LPI 20W/32W
Technical GuideFloor & Roof Applications
Floor Span Tables: Simple Span Applications 2
Floor Span Tables: Continuous Span Applications 3
Uniform Floor Load (PLF) Tables 4
Uniform Roof Load (PLF) Tables 5
Roof Span Tables: Low Slope (6:12 or less) 6
Roof Span Tables: High Slope (over 6:12 thru 12:12) 7
Web Hole Specifications: Circular Holes 8
Web Hole Specifications: Rectangular Holes 9
Load-Bearing Cantilever Tables: 9-1/2" & 11-7/8" 10
Load-Bearing Cantilever Tables: 14" & 16" 11
Brick-Ledge Cantilevers 12-13
Product Specifications & Design Values 14
Framing Connectors 15
Warranty Back Page
is guide must be used in conjunction with the Engineered Wood Product Guide.
-
7/30/2019 lp_i-joists_20-32 (1).pdf
2/162
Floor Span Tables: Simple Span Applications
2005 Louisiana-Pacific Corporation
Span
Simple (single)Span Application
40 PSF LIVE LOAD, 10 PSF DEAD LOAD
Series DepthL/480 L / 360
12" oc 16" oc 19.2" oc 24" oc 12" oc 16" oc 19.2" oc 24" oc
9-1/2" 17'-3" 15'-9" 15'-0" 14'-1" 19'-2" 17'-6" 16'-6" 14'-9"
LPI 20W 11-7/8" 20'-7" 18'-9" 17'-11" 16'-9" 22'-9" 20'-9" 18'-11" 16'-11"
14" 23'-5" 21'-4" 20'-4" 18'-10" 25'-10" 23'-1" 21'-0" 18'-10"
9-1/2" 18'-7" 16'-10" 15'-11" 14'-10" 20'-8" 18'-9" 17'-10" 16'-4"
LPI 32W11-7/8" 22'-1" 20'-0" 18'-11" 17'-7" 24'-6" 22'-3" 21'-1" 19'-0"
14" 25'-0" 22'-8" 21'-5" 19'-11" 27'-9" 25'-2" 23'-7" 21'-1"
16" 27'-7" 25'-0" 23'-8" 22'-0" 30'-8" 27'-10" 25'-7" 22'-10"
DESIGN ASSUMPTIONS:1. The spans listed are the clear distance between supports.2. The spans are based on uniform loads only.
3. These tables reflect the additional stiffness provided by the appropriate span-rated floorsheathing glued and nailed to the top flange of the joists.
4. Live load deflection has been limited to L/480 or L/360 as indicated in the tables above.5. Total deflection has been limited to L/240. Those spans that exceed 3/4" of total deflection
are shown in bold.6. A load sharing (repetitive member) increase has been applied. This increase is based
on the attachment of a proper deck to three or more joists, spaced no more than 24" oc.7. The spans are based on the minimum required bearings as listed on page 14.
ADDITIONAL NOTES:1. Web stiffeners are not required for any of the spans in the Simple Span tables. Web fillers are required
for joists seated in hangers that do not laterally support the top flange.2. L/360 is the minimum deflection criteria allowed per code, which allows the maximum amount of deflection
in the floor.3. These spans are not evaluated for vibration.4. Bridging, blocking, a direct-applied ceiling and/or bottom-flange bracing, though not required for vertical
load capacity, can improve floor vibration and bounce.
5. For conditions not shown, use the Uniform Floor Load (PLF) tables or contact your LP Engineered WoodProducts distributor for assistance.
TO USE:
1. Select the appropriate table based on the project design loads.2. Select the L/480 or L/360 section of that table, as required.3. Find a span that meets or exceeds the design span.4. Read the corresponding joist depth and spacing.
Caution: For floor systems that require both simple span and continuous span joists,it is a good idea to check both before selecting a joist. Some conditions are controlledby continuous span strength rather than simple span deflection.
40 PSF LIVE LOAD, 15 PSF DEAD LOAD
Series DepthL/480 L / 360
12" oc 16" oc 19.2" oc 24" oc 12" oc 16" oc 19.2" oc 24" oc
9-1/2" 17'-3" 15'-9" 15'-0" 14'-1" 19'-2" 17'-3" 15'-9" 14'-1"
LPI 20W 11-7/8" 20'-7" 18'-9" 17'-11" 16'-1" 22'-9" 19'-9" 18'-0" 16'-1"
14" 23'-5" 21'-4" 20'-1" 17'-11" 25'-5" 22'-0" 20'-1" 17'-11"
9-1/2" 18'-7" 16'-10" 15'-11" 14'-10" 20'-8" 18'-9" 17'-6" 15'-7"
LPI 32W11-7/8" 22'-1" 20'-0" 18'-11" 17'-7" 24'-6" 22'-2" 20'-3" 18'-1"
14" 25'-0" 22'-8" 21'-5" 19'-9" 27'-9" 24'-7" 22'-5" 20'-1"
16" 27'-7" 25'-0" 23'-8" 21'-6" 30'-8" 26'-8" 24'-4" 21'-6"
40 PSF LIVE LOAD, 25 PSF DEAD LOAD
Series DepthL/480 L / 360
12" oc 16" oc 19.2" oc 24" oc 12" oc 16" oc 19.2" oc 24" oc
9-1/2" 17'-3" 15'-9" 14'-6" 12'-11" 18'-4" 15'-10" 14'-6" 12'-11"
LPI 20W 11-7/8" 20'-7" 18'-2" 16'-7" 14'-10" 21'-0" 18'-2" 16'-7" 14'-10"
14" 23'-4" 20'-2" 18'-5" 16'-6" 23'-4" 20'-2" 18'-5" 16'-6"9-1/2" 18'-7" 16'-10" 15'-11" 14'-4" 20'-1" 17'-7" 16'-1" 14'-4"
LPI 32W11-7/8" 22'-1" 20'-0" 18'-7" 15'-6" 23'-7" 20'-5" 18'-7" 15'-6"
14" 25'-0" 22'-7" 20'-8" 16'-8" 26'-2" 22'-7" 20'-8" 18'-0"
16" 27'-7" 24'-6" 22'-5" 18'-2" 28'-4" 24'-6" 22'-5" 18'-2"
ACTUAL DEFLECTIONBASED ON SPAN AND LIMIT
Span (ft) L/480 L/360 L/240
10 1/4" 5/16" 1/2"
12 5/16" 3/8" 5/8"
14 3/8" 7/16" 11/16"
16 3/8" 9/16" 13/16"
18 7/16" 5/8" 7/8"
20 1/2" 11/16" 1"
22 9/16" 3/4" 1-1/8"
24 5/8" 13/16" 1-3/16"
26 5/8" 7/8" 1-5/16"
28 11/16" 15/16" 1-3/8"
30 3/4" 1" 1-1/2"
* Deflections rounded to the nearest 1/16".
-
7/30/2019 lp_i-joists_20-32 (1).pdf
3/16
40 PSF LIVE LOAD, 25 PSF DEAD LOAD @ L/480
40 PSF LIVE LOAD, 15 PSF DEAD LOAD @ L/480
3
Floor Span Tables: Continuous Span Applications
2005 Louisiana-Pacific Corporation
SpanSpan Span
Continuous (multiple)Span Application
TO USE:
1. Select the appropriate table based on the project design loads.2. Select the section with or without web stiffeners, as needed.3. Find a span that meets or exceeds the design span.4. Read the corresponding joist depth and spacing.
Caution: For floor systems that require both simple span and continuous span joists,it is a good idea to check both before selecting a joist. Some conditions are controlledby simple span deflection rather than continuous span strength.
DESIGN ASSUMPTIONS:1. The spans listed are the clear distance between supports.2. The spans are based on uniform loads only.3. These tables reflect the additional stiffness provided by the appropriate span-rated floor
sheathing glued and nailed to the top flange of the joists.4. Live load deflection has been limited to L/480.5. Total deflection has been limited to L/240. Those spans that exceed 3/4" of total deflection
are shown in bold.6. A load sharing (repetitive member) increase has been applied. This increase is based on
the attachment of a proper deck to three or more joists, spaced no more than 24" oc.
7. The spans are based on the minimum required bearings as listed on page 14.
ADDITIONAL NOTES:1. Web stiffeners are only required for the spans in the With Web Stiffeners section of each table.
A - indicates that there is no increase in span through the use of web stiffeners. Web fillers are requiredfor joists seated in hangers that do not laterally support the top flange.
2. The design of continuous spans is based on the longest span. The shortest span must not be less than50% of the longest span.
3. These spans are not evaluated for vibration.4. Bridging, blocking, a direct-applied ceiling and/or bottom-flange bracing, though not required for vertical
load capacity, can improve floor vibration and bounce.5. For conditions not shown, use the Uniform Floor Load (PLF) tables or contact your LP Engineered Wood
Products distributor for assistance.
