UL Heating, Cooling, Ventilating and Cooking Equipment

    Directory under the category “Connectors (ALNR).” These devices, since they do not meet all the requirements for airducts, have limitations on their use, length, and location. (For limitations on the use of air connectors, see 4.3.2.1.)A.6.3 The dampers should close as quickly as practicable, subject to requirements of the system fan and air duct

    characteristics. The designer should evaluate whether the smoke dampers normally should be open or closed andshould consider the fail-safe position of the dampers during an event such as a power failure.A.6.3.2 Within the scope of this document, smoke dampers reduce the possibility of smoke transfer within ductwork or

    through wall openings. Activation of smoke dampers can be by area detectors that are installed in the related smokecompartment or by detectors that are installed in the air duct systems. See NFPA 72, National Fire Alarm Code.A.6.4 The use of smoke detectors in relationship to HVAC systems and high air movement areas and the details

    regarding their optimum installation are covered in Section 5.7 of NFPA 72, National Fire Alarm Code.Protection provided by the installation of smoke detectors and related requirements is intended to prevent the

    distribution of smoke through the supply air duct system and, preferably, to exhaust a significant quantity of smoke tothe outside. Neither function, however, guarantees either the early detection of fire or the detection of smokeconcentrations prior to dangerous smoke conditions where smoke movement is other than through the supply airsystem.Where smoke-control protection for a facility is determined to be needed, see NFPA 92A, Standard for Smoke-Control

    Systems Utilizing Barriers and Pressure Differences.A.6.4.2 The summation of the capacities of individual supply-air fans should be made where such fans are connected

    to a common supply air duct system (i.e., all fans connected to a common air duct supply system should be consideredas constituting a single system with respect to the applicability of the Chapter 6 provisions that are dependent on systemcapacity).B.1.1 Owners should develop a greater awareness of the life and property protection abilities of air-conditioning

    systems and should establish a planned maintenance schedule. Failure to maintain proper conditions of cleanliness inair duct systems and carelessness in connection with repair operations have been important contributing causes ofseveral fires that have involved air-conditioning systems. The recommendations in this annex apply, in general, to theperiod of operation of the system; systems operating only part of the year should be given a thorough general checkupbefore starting operation and again after a shutdown.

    This brings consistency with the NEC, which talks about ducts and plenums and not about air ducts.The entire standard addresses air distribution systems. Moreover, there is inconsistency within the standard nowbecause some sections talk about ducts and some talk about air ducts but they mean the same.

    4Printed on 4/7/2010

  • Report on Proposals – June 2011 NFPA 90A

    The committee concludes that there is a need to have the specific phrase "air duct(s)" toprevent any confusion of the term.

    Affirmative: 26 Negative: 11 Howard, III, E.

    HIRSCHLER, M.: It is important to get consistency in language with the NEC and within NFPA 90A and the referencesto duct and air duct are inconsistent at present.

    _______________________________________________________________________________________________90A-2 Log #CP10

    _______________________________________________________________________________________________Technical Committee on Air Conditioning,

    Review entire document to: 1) Update any extracted material by preparing separate proposals to doso, and 2) review and update references to other organizations documents, by preparing proposal(s) as required.

    To conform to the NFPA Regulations Governing Committee Projects.

    Affirmative: 271 Howard, III, E.

    5Printed on 4/7/2010

  • Report on Proposals – June 2011 NFPA 90A_______________________________________________________________________________________________90A-3 Log #53

    _______________________________________________________________________________________________Joshua Elvove, U.S. General Services Administration

    Revise text to read as follows:Revise 1.1 as follows:

    This standard shall cover construction, installation, operation, and maintenance of systems for air conditioning andventilating, including filters, ducts, and related equipment, to protect life and property from fire, smoke, and gasesresulting from fire or from conditions having manifestations similar to fire. The standard does not cover maintenance offire dampers, ceiling dampers, smoke dampers and combination fire/smoke dampers.Add new text to A.1.1 as follows:Maintenance of fire dampers, ceiling dampers, smoke dampers and combination fire/smoke dampers requirements can

    be found in other NFPA standards.NFPA 80 is now responsible for inspection, testing and maintenance of fire and ceiling dampers;

    NFPA 105 is now responsible for inspection, testing and maintenance of smoke dampers; and both NFPA 80 and NFPA105 address inspection, testing and maintenance of combination fire/smoke dampers. As such, any discussion ofinspection, testing and maintenance of fire damper, smoke dampers, or combination fire/smoke dampers should bereferred to the respective standard. Note: I recognize that Section 5.4.8 already addresses this, but it would be better ifthe scope addressed at the beginning of this standard (in fact, Section 5.4.8 could even be deleted in favor of locatingthis text in Section 1.1 and it’s annex.

    Revise text to read as follows:Revise 1.1 as follows:

    This standard shall cover construction, installation, operation, and maintenance of systems for air conditioning andventilating, including filters, ducts, and related equipment, to protect life and property from fire, smoke, and gasesresulting from fire or from conditions having manifestations similar to fire. The standard does not cover maintenance offire dampers, ceiling dampers, smoke dampers and combination fire/smoke dampers.Add new text to A.1.1 as follows:Maintenance of fire dampers, ceiling dampers, smoke dampers and combination fire/smoke dampers requirements can

    be found in other NFPA 80 and NFPA105 standards.The committee concluded that the change to the annex note is appropriate. Scope is what is

    covered. The proposal goes into what is not covered and the committee does not want to to use a laundry list of what isnot covered. If its not in the scope then it isn't covered.

    Affirmative: 271 Howard, III, E.

    6Printed on 4/7/2010

  • Report on Proposals – June 2011 NFPA 90A_______________________________________________________________________________________________90A-4 Log #49

    _______________________________________________________________________________________________David Handwork, Arkansas State University Facilities Management / Rep. APPA.ORG - Association of

    Education Facilities ExecutivesNew text to read as follows:

    Add NFPA 79 to the list of referenced publications as shown below:2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.NFPA 30, Flammable and Combustible Liquids Code, 2008 edition.NFPA 31, Standard for the Installation of Oil-Burning Equipment, 2006 edition.NFPA 54, National Fuel Gas Code, 2009 edition.NFPA 70®, National Electrical Code®, 2008 edition.NFPA 72®, National Fire Alarm Code®, 2007 edition.NFPA 75, Standard for the Protection of Information Technology Equipment, 2009 edition.

    NFPA 80, Standard for Fire Doors and Other Opening Protectives, 2007 edition.NFPA 101®, Life Safety Code®, 2009 edition.NFPA 105, Standard for the Installation of Smoke Door Assemblies and Other Opening Protectives, 2007 edition.NFPA 251, Standard Methods of Tests of Fire Resistance of Building Construction and Materials, 2006 edition.NFPA 259, Standard Test Method for Potential Heat of Building Materials, 2008 edition.NFPA 262, Standard Method of Test for Flame Travel and Smoke of Wires and Cables for Use in Air-Handling Spaces,

    2007 edition.NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire

    Growth, 2006 edition.®, 2009 edition.

    The scope statement of NFPA 79, as shown below, would seem to apply to the control systems forHVAC systems. Extract from NFPA 79:

    Many HVAC control systems are at least as complicated as industrial process control systems. This proposal issubmitted to correlate with another proposal APPA.ORG has submitted to this committee during this ROP cycle toreduce electrical risk in HVAC control cabinets. Reference to NFPA 79 in NFPA 90A strengthens the interoperability ofthe entire suite of NFPA leading safety practice documents.

