DATE REVISIONS NO. DESIGNED: DRAWN: DATE: 2-20-18 CHECKED: SCALE: AS SHOWN 800 Allegheny Avenue Pittsburgh, Pennsylvania 15233 DRAWING NUMBER: HOMEWOOD - BRUSHTON CENTER - 701 N HOMEWOOD AVE, PITTSBURGH PA. 15208 ELECTRICAL SERVICE REPLACEMENT COMMUNITY COLLEGE OF ALLEGHENY COUNTY ASE PROJ. NUMBER: - 1741119 CCAC PROJ. NO.: - 13-CO-003a7a N A H T PROFESSIONAL DAVID C. PRICE N P N E L No. PE081572 Y S V ENGINEER N O M M O C L REGISTERED E W A A I F O MWM E001 MWM DEB ELECTRICAL DATA SHEET GENERAL ELECTRICAL NOTES: GENERAL: UNLESS SPECIFICALLY INDICATED OTHERWISE, ALL WORK SHOWN ON THE ELECTRICAL DRAWINGS IS NEW WORK TO BE PROVIDED UNDER THIS CONTRACT. DEMOLITION: SEE "ELECTRICAL GENERAL DEMOLITION NOTES" SHEET E.001 FOR ADDITIONAL DEMOLITION REQUIREMENTS. COORDINATION: COORDINATE AND COOPERATE WITH ALL TRADES ON THE PROJECT. RECORD DRAWINGS: SECURE AN EXTRA SET OF ELECTRICAL DRAWINGS TO BE KEPT ON SITE AND MARK, DAILY, THE DRAWINGS IN RED AS THE PROJECT PROGRESSES IN ORDER TO KEEP AN ACCURATE RECORD OF ALL DEVIATIONS BETWEEN THE WORK SHOWN ON THE DRAWINGS AND THE WORK WHICH IS ACTUALLY INSTALLED. THESE MARKED DRAWINGS SHALL REFLECT ANY AND ALL CHANGES AND REVISIONS TO THE ORIGINAL DESIGN WHICH EXISTS IN THE COMPLETED WORK. DELIVER THE MARKED DRAWINGS TO THE <ARCHITECT/ENGINEER> AT PROJECT CLOSE-OUT. TESTS: TEST ALL WIRING FOR CONTINUITY AND GROUNDS BEFORE CONNECTING ANY FIXTURES OR DEVICES. PERFORM INSULATION RESISTANCE TESTS ON ALL WIRING #8 OR LARGER TO ENSURE THAT ALL PORTIONS ARE FREE FROM SHORT-CIRCUITS AND GROUNDS. INSPECTIONS: ARRANGE ALL NECESSARY INSPECTIONS. DELIVER ALL REQUIRED INSPECTION CERTIFICATES TO THE OWNER. GROUNDING: PROVIDE GROUNDING IN ACCORDANCE WITH THE NEC FOR THE ELECTRICAL SYSTEM INCLUDING EQUIPMENT FRAMES CONDUITS, SWITCHES, CONTROLLERS, WIRE-WAYS, NEUTRAL CONDUCTORS, AND OTHER EQUIPMENT. PROVIDE A GROUNDING CONDUCTOR IN ALL POWER CIRCUITS. LABELS: PROVIDE LABELS FOR ALL PANELBOARDS, CABINETS, SAFETY SWITCHES, MOTOR-DISCONNECT SWITCHES, AND MOTOR CONTROLLERS. LABELS SHALL BE MACHINE ENGRAVED, LAMINATED PLASTIC, PERMANENTLY ATTACHED WITH SELF-TAPPING SCREWS OR RIVETS. DO NOT USE SELF-ADHESIVE LABELS. J-BOX LABELING: LABEL ALL JUNCTION BOXES WITH PERMANENT MARKER IDENTIFYING CIRCUIT NUMBER AND PANELBOARD OF CIRCUITS WITHIN. PANEL DIRECTORY: PROVIDE TYPEWRITTEN PANELBOARD DIRECTORY CARD IN EACH PANELBOARD INCLUDING EXISTING PANELBOARDS MODIFIED FOR THIS PROJECT WITH CIRCUIT LOAD INFORMATION AND ROOM NUMBER CLEARLY IDENTIFIED. USE ACTUAL ROOM NUMBERS IN THE BUILDING, NOT THE ROOM NUMBERS SHOWN ON THE CONTRACT DRAWINGS, AS THEY ARE OFTEN DIFFERENT. CONNECTION DETAILS: SECURE APPROVED SHOP DRAWINGS SHOWING WIRING DIAGRAMS, ROUGH-IN AND HOOK UP DETAILS FROM OTHER INVOLVED CONTRACTORS FOR EQUIPMENT WHICH MUST BE CONNECTED ELECTRICALLY. EQUIPMENT DETAILS: MECHANICAL EQUIPMENT WILL BE FURNISHED AND INSTALLED BY THE MECHANICAL CONTRACTOR. THE LOCATIONS SHOWN ON THE ELECTRICAL DRAWINGS ARE APPROXIMATE. COORDINATE WITH THE MECHANICAL CONTRACTOR TO DETERMINE THE EXACT LOCATION OF EACH PIECE OF EQUIPMENT AND DETERMINE THE EXACT ROUGH-IN AND CONNECTION REQUIREMENTS. LIGHTING ARRANGEMENT: ARRANGE LIGHTING FIXTURES IN ACCORDANCE WITH THE ARCHITECTURAL REFLECTED CEILING PLANS. LIGHTING COORDINATION: COORDINATE LIGHTING FIXTURES WITH GRILLES, DIFFUSERS, SPRINKLER HEADS, AND ACCESS PANELS, ETC. MATERIAL COORDINATION: VERIFY CEILING AND WALL CONSTRUCTION AND MATERIAL PRIOR TO ORDERING LIGHT FIXTURES OR OTHER DEVICES TO ENSURE PROPER FIXTURES OR DEVICE IS FURNISHED TO MATCH CONSTRUCTION. MOUNTING HEIGHTS: MOUNTING HEIGHTS INDICATED ARE FROM THE FINISHED FLOOR TO THE CENTERLINE OF THE WIRING DEVICE UNLESS OTHERWISE NOTED. MOUNTING HEIGHTS OF LIGHTING FIXTURES AND FIRE ALARM DEVICES ARE TO THE BOTTOM OF THE FIXTURE OR DEVICE UNLESS OTHERWISE NOTED. DEVICE LOCATIONS: COORDINATE LOCATIONS OF SWITCHES, RECEPTACLES, AND TELE/DATA OUTLETS WITH OTHER WALL MOUNTED DEVICES SUCH AS THERMOSTATS AND CONTROL STATIONS. DO NOT MOUNT WIRING DEVICES BACK TO BACK. PROVIDE MINIMUM OF ONE STUD SEPARATION. DEVICE COORDINATION: THOROUGHLY REVIEW AND COORDINATE ALL CASEWORK, DOOR SWINGS, AND CABINET DRAWINGS AND ARCHITECTURAL ELEVATIONS WITH DEVICE LOCATIONS PRIOR TO ROUGH-IN OF OUTLET BOXES. BARRIERS: WHERE A MULTIPLE GANG BOX HAS CIRCUITS OF DIFFERENT VOLTAGES OR SYSTEMS WHICH ARE REQUIRED TO BE SEPARATED, PROVIDE THE CODE-REQUIRED SEPARATION USING A FULL HEIGHT AND DEPTH BARRIER PLATE. FIRE PROOFING: FOR ANY WALL OR FLOOR PENETRATIONS THROUGH FIRE RATED STRUCTURES PROVIDE FIRE-PROOFING TO SEAL ALL THE PENETRATIONS AFTER THE CONDUIT HAS BEEN INSTALLED. FIRE PROOFING FOR PENETRATIONS SHALL BE UL APPROVED PER THE THE PENETRATION MADE IN ORDER TO MAINTAIN FIRE RATED INTEGRITY OF THE STRUCTURE. ELECTRICAL GENERAL DEMOLITION NOTES: GENERAL: DEMOLITION DRAWINGS ARE BASED ON EXISTING PLANS AND FIELD INVESTIGATION PRIOR TO DEMOLITION. VISIT THE EXISTING BUILDING PRIOR TO BID IN ORDER TO BECOME FAMILIAR WITH THE EXISTING CONDITIONS AND IN ORDER TO AVOID CONFLICTS. DASHED ITEMS: ALL ITEMS SHOWN DASHED ON DEMOLITION PLANS ARE EXISTING AND SHALL BE REMOVED COMPLETE INCLUDING BOXES, CONDUIT, WIRE, FASTENERS, AND ASSOCIATED APPURTENANCES UON. SOLID ITEMS: ALL ITEMS SHOWN SOLID ON DEMOLITION PLANS ARE EXISTING TO REMAIN. CIRCUITING TO REMAIN: EXISTING CIRCUITING TO REMAIN SHALL BE REROUTED OR RECONNECTED, AS REQUIRED, WHERE AFFECTED BY NEW WORK IN ORDER TO MAINTAIN CONTINUITY OF CIRCUIT. REUSE OF EXISTING CIRCUITRY: EXISTING CIRCUITRY SERVING LIGHTING FIXTURES AND/OR RECEPTACLES FOR A GIVEN AREA SHALL BE REUSED WHERE CONVENIENT TO SERVE THE NEW LAYOUT. PROVIDE CIRCUIT MODIFICATIONS INDICATED OR AS OTHERWISE REQUIRED TO MAINTAIN THE CONTINUITY OF THE EXISTING CIRCUITS THAT REMAIN. EXISTING CONDUIT: ALL EXISTING CONDUITS AND WIRING THAT WILL NOT BE REUSED SHALL BE REMOVED WHERE THEY WILL BE EXPOSED UPON COMPLETION OF NEW WORK. EXISTING CONDUIT TO REMAIN CONCEALED IN WALLS SHALL BE ABANDONED. EXISTING CONDUIT TO REMAIN BELOW FLOOR SLAB SHALL BE CUT OFF ONE INCH BELOW ROUGH FLOOR AND GROUTED FLUSH. ALL EXISTING WIRING IN CONDUITS TO BE ABANDONED SHALL BE DISCONNECTED FROM POWER SOURCE AND REMOVED. REPAIR DAMAGE: EXERCISE CARE IN REMOVAL OF DEMOLITION ITEMS. REPAIR, AT NO ADDITIONAL COST TO OWNER, ANY DAMAGE CAUSED TO EXISTING CONSTRUCTION AND/OR EQUIPMENT TO REMAIN. ASSOCIATED APPURTENANCES: REMOVE ALL ELECTRICAL APPURTENANCES (DISCONNECTS, STARTERS, WIRING, CONDUIT, ETC.) ASSOCIATED WITH EQUIPMENT TO BE REMOVED BY OTHERS. KNOCKOUT PLUGS AND COVERS: ALL CONDUIT REMOVED SHALL BE REMOVED IN ITS ENTIRETY, INCLUDING FITTINGS, MOUNTING DEVICES, MOUNTING HARDWARE, ETC. PROVIDE CONDUIT PLUGS AND BLANKS FOR ALL OPENINGS CREATED BY THE REMOVAL OF CONDUIT. PROVIDE BLANK COVER PLATES FOR ALL OPENED OUTLET BOXES CREATED BY THE REMOVAL OF THE EQUIPMENT AND/OR DEVICES. DEMOLISHED MATERIALS: ALL MATERIALS REMOVED UNDER DEMOLITION, NOT TO BE RELOCATED OR DESIGNATED TO BE TURNED OVER TO THE OWNER, SHALL BECOME PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED COMPLETELY FROM THE SITE. SCHEDULE OUTAGES: ALL WORK AND ALL POWER OUTAGES IN THE EXISTING BUILDING SHALL BE SCHEDULES AT TIMES CONVENIENT TO THE OWNER. NOTIFICATION: NOTIFY THE OWNER PRIOR TO TURNING OFF ANY CIRCUITS. EXISTING CIRCUITS: IF DURING THE COURSE OF CONSTRUCTION, IT IS DETERMINED BY THE CONTRACTOR THAT AN EXISTING CIRCUIT BECOMES SPARE, THE CONTRACTOR SHALL UPDATE THE PANELBOARD DIRECTORY TO INDICATE SUCH, EVEN IF IT IS NOT EXPLICITLY MARKED ON THE ELECTRICAL PLANS. ELECTRICAL PANELBOARD JUNCTION BOX - ABOVE CEILINGS OR FLUSH IN WALLS. POWER ELECTRICAL CIRCUIT RUN IN CONDUIT AND CIRCUIT HOMERUN TO PANELBOARD (PANEL AND CIRCUIT DESIGNATION AS INDICATED). AS A MINIMUM CONDITION, EACH SINGLE PHASE CIRCUIT SHALL HAVE 1 #12 PHASE CONDUCTOR, 1 #12 NEUTRAL CONDUCTOR, AND 1 #12 GROUNDING CONDUCTOR IN 3/4" CONDUIT. PROVIDE ADDITIONAL PHASE CONDUCTORS AS REQUIRED FOR "MULTIPLE PHASED" ELECTRICAL LOADS. PROVIDE ADDITIONAL "SWITCH LEG" CONDUCTORS TO PROVIDE THE LIGHT FIXTURE CONTROL INDICATED. MULTIPLE SINGLE PHASE CONDUCTORS SHALL BE GROUPED TOGETHER IN A COMMON CONDUIT IN ACCORDANCE WITH THE NEC AND AT THE CONTRACTOR'S DISCRETION. NEUTRAL AND GROUNDING CONDUCTORS SHALL BE SHARED AS ALLOWED BY THE NEC. CONDUIT LARGER THAN 3/4" AND CONDUCTORS LARGER THAN #12 SHALL BE AS INDICATED. GENERAL KEYED WORK NOTE. FUSE SIZE (AMPS), N.F. INDICATES NON-FUSED DISCONNECT SWITCH - SIZE AS INDICATED ON PLANS SIZE (AMPS) 30/2/20/3R No. OF POLES NEMA RATING (IF OTHER THAN 1) DUPLEX RECEPTACLE, 20A, 120V, 18"AFF, UON. SINGLE RECEPTACLE, 20A, 120V, 18"AFF, UON. ABOVE FINISHED FLOOR AFF ABBREVIATIONS AMPERE A ABOVE FINISHED GRADE AFG AIR HANDLING UNIT AHU AIC AMPERE INTERRUPTING CURRENT ATS AUTOMATIC TRANSFER SWITCH AV AUDIO/VISUAL BFG BELOW FINISHED GRADE C CONDUIT CATV CABLE ANTENNA TELEVISION CFL COMPACT FLUORESCENT CKT CIRCUIT EBU EMERGENCY BATTERY UNIT EC EMPTY CONDUIT ECB ENCLOSED CIRCUIT BREAKER EF EXHAUST FAN ERU ENERGY RECOVERY UNIT EQUIP EQUIPMENT ETR EXISTING TO REMAIN EWC ELECTRIC WATER COOLER EWH ELECTRIC WATER HEATER EXIST EXISTING FHP FRACTIONAL HORSE POWER FLA FULL LOAD AMPS GC GENERAL CONTRACTOR GFI GROUND FAULT CIRCUIT GND GROUND HID HIGH INTENSITY DISCHARGE KVA KILO-VOLT AMPERE KW KILO-WATT LC LIGHTING CONTACTOR LTG LIGHTING MAU MAKE UP AIR UNIT MCA MINIMUM CIRCUIT AMPS MC MECHANICAL CONTACTOR MC METAL CLAD MCB MAIN CIRCUIT BREAKER MFR MANUFACTURER MLO MAIN LUGS ONLY MTD MOUNTED NEC NATIONAL ELECTRICAL CODE NF NON-FUSED NIC NOT IN CONTRACT NL NIGHT LIGHT NTS NOT TO SCALE OC ON CENTER OFCI OWNER FURNISHED CONTRACTOR INSTALLED P POLE PCP PUMP CONTROL PANEL PF POWER FACTOR PL PROPERTY LINE PNL PANEL PNLBD PANELBOARD Ø PHASE PRI PRIMARY RECP RTU ROOF TOP UNIT SE SERVICE ENTRANCE SEC SECONDARY TBB TELEPHONE BACKBOARD TVSS TRANSIENT VOLTAGE TYP TYPICAL UON UNLESS OTHERWISE NOTED V VOLTS VAC VOLTS ALTERNATING CURRENT VAV VARIABLE AIR VOLUME VDC VOLTS DIRECT CURRENT CCTV CLOSED CIRCUIT TELEVISION CB CIRCUIT BREAKER EC ELECTRICAL CONTRACTOR HP HORSE POWER/HEAT PUMP HVAC HEATING, VENTILATING, IG ISOLATED GROUND JB JUNCTION BOX PC PLUMBING CONTRACTOR AND AIR CONDITIONING VFD VARIABLE FREQUENCY DRIVE W WATTS/WIRE WG WIRE GUARD WP WEATHERPROOF XFMR TRANSFORMER SURGE SUPPRESSER TR TAMPER RESISTANT RECEPTACLE J 1 INTERRUPTER CLEAN UP: ON PROJECT CLOSE-OUT, CLEAN ALL ELECTRICAL DEVICES, LIGHTING FIXTURES, LAMPS AND LENSES, AND REMOVE ALL PAINT SPATTERS FROM DEVICES, FIXTURES, AND PLATES. REPLACE ALL INOPERATIVE LAMPS. OWNER FURNISHED EQUIPMENT: CONTRACTOR SHALL OBTAIN CUT SHEETS, INSTALLATION DATA, AND ROUGH-IN REQUIREMENTS FOR OWNER FURNISHED, CONTRACTOR INSTALLED EQUIPMENT AND COORDINATE ROUGH-IN AND POWER REQUIREMENTS WITH THE OWNER'S REPRESENTATIVE PRIOR TO STARTING ANY ASSOCIATED WORK. CONDUIT ROUTING: ALL CONDUIT RUN OVERHEAD SHALL BE RUN AT THE BOTTOM OF THE FLOOR, ROOF STRUCTURE, OR LOWEST CHORD OF JOIST SPACE (AS APPLICABLE) ABOVE IN ORDER TO AVOID CONFLICTS WITH OTHER TRADES. WIRING DEVICES: ALL RECEPTACLES AND SWITCHES SHALL BE LABELED WITH PLASTIC LAMINATED LABEL WITH THE PANELBOARD DESIGNATION AND CIRCUIT NUMBER FROM WHICH IT IS FED. EQUIPMENT DEMONSTRATION: PROVIDE A DEMONSTRATION OF THE OPERATION OF ALL ELECTRICAL COMPONENTS UPON REQUEST OF THE OWNER. CEILING PLENUM: ALL WIRING THAT WILL NOT BE RUN IN CONDUIT SHALL BE PLENUM RATED. STRIP LIGHT S T DIGITAL LIGHTING TIMER SWITCH TO GROUND TRIAD SYSTEM TO STRUCTURAL STEEL 6" 4" MASONRY WALL COPPER GROUND BUS 1'-1/2" 1/4" 3/8" DIAMETER X 3" MIN. TO GENERATOR #3/0 BARE COPPER STRANDED MEDIUM DRAWN COPPER FOR ALL CONNECTIONS TO DOMESTIC WATER SERVICE SPARE THREADED BRONZE STUDS AND NUTS FOR FUTURE LUG CONNECTOR 36" X 2" (MINIMUM) COPPER WIRE BUS. SECURE TO WALL. SEE DETAIL THIS SHEET FRONT VIEW SIDE VIEW POLYESTER FIBER GLASS TUBE POLYESTER FIBER GLASS WASHER POLYESTER FIBER GLASS INSULATOR LEAD EXPANSION SHIELD LUG CONNECTOR THREADED BRONZE STUDS AND NUTS (TYPICAL-SEE SPECIFICATIONS) TO NATURAL GAS SERVICE TO MAIN SERVICE ENTRANCE DISCONNECT SWITCH SPARE NOTE: WHERE SPACE PROHIBITS HORIZONTAL MOUNTING, VERTICAL ORIENTATION OF GROUND BAR IS PERMISSIBLE. NO SCALE MAIN GROUND BAR DETAIL 1 E001 MGB GROUNDING NOTES: 1. THE E.C. SHALL INSTALL A MAIN GROUNDING BAR AND BOND TELECOM GROUNDING BARS AND OTHER APPLICABLE GROUNDING ELECTRODES PER THE GROUND BAR DETAIL TO ENSURE THE BUILDING HAS A CODE COMPLIANT GROUNDING SYSTEM. TO TELECOM GROUND BAR (TGB) IN TELECOM ROOM PANEL NAME 208/120 VOLTS 3Ø, 4W, XXXX AMPS MLO/MCB FED FROM PANEL "DISTRIBUTION PANEL NAME" 2 4" NOTES: 1. PANEL NAME SHALL HAVE A MINIMUM LETTER HEIGHT OF 3/8". ALL OTHER TEXT SHALL HAVE A MINIMUM LETTER HEIGHT OF 1/4". 2. NAMEPLATE SHALL BE MACHINE ENGRAVED, LAMINATED PLASTIC, WITH WHITE LETTERING. BACKGROUND COLOR SHALL BE BLACK. 3. NAMEPLATE SHALL BE ATTACHED WITH RIVETS OR SELF TAPPING SCREWS. 4. DIMENSIONS INDICATED ARE MINIMUM DIMENSIONS. PROVIDE LARGER NAMEPLATE IF REQUIRED TO FIT ALL SPECIFIED INFORMATION ON NAMEPLATE. 5. "X" INDICATES FIELD TO BE FILLED IN PER "ELECTRICAL EQUIPMENT NAMEPLATE SCHEDULE". 6. PROVIDE NAMEPLATE FOR ALL ELECTRICAL EQUIPMENT AS INDICATED IN "ELECTRICAL EQUIPMENT NAMEPLATE SCHEDULE" THIS SHEET. NO SCALE ELECTRICAL EQUIPMENT NAMEPLATE DETAIL 3 E001 FIRE ALARM ADDRESSABLE FIRE ALARM SYSTEM PHOTO-ELECTRIC SMOKE DETECTOR, CEILING MOUNTED. DEVICE SHALL MATCH EXISTING BASE BUILDING SYSTEM. FIRE ALARM HORN/VISUAL (HORN/STROBE) APPLIANCE WALL/CEILING MOUNTED. FOR WALL MOUNTED DEVICE MOUNT 80"AFF TO THE BOTTOM OF THE FLASHING ACRYLIC LENS WITH A MAXIMUM HEIGHT OF 96" TO TOP OF LENS. SUBSCRIPT INDICATES MINIMUM CANDELA RATING. DEVICE SHALL MATCH EXISTING BASE BUILDING SYSTEM. AV SD 10'-0" 10'-0" 10'-0" 3/4"D X 10'-0"L SOLID COPPER GROUND ROD (TYP) #3/0 BARE COPPER INTERCONNECT GROUND RODS WITH 1 #3/0 BARE COPPER GROUND WIRE. #3/0 BARE COPPER CADWELD CONNECTION (TYP) TO ELECTRICAL SERVICE GROUND BAR TO ELECTRICAL SERVICE GROUND BAR 2 E001 GROUNDING TRIAD DETAIL NO SCALE

