    LPI 20W/32W

    Technical GuideFloor & Roof Applications

    Floor Span Tables: Simple Span Applications 2

    Floor Span Tables: Continuous Span Applications 3

    Uniform Floor Load (PLF) Tables 4

    Uniform Roof Load (PLF) Tables 5

    Roof Span Tables: Low Slope (6:12 or less) 6

    Roof Span Tables: High Slope (over 6:12 thru 12:12) 7

    Web Hole Specifications: Circular Holes 8

    Web Hole Specifications: Rectangular Holes 9

    Load-Bearing Cantilever Tables: 9-1/2" & 11-7/8" 10

    Load-Bearing Cantilever Tables: 14" & 16" 11

    Brick-Ledge Cantilevers 12-13

    Product Specifications & Design Values 14

    Framing Connectors 15

    Warranty Back Page

    is guide must be used in conjunction with the Engineered Wood Product Guide.

  • 7/30/2019 lp_i-joists_20-32 (1).pdf

    2/162

    Floor Span Tables: Simple Span Applications

    2005 Louisiana-Pacific Corporation

    Span

    Simple (single)Span Application

    40 PSF LIVE LOAD, 10 PSF DEAD LOAD

    Series DepthL/480 L / 360

    12" oc 16" oc 19.2" oc 24" oc 12" oc 16" oc 19.2" oc 24" oc

    9-1/2" 17'-3" 15'-9" 15'-0" 14'-1" 19'-2" 17'-6" 16'-6" 14'-9"

    LPI 20W 11-7/8" 20'-7" 18'-9" 17'-11" 16'-9" 22'-9" 20'-9" 18'-11" 16'-11"

    14" 23'-5" 21'-4" 20'-4" 18'-10" 25'-10" 23'-1" 21'-0" 18'-10"

    9-1/2" 18'-7" 16'-10" 15'-11" 14'-10" 20'-8" 18'-9" 17'-10" 16'-4"

    LPI 32W11-7/8" 22'-1" 20'-0" 18'-11" 17'-7" 24'-6" 22'-3" 21'-1" 19'-0"

    14" 25'-0" 22'-8" 21'-5" 19'-11" 27'-9" 25'-2" 23'-7" 21'-1"

    16" 27'-7" 25'-0" 23'-8" 22'-0" 30'-8" 27'-10" 25'-7" 22'-10"

    DESIGN ASSUMPTIONS:1. The spans listed are the clear distance between supports.2. The spans are based on uniform loads only.

    3. These tables reflect the additional stiffness provided by the appropriate span-rated floorsheathing glued and nailed to the top flange of the joists.

    4. Live load deflection has been limited to L/480 or L/360 as indicated in the tables above.5. Total deflection has been limited to L/240. Those spans that exceed 3/4" of total deflection

    are shown in bold.6. A load sharing (repetitive member) increase has been applied. This increase is based

    on the attachment of a proper deck to three or more joists, spaced no more than 24" oc.7. The spans are based on the minimum required bearings as listed on page 14.

    ADDITIONAL NOTES:1. Web stiffeners are not required for any of the spans in the Simple Span tables. Web fillers are required

    for joists seated in hangers that do not laterally support the top flange.2. L/360 is the minimum deflection criteria allowed per code, which allows the maximum amount of deflection

    in the floor.3. These spans are not evaluated for vibration.4. Bridging, blocking, a direct-applied ceiling and/or bottom-flange bracing, though not required for vertical

    load capacity, can improve floor vibration and bounce.

    5. For conditions not shown, use the Uniform Floor Load (PLF) tables or contact your LP Engineered WoodProducts distributor for assistance.

    TO USE:

    1. Select the appropriate table based on the project design loads.2. Select the L/480 or L/360 section of that table, as required.3. Find a span that meets or exceeds the design span.4. Read the corresponding joist depth and spacing.

    Caution: For floor systems that require both simple span and continuous span joists,it is a good idea to check both before selecting a joist. Some conditions are controlledby continuous span strength rather than simple span deflection.