    The document is not referenced in NFPA 90A and is therefore not a proper reference.

    Affirmative: 271 Howard, III, E.

    7Printed on 4/7/2010

  • Report on Proposals – June 2011 NFPA 90A_______________________________________________________________________________________________90A-5 Log #33

    _______________________________________________________________________________________________Marcelo M. Hirschler, GBH International / Rep. American Fire Safety Council

    Revise text to read as follows:2.3.2 ASTM International Publications.ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959.ASTM C 411, Standard Test Method for Hot-Surface Performance of High-Temperature Thermal Insulation, 1997 2005

    .ASTM D 93, Standard Test Methods for Flashpoint by Pensky-Martens Closed Cup Tester, 2006 2008 .ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials, 2006a 2009c .ASTM E 136, Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750°C, 2004 2009a .ASTM E 2231, Standard Practice for Specimen Preparation and Mounting of Pipe and Duct Insulation Materials to

    Assess Surface Burning Characteristics, 2007 2009 .Standards update

    Affirmative: 271 Howard, III, E.

    8Printed on 4/7/2010

  • Report on Proposals – June 2011 NFPA 90A_______________________________________________________________________________________________90A-6 Log #41

    _______________________________________________________________________________________________Marcelo M. Hirschler, GBH International / Rep. American Fire Safety Council

    Revise text to read as follows:

    810 First Street, NE, Suite 510, Washington, DC 20002 6525 Belcrest Road, Ste 480,Hyattsville, MD 20782 .

    Fire Resistance Design Manual (GA 600) , 18th edition, 2006 19th Edition (2009) .2.3.4 NAIMA Publications.North American Insulation Manufacturers Association, 44 Canal Center Plaza, Suite 310, Alexandria, VA 22314.Fibrous Glass Duct Construction Standards, 5th edition, 2002.2.3.5 SMACNA Publications.Sheet Metal and Air Conditioning Contractors' National Association, 4201 Lafayette Center Drive, Chantilly, VA 20151

    22151-1209.Fibrous Glass Duct Construction Standards , 7th edition, 2003.HVAC Air Duct Leakage Test Manual, 1st edition, 1985.HVAC Duct Construction Standards — Metal and Flexible, 3rd edition, 2005 2nd edition, 1995 with addendum #1,

    November 1997.2.3.6 UL Publications.Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.ANSI/UL 181, Standard for Safety Factory-Made Air Ducts and Air Connectors, 2005.ANSI/UL 181A, Standard for Safety Closure Systems for Use with Rigid Air Ducts, 2005.ANSI/UL 181B, Standard for Safety Closure Systems for Use with Flexible Air Ducts and Air Connectors, 2005.ANSI/UL 555, Standard for Safety Fire Dampers, 2006.ANSI/UL 555C, Standard for Safety Ceiling Dampers, 2006.ANSI/UL 555S, Standard for Safety Smoke Dampers, 1999 2006.ANSI/UL 723, Standard Test Method for Surface Burning Characteristics of Building Materials, 2008 2003.ANSI/UL 867, Standard for Safety Electrostatic Air Cleaners, 2000 2004.ANSI/UL 900, Standard for Safety Air Filter Units, 2004.ANSI/UL 1820, Standard for Safety Fire Test of Pneumatic Tubing for Flame and Smoke Characteristics, 2004.ANSI/UL 1887, Standard for Safety Fire Test of Plastic Sprinkler Pipe for Visible Flame and Smoke Characteristics,

    2004.ANSI/UL 1995, Standard for Safety Heating and Cooling Equipment, 2003, revised 2005.ANSI/UL 2024, Standard for Optical-Fiber and Communications Cable Raceway, 2004.ANSI/ 2043, Standard for Safety Fire Test for Heat and Visible Smoke Release for Discrete Products and Their

    Accessories Installed in Air-Handling Spaces, 2008 1996, revised 2001.Standards update

    Gypsum Association, 810 First Street, NE, Suite 510, Washington, DC 20002 6525 Belcrest Road, Ste 480,Hyattsville, MD 20782 .

    Fire Resistance Design Manual (GA 600), 18th edition, 2006 19th Edition (2009).2.3.4 NAIMA Publications.North American Insulation Manufacturers Association, 44 Canal Center Plaza, Suite 310, Alexandria, VA 22314.Fibrous Glass Duct Construction Standards, 5th edition, 2002.2.3.5 SMACNA Publications.Sheet Metal and Air Conditioning Contractors' National Association, 4201 Lafayette Center Drive, Chantilly, VA 20151

    22151 1209.Fibrous Glass Duct Construction Standards, 7th edition, 2003.HVAC Air Duct Leakage Test Manual, 1st edition, 1985.HVAC Duct Construction Standards — Metal and Flexible, 3rd edition, 2005 2nd edition, 1995 with addendum #1,

    November 1997.The committee handled the UL documents under Proposal 90A-7 (Log #44).

    9Printed on 4/7/2010

  • Report on Proposals – June 2011 NFPA 90AAffirmative: 27

    1 Howard, III, E.

    _______________________________________________________________________________________________90A-7 Log #44

    _______________________________________________________________________________________________Bob Eugene, Underwriters Laboratories Inc.

    2.3.6 UL Publications.Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.ANSI/UL 181, Standard for Safety Factory-Made Air Ducts and Air Connectors, 2005, Revised 2008.ANSI/UL 181A, Standard for Safety Closure Systems for Use with Rigid Air Ducts, 2005, Revised 2008.ANSI/UL 181B, Standard for Safety Closure Systems for Use with Flexible Air Ducts and Air Connectors, 2005,

    Revised 2008.ANSI/UL 555, Standard for Safety Fire Dampers, 2006, Revised 2009.ANSI/UL 555C, Standard for Safety Ceiling Dampers, 2006, Revised 2009.ANSI/UL 555S, Standard for Safety Smoke Dampers, 2006 1999, Revised 2009.ANSI/UL 723, Standard Test Method for Surface Burning Characteristics of Building Materials, 2003 2008.ANSI/UL 867, Standard for Safety Electrostatic Air Cleaners, 2004 2000, Revised 2007.ANSI/UL 900, Standard for Safety Air Filter Units, 2004, Revised 2009.ANSI/UL 1820, Standard for Safety Fire Test of Pneumatic Tubing for Flame and Smoke Characteristics, 2004,

    Revised 2009.ANSI/UL 1887, Standard for Safety Fire Test of Plastic Sprinkler Pipe for Visible Flame and Smoke Characteristics,

    2004, Revised 2009.ANSI/UL 1995, Standard for Safety Heating and Cooling Equipment, 2003, revised 2005, Revised 2008.ANSI/UL 2024, Standard for Optical-Fiber and Communications Cable Raceway, 2004, Revised 2007.ANSI/UL 2043, Standard for Safety Fire Test for Heat and Visible Smoke Release for Discrete Products and Their

    Accessories Installed in Air-Handling Spaces, 1996, revised 2001 2008.Update referenced standards to most recent revisions. Add ANSI approval designation to UL 2043.

    Affirmative: 271 Howard, III, E.

    10Printed on 4/7/2010

  • Report on Proposals – June 2011 NFPA 90A_______________________________________________________________________________________________90A-8 Log #CP2

    _______________________________________________________________________________________________Technical Committee on Air Conditioning,

    Adopt the preferred definition from the NFPA Glossary of Terms as follows:. Having access to but which first may requires the removal of a panel, door, or similar covering of the

    item described. [ , 2009]

    This definition is the preferred definition from the Glossary of Terms. Changing the secondarydefinition to the preferred definition complies with the Glossary of Terms Project.

