M-2-3 Hangers and Supports

download M-2-3 Hangers and Supports

of 214

description

Pipe Support Standards

Transcript of M-2-3 Hangers and Supports

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES MECHANICAL PIPE HANGERS AND SUPPORTS

    1 of 18

    Pipe Hangers and Supports

    Index

    1.0 INTRODUCTION

    1.1. Purpose 1.2. Scope

    2.0 DEFINITIONS 3.0 CODES AND STANDARDS 4.0 DESIGN CRITERIA AND GUIDELINES

    4.1. Component Designation 4.2. Loads 4.3. Pipe Stress 4.4. Welds 4.5. Support Spacing 4.6. The Pipe Support Contractor and Support Details 4.7. Pipe Support Callout 4.8. Specialty Supports 4.9. Support Placement Tolerance

    5.0 PIPE SUPPORT TYPES AND COMPONENTS RIGID SUPPORTS

    5.1. Rod Hangers and Components 5.1.1 Beam Attachments 5.1.2 Hanger Rods 5.1.3 Turnbuckles 5.1.4 Clamps 5.1.5 Welds 5.1.6 Trapeze Hangers

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES MECHANICAL PIPE HANGERS AND SUPPORTS

    2 of 18

    5.1.7 Riser Clamps 5.1.8 Washer Plates

    5.2. Pipe Shoe and Stanchion Supports 5.3. Guides 5.4. Limit Stops 5.5. Anchors 5.6. Welded Pipe Attachments

    6.0 PIPE SUPPORT TYPES AND COMPONENTS ENGINEERED SUPPORTS

    6.1. Variable Spring Hangers 6.2. Constant Supports 6.3. Design of Supplemental Steel

    7.0 REFERENCES

    Appendices

    Appendix A Standard Support Details Appendix B Supplemental Steel Appendix C FRP Standard Support Details Appendix D HDPE Standard Support Details Appendix E Pipe Support Guidelines; FRP & HDPE Pipe

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES MECHANICAL PIPE HANGERS AND SUPPORTS

    3 of 18

    REVISION PAGE 1.0 REVISION 1 1.1 Index:

    Added sub section 4.9 in section 4.0 Added Appendix C: FRP Standard Support Details Added Appendix D: HDPE Standard Support Details Added Appendix E: Pipe Support Guidelines; FRP and HDPE Pipe in section 7.0

    1.2 Appendix A:

    Added Rigid Base Support details RBS-10 through RBS-16 in section 2.0 Added Rod Hanger detail RHS-5 in section 3.0 Added Guide Base Support details GBS-12, GBS-13 and GBS-14 in section 4.0 Added Anchor Base Support details ABS-7, ABS-8 and ABS-9 in section 6.0

    1.3 Appendix B:

    Added detail 1D in section 2.0 Added detail 5G in section 6.0 Added details 7F, 7G, 7H, 7J, 7K and 7L in section 8.0 Added details 8H and 8J in section 9.0 Added detail 11B in section 12.0 Added detail 12B in section 13.0

    1.4 Added Appendix C: FRP Standard Support Details 1.5 Added Appendix D: HDPE Standard Support Details 1.6 Added Appendix E: Pipe Support Guidelines; FRP & HDPE Pipe

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES MECHANICAL PIPE HANGERS AND SUPPORTS

    4 of 18

    PIPE HANGERS AND SUPPORTS 1.0 INTRODUCTION 1.1 Purpose

    This document provides a guideline for the design of pipe supports. The document is not intended to supersede project specific design criteria but to reflect current SCS practices.

    1.2 Scope

    This standard shall apply to pipe supports for piping systems ranging in size up to 24 inches, unless noted otherwise.

    For the purposes of this standard, pipe supports have been divided into two main categories: Rigid Pipe Supports Application where rigid pipe hangers are acceptable.

    Design Engineering shall be responsible for the location and selection of rigid pipe hangers. Generally, after the engineer has identified the type and location of rigid supports, the detailer shall use the guidelines in section 5.0, Pipe Support Types and Components Rigid Supports, to provide detailed support design.

    Engineered Supports Application where support flexibility must be designed into the piping system by providing variable springs, constant supports and/or rigid hangers, or the support design is critical to the system.

    Design Engineering shall be responsible for the design of engineered pipe hangers and supports. Design criteria and guidelines are given in section 6.0 of this standard. Engineered supports shall be specified after a thorough pipe stress analysis has been performed, unless noted otherwise. See Mechanical Standard M-2-2, Piping Stress Analysis.

    NOTE

    Piping systems containing engineered supports shall be designed as an engineered system of supports. Therefore, the engineer and detailer shall refer to section 5.0, Pipe Support Types and Components Rigid Supports, of this standard, when rigid type supports are required as part of the engineered pipe support system.

    2.0 DEFINITIONS

    The following definitions are applicable to new generation, environmental, and retrofit projects.

    2.1 Piping System Category Indicates the piping systems criticalness of service as defined

    in Pipe Class Criteria found in appendix A of Piping Design Standard M-2-1. In general, there are the following three categories:

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES MECHANICAL PIPE HANGERS AND SUPPORTS

    5 of 18

    2.1.1 Category 1/Critical Systems - These systems include main steam, hot and cold reheat, boiler feed-water pump suction, and discharge. The failure of any of these systems will result in the loss of generation capability and/or substantially impact the safety of plant personnel.

    2.1.2 Category 2/Intermediate Systems - These systems include extraction steam, high pressure heater drains, or condensate systems. Failure of any of these systems has less impact on the loss of generation capability or personnel safety.

    2.1.3 Category 3/Non-critical Systems - All other systems such as floor drains, cold water

    systems, potable water, plant service water, vents, or circulating water. Failure of any of these systems has no impact on generation capability.

    2.2 Design Load - This is the pipe load used in the design of the pipe support. It is the higher

    of the load cases for the piping system.

    2.3 Operating Load - This is the pipe load that acts on the support when the system is in service. This load is the algebraic sum of weight load and thermal load. Operating load is equal to hot load for spring hangers.

    2.4 Hydrostatic Load - This is the pipe load acting on the support during hydrostatic testing of the piping system. Hydrostatic loads are often much higher than design loads for steam and gas piping systems.

    2.5 Sustained Load - This is the sum of the weight of the pipe, contents, and pipe support attachment components plus the pressure acting on the system.

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES MECHANICAL PIPE HANGERS AND SUPPORTS

    6 of 18

    2.6 Minimum Load - The support shall be designed for the minimum load if the design load is less than the minimum load. The table below (reprinted from MSS SP-58 Pipe Hangers and Supports Materials and Fitting Industry) suggests the minimum design loads based upon the pipe size. This minimum load should be used in designing supplemental steel.

    MINIMUM DESIGN LOADS

    (From MSS SP-58 Pipe Hangers and Supports Materials and Fitting Industry)

    Nominal Pipe Size (in) Load (lb) 3/8 150 150 150 1 150 1 150 1 150 2 150 2 150 3 200 3 210 4 250 5 360 6 480 8 760 10 1120 12 1480 14 1710 16 2130 18 2580 20 3060 24 3060

    2.7 Thermal Load - Stresses imposed on the piping system due to expansion or contraction

    (or both) of the components due to a wide range of temperatures. 3.0 CODES AND STANDARDS

    Pipe support design is governed by the codes and standards that apply to the piping system. The piping codes used in new generation, environmental, and retrofit projects have provisions for the design of pipe supports. The designer should be familiar with the support design portions of the applicable codes listed in section 7.0 References.

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES MECHANICAL PIPE HANGERS AND SUPPORTS

    7 of 18

    4.0 DESIGN CRITERIA AND GUIDELINES 4.1 Component Designation

    For the purpose of design standardization all support component designations shall be based on the Anvil International, Inc. Pipe Hangers Catalog numbering system.

    4.2 Loads Supports shall be designed for the most severe conditions of coincident pressure, weight, temperature, and any fluid dynamic events. In addition, piping exposed to wind load, snow, ice, earthquake, or other natural phenomena shall be designed for such loading.