    40 PSF LIVE LOAD, 15 PSF DEAD LOAD

    Series DepthL/480 L / 360

    12" oc 16" oc 19.2" oc 24" oc 12" oc 16" oc 19.2" oc 24" oc

    9-1/2" 17'-3" 15'-9" 15'-0" 14'-1" 19'-2" 17'-3" 15'-9" 14'-1"

    LPI 20W 11-7/8" 20'-7" 18'-9" 17'-11" 16'-1" 22'-9" 19'-9" 18'-0" 16'-1"

    14" 23'-5" 21'-4" 20'-1" 17'-11" 25'-5" 22'-0" 20'-1" 17'-11"

    9-1/2" 18'-7" 16'-10" 15'-11" 14'-10" 20'-8" 18'-9" 17'-6" 15'-7"

    LPI 32W11-7/8" 22'-1" 20'-0" 18'-11" 17'-7" 24'-6" 22'-2" 20'-3" 18'-1"

    14" 25'-0" 22'-8" 21'-5" 19'-9" 27'-9" 24'-7" 22'-5" 20'-1"

    16" 27'-7" 25'-0" 23'-8" 21'-6" 30'-8" 26'-8" 24'-4" 21'-6"

    40 PSF LIVE LOAD, 25 PSF DEAD LOAD

    Series DepthL/480 L / 360

    12" oc 16" oc 19.2" oc 24" oc 12" oc 16" oc 19.2" oc 24" oc

    9-1/2" 17'-3" 15'-9" 14'-6" 12'-11" 18'-4" 15'-10" 14'-6" 12'-11"

    LPI 20W 11-7/8" 20'-7" 18'-2" 16'-7" 14'-10" 21'-0" 18'-2" 16'-7" 14'-10"

    14" 23'-4" 20'-2" 18'-5" 16'-6" 23'-4" 20'-2" 18'-5" 16'-6"9-1/2" 18'-7" 16'-10" 15'-11" 14'-4" 20'-1" 17'-7" 16'-1" 14'-4"

    LPI 32W11-7/8" 22'-1" 20'-0" 18'-7" 15'-6" 23'-7" 20'-5" 18'-7" 15'-6"

    14" 25'-0" 22'-7" 20'-8" 16'-8" 26'-2" 22'-7" 20'-8" 18'-0"

    16" 27'-7" 24'-6" 22'-5" 18'-2" 28'-4" 24'-6" 22'-5" 18'-2"

    ACTUAL DEFLECTIONBASED ON SPAN AND LIMIT

    Span (ft) L/480 L/360 L/240

    10 1/4" 5/16" 1/2"

    12 5/16" 3/8" 5/8"

    14 3/8" 7/16" 11/16"

    16 3/8" 9/16" 13/16"

    18 7/16" 5/8" 7/8"

    20 1/2" 11/16" 1"

    22 9/16" 3/4" 1-1/8"

    24 5/8" 13/16" 1-3/16"

    26 5/8" 7/8" 1-5/16"

    28 11/16" 15/16" 1-3/8"

    30 3/4" 1" 1-1/2"

    * Deflections rounded to the nearest 1/16".

  • 7/30/2019 lp_i-joists_20-32 (1).pdf

    3/16

    40 PSF LIVE LOAD, 25 PSF DEAD LOAD @ L/480

    40 PSF LIVE LOAD, 15 PSF DEAD LOAD @ L/480

    3

    Floor Span Tables: Continuous Span Applications

    2005 Louisiana-Pacific Corporation

    SpanSpan Span

    Continuous (multiple)Span Application

    TO USE:

    1. Select the appropriate table based on the project design loads.2. Select the section with or without web stiffeners, as needed.3. Find a span that meets or exceeds the design span.4. Read the corresponding joist depth and spacing.

    Caution: For floor systems that require both simple span and continuous span joists,it is a good idea to check both before selecting a joist. Some conditions are controlledby simple span deflection rather than continuous span strength.

    DESIGN ASSUMPTIONS:1. The spans listed are the clear distance between supports.2. The spans are based on uniform loads only.3. These tables reflect the additional stiffness provided by the appropriate span-rated floor

    sheathing glued and nailed to the top flange of the joists.4. Live load deflection has been limited to L/480.5. Total deflection has been limited to L/240. Those spans that exceed 3/4" of total deflection

    are shown in bold.6. A load sharing (repetitive member) increase has been applied. This increase is based on

    the attachment of a proper deck to three or more joists, spaced no more than 24" oc.

