Lux Calculation Training - Indoor

34
LUX CALCULATION TRAINING (INDOOR) Reference: IESNA Lighting Handbook, 9th Ed. BY: CAMILO C. AQUINO EE TEAM

description

Lumen method

Transcript of Lux Calculation Training - Indoor

Page 1: Lux Calculation Training - Indoor

LUX CALCULATION TRAINING(INDOOR)

Reference: IESNA Lighting Handbook, 9th Ed.

BY: CAMILO C. AQUINOEE TEAM

Page 2: Lux Calculation Training - Indoor

OBJECTIVESOBJECTIVES

At the end of the training, attendees will be able to:1. Design indoor lighting calculation using lumen 

method.2. Evaluate photometric curves.3. Properly select percentage reflections.

f4. Determine maintenance factors5. Designate minimum lux level

U ff ti it fl t t bl6. Use effective cavity reflectance table7. Use CU tables of various fixtures.

2

Page 3: Lux Calculation Training - Indoor

CONTENTSCONTENTS

1. Notes2. Room data and cavity heights3. Room surface reflectance3. Room surface reflectance4. Luminaire and lamp selection5 Factors affecting calculation5. Factors affecting calculation6. Calculation formula7 Actual excel calculation7. Actual excel calculation

3

Page 4: Lux Calculation Training - Indoor

SOME NOTESSOME NOTES…

1. Establish desired lux levels2. Establish type of luminaire to used in the room3. Lumen method calculates average illuminance3. Lumen method calculates average illuminance 

into an area

4

Page 5: Lux Calculation Training - Indoor

STEP 1:STEP 1:

Know your data!y1. Room dimensions & cavity heightsa) Lengthgb) Widthc) Ceiling heightd) hCCe) hRCf) hFCg) Work plane height 

5

Page 6: Lux Calculation Training - Indoor

STEP 1:STEP 1:

Know your data!Know your data!2. Room surface percentage (%) reflectance) Ceilinga) Ceilingb) Wall 

Flc) Floor* Color shade, surface finish, materials used affects 

reflectancereflectance.

6

Page 7: Lux Calculation Training - Indoor

7

Page 8: Lux Calculation Training - Indoor

STEP 1:STEP 1:

Know your data!Know your data!3. Room surface Effective reflectance: 

) C l l t it ti RCR CCR FCRa) Calculate cavity ratios: RCR,CCR, FCRl = room length

= idth w = room width h = height** h for room cavity ratio hrc for room cavity ratiohcc for ceiling cavity ratiohfc for floor cavity ratiofc f f y

8

Page 9: Lux Calculation Training - Indoor

STEP 1:STEP 1:

Know your data!Know your data!3. Room surface Effective reflectance: 

b) Using cavity ratios refer to Figure 9 27 and look forb) Using cavity ratios, refer to Figure 9‐27 and look for effective reflectance values.

c) if luminaire is ceiling surface/recessedc)  if luminaire is ceiling surface/recessed mounted, hcc=0

d) if working plane is on the floor h =0d)  if working plane is on the floor, hfc=0

9

Page 10: Lux Calculation Training - Indoor

10

Page 11: Lux Calculation Training - Indoor

11

Page 12: Lux Calculation Training - Indoor

STEP 2:STEP 2:

Know your luminaires!y1. Refer from ITB / Technical Specification2. HID / Fluorescent / Incandescent2. HID / Fluorescent / Incandescent3. Direct / Semi‐direct / Indirect4 Study photometric data4. Study photometric data5. Longitudinal / Transverse6 Lamp lumens6. Lamp lumens

12

Page 13: Lux Calculation Training - Indoor

STEP 2:STEP 2:

Photometric CurvePhotometric Curve Shows the luminous intensity distributionintensity distribution of a lighting device.

13

Page 14: Lux Calculation Training - Indoor

STEP 2:STEP 2:

Figure of a photometric curves in 2D/3D.g p /

14

Page 15: Lux Calculation Training - Indoor

STEP 2:STEP 2:

Figure of a photometric curves in 2D/3D.g p /

15

Page 16: Lux Calculation Training - Indoor

STEP 2:STEP 2:

Figure of a photometric curves in 2D/3D.g p /

16

Page 17: Lux Calculation Training - Indoor

BREAK?

Next in Line:•FACTORS AFFECTING DESIRED LUX CALCULATION

17

Page 18: Lux Calculation Training - Indoor

STEP 4:STEP 4:

Know the factors affecting your calculation!g y1. CU2. Maintenance factors2. Maintenance factors

18

Page 19: Lux Calculation Training - Indoor

STEP 4:STEP 4:

Determination of CU1. From Step 1: once all reflectance values (

are available, using Figure 9‐28 determine CU g gby selecting the proper luminaire.