    The proposed definition add a requirement the committee concludes is too limiting.

    Affirmative: 271 Howard, III, E.

    BUNKER, JR., M.: I agree with the action to reject. This definition would be in direct conflict with the NEC. Further, theproposed definition would be nearly useless. The proposed definition would seem to imply that removal of drywall orother fixed coverings would be covered by the definition of accessible.HIRSCHLER, M.: The Air Conditioning Committee should request that the definition for this term in NFPA 90A be the

    primary definition, as it is more generic than the one from NFPA 54, which is now the preferred one. This should bedone by writing to Standards Council. This advice was also recommended by the Glossary Advisory Committee.

    _______________________________________________________________________________________________90A-9 Log #CP3

    _______________________________________________________________________________________________Technical Committee on Air Conditioning,

    Adopt the preferred definition from the NFPA Glossary of Terms as follows:A device used to reduce or remove airborne solids from heating, ventilating, and air-conditioning

    systems. ( , 2009)This definition is the preferred definition from the Glossary of Terms. Changing the secondary

    definition to the preferred definition complies with the Glossary of Terms Project.

    Affirmative: 271 Howard, III, E.

    11Printed on 4/7/2010

  • Report on Proposals – June 2011 NFPA 90A_______________________________________________________________________________________________90A-10 Log #36

    _______________________________________________________________________________________________Marcelo M. Hirschler, GBH International / Rep. American Fire Safety Council

    New text to read as follows:3.3.x Continued progressive combustion. A flame front progressing more than 10.5 ft (3.2 m) beyond the centerline of

    the burners at some time during a 30 minute test in accordance with ASTM E 84 or ANSI/UL 723.The concept of “evidence of continued progressive combustion” has never been defined and is usually

    interpreted by labs as meaning that the flame front in the ASTM E 84 tunnel does not exceed 10.5 ft during the 30minute test. This provides a definition.NFPA 703 (and building codes) address the following: “a flame spread of 25 or less, and shows no evidence of

    significant progressive combustion when the test is continued for an additional 20-minute period; nor does the flamefront progress more than 10.5 ft (3.2 m) beyond the centerline of the burners at any time during the test.” In fact, the “noevidence of significant progressive combustion”, which is undefined is simply taken to mean that the flame front doesnot progress more than 10.5 ft during the 30 minute test.

    New text to read as follows:3.3.x Continued progressive combustion. A flame front progressing more than 10.5 ft (3.2 m) beyond the centerline of

    the burners at some time during a 30 minute test during a test in accordance with ASTM E 84 or ANSI/UL 723.The committee clarified the language.

    Affirmative: 26 Negative: 11 Howard, III, E.

    BEITEL, J.: I vote against this because the 10.5 ft is used only for fire-retardant treated wood during a 30 minute test.The "continuous progressive combustion" used in 3.3 applies to Limited-combustible material and not to FRTW. In thisdefinition, the 10.5 ft limit is not applicable...no justification for use in this definition.

    HIRSCHLER, M.: Note that there is a difference between “evidence of continued progressive combustion”, which isused in the definition of limited combustible and “evidence of significant progressive combustion” which is used for the30 minute ASTM E 84 test when dealing with fire retardant treated wood.

    _______________________________________________________________________________________________90A-11 Log #CP4

    _______________________________________________________________________________________________Technical Committee on Air Conditioning,

    Adopt the preferred definition from the NFPA Glossary of Terms as follows:A system that is intended for the purpose of smoke control only, which

    are separate systems of air moving and distribution equipment that do not function under normal building operatingconditions. [ , 2009]

    This definition is the preferred definition from the Glossary of Terms. Changing the secondarydefinition to the preferred definition complies with the Glossary of Terms Project.

    The term is not used in the document.

    Affirmative: 271 Howard, III, E.

    12Printed on 4/7/2010

  • Report on Proposals – June 2011 NFPA 90A_______________________________________________________________________________________________90A-12 Log #CP5

    _______________________________________________________________________________________________Technical Committee on Air Conditioning,

    Adopt the preferred definition from the NFPA Glossary of Terms as follows:A listed device installed in a ceiling membrane of a fire resistance-rated

    floor-ceiling or roof-ceiling assembly to automatically limit the radiative heat transfer through an air inlet/outlet opening.[ , 2009]

    This definition is the preferred definition from the Glossary of Terms. Changing the secondarydefinition to the preferred definition complies with the Glossary of Terms Project.

    Adopt the preferred definition from the NFPA Glossary of Terms as follows:A listed device installed in a ceiling membrane of a fire resistance-rated

    floor-ceiling or roof-ceiling assembly to automatically limit the radiative heat transfer through an air inlet/outlet opening.See committee action and statement on Proposal 90A-13 (Log #56).

    Affirmative: 271 Howard, III, E.

    _______________________________________________________________________________________________90A-13 Log #56

    _______________________________________________________________________________________________Joshua Elvove, U.S. General Services Administration

    Revise the definition of “Ceiling Radiation Damper” in 3.3.13.1 as follows:A listed device installed in a ceiling membrane of a fire resistance-rated

    floor-ceiling or roof ceiling assembly to automatically limit the radiant radiative heat transfer through an air outlet or airinlet/outlet opening. [ , 2009] in the ceiling of a floor- or roof-ceiling assembly having not less than a 1-hour fireresistance rating. Such a device is described in the construction details for some tested floor- or roof-ceiling assemblies.

    Some such devices are listed in UL under thecategory of “Ceiling Damper (CABS).”

    The definition for ceiling radiation damper should be consistent between the standard that requires itsinstallation (NFPA 90A) and the standard that requires its maintenance (NFPA 80), given it’s the same piece ofequipment. The proposed definition comes from NFPA 80 (which basically comes from NFPA 5000). If the NFPA 90Acommittee has an issue with this definition, suggest they reconcile this with the NFPA 80 committee. Note: the NFPAmanual of style doesn’t permit performance criteria within a definition, hence, the language regarding “not less than 1hour” should be stricken anyway (performance criteria belongs in Chapter 5).

    Revise the definition of “Ceiling Radiation Damper” in 3.3.13.1 as follows:A listed device installed in a ceiling membrane of a fire resistance-rated

    floor-ceiling or roof ceiling assembly to automatically limit the radiant radiative heat transfer through an air outlet or airinlet/outlet opening. [5000, 2009] in the ceiling of a floor- or roof-ceiling assembly having not less than a 1-hour fireresistance rating. Such a device is described in the construction details for some tested floor- or roof-ceiling assemblies.

    Some such devices are listed in UL under thecategory of “Ceiling Damper (CABS).”

    The committee removed the word "radiation" to be consistent with the text and the teststandard.

    Affirmative: 271 Howard, III, E.

    13Printed on 4/7/2010

  • Report on Proposals – June 2011 NFPA 90A_______________________________________________________________________________________________90A-14 Log #57

    _______________________________________________________________________________________________Joshua Elvove, U.S. General Services Administration

    Revise definition of “Fire Damper” in 3.3.13.3 as follows:A device, installed in an air distribution system, designed to close automatically upon

    detection of heat, to interrupt migratory airflow, and to restrict the passage of flame. [ , 2009] Fire dampers areclassified for use in either static systems or for dynamic systems, where the dampers are rated for closure under airflow.[ , 2009]

    Some such devices are listed in ULunder the category of “Fire Dampers for Fire Barrier and Smoke Applications (EMME).”