    7. The spans are based on the minimum required bearings as listed on page 14.

    ADDITIONAL NOTES:1. Web stiffeners are only required for the spans in the With Web Stiffeners section of each table.

    A - indicates that there is no increase in span through the use of web stiffeners. Web fillers are requiredfor joists seated in hangers that do not laterally support the top flange.

    2. The design of continuous spans is based on the longest span. The shortest span must not be less than50% of the longest span.

    3. These spans are not evaluated for vibration.4. Bridging, blocking, a direct-applied ceiling and/or bottom-flange bracing, though not required for vertical

    load capacity, can improve floor vibration and bounce.5. For conditions not shown, use the Uniform Floor Load (PLF) tables or contact your LP Engineered Wood

    Products distributor for assistance.

    40 PSF LIVE LOAD, 10 PSF DEAD LOAD @ L/480

    Series DepthWithout Web Stiffeners With Web Stiffeners

    12" oc 16" oc 19.2" oc 24" oc 12" oc 16" oc 19.2" oc 24" oc

    9-1/2" 18'-10" 17'-2" 16'-4" 14'-8" - - - -

    LPI 20W 11-7/8" 22'-5" 20'-5" 18'-10" 16'-10" - - - -

    14" 25'-6" 23'-0" 20'-11" 18'-9" - - - -

    9-1/2" 20'-2" 18'-3" 17'-3" 15'-8" - - - 15'-11"

    LPI 32W11-7/8" 24'-0" 21'-9" 20'-6" 18'-6" - - - 18'-11"

    14" 27'-10" 24'-7" 23'-3" 19'-8" - - - 21'-0"

    16" 30'-10" 27'-11" 24'-8" 19'-8" - - 25'-6" 22'-9"

    Series DepthWithout Web Stiffeners With Web Stiffeners

    12" oc 16" oc 19.2" oc 24" oc 12" oc 16" oc 19.2" oc 24" oc

    9-1/2" 18'-10" 17'-2" 15'-8" 14'-0" - - - -

    LPI 20W 11-7/8" 22'-5" 19'-8" 17'-11" 16'-0" - - - -

    14" 25'-4" 21'-11" 20'-0" 17'-4" - - - 17'-10"

    9-1/2" 20'-2" 18'-3" 17'-3" 14'-3" - - - 14'-5"

    LPI 32W11-7/8" 24'-0" 21'-9" 20'-2" 16'-9" - - - 18'-0"

    14" 27'-10" 24'-6" 22'-4" 17'-10" - - - 20'-0"

    16" 30'-9" 26'-7" 24'-5" 17'-10" - - 24'-3" 21'-8"

    Series DepthWithout Web Stiffeners With Web Stiffeners

    12" oc 16" oc 19.2" oc 24" oc 12" oc 16" oc 19.2" oc 24" oc

    9-1/2" 18'-3" 15'-9" 14'-5" 12'-0" - - - 12'-2"

    LPI 20W 11-7/8" 20'-11" 18'-1" 16'-6" 14'-2" - - - 14'-9"

    14" 23'-3" 20'-1" 18'-4" 14'-7" - - - 16'-5"9-1/2" 20'-2" 17'-6" 15'-1" 12'-0" - - 15'-3" 12'-2"

    LPI 32W11-7/8" 23'-6" 20'-4" 17'-9" 14'-2" - - 18'-6" 15'-3"

    14" 26'-1" 22'-6" 18'-11" 15'-1" - - 20'-7" 18'-4"

    16" 28'-3" 22'-9" 18'-11" 15'-1" - 24'-5" 22'-4" 19'-11"

    ACTUAL DEFLECTIONBASED ON SPAN AND LIMIT

    Span (ft) L/480 L/360 L/240

    10 1/4" 5/16" 1/2"

    12 5/16" 3/8" 5/8"

    14 3/8" 7/16" 11/16"

    16 3/8" 9/16" 13/16"

    18 7/16" 5/8" 7/8"

    20 1/2" 11/16" 1"

    22 9/16" 3/4" 1-1/8"

    24 5/8" 13/16" 1-3/16"

    26 5/8" 7/8" 1-5/16"

    28 11/16" 15/16" 1-3/8"

    30 3/4" 1" 1-1/2"

    * Deflections rounded to the nearest 1/16".