40 PSF LIVE LOAD, 10 PSF DEAD LOAD @ L/480
Series DepthWithout Web Stiffeners With Web Stiffeners
12" oc 16" oc 19.2" oc 24" oc 12" oc 16" oc 19.2" oc 24" oc
9-1/2" 18'-10" 17'-2" 16'-4" 14'-8" - - - -
LPI 20W 11-7/8" 22'-5" 20'-5" 18'-10" 16'-10" - - - -
14" 25'-6" 23'-0" 20'-11" 18'-9" - - - -
9-1/2" 20'-2" 18'-3" 17'-3" 15'-8" - - - 15'-11"
LPI 32W11-7/8" 24'-0" 21'-9" 20'-6" 18'-6" - - - 18'-11"
14" 27'-10" 24'-7" 23'-3" 19'-8" - - - 21'-0"
16" 30'-10" 27'-11" 24'-8" 19'-8" - - 25'-6" 22'-9"
Series DepthWithout Web Stiffeners With Web Stiffeners
12" oc 16" oc 19.2" oc 24" oc 12" oc 16" oc 19.2" oc 24" oc
9-1/2" 18'-10" 17'-2" 15'-8" 14'-0" - - - -
LPI 20W 11-7/8" 22'-5" 19'-8" 17'-11" 16'-0" - - - -
14" 25'-4" 21'-11" 20'-0" 17'-4" - - - 17'-10"
9-1/2" 20'-2" 18'-3" 17'-3" 14'-3" - - - 14'-5"
LPI 32W11-7/8" 24'-0" 21'-9" 20'-2" 16'-9" - - - 18'-0"
14" 27'-10" 24'-6" 22'-4" 17'-10" - - - 20'-0"
16" 30'-9" 26'-7" 24'-5" 17'-10" - - 24'-3" 21'-8"
Series DepthWithout Web Stiffeners With Web Stiffeners
12" oc 16" oc 19.2" oc 24" oc 12" oc 16" oc 19.2" oc 24" oc
9-1/2" 18'-3" 15'-9" 14'-5" 12'-0" - - - 12'-2"
LPI 20W 11-7/8" 20'-11" 18'-1" 16'-6" 14'-2" - - - 14'-9"
14" 23'-3" 20'-1" 18'-4" 14'-7" - - - 16'-5"9-1/2" 20'-2" 17'-6" 15'-1" 12'-0" - - 15'-3" 12'-2"
LPI 32W11-7/8" 23'-6" 20'-4" 17'-9" 14'-2" - - 18'-6" 15'-3"
14" 26'-1" 22'-6" 18'-11" 15'-1" - - 20'-7" 18'-4"
16" 28'-3" 22'-9" 18'-11" 15'-1" - 24'-5" 22'-4" 19'-11"
ACTUAL DEFLECTIONBASED ON SPAN AND LIMIT
Span (ft) L/480 L/360 L/240
10 1/4" 5/16" 1/2"
12 5/16" 3/8" 5/8"
14 3/8" 7/16" 11/16"
16 3/8" 9/16" 13/16"
18 7/16" 5/8" 7/8"
20 1/2" 11/16" 1"
22 9/16" 3/4" 1-1/8"
24 5/8" 13/16" 1-3/16"
26 5/8" 7/8" 1-5/16"
28 11/16" 15/16" 1-3/8"
30 3/4" 1" 1-1/2"
* Deflections rounded to the nearest 1/16".
-
7/30/2019 lp_i-joists_20-32 (1).pdf
4/164
Uniform Floor Load (PLF) Tables
2005 Louisiana-Pacific Corporation
EXAMPLE:
Select an I-Joist for a 17'-6" clear span supporting 40 psf Live Load and 20 psf Dead Load,spaced 16" oc, at an L/480 deflection limit.
1. Design Total Load = (40 + 20) * (16 / 12) = 80 plfDesign Live Load = 40 * (16 / 12) = 54 plf
2. Select the row corresponding to an 18' span.
3. The first I-Joist to exceed both Total Load and L/480:11-7/8" LPI 32W can support 102 plf Total and 62 plf Live @ L/480
TO USE:
1. Select the span required.2. Compare the design total load to the Total Load column and compare the design live load
to either the L/480 or L/360 column as needed.3. Select a product that exceeds both the design total and live loads.
DESIGN ASSUMPTIONS:
1. Span is the clear distance between supports and is valid for simpleor continuous spans.
2. The values are based on uniform loads of standard duration.3. These tables assume that the joist is NOT a repetitive member, therefore load
sharing has not been applied. Also, the deflection values do not reflect anyadditional stiffness due to composite action.
4. Total deflection has been limited to L/ 240. Long term deflection (creep) has NOTbeen considered.
5. These tables assume full lateral support of the compression flange. Full supportis considered to be a maximum unbraced length of 24".
6. The values are based on the minimum required bearings as listed on page 14.
ADDITIONAL NOTES:
1. The values represent the capacity of the joist in pounds per lineal foot (plf) of length.2. The designer must check both the Total Load and the appropriate Live Load columns.3. To design for a double I-Joist, the values in these tables can be doubled, or the design loads on the joist may be halved to verify the
capacity of each ply. The capacity is additive.4. Web stiffeners arenotrequired for these spans and loads. Web fillersare required for joists seated in hangers that do not laterally
support the top flange.5. Where the Live Load is blank, the Total Load governs the design.6. Do not use a product where designated - without further analysis by a professional engineer.
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Span
(ft)
Span
(ft)
8
9
10
11
12
13
14
15
16
17
1819
20
21
22
23
24
25
26
27
28
29
30
31
32
8
9
10
11
12
13
14
15
16
17
1819
20
21
22
23
24
25
26
27
28
29
30
31
32
Span
(ft)
Span
(ft)
14" LPI 20W 14" LPI 32W 16" LPI 32W
Live Load Total Live Load Total Live Load Total
L /480 L /360 Load L /480 L /360 Load L /480 L /360 Load
234 241 241
209 215 215
188 194 194
172 177 177
158 162 162
146 150 150
135 140 140
121 127 130 130
101 119 118 122 122
86 112 101 115 115
73 98 101 87 109 10963 84 91 76 101 103 99 103
54 73 82 66 88 98 86 98
47 63 74 58 77 93 76 94
41 55 68 51 68 85 67 89
36 49 62 45 61 78 60 80 85
32 43 57 40 54 71 53 71 82
29 38 52 36 48 66 47 63 77
26 34 48 32 43 61 43 57 71
23 31 45 29 39 56 38 51 66
21 28 42 26 35 52 35 46 62
18 25 37 24 32 48 31 42 57
17 22 34 21 29 43 29 38 54
15 20 31 19 26 39 26 35 50
- - - - - - 24 32 47
9-1/2" LPI 20W 9-1/2" LPI 32W 11-7/8" LPI 20W 11-7/8" LPI 32W
Live Load Total Live Load Total Live Load Total Live Load TotalL /480 L /360 Load L /480 L /360 Load L /480 L /360 Load L /480 L /360 Load
193 193 227 227
172 172 202 202
155 155 155 183 183
120 141 139 141 166 166
95 127 130 112 130 153 153
76 102 119 92 120 125 141 141
62 83 103 76 101 112 102 131 119 131
51 68 89 63 85 104 85 113 117 100 123
43 57 79 53 71 97 71 94 103 85 113 115
36 48 70 45 61 86 60 80 92 72 97 108
30 41 61 39 52 77 51 68 82 62 83 102
26 35 52 33 45 67 43 58 73 54 72 92
22 30 45 29 39 58 38 50 66 47 63 83
19 26 39 25 34 51 33 44 60 41 55 76
- - - - - - 28 38 55 36 48 69
- - - - - - 25 34 50 32 43 63
- - - - - - 22 30 45 28 38 57
PSF TO PLF CONVERSION TABLE
OC Spacing Load (psf)
(12") 20 25 30 35 40 45 50 55 60 65
16" 27 34 40 47 54 60 67 74 80 87
19.2" 32 40 48 56 64 72 80 88 96 104
24" 40 50 60 70 80 90 100 110 120 130
-
7/30/2019 lp_i-joists_20-32 (1).pdf
5/16 2005 Louisiana-Pacific Corporation5
ROOF SLOPE ADJUSTMENT FACTORS
Uniform Roof Load (PLF) Tables
Slope 2:12 3:12 4:12 5:12 6:12 7:12 8:12 9:12 10:12 11:12 12:12
Factor 1.014 1.031 1.054 1.083 1.118 1.158 1.202 1.250 1.302 1.357 1.414
9-1/2" LPI 20W 9-1/2" LPI 32W 11-7/8" LPI 20W 11-7/8" LPI 32WSpan
Live Load Total Load Live Load Total Load Live Load Total Load Live Load Total LoadSpan
(ft)L/240 Snow 115% Non-Snow 125% L/240 Snow 115% Non-Snow 125% L/240 Snow 115% Non-Snow 125% L /240 Snow 115% Non-Snow 125%
(ft)
8 222 241 222 241 261 284 261 284 8
9 198 215 198 215 233 253 233 253 9
10 179 194 179 194 210 228 210 228 10
11 163 177 163 177 191 208 191 208 11
12 149 162 149 162 176 191 176 191 12
13 137 149 138 150 162 177 162 177 13
14 125 118 128 128 140 151 164 151 164 14
15 103 103 112 127 120 130 135 147 141 153 15
16 86 91 98 107 111 121 119 129 132 144 16
17 72 80 87 91 99 107 105 115 125 136 17
18 61 72 78 78 88 96 102 94 102 125 118 128 18
19 52 64 70 67 79 86 87 84 92 108 106 115 1920 45 58 60 58 71 78 76 76 83 94 96 104 20
21 39 52 52 51 65 68 66 69 75 83 87 95 21
22 34 46 46 45 59 60 57 63 69 73 79 86 22
23 30 40 40 39 53 53 51 58 63 64 73 79 23
24 26 35 35 35 47 47 45 53 58 57 67 72 24
14" LPI 20W 14" LPI 32W 16" LPI 32WSpan
Live Load Total Load Live Load Total Load Live Load Total LoadSpan
(ft)L/240 Snow 115% Non-Snow 125% L/240 Snow 115% Non-Snow 125% L /240 Snow 115% Non-Snow 125%
(ft)
8 269 293 278 302 278 302 8
9 240 261 248 269 248 269 9
10 217 236 223 243 223 243 10
11 197 215 204 221 204 221 11
12 181 197 187 203 187 203 12
13 168 182 173 188 173 188 13
14 156 169 161 175 161 175 1415 146 158 150 163 150 163 15
16 137 149 141 153 141 153 16
17 129 140 133 144 133 144 17
18 116 126 125 136 125 136 18
19 104 113 119 129 119 129 19
20 94 102 113 123 113 123 20
21 85 93 107 116 108 117 21
22 83 78 85 103 98 106 103 112 22
23 73 71 77 91 89 97 98 107 23
24 65 65 71 81 82 89 94 103 24
25 58 60 66 72 76 82 95 89 97 25
26 52 56 61 65 70 76 86 82 89 26
27 46 52 56 58 65 70 77 76 83 27
28 42 48 52 53 60 66 70 71 77 28
29 37 45 49 48 56 61 63 66 72 29
30 34 42 45 43 52 57 58 62 67 30
31 31 39 41 39 49 53 52 58 63 31
32 28 37 38 36 46 48 48 54 59 32
EXAMPLE:
Select an I-Joist for a 12'-8" horizontal clear span supporting 45 psf Snow (Live) Loadand 15 psf Dead Load, spaced 24" oc, with a roof slope of 6:12.