    The definition for fire damper should be consistent between the standard that requires its installation(NFPA 90A) and the standard that requires its maintenance (NFPA 80), given it’s the same piece of equipment. Theproposed definition comes from NFPA 80 (which basically comes from NFPA 221) and simply adds the secondsentence from the definition of fire damper in NFPA 80. If the NFPA 90A committee has an issue with this definition,suggest they reconcile this with the NFPA 80 committee.

    Revise definition of “Fire Damper” in 3.3.13.3 as follows:A device, installed in an air distribution system, designed to close automatically upon

    detection of heat, to interrupt migratory airflow, and to restrict the passage of flame. [ , 2009]Add to the end of annex note Fire dampers are classified for use in either static systems or for dynamicsystems, where the dampers are rated for closure under airflow. [ , 2009]

    The committee removed the reference to NFPA 221, Standard for High Challenge Fire Walls,Fire Walls, and Fire Barrier Walls, as the chosen definition does not match that in 221. The committee moved theproposed last sentence to the Annex.

    Affirmative: 271 Howard, III, E.

    _______________________________________________________________________________________________90A-15 Log #CP6

    _______________________________________________________________________________________________Technical Committee on Air Conditioning,

    Adopt the preferred definition from the NFPA Glossary of Terms as follows:A blower or exhauster assembly comprising blades or runners and housings or casings. [ 2006]

    This definition is the preferred definition from the Glossary of Terms. Changing the secondarydefinition to the preferred definition complies with the Glossary of Terms Project.

    Affirmative: 25 Negative: 21 Howard, III, E.

    BUCKLEY, J.: The proposed fan definition does not cover the use of plug fans (fans that do not have a housingaround the fan).DILLON, M.: The proposed definition is technically in error and incompatible with the industry-accepted definition of a

    fan, to wit: see "ASHRAE Terminology of Heating, Ventilation, Air Conditioning, & Refrigeration", pg. 42 Fan 'Device formoving air by two or more blades or vanes attached to a rotating shaft. See also impeller.' Please note in reviewing themore correct definition that there are several fans that do not include a housing, i.e. plug fans.

    14Printed on 4/7/2010

  • Report on Proposals – June 2011 NFPA 90A_______________________________________________________________________________________________90A-16 Log #31

    _______________________________________________________________________________________________Marcelo M. Hirschler, GBH International / Rep. American Fire Safety Council

    Revise text to read as follows:3.3.16* Fire Resistance Rating. The time, in minutes or hours, that materials or assemblies have withstood a fire

    exposure as established in accordance with the test procedures of NFPA 251, Standard Methods of Tests of FireResistance of Building Construction and Materials, ASTM E 119, Standard Test Methods for Fire Tests of BuildingConstruction and Materials, or ANSI/UL 263, Standard for Fire Tests of Building Construction and Materials .4.3.5.6 Where a service opening is necessary in an air duct located above the ceiling of a floor- or roof-ceiling

    assembly that has been tested and assigned a fire resistance rating in accordance with NFPA 251, Standard Methods ofTests of Fire Resistance of Building Construction and Materials, ASTM E 119, Standard Test Methods for Fire Tests ofBuilding Construction and Materials, or ANSI/UL 263, Standard for Fire Tests of Building Construction and Materials,access shall be provided in the ceiling.5.3.3.1 Where air ducts and openings for air ducts are used in a floor- or roof-ceiling assembly that is required to have

    a fire resistance rating, all the materials and the construction of the assembly, including the air duct materials and thesize and protection of the openings, shall conform with the design of the fire-resistive assembly, as tested in accordancewith NFPA 251, Standard Methods of Tests of Fire Resistance of Building Construction and Materials, ASTM E 119,Standard Test Methods for Fire Tests of Building Construction and Materials, or ANSI/UL 263, Standard for Fire Tests ofBuilding Construction and Materials.

    NFPA codes and standards, including NFPA 101, recognize ASTM E 119 and UL 263 as alternateacceptable tests for assessing fire resistance rating.

    Affirmative: 271 Howard, III, E.

    15Printed on 4/7/2010

  • Report on Proposals – June 2011 NFPA 90A_______________________________________________________________________________________________90A-17 Log #37

    _______________________________________________________________________________________________Marcelo M. Hirschler, GBH International / Rep. American Fire Safety Council

    Revise text to read as follows:3.3.20* Limited-Combustible (Material). Refers to a building construction material not complying with the definition of

    noncombustible material that, in the form in which it is used, has a potential heat value not exceeding 3500 Btu/lb (8141kJ/kg), where tested in accordance with NFPA 259, Standard Test Method for Potential Heat of Building Materials, andincludes either of the following: (1) materials having a structural base of noncombustible material, with a surfacing notexceeding a thickness of 1/8 in. (3.2 mm) that has a flame spread index not greater than 50; and (2) materials, in theform and thickness used, having neither a flame spread index greater than 25 and a flame front progressing no morethan 10.5 ft (3.2 m) in a 30 minute test nor evidence of continued progressive combustion, and of such composition thatsurfaces that would be exposed by cutting through the material on any plane would have neither a flame spread indexgreater than 25 nor a flame front progressing no more than 10.5 ft (3.2 m) in a 30 minute test evidence of continuedprogressive combustion, when tested in accordance with ASTM E 84, Standard Test Method of Surface BurningCharacteristics of Building Materials, or ANSI/UL 723 Standard Test Method for Surface Burning Characteristics ofBuilding Materials.4.3.1.3.1 Gypsum board having a maximum flame spread index of 25 and a flame front progressing no more than 10.5

    ft (3.2 m) in a 30 minute test without evidence of continued progressive combustion and a maximum smoke developedindex of 50 when tested in accordance with ASTM E 84, Standard Test Method for Surface Burning Characteristics ofBuilding Materials, or ANSI/UL 723, Standard Test Method for Surface Burning Characteristics of Building Materials,shall be permitted to be used for negative pressure exhaust and return ducts where the temperature of the conveyed airdoes not exceed 52°C (125°F) in normal service.4.3.3.1* Pipe and duct insulation and coverings, duct linings, vapor retarder facings, adhesives, fasteners, tapes, and

    supplementary materials added to air ducts, plenums, panels, and duct silencers used in duct systems, unless otherwiseprovided for in 4.3.3.1.1 or 4.3.3.1.2, shall have, in the form in which they are used, a maximum flame spread index of25 and a flame front progressing no more than 10.5 ft (3.2 m) in a 30 minute test without evidence of continuedprogressive combustion and a maximum smoke developed index of 50 when tested in accordance with ASTM E 84,Standard Test Method for Surface Burning Characteristics of Building Materials, or with ANSI/UL 723, Standard TestMethod for Surface Burning Characteristics of Building Materials. Pipe and duct insulation and coverings, duct liningsand their adhesives, and tapes shall use the specimen preparation and mounting procedures of ASTM E 2231,Standard Practice for Specimen Preparation and Mounting of Pipe and Duct Insulation Materials to Assess SurfaceBurning Characteristics.4.3.11.2.6.9 Materials that, in the form in which they are used, have a potential heat value not exceeding 8141 kJ/kg

    (3500 Btu/lb), where tested in accordance with NFPA 259, Standard Test Method for Potential Heat of BuildingMaterials, and include either of the following:(1) Materials having a structural base of noncombustible material, with a surfacing not exceeding a thickness of