  • 7/30/2019 lp_i-joists_20-32 (1).pdf

    4/164

    Uniform Floor Load (PLF) Tables

    2005 Louisiana-Pacific Corporation

    EXAMPLE:

    Select an I-Joist for a 17'-6" clear span supporting 40 psf Live Load and 20 psf Dead Load,spaced 16" oc, at an L/480 deflection limit.

    1. Design Total Load = (40 + 20) * (16 / 12) = 80 plfDesign Live Load = 40 * (16 / 12) = 54 plf

    2. Select the row corresponding to an 18' span.

    3. The first I-Joist to exceed both Total Load and L/480:11-7/8" LPI 32W can support 102 plf Total and 62 plf Live @ L/480

    TO USE:

    1. Select the span required.2. Compare the design total load to the Total Load column and compare the design live load

    to either the L/480 or L/360 column as needed.3. Select a product that exceeds both the design total and live loads.

    DESIGN ASSUMPTIONS:

    1. Span is the clear distance between supports and is valid for simpleor continuous spans.

    2. The values are based on uniform loads of standard duration.3. These tables assume that the joist is NOT a repetitive member, therefore load

    sharing has not been applied. Also, the deflection values do not reflect anyadditional stiffness due to composite action.

    4. Total deflection has been limited to L/ 240. Long term deflection (creep) has NOTbeen considered.

    5. These tables assume full lateral support of the compression flange. Full supportis considered to be a maximum unbraced length of 24".

    6. The values are based on the minimum required bearings as listed on page 14.

    ADDITIONAL NOTES:

    1. The values represent the capacity of the joist in pounds per lineal foot (plf) of length.2. The designer must check both the Total Load and the appropriate Live Load columns.3. To design for a double I-Joist, the values in these tables can be doubled, or the design loads on the joist may be halved to verify the

    capacity of each ply. The capacity is additive.4. Web stiffeners arenotrequired for these spans and loads. Web fillersare required for joists seated in hangers that do not laterally

    support the top flange.5. Where the Live Load is blank, the Total Load governs the design.6. Do not use a product where designated - without further analysis by a professional engineer.

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    21

    22

    23

    24

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    21

    22

    23

    24

    Span

    (ft)

    Span

    (ft)

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    1819

    20

    21

    22

    23

    24

    25

    26

    27

    28

    29

    30

    31

    32

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    1819

    20

    21

    22

    23

    24

    25

    26

    27

    28

    29

    30

    31

    32

    Span

    (ft)

    Span

    (ft)

    14" LPI 20W 14" LPI 32W 16" LPI 32W

    Live Load Total Live Load Total Live Load Total

    L /480 L /360 Load L /480 L /360 Load L /480 L /360 Load

    234 241 241

    209 215 215

    188 194 194

    172 177 177

    158 162 162

    146 150 150

    135 140 140

    121 127 130 130

    101 119 118 122 122

    86 112 101 115 115

    73 98 101 87 109 10963 84 91 76 101 103 99 103

    54 73 82 66 88 98 86 98

    47 63 74 58 77 93 76 94

    41 55 68 51 68 85 67 89

    36 49 62 45 61 78 60 80 85

    32 43 57 40 54 71 53 71 82

    29 38 52 36 48 66 47 63 77

    26 34 48 32 43 61 43 57 71

    23 31 45 29 39 56 38 51 66

    21 28 42 26 35 52 35 46 62

    18 25 37 24 32 48 31 42 57

    17 22 34 21 29 43 29 38 54

    15 20 31 19 26 39 26 35 50

    - - - - - - 24 32 47

    9-1/2" LPI 20W 9-1/2" LPI 32W 11-7/8" LPI 20W 11-7/8" LPI 32W

    Live Load Total Live Load Total Live Load Total Live Load TotalL /480 L /360 Load L /480 L /360 Load L /480 L /360 Load L /480 L /360 Load