Transcript of LWEA ONTH REGISTERED MOF PROFESSIONAL C€¦ · to ground triad system to structural steel 6" 4"...

  • DATE

    REVISIONS

    NO.

    DESIGNED:

    DRAWN:

    DATE: 2-20-18

    CHECKED:

    SCALE: AS SHOWN

    800 Allegheny Avenue Pittsburgh, Pennsylvania 15233

    DRAWING NUMBER:

    HOMEWOOD - BRUSHTON CENTER -

    701 N HOMEWOOD AVE, PITTSBURGH PA. 15208

    ELECTRICAL SERVICE REPLACEMENT

    COMMUNITY COLLEGE OF ALLEGHENY COUNTY

    ASE PROJ. NUMBER: - 1741119

    CCAC PROJ. NO.: - 13-CO-003a7a

    NA

    HT

    PROFESSIONAL

    DAVID C. PRICE

    N

    P

    NE

    L

    No. PE081572

    YS V

    ENGINEER

    NOM

    MO

    C

    L

    REGISTERED

    EW A

    AI

    FO

    MWM

    E001

    MWM

    DEB

    ELECTRICAL DATA SHEET

    GENERAL ELECTRICAL NOTES:GENERAL: UNLESS SPECIFICALLY INDICATED OTHERWISE, ALL WORK SHOWN ON THE ELECTRICAL DRAWINGS ISNEW WORK TO BE PROVIDED UNDER THIS CONTRACT.

    DEMOLITION: SEE "ELECTRICAL GENERAL DEMOLITION NOTES" SHEET E.001 FOR ADDITIONAL DEMOLITIONREQUIREMENTS.

    COORDINATION: COORDINATE AND COOPERATE WITH ALL TRADES ON THE PROJECT.

    RECORD DRAWINGS: SECURE AN EXTRA SET OF ELECTRICAL DRAWINGS TO BE KEPT ON SITE AND MARK, DAILY, THEDRAWINGS IN RED AS THE PROJECT PROGRESSES IN ORDER TO KEEP AN ACCURATE RECORD OF ALL DEVIATIONSBETWEEN THE WORK SHOWN ON THE DRAWINGS AND THE WORK WHICH IS ACTUALLY INSTALLED. THESE MARKEDDRAWINGS SHALL REFLECT ANY AND ALL CHANGES AND REVISIONS TO THE ORIGINAL DESIGN WHICH EXISTS INTHE COMPLETED WORK. DELIVER THE MARKED DRAWINGS TO THE AT PROJECT CLOSE-OUT.

    TESTS: TEST ALL WIRING FOR CONTINUITY AND GROUNDS BEFORE CONNECTING ANY FIXTURES OR DEVICES.PERFORM INSULATION RESISTANCE TESTS ON ALL WIRING #8 OR LARGER TO ENSURE THAT ALL PORTIONS ARE FREEFROM SHORT-CIRCUITS AND GROUNDS.

    INSPECTIONS: ARRANGE ALL NECESSARY INSPECTIONS. DELIVER ALL REQUIRED INSPECTION CERTIFICATES TO THEOWNER.

    GROUNDING: PROVIDE GROUNDING IN ACCORDANCE WITH THE NEC FOR THE ELECTRICAL SYSTEM INCLUDINGEQUIPMENT FRAMES CONDUITS, SWITCHES, CONTROLLERS, WIRE-WAYS, NEUTRAL CONDUCTORS, AND OTHEREQUIPMENT. PROVIDE A GROUNDING CONDUCTOR IN ALL POWER CIRCUITS.

    LABELS: PROVIDE LABELS FOR ALL PANELBOARDS, CABINETS, SAFETY SWITCHES, MOTOR-DISCONNECT SWITCHES,AND MOTOR CONTROLLERS. LABELS SHALL BE MACHINE ENGRAVED, LAMINATED PLASTIC, PERMANENTLYATTACHED WITH SELF-TAPPING SCREWS OR RIVETS. DO NOT USE SELF-ADHESIVE LABELS.

    J-BOX LABELING: LABEL ALL JUNCTION BOXES WITH PERMANENT MARKER IDENTIFYING CIRCUIT NUMBER ANDPANELBOARD OF CIRCUITS WITHIN.

    PANEL DIRECTORY: PROVIDE TYPEWRITTEN PANELBOARD DIRECTORY CARD IN EACH PANELBOARD INCLUDINGEXISTING PANELBOARDS MODIFIED FOR THIS PROJECT WITH CIRCUIT LOAD INFORMATION AND ROOM NUMBERCLEARLY IDENTIFIED. USE ACTUAL ROOM NUMBERS IN THE BUILDING, NOT THE ROOM NUMBERS SHOWN ON THECONTRACT DRAWINGS, AS THEY ARE OFTEN DIFFERENT.

    CONNECTION DETAILS: SECURE APPROVED SHOP DRAWINGS SHOWING WIRING DIAGRAMS, ROUGH-IN AND HOOK UPDETAILS FROM OTHER INVOLVED CONTRACTORS FOR EQUIPMENT WHICH MUST BE CONNECTED ELECTRICALLY.

    EQUIPMENT DETAILS: MECHANICAL EQUIPMENT WILL BE FURNISHED AND INSTALLED BY THE MECHANICALCONTRACTOR. THE LOCATIONS SHOWN ON THE ELECTRICAL DRAWINGS ARE APPROXIMATE. COORDINATE WITH THEMECHANICAL CONTRACTOR TO DETERMINE THE EXACT LOCATION OF EACH PIECE OF EQUIPMENT AND DETERMINETHE EXACT ROUGH-IN AND CONNECTION REQUIREMENTS.

    LIGHTING ARRANGEMENT: ARRANGE LIGHTING FIXTURES IN ACCORDANCE WITH THE ARCHITECTURAL REFLECTEDCEILING PLANS.

    LIGHTING COORDINATION: COORDINATE LIGHTING FIXTURES WITH GRILLES, DIFFUSERS, SPRINKLER HEADS, ANDACCESS PANELS, ETC.

    MATERIAL COORDINATION: VERIFY CEILING AND WALL CONSTRUCTION AND MATERIAL PRIOR TO ORDERING LIGHTFIXTURES OR OTHER DEVICES TO ENSURE PROPER FIXTURES OR DEVICE IS FURNISHED TO MATCH CONSTRUCTION.

    MOUNTING HEIGHTS: MOUNTING HEIGHTS INDICATED ARE FROM THE FINISHED FLOOR TO THE CENTERLINE OF THEWIRING DEVICE UNLESS OTHERWISE NOTED. MOUNTING HEIGHTS OF LIGHTING FIXTURES AND FIRE ALARM DEVICESARE TO THE BOTTOM OF THE FIXTURE OR DEVICE UNLESS OTHERWISE NOTED.

    DEVICE LOCATIONS: COORDINATE LOCATIONS OF SWITCHES, RECEPTACLES, AND TELE/DATA OUTLETS WITH OTHERWALL MOUNTED DEVICES SUCH AS THERMOSTATS AND CONTROL STATIONS. DO NOT MOUNT WIRING DEVICESBACK TO BACK. PROVIDE MINIMUM OF ONE STUD SEPARATION.

    DEVICE COORDINATION: THOROUGHLY REVIEW AND COORDINATE ALL CASEWORK, DOOR SWINGS, AND CABINETDRAWINGS AND ARCHITECTURAL ELEVATIONS WITH DEVICE LOCATIONS PRIOR TO ROUGH-IN OF OUTLET BOXES.

    BARRIERS: WHERE A MULTIPLE GANG BOX HAS CIRCUITS OF DIFFERENT VOLTAGES OR SYSTEMS WHICH AREREQUIRED TO BE SEPARATED, PROVIDE THE CODE-REQUIRED SEPARATION USING A FULL HEIGHT AND DEPTHBARRIER PLATE.

    FIRE PROOFING: FOR ANY WALL OR FLOOR PENETRATIONS THROUGH FIRE RATED STRUCTURES PROVIDEFIRE-PROOFING TO SEAL ALL THE PENETRATIONS AFTER THE CONDUIT HAS BEEN INSTALLED. FIRE PROOFING FORPENETRATIONS SHALL BE UL APPROVED PER THE THE PENETRATION MADE IN ORDER TO MAINTAIN FIRE RATEDINTEGRITY OF THE STRUCTURE.