1. Sloped Span = (12 + 8 / 12) * 1.118 = 14.16' use 15'
2. Design Total Load = (45 + 15) * (24 / 12) = 120 plfDesign Live Load = 45 * (24 / 12) = 90 plf
3. Select the row corresponding to a 15' span.
4. The first I-Joist to exceed both Total Load for Snow (115%) and L/240:9-1/2" LPI 32W can support 120 plf Total Load (115%) Live Load does not control
NOTE: For a live load deflection limit of L/360, the Uniform Floor Load Tables on page 4require an 11-7/8" LPI 20W, which can support 113 plf Live Load @ L/360.
TO USE:
1. Select the span required. For roofs with a slope of 2:12 or greater, the horizontal span must bemultiplied by the appropriate slope adjustment factor from the table at the bottom of this page.
2. Compare the design total load to the appropriate Total Load column for Snow (115%) orNon-Snow (125%), and compare the design live load to the Live Load L/240 column.For live load deflection limits of L/360 or L/480, compare the design live load to the appropriateLive Load column from the Uniform Floor Load Tables on page 4.
3. Select a product that exceeds both the design total and live loads.
DESIGN ASSUMPTIONS:1. Span is the clear distance between supports, along the slope of the joist, and is valid for simple
or continuous spans.2. The values are based on uniform loads only.3. These tables assume that the joist is NOT a repetitive member, therefore load sharing has not been
applied. Also, the deflection values do not reflect any additional stiffness due to composite action.4. Total deflection has been limited to L/180. Long term deflection (creep) has NOT been considered.5. These tables assume full lateral support of the compression flange. Full support is considered to be
a maximum unbraced length of 24".
6. The values are based on the minimum required bearings as listed on page 14.
ADDITIONAL NOTES:1. The values represent the capacity of the joist in pounds per lineal foot (plf) of length.2. The designer must check the appropriate Total Load column and the Live Load column.3. For roofs with a slope of 2:12 or greater, the horizontal span must be multiplied by the appropriate slope
adjustment factor from the table at the bottom of this page.4. To design for a double I-Joist, the values in these tables can be doubled, or the design loads on the joist may
be halved to verify the capacity of each ply. The capacity is additive.5. Web stiffeners arenotrequired for these spans and loads. Web fillersare required for joists seated in hangers
that do not laterally support the top flange.
6. Where the Live Load is blank, the Total Load governs the design.7. To design for a live load limit of L/ 360 or L/480, use the Uniform Floor Load tables.8. Do not use a product where designated - without further analysis by a professional engineer.
-
7/30/2019 lp_i-joists_20-32 (1).pdf
6/16
Series Depth 16" oc 19.2" oc 24" oc
Roof Dead Load 15 psf 20 psf 15 psf 20 psf 15 psf 20 psf
9-1/2" 20'-9" 19'-9" 19'-6" 18'-7" 18'-1" 17'-2"
LPI 20W 11-7/8" 24'-10" 23'-8" 23'-4" 22'-3" 21'-7" 20'-6"
14" 28'-3" 26'-11" 26'-7" 25'-3" 24'-6" 22'-10"
9-1/2" 22'-10" 21'-9" 21'-5" 20'-5" 19'-10" 18'-10"
LPI 32W11-7/8" 27'-2" 25'-11" 25'-6" 24'-3" 23'-7" 22'-5"
14" 30'-10" 29'-4" 28'-11" 27'-6" 26'-9" 25'-5"
16" 34'-1" 32'-5" 31'-11" 30'-5" 29'-6" 27'-9"
9-1/2" 19'-10" 19'-0" 18'-8" 17'-10" 17'-3" 16'-3"
LPI 20W 11-7/8" 23'-9" 22'-9" 22'-2" 20'-10" 19'-10" 18'-7"
14" 27'-0" 25'-4" 24'-8" 23'-2" 22'-0" 20'-8"
9-1/2" 21'-10" 20'-11" 20'-6" 19'-7" 18'-11" 18'-0"
LPI 32W11-7/8" 26'-0" 24'-11" 24'-5" 23'-4" 22'-3" 20'-10"
14" 29'-6" 28'-3" 27'-7" 25'-11" 24'-8" 23'-2"
16" 32'-7" 30'-10" 29'-11" 28'-1" 26'-9" 25'-1"
9-1/2" 19'-1" 18'-4" 17'-11" 17'-3" 16'-4" 15'-5"
LPI 20W 11-7/8" 22'-10" 21'-8" 20'-11" 19'-9" 18'-8" 17'-8"
14" 25'-6" 24'-1" 23'-3" 22'-0" 20'-10" 19'-8"
9-1/2" 21'-0" 20'-2" 19'-8" 18'-11" 18'-1" 17'-1"
LPI 32W11-7/8" 25'-0" 24'-0" 23'-5" 22'-2" 21'-0" 19'-10"
14" 28'-4" 27'-0" 26'-1" 24'-7" 23'-3" 22'-0"
16" 31'-0" 29'-3" 28'-3" 26'-9" 25'-3" 22'-8"
9-1/2" 17'-10" 17'-3" 16'-7" 15'-9" 14'-9" 14'-1"
LPI 20W 11-7/8" 20'-10" 19'-10" 19'-0" 18'-1" 16'-11" 16'-2"
14" 23'-2" 22'-1" 21'-1" 20'-2" 18'-10" 18'-0"
9-1/2" 19'-7" 18'-11" 18'-4" 17'-6" 16'-5" 15'-0"
LPI 32W11-7/8" 23'-4" 22'-3" 21'-4" 20'-4" 19'-0" 17'-8"
14" 25'-11" 24'-9" 23'-8" 22'-6" 20'-7" 18'-10"
16" 28'-1" 26'-10" 25'-8" 23'-8" 20'-7" 18'-10"
9-1/2" 16'-9" 16'-1" 15'-3" 14'-8" 13'-7" 12'-10"
LPI 20W 11-7/8" 19'-2" 18'-5" 17'-6" 16'-9" 15'-7" 15'-0"
14" 21'-4" 20'-6" 19'-5" 18'-8" 16'-10" 15'-7"
9-1/2" 18'-6" 17'-10" 16'-11" 16'-1" 13'-10" 12'-10"
LPI 32W11-7/8" 21'-6" 20'-8" 19'-7" 18'-10" 16'-4" 15'-2"
14" 23'-11" 22'-11" 21'-9" 20'-3" 17'-5" 16'-1"
16" 25'-11" 24'-4" 21'-10" 20'-3" 17'-5" 16'-1"
9-1/2" 15'-7" 15'-0" 14'-2" 13'-9" 11'-11" 11'-2"
LPI 20W 11-7/8" 17'-10" 17'-3" 16'-4" 15'-9" 14'-1" 13'-2"
14" 19'-10" 19'-2" 18'-1" 17'-1" 14'-7" 13'-8"
9-1/2" 17'-4" 16'-8" 15'-0" 14'-1" 11'-11" 11'-2"
LPI 32W11-7/8" 20'-1" 19'-4" 17'-8" 16'-7" 14'-1" 13'-2"
14" 22'-3" 21'-3" 18'-10" 17'-8" 15'-0" 14'-1"
16" 22'-8" 21'-3" 18'-10" 17'-8" 15'-0" 14'-1"
6
Roof Span Tables: Low Slope (6:12 or less)
2005 Louisiana-Pacific Corporation
TO USE:
1. Select the appropriate set of tables based on roof slope.
2. Select the section of that table that corresponds to the designlive load and load duration.
3. Find a span that meets or exceeds the design span for theappropriate roof dead load (15 psf or 20 psf).
4. Read the corresponding joist, depth and spacing.
DESIGN ASSUMPTIONS:
1. The spans listed are the horizontal clear distance between supports.Refer to the diagram below.
2. The spans are based on uniform gravity loads only and havenotbeen evaluated for wind.
3. These tables do notreflect any additional stiffness provided bythe roof sheathing.
4. Live load deflection has been limited to L/240.
5. Total load deflection has been limited to L/180.
6. A load sharing (repetitive member) increase has been applied.This increase is based on the attachment of a proper deckto three or more joists, spaced no more than 24" oc.