2. Interpolate values as required if effective reflectance are not exactly equal in the table

19

Page 20: Lux Calculation Training - Indoor

STEP 4: LIGHT LOSS FACTORSTEP 4: LIGHT LOSS FACTOR

Look at IESNA Lighting Handbook, 9th Ed., page 395

1. Non‐recoverablea. Luminaire ambient temp.

2. Recoverablea. Lamp lumen dep’n.

b. Heat extractionc. Voltage to luminaire

b. Luminaire dirt dep’n.c. Room surface dep’n.

d. Ballast factore. Ballast‐lamp photometricf Eqpt Operating

d. Lamp burnout

f. Eqpt. Operatingg. Tilt h Luminaire surface dep’n.h. Luminaire surface dep n.

20

Page 21: Lux Calculation Training - Indoor

STEP 4: LIGHT LOSS FACTORSTEP 4: LIGHT LOSS FACTOR

a) Lamp lumen depreciation (LLD) factor Check manufacturers' data for LLD factors.  70% of average rated life is the recommended criterion for lamp 

l f b h d l ireplacement for both group and spot re‐lamping programs.

21

Page 22: Lux Calculation Training - Indoor

STEP 4: LIGHT LOSS FACTORSTEP 4: LIGHT LOSS FACTOR

Fluorescent lamp LLD

22

Page 23: Lux Calculation Training - Indoor

STEP 4: LIGHT LOSS FACTORSTEP 4: LIGHT LOSS FACTOR

HID lamp LLD

23

Page 24: Lux Calculation Training - Indoor

STEP 4: LAMP DIRT DEPRECIATION (LDD) FACTORSTEP 4: LAMP DIRT DEPRECIATION (LDD) FACTOR

a) Lamp dirt depreciation (LDD) factor Check luminaire maintenance category  Check atmosphere Using Figure 9‐17, look for LDD

24

Page 25: Lux Calculation Training - Indoor

STEP 4: LDDSTEP 4: LDD

Lamp Dirt Depreciation (LDD) factor To arrive at categories luminaires are To arrive at categories, luminaires are 

arbitrarily divided into sections, a Top Enclosure and a Bottom Enclosure, by drawing a horizontal line through the light center of the lamp or lamps. 

The characteristics listed for the enclosures are then selected as best describing the luminaire. 

Only one characteristic for the top enclosure and one for the bottom enclosure should beand one for the bottom enclosure should be used in determining the category of a luminaire. Percentage of up‐light is based on 100% for the luminaire. 

The maintenance category is determined g ywhen there are characteristics in both enclosure columns. 

If a luminaire falls into more than one category, the lower numbered category is usedused.

25

Page 26: Lux Calculation Training - Indoor

STEP 4: LDDSTEP 4: LDD

26

Page 27: Lux Calculation Training - Indoor

STEP 4: LDDSTEP 4: LDD

27

Page 28: Lux Calculation Training - Indoor

STEP 4: LDDSTEP 4: LDD

28

Page 29: Lux Calculation Training - Indoor

STEP 4: LDDSTEP 4: LDD

or use the below formula: or use the below formula:

where:A and B are found from Figure 9‐18,based on the luminaire maintenancecategory and the atmospherecondition involvedt is time in decimal years (e.g., 1 yr 6mo is entered as 1.5 yr)

29

Page 30: Lux Calculation Training - Indoor

STEP 4: ROOM SURFACE DIRT DEP’N (RSDD)STEP 4: ROOM SURFACE DIRT DEP N. (RSDD)

30

Page 31: Lux Calculation Training - Indoor

STEP 4: LAMP BURNOUT (LB) FACTORSTEP 4: LAMP BURNOUT (LB) FACTOR

The lamp burnout (LBO) factor is the ratio of the The lamp burnout (LBO) factor is the ratio of the number of lamps remaining lighted to the total, for the maximum number of burnouts permitted.for the maximum number of burnouts permitted.

For example, in a room with 100 lamps, 5 lamps are allowed to be burnout without replacingare allowed to be burnout without replacing. 

So the factor is 95 out of 100 or 0.95

31

Page 32: Lux Calculation Training - Indoor

STEP 4: FINALLY!STEP 4: FINALLY!

Light loss factor are the product of:Light loss factor are the product of:  LLD

LDD LDD RSDD LB   

In excel file, just put 0.8

32

Page 33: Lux Calculation Training - Indoor

STEP 5: CALCULATION FORMULASTEP 5: CALCULATION FORMULA

33

Page 34: Lux Calculation Training - Indoor

THANK YOU FOR YOUR TIME!