    4.3 Pipe Stress

    Critical piping systems, Piping Category 1, 2, or otherwise designated due to piping loads, shall be stress analyzed in accordance with Mechanical Standard M-2-2, Piping Stress Analysis. The pipe support engineer and designer shall base pipe support selection and design on results from the pipe stress analysis.

    4.4 Welds Welding or bolting attachments to the building or pipe rack structural steel shall be done in accordance with the latest edition of the AISC Manual of Steel Construction Allowable Stress Design. Maximum allowable shear stress in welds shall be limited to 80 percent of the maximum allowable stress of the weaker of the base metals being joined. Maximum allowable tension and bending stresses in welds shall be limited to the maximum allowable stress of the weaker of the base metals being joined.

    4.5 Support Spacing Horizontal piping shall be supported such that excessive sag, bending, or shear stress is minimized. Special consideration will be given where components such as flanges and valves impose concentrated loads. Vertical piping shall be supported with riser clamps. See section 5.1.7 Riser Clamps for spacing of vertical restraints. Supports for piping 3 inches or larger shall be designed and detailed individually. Supports for piping 2 1/2 inches and smaller shall be designated as field-designed and located (except for Category 1 and 2 systems), unless noted otherwise. Field-designed pipe supports shall consider all critical movement, load, and operational conditions. Design criteria and guidelines for rigid-type pipe hangers given in section 5.0 Pipe Support Types and Components Rigid Supports shall be followed. Where stress analysis calculations are not performed, pipe support spacing for standard and heavier weight pipe shall be in accordance with table 121.5 of ASME B31.1 code. Suggested pipe support spacing chart is reprinted in table 4.5. This chart shall not be used where components, such as flanges and valves, impose concentrated loads.

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES MECHANICAL PIPE HANGERS AND SUPPORTS

    8 of 18

    Table 4.5 SUGGESTED PIPE SUPPORT SPACING

    Suggested Maximum Span (carbon steel pipe only)

    Nominal Pipe Size (NPS) Water Service (ft) Steam, Gas, or Air Service (ft)

    1 7 9 2 10 13 3 12 15 4 14 17 6 17 21 8 19 24 12 23 30 16 27 35 20 30 39 24 32 42

    NOTES:

    1. The above data is based on ANSI B31.1 Power Piping Code. 2. The maximum spacing for pipe supports, shown above, applies only for horizontal straight runs of standard

    weight and heavier pipe when the operating temperature does not exceed 750 F. 3. The above table does not apply where span calculations are made or where there are concentrated loads

    between supports such as flanges, valves, and specialties. 4. The spacing shown above is based on a maximum combined bending and shear stress of 2800 psi and

    insulated pipe filled with water or the equivalent weight of pipe or steam, gas or air service. The pitch of the line is such that sag of 0.1 inch between supports is permissible.

    4.6 The Pipe Support Contractor and Support Details

    Manufacturers Standardization Society specification MSS SP-77 Guidelines for Pipe Support Contractual Relationships shall be used as the basis for establishing responsibilities for pipe support details. Contractual relationships shall be arranged to track the following in order of governing precedence: 1. Project specific contract documents 2. This standard M-2-3 Pipe Hangers and Supports 3. MSS SP-77 Guidelines for Pipe Support Contractual Relationships

    Pipe support details shall be developed with information provided by Design Engineering drawings and stress analysis results, if applicable. Pipe support details shall be developed by an SCS-approved pipe support contractor. The contractor shall be responsible for pipe support details, development of the bill of materials, fabrication, and delivery of pipe support assemblies. As dictated by the project and where job requirements permit, Design Engineering may develop pipe support details, or typical details may be used in lieu of individual drawings. The following information is required by the pipe support contractor and provided by Design Engineering:

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES MECHANICAL PIPE HANGERS AND SUPPORTS

    9 of 18

    Location of pipe support assembly with respect to the piping system along with the support type and supplementary steel type, if required, shall be shown on the piping isometric and/or orthographic drawings. Support load required for the contractor to size supplementary steel. In some instances, support steel size may be shown in lieu of load. Detailed structural steel and concrete drawings. For spring hangers, hot and cold loads, hot and cold positions, and hydro load shall be noted. For constant supports, design load, calculated travel (up or down), and total travel shall be noted.

    The pipe support contractor shall provide the following: Complete pipe support assembly drawings including details of supplemental steel,

    when applicable. When loads are submitted in lieu of steel size, the contractor is responsible for sizing the appropriate steel. Consideration must be given to appropriate bearing surface as well as load capacity. Design, fabrication and erection of structural steel shall be in accordance with the AISC manual of steel construction, latest edition. Complete bill of materials. Weld sizes. Special field welding procedures shall be noted when required. Supply of pipe support assemblies.

    All documents provided by the pipe support contractor shall contain the plant, unit, line number, and pipe support callout matching the purchasers documents. The pipe support contractors design documents are subject to review and approval by Design Engineering prior to release for fabrication. Existing support steel shall be utilized, when possible. Complex supplemental steel arrangements should be avoided if possible.

    4.7 Pipe Support Callout

    Pipe supports shall be tagged on the piping isometric and/or orthographic drawings. Each pipe support shall have an identification number, Sx, where x identifies the bill of materials item number. Each pipe support shall have a pipe support detail callout which shall contain the support type (Appendix A), a unique identifier, and supplemental steel type (Appendix B). A short description shall be included in the bill of materials along with the calculated load, if applicable. The pipe support identifier shall be unique for a particular line number.

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES MECHANICAL PIPE HANGERS AND SUPPORTS

    10 of 18

    Both tags shall have a box surrounding the number. Example: S9

    GBS-5-01/1A

    S9 - bill of materials item number GBS-5 - pipe support type 01 - unique pipe support identifier 1A - supplemental steel type

    When specifying that existing structural steel will be used and supplemental steel will not be necessary, no designation will follow the pipe support unique identifier (for example GBS-5-01).

    4.8 Special Supports

    When necessary, project-specific supports shall be noted in the following manner: S10

    SP-02/1A

    S10 - bill of materials item number SP - support type (SP denotes special or project-specific) 02 - unique pipe support identifier 1A - supplemental steel type

    4.9 Support Placement Tolerance Support installation location shall be within 1-0 from that designated on the pipe support drawing, piping isometric, or orthographic. 5.0 PIPE SUPPORT TYPES AND COMPONENTS RIGID SUPPORTS 5.1 Rod Hangers and Components

    The rod hanger is the most common type of hanger in a piping system. The rod hanger is a rigid, one-way vertical restraint consisting of a rod attached to a pipe clamp at one end and to the building or pipe rack structure at the other end, usually via a beam attachment. Rod hangers should not swing more than 4 degrees from the vertical position. Where necessary, offset of pipe attachments and building/rack attachments shall be used to maintain the 4-degree angular swing and to maintain concentric loading of the hanger when the piping is at operating conditions.

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES MECHANICAL PIPE HANGERS AND SUPPORTS

    11 of 18

    5.1.1 Beam Attachments

    Welded beam attachments with a pin or bolt shall be used where possible. This type of attachment can accommodate a welded eye rod or weld-less eye nut and allows up to a 4-degree swing of the rod in the direction parallel to the pin. Mechanical beam attachments or beam clamps shall be used for ambient systems (temperature < 120F) or for temporary support. Their use is prohibited except for dry pipe fire protection sprinkler systems, draft system sensing lines, or other light duty piping systems.

    A welded beam lug and clevis shall be used when the beam flange is not wide enough to accommodate the welded beam attachment. The beam lug shall be used for pipe supports requiring double lugs.

    Load pins shall have cotters to prevent slippage. Load bolts shall have jamming nuts (double nut). All bolted joints shall have locking devices, such as jam nuts. Offsetting thread or tack-welding shall not be used, unless stated otherwise.

    For a welded beam attachment, the welding shall be performed on the straight sides of the attachment only. There shall not be any welding on beam attachment rounded sides or across the webs of beams. When attachment to concrete is required, embedded anchor bolts or inserts shall be utilized. Approved concrete fasteners shall be used in shear only where required.