    3.2 mm (1/8 in.) that has a flame spread index not greater than 50(2) Materials, in the form and thickness used, having neither a flame spread index greater than 25 and a flame

    front progressing no more than 10.5 ft (3.2 m) in a 30 minute test nor evidence of continued progressive combustion ,and of such composition that surfaces that would be exposed by cutting through the material on any plane would haveneither a flame spread index greater than 25 and a flame front progressing no more than 10.5 ft (3.2 m) in a 30 minutetest nor evidence of continued progressive combustion , when tested in accordance with ASTM E 84, Standard TestMethod of Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard Test Method of SurfaceBurning Characteristics of Building Materials.4.3.11.5.5.8 Materials that, in the form in which they are used, have a potential heat value not exceeding 3500 Btu/lb

    (8141 kJ/kg), where tested in accordance with NFPA 259, Standard Test Method for Potential Heat of BuildingMaterials, and include either of the following:(1) Materials having a structural base of noncombustible material, with a surfacing not exceeding a thickness of

    1/8 in. (3.2 mm) that has a flame spread index not greater than 50(2) Materials, in the form and thickness used, having neither a flame spread index greater than 25 and a flame

    front progressing no more than 10.5 ft (3.2 m) in a 30 minute test nor evidence of continued progressive combustion,and of such composition that surfaces that would be exposed by cutting through the material on any plane would haveneither a flame spread index greater than 25 and a flame front progressing no more than 10.5 ft (3.2 m) in a 30 minutetest nor evidence of continued progressive combustion , when tested in accordance with ASTM E 84, Standard Test

    16Printed on 4/7/2010

  • Report on Proposals – June 2011 NFPA 90AMethod of Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard Test Method for SurfaceBurning Characteristics of Building Materials.

    The concept of “evidence of continued progressive combustion” has never been defined and is usuallyinterpreted by labs as meaning that the flame front in the ASTM E 84 tunnel does not exceed 10.5 ft during the 30minute test.NFPA 703 (and building codes) address the following: “a flame spread of 25 or less, and shows no evidence of

    significant progressive combustion when the test is continued for an additional 20-minute period; nor does the flamefront progress more than 10.5 ft (3.2 m) beyond the centerline of the burners at any time during the test.” In fact, the “noevidence of significant progressive combustion”, which is undefined is simply taken to mean that the flame front doesnot progress more than 10.5 ft during the 30 minute test.

    This change is not needed based upon the action on 90A-10 (Log #36).

    Affirmative: 271 Howard, III, E.

    _______________________________________________________________________________________________90A-18 Log #CP7

    _______________________________________________________________________________________________Technical Committee on Air Conditioning,

    Adopt the preferred definition from the NFPA Glossary of Terms as follows:Refers to a building construction material not complying with the definition of

    noncombustible that, in the form in which it is used, has a potential heat value not exceeding 8141 kJ/kg (3500 Btu/lb),where tested in accordance with NFPA 259 and includes either (1) materials having a structural base of noncombustiblematerial, with a surfacing not exceeding a thickness of 3.2 mm (1/8 in.) that has a flame spread index not greater than50, or (2) materials, in the form and thickness used having neither a flame spread index greater than 25 nor evidence ofcontinued progressive combustion, and of such composition that surfaces that would be exposed by cutting through thematerial on any plane would have neither a flame spread index greater than 25 nor evidence of continued progressivecombustion, when tested in accordance with UL 723 or ASTM E 84. ( , 2009)

    This definition is the preferred definition from the Glossary of Terms. Changing the secondarydefinition to the preferred definition complies with the Glossary of Terms Project.

    The committee prefers the current definition and the substantiation is incorrect as this is not theonly "preferred" definition.

    Affirmative: 271 Howard, III, E.

    17Printed on 4/7/2010

  • Report on Proposals – June 2011 NFPA 90A_______________________________________________________________________________________________90A-19 Log #CP8

    _______________________________________________________________________________________________Technical Committee on Air Conditioning,

    Adopt the preferred definition from the NFPA Glossary of Terms as follows:A material that, in the form in which it is used and under the conditions anticipated,

    will not ignite, burn, support combustion, or release flammable vapors, when subjected to fire or heat. Materials that arereported as passing ASTM E 136 Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750Degrees C, shall be are considered noncombustible materials. [ 2009]

    This definition is the preferred definition from the Glossary of Terms. Changing the secondarydefinition to the preferred definition complies with the Glossary of Terms Project.

    Affirmative: 271 Howard, III, E.

    KOFFEL, W.: The proposed revision to the definition is not consistent with revisions to NFPA 220 and a new definitionwithin the NFPA 101 and NFPA 5000 projects.

    _______________________________________________________________________________________________90A-20 Log #17

    _______________________________________________________________________________________________Marcelo M. Hirschler, GBH International / Rep. American Fire Safety Council

    Revise text to read as follows:3.3.21* Noncombustible Material. A material that, in the form in which it is used and under the conditions anticipated,

    will not ignite, burn, support combustion, or release flammable vapors, when subjected to fire or heat. Materials that arereported as passing ASTM E 136, Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750Degrees C, shall be considered noncombustible materials.[220, 2009]A.3.3.21 A material that is reported as complying with the pass/fail criteria of ASTM E 136 when tested in accordance

    with the test method and procedure in ASTM E 2652, Standard Test Method for Behavior of Materials in a Tube Furnacewith a Cone-shaped Airflow Stabilizer, at 750 Degrees C, is considered a noncombustible material.

    The definition proposed is consistent with that in NFPA 220, Standard on Types of BuildingConstruction, 2009 edition. The proposed definition will be extracted from NFPA 220, 2009 edition. The annex note isbeing added because the equipment for ASTM E 136 is virtually unavailable and therefore ASTM E 2652 has beendeveloped as an alternate apparatus and is presented as an option. This has already been addressed in several otherdocuments, including NFPA 101, 5000 and draft NFPA 556.

    Affirmative: 271 Howard, III, E.

    18Printed on 4/7/2010

  • Report on Proposals – June 2011 NFPA 90A_______________________________________________________________________________________________90A-21 Log #CP9

    _______________________________________________________________________________________________Technical Committee on Air Conditioning,

    Adopt the preferred definition from the NFPA Glossary of Terms as follows:A continuous membrane, or a membrane with discontinuities created by protected openings,

    where such membrane is designed and constructed to restrict the movement of smoke. [ 2009]This definition is the preferred definition from the Glossary of Terms. Changing the secondary

    definition to the preferred definition complies with the Glossary of Terms Project.

    Affirmative: 271 Howard, III, E.

    _______________________________________________________________________________________________90A-22 Log #58

    _______________________________________________________________________________________________Joshua Elvove, U.S. General Services Administration

    Revise the definition of “Smoke Barrier” in 3.3.24 and revise corresponding annex note A.3.3.24. asfollows:

    A continuous membrane, or a member with discontinuities created by protected openings,where such member either vertical or horizontal, such as a wall, floor, or ceiling assembly, that is designed andconstructed to restrict the movement of smoke.

    A smoke barriers might be vertically or horizontally aligned, such as a wall, floor or ceilingassembly. A smoke barrier might or might not have a fire resistance rating. See also NFPA , ,Chapter 8, for additional guidance.

    The definition for smoke barrier should be consistent between NFPA documents that utilize the term.The proposed definition comes from NFPA 101 which is the same as the definition in NFPA 5000. If the NFPA 90Acommittee has an issue with this definition, suggest they reconcile this with the NFPA 101 committee. Note: the NFPAmanual of style doesn’t permit lists (i.e,. using the term “such as” in a definition); hence, relocating this text to the annexis more appropriate.