7. The spans are based on the minimum required bearings as listedon page 14.
ADDITIONAL NOTES:
1. Web stiffeners arenotrequired for any of the spans listed in these
tables. Web stiffeners are required when using the birds mouthbearing detail. Web fillers are required for joists seated in hangersthat do not laterally support the top flange.
2. The design of continuous spans is based on the longest span.The shortest span must not be less than 50% of the longest span.
3. L/240 is the minimum deflection criteria allowed per code for roofjoists supporting non-plaster ceilings. Verify deflection limits withlocal code requirements.
4. Roof joists must have a minimum slope of 1/4" per foot (1/4:12)for positive drainage.
5. For conditions not shown, use the Uniform Roof Load (PLF) Tablesor contact your LP Engineered Wood Products distributor for assistance.
6. Roof applications in high wind areas require special analysis whichmay result in reduced spans and special connectors to resist uplift.
ACTUAL DEFLECTIONBASED ON SPAN AND LIMIT
* Deflections rounded to the nearest 1/16".
Span (ft) L/360 L/240 L/180
10 5/16" 1/2" 11/16"
12 3/8" 5/8" 13/16"
14 7/16" 11/16" 15/16"
16 9/16" 13/16" 1-1/16"
18 5/8" 7/8" 1-3/16"
20 11/16" 1" 1-5/16"
22 3/4" 1-1/8" 1-7/16"
24 13/16" 1-3/16" 1-5/8"
26 7/8" 1-5/16" 1-3/4"
28 15/16" 1-3/8" 1-7/8"
30 1" 1-1/2" 2"
20psf
125%
Non-
Snow
25psf
115%
Snow
30psf
115%
Snow
40
psf
115%
Snow
50psf
115%
Snow
60psf
115%
Snow
ROOF
LIVE
LOAD
Horizontal Span
12
Pitch
edSpa
n
ROOF JOIST SPAN
Rise
RoofSlope=R
ise:
12
-
7/30/2019 lp_i-joists_20-32 (1).pdf
7/16
Roof Span Tables: High Slope (over 6:12 thru 12:12)
2005 Louisiana-Pacific Corporation7
ACTUAL DEFLECTIONBASED ON SPAN AND LIMIT
* Deflections rounded to the nearest 1/16".
Span (ft) L/360 L/240 L/180
10 5/16" 1/2" 11/16"
12 3/8" 5/8" 13/16"
14 7/16" 11/16" 15/16"
16 9/16" 13/16" 1-1/16"
18 5/8" 7/8" 1-3/16"
20 11/16" 1" 1-5/16"
22 3/4" 1-1/8" 1-7/16"
24 13/16" 1-3/16" 1-5/8"
26 7/8" 1-5/16" 1-3/4"
28 15/16" 1-3/8" 1-7/8"
30 1" 1-1/2" 2"
Series Depth 16" oc 19.2" oc 24" oc
Roof Dead Load 15 psf 20 psf 15 psf 20 psf 15 psf 20 psf
9-1/2" 18'-6" 17'-7" 17'-5" 16'-6" 16'-2" 15'-3"
LPI 20W 11-7/8" 22'-2" 21'-0" 20'-10" 19'-9" 19'-4" 18'-3"
14" 25'-3" 23'-11" 23'-9" 22'-6" 22'-0" 20'-10"
9-1/2" 20'-6" 19'-4" 19'-2" 18'-2" 17'-9" 16'-9"
LPI 32W11-7/8" 24'-4" 23'-0" 22'-10" 21'-7" 21'-1" 20'-0"
14" 27'-7" 26'-1" 25'-11" 24'-6" 23'-11" 22'-8"
16" 30'-6" 28'-10" 28'-7" 27'-1" 26'-6" 25'-0"
9-1/2" 17'-10" 17'-0" 16'-9" 15'-11" 15'-6" 14'-9"
LPI 20W 11-7/8" 21'-4" 20'-4" 20'-0" 19'-1" 18'-7" 17'-7"
14" 24'-3" 23'-1" 22'-10" 21'-9" 21'-0" 19'-6"
9-1/2" 19'-8" 18'-9" 18'-5" 17'-7" 17'-1" 16'-3"
LPI 32W11-7/8" 23'-5" 22'-3" 21'-11" 20'-10" 20'-3" 19'-3"
14" 26'-6" 25'-3" 24'-11" 23'-8" 23'-0" 21'-10"
16" 29'-3" 27'-10" 27'-6" 26'-2" 25'-5" 23'-8"
9-1/2" 17'-2" 16'-5" 16'-2" 15'-5" 15'-0" 14'-4"
LPI 20W 11-7/8" 20'-7" 19'-8" 19'-4" 18'-6" 17'-11" 16'-9"
14" 23'-5" 22'-5" 22'-0" 20'-10" 19'-11" 18'-8"
9-1/2" 19'-0" 18'-2" 17'-10" 17'-0" 16'-5" 15'-8"
LPI 32W11-7/8" 22'-7" 21'-7" 21'-2" 20'-3" 19'-7" 18'-8"
14" 25'-7" 24'-5" 24'-0" 22'-11" 22'-2" 20'-11"
16" 28'-3" 27'-0" 26'-6" 25'-4" 24'-2" 22'-8"
9-1/2" 16'-2" 15'-7" 15'-2" 14'-8" 14'-1" 13'-6"
LPI 20W 11-7/8" 19'-4" 18'-8" 18'-2" 17'-4" 16'-4" 15'-6"
14" 22'-0" 21'-1" 20'-4" 19'-3" 18'-2" 17'-3"
9-1/2" 17'-10" 17'-2" 16'-8" 16'-1" 15'-5" 14'-10"
LPI 32W11-7/8" 21'-2" 20'-5" 19'-11" 19'-1" 18'-4" 17'-1"
14" 24'-0" 23'-2" 22'-6" 21'-7" 20'-4" 19'-3"
16" 26'-7" 25'-7" 24'-9" 23'-5" 22'-1" 20'-0"
9-1/2" 15'-4" 14'-10" 14'-5" 13'-11" 13'-3" 12'-7"
LPI 20W 11-7/8" 18'-5" 17'-9" 17'-0" 16'-2" 15'-2" 14'-5"
14" 20'-8" 19'-9" 18'-10" 18'-0" 16'-10" 16'-1"
9-1/2" 16'-11" 16'-4" 15'-10" 15'-4" 14'-7" 13'-9"
LPI 32W11-7/8" 20'-1" 19'-5" 18'-10" 18'-2" 16'-4" 14'-10"
14" 22'-9" 22'-0" 21'-1" 20'-2" 18'-10" 17'-3"
16" 25'-1" 23'-11" 22'-11" 21'-10" 19'-0" 17'-5"
9-1/2" 14'-8" 14'-3" 13'-9" 13'-3" 12'-4" 11'-10"
LPI 20W 11-7/8" 17'-5" 16'-8" 15'-10" 15'-3" 14'-2" 13'-2"
14" 19'-4" 18'-7" 17'-8" 16'-11" 15'-9" 14'-10"
9-1/2" 16'-1" 15'-8" 15'-1" 14'-8" 13'-1" 12'-2"
LPI 32W11-7/8" 19'-2" 18'-7" 17'-10" 16'-6" 14'-4" 13'-2"
14" 21'-8" 20'-9" 19'-9" 18'-11" 16'-6" 15'-3"
16" 23'-6" 22'-7" 20'-8" 19'-3" 16'-6" 15'-4"
TO USE:
1. Select the appropriate set of tables based on roof slope.
2. Select the section of that table that corresponds to the designlive load and load duration.
3. Find a span that meets or exceeds the design span for theappropriate roof dead load (15 psf or 20 psf).
4. Read the corresponding joist, depth and spacing.
DESIGN ASSUMPTIONS:
1. The spans listed are the horizontal clear distance between supports.Refer to the diagram below.
2. The spans are based on uniform gravity loads only and havenotbeen evaluated for wind.
3. These tables do notreflect any additional stiffness provided bythe roof sheathing.
4. Live load deflection has been limited to L/240.
5. Total load deflection has been limited to L/180.
6. A load sharing (repetitive member) increase has been applied.This increase is based on the attachment of a proper deckto three or more joists, spaced no more than 24" oc.
7. The spans are based on the minimum required bearings as listedon page 14.
ADDITIONAL NOTES:
1. Web stiffeners arenotrequired for any of the spans listed in these
tables. Web stiffeners are required when using the birds mouthbearing detail. Web fillers are required for joists seated in hangersthat do not laterally support the top flange.