    ELECTRICAL GENERAL DEMOLITION NOTES:GENERAL: DEMOLITION DRAWINGS ARE BASED ON EXISTING PLANS AND FIELDINVESTIGATION PRIOR TO DEMOLITION. VISIT THE EXISTING BUILDING PRIOR TO BID INORDER TO BECOME FAMILIAR WITH THE EXISTING CONDITIONS AND IN ORDER TOAVOID CONFLICTS.

    DASHED ITEMS: ALL ITEMS SHOWN DASHED ON DEMOLITION PLANS ARE EXISTINGAND SHALL BE REMOVED COMPLETE INCLUDING BOXES, CONDUIT, WIRE, FASTENERS,AND ASSOCIATED APPURTENANCES UON.

    SOLID ITEMS: ALL ITEMS SHOWN SOLID ON DEMOLITION PLANS ARE EXISTING TOREMAIN.

    CIRCUITING TO REMAIN: EXISTING CIRCUITING TO REMAIN SHALL BE REROUTED ORRECONNECTED, AS REQUIRED, WHERE AFFECTED BY NEW WORK IN ORDER TOMAINTAIN CONTINUITY OF CIRCUIT.

    REUSE OF EXISTING CIRCUITRY: EXISTING CIRCUITRY SERVING LIGHTING FIXTURESAND/OR RECEPTACLES FOR A GIVEN AREA SHALL BE REUSED WHERE CONVENIENT TOSERVE THE NEW LAYOUT. PROVIDE CIRCUIT MODIFICATIONS INDICATED OR ASOTHERWISE REQUIRED TO MAINTAIN THE CONTINUITY OF THE EXISTING CIRCUITS THATREMAIN.

    EXISTING CONDUIT: ALL EXISTING CONDUITS AND WIRING THAT WILL NOT BE REUSEDSHALL BE REMOVED WHERE THEY WILL BE EXPOSED UPON COMPLETION OF NEWWORK. EXISTING CONDUIT TO REMAIN CONCEALED IN WALLS SHALL BE ABANDONED.EXISTING CONDUIT TO REMAIN BELOW FLOOR SLAB SHALL BE CUT OFF ONE INCHBELOW ROUGH FLOOR AND GROUTED FLUSH. ALL EXISTING WIRING IN CONDUITS TOBE ABANDONED SHALL BE DISCONNECTED FROM POWER SOURCE AND REMOVED.

    REPAIR DAMAGE: EXERCISE CARE IN REMOVAL OF DEMOLITION ITEMS. REPAIR, AT NOADDITIONAL COST TO OWNER, ANY DAMAGE CAUSED TO EXISTING CONSTRUCTIONAND/OR EQUIPMENT TO REMAIN.

    ASSOCIATED APPURTENANCES: REMOVE ALL ELECTRICAL APPURTENANCES(DISCONNECTS, STARTERS, WIRING, CONDUIT, ETC.) ASSOCIATED WITH EQUIPMENT TOBE REMOVED BY OTHERS.

    KNOCKOUT PLUGS AND COVERS: ALL CONDUIT REMOVED SHALL BE REMOVED IN ITSENTIRETY, INCLUDING FITTINGS, MOUNTING DEVICES, MOUNTING HARDWARE, ETC.PROVIDE CONDUIT PLUGS AND BLANKS FOR ALL OPENINGS CREATED BY THEREMOVAL OF CONDUIT. PROVIDE BLANK COVER PLATES FOR ALL OPENED OUTLETBOXES CREATED BY THE REMOVAL OF THE EQUIPMENT AND/OR DEVICES.

    DEMOLISHED MATERIALS: ALL MATERIALS REMOVED UNDER DEMOLITION, NOT TO BERELOCATED OR DESIGNATED TO BE TURNED OVER TO THE OWNER, SHALL BECOMEPROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED COMPLETELY FROM THESITE.

    SCHEDULE OUTAGES: ALL WORK AND ALL POWER OUTAGES IN THE EXISTINGBUILDING SHALL BE SCHEDULES AT TIMES CONVENIENT TO THE OWNER.

    NOTIFICATION: NOTIFY THE OWNER PRIOR TO TURNING OFF ANY CIRCUITS.

    EXISTING CIRCUITS: IF DURING THE COURSE OF CONSTRUCTION, IT IS DETERMINED BYTHE CONTRACTOR THAT AN EXISTING CIRCUIT BECOMES SPARE, THE CONTRACTORSHALL UPDATE THE PANELBOARD DIRECTORY TO INDICATE SUCH, EVEN IF IT IS NOTEXPLICITLY MARKED ON THE ELECTRICAL PLANS.

    ELECTRICAL PANELBOARD

    JUNCTION BOX - ABOVE CEILINGS OR FLUSH IN WALLS.

    POWER

    ELECTRICAL CIRCUIT RUN IN CONDUIT AND CIRCUIT HOMERUN TOPANELBOARD (PANEL AND CIRCUIT DESIGNATION AS INDICATED).AS A MINIMUM CONDITION, EACH SINGLE PHASE CIRCUIT SHALLHAVE 1 #12 PHASE CONDUCTOR, 1 #12 NEUTRAL CONDUCTOR, AND 1#12 GROUNDING CONDUCTOR IN 3/4" CONDUIT. PROVIDEADDITIONAL PHASE CONDUCTORS AS REQUIRED FOR "MULTIPLEPHASED" ELECTRICAL LOADS. PROVIDE ADDITIONAL "SWITCH LEG"CONDUCTORS TO PROVIDE THE LIGHT FIXTURE CONTROLINDICATED. MULTIPLE SINGLE PHASE CONDUCTORS SHALL BEGROUPED TOGETHER IN A COMMON CONDUIT IN ACCORDANCEWITH THE NEC AND AT THE CONTRACTOR'S DISCRETION. NEUTRALAND GROUNDING CONDUCTORS SHALL BE SHARED AS ALLOWEDBY THE NEC. CONDUIT LARGER THAN 3/4" AND CONDUCTORSLARGER THAN #12 SHALL BE AS INDICATED.

    GENERALKEYED WORK NOTE.

    FUSE SIZE (AMPS), N.F. INDICATES NON-FUSED

    DISCONNECT SWITCH - SIZE AS INDICATED ON PLANS

    SIZE (AMPS)

    30/2/20/3R

    No. OF POLES

    NEMA RATING (IF OTHER THAN 1)

    DUPLEX RECEPTACLE, 20A, 120V, 18"AFF, UON.

    SINGLE RECEPTACLE, 20A, 120V, 18"AFF, UON.

    ABOVE FINISHED FLOORAFF

    ABBREVIATIONSAMPEREA

    ABOVE FINISHED GRADEAFGAIR HANDLING UNITAHU

    AIC AMPERE INTERRUPTING CURRENTATS AUTOMATIC TRANSFER SWITCHAV AUDIO/VISUALBFG BELOW FINISHED GRADEC CONDUITCATV CABLE ANTENNA TELEVISION

    CFL COMPACT FLUORESCENTCKT CIRCUITEBU EMERGENCY BATTERY UNITEC EMPTY CONDUIT

    ECB ENCLOSED CIRCUIT BREAKEREF EXHAUST FANERU ENERGY RECOVERY UNITEQUIP EQUIPMENTETR EXISTING TO REMAINEWC ELECTRIC WATER COOLEREWH ELECTRIC WATER HEATEREXIST EXISTINGFHP FRACTIONAL HORSE POWERFLA FULL LOAD AMPSGC GENERAL CONTRACTORGFI GROUND FAULT CIRCUIT

    GND GROUNDHID HIGH INTENSITY DISCHARGE

    KVA KILO-VOLT AMPEREKW KILO-WATTLC LIGHTING CONTACTORLTG LIGHTINGMAU MAKE UP AIR UNITMCA MINIMUM CIRCUIT AMPSMC MECHANICAL CONTACTORMC METAL CLADMCB MAIN CIRCUIT BREAKERMFR MANUFACTURERMLO MAIN LUGS ONLYMTD MOUNTEDNEC NATIONAL ELECTRICAL CODENF NON-FUSEDNIC NOT IN CONTRACTNL NIGHT LIGHTNTS NOT TO SCALEOC ON CENTEROFCI OWNER FURNISHED

    CONTRACTOR INSTALLEDP POLE

    PCP PUMP CONTROL PANELPF POWER FACTORPL PROPERTY LINEPNL PANELPNLBD PANELBOARDØ PHASEPRI PRIMARYRECPRTU ROOF TOP UNITSE SERVICE ENTRANCESEC SECONDARYTBB TELEPHONE BACKBOARD

    TVSS TRANSIENT VOLTAGE

    TYP TYPICALUON UNLESS OTHERWISE NOTEDV VOLTSVAC VOLTS ALTERNATING CURRENTVAV VARIABLE AIR VOLUMEVDC VOLTS DIRECT CURRENT

    CCTV CLOSED CIRCUIT TELEVISIONCB CIRCUIT BREAKER

    EC ELECTRICAL CONTRACTOR

    HP HORSE POWER/HEAT PUMPHVAC HEATING, VENTILATING,

    IG ISOLATED GROUNDJB JUNCTION BOX

    PC PLUMBING CONTRACTOR

    AND AIR CONDITIONING

    VFD VARIABLE FREQUENCY DRIVEW WATTS/WIREWG WIRE GUARDWP WEATHERPROOFXFMR TRANSFORMER

    SURGE SUPPRESSER

    TR TAMPER RESISTANT

    RECEPTACLE

    J

    1

    INTERRUPTER

    CLEAN UP: ON PROJECT CLOSE-OUT, CLEAN ALL ELECTRICAL DEVICES, LIGHTING FIXTURES, LAMPS AND LENSES,AND REMOVE ALL PAINT SPATTERS FROM DEVICES, FIXTURES, AND PLATES. REPLACE ALL INOPERATIVE LAMPS.

    OWNER FURNISHED EQUIPMENT: CONTRACTOR SHALL OBTAIN CUT SHEETS, INSTALLATION DATA, AND ROUGH-INREQUIREMENTS FOR OWNER FURNISHED, CONTRACTOR INSTALLED EQUIPMENT AND COORDINATE ROUGH-IN ANDPOWER REQUIREMENTS WITH THE OWNER'S REPRESENTATIVE PRIOR TO STARTING ANY ASSOCIATED WORK.

    CONDUIT ROUTING: ALL CONDUIT RUN OVERHEAD SHALL BE RUN AT THE BOTTOM OF THE FLOOR, ROOF STRUCTURE,OR LOWEST CHORD OF JOIST SPACE (AS APPLICABLE) ABOVE IN ORDER TO AVOID CONFLICTS WITH OTHER TRADES.

    WIRING DEVICES: ALL RECEPTACLES AND SWITCHES SHALL BE LABELED WITH PLASTIC LAMINATED LABEL WITH THEPANELBOARD DESIGNATION AND CIRCUIT NUMBER FROM WHICH IT IS FED.

    EQUIPMENT DEMONSTRATION: PROVIDE A DEMONSTRATION OF THE OPERATION OF ALL ELECTRICAL COMPONENTSUPON REQUEST OF THE OWNER.

    CEILING PLENUM: ALL WIRING THAT WILL NOT BE RUN IN CONDUIT SHALL BE PLENUM RATED.

    STRIP LIGHT

    ST DIGITAL LIGHTING TIMER SWITCH

    TO GROUND TRIADSYSTEM TO

    STR

    UCTU

    RAL

    STEE

    L

    6"

    4"

    MASONRY WALLCOPPER GROUND BUS

    1'-1/2" 1/4"

    3/8" DIAMETER X 3" MIN.

    TO G

    ENER

    ATOR

    #3/0 BARE COPPERSTRANDED MEDIUMDRAWN COPPERFOR ALL CONNECTIONS

    TO D

    OMES

    TICW

    ATER

    SER

    VICE

    SPAR

    E

    THREADED BRONZESTUDS AND NUTS FORFUTURE LUG CONNECTOR

    36" X 2" (MINIMUM)COPPER WIRE BUS. SECURETO WALL. SEE DETAILTHIS SHEET

    FRONT VIEW

    SIDE VIEW

    POLYESTER FIBERGLASS TUBE

    POLYESTER FIBERGLASS WASHER

    POLYESTER FIBERGLASS INSULATOR

    LEAD EXPANSIONSHIELD

    LUG CONNECTORTHREADED BRONZE

    STUDS AND NUTS(TYPICAL-SEE

    SPECIFICATIONS)

    TO N

    ATUR

    AL G

    AS S

    ERVI

    CE

    TO M

    AIN

    SERV

    ICE

    ENTR

    ANCE

    DISC

    ONNE

    CT S

    WITC

    H

    SPAR

    E

    NOTE:WHERE SPACE PROHIBITS HORIZONTAL MOUNTING,VERTICAL ORIENTATION OF GROUND BAR ISPERMISSIBLE.

    NO SCALE

    MAIN GROUND BAR DETAIL1E001

    MGB

    GROUNDING NOTES:

    1. THE E.C. SHALL INSTALL A MAIN GROUNDINGBAR AND BOND TELECOM GROUNDING BARSAND OTHER APPLICABLE GROUNDINGELECTRODES PER THE GROUND BAR DETAIL TOENSURE THE BUILDING HAS A CODE COMPLIANTGROUNDING SYSTEM.

    TO T

    ELEC

    OMGR

    OUND

    BAR

    (TGB

    ) IN

    TELE

    COM

    ROO

    M

    PANEL NAME208/120 VOLTS 3Ø, 4W,

    XXXX AMPS MLO/MCB FED FROMPANEL "DISTRIBUTION PANEL NAME"

    2

    4"

    NOTES:

    1. PANEL NAME SHALL HAVE A MINIMUM LETTER HEIGHT OF 3/8". ALL OTHER TEXT SHALL HAVE AMINIMUM LETTER HEIGHT OF 1/4".

    2. NAMEPLATE SHALL BE MACHINE ENGRAVED, LAMINATED PLASTIC, WITH WHITE LETTERING.BACKGROUND COLOR SHALL BE BLACK.

    3. NAMEPLATE SHALL BE ATTACHED WITH RIVETS OR SELF TAPPING SCREWS.

    4. DIMENSIONS INDICATED ARE MINIMUM DIMENSIONS. PROVIDE LARGER NAMEPLATE IF REQUIRED TOFIT ALL SPECIFIED INFORMATION ON NAMEPLATE.

    5. "X" INDICATES FIELD TO BE FILLED IN PER "ELECTRICAL EQUIPMENT NAMEPLATE SCHEDULE".

    6. PROVIDE NAMEPLATE FOR ALL ELECTRICAL EQUIPMENT AS INDICATED IN "ELECTRICAL EQUIPMENTNAMEPLATE SCHEDULE" THIS SHEET.

    NO SCALE

    ELECTRICAL EQUIPMENT NAMEPLATE DETAIL3E001

    FIRE ALARMADDRESSABLE FIRE ALARM SYSTEM PHOTO-ELECTRIC SMOKEDETECTOR, CEILING MOUNTED. DEVICE SHALL MATCH EXISTINGBASE BUILDING SYSTEM.

    FIRE ALARM HORN/VISUAL (HORN/STROBE) APPLIANCEWALL/CEILING MOUNTED. FOR WALL MOUNTED DEVICE MOUNT80"AFF TO THE BOTTOM OF THE FLASHING ACRYLIC LENS WITH AMAXIMUM HEIGHT OF 96" TO TOP OF LENS. SUBSCRIPT INDICATESMINIMUM CANDELA RATING. DEVICE SHALL MATCH EXISTINGBASE BUILDING SYSTEM.