    193 193 227 227

    172 172 202 202

    155 155 155 183 183

    120 141 139 141 166 166

    95 127 130 112 130 153 153

    76 102 119 92 120 125 141 141

    62 83 103 76 101 112 102 131 119 131

    51 68 89 63 85 104 85 113 117 100 123

    43 57 79 53 71 97 71 94 103 85 113 115

    36 48 70 45 61 86 60 80 92 72 97 108

    30 41 61 39 52 77 51 68 82 62 83 102

    26 35 52 33 45 67 43 58 73 54 72 92

    22 30 45 29 39 58 38 50 66 47 63 83

    19 26 39 25 34 51 33 44 60 41 55 76

    - - - - - - 28 38 55 36 48 69

    - - - - - - 25 34 50 32 43 63

    - - - - - - 22 30 45 28 38 57

    PSF TO PLF CONVERSION TABLE

    OC Spacing Load (psf)

    (12") 20 25 30 35 40 45 50 55 60 65

    16" 27 34 40 47 54 60 67 74 80 87

    19.2" 32 40 48 56 64 72 80 88 96 104

    24" 40 50 60 70 80 90 100 110 120 130

  • 7/30/2019 lp_i-joists_20-32 (1).pdf

    5/16 2005 Louisiana-Pacific Corporation5

    ROOF SLOPE ADJUSTMENT FACTORS

    Uniform Roof Load (PLF) Tables

    Slope 2:12 3:12 4:12 5:12 6:12 7:12 8:12 9:12 10:12 11:12 12:12

    Factor 1.014 1.031 1.054 1.083 1.118 1.158 1.202 1.250 1.302 1.357 1.414

    9-1/2" LPI 20W 9-1/2" LPI 32W 11-7/8" LPI 20W 11-7/8" LPI 32WSpan

    Live Load Total Load Live Load Total Load Live Load Total Load Live Load Total LoadSpan

    (ft)L/240 Snow 115% Non-Snow 125% L/240 Snow 115% Non-Snow 125% L/240 Snow 115% Non-Snow 125% L /240 Snow 115% Non-Snow 125%

    (ft)

    8 222 241 222 241 261 284 261 284 8

    9 198 215 198 215 233 253 233 253 9

    10 179 194 179 194 210 228 210 228 10

    11 163 177 163 177 191 208 191 208 11

    12 149 162 149 162 176 191 176 191 12

    13 137 149 138 150 162 177 162 177 13

    14 125 118 128 128 140 151 164 151 164 14

    15 103 103 112 127 120 130 135 147 141 153 15

    16 86 91 98 107 111 121 119 129 132 144 16

    17 72 80 87 91 99 107 105 115 125 136 17

    18 61 72 78 78 88 96 102 94 102 125 118 128 18

    19 52 64 70 67 79 86 87 84 92 108 106 115 1920 45 58 60 58 71 78 76 76 83 94 96 104 20

    21 39 52 52 51 65 68 66 69 75 83 87 95 21

    22 34 46 46 45 59 60 57 63 69 73 79 86 22

    23 30 40 40 39 53 53 51 58 63 64 73 79 23

    24 26 35 35 35 47 47 45 53 58 57 67 72 24

    14" LPI 20W 14" LPI 32W 16" LPI 32WSpan

    Live Load Total Load Live Load Total Load Live Load Total LoadSpan

    (ft)L/240 Snow 115% Non-Snow 125% L/240 Snow 115% Non-Snow 125% L /240 Snow 115% Non-Snow 125%

    (ft)