2. The design of continuous spans is based on the longest span.The shortest span must not be less than 50% of the longest span.
3. L/240 is the minimum deflection criteria allowed per code for roofjoists supporting non-plaster ceilings. Verify deflection limits withlocal code requirements.
4. Roof joists must have a minimum slope of 1/4" per foot (1/4:12)for positive drainage.
5. For conditions not shown, use the Uniform Roof Load (PLF) Tablesor contact your LP Engineered Wood Products distributor for assistance.
6. Roof applications in high wind areas require special analysis whichmay result in reduced spans and special connectors to resist uplift.
20psf
125%
Non-
Snow
25psf
115%
Snow
30psf
115%
Snow
40
psf
115%
Snow
50psf
115%
Snow
60psf
115%
Snow
ROOF
LIVE
LOAD
Horizontal Span
12
Pitch
edSpan
ROOF JOIST SPAN
Rise
RoofSlope=R
ise:
12
-
7/30/2019 lp_i-joists_20-32 (1).pdf
8/16
ROUND HOLES UP TO 40 PSF LIVE LOAD AND 25 PSF DEAD LOAD; UP TO 24" OC
8 2005 Louisiana-Pacific Corporation
Web Hole Specifications: Circular Holes
TO USE:
1. Select the required product from the left column.
2. Determine the support condition for the nearest bearing: end support or interior support (including end supports with cantilevers).
3. Select the row corresponding to the required span. For spans between those listed, use the next largest value.
4 Select the column corresponding to the required hole diameter. For diameters between those listed, use the next largest value.5. The intersection of the Span row and Hole Diameter column gives the minimum distance from the inside face of bearing to the center of the circular hole.
6. Double check the distance to the other support, using the appropriate support condition.
Series Depth ClearDistance from End Support Distance from Interior or Cantilever-End Support
Span (ft)Hole Diameter Hole Diameter
2" 4" 6" 8" 10" 12" 14" 2" 4" 6" 8" 10" 12" 14"
DESIGN ASSUMPTIONS:1. The hole locations listed above are valid for floor joists supporting only uniform loads as follows:
For joists 16" deep and less, the total uniform load must not exceed 130 plf (e.g., 40 psf Live Load anda 25 psf Dead Load, spaced up to 24" oc). The uniform dead load must be at least 10 plf.
2. Hole location is measured from the inside face of bearing to the center of a circular hole, from theclosest support.
3. Clear Span has NOT been verified for these joists and is shown for informational purposes only! Verify thatthe joist selected will work for the span and loading conditions needed before checking hole location.
4. Maximum hole depth for circular holes is Joist Depth less 4", not to exceed 14", except the maximum holedepth is 6" for 9-1/2", and 8" for 11-7/8" LP I-Joists.5. Holes cannot be located in the span where designated - without further analysis by a professional engineer.
NOTES:1. CUT HOLES CAREFULLY! DO NOT OVERCUT HOLES! DO NOT CUT JOIST FLANGES!2. Holes may be placed anywhere within the depth of the joist. A minimum 1/4" clear distance is required
between the hole and the flanges.3. Round holes up to 1-1/2" diameter may be placed anywhere in the web.4. Perforated knockouts may be neglected when locating web holes.5. Holes larger than 1-1/2" are not permitted in cantilevers without special engineering.
6. Multiple holes must have a clear separation along the length of the joist of at least twice the length
of the larger adjacent hole, or a minimum of 12" center-to-center, whichever is greater.7. Multiple holes may be spaced closer provided they fit within the boundary of an acceptable larger hole.
Example: two 3" round holes aligned parallel to the joist length may be spaced 2" apart (clear distance)provided that a 3" high by 8" long rectangle or an 8" diameter round hole are acceptable for the joistdepth at that location and completely encompass the holes.
8. Not all series are available in all depths. Check availability with a local LP Engineered WoodProducts distributor.
9. Locating holes in joists with spans exceeding those in the tables or larger holes, greater uniform loadsor non-uniform loads, and closer proximity to supports and other holes may be possible with analysisusing LPs design software. Please contact your local LP Engineered Wood Products distributor formore information.
6 1'-0" 1'-0" 1'-6" - - - - 1'-0" 1'-0" 1'-6" - - - -LPI 20W
9-1/2"10 1'-0" 1'-0" 1'-6" - - - - 1'-0" 1'-0" 1'-6" - - - -
&14 1'-0" 1'-0" 1'-6" - - - - 1'-0" 1'-8" 3'-5" - - - -
LPI 32W18 1'-0" 1'-10" 3'-8" - - - - 2'-8" 4'-5" 6'-3" - - - -
6 1'-0" 1'-0" 1'-6" 2'-0" - - - 1'-0" 1'-0" 1'-6" 2'-0" - - -LPI 20W
11-7/8"10 1'-0" 1'-0" 1'-6" 2'-0" - - - 1'-0" 1'-0" 1'-6" 2'-0" - - -
&14 1'-0" 1'-0" 1'-6" 2'-0" - - - 1'-0" 1'-0" 2'-5" 3'-10" - - -
LPI 32W
18 1'-0" 1'-5" 2'-9" 4'-1" - - - 2'-2" 3'-6" 5'-4" 6'-9" - - -8 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" - - 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" - -
LPI 20W
14"12 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" - - 1'-0" 1'-0" 1'-6" 2'-0" 2'-8" - -
&16 1'-0" 1'-0" 1'-6" 2'-1" 3'-8" - - 1'-0" 1'-11" 3'-2" 4'-4" 5'-7" - -
LPI 32W20 1'-0" 2'-1" 3'-1" 4'-7" 6'-1" - - 3'-5" 4'-5" 6'-0" 7'-6" 9'-0" - -
8 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" 3'-0" - 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" 3'-0" -
16"12 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" 3'-0" - 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" 3'-3" -
LPI 32W16 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" 3'-8" - 1'-0" 1'-6" 2'-9" 3'-7" 4'-9" 6'-0" -
20 1'-0" 1'-7" 2'-7" 3'-7" 5'-1" 6'-7" - 2'-11" 4'-5" 5'-5" 6'-6" 8'-0" 9'-6" -
Up to a 1-1/2" diameter holeallowed anywhere in the web.Closest spacing 12" oc.
Diameter
Closest distance (x) to center of circular hole
FROM EITHER SUPPORT
Uncut length of web between adjacent holesmust be at least twice the length of the larger hole
or 12" center-to-center, whichever is larger.
Closest distance (x) to center of circular hole
FROM EITHER SUPPORT
END SUPPORT INTERIOR OR CANTILEVER-END SUPPORT
-
7/30/2019 lp_i-joists_20-32 (1).pdf
9/16
RECTANGULAR HOLES UP TO 40 PSF LIVE LOAD AND 25 PSF DEAD LOAD; UP TO 24" OC
Web Hole Specifications: Rectangular Holes
2005 Louisiana-Pacific Corporation9
TO USE:
1. Select the required product from the left column.
2. Determine the support condition for the nearest bearing: end support or interior support (includes end supports with cantilevers).
3. Select the row corresponding to the required span. For spans between those listed, use the next largest value.
4. Select the column corresponding to the required hole dimension. For dimensions between those listed, use the next largest value.5. The intersection of the Span row and Hole Dimension column gives the minimum distance from the inside face of bearing to the nearest edge of the rectangular hole.
6. Double check the distance to the other support, using the appropriate support condition.
DESIGN ASSUMPTIONS:1. The hole locations listed above are valid for floor joists supporting only uniform loads as follows:
For joists 16" deep and less, the total uniform load must not exceed 130 plf (e.g., 40 psf Live Load anda 25 psf Dead Load, spaced up to 24" oc). The uniform dead load must be at least 10 plf.
2. Hole location is measured from the inside face of bearing to the nearest edge of a rectangular hole, from theclosest support.
3. Clear Span has NOT been verified for these joists and is shown for informational purposes only! Verify thatthe joist selected will work for the span and loading conditions needed before checking hole location.
4. Maximum hole depth for rectangular holes is Joist Depth less 4", not to exceed 14", except the maximum holedepth is 6" for 9-1/2", and 8" for 11-7/8" LP I-Joists. Maximum hole width for rectangular holes is 18". Wherethe Maximum Hole Dimension for rectangular holes exceeds the maximum hole depth, the dimension refers tohole width, and the hole depth is assumed to be the maximum for that joist depth.
5. Holes cannot be located in the span where designated - without further analysis by a professional engineer.
NOTES:1. CUT HOLES CAREFULLY! DO NOT OVERCUT HOLES! DO NOT CUT JOIST FLANGES!2. Holes may be placed anywhere within the depth of the joist. A minimum 1/4" clear distance is required
between the hole and the flanges.3. Round holes up to 1-1/2" diameter may be placed anywhere in the web.4. Perforated knockouts may be neglected when locating web holes.
5. Holes larger than 1-1/2" are not permitted in cantilevers without special engineering.6. Multiple holes must have a clear separation along the length of the joist of at least twice the length
of the larger adjacent hole, or a minimum of 12" center-to-center, whichever is greater.7. Multiple holes may be spaced closer provided they fit within the boundary of an acceptable larger hole.