    5.1.2 Hanger Rods

    Machine threaded rods or welded eye rods shall be used unless stated otherwise. Linked eye rods shall be used to accommodate large lateral and axial movements of pipe. Standard load rated hanger rods shall be used. Table 121.7.2(A) of B31.1 code provides load carrying capacities for threaded rods made of A-36, A-575, and A-576 hot-rolled carbon steel. To support hot and insulated piping, hanger rods shall be fitted with a forged or welded eye connected to the pipe clamps through a load pin or load bolt separate from those bolts attaching the clamp to the pipe. Hanger rods should not be subjected to bending or stresses other than tension. Where lateral or axial movement is anticipated, suitable linkages shall be provided to permit swinging. Hanger rods shall not be threaded directly to concrete fasteners. Attachment by conventional means to an intermediate plate or member held in place by at least two full-strength concrete fasteners is required.

    5.1.3 Turnbuckles

    Turnbuckles shall be used to provide an adjustable length connection between two rods. Orient the turnbuckle with the left-hand thread at the top and the right-hand thread at the bottom. This will shorten both rods when the turnbuckle is turned counterclockwise and lengthen both rods when the turnbuckle is turned clockwise.

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES MECHANICAL PIPE HANGERS AND SUPPORTS

    12 of 18

    For rod take-out calculations (specifying length of rods to be purchased), a 3-inch gap between rod tips within the turnbuckle shall be used for a standard 6-inch turnbuckle. The turnbuckle is typically located about 3 feet from the pipe for ease of adjustment. A right-hand threaded hex nut with lock nut shall be used for jamming the turnbuckle to prevent it from disengaging.

    5.1.4 Clamps

    Two-bolt pipe clamps shall be used to support cold pipelines with little or no insulation. Three-bolt clamps shall be used for all other systems. For high temperature piping systems (temperature > 750 F), alloy clamps shall be used. Otherwise, carbon steel clamps are adequate. Jamb nuts (or suitable locking devices) shall be specified for clamp bolts.

    5.1.5 Welds

    Beam attachments should be welded to building, pipe rack, or supplemental steel with fillet welds along two edges of the attachment. Unless pipe movement otherwise dictates, orient the attachment so that the axis of the pin or bolt is parallel to the axis of the beam. The weld should run along the beam flange. Welding shall be on the straight sides of the attachment, not on the rounded sides. Welds shall be designed to develop the full strength of the pipe support component being joined.

    5.1.6 Trapeze Hangers

    Trapeze hangers shall be used to avoid interferences, especially where a piping system is routed below another piping system. Pipe may be off center of the trapeze. Where piping is off-center, spring hanger spring loads must be re-calculated. Pipe must be attached to a trapeze by an anchoring device such as a U-bolt. When required, insulation protection devices shall be used with trapeze hangers when the pipe is insulated. Rods used in trapeze hanger assemblies shall be designed to carry a minimum of 75 percent of the calculated total operating load.

    5.1.7 Riser Clamps

    Riser clamps shall used to support vertical piping. Friction shall not be relied upon to hold the riser clamp in place. A minimum of three shear lugs shall be provided and welded to the pipe along the two vertical sides and the top with sufficient weld material to support the total pipe load. Shear lugs shall be manufactured of the same material as the pipe. Typically, a pipe support vendor has three types of riser clamps:

    Simple strap with four bolts. Heavy duty type. Welded, reinforced bars (to take torsion out of the clamp and increase the capacity).

    When designing supports with riser clamps, consideration shall be given to the load pin center-to-center dimensions. The center-to-center span should be kept as close to the pipe as possible to reduce the bending effect on the clamp.

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES MECHANICAL PIPE HANGERS AND SUPPORTS

    13 of 18

    Each rod of a riser support shall be sized for the full load of the support. This requirement does not apply to spring or constant supports where the rod size is determined by the spring housing itself. Where vertical restraints are required on piping systems (such as main steam, hot reheat, cold reheat, extraction to deaerator, and boiler feed pump suction piping), each support rod must be capable of supporting 60 percent of the total hydrostatic load of the riser and adjacent piping or 75 percent of the calculated operating load - whichever is greater. This requirement is necessary although other hangers may be designed to support the riser. Generally, the support spacing shall be limited to 1.5 times the recommended horizontal spans, and the vertical restraint must be located above the center of gravity of the riser. The vertical restraint shall be located in the upper third of the pipe. Alloy risers and pipe clamps shall use bolting material manufactured from ASTM A-193, B-7 studs, and A-194 grade 2H heavy hex nuts, unless required otherwise.

    5.1.8 Washer Plates

    When pairs of channels are used as supplemental steel, a washer plate shall be welded to both the top and bottom flanges of the channels to prevent rotation of the channel. The washer plate shall be selected to match the rod size. The hole in the washer plate should be 1/8 inch larger in diameter than the rod, unless required otherwise. The hanger rod extends through the channels and shall be attached using two hex nuts.

    5.2 Shoe and Stanchion Supports

    Shoe and stanchion supports are rigid, one-way vertical restraints. Piping without insulation shall be supported from below by resting it on a steel member or by welding a pipe stanchion and a plate. Piping with insulation shall be supported from below by welding a shoe, a pipe covering protection saddle, or a pipe stanchion and a plate. Welded attachments to pipe shall be designed for the vertical force to be supported at the given support location. A pipe shoe, pipe covering protection saddle, or pipe stanchion and a plate shall be supported on a sliding surface of a steel member or a steel plate anchored on a concrete member.

    5.3 Guides

    Guides are two-way piping system restraints. In horizontal piping, the pipe shall be supported vertically and restrained in lateral direction. In vertical risers, the pipe shall be restrained in the lateral direction only. Two common types of guides are the box type and sway strut type. The box-type guide, built up by using structural steel members, shall be used for low-temperature piping systems, unless required otherwise. Box-type guides should not be used for high-temperature systems because of pipe contact with structural members. Such contact results in friction caused by axial movement of the pipe and heating of the structural member. High-temperature systems also have significant insulation which requires additional components such as insulation shoes or lugs.

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES MECHANICAL PIPE HANGERS AND SUPPORTS

    14 of 18

    Two perpendicular sway struts can provide the same movement control as a box guide. This type of arrangement has advantages over the box type: Simpler to design and install. Flexible in orientation. Require less space. Provide more pipe axial movement without friction load. Allow field adjustment.

    Sway strut guides require standard support components that need considerable lead time from order to delivery. The use of sway struts may not be economical for supporting light loads or small-bore pipe, especially cold pipe. The following cautions apply to the design of guides using sway strut assemblies: When a sway strut is used in the vertical direction, the piping shall be supported from

    above rather than from below. The pin-to-pin dimension for allowable load shall be verified. The longer a strut, the lower its buckling load. The angle between the two struts should be no less than 45 degrees and no more than 135 degrees. Where this condition cannot be satisfied, the piping model and stress analysis shall be modified accordingly.

    5.4 Limit Stops

    Limit stops are two-way restraints in a piping system. In horizontal piping, the pipe shall be supported vertically and restrained in order to control axial movements. Limit stops are most often found in high temperature and insulated piping systems. Limit stops shall be built by welding two plates or shoes axially to a pipe, 180 degrees apart. Axial pipe movement is restrained by attaching a steel member across the plate or the shoe. The limit stop plate or shoe and steel members shall be designed to resist the limit stop restraint loads determined by a stress analysis load report.

    5.5 Anchors

    Anchors shall be designed to restrain the movement of pipe in all directions. Anchors are built by welding plates, shoes, or stanchions around pipe. Such an anchor assembly shall be welded or bolted to the building or pipe rack structure. The weld and the size of the plates, shoes, or stanchions welded to the pipe shall be designed for the anchor design loads determined by a stress analysis load report. As necessary, anchor, guide, and limit stop restraint loads shall be reviewed by the civil or structural design group before issuing the final design.

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES MECHANICAL PIPE HANGERS AND SUPPORTS

    15 of 18

    5.6 Welded Pipe Attachments

    Welded pipe attachments include shear lugs, stanchions, insulation lugs, and other assemblies which transfer the load from the pipe to the support. Welded attachment lugs impose local stress on the pipe wall which must be considered. The design of shear lugs on a pipe risers vertical restraints shall be such that only half of the number of lugs shall be required to carry the total load of the support. For example, if the total load is 4,000 lb and the support has 4 lugs, each lug shall be designed to carry a load of 2,000 lb. This provision anticipates that fabrication tolerance, erection, pipe movements, or other factors prevent the contact of all the lugs onto the clamp or supporting structure.