    8 269 293 278 302 278 302 8

    9 240 261 248 269 248 269 9

    10 217 236 223 243 223 243 10

    11 197 215 204 221 204 221 11

    12 181 197 187 203 187 203 12

    13 168 182 173 188 173 188 13

    14 156 169 161 175 161 175 1415 146 158 150 163 150 163 15

    16 137 149 141 153 141 153 16

    17 129 140 133 144 133 144 17

    18 116 126 125 136 125 136 18

    19 104 113 119 129 119 129 19

    20 94 102 113 123 113 123 20

    21 85 93 107 116 108 117 21

    22 83 78 85 103 98 106 103 112 22

    23 73 71 77 91 89 97 98 107 23

    24 65 65 71 81 82 89 94 103 24

    25 58 60 66 72 76 82 95 89 97 25

    26 52 56 61 65 70 76 86 82 89 26

    27 46 52 56 58 65 70 77 76 83 27

    28 42 48 52 53 60 66 70 71 77 28

    29 37 45 49 48 56 61 63 66 72 29

    30 34 42 45 43 52 57 58 62 67 30

    31 31 39 41 39 49 53 52 58 63 31

    32 28 37 38 36 46 48 48 54 59 32

    EXAMPLE:

    Select an I-Joist for a 12'-8" horizontal clear span supporting 45 psf Snow (Live) Loadand 15 psf Dead Load, spaced 24" oc, with a roof slope of 6:12.

    1. Sloped Span = (12 + 8 / 12) * 1.118 = 14.16' use 15'

    2. Design Total Load = (45 + 15) * (24 / 12) = 120 plfDesign Live Load = 45 * (24 / 12) = 90 plf

    3. Select the row corresponding to a 15' span.

    4. The first I-Joist to exceed both Total Load for Snow (115%) and L/240:9-1/2" LPI 32W can support 120 plf Total Load (115%) Live Load does not control

    NOTE: For a live load deflection limit of L/360, the Uniform Floor Load Tables on page 4require an 11-7/8" LPI 20W, which can support 113 plf Live Load @ L/360.

    TO USE:

    1. Select the span required. For roofs with a slope of 2:12 or greater, the horizontal span must bemultiplied by the appropriate slope adjustment factor from the table at the bottom of this page.

    2. Compare the design total load to the appropriate Total Load column for Snow (115%) orNon-Snow (125%), and compare the design live load to the Live Load L/240 column.For live load deflection limits of L/360 or L/480, compare the design live load to the appropriateLive Load column from the Uniform Floor Load Tables on page 4.

    3. Select a product that exceeds both the design total and live loads.

    DESIGN ASSUMPTIONS:1. Span is the clear distance between supports, along the slope of the joist, and is valid for simple

    or continuous spans.2. The values are based on uniform loads only.3. These tables assume that the joist is NOT a repetitive member, therefore load sharing has not been

    applied. Also, the deflection values do not reflect any additional stiffness due to composite action.4. Total deflection has been limited to L/180. Long term deflection (creep) has NOT been considered.5. These tables assume full lateral support of the compression flange. Full support is considered to be

    a maximum unbraced length of 24".

    6. The values are based on the minimum required bearings as listed on page 14.

    ADDITIONAL NOTES:1. The values represent the capacity of the joist in pounds per lineal foot (plf) of length.2. The designer must check the appropriate Total Load column and the Live Load column.3. For roofs with a slope of 2:12 or greater, the horizontal span must be multiplied by the appropriate slope

    adjustment factor from the table at the bottom of this page.4. To design for a double I-Joist, the values in these tables can be doubled, or the design loads on the joist may

    be halved to verify the capacity of each ply. The capacity is additive.5. Web stiffeners arenotrequired for these spans and loads. Web fillersare required for joists seated in hangers

    that do not laterally support the top flange.

    6. Where the Live Load is blank, the Total Load governs the design.7. To design for a live load limit of L/ 360 or L/480, use the Uniform Floor Load tables.8. Do not use a product where designated - without further analysis by a professional engineer.