Example: two 3" round holes aligned parallel to the joist length may be spaced 2" apart (clear distance)provided that a 3" high by 8" long rectangle or an 8" diameter round hole are acceptable for the joistdepth at that location and completely encompass the holes.
8. Not all series are available in all depths. Check availability with a local LP Engineered WoodProducts distributor.
9. Locating holes in joists with spans exceeding those in the tables or larger holes, greater uniform loadsor non-uniform loads, and closer proximity to supports and other holes may be possible with analysisusing LPs design software. Please contact your local LP Engineered Wood Products distributor formore information.
Depth
Closest distance (x) to edge of rectangular hole
FROM EITHER SUPPORT
Closest distance (x) to edge of rectangular hole
FROM EITHER SUPPORT
END SUPPORT INTERIOR OR CANTILEVER-END SUPPORT
Width
Uncut length of web between adjacent holesmust be at least twice the length of the larger hole
or 12" center-to-center, whichever is larger.
Series Depth ClearDistance from End Support Distance from Interior or Cantilever-End Support
Span (ft)Maximum Hole Dimension: Depth or Width Maximum Hole Dimension: Depth or Width
2" 4" 6" 8" 10" 12" 14" 16" 18" 2" 4" 6" 8" 10" 12" 14" 16" 18"
6 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" 3'-0" - - - 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" 3'-0" - - -LPI 20W
9-1/2"10 1'-0" 1'-1" 2'-7" 3'-1" 3'-7" 4'-1" 4'-7" - - 1'-0" 2'-5" 4'-0" 4'-6" 5'-0" - - - -
&14 1'-10" 3'-3" 5'-4" 5'-8" 6'-5" 6'-9" - - - 3'-10" 5'-3" - - - - - - -
LPI 32W18 4'-1" 5'-11" 7'-9" 8'-8" - - - - - 6'-9" 8'-7" - - - - - - -
6 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" 3'-0" - - - 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" 3'-0" - - -LPI 20W
11-7/8"10 1'-0" 1'-0" 1'-10" 3'-4" 3'-10" 4'-4" 4'-10" - - 1'-0" 1'-11" 3'-3" 4'-9" - - - - -
&14 1'-5" 2'-10" 4'-3" 6'-1" 6'-9" - - - - 3'-5" 4'-10" 6'-3" - - - - - -
LPI 32W
18 3'-8" 5'-6" 6'-10" 8'-8" - - - - - 6'-3" 8'-1" - - - - - - -8 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" 3'-0" 3'-6" 4'-0" - 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" 3'-0" 3'-10" - -
LPI 20W
14"12 1'-0" 1'-0" 1'-6" 2'-0" 3'-8" 4'-7" 5'-2" - - 1'-0" 1'-0" 1'-6" 3'-3" 5'-5" - - - -
&16 1'-0" 1'-0" 2'-1" 4'-1" 6'-6" 7'-4" - - - 1'-0" 2'-4" 4'-4" 6'-5" - - - - -
LPI 32W20 1'-0" 2'-7" 4'-7" 6'-7" 9'-1" - - - - 2'-11" 4'-11" 7'-0" 9'-6" - - - - -
8 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" 3'-0" 3'-6" 4'-0" - 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" 3'-5" - - -
16"12 1'-0" 1'-0" 1'-6" 2'-0" 2'-9" 4'-11" 5'-10" - - 1'-0" 1'-0" 1'-6" 2'-8" 4'-6" - - - -
LPI 32W16 1'-0" 1'-0" 1'-8" 3'-3" 5'-3" 7'-8" - - - 1'-0" 1'-11" 3'-7" 5'-7" 7'-7" - - - -
20 1'-0" 2'-1" 3'-7" 5'-7" 8'-1" - - - - 2'-11" 4'-11" 6'-6" 8'-6" - - - - -
-
7/30/2019 lp_i-joists_20-32 (1).pdf
10/1610
Load-Bearing Cantilever Tables: 9-1/2" & 11-7/8"
2005 Louisiana-Pacific Corporation
TO USE:
1. Select the page (10 or 11) that corresponds to the required product.
2. Select the row corresponding to the Roof Load and Truss Span needed.
DESIGN ASSUMPTIONS:1. These tables are valid for joists selected from the Floor Span Tables in this design guide.2. The floor design loads mustnotexceed 40 psf Live and 25 psf Dead Load.
3. The maximum cantilever length is 2' (the amount of overhang).4. The wall load is assumed to be 100 plf.
5. Roof Load is the Total Load (Live plus Dead) on the roof trusses.6. Truss Span is the out-to-out distance of the truss bearing walls as shown above.
7. A maximum overhang of 2' is allowed for the trusses.
ADDITIONAL NOTES:1. The reinforcement (when required) must match the depth of the I-Joist.2. Where designated B/D, either detail (B or D) is valid.3. The closure at the end of the cantilever must be a minimum of 23/32" APA-Rated OSB (or equal).
Certain codes may require a thicker pr oduct for lateral load transfer.
4. For short cantilevers up to 6" long, use the Brick-Ledge Cantilever Tables on page 12.5. For conditions not shown, use LPs design software or contact your LP Engineered Wood Products
distributor for assistance.
6. Do not use a product where designated - without further analysis by a professional engineer.
Roof Truss Span
2'-0"
2'-0"
2'-0"max.
APA-Rated 23/32" OSB(or equal) closure oras required by code
LPIblocking
2'-0"max.
APA-Rated 23/32" OSB(or equal) closure oras required by code
LPIblocking
A: NO REINFORCEMENT REQUIRED W: WEB STIFFENERS ONLY
3. Follow across the row to the required joist spacing.
4. The letter represents the required detail.
Roof Truss 9-1/2" LPI 20W 9-1/2" LPI 32W 11-7/8" LPI 20W 11-7/8" LPI 32W Truss RoofLoad Span (ft) 12" 16" 19.2" 24" 12" 16" 19.2" 24" 12" 16" 19.2" 24" 12" 16" 19.2" 24" Span (ft) Load
22 A A A B/D A A A B/D A A A A A A A A 22
24 A A A B/D A A W B/D A A A A A A A A 24
26 A A B/D B/D A A B/D B/D A A A W A A A W 26
28 A A B/D B/D A A B/D B/D A A A W A A A W 28
30 A A B/D B/D A A B/D B/D A A A W A A A W 30
30 psf 32 A A B/D B/D A A B/D B/D A A A B/D A A A B/D 32 30 psf
34 A W B/D B/D A B/D B/D B/D A A A B/D A A A B/D 34
36 A B/D B/D B/D A B/D B/D B/D A A A B/D A A A B/D 36
38 A B/D B/D C A B/D B/D C A A W B/D A A W B/D 38
40 A B/D B/D C A B/D B/D C A A W B/D A A W B/D 40
42 A B/D B/D C A B/D B/D C A A W C A A W C 42
22 A A B/D B/D A A B/D B/D A A A W A A A W 22
24 A W B/D B/D A W B/D B/D A A A B/D A A A B/D 24
26 A B/D B/D B/D A B/D B/D B/D A A A B/D A A A B/D 26
28 A B/D B/D C A B/D B/D C A A W B/D A A W B/D 28
30 A B/D B/D C A B/D B/D C A A W C A A W C 30
40 psf 32 A B/D B/D C A B/D B/D C A A W C A A W C 32 40 psf34 A B/D B/D - A B/D B/D C A A B/D C A A B/D C 34
36 A B/D C - A B/D C - A W B/D C A W B/D C 36
38 W B/D C - B/D B/D C - A W B/D C A W B/D C 38
40 B/D B/D C - B/D B/D C - A W C - A W C - 40
42 B/D B/D C - B/D B/D C - A B/D C - A B/D C - 42
22 A B/D B/D C A B/D B/D C A A W B/D A A W B/D 22
24 A B/D B/D C A B/D B/D C A A W C A A W C 24
26 A B/D B/D C A B/D B/D C A A B/D C A A B/D C 26
28 A B/D C - A B/D C - A W B/D C A W B/D C 28
30 W B/D C - B/D B/D C - A W B/D - A W B/D - 30
50 psf 32 B/D B/D C - B/D B/D C - A W C - A W C - 32 50 psf
34 B/D B/D C - B/D B/D C - A B/D C - A B/D C - 34
36 B/D C - - B/D C - - A B/D C - A B/D C - 36
38 B/D C - - B/D C - - A B/D C - A B/D C - 38
40 B/D C - - B/D C - - W C - - W C - - 40
42 B/D C - - B/D C - - W C - - W C - - 42
22 A B/D B/D - A B/D B/D - A W B/D C A W B/D C 22
24 W B/D C - B/D B/D C - A W B/D C A W B/D C 24
26 B/D B/D C - B/D B/D C - A W C - A W C - 26
28 B/D B/D C - B/D B/D C - A B/D C - A B/D C - 28
30 B/D C - - B/D C - - A B/D C - A B/D C - 30
60 psf 32 B/D C - - B/D C - - W C C - W C C - 32 60 psf
34 B/D C - - B/D C - - W C - - W C - - 34
36 B/D C - - B/D C - - W C - - W C - - 36
38 B/D - - - B/D - - - W C - - W C - - 38
40 B/D - - - B/D - - - B/D C - - B/D C - - 40
42 C - - - C - - - B/D - - - B/D - - - 42
ROO
FTRUSSSPANWITH2'OVERHANG
-
7/30/2019 lp_i-joists_20-32 (1).pdf
11/1611
Load-Bearing Cantilever Tables: 14" & 16"
2005 Louisiana-Pacific Corporation
LPIblocking
2'-0"max.