    AV

    SD

    10'-0" 10'-0"

    10'-0"

    3/4"D X 10'-0"LSOLID COPPERGROUND ROD (TYP)

    #3/0 BARE COPPER

    INTERCONNECTGROUND RODS

    WITH 1 #3/0BARE COPPER

    GROUND WIRE.

    #3/0 BARE COPPER

    CADWELDCONNECTION (TYP)

    TO ELECTRICAL SERVICE GROUND BAR

    TO ELECTRICAL SERVICE GROUND BAR

    2

    E001GROUNDING TRIAD DETAILNO SCALE

  • DATE

    REVISIONS

    NO.

    DESIGNED:

    DRAWN:

    DATE: 2-20-18

    CHECKED:

    SCALE: AS SHOWN

    800 Allegheny Avenue Pittsburgh, Pennsylvania 15233

    DRAWING NUMBER:

    HOMEWOOD - BRUSHTON CENTER -

    701 N HOMEWOOD AVE, PITTSBURGH PA. 15208

    ELECTRICAL SERVICE REPLACEMENT

    COMMUNITY COLLEGE OF ALLEGHENY COUNTY

    ASE PROJ. NUMBER: - 1741119

    CCAC PROJ. NO.: - 13-CO-003a7a

    NA

    HT

    PROFESSIONAL

    DAVID C. PRICE

    N

    P

    NE

    L

    No. PE081572

    YS V

    ENGINEER

    NOM

    MO

    C

    L

    REGISTERED

    EW A

    AI

    FO

    MWM

    E002

    MWM

    DEB

    ELECTRICAL SPECIFICATIONS

    ELECTRICAL SPECIFICATIONS

    A. GENERAL PROVISIONS

    1. REQUIREMENTS SPECIFIED IN DIVISION 1, INSTRUCTIONS TO BIDDERS, SUPPLEMENTAL GENERALCONDITIONS, SPECIAL CONDITIONS, ADDENDA, ALTERNATES, CONTRACT AND PROPOSAL, ALONGWITH DIVISION 16 AND ALL IT'S SECTIONS, COMPRISE THE CONTRACT DOCUMENTS FOR THEELECTRICAL CONTRACT. DRAWINGS AND ALL THEIR REVISIONS UP TO THE BID SUBMITTAL DATEBECOME A BINDING PART OF THE CONTRACT, ALONG WITH THESE SPECIFICATIONS AS THOUGH THEYWERE ONE, AND ANYTHING IMPLIED BY THE SPECIFICATIONS AS THOUGH SHALL BE INTERPRETED ASALSO IMPLIED BY THE DRAWINGS AND VICE VERSA. PROVIDE NECESSARY ITEMS FOR A COMPLETEINSTALLATION OF ALL ELECTRICALLY OPERATED EQUIPMENT LISTED IN THE SPECIFICATIONS ORSHOWN ON THE DRAWINGS.

    2. THE ARCHITECTURAL, STRUCTURAL, MECHANICAL, PLUMBING AND EQUIPMENT DRAWINGS ANDSPECIFICATIONS ARE INCORPORATED INTO, AND BECOME A PART OF THIS DIVISION. THISCONTRACTOR SHALL EXAMINE ALL SUCH DRAWINGS AND SPECIFICATIONS AND BECOMETHOROUGHLY FAMILIAR WITH THE PROVISIONS CONTAINED THEREIN. THE SUBMISSION OF THE BIDSHALL INDICATE SUCH KNOWLEDGE.

    3. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC. THEY ARE INTENDED TO SHOW THE APPROXIMATELOCATIONS OF EQUIPMENT AND CONDUIT. DIMENSIONS GIVEN ON THE PLANS, IN FIGURES, SHALLTAKE PRECEDENCE OVER SCALED DIMENSIONS AND SHALL BE VERIFIED IN THE FIELD. THEELECTRICAL CONTRACTOR SHALL LAYOUT ALL EQUIPMENT ROOMS TO MAKE SURE THE EQUIPMENT,AS PURCHASED, FITS IN THE ROOM OR SPACE SHOWN AND HAS ALL CLEARANCES REQUIRED BY THENEC. EXACT LOCATION OF ALL EQUIPMENT SHALL BE VERIFIED IN THE FIELD AND ROUTING OFCONDUITS SHALL SUIT FIELD CONDITIONS.

    4. UNTIL TIME OF INSTALLATION, THE ARCHITECT RESERVES THE RIGHT TO MAKE MINOR CHANGES IN THELOCATION OF CONDUIT AND EQUIPMENT WITHOUT ADDITIONAL COST TO THE CONTRACT.

    5. THE ELECTRICAL DRAWINGS AND SPECIFICATIONS ARE INTENDED TO SUPPLEMENT EACH OTHER.MATERIAL AND LABOR NECESSARY TO THE PROJECT SHALL BE FURNISHED AND INSTALLED EVENTHOUGH NOT SPECIFICALLY MENTIONED IN BOTH. LABOR AND/OR MATERIALS NEITHER SHOWN NORSPECIFIED, BUT OBVIOUSLY NECESSARY FOR THE COMPLETION AND PROPER FUNCTIONING OF THESYSTEM, SHALL BE FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR.

    6. ARRANGE ALL EQUIPMENT SUBSTANTIALLY AS SHOWN ON THE DRAWINGS. MAKE DEVIATIONS ONLYWHERE NECESSARY TO AVOID INTERFERENCE. CHECK ALL EQUIPMENT SIZES AGAINST AVAILABLESPACE PRIOR TO SHIPMENT TO AVOID INTERFERENCE.

    7. EXAMINE THE WORK OF OTHER TRADES INSOFAR AS THEIR WORK COMES IN CONTACT WITH OR ISCOVERED BY THIS WORK. IN NO CASE ATTACH TO, OR FINISH AGAINST ANY DEFECTIVE WORK ORINSTALL WORK IN A MANNER WHICH WILL PREVENT PROPER INSTALLATION OF THE WORK OF OTHERTRADES.

    8. ELECTRICAL CONTRACTOR SHALL VERIFY WITH OTHER TRADES ALL ELECTRICAL CONNECTIONS.CONTRACTOR SHALL VERIFY VOLTAGE, PHASE AND HORSEPOWER AND SHALL NOTIFY ENGINEER OFDISCREPANCIES PRIOR TO START OF WORK. ELECTRICAL CONTRACTOR SHALL PROVIDEDISCONNECTING MEANS AND OVERLOAD PROTECTION FOR ALL EQUIPMENT UNLESS FURNISHEDINTEGRAL WITH EQUIPMENT PACKAGE.

    9. IT IS THE INTENT OF THESE DRAWINGS THAT THIS BE A COMPLETE ELECTRICAL JOB, ANY ERRORS OROMISSIONS SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER PRIOR TO BIDDING THE JOB.

    B. VISIT TO THE SITE

    1. THIS CONTRACTOR SHALL VISIT THE SITE OF THE WORK AND FAMILIARIZE THEMSELVES WITH ALLCONDITIONS AFFECTING THIS CONTRACTORS WORK. THE SUBMISSION OF THE PROPOSAL SHALLINDICATE SUCH KNOWLEDGE. NO ADDITIONAL PAYMENT SHALL BE MADE ON CLAIMS THAT ARISEFROM A LACK OF KNOWLEDGE OF THE EXISTING CONDITIONS.

    C. CODE AND PERMITS

    1. INSTALLATION SHALL BE IN FULL ACCORDANCE WITH ALL CODES, RULES AND REGULATIONS OFMUNICIPAL, CITY, COUNTY, STATE AND PUBLIC UTILITIES AND ALL OTHER AUTHORITIES HAVINGJURISDICTION OVER THE PREMISES.

    2. COMPLY WITH ANY SPECIFICATION REQUIREMENTS THAT ARE IN EXCESS, BUT NOT IN CONFLICT WITHCODE REQUIREMENTS.

    3. THE CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, PLAN REVIEWS, AND CERTIFICATES OFINSPECTION IN CONNECTION WITH THE WORK REQUIRED BY THE FOREGOING AUTHORITIES. BEFOREFINAL PAYMENT OF THE CONTRACT IS ALLOWED, ALL CERTIFICATES SHALL BE DELIVERED TO THEARCHITECT IN DUPLICATE.

    4. ELECTRICAL MATERIAL AND EQUIPMENT SHALL BEAR THE UL LABEL EXCEPT WHERE UL DOES NOTLABEL SUCH TYPES OF MATERIAL AND EQUIPMENT.

    D. SHOP DRAWING SUBMITTALS

    1. THE ELECTRICAL CONTRACTOR SHALL SUBMIT FIVE (5) SETS OF SHOP DRAWINGS. THE SHOPDRAWINGS OF THE FOLLOWING EQUIPMENT USING THE INDICATED NUMBERING SYSTEM AND TITLES,SHALL BE SUBMITTED THROUGH THE ARCHITECT TO THE ENGINEER AND THEN RESUBMITTED FOR FINALAPPROVAL IF NECESSARY. SHOP DRAWINGS SHALL BE SUBMITTED FOR THE FOLLOWING ITEMS:

    a. WIRING DEVICESb. PANEL BOARDS, SAFETY SWITCHES

    2. ALL SUBMITTED SHOP DRAWINGS (MANUFACTURERS' EQUIPMENT DESCRIPTIVE SHEETS OR VENDORS'PREPARED DRAWINGS) SHALL HAVE THE GENERAL CONTRACTOR'S OR SUBCONTRACTOR'S STAMP OFAPPROVAL INDICATING THAT THE ITEM SUBMITTED IS AS CALLED FOR ON THE PLANS ANDSPECIFICATION, IS APPROVED BY THE GENERAL CONTRACTOR OR SUBCONTRACTOR, THE DATE OFAPPROVAL AND INITIALED BY THE PERSON APPROVING THE SUBMITTAL AND THE NAME OF THECOMPANY SUBMITTING SAID EQUIPMENT FOR APPROVAL.

    3. SUBMIT BOUND BROCHURES COMPLETE WITH A TABLE OF CONTENTS. LOOSE OR STAPLED TOGETHERSHEETS ARE NOT ACCEPTABLE. ANY SUBMITTALS NOT IN BROCHURE FORM OR NOT AS SPECIFIEDSHALL BE RETURNED AT THE CONTRACTORS EXPENSE FOR RESUBMITTAL.

    4. ALL DESCRIPTIVE LITERATURE SHALL BE SUBMITTED IN A THREE (3) HOLE BROCHURE WITH A COVERIDENTIFYING THE FOLLOWING:

    a. NAME OF THE JOB.b. LOCATION OF THE JOB, ADDRESS, CITY AND STATEc. NAME AND ADDRESS OF THE COMPANY SUBMITTING THE BROCHURES.d. DATE OF THE SUBMITTAL.

    5. EVERY EFFORT SHALL BE MADE, IN CHECKING THE SHOP DRAWINGS, TO DETECT AND CORRECT ALLERRORS, OMISSIONS AND INACCURACIES. FAILURE TO DO THIS WILL NOT RELIEVE THE ELECTRICALCONTRACTOR OF THE RESPONSIBILITY FOR THE PROPER AND COMPLETE INSTALLATION INACCORDANCE WITH THE CONTRACT DOCUMENTS.

    E. AS-BUILT DRAWINGS

    1. SUBMIT TO THE ARCHITECT ON SET OF REPRODUCIBLE ELECTRICAL DRAWINGS SHOWING THE AS BUILTCONDITIONS.

    F. STANDARDS AND SUBSTITUTIONS

    1. WHEREVER THE WORDS "APPROVED BY", "APPROVED EQUAL", "AS DIRECTED" OR SIMILARPHRASES ARE USED IN THE FOLLOWING SPECIFICATIONS, THEY SHALL BE UNDERSTOOD TOREFER TO THE OWNER AS THE APPROVING AGENCY. THE NAME OR MAKE OF ANY EQUIPMENTOR MATERIALS NAMED IN THIS SPECIFICATION (WHETHER OR NOT THE WORDS "OR APPROVEDEQUAL" ARE USED) SHALL BE KNOWN AS THE "STANDARD".

    2. THESE SPECIFICATIONS ESTABLISH QUALITY STANDARDS OF MATERIALS AND EQUIPMENT TO BEPROVIDED. SPECIFIC ITEMS ARE IDENTIFIED BY MANUFACTURER, TRADE NAME OR CATALOGDESIGNATION. THE CONTRACTOR SHALL SUBMIT THE BASE BID PRICE BASED UPON STANDARDSPECIFIED EQUIPMENT DESCRIBED HEREIN AND AS DETAILED ON DRAWINGS AND ASSOCIATEDCONTRACT DOCUMENTS. THESE SPECIFICATIONS ARE NOT TO BE CONSIDERED PROPRIETARY.THE CONTRACTOR MAY SUBMIT INFORMATION ON MATERIALS AND MANUFACTURERS (OTHERTHAN THOSE LISTED) FOR REVIEW BY THE OWNER, ARCHITECT AND ENGINEER NO LATER THANTEN (10) DAYS BEFORE BIDS ARE SUBMITTED. IN ADDITION, SAMPLES OF THE PROPOSEDEQUIPMENT MAY BE REQUIRED TO BE SUBMITTED TO THE ENGINEER FOR REVIEW NO LATER THANTEN (10) DAYS BEFORE BIDS ARE SUBMITTED. MANUFACTURERS OF PRODUCTS ACCEPTED BYTHE OWNER, ARCHITECT, AND ENGINEER WILL BE LISTED IN AN ADDENDUM TO THESPECIFICATIONS AS AN ACCEPTABLE SUBSTITUTION. EQUIPMENT ACCEPTED AS DETAILEDBELOW AND SHALL BE SHOWN AS A SEPARATE ADD OR DEDUCT PRICE TO BE FACTORED INTOTHE BASE PRICE BY THE ARCHITECT AND OWNER IF ACCEPTED.

    3. SHOULD THE CONTRACTOR PROPOSE TO FURNISH MATERIALS AND EQUIPMENT OTHER THANTHOSE SPECIFIED OR APPROVED BY ADDENDUM, SUBMIT A WRITTEN REQUEST FORSUBSTITUTION TO THE OWNER, ARCHITECT, AND ENGINEER AT BID OPENING. THE REQUESTSHALL BE AN ALTERNATE TO THE ORIGINAL BID; BE ACCOMPANIED WITH COMPLETE DESCRIPTIVE(MANUFACTURER, BRAND NAME, CATALOG NUMBER, ETC.) AND TECHNICAL DATA FOR ALLITEMS. FAILURE BY THIS CONTRACTOR TO SUBMIT THE REQUISITE DOCUMENTATION DETAILEDABOVE SHALE BE UNDERSTOOD BY THE OWNER, ARCHITECT AND ENGINEER TO INDICATE THATSUBSTITUTE EQUIPMENT WILL NOT BE PRESENTED BY THE CONTRACTOR FOR CONSIDERATION.SUCH SUBSTITUTIONS WILL NOT BE CONSIDERED AFTER THE BID OPENING DATE AND DELAY OFTHE PROJECT WILL NOT BE PERMITTED FOR FURTHER INSPECTION AND EVALUATION AFTER THISDATE.

    4. WHERE SUCH SUBSTITUTIONS ALTER THE DESIGN OR SPACE REQUIREMENTS INDICATED ON THEDRAWINGS, INCLUDE ALL ITEMS OF COST FOR THE REVISED DESIGN AND CONSTRUCTIONINCLUDING COST OF ALL ALLIED TRADES INVOLVED.

    5. ACCEPTANCE OR REJECTION OF THE PROPOSED SUBSTITUTIONS SHALL BE SUBJECT TOAPPROVAL OF THE OWNER, ARCHITECT, AND ENGINEER. IF REQUESTED, THE CONTRACTORSHALL SUBMIT (AT THEIR COST) INSPECTION SAMPLES OF BOTH THE SPECIFIED AND PROPOSEDSUBSTITUTE ITEMS.