  • 7/30/2019 lp_i-joists_20-32 (1).pdf

    6/16

    Series Depth 16" oc 19.2" oc 24" oc

    Roof Dead Load 15 psf 20 psf 15 psf 20 psf 15 psf 20 psf

    9-1/2" 20'-9" 19'-9" 19'-6" 18'-7" 18'-1" 17'-2"

    LPI 20W 11-7/8" 24'-10" 23'-8" 23'-4" 22'-3" 21'-7" 20'-6"

    14" 28'-3" 26'-11" 26'-7" 25'-3" 24'-6" 22'-10"

    9-1/2" 22'-10" 21'-9" 21'-5" 20'-5" 19'-10" 18'-10"

    LPI 32W11-7/8" 27'-2" 25'-11" 25'-6" 24'-3" 23'-7" 22'-5"

    14" 30'-10" 29'-4" 28'-11" 27'-6" 26'-9" 25'-5"

    16" 34'-1" 32'-5" 31'-11" 30'-5" 29'-6" 27'-9"

    9-1/2" 19'-10" 19'-0" 18'-8" 17'-10" 17'-3" 16'-3"

    LPI 20W 11-7/8" 23'-9" 22'-9" 22'-2" 20'-10" 19'-10" 18'-7"

    14" 27'-0" 25'-4" 24'-8" 23'-2" 22'-0" 20'-8"

    9-1/2" 21'-10" 20'-11" 20'-6" 19'-7" 18'-11" 18'-0"

    LPI 32W11-7/8" 26'-0" 24'-11" 24'-5" 23'-4" 22'-3" 20'-10"

    14" 29'-6" 28'-3" 27'-7" 25'-11" 24'-8" 23'-2"

    16" 32'-7" 30'-10" 29'-11" 28'-1" 26'-9" 25'-1"

    9-1/2" 19'-1" 18'-4" 17'-11" 17'-3" 16'-4" 15'-5"

    LPI 20W 11-7/8" 22'-10" 21'-8" 20'-11" 19'-9" 18'-8" 17'-8"

    14" 25'-6" 24'-1" 23'-3" 22'-0" 20'-10" 19'-8"

    9-1/2" 21'-0" 20'-2" 19'-8" 18'-11" 18'-1" 17'-1"

    LPI 32W11-7/8" 25'-0" 24'-0" 23'-5" 22'-2" 21'-0" 19'-10"

    14" 28'-4" 27'-0" 26'-1" 24'-7" 23'-3" 22'-0"

    16" 31'-0" 29'-3" 28'-3" 26'-9" 25'-3" 22'-8"

    9-1/2" 17'-10" 17'-3" 16'-7" 15'-9" 14'-9" 14'-1"

    LPI 20W 11-7/8" 20'-10" 19'-10" 19'-0" 18'-1" 16'-11" 16'-2"

    14" 23'-2" 22'-1" 21'-1" 20'-2" 18'-10" 18'-0"

    9-1/2" 19'-7" 18'-11" 18'-4" 17'-6" 16'-5" 15'-0"

    LPI 32W11-7/8" 23'-4" 22'-3" 21'-4" 20'-4" 19'-0" 17'-8"

    14" 25'-11" 24'-9" 23'-8" 22'-6" 20'-7" 18'-10"

    16" 28'-1" 26'-10" 25'-8" 23'-8" 20'-7" 18'-10"

    9-1/2" 16'-9" 16'-1" 15'-3" 14'-8" 13'-7" 12'-10"

    LPI 20W 11-7/8" 19'-2" 18'-5" 17'-6" 16'-9" 15'-7" 15'-0"

    14" 21'-4" 20'-6" 19'-5" 18'-8" 16'-10" 15'-7"

    9-1/2" 18'-6" 17'-10" 16'-11" 16'-1" 13'-10" 12'-10"

    LPI 32W11-7/8" 21'-6" 20'-8" 19'-7" 18'-10" 16'-4" 15'-2"

    14" 23'-11" 22'-11" 21'-9" 20'-3" 17'-5" 16'-1"

    16" 25'-11" 24'-4" 21'-10" 20'-3" 17'-5" 16'-1"

    9-1/2" 15'-7" 15'-0" 14'-2" 13'-9" 11'-11" 11'-2"

    LPI 20W 11-7/8" 17'-10" 17'-3" 16'-4" 15'-9" 14'-1" 13'-2"

    14" 19'-10" 19'-2" 18'-1" 17'-1" 14'-7" 13'-8"

    9-1/2" 17'-4" 16'-8" 15'-0" 14'-1" 11'-11" 11'-2"