APA-Rated 23/32" OSB(or equal) reinforcement
one side, 4'-0" long min.
Attach reinforcement to top andbottom flanges with 8d nails at 6" oc
2'-0"min.
APA-Rated 23/32" OSB(or equal) reinforcement
both sides, 4'-0" long min.
LPIblocking
2'-0"max.2'-0"min.
APA-Rated 23/32" OSB(or equal) closure or as
required by code
Attach reinforcement to top and bottom flangeswith 8d nails at 6" oc both sides with nails staggered to avoid splitting
LP Rim Boardreinforcement one
side, 4'-0" long min.
LPIblocking
2'-0"max.2'-0"min.
Attach reinforcement to topand bottom flanges with 8d nails at 6" oc
APA-Rated 23/32" OSB(or equal) closure or
as required by code
APA-Rated 23/32" OSB(or equal) closure or
as required by code
B: 23/32" OSB (OR EQUAL) REINFORCEMENTOne Side Only
C: 23/32" OSB (OR EQUAL) REINFORCEMENTBoth Sides
D: 1" OR 1-1/8" LP RIM BOARDMay be Substituted for Detail B
ROO
FTRUSSSPANWITH2'OVERHANG
Roof Truss 14" LPI 20W 14" LPI 32W 16" LPI 32W Truss RoofLoad Span (ft) 12" 16" 19.2" 24" 12" 16" 19.2" 24" 12" 16" 19.2" 24" Sp an (ft ) Lo ad
22 A A A A A A A A A A A A 22
24 A A A A A A A A A A A A 24
26 A A A A A A A A A A A A 26
28 A A A A A A A A A A A A 28
30 A A A A A A A A A A A W 30
30 psf 32 A A A W A A A W A A A W 32 30 psf
34 A A A W A A A W A A A W 34
36 A A A W A A A W A A A W 36
38 A A A W A A A W A A A W 38
40 A A A W A A A W A A A W 40
42 A A A B/D A A A B/D A A W W 42
22 A A A A A A A A A A A W 22
24 A A A W A A A W A A A W 24
26 A A A W A A A W A A A W 26
28 A A A W A A A W A A A W 28
30 A A A W A A A W A A W W 30
40 psf 32 A A W B/D A A W B/D A A W B/D 32 40 psf34 A A W B/D A A W B/D A A W B/D 34
36 A A W B/D A A W B/D A A W B/D 36
38 A A W C A A W C A A W B/D 38
40 A A W C A A W C A W W B/D 40
42 A W B/D C A W B/D C A W W B/D 42
22 A A A W A A A W A A A W 22
24 A A A B/D A A A B/D A A W W 24
26 A A W B/D A A W B/D A A W B/D 26
28 A A W B/D A A W B/D A A W B/D 28
30 A A W C A A W C A A W B/D 30
50 psf 32 A A W C A A W C A W W B/D 32 50 psf
34 A W B/D C A W B/D C A W W C 34
36 A W B/D C A W B/D C A W B/D C 36
38 A W B/D - A W B/D - A W B/D - 38
40 A W C - A W C - A W B/D - 40
42 A W C - A W C - A W B/D - 42
22 A A W B/D A A W B/D A A W B/D 22
24 A A W C A A W C A A W B/D 24
26 A A W C A A W C A W W B/D 26
28 A W B/D C A W B/D C A W B/D C 28
30 A W B/D - A W B/D - A W B/D - 30
60 psf 32 A W C - A W C - A W B/D - 32 60 psf
34 A W C - A W C - A W B/D - 34
36 A B/D C - A B/D C - A B/D C - 36
38 A B/D C - A B/D C - W B/D C - 38
40 W C - - W C - - W B/D - - 40
42 W C - - W C - - W B/D - - 42
DESIGN ASSUMPTIONS:1. These tables are valid for joists selected from the Floor Span Tables in this design guide.2. The floor design loads mustnotexceed 40 psf Live and 25 psf Dead Load.
3. The maximum cantilever length is 2' (the amount of overhang).4. The wall load is assumed to be 100 plf.
5. Roof Load is the Total Load (Live plus Dead) on the roof trusses.6. Truss Span is the out-to-out distance of the truss bearing walls as shown on page 10.
7. A maximum overhang of 2' is allowed for the trusses.
ADDITIONAL NOTES:1. The reinforcement (when required) must match the depth of the I-Joist.2. Where designated B/D, either detail (B or D) is valid.3. The closure at the end of the cantilever must be a minimum of 23/32" APA-Rated OSB (or equal).
Certain codes may require a thicker product for lateral load transfer.
4. For short cantilevers up to 6" long, use the Brick-Ledge Cantilever Tables on page 12.5. For conditions not shown, use LPs design software or contact your LP Engineered Wood Products
distributor for assistance.
6. Do not use a product where designated - without further analysis by a professional engineer.
-
7/30/2019 lp_i-joists_20-32 (1).pdf
12/1612
Brick-Ledge Cantilevers
2005 Louisiana-Pacific Corporation
LP Rim Board orLPI blocking panel between I-Joists
Closure and/orflashing may be
required per localbuilding code
Full depth reinforcing
Web filler reinforcing
Provide vapor barrier/house wrapper local building code
Wall framing sheathing air gap
No reinforcing
Total Joist Reaction
Calculation
LP I-Joists can cantilever up to 6" to support a
load-bearing wall over a brick finish. Depending
on the Total Joist Reaction (TJR), the joists may
require reinforcement. If the TJR is less than the
End Bearing W/out Stiffeners (page 14), then no
reinforcement is required. If the TJR is greater
than the End Bearing W/out Stiffeners, but less
than the End Bearing With Stiffeners, then web
stiffeners must be installed at the bearing.
Otherwise, one of the reinforcing details from
below must be used.
Total Joist Reaction, TJR = FLR + WLR + RLR
Where: FLR = Floor Load Reaction
WLR = Wall Load Reaction
RLR = Roof Load Reaction,including any other floor,
ceiling or attic loads imposed
on wall
Blocking panels are required at the bearing, but are not shown for clarity* NOTE: Pilot holes required when using screws
Blocking panels are required at the bearing, but are not shown for clarity
WEB FILLER REINFORCING
23/32" APA-Rated OSB(or equal) fillers (both sides)
6"max.
Nail web filler with two rows of 3-10dor 12d box or equivalent gun nail, clinched
Use construction adhesive between surfaces
12"min.Leave
1/8" gap
For 14" and 16" I-Joists, web filler
(both sides) and OSB or plywoodreinforcing are required.(See left.)
Nail or screw reinforcing with3-6d or 8d box nails or 6 x 1-1/2"wood screws into both flanges*
Reinforcing mustbe same depth
as I-Joist
Construction adhesive is recommendedbetween surfaces
2" min. fromI-Joist end
6"max.
23/32"reinforcing-12"min.
1"reinforcing-18"min.
FULL-DEPTH REINFORCINGOne Side
SeriesWeb Filler Thickness Reaction Capacity
(in) (lbs)
LPI 20W 23/32" APA-Rated OSB (or Equal) 2600
LPI 32W 23/32" APA-Rated OSB (or Equal) 2600
SeriesReaction Capacity (lbs)
23/32 " APA -Rated O SB ( or E qu al ) 1 " or 1 -1 /8 " LP R im Board
LPI 20W 3500 3800
LPI 32W 3500 3800
-
7/30/2019 lp_i-joists_20-32 (1).pdf
13/16
EXAMPLE 1:
Brick-Ledge Cantilevers
2005 Louisiana-Pacific Corporation13
I-Joist: 9-1/2" LPI20W Allowable End Bearing = 950 lbs. W/out Stiffeners, 1230 lbs. With Stiffeners (page 14)
Design Loads: Floor:40/10 psf Floor System: Joist Span = 11' Roof System: Roof Span = 22'
Roof: 20/10 psf Joist Overhang = 5" Roof Overhang = 1'
Wall: 80 plf Joist Spacing = 16"
FLR = (Joist Span / 2 + Joist Overhang / 12) * Design Floor Load * (Joist Spacing / 12)= (11' / 2 + 5" / 12) * (40 psf + 10 psf) * (16" / 12)
= 394 lbs.
WLR = Design Wall Load * (Joist Spacing / 12)
= 80 plf * (16" / 12)
= 107 lbs.
RLR = (Roof Span / 2 + Roof Overhang) * Design Roof Load * (Joist Spacing / 12)
= (22' / 2 + 1') * (20 psf + 10 psf) * (16" / 12)
= 480 lbs.
TJR = 394 + 107 + 480
= 981 lbs.
Since the Total Joist Reaction, 981 lbs., is greater than the End Bearing W/out Stiffeners, 950 lbs., but less than End Bearing With Stiffeners, 1230 lbs.,this joist only requires the installation of web stiffeners at the bearing.