    6. IN ALL CASES WHERE SUBSTITUTIONS ARE PERMITTED, THE CONTRACTOR SHALL BEAR ANY EXTRACOST OF EVALUATING THE QUALITY OF THE MATERIAL AND EQUIPMENT TO BE PROVIDED.

    G. TESTING AND PLACING IN SERVICE

    1. ANY MATERIAL OR EQUIPMENT FAILING A TEST SHALL BE REPAIRED OR REPLACED AT THECONTRACTOR'S EXPENSE.

    2. TESTS SHALL INCLUDE THE FOLLOWING:

    a. MEASURE THE LOAD ON EACH PHASE OF THE MAIN SERVICE AND EACH PHASE OF EVERY FEEDERUNDER FULL BUILDING LOAD CONDITIONS FOR 48 HOURS DURING REGULAR BUSINESS HOURS.

    b. MEASURE THE NO-LOAD AND FULL-LOAD VOLTAGES (PHASE TO PHASE, PHASE TO NEUTRAL ANDPHASE TO GROUND FOR EACH PHASE OF EACH SERVICE, OF EACH SEPARATELY DERIVED SYSTEM,AND AT EACH PANELBOARD OR TRANSFORMER).

    c. MEASURE THE GROUND RESISTANCE OF THE MAIN SERVICE GROUNDING ELECTRODE AND THEGROUND RESISTANCE OF EACH SEPARATELY DERIVED SYSTEM'S GROUNDING ELECTRODE.

    d. MAKE INSULATION RESISTANCE TESTS ON ALL DRY TYPE TRANSFORMERS AND MOTORS.

    H. INTERFERENCES

    1. BEFORE THE INSTALLATION OF ANY ITEM BEGINS, THE ELECTRICAL CONTRACTOR SHALL CAREFULLYASCERTAIN THAT IT DOES NOT INTERFERE WITH CLEARANCES FOR THE ERECTION OF FINISH BEAMS,COLUMNS, PILASTERS, WALLS OR OTHER STRUCTURAL OR ARCHITECTURAL MEMBERS AS SHOWN ONTHE ARCHITECTURAL DRAWINGS. IF ANY WORK IS INSTALLED AND THE ARCHITECTURAL DESIGNCANNOT BE FOLLOWED, THIS CONTRACTOR SHALL, AT THEIR OWN EXPENSE, MAKE CHANGES IN THEWORK AS DIRECTED BY THE ARCHITECT TO PERMIT THE COMPLETION OF THE ARCHITECTURAL WORK INACCORDANCE WITH DRAWINGS AND SPECIFICATIONS.

    2. IT SHALL BE THE DUTY OF THIS CONTRACTOR TO REPORT ANY INTERFERENCES BETWEEN THISCONTRACTORS WORK AND THAT OF ANY OF THE OTHER CONTRACTORS AS SOON AS THEY AREDISCOVERED. THE ARCHITECT SHALL DETERMINE WHICH EQUIPMENT WILL BE RELOCATED,REGARDLESS OR WHICH WAS INSTALLED FIRST. THE DECISION WILL BE FINAL.

    I. QUALITY ASSURANCE

    1. ALL PRODUCTS SHALL BE NEW AND OF THE TYPE AND QUALITY SPECIFIED. WHERE MATERIAL,EQUIPMENT, APPARATUS OR OTHER PRODUCTS ARE SPECIFIED BY MANUFACTURER, BRAND NAME,TYPE OF CATALOG NUMBER, SUCH DESIGNATION SHALL ESTABLISH THE STANDARDS OF THE DESIREDQUALITY AND STYLE. IT IS THE INTENT OF THESE SPECIFICATIONS TO ESTABLISH A STANDARD OFQUALITY OF MATERIALS AND EQUIPMENT INSTALLED.

    J. NAMEPLATES

    1. CENTRAL: FURNISH AND MOUNT ON EACH PANELBOARD, SWITCHBOARD (INCLUDING BRANCHSWITCHES), LARGE JUNCTION BOX, SAFETY SWITCH, STARTER, REMOTE CONTROL, PUSH BUTTONSTATION, AND ALL SIMILAR CONTROLS, A NAMEPLATE DESCRIPTIVE OF THE EQUIPMENT OREQUIPMENT CONTROLLED.

    2. PROVIDE BLACK AND WHITE NAMEPLATES CONSTRUCTED FROM LAMINATED PHENOLIC WITH A WHITECENTER CORE. LETTERS SHALL BE ENGRAVED IN THE PHENOLIC TO FORM WHITE LETTERS 3/8" HIGH.FASTEN THE NAMEPLATES WITH SCREWS AND AN ADHESIVE TYPE FASTENER.

    K. MOUNTING ACCESSORIES

    1. THIS CONTRACTOR SHALL FURNISH AND INSTALL ALL ANGLE IRON, CHANNEL IRON, RODS, SUPPORTS,HANGERS, CONCRETE OR PLYWOOD REQUIRED TO INSTALL, MOUNT AND SUPPORT ANY ELECTRICALEQUIPMENT OR DEVICE CALLED FOR ON THE PLANS.

    2. SUPPORTING MATERIAL SHALL BE COMPLETE WITH HANGARS, CONNECTORS, BOLTS, CLAMPS ANDNECESSARY ACCESSORIES TO MAKE A COMPLETE INSTALLATION. SUPPORTING MATERIAL SHALL BEGALVANIZED, PAINTED OR OTHERWISE SUITABLY FINISHED. PRODUCTS BY BINKLEY, STEEL CITY ORRACO WILL BE ACCEPTABLE.

    3. ALL SURFACE-MOUNTED EQUIPMENT ON BLOCK WALLS SHALL BE MOUNTED ON 3/4" PLYWOODBACKBOARD. ALL FLOOR MOUNTED EQUIPMENT SHALL BE INSTALLED ON A 4" HIGH CONCRETEHOUSEKEEPING PAD.

    L. EXECUTION

    1. THE ELECTRICAL WORK FOR CONSTRUCTION PURPOSES SHALL CONFORM TO ALL FEDERAL (OSHA),STATE, ALL SPECIFIC SAFETY REQUIREMENTS AND THE REQUIREMENTS OF THE CURRENT EDITION OFTHE NEC.

    2. CHECK THE HVAC AND PLUMBING SPECIFICATIONS FOR ELECTRICAL REQUIREMENTS AND INCLUDE THESAME IN THE CONTRACT COST.

    3. EQUIPMENT CONNECTIONS, STARTERS, DISCONNECT SWITCHES, CONTROL TRANSFORMERS ANDPUSHBUTTON STATIONS FOR THE EQUIPMENT FURNISHED BY THE OWNER OR UNDER A SEPARATECONTRACT SHALL BE INSTALLED AND CONNECTED UNDER THIS DIVISION, AS INDICATED ON THECONTRACT DRAWINGS.

    4. ALL CUTTING, PATCHING, EXCAVATING, BACKFILLING AND CONCRETE WORK RELATED TO THISCONTRACT WILL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR. THIS CONTRACTORSHALL ASSUME THE RESPONSIBILITY OF PROVIDING THE SLEEVES, CHASES AND OPENINGSNECESSARY FOR THE ELECTRICAL INSTALLATION AND FOR THEIR REPAIR IN AN ACCEPTABLE MANNER,AS DETERMINED BY THE ARCHITECT. ALL HOLES SHALL BE CORE DRILLED. PROVIDE FIRE STOP IN ALLOPENINGS CREATED THROUGH FIRE-RATED WALLS, FLOORS OR CEILINGS.

    5. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL REQUIRED ACCESS PANELSNECESSARY FOR THIS WORK. COORDINATE WITH ARCHITECT PRIOR TO INSTALLATION.

    M. MATERIALS AND QUALITY OF WORK

    1. ALL WORK SHALL BE INSTALLED IN A PRACTICAL AND PROFESSIONAL MANNER, BY MECHANICSSKILLED IN THE SEVERAL TRADES NECESSARY.

    2. ALL MATERIALS SHALL BE NEW AND FREE FROM DEFECTS AND SHALL BE THE BEST OF THEIRSEVERAL KINDS UNLESS SPECIFIED OR INDICATED ON THE DRAWINGS TO THE CONTRARY.

    3. DURING EACH PHASE AND AT THE COMPLETION OF THE CONSTRUCTION, THIS CONTRACTOR SHALLREMOVE ALL DEBRIS AND EXCESS MATERIALS CAUSED BY THIS WORK. THIS CONTRACTOR SHALLLEAVE THE AREA OF OPERATION BROOM CLEAN.

    4. ALL ELECTRICAL EQUIPMENT SHALL BEAR THE UNDERWRITERS LABORATORIES LABEL OR ETL LABEL.

    5. THIS CONTRACTOR SHALL GUARANTEE THE QUALITY OF WORK AND MATERIALS (EXCEPT LAMPS) FORA PERIOD OF ONE YEAR FROM THE DATE OF THE BUILDING OPENING AND LEAVE THE WORK INPERFECT ORDER AT THE COMPLETION. SHOULD DEFECTS DEVELOP WITHIN THE GUARANTEE PERIOD,THE CONTRACTOR SHALL, UPON NOTICE OF THE SAME, REMEDY THE DEFECTS AND HAVE ALLDAMAGES TO OTHER WORK OR FURNISHINGS CAUSED BY THE REPAIRS CORRECTED AT THISCONTRACTORS EXPENSE TO THE CONDITION BEFORE SUCH DAMAGE.

    N. SCOPE OF WORK

    1. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIAL, STORAGE, UNPACKING ANDPLACEMENT; TO INCLUDE BUT NOT LIMITED TO, THE FOLLOWING ITEMS:

    a. COMPLETE POWER DISTRIBUTION SYSTEM INCLUDING ALL PANELS, TRANSFORMERS, AND FEEDERSb. COMPLETE BRANCH CIRCUIT WIRING SYSTEM.c. TEMPORARY ELECTRICAL POWER AND LIGHTING AS REQUIRED FOR CONSTRUCTION.d. TESTING OF ALL CABLES AND CIRCUIT WIRING AFTER INSTALLATION.e. WIRING DEVICES AND FLOOR BOXES.f. GROUNDING OF THE ELECTRICAL SYSTEM.

    O. TEMPORARY SERVICE

    1. THE ELECTRICAL CONTRACTOR SHALL FURNISH, INSTALL AND REMOVE AS REQUIRED ALL TEMPORARYPOWER AND TEMPORARY LIGHTING IN ALL AREAS AND INDIVIDUAL ROOMS WHEN NEEDED BY THEINDIVIDUAL TRADES IN THE PERFORMANCE OF THEIR WORK. THIS CONTRACTOR SHALL PROVIDE AMINIMUM OF TWENTY (20) FOOTCANDLES OF ILLUMINATION FOR TEMPORARY LIGHTING. ANYADDITIONAL LIGHTING REQUIRED BY INDIVIDUAL TRADES SHALL BE PROVIDED BY THE INDIVIDUALTRADES INCLUDING POWER FOR THE LIGHTING. THE ELECTRICAL WORK FOR CONSTRUCTIONPURPOSES SHALL CONFORM TO ALL FEDERAL (OSHA), STATE, SPECIFIC SAFETY REQUIREMENTS, ASWELL AS, THE REQUIREMENTS OF THE NATIONAL ELECTRIC CODE AND NATIONAL ELECTRICAL SAFETYCODE. THE ELECTRICAL CONTRACTOR SHALL OBTAIN AND PAY FOR ALL REQUIRED APPLICATIONS,PERMITS AND INSPECTIONS PERTAINING TO THIS WORK. THIS COST SHALL BE INCLUDED IN THECONTRACTOR'S PRICE.

  • DATE

    REVISIONS

    NO.

    DESIGNED:

    DRAWN:

    DATE: 2-20-18

    CHECKED:

    SCALE: AS SHOWN

    800 Allegheny Avenue Pittsburgh, Pennsylvania 15233

    DRAWING NUMBER:

    HOMEWOOD - BRUSHTON CENTER -

    701 N HOMEWOOD AVE, PITTSBURGH PA. 15208

    ELECTRICAL SERVICE REPLACEMENT

    COMMUNITY COLLEGE OF ALLEGHENY COUNTY

    ASE PROJ. NUMBER: - 1741119

    CCAC PROJ. NO.: - 13-CO-003a7a

    NA

    HT

    PROFESSIONAL

    DAVID C. PRICE

    N

    P

    NE

    L

    No. PE081572

    YS V

    ENGINEER

    NOM

    MO

    C

    L

    REGISTERED

    EW A

    AI

    FO

    MWM

    E003

    MWM

    DEB

    ELECTRICAL SPECIFICATIONS

    ELECTRICAL SPECIFICATIONS

    P. RACEWAYS

    1. ALL WIRE SHALL BE RUN IN ACCORDANCE WITH CODE IN CORROSION RESISTANT, RIGID, THREADED,METAL CONDUIT OR ELECTRICAL METALLIC TUBING (EMT) OR METAL CLAD (MC) CABLING UNLESSOTHERWISE SPECIFICALLY STATED HEREIN.

    a. CONDUIT IN EXTERIOR WALLS, BELOW FLOOR SLAB, OR UNDERGROUND SHALL BE RIGID,THREADED, GALVANIZED, HEAVY WALL TYPE.

    b. CARLON PVC TYPE 40 HEAVY WALL CONDUIT WITH GROUND WIRE MAY BE USED BELOW FLOORSLAB OR UNDERGROUND IN LIEU OF RIGID, THREADED, GALVANIZED CONDUIT. PVC 40 CONDUITSHALL NOT BE RUN IN OR ABOVE FLOOR SLAB. PVC CONDUIT SHALL TERMINATE BELOW FLOORSLAB WITH RIGID, THREADED METAL CONDUIT ADAPTER. CONDUIT ABOVE SLAB SHALL BE METAL.

    c. CONDUIT RUN EXPOSED TO THE WEATHER SHALL BE HEAVY WALL, METAL THREADED TYPE.

    2. CONDUIT SIZE SHALL BE 3/4" MINIMUM UNLESS NOTED OTHERWISE.

    3. CONDUIT SHALL BE SECURELY FASTENED IN PLACE.

    4. ALL CONDUIT SHALL BE CONCEALED IN WALLS, FLOORS AND CEILINGS WHEREVER POSSIBLE.EXPOSED CONDUIT IN FINISHED AREAS WILL NOT BE PERMITTED. EXPOSED CONDUIT WILL BEPERMITTED IN UNFINISHED AREAS WITH THE SPECIFIC APPROVAL OF THE ARCHITECT.

    5. USE FLEXIBLE CONDUIT FOR THE CONNECTION TO THE RECESSED OR SEMI-RECESSED LIGHTINGFIXTURES (6' LENGTH MAXIMUM). USE LIQUID TIGHT METAL CONDUIT FOR ALL CONNECTIONS TOMOTORS AND OTHER EQUIPMENT SUBJECT TO VIBRATION AND IN AREAS SUBJECT TO MOISTURE.

    6. USE WATERTIGHT JOINTS WITH BURIED AND CONCRETE ENCASED CONDUIT. ALL BURIED CONDUITSOUTSIDE OF BUILDINGS SHALL HAVE A MINIMUM OF 24" OF COVER. METAL CONDUITS BURIED INEARTH SHALL BE PAINTED WITH TWO COATS OF HEAVY ASPHALTUM PAINT.