    For pipe larger than 6 inches NPS, at least four lugs shall be used for axial support in each direction. Lugs shall be welded on two sides and on the top. Lug material shall be the same as the piping material. Stanchions may be welded to the pipe. Welds between the stanchion and the pipe should be partial penetration welds with a fillet cap. The weld shall be treated as a piping weld.

    6.0 PIPE SUPPORT TYPES AND COMPONENTS ENGINEERED SUPPORTS

    6.1 Variable Spring Hangers

    Spring hangers, or variable supports, allow pipe to move vertically while still providing support. This support varies according to the amount of pipe movement.

    Spring hangers shall be supported in such a manner that the rod will remain concentric with the spring at all times and will not be subject to bending. Rollers or similar approved supports shall be provided in the event the amount of hanger rod angular swing exceeds 4 degrees. Spring hangers or variable supports consist of pre-compressed enclosed springs. A load plate positioned on top of the spring is attached to the pipe so the pipe weight compresses the spring. The spring housing transfers the support load to the building or pipe rack structure. There are seven types of variable spring hangers to choose from depending on the way the spring is attached to the building/pipe rack structure or pipe. Refer to Anvil International Pipe Support Catalog for additional descriptions and pictures of each hanger type. Type A spring hangers are used where sufficient headroom is available. The spring cans should be furnished with threaded connections and rod stops in the top plate to provide a simple attachment for the upper rod connection. Adjustment and spring loading are accomplished by turning the load coupling or turnbuckle to achieve the desired spring load or pipe elevation.

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES MECHANICAL PIPE HANGERS AND SUPPORTS

    16 of 18

    The supports for type A spring hangers should be designed with the spring can positioned approximately 3 to 5 feet from the pipe to provide access for inspection. A turnbuckle shall be installed between the pipe clamp and the spring can for load adjustment, unless noted otherwise. Type B and type C spring hangers are used where headroom is limited, and the spring cans have to be attached directly to the building or pipe rack structure. Type B spring hangers have a single lug welded to the top plate of the housing. Type C spring hangers are similar to type B hangers, but instead of a single lug, type C spring hangers have double lugs welded to the top plate of the housing. Unless the beam attachment requires otherwise, type B spring hangers shall be used. Type D and type E spring hangers are used to position the spring can above the support structure (usually a pair of channels). Type D spring hangers are adjusted using the load nut on top of the spring housing. Instead of a top-mounted load nut, type E spring hangers are usually supplied with a turnbuckle and adjusted from below. Type F spring hangers are designed to support piping from below. The disadvantage of this type is its unsatisfactory performance when subjected to significant lateral pipe movement. Pipe movement may cause the load plate to tilt, or the pipe may move off the load plate. Hanger manufacturers recommend rollers for pipe with high axial movements. Type G spring hangers are made up of two spring units welded to the ends of a single angle or pair of channels in a trapeze configuration. This type of support is used where headroom is limited or where obstruction prohibits the use of a single spring hanger. When specifying this type of spring hanger, it is assumed that the pipe is centered between the springs, each spring carrying only half the total pipe load. Most variable supports shall have no more than 25 percent variability. Variable supports in critical systems such as main steam, hot reheat, or cold reheat shall have less than 10 percent variability. Constant supports should be used if the above variability cannot be met. Where designing spring pipe supports for piping systems subject to vibration, the spring unit shall be attached directly to the building or pipe rack structure. If the spring can is positioned in the middle of a long rod, piping vibration will cause the spring can to eventually bend the rod. The disadvantage of attaching the spring can to the building/pipe rack structure is the difficulty of spring adjustment or inspection. The spring can should be positioned as close as possible to the pipe and never at the middle of a long rod. The weight of the spring unit must be added to the specified load in setting the hot and cold loads of the spring. The weight of the components, especially the clamp weight, acting on the spring may be significant. Because the pipe load is acting on the housing of the spring, and the load plate is attached to the building or pipe rack structure, the weight of all components shall be taken into account if the hot or cold load settings are near the bottom of the spring hangers operating range.

    Variable springs shall be equipped with a complete travel stop for steam and liquid fluid piping systems. Travel stops for hot air or flue gas systems shall be equipped with cold

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES MECHANICAL PIPE HANGERS AND SUPPORTS

    17 of 18

    travel stops. Load scales shall be equipped with permanently attached cold and hot buttons. Stops should be removed after hydro test only.

    6.2 Constant Supports A constant support is a spring hanger with a mechanism located inside the spring housing. The mechanism allows a balance of spring force and the pipe weight in such a way that the supporting load remains constant throughout the range of pipe travel. In a critical piping system such as main steam, hot reheat, or cold reheat, the thermal expansion of the piping system may reach 6 to 12 inches, but the allowable range is 6 percent. Constant supports shall be used when the load variability of a spring hanger is not acceptable. Constant supports can generally be divided into two categories: vertical and horizontal. Constant support designs vary from one manufacturer to another. Hanger catalogs should be used in choosing constant supports. Constant pipe supports shall be designed for a 2-inch difference between the calculated thermal movement and the total travel for pipe movements less than 4 inches. When predicted pipe movements will exceed 4 inches, the support is designed for a 50 percent difference between actual and total travel. For example, if the pipe moves 6 inches, the calculated travel shall be 6 inches, and the total specified travel shall be 9 inches. The constant support should have at least 9 inch total travel. In designing a constant support hanger, all component weights acting on the support spring must be taken into account. The load adjustment of a constant support is much more limited than that of a spring hanger. As with type G spring hangers, the weight of type G constant supports must be added to the total load acting on the support.

    Constant pipe supports shall be equipped with a permanent travel stop with load

    indication.

    6.3 Design of Supplemental Steel

    Building steel and pipe rack steel shall be used for support where practical. Support spans shall be governed by paragraph 121.5 of ANSI/ASME B31.1 Power Piping Code with due consideration of concentrated loading caused by valves, flanges, and other fittings. See table 4.5 for suggested pipe support spacing. Supplemental steel shall be designed and provided when building or pipe rack steel necessary to conform to support requirements cannot be located. Supplemental steel shall be designed for the larger of the pipe design loads and the hydrostatic test load. Supplemental steel shall be designed in accordance with the requirements of the AISC Manual of Steel Construction.

    Support structures shall be designed with proper stiffness to prevent excessive support deflection that could invalidate the piping stress analysis. For critical systems, a rigid

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES MECHANICAL PIPE HANGERS AND SUPPORTS

    18 of 18

    support should not deflect more than 1/16 inch. For non-critical systems, a deflection of 1/8 inch is allowed. Where it is necessary to frame structural members between existing steel or concrete members, such supplemental steel shall be designed in accordance with American Institute of Steel Construction Specifications, the Uniform Building Code, or similar recognized structural design standards. Concrete connections shall be made only when addition of supplemental steel is impractical. Base plate shall be anchored to the concrete, except in cases of pure tension loading. Expansion bolts shall be wedge-type, Hilti, Kwik bolts, or equal. Use maximum embedment length recommended by manufacturer. Concrete beam attachments shall be bolted through or welded to cast-in place insert plates. Pipe supports shall not be attached to concrete block walls.

    7.0 REFERENCES

    American Institute of Steel Construction (AISC). AISC Manual of Steel Construction American Society of Mechanical Engineers.

    ASME B31.1 Power Piping ASME B31.3 Process Piping ASME Boiler and Pressure Vessel Code

    American Society of Testing and Materials American Welding Society. AWS D1.1 Structural Welding Code Steel Anvil International, Inc. Pipe Hangers Catalog Manufacturers Standardization Society of the Valve and Fitting Industry.