EXAMPLE 2:
I-Joist: 11-7/8" LPI 32W Allowable End Bearing = 1025 lbs. W/out Stiffeners, 1350 lbs. With Stiffeners (page 14)
Design Loads: Floor:40/15 psf Floor System: Joist Span = 16' Roof System: Roof Span = 32'
Roof: 30/15 psf Joist Overhang = 5" Roof Overhang = 2'
Wall: 100 plf Joist Spacing = 24"
FLR = (Joist Span / 2 + Joist Overhang / 12) * Design Floor Load * (Joist Spacing / 12)
= (16' / 2 + 5" / 12) * (40 psf + 15 psf) * (24" / 12)
= 926 lbs.
WLR = Design Wall Load * (Joist Spacing / 12)
= 100 plf * (24" / 12)
= 200 lbs.
RLR = (Roof Span / 2 + Roof Overhang) * Design Roof Load * (Joist Spacing / 12)
= (32' / 2 + 2') * (30 psf + 15 psf) * (24" / 12)
= 1620 lbs.
TJR = 926 + 200 + 1620
= 2746 lbs.
Since the Total Joist Reaction, 2746 lbs., is greater than the End Bearing With Stiffeners, 1350 lbs., this joist needs reinforcing.The Full-Depth Reinforcing detail has a capacity of 3500 lbs. with 23/32" APA-Rated OSB (or Equal) attached to one side.
-
7/30/2019 lp_i-joists_20-32 (1).pdf
14/1614 2005 Louisiana-Pacific Corporation
Product Specifications & Design Values
* Nail Size is for common or box nails.
RIM AND BLOCKING CAPACITY
NOTES:1. Lateral Load Capacity for all series above = 200 plf.2. For LPI Rim or Blocking used for lateral load transfer, nail to bearing plate with same nail schedule as the deck-to-rim connection.
Uniform
Depth Load
(plf)
9-1/2" 1900
11-7/8" 1760
14" 1600
9-1/2" 2200
11-7/8" 2200
14" 1600
16" 1500
Series
LPI 20W
LPI 32W
RIM AND BLOCKING NAIL SCHEDULE
Series
LPI 20W
&
LPI 32W
LPI 20W
LPI 32W
2-1/2"
9-1/2,"
11-7/8"
or 14""
3/8"
1-1/2"
2-1/2"
9-1/2,"
11-7/8",
14"" or 16"
3/8"
1-1/2"
*Includes 16d Sinker (3-1/4")
NOTES:1. Moment, Shear and Reaction Capacity values are for normal load duration and may be adjusted according to code.
2. When calculating deflection, both bending and shear deformation must be determined as follows:
For simple span, uniform load: = + Where: = deflection in inches EI= bending sti ffness from table
w = uni for m load i n p lf K = shear s ti ffness f rom tab leL = design span in feet
3. The Moment capacity may be increased 7% for repetitive member applications.4. These design values are based on the product being used in a dry, well ventilated environment where the moisture content will not exceed 16% such as
in most covered structures. These products are intended to resist the effects of moisture on structural performance from normal construction delays but arenot intended for permanent exposure to the weather.
22.5wL4
wL2
El K
DESIGN VALUES
Series
LPI 20W
LPI 32W
Weight Moment EI (x 106) K (x 10
6) Shear
Reaction Capacity (lbs)
Depth End Bearing (1-1/2" min.) Interior Bearing (3-1/2" min.)
(plf) (lb-ft) (lb-in2) (lb-ft/in) (lbs) W/out Stiffeners With Stiffeners W/out Stiffeners With Stiffeners
9-1/2" 2.6 2600 176 0.358 1230 950 1230 2000 2025
11-7/8" 2.9 3406 300 0.438 1350 1025 1350 2350 2525
14" 3.1 4200 441 0.512 1620 1190 1620 2425 3490
9-1/2" 2.6 3195 243 0.213 1250 950 1250 2000 2025
11-7/8" 2.9 4275 406 0.267 1350 1025 1350 2350 2525
14" 3.1 5255 589 0.313 1620 1190 1620 2500 349016" 3.3 6180 791 0.358 1800 1200 1800 2500 3700
Nail SizeMinimum Nail Distance
OC End
8d (2-1/2") Box 2" 1"
10d (3") & 12d (3-1/4") Box 2" 1"
10d (3") & 12d (3-1/4") Common* 3" 1-1/2"
16d (3-1/2") Common 4" 4"
WEB STIFFENER REQUIREMENTS
DepthMinimum Maximum
Nail Size* Nail QtyThickness Height
9-1/2" 23/32" 6-3/8" 8d (2-1/2") 3
11-7/8" 23/32" 8-3/4" 8d (2-1/2") 3
14" 23/32" 10-7/8" 8d (2-1/2") 3
16" 23/32" 12-7/8" 8d (2-1/2") 3
Series
LPI 20W
&
LPI 32W
NOTES:1. Web stiffeners, when required, must be installed
in pairs one to each side of the web. Webstiffeners are always required for the BirdsMouth roof bearing detail.
2. Web stiffeners should be cut to fit between theflanges of the I-Joist, leaving a minimum 1/8"gap (1" maximum). At bearing locations, thestiffeners should be installed tight to the bottom
flange with the gap to the top flange. At locationsof concentrated loads, the stiffeners should beinstalled tight to the top flange with the gap tothe bottom flange.
3. Web stiffeners should be cut from APA-Rated OSB(or equal). 2X lumber is permissible. Do NOT use1X lumber as it tends to split.
4. Web stiffeners should be the same width as thebearing surface, with a minimum of 3-1/2".
5. See Web Stiffener Requirements table above forminimum stiffener thickness, maximum stiffenerheight and required nailing.
End support
min. 1-1/2" bearing
Intermediate support
min. 3-1/2" bearing
Nails to be equallyspaced, staggered and driven
alternately from each face.Clinch nails where possible.
1/8" min. gap
1/8" min. gap1/8" min. gap
1/8" min. gapConcentrated load
WEB STIFFENER REQUIREMENTS
-
7/30/2019 lp_i-joists_20-32 (1).pdf
15/16 2005 Louisiana-Pacific Corporation15
TOP-MOUNT FACE-MOUNT45 RAFTER- RAFTER-
SKEWED TO-RIDGE TO-PLATE
Framing Connectors
Series DepthTop-Mount Face-Mount 45 Skewed Rafter-To-Ridge Rafter-To-Plate
Single Double Single Double Single Single Single
9-1/2" ITT39.5 MIT39.5-2 IUT310 HU310-2* SUR/L310* LSSUH310* VPA3
LPI 20W 11-7/8" ITT311.88 MIT311.88-2 IUT312 HU312-2* SUR/L310* LSSUH310* VPA3
14" ITT314 MIT314-2 IUT314 HU314-2* SUR/L314* LSSUH310* VPA3
9-1/2" ITT39.5 MIT39.5-2 IUT310 HU310-2* SUR/L310* LSSUH310* VPA3
11-7/8" ITT311.88 MIT311.88-2 IUT312 HU312-2* SUR/L310* LSSUH310* VPA3LPI 32W
14" ITT314 MIT314-2 IUT314 HU314-2* SUR/L314* LSSUH310* VPA3
16" ITT316 WPI316-2* IUT316 HU314-2* SUR/L314* LSSUH310* ** VPA3
Series DepthTop-Mount Face-Mount 45 Skewed Rafter-To-Ridge Rafter-To-Plate
Single Double Single Double Single Single Single
9-1/2" THO25950 THO25950-2* THF25925 THF25925-2* SKH310R/L* TMU25* TMP25 or TMPH25*
LPI 20W 11-7/8" THO25118 THO25118-2* THF25112 THF25112-2* SKH312R/L* TMU25* TMP25 or TMPH25*
14" THO25140 THO25140-2* THF25140 THF25140-2* SKH312R/L* TMU25* TMP25 or TMPH25*
9-1/2" THO25950 THO25950-2* THF25925 THF25925-2* SKH310R/L* TMU25* TMP25 or TMPH25*
11-7/8" THO25118 THO25118-2* THF25112 THF25112-2* SKH312R/L* TMU25* TMP25 or TMPH25*LPI 32W
14" THO25140 THO25140-2* THF25140 THF25140-2* SKH312R/L* TMU25* TMP25 or TMPH25*
16" THO25160 THO25160-2* THF25160 THF25160-2* SKH312R/L* TMU25* ** TMP25 or TMPH25*
USP LUMBER CONNECTORS
The above connectors are manufactured by Simpson Strong-Tie Co., Inc.To verify connector suitability for a particular application, refer to the current Simpson St rong-Tie Connector catalog.
The above connectors are manufactured by USP (United Steel Products Company).To verify connector suitability for a particular application, refer to the current USP Lumber Connectors catalog.
GENERAL NOTES:
* Web fillers required for properinstallation of hanger.Refer to Engineered WoodProduct Guide for filler sizes.
** Hanger is less than 60% of joistdepth. Additional rotationresistance is required.Refer to the appropriate hangermanufacturers catalog for details.
SIMPSON STRONG-TIE
-
7/30/2019 lp_i-joists_20-32 (1).pdf
16/16
LP is a registered trademark of Louisiana-Pacific Corporation. 2005
Louisiana-Pacific Corporation. All rights reserved. Printed in USA. MW 10M
Specifications (details) subject to change without notice.
EW6120BR 4/05
For more information on the full line of
LP Engineered Wood Products or the nearest
distributor, please contact 1.800.999.9105
or e-mail [email protected].
Visit our web site at www.lpcorp.com .