    7. SUPPORT RUNS OF CONDUIT AS DETAILED IN THE APPROPRIATE TABLE OF THE NATIONAL ELECTRICALCODE.

    8. INSTALL EXPOSED RUNS OF CONDUIT AND CONDUIT ABOVE LAY-IN CEILINGS PARALLEL ORPERPENDICULAR TO THE WALLS, STRUCTURAL MEMBERS OF INTERSECTIONS OF VERTICAL PLANESAND CEILINGS. PROVIDE RIGHT ANGLE TURNS USING FITTINGS OR SYMMETRICAL BENDS. SUPPORTCONDUITS WITHIN 1' OF ALL CHANGES INDIRECTION.

    9. IF A CONDUIT IS SUSPENDED, IT SHALL BE SUPPORTED ON TRAPEZE HANGERS WHICH USE"ALL-THREAD" RODS FROM THE STRUCTURAL STEEL. THE USE OF CEILING SUPPORT WIRE OR SIMILARMATERIAL WILL NOT BE ACCEPTED.

    10. INSTALL EMPTY CONDUIT FOR FUTURE USE AS INDICATED ON THE DRAWINGS. CONDUIT SHALL BECOMPLETE WITH JETLINE OR PULL ROPE, JUNCTION/OUTLET BOXES, TILE RINGS AND APPROPRIATECOVER PLATES.

    11. PROVIDE PITCHPOCKETS WHERE CONDUITS PENETRATE THE ROOF.

    12. THREAD LUBRICATION/SEALANT IS REQUIRED ON OUTDOOR AND UNDERGROUND THREADED METALJOINTS.

    13. INSTALL FIRE SEAL FITTINGS WHERE CONDUITS PENETRATE CONCRETE FLOOR SLABS, MASONRYWALLS, OR CEILINGS REQUIRED TO BE FIRE RATED.

    14. HORIZONTAL PORTION OF CONDUIT EXPOSED ON THE ROOF AND FEEDING EQUIPMENT SHALL NOT BEMORE THAN 5'-0" UNLESS THE WRITTEN APPROVAL FROM ARCHITECT OR ENGINEER IS OBTAINED.

    Q. PULL AND JUNCTION BOXES

    1. INSTALL PULL AND JUNCTION BOXES WHERE SHOWN ON THE DRAWINGS, AND WHERE REQUIRED FORCHANGES IN DIRECTION, AT JUNCTION POINTS AND TO FACILITATE WIRE PULLING. FURNISH BOX SIZESIN ACCORDANCE WITH NEC UNLESS LARGER BOXES ARE INDICATED ON THE DRAWINGS.

    2. PROVIDE STEEL BOXES AND REMOVABLE COVERS OF CODE GAUGE, HOT ROLLED SHEET STEEL, HOTDIPPED GALVANIZED INSIDE AND OUTSIDE, FOR ABOVE GROUND WORK. FURNISH WEATHERPROOFBOXES WHEN INSTALLED ABOVE GROUND OUTSIDE.

    3. PROVIDE CAST IRON BOXES, HOT DIPPED GALVANIZED INSIDE AND OUTSIDE WHERE SHOWN ON THEDRAWINGS. FURNISH REMOVABLE COVERS WITH GASKETS AND STAINLESS STEEL, BRASS, OR BRONZESCREWS.

    4. PROVIDE CONCRETE BOXES FOR UNDERGROUND WORK UNLESS OTHERWISE INDICATED ON THEDRAWINGS. FURNISH STEEL FRAMES AND COVERS WITH THE COVER ATTACHED TO THE FRAME WITHHEXAGON HEAD, BRASS OR BRONZE CAP SCREWS, 3/8" IN DIAMETER. PROVIDE A RUBBER GASKET FORSEALING BETWEEN THE COVER AND THE FRAME. PAINT THE COVER WITH TWO COATS OF HEAVYASPHALTUM.

    R. OUTLET BOXES

    1. USE SHEET STEEL BOXES, ZINC COATED OR CADMIUM PLATED, FOR CONCEAL INTERIOR WORK.

    2. USE CAST BOXES, ZINC-CADMIUM FINISH MALLEABLE IRON, FOR EXPOSED INTERIOR WORK, AND FOREXPOSED OR CONCEALED WORK IN WET, DAMP OR EXTERIOR LOCATIONS. CAST BOXES SHALL BESERIES FD BY CROUSE HINDS OR APPLETON.

    3. WALL BOX SIZES (MINIMUM) SHALL BE 4" SQUARE X 2-1/2" DEEP WHERE WALL CONSTRUCTION PERMITS.WHERE WALL CONSTRUCTION DICTATES, THE WIDTH MAY BE REDUCED TO 2-1/8" OR 1-1/2" UNDERSPECIAL CONDITIONS.

    4. FIXTURE OUTLETS IN CEILING (MINIMUM) SHALL BE 4" OCTAGONAL X 1-1/2" DEEP (4-11/16 OCTAGONAL X2-1/2" DEEP WHERE REQUIRED TO ACCOMMODATE LARGER CONDUIT OR LARGER NUMBER OF WIRES).

    5. GANG BOXES SHALL BE ONE PIECE (MINIMUM), 2-1/8" DEEP.

    6. PROVIDE CAST IRON, CONCRETE-TITE FLOOR BOXES WITH ADJUSTABLE COVERS SET FLUSH AND LEVELWITH THE FINISHED FLOOR, WITH OUTLETS AS INDICATED ON THE DRAWINGS. PROVIDE HUBBELL#8-2400, 4200, OR 4300 SERIES BOXES WITH LEVELING SCREWS. FLUSH TYPE COVERS ANDOPENINGS TO SERVE OUTLETS USED. FURNISH FLUSH CAPS FOR CLOSING OFF BOX WHEN NOT IN USE.

    7. FLUSH MOUNT BOXES IN ALL FINISHED WALLS, INSTALL THE PLASTER RINGS IN DRYWALLEDPLASTERED WALLS AND RAISED COVERS AS REQUIRED IN WALLS WITH OTHER FINISHES SO THAT THECOVER PLATES FIT TIGHTLY AGAINST BOXES OR RINGS. 3/16" MAXIMUM GAPS ARE ALLOWED FORNONCOMBUSTIBLE WALLS.

    8. ADJUST LOCATIONS OF OUTLETS IN MASONRY OR TILE CONSTRUCTION TO OCCUR IN THE NEARESTJOINT TO THE HEIGHT SPECIFIED. HEIGHTS SHALL MEET ADA REQUIREMENTS.

    9. SUPPORT ALL BOXES TO MAINTAIN PROPER ALIGNMENT AND RIGIDITY.

    10. CLEAN BOXES OF ALL FOREIGN MATTER PRIOR TO THE INSTALLATION OR WIRING OR DEVICES.

    11. MOUNTING HEIGHTS ON THE DRAWING ARE TO THE CENTERLINE OF THE BOXES UNLESS OTHERWISENOTED.

    S. WIRE AND CABLE UNITS

    1. COLOR CODE CONDUCTORS (EXCEPT CONTROL AND INSTRUMENTATION CONDUCTORS) AS FOLLOWS: 208/120 VOLT SYSTEM PHASE A BLACK PHASE B RED PHASE C BLUE NEUTRAL WHITE GROUND GREEN

    a. #12 AND #10 CONDUCTORS SHALL HAVE CONTINUOUS INSULATION COLOR, AS LISTED ABOVE.b. COLOR CODE CONDUCTORS LARGER THAN ABOVE, WHICH DO NOT HAVE CONTINUOUS INSULATION

    COLOR BY APPLICATION OF AT LEAST TWO LAPS OF COLORED TAPE ON EACH CONDUCTOR AT ALLPOINTS OF ACCESS INCLUDING JUNCTION BOXES. COLOR TAPE SHALL BE THE EQUAL OF 3MPRODUCTS SCOTCH #35.

    c. CONDUCTORS SHALL BE SOFT ANNEALED COOPER INSULATED FOR 600 VOLTS UNLESSSPECIFICALLY INDICATED OTHERWISE. ALUMINUM CONDUCTORS ARE NOT ALLOWED ON THISPROJECT.

    2. INSULATION TYPE SHALL BE TYPE THW FOR WIRE SIZES #8 AWG AND LARGER AND THWN FOR #10 AWGAND SMALLER. THHN SHALL NOT BE USED IN WET OR DAMP LOCATIONS.

    3. FLEXIBLE CORD SHALL BE HEAVY DUTY TYPE SO WITH AN EQUIPMENT GROUND CONDUCTOR INADDITION TO THE CURRENT CARRYING CONDUCTORS.

    4. PROVIDE #12 CONDUCTORS, UNLESS OTHERWISE INDICATED.

    a. CONTROL CONDUCTORS SHALL BE #14 MINIMUM FOR NEC CLASS 1 AND #16 FOR NEC CLASS 11.

    5. CONDUCTORS #8 AWG AND LARGER SHALL BE STRANDED.

    6. CONDUCTORS #10 AWG AND SMALLER SHALL BE SOLID.

    7. INSTALL WIRING IN CONDUIT.

    8. CONNECT #10 AND SMALLER WIRES WITH CONSTANT PRESSURE EXPANDABLE SPRING TYPECONNECTORS, "SCOTCHLOK" BY 3M OR B-CAP BY BUCHANAN.

    9. CONNECT #8 AND LARGER WIRES WITH COMPRESSION CONNECTORS OR SPLICES ASMANUFACTURERED BY BURNDY OR T&B.

    10. INSULATE SPLICING CONNECTORS TO AT LEAST 200% OF THE WIRE INSULATION. USE PRE-STRETCHEDTUBING CONNECTOR INSULATORS, 3M PST FOR #2 AND LARGER CONDUCTORS.

    11. PULL CONDUCTORS USING RECOGNIZED METHODS AND EQUIPMENT LEAVING AT LEAST 6" WIRE AT ALLJUNCTION BOXES FOR CONNECTIONS.

    a. CLEANOUT EACH CONDUIT SYSTEM BEFORE PULLING WIRE.

    12. FORM AND TIE ALL WIRING IN PANELBOARDS.

    13. THERE SHALL BE NO WIRENUT JOINTS OR SPLICES MADE INSIDE SWITCHBOARDS/PANELBOARDS.

    14. BRANCH CIRCUIT WIRE SIZES (AND CONDUITS) SHALL BE INCREASED FROM THOSE INDICATED ON THEPLANS TO PREVENT EXCESSIVE VOLTAGE DROP. BRANCH CIRCUITS SHALL BE INSTALLED WITH WIRESOF SUFFICIENT SIZE SO THAT VOLTAGE DROP BETWEEN THE PANEL AND THE LOADS DOES NOT EXCEEDLIMIT OF 2%.

    15. WIRE SIZES SHALL BE BASED ON THE 60°C. AMPACITIES FOR WIRE SIZES #14-1 AWG AND 75°CAMPACITIES FOR WIRE SIZES #1/0 AWG AND LARGER.

    16. CIRCUITS MAY BE MULTI-PLEXED IN CONDUIT PROVIDED WIRE IS PROPERLY DERATED AND CONDUITSIZED PER NEC. UNDER NO CIRCUMSTANCES SHALL MORE THAN NINE (9) CURRENT CARRYINGCONDUCTORS BE RUN IN A SINGLE CONDUIT. WIREMOLD SERVED BY MULTIPLE CIRCUITS SHALL BEWIRED WITH INDIVIDUAL SEPARATE NEUTRALS FOR EACH CIRCUIT.

    T. WIRING DEVICES

    1. WIRING DEVICE COLOR SHALL BE SELECTED BY ARCHITECT, UNLESS OTHERWISE INDICATED.

    2. PROVIDE TOTALLY ENCLOSED, 20 AMPERE, 120/277 VOLT QUIET A/C GENERAL USE SNAP SWITCHES.

    3. SWITCHES SHALL BE SPECIFICATION GRADE AS MANUFACTURED BY HUBBELL, P&S OR LEVITON.

    4. PROVIDE NEMA CONFIGURATION 5-20R DUPLEX 125 VOLT GROUNDING TYPE RECEPTACLES RATED FOR20 AMPERES UNLESS OTHERWISE NOTED ON THE DRAWINGS.

    5. RECEPTACLES SHALL BE SPECIFICATION GRADE AS MANUFACTURED BY HUBBELL, P&S OR LEVITON.

    6. RECEPTACLES REQUIRING AMPERAGES, VOLTAGES OR CONFIGURATIONS DIFFERENT FROM THE DUPLEXCONVENIENCE RECEPTACLES ABOVE SHALL BE AS INDICATED ON THE DRAWINGS.

    7. PROVIDE OTHER RECEPTACLES OF A QUALITY, MATERIAL AND CONSTRUCTION EQUAL TO THATSPECIFIED FOR DUPLEX CONVENIENCE RECEPTACLES.

    8. PROVIDE COVER OR DEVICE PLATES FOR OUTLET BOXES AS FOLLOWS UNLESS OTHERWISE NOTED:

    a. FINISHED AREAS: THERMOPLASTIC- COLOR TO MATCH DEVICEb. UNFINISHED AREAS: ZINC COATED SHEET METAL, ALUMINUM, OR CAST METAL AS APPROPRIATE FOR

    THE TYPE OF BOX.c. EXTERIOR AREAS: COPPER FREE ALUMINUM WITH GRAY, POWDER EPOXY FINISH, GASKET,

    WEATHERPROOF, CROUSE-HINDS 'WLRD' FOR DUPLEX RECEPTACLES AND WLRS FOR SINGLERECEPTACLES OR EQUAL.

    d. TELEPHONE, COMMUNICATION, AND SIGNAL OUTLET PLATES, SHALL MATCH THOSE USED FORRECEPTACLES AND SWITCHES. ALL OUTLET AND/OR JUNCTION BOXES SHALL BE COMPLETE WITH ACOVER PLATE BY THIS CONTRACTOR.

    e. WHERE DEVICES ARE GANGED, THEY SHALL BE INSTALLED UNDER A COMMON COVERPLATE.f. LOCATE THE SWITCHES APPROXIMATELY 4'-0" ABOVE THE FINISHED FLOOR ELEVATION OR NEAREST

    BLOCK COURSE (WITH IN ADA REQUIREMENTS) UNLESS OTHERWISE NOTED. THE LONG DIMENSIONOF THE SWITCHES SHALL BE VERTICAL.

    g. BRASS PLATE/RING FOR CARPET INSTALLATION

    9. LOCATE RECEPTACLES APPROXIMATELY 1'-6" ABOVE THE FINISHED FLOOR ELEVATION OR NEARESTBLOCK COURSE (WITH IN ADA REQUIREMENTS), UNLESS OTHERWISE NOTED. THE LONG DIMENSION OFTHE RECEPTACLE SHALL BE VERTICAL.

    U. SAFETY SWITCHES

    1. SAFETY SWITCHES SHALL BE THE ENCLOSED HEAVY-DUTY TYPE (TYPE HD) WITH QUICK-MAKE,QUICK-BREAK MECHANISM AND EXTERNAL PAD LOCKABLE OPERATING HANDLE.

    2. SAFETY SWITCHES SHALL BE RATED FOR 240 OR 600 VOLTS AS APPLICABLE. THEY SHALL BEHORSEPOWER RATED WHEN USED IN MOTOR CIRCUITS.