    MSS SP-58 Pipe Hangers and Supports Materials and Fitting Industry MSS SP-69 Pipe Hangers and Supports Selection and Application MSS SP-77 Guidelines for Pipe Support Contractual Arrangements MSS SP-89 Pipe Hangers and Supports Fabrication and Installation Practices MSS SP-127 Bracing for Piping Systems Seismic-Wind-Dynamic Design, Selection, Application

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    1 OF 68

    Appendix A: Standard Support Details

    Index

    1.0 GENERAL NOTES 2.0 RIGID BASE SUPPORT

    2.1 RBS-1: Pipe On Steel 2.2 RBS-2: Adjustable Pipe Stanchion Support 2.3 RBS-3: Non-Adjustable Pipe Stanchion Support 2.4 RBS-4: Pipe Clamp and Stanchion Support 2.5 RBS-5: Pipe Covering Protection Saddle 2.6 RBS-6: Pipe Shoe, 8 and Smaller 2.7 RBS-7: Pipe Shoe, 10 and Larger 2.8 RBS-8: Pipe Slide Bearing 2.9 RBS-9: Dummy Leg Supports 2.10 RBS-10: U-Bolt Support 2.11 RBS-11: Insulation Shield Support 2.12 RBS-12: Insulation Shield U-Bolt Support 2.13 RBS-13: Riser Clamp Support 2.14 RBS-14: Riser Trunion Support 2.15 RBS-15: Thin Wall Pipe Rigid Support, 2-12 2.16 RBS-16: Thin Wall Pipe Rigid Support, 14-48

    3.0 RIGID HANGER SUPPORT

    3.1 RHS-1: Pipe Clevis Rod Hanger 3.2 RHS-2: Double Bolt Pipe Clamp Rod Hanger 3.3 RHS-2A: Alloy Double Bolt Pipe Clamp Rod Hanger 3.4 RHS-3: Riser Clamp Rod Hanger 3.5 RHS-4: Trapeze Rod Hanger 3.6 RHS-5: Thin Wall Pipe Rod Hanger

    4.0 GUIDE BASE SUPPORT

    4.1 GBS-1: Guide U-Bolt 4.2 GBS-2: Guide Adjustable Pipe Stanchion and U-Bolt 4.3 GBS-3: Guide Pipe Covering Protection Saddle and U-Bolt 4.4 GBS-4: Guide Stanchion and Plate 4.5 GBS-5: Guide Pipe Shoe, 8 and Smaller 4.6 GBS-6: Guide Pipe Shoe, 10 and Larger 4.7 GBS-7: Guide Pipe Covering Protection Saddle 4.8 GBS-8: Riser Guide Pipe Saddle and U-Bolt

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    2 OF 68

    4.9 GBS-9: Riser Guide With Stanchion 4.10 GBS-10: U-Bolt Supports For Light Loads 4.11 GBS-11: Pipe Slide Bearing Guide 4.12 GBS-12: Insulation Shield Support Guide 4.13 GBS-13: Thin Wall Pipe Guide Support, 2-12 4.14 GBS-14: Thin Wall Pipe Guide Support, 14-48

    5.0 LIMIT BASE SUPPORT

    5.1 LBS-1: Limit Stop Saddle and Tees 5.2 LBS-2: Limit Stop Pipe Shoe, 8 and Smaller 5.3 LBS-3: Pipe Shoe, 10 and Larger

    6.0 ANCHORED BASE SUPPORT

    6.1 ABS-1: Anchor Horizontal Pipe (Concrete) 6.2 ABS-2: Anchor Horizontal Pipe (Steel) 6.3 ABS-3: Anchor Pipe Riser 6.4 ABS-4: Anchor Pipe Shoe, 8 and Smaller 6.5 ABS-5: Anchor Pipe Shoe, 10 and Larger 6.6 ABS-6: Non-Adjustable Pipe Stanchion Anchor 6.7 ABS-7: Thin Wall Pipe Anchor Support, 2-12 6.8 ABS-8: Thin Wall Pipe Anchor Support, 14-48 6.9 ABS-9: Pipe Anchor Support, 1-24

    7.0 SPRING HANGER SUPPORT

    7.1 SHS-1: Variable Spring Type B Spring 7.2 SHS-2: Variable Spring Type C Spring 7.3 SHS-3: Variable Spring Type D and Type E Spring 7.4 SHS-4: Variable Spring Type F Spring 7.5 SHS-5: Variable Spring Type G Spring 7.6 SHS-6: Variable Spring Trapeze 7.7 SHS-7: Variable Spring On Riser

    8.0 CONSTANT HANGER SUPPORT

    8.1 CHS-1: Constant Spring Type B Support 8.2 CHS-2: Constant Spring Type C Support 8.3 CHS-3: Constant Spring Type D Support 8.4 CHS-4: Constant Spring Type E Support 8.5 CHS-5: Constant Spring Type G Support

    9.0 DETAILS

    9.1 Detail-1: Base Plate Detail Pipe Stanchion

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    3 OF 68

    9.2 Detail-2: Anchored Base Plate Detail Pipe Stanchion 9.3 Detail-3: Upper Rod Hanger Assembly 9.4 Detail-4: Shoe Table and Notes

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    4 OF 68

    1.0 General Notes

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    5 OF 68

    2.0 Rigid Base Support

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    6 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    7 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    8 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    9 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    10 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    11 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    12 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    13 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    14 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    15 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    16 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    17 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    18 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    19 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    20 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    21 OF 68

    3.0 Rigid Hanger Support

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    22 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    23 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    24 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    25 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    26 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    27 OF 68

    4.0 Guide Base Support

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    28 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    29 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    30 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    31 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    32 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    33 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    PLAN VIEW

    34 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    PLAN VIEW

    35 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    36 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    37 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    38 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    39 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    40 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    41 OF 68

    5.0 Limit Base Support

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    42 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    43 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    44 OF 68

    6.0 Anchored Base Support

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    45 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    46 OF 68

    ELEVATION

    PLAN VIEW

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    47 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    48 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    49 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    50 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    51 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    52 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    53 OF 68

    7.0 Spring Hanger Support

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    54 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    55 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    56 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    57 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    58 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    59 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    60 OF 68

    8.0 Constant Hanger Support

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    61 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    62 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    63 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    64 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    65 OF 68

    9.0 Details

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    66 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    67 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX A MECHANICAL PIPE HANGERS AND SUPPORTS

    68 OF 68

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    1 OF 58

    Appendix B: Supplemental Steel

    Index

    1.0 DESIGN RULES FOR SUPPLEMENTAL STEEL

    2.0 BEAM TO BEAM

    2.1 1A: Span Between Beams 2.2 1B: Span Under Beam 2.3 1C: Span Underside Beams With Overhang 2.4 1D: Span Over the Beams

    3.0 BETWEEN COLUMNS

    3.1 2A: Steel to Steel 3.2 2B: Concrete to Steel

    4.0 COLUMN TO COLUMN

    4.1 3A: Side of Column/Under Beam 4.2 3B: Side of Column/Above Beam 4.3 3C: Side of Column/Under Beam with Extension

    5.0 FLOOR BRACED MEMBER

    5.1 4A: Floor Braced Tier

    6.0 EXTENDED MEMBER

    6.1 5A: Horizontal Cantilever 6.2 5B: Vertical Cantilever 6.3 5C: From Side of Beam 6.4 5D: Cantilever From Underside of Beam 6.5 5E: Vertical Cantilever Angle 6.6 5F: Straddle Underside of One Beam 6.7 5G: From Side of Column

    7.0 CANTILEVER

    7.1 6A: Cantilever Underside Unequal Beams 7.2 6B: Cantilever Underside Equal Beams 7.3 6C: Modified Structural Trapeze

    8.0 KNEE BRACES

    8.1 7A: Knee Brace From Column 8.2 7B: Knee Brace Tier From Column 8.3 7C: Cantilever From Column 8.4 7D: Cantilever From Concrete Wall 8.5 7E: Bolted Cantilever From Column 8.6 7F: Cantilever Angle Frame From Vessel

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    2 OF 58

    8.7 7G: Riser Support Frame From Vessel 8.8 7H: Riser Guide Frame From Vessel 8.9 7J: Sway Brace For Riser 8.10 7K: Riser Guide Frame Off Beam 8.11 7L: Riser Guide Frame Off Column

    9.0 TRAPEZES

    9.1 8A: Single Tier Structural Trapeze 9.2 8B: Double Tier Structural Trapeze 9.3 8C: Triple Tier Structural Trapeze 9.4 8D: Structural Trapeze Equal Legs 9.5 8E: Structural Trapeze Unequal Legs 9.6 8F: Under Beam-Angle Frame 9.7 8G: Trapeze With Extension Under Beam 9.8 8H: Straddle Underside Beam w/Trapeze 9.9 8J: Lateral Strut