    Revise the definition of “Smoke Barrier” in 3.3.24 and revise corresponding annex note A.3.3.24. as follows:A continuous membrane, or a membrane with discontinuities created by protected openings,

    where such membrane either vertical or horizontal, such as a wall, floor, or ceiling assembly, that is designed andconstructed to restrict the movement of smoke.

    A smoke barrier might be vertically or horizontally aligned, such as a wall, floor or ceilingassembly. A smoke barrier might or might not have a fire resistance rating. See also NFPA , ,Chapter 8, for additional guidance.

    The committee editorially changed "member" to "membrane" in two places and "barriers" to"barrier".

    Affirmative: 271 Howard, III, E.

    19Printed on 4/7/2010

  • Report on Proposals – June 2011 NFPA 90A_______________________________________________________________________________________________90A-23 Log #CP16

    _______________________________________________________________________________________________Technical Committee on Air Conditioning,

    Revise text to read as follows:4.2.2.2* Air filters shall be rated either as Class 1 or Class 2 in accordance comply with ANSI/UL 900, Standard for

    Safety Air Filter Units.

    Class I and 2 are no longer used by the UL standard.

    Affirmative: 271 Howard, III, E.

    _______________________________________________________________________________________________90A-24 Log #50

    _______________________________________________________________________________________________David Handwork, Arkansas State University Facilities Management / Rep. APPA.ORG - Association of

    Education Facilities ExecutivesNew text to read as follows:

    Add the following text to Chapter 4Moving parts, such as shafts, pulleys, couplings and belts, installed within air

    ducts that are accessible for maintenance, shall be protected with metal guards that enclose all moving parts.The danger posed by moving parts -- especially the belts associated with driven equipment within

    large, walk-in air ducts -- ought to be self evident. This is a borderline product-standard/field-installation issue that oughtto be addressed in both product and installation standards for HVAC equipment. This is a first step for covering it in aninstallation standard even if it means field fabrication of guarding. Hopefully, manufacturers will take a cue from thisrequirement and build it into the cost of the product.

    The committee does not find this addition to be necessary nor within the committee's scope.This more appropriately belongs in an OSHA standard.

    Affirmative: 271 Howard, III, E.

    20Printed on 4/7/2010

  • Report on Proposals – June 2011 NFPA 90A_______________________________________________________________________________________________90A-25 Log #2

    _______________________________________________________________________________________________Jonathan Paul, Lebanon Fire Dept.

    New text to read as follows:(New paragraph 4.2.4.1.3): Window air-conditioning units shall only be used for listed use.

    Numerous improper installations of window air-conditioning are found on inspection of buildings. Inparticular, computer server rooms are being cooled by window air-conditioning units instead of thru the wall units orcentral air. These window units are being found exhausting into wall spaces, closets and attics, presenting a possiblefire hazard.Air-conditioning manufacturer’s that I have spoken to have stated that such installations void all warranties and safety

    features.

    This proposal is outside the scope of the document. NFPA 90A does not address appliances.

    Affirmative: 271 Howard, III, E.

    _______________________________________________________________________________________________90A-26 Log #19

    _______________________________________________________________________________________________Marcelo M. Hirschler, GBH International / Rep. American Fire Safety Council

    Revise text to read as follows:

    To get language consistent with other equivalent sections.

    Affirmative: 271 Howard, III, E.

    21Printed on 4/7/2010

  • Report on Proposals – June 2011 NFPA 90A_______________________________________________________________________________________________90A-27 Log #29

    _______________________________________________________________________________________________Marcelo M. Hirschler, GBH International / Rep. American Fire Safety Council

    Revise text to read as follows:4.3.1.5.1 Air ducts shall be considered to be in compliance with this requirement where constructed and installed in

    accordance with the ASHRAE Handbook — HVAC Systems and Equipment, and with one of the following as applicable:(1) NAIMA Fibrous Glass Duct Construction Standards(2) SMACNA Fibrous Glass Duct Construction Standard(3) SMACNA HVAC Duct Construction Standards — Metal and Flexible(4) SMACNA HVAC Air Duct Leakage Test ManualA.4.3.3.5 See NAIMA Fibrous Glass Duct Liner Standard, and NAIMA Fibrous Glass Duct Construction Standards

    and NAIMA Residential Fibrous Glass Duct Construction Standards for additional information.Corrects title and correlates with references

    The committee concludes that residential duct construction is outside the scope of 90A.

    Affirmative: 271 Howard, III, E.

    _______________________________________________________________________________________________90A-28 Log #18

    _______________________________________________________________________________________________Marcelo M. Hirschler, GBH International / Rep. American Fire Safety Council

    Revise text to read as follows:

    UL 2024 is used for testing and listing all types of raceways, including optical fiber raceways,communications raceways, signaling raceways, fire alarm raceways. CATV raceways when they are to be used inplenums. The critical issue is that the raceway has been tested and listed to UL 2024 and it is important to eliminatepotential language problems. The change in nomenclature does not change the requirements.

    Revise text to read as follows:Electrical wires and cables or optical fiber cables, or optical-fiber and communications raceways within a

    duct enclosure shall comply with 4.3.4.The committee deleted raceways from this section as it is not the correct location.

    Affirmative: 271 Howard, III, E.

    22Printed on 4/7/2010

  • Report on Proposals – June 2011 NFPA 90A_______________________________________________________________________________________________90A-29 Log #42

    _______________________________________________________________________________________________Marcelo M. Hirschler, GBH International / Rep. American Fire Safety Council

    Revise text to read as follows:4.3.2 Air Connectors.4.3.2.1 Air connectors are limited-use, flexible air ducts that shall not be required to conform to the provisions for air

    ducts where they meet the requirements of 4.3.2.1.1 through 4.3.2.1.5.4.3.2.1.1 Air connectors shall conform to the requirements for Class 0 or Class 1 connectors when tested in

    accordance with ANSI/UL 181, Standard for Safety Factory-Made Air Ducts and Air Connectors.4.3.2.1.2 Class 0 or Class 1 air connectors shall not be used for ducts containing air at temperatures in excess of

    121°C (250°F).4.3.2.1.3 Air connector runs shall not exceed 4.27 m (14 ft) in length.4.3.2.1.4 Air connectors shall not pass through any wall, partition, or enclosure of a vertical shaft that is required to

    have a fire resistance rating of 1 hour or more.4.3.2.1.5 Air connectors shall not pass through floors.4.3.2.2 Vibration isolation connectors in duct systems shall be made of an approved flame-retardant fabric or shall

    consist of sleeve joints with packing of approved material, each having a maximum flame spread index of 25 and amaximum smoke developed index of 50.4.3.2.2 Vibration isolation connectors in duct systems shall be made of materials having a maximum flame spread

    index of 25 and a maximum smoke developed index of 50.4.3.2.3 Approved flame-retardant fabric Unlisted vibration isolation connectors complying with 4.3.2.2 having a

    maximum length of 254 mm (10 in.) in the direction of airflow shall be permitted to be used.4.3.2.4 Wiring shall not be installed in air connectors.