    3. SAFETY SWITCHES SHALL BE FUSIBLE OR NONFUSIBLE 2, 3 OR 4 POLE AS INDICATED ON THEDRAWINGS.

    4. SAFETY SWITCHES SHALL BE SINGLE THROW UNLESS OTHERWISE INDICATED ON DRAWINGS.

    5. ENCLOSURES SHALL BE NEMA 1 INDOORS AND NEMA 3R OUTDOORS UNLESS OTHERWISE INDICATED ONTHE DRAWINGS.

    6. MANUFACTURER SHALL BE SQUARE D, SIEMENS, OR EATON CUTLER-HAMMER. ALL SAFETY SWITCHESSHALL BE BY ONE MANUFACTURER.

    7. MOUNT THE SAFETY SWITCHES SECURELY BETWEEN 3' X 6' LEVELS ABOVE THE FLOOR UNLESSOTHERWISE NOTED IN THE DRAWINGS.

    8. SWITCHES ON BLOCK WALLS SHALL BE MOUNTED ON A 3/4" PLYWOOD BACKBOARD, WHERE LOCATEDINDOORS.

    V. GROUNDING

    1. GROUND ALL EQUIPMENT PER N.E.C.

    2. ALL CONDUITS SHALL CONTAIN A CODE SIZED GROUND WIRE SIZE PER NEC IN ADDITION TO THECONDUCTORS SHOWN ON THE PLANS. WHERE CIRCUIT CONDUCTORS ARE INCREASED IN SIZE FORVOLTAGE DROP, THE GROUND WIRE SIZE SHALL BE INCREASED PROPORTIONATELY.

    Y. PANELBOARDS1. PANELBOARDS SHALL BE ENCLOSED DEAD FRONT SAFETY TYPE WITH FEATURES AND RATINGS AS

    SCHEDULED ON DRAWINGS.

    2. PANELS KNOWN AS "LOAD CENTERS" ARE UNACCEPTABLE.

    3. MOLDED CASE CIRCUIT BREAKERS SHALL BE AS SCHEDULED ON THE DRAWINGS AND SPECIFIED IN THISDIVISION.

    4. ALL BUS BARS SHALL BE RECTANGULAR SOLID COPPER.

    5. SPACE, WHERE SHOWN IN PANEL SCHEDULES, DESIGNATES SPACE FOR FUTURE PROTECTIVE DEVICESAND SHALL INCLUDE BUS AND SUPPORT.

    6. INSTALL CABINETS SO THAT CENTER OF THE TOP BREAKER DOES NOT EXCEED 6'-6" ABOVE THEFINISHED FLOOR.

    7. ENTRIES ON DIRECTORY CARDS SHALL BE TYPED, COMPLETE AND ACCURATE.

    8. ALL BOLTED CONNECTIONS SHALL BE TORQUED IN ACCORDANCE WITH MANUFACTURERS STANDARDS.

    9. ELECTRICAL CONTRACTOR SHALL ARRANGE CIRCUITS AS NEAR AS POSSIBLE TO CIRCUIT NUMBERS ONTHE DRAWINGS. AT COMPLETION OF JOB, ELECTRICAL CONTRACTOR SHALL TAKE CURRENT READINGCHECKS OF RESPECTIVE PHASES. A MINIMUM OF CIRCUIT CONNECTIONS SHALL BE REARRANGED TOBALANCE, AS CLOSELY AS POSSIBLE, THE LOAD IN THE PANEL.

    10. ALL BREAKERS SHALL BE BOLT ON TYPE.

    11. PROVIDE (3) SPARE 1" CONDUITS INTO ACCESSIBLE CEILING WHERE PANELS ARE FLUSH MOUNTED.

    12. MANUFACTURER SHALL BE SQUARE D, GE, SIEMENS, OR EATON CUTLER-HAMMER.

    Z. FUSES1. THE CONTRACTOR SHALL FURNISH A COMPLETE SET OF FUSES FOR ALL SWITCHES, PLUS FUSIBLE

    EQUIPMENT FURNISHED BY OTHER TRADES. UNLESS OTHERWISE INDICATED ON THE DRAWINGS, THEFUSES SHALL BE OF THE FOLLOWING TYPE:

    a. FUSES 601 TO 600 AMPS SHALL BE UL CLASS. TRADE TYPE SHALL BE KRP-C AS MANUFACTUREDBY THE BUSSMAN COMPANY.

    b. FUSES 1/10 TO 600 AMPS SHALL BE UL CLASS RK1. TRADE TYPE SHALL BE LOW PEAK LPS-RK(600V) AND LPN-RK (250C) AS LET BOXE MANUFACTURED BY BUSSMAN COMPANY.

    c. ALL OTHER FUSES SHALL BE DUAL ELEMENT CURRENT LIMITING TYPE WITH 200,000 AMPERESSYMMETRICAL INTERRUPTING CAPACITY.

    2. FUSES SHALL BE MANUFACTURED BY BUSSMANN, FERRAZ-SHAWMUT OR RELIANCE.

    3. SPARE FUSES AMOUNTING TO A DUPLICATE SET OF EACH SIZE INSTALLED SHALL BE TURNED OVER TOTHE OWNER UPON COMPLETION OF THE PROJECT. PROVIDE AND PLACE IN A SPARE FUSE CABINETSIMILAR TO BUSSMAN #SFC.

    4. THIS CONTRACTOR SHALL REPLACE ALL FUSES BLOWN DURING CONSTRUCTION.

    AA. FINAL COMMISSIONING1. THE ELECTRICAL CONTRACTOR SHALL PROVIDE A FULLY COMPLETE AND COMMISSIONED ELECTRICAL

    SERVICE. THIS SHALL INCLUDE BUT LIMITED TO THE FOLLOWING: OPERATIONAL TESTING OF THE ENTIRESWITCHGEAR LINEUP, SPLICING OF ALL EXISTING FEEDERS, TIE INTO BUILDING METASYS SYSTEM.

  • EXISTING PANEL 'A'SHALL REMAIN

    1

    3

    2

    1

    45

    6

    DEMO CODED NOTES:

    1. DISCONNECT AND REMOVE EXISTING DISCONNECT SWITCH IN THEBASEMENT. INTERCEPT EXISTING FEEDER AND EXTEND TO BREAKERIN SWITCHBOARD. REFER TO ELECTRICAL RISER DIAGRAM E301 FORFURTHER INFORMATION.

    2. INTERCEPT EXISTING SERVICE ENTRANCE DISCONNECT SWITCH.

    3. DISCONNECT AND REMOVE EXISTING PANELS. INTERCEPTEXISTING FEEDER(S) AND EXTEND TO BREAKER IN SWITCHBOARD.REFER TO ELECTRICAL RISER DIAGRAM E301 FOR FURTHERINFORMATION.

    4. EXISTING WIREWAY SECTIONS AT BOTTOM AND AT HIGHER LEVELSHALL BE DISCONNECTED AND REMOVED.

    5. EXISTING C.T. CABINET SHALL BE DISCONNECTED AND REMOVED.CONTACT UTILITY COMPANY PRIOR TO REMOVAL FOR SEQUENCINGPURPOSES.

    6. EXISTING TRANSOCKET CABINET SHALL BE DISCONNECTED ANDREMOVED. CONTACT UTILITY COMPANY PRIOR TO REMOVAL FORSEQUENCING PURPOSES.

    #

    DEMO GENERAL NOTES:

    1. THE CONTINUITY OF EXISTING CIRCUITS THAT MAY BEINTERRUPTED BY THE ALTERATION, EVEN THOUGH THEY MAY NOTBE INDICATED ON THE DRAWINGS, SHALL BE MAINTAINED.

    2. ELECTRICAL EQUIPMENT, FIXTURES, AND/OR DEVICES SCHEDULEDTO REMAIN OR BE RELOCATED THAT ARE DAMAGED DURINGDEMOLITION SHALL BE REPLACED WITH SIMILAR TYPE ASAPPROVED BY THE OWNER, AT NO ADDITIONAL CHARGE TO THEOWNER.

    3. INFORMATION SHOWN ON THIS DRAWING PERTAINING TOEXISTING CONDITIONS HAS BEEN OBTAINED FROM AVAILABLEBUILDING DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAYOR MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL ORDIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR DETERMININGTHE ACTUAL EXISTING CONDITIONS PRIOR TO FABRICATION ORPERFORMANCE OF ANY WORK. SHOULD CONDITIONS BEDISCOVERED THAT PREVENT THE EXECUTION OF THE WORK ASINDICATED, THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THEARCHITECT IN WRITING AND AWAIT DIRECTION BEFORE PROCEEDINGWITH THE WORK.

    4. EXISTING ELECTRICAL CONNECTIONS ARE TO REMAIN FOR HVACEQUIPMENT THAT IS NOT BEING DEMOLISHED. REFER TOMECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION.

    5. THE ELECTRICAL CONTRACTOR SHALL REWORK ALL EXISTINGCONDUIT, WIRING AND/OR ELECTRICAL AND MECHANICAL DEVICESBEING DISTURBED BY THE SCOPE OF DEMOLITION WORK ASREQUIRED, RESTORING THE ITEMS TO THEIR FORMER EXISTINGOPERATING CONDITION.

    DATE

    REVISIONS

    NO.

    DESIGNED:

    DRAWN:

    DATE: 2-20-18

    CHECKED:

    SCALE: AS SHOWN

    800 Allegheny Avenue Pittsburgh, Pennsylvania 15233

    DRAWING NUMBER:

    HOMEWOOD - BRUSHTON CENTER -

    701 N HOMEWOOD AVE, PITTSBURGH PA. 15208

    ELECTRICAL SERVICE REPLACEMENT

    COMMUNITY COLLEGE OF ALLEGHENY COUNTY

    ASE PROJ. NUMBER: - 1741119

    CCAC PROJ. NO.: - 13-CO-003a7a

    NA

    HT

    PROFESSIONAL

    DAVID C. PRICE

    N

    P

    NE

    L

    No. PE081572

    YS V

    ENGINEER

    NOM

    MO

    C

    L

    REGISTERED

    EW A

    AI

    FO

    MWM

    E100

    MWM

    DEB

    BASEMENT ELECTRICAL DEMOLITION PLAN

    1

    E100BASEMENT ELECTRICAL DEMOLITION PLAN1/8" = 1'-0"

  • EXISTING PANEL 'A'SHALL REMAIN

    MAIN SERVICEENTRANCEDISCONNECTSWITCH

    1200 AMP SWITCHBOARD 'MSB'120/208V., 3Ø, 4W.

    PROVIDE (2) LED STRIP LIGHTING FIXTURES.LITHONIA MODEL #ZL1D L48 SMR 5000LM FST 12035K 80CRI WH ZACVH. SURFACE MOUNT FROMSTRUCTURAL MEMBER ABOVE.

    ST

    PROVIDE (3) LED STRIP LIGHTING FIXTURES.LITHONIA MODEL #ZL1D L48 SMR 5000LM FST 12035K 80CRI WH ZACVH. SURFACE MOUNT FROMSTRUCTURAL MEMBER ABOVE.

    PROVIDE DIGITAL TIMER SWITCH.SENSOR SWITCH CAT. # PTS 720 WH

    ST

    PROVIDE DIGITAL TIMER SWITCH.SENSOR SWITCH CAT. # PTS 720 WH

    SD

    SD

    EXISTING ELECTRICAL FEEDERS

    V

    STPROVIDE (1) LED STRIP LIGHTING FIXTURES.LITHONIA MODEL #ZL1D L48 SMR 5000LM FST 12035K 80CRI WH ZACVH. SURFACE MOUNT FROMSTRUCTURAL MEMBER ABOVE.

    EXISTING ELECTRICAL FEEDERS

    MGB

    TGB

    DATE

    REVISIONS

    NO.

    DESIGNED:

    DRAWN:

    DATE: 2-20-18

    CHECKED:

    SCALE: AS SHOWN

    800 Allegheny Avenue Pittsburgh, Pennsylvania 15233

    DRAWING NUMBER:

    HOMEWOOD - BRUSHTON CENTER -

    701 N HOMEWOOD AVE, PITTSBURGH PA. 15208

    ELECTRICAL SERVICE REPLACEMENT

    COMMUNITY COLLEGE OF ALLEGHENY COUNTY

    ASE PROJ. NUMBER: - 1741119

    CCAC PROJ. NO.: - 13-CO-003a7a

    NA

    HT

    PROFESSIONAL

    DAVID C. PRICE

    N

    P

    NE

    L

    No. PE081572

    YS V

    ENGINEER

    NOM

    MO

    C

    L

    REGISTERED

    EW A

    AI

    FO

    MWM

    E200

    MWM

    DEB

    BASEMENT ELECTRICAL PLAN

    1

    E200BASEMENT ELECTRICAL PLAN1/8" = 1'-0"

    2ND FLOOR

    ROOF

    CM

    EXISTINGFIRE

    ALARMPANEL

    SDF F SD SD E

    AV

    SD E

    AV

    ETRSD D

    ETR ETR ETR ETR ETR ETR ETR

    3

    E200PARTIAL FIRE ALARM RISER DIAGRAMNTS

    FIRE ALARM RISER NOTES:

    1. REFER TO FLOOR PLAN FOR QUANTITY AND LOCATION OFSYSTEM COMPONENTS. EXACT ARRANGEMENT AND QUANTITYOF DEVICES SHALL BE INDICATED ON THE SHOP DRAWINGS.PROVIDE COMPLETE RISER DIAGRAM AS PART OF SHOPDRAWINGS.

    2. PROVIDE WIRING PER EXISTING MANUFACTURER'SRECOMMENDATION.

    3. CANDELA RATING SHALL BE PER NFPA 72 REQUIREMENTS.

    4. ALL FIRE ALARM WIRING SHALL BE IN 3/4"C (MINIMUM). FIRERATED MC CABLE IS ACCEPTABLE. MC CABLE SHALL BECOLORED RED.

    5. DO NOT LOAD ANY CIRCUIT BEYOND 80% OF RATED CAPACITY.SUBMIT CALCULATIONS TO SUBSTANTIATE. ADD ADDITIONALCIRCUITS AS NECESSARY.

    6. PROVIDE CONDUIT SLEEVES WITH ESCUTCHEON PLATESWHERE WIRING PASSES THROUGH WALLS, FLOORS, ORCEILINGS.

    7. PROVIDE EXTENSION OF EXISTING FIRE ALARM CIRCUITSSERVING BASEMENT TO SUPPLY NEW FIRE ALARM DEVICES ASINDICATED ON PLAN. WHERE EXISTING CIRCUITS ARE NOT SIZEDTO ACCOMMODATE ADDITIONAL FIRE ALARM DEVICES, PROVIDENEW FIRE ALARM CIRCUIT TO SERVE FLOOR. CONTRACTOR SHALLCONSULT WITH MANUFACTURER ON EXPANDABILITY OF EXISTINGSYSTEM INCLUDING CIRCUITS AND EXISTING BATTERY CAPACITYTO OPERATE SYSTEM PER NFPA. WHERE REQUIRED TOACCOMMODATE NEW DEVICES, CONTRACTOR SHALL PROVIDENEW TRANSPONDERS, BATTERIES, ETC. TO FIRE ALARM SYSTEMTO SUPPORT FIRE ALARM EXPANSION AND OPERATE PER NFPAGUIDELINES.

    SD MM

    1ST FLOOR

    BASEMENT

    SDF F SD

    AV

    ETR ETR ETR ETR

    SD SD

    E

    ETR ETR

    CM SDF F SD SD E

    AV

    SD E

    AV

    ETRSD D

    ETR ETR ETR ETR ETR ETR ETR

    SD MM

    ETR ETR

    ETR ETR

    ETR ETR

    FIRE ALARM GENERAL NOTE FOR PERMIT - CITY OF PITTSBURGH:THE E.C. SHALL INCLUDE IN HIS BID, THE COST FOR AN INDEPENDENT THIRD PARTY PROFESSIONAL ENGINEER TO SIGN, DATE,AND SEAL ALL FIRE ALARM DOCUMENTS REQUIRED FOR A BUILDING PERMIT. THE FIRE ALARM DOCUMENTS INCLUDED WITHTHE E-SERIES DRAWINGS ARE PROVIDED FOR FIRE ALARM DESIGN INTENT WITHIN THE CITY OF PITTSBURGH. THE CITY OFPITTSBURGH WILL REQUIRE SIGNED/SEALED MANUFACTURER SHOP DRAWINGS (BY THE INDEPENDENT THIRD PARTY) FORPERMIT APPROVAL BEYOND THE DOCUMENTS CONTAINED IN THE E-SERIES DRAWINGS.