    10.0 TEE POLES

    10.1 9A: Structural Tee Pole 10.2 9B: Tee Pole 4 Diameter Pipe 10.3 9C: Tee Pole 6 Diameter Pipe 10.4 9D: Offset Tee Pole 10.5 9E: Pipe Stand 10.6 9F: Angle Pipe Stand

    11.0 MISC. UTILITY BENTS

    11.1 10A: Single Tier Support From Floor

    12.0 PLATE MOUNTED ON CONCRETE

    12.1 11A: Plate Mounted on Concrete 12.2 11B: FRP Vessel Lug

    13.0 U-DRAIN SUPPORTS

    13.1 12A: U-Drain Support

    13.2 12B: U-Drain Support (FRP & HDPE Pipe)

    14.0 SHIM STEEL

    14.1 13A: Shim Steel

    15.0 SUPPORT FOUNDATIONS

    15.1 14A: Pipe Stanchion Foundation 15.2 14B: Pipe Support Pier 15.3 14C: Pipe Stanchion on Concrete Slab

    16.0 PIPE STAND

    16.1 15A: Pipe Stand 4 and Smaller Pipe

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    3 OF 58

    17.0 ACCEPTABLE CONNECTION DETAILS

    17.1 Connection Details 1 of 2 17.2 Connection Details 2 of 2

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    4 OF 58

    1.0 Design Rules for Supplemental Steel

    1. The pipe support contractor can usually use existing steel or provide relatively light steel members for the piping supports. SCS Engineering need not be involved unless the loads are greater than 3000 lb or introduce a moment greater than 1000 ft-lb into the structure. When supporting from bar joist, the pipe support contractor shall coordinate with SCS Engineering any loads which exceed 500 lb. These loads shall be applied at panel points only. Pipes shall not be supported from building girts.

    2. When loads exceed 3000 lb or 1000 ft-lb, coordination with the SCS Engineering Civil

    Department is necessary. The SCS Engineering Civil Department will analyze the building frame, pipe bridge, or support structure for its ability to support the loads. If the investigation requires that the support structure be modified or reinforced to accommodate the piping loads, the modifications will be shown on the structural drawings. The SCS Engineering Civil Department will also show supplemental steel for piping supports meeting the above load criteria where structural drawings have been prepared for buildings, pipe bridges, and other structures.

    3. Pipe bridges, T-poles requiring foundations or exceeding the limits of 9A, 9B, or 9C, and

    sleeper-type supports will be designed by the structural department and shown on structural drawings.

    4. As the piping analysis problems are completed, data will be transmitted in writing to the pipe

    support contractor. This data will consist of isometrics of the piping with locations, support supplemental steel configurations, and loads. The pipe support contractor and SCS Engineering should hold a periodic review be to evaluate the supplemental steel added for piping supports.

    5. Standard structural connection details are shown and may be used at the contractors option.

    Structural connections should be chosen to minimize fit-up and field welding.

    6. No supplemental steel member shall be added to roofing trusses or light weight Z purlins without consulting SCS Engineering.

    7. Whenever welds are made to galvanized steel, the area must be cleaned and passivated after

    welding. Cold galvanized spray paint (Galvicon or equal) shall be applied to the area. 8. Stop plates (1/4 in thick plate minimum) must be added to the end of steel members where

    the pipe rests on top of a steel section with no other lateral restraint.

    9. The stop plate shall be eliminated when the pipe support on the supplemental steel is an anchor or a guide.

    10. SCS Engineering and the pipe support contractor must agree to any deviation to items 1

    through 9 prior to detailed engineering.

    11. The supplemental support steel shall have a protective coating consistent with the structural steel to which it connects. Surfaces to be painted shall be cleared and coated in accordance with Technical Specification Sections 09910 (SHOP PAINTING) and 09912 (FIELD

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    5 OF 58

    PAINTING). Surfaces to be galvanized shall be cleaned and coated in accordance with Section 09915 (HOT DIP GALVANIZING). Field repair of damaged zinc coating shall be in accordance with ASTM A730, Section 4.2.1 and Annex A1.

    12. All welds on supplemental steel shall be a minimum of 3/16 in unless noted otherwise.

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    6 OF 58

    2.0 Beam to Beam

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    7 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    8 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    9 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    10 OF 58

    3.0 Between Columns

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    11 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    12 OF 58

    4.0 Column to Column

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    13 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    14 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    15 OF 58

    5.0 Floor Braced Member

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    16 OF 58

    6.0 Extended Member

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    17 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    7.0 Cantilever

    18 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    19 OF 58

    SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    19 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    20 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    21 OF 58

    8.0 Knee Braces

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    22 OF 58

    SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    22 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    23 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    24 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    25 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    26 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    27 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    28 OF 58

    SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    28 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    29 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    30 OF 58

    SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    30 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    31 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    32 OF 58

    9.0 Knee Braces

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    33 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    34 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    35 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    36 OF 58

    SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    36 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    37 OF 58

    SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    37 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    38 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    39 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    40 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    10.0 Tee Poles

    41 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    42 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    43 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    44 OF 58

    SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    44 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    45 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    46 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    47 OF 58

    11.0 Misc. Utility Bents

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    48 OF 58

    12.0 Plate Mounted on Concrete

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    49 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL 13.0 U-Drain Supports

    50 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    51 OF 58

    PLAN

    ELEVATION ELEVATION

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    52 OF 58

    14.0 Shim Steel

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    53 OF 58

    15.0 Support Foundations

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    54 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    55 OF 58

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    56 OF 58

    16.0 Pipe Stand

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    57 OF 58

    17.0 Acceptable Connection Details

    (W/ WELDED OR BOLTED CLIP ANGLE)

    (W/ WELDED OR BOLTED CLIP ANGLE & BEAM COPED)

    (W/ WELDED OR BOLTED CLIP ANGLE)(W/ WELDED BASE PLATE)(W/ BOLTED GUSSET PLATE)

    (W/ BOLTED CLIP ANGLE)(W/ WELDED CLIP ANGLE)

  • SOUTHERN COMPANY SERVICES M-2-3 ENGINEERING STANDARDS AND GUIDELINES APPENDIX B MECHANICAL SUPPLEMENTAL STEEL

    58 OF 58

    (WELDED OR BOLTED)(WELDED OR BOLTED)(W/ CLIP ANGLES)

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX CMECHANICAL FRP PIPE SUPPORTS

    2 OF 30

    Appendix CFRP Standard Support Details

    Index

    1.0 Introduction

    1.1. Purpose1.2. Scope

    2.0 Codes and Standards

    3.0 Design Criteria and Guidelines

    3.1. General Design Consideration3.2. FRP Pipe Supports3.3. Supplementary Steel3.4. FRP Pipe Support Spacing

    4.0 General Notes for FRP Pipe Supports

    5.0 Rigid Supports

    5.1. FSR-1: Fiberglass Pipe Cradle Support, 1-45.2. FSR-2: Fiberglass Pipe Cradle Support, 6-425.3. FSR-3: Fiberglass Insulated Pipe Support, 2-425.4. FSR-4: Valve/Pipe Flange Support, 2-425.5. FSR-5: Light Duty Fiberglass Pipe Hanger, 2-205.6. FSR-6: Fiberglass Pipe Component Hanger, 2-425.7. FSR-7: Fiberglass Pressure Pipe Clamp Hanger, 2-425.8. FSR-8: Fiberglass Pipe Riser Hanger, 2-425.9. FSR-9: Component Riser Support, 2-425.10.FSR-10: Fiberglass Pipe Riser Support, 2-425.11.Detail-FSR-11: Stanchion Flange Support, 2-42

    6.0 Guide Supports

    6.1. FSG-1: Fiberglass Pipe Cradle Guide, 1-46.2. FSG-2: Fiberglass Pipe Support Guide, 6-426.3. FSG-3: Fiberglass Insulated Pipe Support Guide, 2-426.4. FSG-4: Valve/Pipe Flange Guide, 2-426.5. FSG-5: Fiberglass Pipe Riser Guide, 2-426.6. FSG-6: Fiberglass Pipe Braced Hanger Guide

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX CMECHANICAL FRP PIPE SUPPORTS

    3 OF 30

    7.0 Anchored Supports

    7.1. FSA-1: Fiberglass Pipe Anchor, 2-47.2. FSA-2: Fiberglass Pipe Anchor, 6-427.3. FSA-3: Fiberglass Insulated Pipe Anchor, 2-427.4. FSA-4: Valve/Pipe Flange Anchor, 2-427.5. Detail-FS1: Fiberglass Pipe Shear Collar

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX CMECHANICAL FRP PIPE SUPPORTS

    4 OF 30

    FRP PIPE SUPPORTS

    1.0 Introduction

    1.1 Purpose

    The purpose of this chapter is intended to serve as a guide to the proper use of pipe hangers and supports of fiber glass piping system. The document is not intended to supersede project specific design criteria but to reflect Mechanical Design Standards.