    Vibration isolation connectors need to be made of materials complying with the same requirements asother materials in ducts. Even fabrics are being manufactured that meet the ASTM E 84 25/50 requirements.A “flame retardant fabric” is usually taken to mean a fabric that complies with the small-scale test from NFPA 701,

    which has been eliminated from that standard for over 10 years. Present versions of NFPA 701 contain two tests(depending on the weight, or areal density of the fabric) but both of them are very much less severe than ASTM E 84and neither one measures smoke. The term “flame retardant fabric” is misleading and has been eliminated from mostNFPA documents.In fact, this section can be interpreted to consider that the fabrics need to meet both fire tests: NFPA 701 and ASTM E

    84 with 25/50. This is a clarification, in that case. Fabrics that meet ASTM E 84 with 25/50 need not be tested also toNFPA 701.Note that the proposal does not require testing of the system and thus allows unlisted combinations of materials tested

    individually as long as they are restricted to a maximum length of 10 in.

    Revise text to read as follows:4.3.2 Air Connectors.4.3.2.1 Air connectors are limited-use, flexible air ducts that shall not be required to conform to the provisions for air

    ducts where they meet the requirements of 4.3.2.1.1 through 4.3.2.1.5.4.3.2.1.1 Air connectors shall conform to the requirements for Class 0 or Class 1 connectors when tested in

    accordance with ANSI/UL 181, Standard for Safety Factory-Made Air Ducts and Air Connectors.4.3.2.1.2 Class 0 or Class 1 air connectors shall not be used for ducts containing air at temperatures in excess of

    121°C (250°F).4.3.2.1.3 Air connector runs shall not exceed 4.27 m (14 ft) in length.4.3.2.1.4 Air connectors shall not pass through any wall, partition, or enclosure of a vertical shaft that is required to

    have a fire resistance rating of 1 hour or more.4.3.2.1.5 Air connectors shall not pass through floors.4.3.2.2 Vibration isolation connectors in duct systems shall be made of an approved flame-retardant fabric or shall

    consist of sleeve joints with packing of approved material, each having a maximum flame spread index of 25 and amaximum smoke developed index of 50.4.3.2.2 Vibration isolation connectors in duct systems shall be made of materials having a maximum flame spread

    index of 25 and a maximum smoke developed index of 50.4.3.2.3 Approved flame-retardant fabric Unlisted vibration isolation connectors complying with 4.3.2.2 having a

    23Printed on 4/7/2010

  • Report on Proposals – June 2011 NFPA 90Amaximum length of 254 mm (10 in.) in the direction of airflow shall be permitted to be used.4.3.2.3 4 Wiring shall not be installed in air connectors.

    The committee deleted 4.2.3 and renumber and replace 4.3.2.2 with the wording from 90A-26(Log #19) for consistency.

    Affirmative: 271 Howard, III, E.

    _______________________________________________________________________________________________90A-30 Log #51

    _______________________________________________________________________________________________David Handwork, Arkansas State University Facilities Management / Rep. APPA.ORG - Association of

    Education Facilities ExecutivesRevise text to read as follows:

    Air connector runs shall not exceed 4.27 1.83 m (14 6 ft) in length.The allowance of 14 ft of flexible duct connectors is excessive in practice for the following reasons:

    1. Texas A&M research supported by ASHRAE exhibited flexible ductwork at compression levels over 4% has 2 to 10times the pressure losses over sheet metal (Ref. Weaver – “Static pressure losses in 6”, 8”, and 10” non-metallic flexibleduct” ).2. Excessive pressure losses will compromise effective air distribution and will dramatically increase fan energy use.3. Flexible ductwork in commercial settings can be more susceptible to damage than rigid duct. Air leaks in punctured

    ductwork can be a significant loss in energy and air flow to the conditioned space. Allowing lengths up to 14 ft. increasesthe susceptibility to damage.4. The energy losses relative to excessive use of flexible ductwork contradicts NFPA 900 – Building Energy Code5. The air flow losses with flexible ductwork can also contradict ASHRAE 62 for adequate airflow to spaces.

    Note: Supporting material is available for review at NFPA Headquarters.

    The committee disagrees with the change as the substantiation is not relevant to fire safety noris technically supported.

    Affirmative: 271 Howard, III, E.

    24Printed on 4/7/2010

  • Report on Proposals – June 2011 NFPA 90A_______________________________________________________________________________________________90A-31 Log #39

    _______________________________________________________________________________________________Marcelo M. Hirschler, GBH International / Rep. American Fire Safety Council

    New text to read as follows:4.3.3.1.2 Smoke detectors required by 6.4.4 shall not be required to meet flame spread index or smoke developed

    index requirements.4.3.3.1.3 Smoke detectors installed in ducts or plenums shall exhibit a maximum peak optical density of 0.5 or less, an

    average optical density of 0.15 or less, and a peak heat release rate of 100 kW or less when tested in accordance withUL 2043, Standard for Safety Fire Test for Heat and Visible Smoke Release for Discrete Products and TheirAccessories Installed in Air-Handling Spaces.4.3.11.2.6.7 Smoke detectors shall comply with the requirements of 4.3.3.1.3 not be required to meet the provisions of

    this section.4.3.11.5.6 Smoke detectors shall comply with the requirements of 4.3.3.1.3 not be required to meet the requirements

    of 4.3.11.5.1.The standard does not contain any fire safety requirements associated with smoke detectors at

    present. If the smoke detectors are installed in ducts or in plenums they should comply with the requirements of UL2043 just like all other discrete electrical equipment in plenums (see 4.3.11.2.6.5 and 4.3.11.5.5.6). This is probablyalready implied by the plenum sections but needs to be explicitly stated.

    ANSI/UL 268A specifies the flame spread test that is the industry test standard.

    Affirmative: 26 Negative: 11 Howard, III, E.

    HIRSCHLER, M.: Smoke detectors are discrete electrical equipment and they should comply with the samerequirements as other such equipment when installed in plenums.

    BUNKER, JR., M.: I agree with the TC action. The proposed requirements are unnecessary. Most duct smokedetectors installed today are located in external housings and are power limited. They pose little or no safety hazard.

    25Printed on 4/7/2010

  • Report on Proposals – June 2011 NFPA 90A_______________________________________________________________________________________________90A-32 Log #7

    _______________________________________________________________________________________________Stanley Kaufman, CableSafe Inc. / Rep. The Society of the Plastics Industry

    Revise 4.3.4.2 as shown:Wiring shall be permitted to be installed in air ducts, only if the wiring is directly associated with the air

    distribution system and each length of cable exposed to the airflow does not exceed 1.22 m (4 ft).The current text could be interpreted to only permit an aggregate sum of 4 feet of all the cables

    exposed to the airflow.

    This would allow a significant increase in the aggregate total of wire and cable. The committeeprefers the current language as allowing the appropriate amount of wire and cable for the desired level of safety.

    Affirmative: 25 Negative: 21 Howard, III, E.

    KAHN, S.: The proposal should have been accepted. Does the current language indicate the the 4 ft limitation refersto the total length of cable permitted in a duct or that each cable run is limited to 4 ft? There may be several devicesneeded in an air duct and I believe the current wording refers to each cable run. The proposal clarifies the intent of thissection and does not allow for any increased amount of cable.KOFFEL, W.: The current language is not enforceable. Based upon the Committee Statement the total length of cable

    in air ducts (is that an individual duct or the entire system of ducts within an building) is limited to 4 ft.

    _______________________________________________________________________________________________90A-33 Log #8

    _______________________________________________________________________________________________Stanley Kaufman, CableSafe Inc. / Rep. The Society of the Plastics Industry

    Revise 4.3.4.4 as shown:Electrical wires and cables and optical fiber cables shall consist of wires or cables listed as having a

    maximum peak optical density of 0.50 or less, an average optical density of 0.15 or less, and a maximum flame spreaddistance of 1.5 m (5 ft) or less when tested in accordance with NFPA 262,

    , or shall be installed in metal raceways without anoverall nonmetallic covering, or metal sheathed cable without an overall nonmetallic covering,.