    THE FIRE ALARM SHOP DRAWINGS SHALL INCLUDE AT A MINIMUM BOTH FIRE ALARM FLOOR PLANS AND RISER DIAGRAM. EACHPLAN OR RISER SHALL INDICATE THE NUMBER AND TYPES OF FIRE ALARM DEVICES INSTALLED ON EACH CIRCUIT, DEVICEADDRESSES, CONDUCTOR TYPES AND SIZES, FIRE ALARM ZONES, PRIMARY AND SECONDARY POWER SUPPLIES (ASNECESSARY), AND ALL NEW FIRE ALARM DEVICES AS ADDED TO EXISTING CIRCUITS. DOCUMENTS SHALL ALSO CONTAINBATTERY AND VOLTAGE DROP CALCULATIONS.

    AutoCAD SHX Text~

    AutoCAD SHX Text~

    AutoCAD SHX Text~

    AutoCAD SHX Text~

    AutoCAD SHX Text~

    AutoCAD SHX Text~

    AutoCAD SHX Text~

    AutoCAD SHX Text~

    AutoCAD SHX Text~

    AutoCAD SHX Text~

    AutoCAD SHX Text~

    AutoCAD SHX Text~

    AutoCAD SHX Text~

    AutoCAD SHX Text~

    AutoCAD SHX Text~

    AutoCAD SHX Text~

  • EXISTING PANEL WITH 225 AMP MCB SHALLREMAIN. INTERCEPT EXISTING FEEDER SERVINGWIREWAY FROM EXISTING SWITCHBOARD INBASEMENT. ELECTRICAL CONTRACTOR SHALLVERIFY FUSE SIZE IN EXISTING DISCONNECTSWITCH AND PROVIDE BREAKER INSWITCHBOARD 'MSB' TO MATCH. PROVIDEFEEDER TO MATCH BREAKER SIZE.

    EXISTING PANEL 'D' SHALL REMAIN.INTERCEPT EXISTING FEEDER SERVINGPANEL FROM EXISTING SWITCHBOARDIN BASEMENT. THIS PANEL FEEDSTHRU TO PANEL 'G' ON 2ND FLOOR.MATCH EXISTING AIC RATINGS.

    EXISTING PANEL 'E' SHALL REMAIN.INTERCEPT EXISTING FEEDER SERVINGPANEL FROM EXISTING SWITCHBOARDIN BASEMENT. THIS PANEL FEEDSTHRU TO PANEL 'H' ON 2ND FLOOR.MATCH EXISTING AIC RATINGS.

    DATE

    REVISIONS

    NO.

    DESIGNED:

    DRAWN:

    DATE: 2-20-18

    CHECKED:

    SCALE: AS SHOWN

    800 Allegheny Avenue Pittsburgh, Pennsylvania 15233

    DRAWING NUMBER:

    HOMEWOOD - BRUSHTON CENTER -

    701 N HOMEWOOD AVE, PITTSBURGH PA. 15208

    ELECTRICAL SERVICE REPLACEMENT

    COMMUNITY COLLEGE OF ALLEGHENY COUNTY

    ASE PROJ. NUMBER: - 1741119

    CCAC PROJ. NO.: - 13-CO-003a7a

    NA

    HT

    PROFESSIONAL

    DAVID C. PRICE

    N

    P

    NE

    L

    No. PE081572

    YS V

    ENGINEER

    NOM

    MO

    C

    L

    REGISTERED

    EW A

    AI

    FO

    MWM

    E201

    MWM

    DEB

    FIRST FLOOR ELECTRICAL PLAN

    1

    E201FIRST FLOOR ELECTRICAL PLAN1/8" = 1'-0"

  • EXISTING PANEL 'G'

    EXISTING PANEL 'H'

    EXISTING PANEL 'J' SHALL REMAIN.INTERCEPT EXISTING FEEDER SERVINGPANEL FROM EXISTING SWITCHBOARDIN BASEMENT.

    DATE

    REVISIONS

    NO.

    DESIGNED:

    DRAWN:

    DATE: 2-20-18

    CHECKED:

    SCALE: AS SHOWN

    800 Allegheny Avenue Pittsburgh, Pennsylvania 15233

    DRAWING NUMBER:

    HOMEWOOD - BRUSHTON CENTER -

    701 N HOMEWOOD AVE, PITTSBURGH PA. 15208

    ELECTRICAL SERVICE REPLACEMENT

    COMMUNITY COLLEGE OF ALLEGHENY COUNTY

    ASE PROJ. NUMBER: - 1741119

    CCAC PROJ. NO.: - 13-CO-003a7a

    NA

    HT

    PROFESSIONAL

    DAVID C. PRICE

    N

    P

    NE

    L

    No. PE081572

    YS V

    ENGINEER

    NOM

    MO

    C

    L

    REGISTERED

    EW A

    AI

    FO

    MWM

    E202

    MWM

    DEB

    SECOND FLOOR ELECTRICAL PLAN

    1

    E202SECOND FLOOR ELECTRICAL PLAN1/8" = 1'-0"

  • DATE

    REVISIONS

    NO.

    DESIGNED:

    DRAWN:

    DATE: 2-20-18

    CHECKED:

    SCALE: AS SHOWN

    800 Allegheny Avenue Pittsburgh, Pennsylvania 15233

    DRAWING NUMBER:

    HOMEWOOD - BRUSHTON CENTER -

    701 N HOMEWOOD AVE, PITTSBURGH PA. 15208

    ELECTRICAL SERVICE REPLACEMENT

    COMMUNITY COLLEGE OF ALLEGHENY COUNTY

    ASE PROJ. NUMBER: - 1741119

    CCAC PROJ. NO.: - 13-CO-003a7a

    NA

    HT

    PROFESSIONAL

    DAVID C. PRICE

    N

    P

    NE

    L

    No. PE081572

    YS V

    ENGINEER

    NOM

    MO

    C

    L

    REGISTERED

    EW A

    AI

    FO

    MWM

    E301

    MWM

    DEB

    ELECTRICAL RISER DIAGRAM

    BASEMENT

    POWER RISER CODED NOTES:P1. INTERCEPT EXISTING 30A/3-POLE FEED SERVED FROM EXISTINGLIGHTING/POWER PANEL BEING DEMOLISHED AND RE-FEED FROM'MSB'. PROVIDE 4#10 + 1#10G - 3/4"C BRANCH CIRCUITING. VERIFYLOCATION OF BRANCH CIRCUIT PRIOR TO DEMOLITION.

    P2. PROVIDE SQUARE 'D' EM3500 SERIES METER OR APPROVEDEQUAL MONITORING DEVICE (BACNET) COMPATIBLE WITH CAMPUSMETERING SYSTEM TO MONITOR FEEDER BREAKER. PROVIDE ALLC.T'S REQUIRED FOR METERING OF BREAKER. PROVIDE TIE INTOEXISTING DATA BAS AUTOMATED SYSTEM.

    P3. PROVIDE SQUARE 'D' EM3500 SERIES METER OR APPROVEDEQUAL MONITORING DEVICE (BACNET) COMPATIBLE WITH CAMPUSMETERING SYSTEM TO MONITOR MAIN SERVICE ENTRANCEDISCONNECT. PROVIDE ALL C.T'S REQUIRED FOR METERING OFBREAKER. PROVIDE TIE INTO EXISTING DATA BAS AUTOMATEDSYSTEM.

    P4. VERIFY FEEDER SIZE AND LOCATION FOR EXISTING FEEDERSERVING BARBER SHOP AS INDICATED ON DRAWING E201.

    1ST FLOOR

    #

    EXISTING UTILITY POLEAND 3-PHASETRANSFORMERS

    UTILITYC.T. CABINET

    PANELA

    125A MLO

    EXISTING

    208/120V3Ø., 4W

    'MSB'1200 AMP MLO

    208/120V., 3Ø, 4W.65KAIC1200 AMP SERVICEENTRANCE RATED

    DISCONNECTSWITCH

    208/120V., 3Ø,4W. 65KAIC

    EXISTINGAIR COOLED CHILLER

    PANELJ

    100A

    EXISTING

    208/120V3Ø., 4W

    PANELG

    XXXA

    EXISTING

    208/120V3Ø., 4W

    PANELH

    XXXA

    EXISTING

    208/120V3Ø., 4W

    EXISTINGELEVATOR

    EXISTINGELEVATOR

    CONTROLLER

    EXISTING ROOF HVACEQUIPMENT

    (4) #2 + (1) #8G - 1 1/4"C.

    2 SETS EACH WITH(3) 250KCMIL + (1) #2G - 2"C.

    3 SETS EACH WITH(4) 600KCMIL +(1) #3/0G - 4"C.

    (4) #1 + (1) #6G - 1 1/2"C.

    INTERCEPT EXISTING FEEDERS ANDEXTEND TO SWITCHBOARD 'MSB'.PROVIDE JUNCTION BOXES FOR SPLICING.

    INTERCEPT EXISTING FEEDERS AND EXTEND TO SWITCHBOARD'MSB' AND TERMINATE ON BREAKERS SCHEDULED.VERIFY IF EXISTING FEEDERS THAT ARE TO BE INTERCEPTEDHAVE BEEN INCREASED IN SIZE TO ACCOMMODATE FORVOLTAGE DROP. IF THEY WERE INCREASED COMPARED TOWHAT IS INDICATED ON RISER, THEN THE ELECTRICALCONTRACTOR SHALL PROVIDE FEEDER SIZE TO MATCHEXISTING.

    (4) #2 + (1) #8G - 1 1/4"C.

    (4) #3/0 + (1) #6G - 2"C.

    1

    E301ELECTRICAL RISER DIAGRAMNTS

    1200A/3P

    EXISTING SERVICE ENTRANCE FEEDERS SHALL BE DISCONNECTEDFROM EXISTING WIREWAYS AND CONNECTED TO SERVICEENTRANCE DISCONNECT SWITCH. PROVIDE TERMINATIONS OFEXISTING SERVICE ENTRANCE CONDUCTORS TO SERVICE ENTRANCERATED DISCONNECT SWITCH. COORDINATE WITH UTILITY COMPANYFOR SHUT DOWN OF UTILITY POWER AND METERING REQUIREMENTS.ELECTRICAL CONTRACTOR SHALL COORDINATE ALL OUTAGES WITHCCAC HOMEWOOD BRUSHTON CAMPUS PRIOR TO SHUTDOWN.PROVIDE ALL LABOR AND MATERIALS REQUIRED FOR A COMPLETEAND FULLY FUNCTIONAL SERVICE ENTRANCE ELECTRICAL SYSTEM.ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ELECTRICALINSPECTIONS TO BE APPROVED PRIOR TO DUQUESNE LIGHTCOMPANY RECONNECT.

    PANELD

    XXXA

    EXISTING

    208/120V3Ø., 4W

    2ND FLOOR

    PROVIDE SURGE PROTECTIONDEVICE(S) AT MAIN BREAKER

    (4) #3/0 +(1) #6G - 2"C.

    (3) #2/0 + (1) #6G - 2"C.

    PANELE

    XXXA

    EXISTING

    208/120V3Ø., 4W

    PANELBARBER SHOP225A MCB

    EXISTING

    208/120V3Ø., 4W

    (4) 600KCMIL +(1) #3G - 4"C.

    EXISTING DISCONNECT SWITCHESSHALL REMAIN.

    P1

    P1

    P2

    P2

    P2

    P3

    M

    PROVIDE UTILITY METER SOCKET. PROVIDE 1 1/2"CCONDUIT FROM C.T. COMPARTMENT TO UTILITYMETER SOCKET. COORDINATE WITH UTILITYCOMPANY METER SOCKET REQUIREMENTS ANDLOCATION.

    #3/0 COPPER GROUND ELECTRICAL CONTRACTORSHALL PROVIDE 4" MINIMUMCONCRETE HOUSEKEEPINGPAD.

    ELECTRICAL CONTRACTOR SHALLPROVIDE 4" MINIMUM CONCRETEHOUSEKEEPING PAD.

    P4

    MAIN SERVICE COPPER GROUND BAR.REFER TO DETAIL 1/E001.

    MGB

    PROVIDE COPPER GROUNDINGTRIAD ELECTRODES LOCATED ATEXTERIOR OF BUILDING.

    GENERAL NOTE:

    THE SHUTDOWN OF THE EXISTING ELECTRICAL SERVICE BY DLCO,DISCONNECTION OF EXISTING SERVICE ENTRANCE CONDUCTORS, THEDEMOLITION OF THE EXISTING ELECTRICAL SERVICE EQUIPMENT,INSTALLATION OF THE NEW ELECTRICAL SERVICE SWITCHGEAR,INTERCEPTING AND RECONNECTION OF ALL EXISTING EQUIPMENTFEEDERS AND RECONNECTION OF THE DUQUESNE LIGHT SERVICE FORFINAL COMPLETION AND INSPECTION, SHALL BE COMPLETED BETWEENJULY 28, 2018 6:00 AM TO AUGUST 5TH, 2018 12:00 PM EST. THEELECTRICAL SERVICE AND THE ENTIRE BUILDING FACILITY SHALL BEFULLY INSPECTED AND OPERATIONAL BY AUGUST 5TH AT 12:00 PM.

    GENERAL NOTE:

    THE ELECTRICAL CONTRACTOR SHALL INCLUDE IN THEIR BID TO PROVIDE A 150 AMP,3-PHASE, 4-WIRE TEMPORARY ELECTRICAL SERVICE PANEL FOR THE WORK BEINGPERFORMED BETWEEN JULY 28, 2018 6:00 AM TO AUGUST 5TH, 2018 12:00 PM EST. THEELECTRICAL CONTRACTOR SHALL COORDINATE WITH DUQUESNE LIGHT COMPANY THEMEANS AND METHODS TO ACCOMPLISH THIS TEMPORARY ELECTRICAL SERVICE.

    THE ELECTRICAL CONTRACTOR SHALL PROVIDE TEMPORARY POWER FOR THE FOLLOWING:THE EXISTING FIRE ALARM PANEL, EXISTING SECURITY PANEL, FIRST FLOOR CORRIDOR ANDLOBBY LIGHTING, LOBBY RECEPTACLES, EXTERIOR FLOODLIGHTS FED FROM EXISTINGPANEL 'J' ON THE 2ND FLOOR, TEMPORARY CONSTRUCTION LIGHTING AND RECEPTACLESFOR THE ELECTRICAL CONTRACTOR'S EQUIPMENT.

    1741119 E001 Electrical Data Sheet-LayoutSheets and Views1741119 E001 Electrical Data Sheet-Layout

    1741119 E002 Electrical Specifications-LayoutSheets and Views1741119 E002 Electrical Specifications-Layout

    1741119 E003 Electrical Specifications-LayoutSheets and Views1741119 E003 Electrical Specifications-Layout

    1741119 E100 Basement Electrical Demolition Plan-LayoutSheets and Views1741119 E100 Basement Electrical Demolition Plan-Layout

    1741119 E200 Basement Electrical Plan-LayoutSheets and Views1741119 E200 Basement Electrical Plan-Layout

    1741119 E201 First Floor Electrical Plan-LayoutSheets and Views1741119 E201 First Floor Electrical Plan-Layout

    1741119 E202 Second Floor Electrical Plan-LayoutSheets and Views1741119 E202 Second Floor Electrical Plan-Layout

    1741119 E301 Electrical Riser Diagram-LayoutSheets and Views1741119 E301 Electrical Riser Diagram-Layout