    1.2 Scope

    This standard shall apply to pipe supports for FRP piping systems ranging in size up to 42 inches, unless noted otherwise.

    Design of FRP pipe supports shall be the responsibility of Design Engineering. Design criteria and guidelines are given in Section 3.0 of this Appendix C. FRP pipe supports shall be specified after a thorough support evaluation or pipe stress analysis has been performed, unless noted otherwise.

    NOTEFRP piping systems containing FRP supports is typically designed as an

    engineered system of supports. Design of FRP engineered supports will include standard FRP pipe supports represented in the following sections.

    2.0 Codes and Standards

    FRP pipe support design is governed by the codes and standards that apply to the FRP piping system. The designer should be familiar with the support design portions of the applicable codes. The following standards are applicable to FRP piping systems and FRP pipe support systems.

    American Society of Mechanical Engineers.

    ASME Standard B31.3 Process Piping(Addresses primarily metallic piping, but it is expanded to cover Non-metallic piping including thermoplastic and thermo set piping system.)

    NBS Voluntary Product Standard PS 15-69.

    3.0 Design Criteria and Guidelines

    3.1 General Design Consideration

    The principles of design and analysis for FRP pipe differ considerably from the principles of design for metallic pipe. The analysis of steel pipe normally begins with maximum flexibility and the final support-guide-anchor design ends when allowable stresses and loads are achieved.

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX CMECHANICAL FRP PIPE SUPPORTS

    5 OF 30

    When analyzing FRP pipe, the analysis normally begins with a semi rigid system and the final support-guide-anchor configuration is established when the minimum stress condition is reached, based on the available structural support structures. Long straight runs can use a fully anchored approach for smaller diameter pipe (

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX CMECHANICAL FRP PIPE SUPPORTS

    6 OF 30

    3.3 Supplementary steel

    Building steel and pipe rack steel shall be used for support where practical.

    Supplementary steel shall be designed and provided where building steel or pipe rack steel is not available. Refer to Appendix B of this Standard for supplemental steel requirements.

    Supplementary steel shall be designed for the larger of the pipe design loads or the hydrostatic test load.

    Supplementary steel shall be designed in accordance with the requirements of the AISC Manual of Steel Construction.

    3.4 FRP Pipe Support Spacing

    Horizontal FRP piping shall be supported to prevent excessive sag, bending and shear stresses in the piping. Special design consideration shall be given where components such as flanges and valves impose concentrated loads.

    Vertical FRP pipe shall be supported to prevent the pipe from being overstressed due to the combination of all loading effects.

    Where stress analysis calculations are not made, FRP pipe manufacturer recommended maximum spacing requirements, reduced by 20%, shall be used.

    The following table of recommended FRP pipe support spacing shall be used for FRP pipes manufactured by Reinforced Plastic Systems Inc. only. This table is based on the criteria of Strength Ratio (SR) in structure greater than 1.6; and deflection less than 0.50 inch.

    TABLERecommended FRP Pipe Support Spacing

    Support spacing (ft.) @ 150 deg. F0For RPS P150 & A150 piping

    Nominal Pipe Diameter

    Single SpanSG=1.0

    Single SpanSG=1.3

    Continuous SpanSG=1.0

    Continuous SpanSG=1.3

    1 7.0 7.0 9.0 9.01-1/2 7.3 7.1 9.3 8.7

    2 8.0 7.5 9.8 9.23 8.4 7.7 10.3 9.54 8.7 8.0 10.7 9.86 10.9 10.0 13.3 12.28 10.9 10.0 13.1 12.0

    10 13.0 11.6 15.6 13.912 13.7 13.0 16.4 15.6

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX CMECHANICAL FRP PIPE SUPPORTS

    7 OF 30

    14 13.7 13.0 16.4 15.616 15.2 14.0 18.2 16.818 16.7 15.0 20.0 18.020 17.4 15.5 20.9 18.624 19.1 17.0 22.9 20.430 20.5 18.3 24.6 22.036 22.1 19.7 26.5 23.6

    CAUTION NOTE: Above values shall not be used for spans having concentrated loads, such as valves,branch connections, etc., where excessive vibration or pulsation is expected. Support spans, near or around a bend, shall be reduced by 1/3.

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX CMECHANICAL FRP PIPE SUPPORTS

    8 OF 30

    4.0 General Notes for FRP Pipe Supports

    1. Hangers shall be fabricated from 3/16, 1/4, 3/8, or 1/2 thick plate per ASTM A36, unless noted.

    2. All hanger hardware shall be galvanized unless otherwise specified. Where galvanizing is damaged by welding and/or by drilling, one coat of a non-toxic, zinc-rich compound (such as DRYGALV by American Solder and Flux Company or approved equivalent) at 5.0 mils dry film thickness shall be applied. Support assembly shall not be installed until repair coating is cured.

    3. Supports shall be designed to fit the O.D. of the pipe and must be located to clear all pipe wraps at fittings and shop or field joints.

    4. FSG-1 guides shall have special u-bolt clearances as indicated in the detail. Under no circumstances shall FRP pipe be clamped tightly by u-bolt or supported without a cradle.

    5. All cradle or clamp type supports that contact the O.D. of the pipe shall include an elastomeric liner bonded to the cradle.

    6. Flanged component supports, such as FSR-4, shall be used to support components such as valves. The length of flange bolts must be increased approximately 1/2. All thread rodsshall be used in lieu of bolts for ease of installation, unless stated otherwise.

    7. Component supports 12 diameter and larger shall be scalloped to provide clearance for the flange hub reinforcement specified in National Bureau of Standards Voluntary Product Standard PS-15-69.

    8. Support details call-out Jove # FS-XX refers to support model number published by JTI Manufacturing, Inc., Birmingham, AL, and is for reference only. FRP supports by Britt Engineering of Birmingham, AL and Maverick Applied Science of Palmetto, FL are also acceptable; any others must be approved in writing by Southern Company Mechanical Department.

    9. Rod hanger component designations for support details FSR-5, FSR-6, FSR-7, FSR-8 and FSG-6 shall be based on the Anvil, formerly Grinnell, numbering system.

    10. FRP pipe supports with an S suffix (ex. FSR-2S, FSG-2S, etc.) are non-standard supports. If dimensions are different than shown in standard detail, dimensions shall be specified with non-standard call-out (etc. FSR-2S, L=15).