    Metal raceways can have a combustible nonmetallic jacket and therefore would not be suitable for anapplication exposed to the airflow. Likewise for metal sheathed cables.

    Affirmative: 271 Howard, III, E.

    26Printed on 4/7/2010

  • Report on Proposals – June 2011 NFPA 90A_______________________________________________________________________________________________90A-34 Log #13

    _______________________________________________________________________________________________William C. Wagner, Certification Solutions

    Revise text to read as follows:4.3.4.4* Electrical wires and cables and optical fiber cables shall be consist of wires or cables listed as having a

    maximum peak optical density of 0.50 or less, an average optical density of 0.15 or less, and a maximum flame spreaddistance of 1.5 m (5 ft) or less when tested in accordance with NFPA 262,

    , or shall be installed in metal raceways, or metalsheathed cable or Reinforced Thermosetting Resin Conduit (RTRC) listed as having a maximum peak optical density of0.50 or less, an average optical density of 0.15 or less, and a maximum flame spread distance of 1.5 m (5 ft) or lesswhen tested in accordance with NFPA 262,

    Paragraph 4.3.4.4 of NFPA 90A currently permits electrical wires and cables and optical fiber cables tobe installed in metal raceways or metal sheathed cable. As an alternative to this, the wires and cables are not requiredto be installed using one of these methods if they themselves comply with the required optical smoke density and flamepropagation requirements specified in NFPA 90A when evaluated in accordance with the Standard Method of Test forFlame Travel and Smoke of Wires and Cables for Use in Air-Handling Spaces, NFPA 262. However, the use of any typeof nonmetallic raceway is not currently permitted.Recent developments in the formulation of materials which can be utilized in the production of Reinforced

    Thermosetting Resin Conduit (RTRC) warrant an expansion of the permitted installation methods. Resins for RTRC thatcomply with the identical flame propagation and smoke optical density requirements currently delineated in NFPA 90Afor wires and cables, while still complying with all listing requirements for RTRC, will permit the use of this alternativewire and cable installation method without any increase in flame and smoke hazards.Therefore, RTRC meeting all of these requirements should be permitted as an acceptable alternative to metal

    raceways for the installation of electrical wires and cables and optical fiber cables. Compliance with the flamepropagation and optical smoke density requirements of NFPA 262, as well as ASTM E 84, has been confirmed throughindependent testing at Underwriters Laboratories. The inclusion of this type of conduit in NFPA 90A is a necessary firststep toward their eventual listing for this application.

    RTRC should not simply be treated as non-combustible. It needs to be tested as othermaterials are. The committee also reaffirms its position not to create a laundry list of products.

    Affirmative: 271 Howard, III, E.

    _______________________________________________________________________________________________90A-35 Log #60

    _______________________________________________________________________________________________Joshua Elvove, U.S. General Services Administration

    Revise 4.3.5.1 as follows:A service opening shall be provided in air ducts adjacent to each fire damper, smoke damper, combination

    fire/smoke damper, and any smoke detectors that need access for installation, cleaning, maintenance, inspection, andtesting.

    To ensure that service openings are also provided for combination fire/smoke dampers.

    Affirmative: 271 Howard, III, E.

    27Printed on 4/7/2010

  • Report on Proposals – June 2011 NFPA 90A_______________________________________________________________________________________________90A-36 Log #61

    _______________________________________________________________________________________________Joshua Elvove, U.S. General Services Administration

    Revise 4.3.5.4 as follows:Inspection windows shall be permitted in air ducts, provided they are glazed with wired or fire protection rated

    glass.To permit other appropriate glazing and not limit this to only wire glass.

    Affirmative: 271 Howard, III, E.

    _______________________________________________________________________________________________90A-37 Log #67

    _______________________________________________________________________________________________Joshua Elvove, U.S. General Services Administration

    Add new 4.3.10.2.3 as follows:Smoke dampers shall be installed in systems with a capacity greater than 7080 L/sec (15,000 ft3/min) to

    isolate the air-handling equipment, including filters, from the remainder of the system on both the building supply andreturn sides, in order to restrict the circulation of smoke, unless specifically exempted by 4.3.10.2.1 or 4.3.10.2.2.

    Air-handling units located on the floor they serve and serving only that floor shall be exempt from therequirements of 4.3.10.2.

    Air-handling units located on the roof and serving only the floor immediately below the roof shall be exemptfrom the requirements of 4.3.10.2.

    Air handling units located in buildings that are completely sprinkler protected in accordance with NFPA 13,do not require smoke dampers on the return side.

    Given the two existing exceptions, it would seem appropriate to allow a third for return air units inbuildings completely protected by sprinkler systems when the sprinkler system has been installed in accordance withNFPA 13, since the likelihood of smoke of any significance in fully sprinklered buildings is minimal. Furthermore, airhandling units of this size already require detection on both the supply and return side which would cause the unit(s) toshut down upon detection of smoke. Hence, whatever little smoke there is would not be recirculated throughout thebuilding. Moreover, smoke from a supply air side filter or motor fire, or from an outside fire would still be prevented fromspreading through the building since the supply side smoke damper is still required.

    The change would eliminate the requirement to "isolate" the unit when the unit catches firewhich is exactly what the committee wants to happen.

    Affirmative: 271 Howard, III, E.

    28Printed on 4/7/2010

  • Report on Proposals – June 2011 NFPA 90A_______________________________________________________________________________________________90A-38 Log #CP1

    _______________________________________________________________________________________________Technical Committee on Air Conditioning,

    Clarify the text that was the subject of the following Formal Interpretation.Is the intent of the paragraph to require multiple locations for return air in a corridor?

    No.Is one point of return air with multiple supply air locations as indicated on the sketch below

    acceptable?Yes.

    ******INSERT ARTWORK HERE******

    The Regulations Governing Committee Projects require that a proposal be processed to clarify the textof a document on which a Formal Interpretation has been issued. After issuance of the next edition of the document, theFormal Interpretation will no longer be published.

    The committee concludes that the text has been sufficiently clarified since this interpretationwas originally issued to permit removing it from publication in future editions.

    Affirmative: 271 Howard, III, E.

    _______________________________________________________________________________________________90A-39 Log #20

    _______________________________________________________________________________________________Marcelo M. Hirschler, GBH International / Rep. American Fire Safety Council

    Revise text to read as follows:

    This requirement is based on the equivalent requirement in the NEC, which has revised the languageto make the requirement more explicit: abandoned materials must be removed. If cables are present intended for futureuse they need to be appropriately identified for future use with a tag.The main reason for requiring removal of abandoned materials is for safety of personnel in terms of the potential for

    abandoned material to fall and/or entangle workers, electrical personnel and firefighters. Note that section 4.3.11.5.8states as follows:“4.3.11.5.8 The accessible portion of abandoned materials exposed to airflow shall be removed.”

    Revise text to read as follows:Accessible abandoned material shall be deemed to be storage and shall be removed not be permitted to

    remain. Where cables are identified for future use with a tag, the tag shall be of sufficient durability to withstand theenvironment involved.

    The committee concludes that the second sentence is covered in the NEC and is not necessaryhere.

    Affirmative: 26 Negative: 11 Howard, III, E.

    BUNKER, JR., M.: The proposal should have been accepted, or as a minimum, should have referenced the NEC forbetter user friendliness.

    29Printed on 4/7/2010

  • Report on Proposals – June 2011 NFPA 90A_____________