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX CMECHANICAL FRP PIPE SUPPORTS

    9 OF 30

    5.0 Rigid Supports

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX CMECHANICAL FRP PIPE SUPPORTS

    10 OF 30

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX CMECHANICAL FRP PIPE SUPPORTS

    11 OF 30

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX CMECHANICAL FRP PIPE SUPPORTS

    12 OF 30

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX CMECHANICAL FRP PIPE SUPPORTS

    13 OF 30

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX CMECHANICAL FRP PIPE SUPPORTS

    14 OF 30

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX CMECHANICAL FRP PIPE SUPPORTS

    15 OF 30

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX CMECHANICAL FRP PIPE SUPPORTS

    16 OF 30

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX CMECHANICAL FRP PIPE SUPPORTS

    17 OF 30

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX CMECHANICAL FRP PIPE SUPPORTS

    18 OF 30

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX CMECHANICAL FRP PIPE SUPPORTS

    19 OF 30

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX CMECHANICAL FRP PIPE SUPPORTS

    20 OF 30

    6.0 Guide Supports

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX CMECHANICAL FRP PIPE SUPPORTS

    21 OF 30

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX CMECHANICAL FRP PIPE SUPPORTS

    22 OF 30

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX CMECHANICAL FRP PIPE SUPPORTS

    23 OF 30

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX CMECHANICAL FRP PIPE SUPPORTS

    24 OF 30

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX CMECHANICAL FRP PIPE SUPPORTS

    25 OF 30

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX CMECHANICAL FRP PIPE SUPPORTS

    26 OF 30

    7.0 Anchor Supports

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX CMECHANICAL FRP PIPE SUPPORTS

    27 OF 30

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX CMECHANICAL FRP PIPE SUPPORTS

    28 OF 30

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX CMECHANICAL FRP PIPE SUPPORTS

    29 OF 30

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX CMECHANICAL FRP PIPE SUPPORTS

    30 OF 30

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX DMECHANICAL HDPE PIPE SUPPORTS

    1 OF 32

    Appendix D:HDPE Standard Support Details

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX DMECHANICAL HDPE PIPE SUPPORTS

    2 OF 32

    Appendix D:HDPE Standard Support Details

    Index1.0 Introduction

    1.1. Purpose1.2. Scope

    2.0 Codes and Standards

    3.0 Design Criteria and Guidelines

    3.1. General Design Consideration3.2. HDPE Pipe Supports3.3. Supplementary Steel3.4. HDPE Pipe Support Spacing

    4.0 General Notes for HDPE Pipe Supports

    5.0 Rigid Supports

    5.1. HPR-1: HDPE Pipe Rigid Support, 2-365.2. HPR-2: HDPE Pipe Rigid Support, 2-365.3. HPR-3: HDPE Pipe Riser Support, 2-125.4. HPR-4: HDPE Pipe Rod Hanger, 2-205.5. HPR-5: HDPE Pipe Component Hanger, 2-365.6. HPR-6: HDPE Pipe Riser Component Support, 2-365.7. HPR-7: HDPE Pipe Rod Hanger, 2-205.8. HPR-8: HDPE Pipe Riser Hanger, 2-16

    6.0 Guide Supports

    6.1. HPG-1: HDPE Pipe Guide, 2-366.2. HPG-1A: HDPE Pipe Guide, 2-166.3. HPG-2: HDPE Pipe Guide, 2-366.4. HPG-3: HDPE Pipe Riser Guide, 2-66.5. HPG-4: HDPE Pipe Riser Guide, 8-12

    7.0 Anchor Supports

    7.1. HPA-1: HDPE Pipe Friction Anchor, 2-367.2. HPA-1A: HDPE Pipe Friction Anchor, 2-167.3. HPA-2: HDPE Pipe Friction Anchor, 2-367.4. HPA-3: HDPE Pipe Riser Anchor, 2-67.5. HPA-4: HDPE Pipe Riser Anchor, 8-127.6. HPA-5: HDPE Pipe Anchor, 2-367.7. HPA-6: HDPE Pipe Anchor, 2-367.8. HPA-7: HDPE Pipe Riser Component Anchor, 2-36 7.9. HPA-8: HDPE Pipe Anchor, 2-36

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX DMECHANICAL HDPE PIPE SUPPORTS

    3 OF 32

    7.10. HPA-9: HDPE Pipe Anchor, 2-367.11. HPA-10: HDPE Pipe Positive Anchor, 4-16

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX DMECHANICAL HDPE PIPE SUPPORTS

    4 OF 32

    HDPE PIPE SUPPORTS

    1.0 Introduction

    1.1 Purpose

    The purpose of this chapter is intended to serve as a guide to the proper use of pipe hangers and supports of High Density Polyethylene, normally called HDPE piping system. The document is not intended to supersede project specific design criteria but to reflect Mechanical Design Standards.

    1.2 Scope

    This standard shall apply to HDPE pipe supports for piping systems ranging in size up to 36 inches, unless noted otherwise. Design of HDPE pipe supports shall be the responsibility of Design Engineering. Design criteria and guidelines are given in Section 3.0 of this Appendix D.

    2.0 Standards

    HDPE pipe support design and installation shall be in accordance with the pipe manufacturers recommendation. This standard gives general guidelines applicable to nonmetallic piping system and pipe support design in accordance with

    American Society of Mechanical Engineers,ASME Standard B31.3 Process Piping.

    3.0 Design Criteria and Guidelines

    3.1 General Design Consideration

    Supports shall be designed for the most severe conditions of coincident pressure, weight, temperature, and any fluid dynamic events. In addition, piping exposed to wind, snow, ice, earthquake, or other natural phenomena shall be considered and supports shall be designed for such loading.

    Thermal expansion and contraction must be considered during piping system design. These design parameters shall be incorporated into the installation specifications. Thermal expansion of HDPE is much greater than that of steel. Allowances must be made to accommodate or control this expansion. HDPE piping supports shall be designed for the maximum operating conditions, including thermal effects.

    HDPE pipe supports, hanger components, support spacing, and installation shall meet the requirements specified by the HDPE pipe manufacturer.

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX DMECHANICAL HDPE PIPE SUPPORTS

    5 OF 32

    Pipe supports shall be located close to concentrated loads such as valves, flanges, branch connections, short risers, and other components in order to keep bending stresses to a minimum. Heavy valves must be supported independently. Heavy fittings and metal flanged connections should be supported on either side.

    All valves and inline components shall be supported independently of the pipe. Heavycomponents such as actuators, and/or external loads shall be anchored to prevent pipe damage.

    Where the pipeline is designed to move due to expansion, a sliding support, capable of guidingwithout restraint in the direction of movement, shall be provided.

    For buried HDPE applications, soil friction along the pipe length, combined with moderate or low temperature change, shall be sufficient to prevent dimensional change and expansion movement, unless determined otherwise. Thrust blocks for underground pipelines shall be utilized on underground pipelines where water hammer and temperature changes are anticipateddue to a transient analysis.

    HDPE piping shall be protected against excessive bending and shear loads where pipes emerge from structures as walls or casings; in addition to rigid connections such as flanges and mechanical joints.

    3.2 HDPE Pipe Supports

    The basic types of supports are weight supports, guide supports and anchor supports.

    Above grade HDPE applications require non-continuous support. Such applications involve piping in a rack or trestle, on sleepers, or suspended from an overhead structure. Supportstructures must provide proper pipeline support, accommodate thermal expansion and contraction movement, and provide support spacing that limits vertical deflection between supports within acceptable limits. See section 3.4 of this Appendix for HDPE spacing requirements.

    The weight of the pipe and the contents must be distributed over a broad surface. Commercial pipe supports such as u-bolts, narrow strap-type hangers, and roller type supports are unsuitable unless modified for width and cradling. Narrow support surfaces can produce high concentrated stress, and lead to pipeline failure.

    Pipes supported in an overhead rack shall be designed for both support spacing and thermal length change. Support beams shall be spaced according to vertical deflection limits. Pipe supports should be allowed to move along support beams.

    Pipe hangers shall be capable of supporting the pipe in all conditions of operation. They shall allow free expansion and contraction of the piping, and prevent excessive stress resulting from transferred weight being induced into the pipe or connected equipment.

  • SOUTHERN COMPANY SERVICES M-2-3ENGINEERING STANDARDS AND GUIDELINES APPENDIX DMECHANICAL HDPE PIPE SUPPORTS

    6 OF 32

    HDPE piping shall be protected against excessive bending and shear loads where pipes emerge from structures such as walls or castings, in addition to rigid connections such as flanges and mechanical joints.

    3.4 HDPE Pipe Support Spacing

    Horizontal HDPE pipe shall be supported to prevent excessive sag, bending and shear stresses in the piping. Special design consideration shall be given where components such as flanges and valves impose concentrated loads.

    Vertical HDPE pipe supports shall be spaced to prevent the pipe from being overstressed due to the combination of all loading effects.

    HDPE supports shall be spaced to meet the requirements of the recommended hanger and support spacing chart issued by the pipe manufacturer.

    The following table o