    LPI 32W11-7/8" 20'-1" 19'-4" 17'-8" 16'-7" 14'-1" 13'-2"

    14" 22'-3" 21'-3" 18'-10" 17'-8" 15'-0" 14'-1"

    16" 22'-8" 21'-3" 18'-10" 17'-8" 15'-0" 14'-1"

    6

    Roof Span Tables: Low Slope (6:12 or less)

    2005 Louisiana-Pacific Corporation

    TO USE:

    1. Select the appropriate set of tables based on roof slope.

    2. Select the section of that table that corresponds to the designlive load and load duration.

    3. Find a span that meets or exceeds the design span for theappropriate roof dead load (15 psf or 20 psf).

    4. Read the corresponding joist, depth and spacing.

    DESIGN ASSUMPTIONS:

    1. The spans listed are the horizontal clear distance between supports.Refer to the diagram below.

    2. The spans are based on uniform gravity loads only and havenotbeen evaluated for wind.

    3. These tables do notreflect any additional stiffness provided bythe roof sheathing.

    4. Live load deflection has been limited to L/240.

    5. Total load deflection has been limited to L/180.

    6. A load sharing (repetitive member) increase has been applied.This increase is based on the attachment of a proper deckto three or more joists, spaced no more than 24" oc.

    7. The spans are based on the minimum required bearings as listedon page 14.

    ADDITIONAL NOTES:

    1. Web stiffeners arenotrequired for any of the spans listed in these

    tables. Web stiffeners are required when using the birds mouthbearing detail. Web fillers are required for joists seated in hangersthat do not laterally support the top flange.

    2. The design of continuous spans is based on the longest span.The shortest span must not be less than 50% of the longest span.

    3. L/240 is the minimum deflection criteria allowed per code for roofjoists supporting non-plaster ceilings. Verify deflection limits withlocal code requirements.

    4. Roof joists must have a minimum slope of 1/4" per foot (1/4:12)for positive drainage.

    5. For conditions not shown, use the Uniform Roof Load (PLF) Tablesor contact your LP Engineered Wood Products distributor for assistance.

    6. Roof applications in high wind areas require special analysis whichmay result in reduced spans and special connectors to resist uplift.

    ACTUAL DEFLECTIONBASED ON SPAN AND LIMIT

    * Deflections rounded to the nearest 1/16".

    Span (ft) L/360 L/240 L/180

    10 5/16" 1/2" 11/16"

    12 3/8" 5/8" 13/16"

    14 7/16" 11/16" 15/16"

    16 9/16" 13/16" 1-1/16"

    18 5/8" 7/8" 1-3/16"

    20 11/16" 1" 1-5/16"

    22 3/4" 1-1/8" 1-7/16"

    24 13/16" 1-3/16" 1-5/8"

    26 7/8" 1-5/16" 1-3/4"

    28 15/16" 1-3/8" 1-7/8"

    30 1" 1-1/2" 2"

    20psf

    125%

    Non-

    Snow

    25psf

    115%

    Snow

    30psf

    115%

    Snow

    40

    psf

    115%

    Snow

    50psf

    115%

    Snow

    60psf

    115%

    Snow

    ROOF

    LIVE

    LOAD

    Horizontal Span

    12

    Pitch

    edSpa

    n

    ROOF JOIST SPAN

    Rise

    RoofSlope=R

    ise:

    12

  • 7/30/2019 lp_i-joists_20-32 (1).pdf

    7/16

    Roof Span Tables: High Slope (over 6:12 thru 12:12)

    2005 Louisiana-Pacific Corporation7

    ACTUAL DEFLECTIONBASED ON SPAN AND LIMIT

    * Deflections rounded to the nearest 1/16".

    Span (ft) L/360 L/240 L/180

    10 5/16" 1/2" 11/16"

    12 3/8" 5/8" 13/16"

    14 7/16" 11/16" 15/16"

    16 9/16" 13/16" 1-1/16"

    18 5/8" 7/8" 1-3/16"

    20 11/16" 1" 1-5/16"

    22 3/4" 1-1/8" 1-7/16"

    24 13/16" 1-3/16" 1-5/8"

    26 7/8" 1-5/16" 1-3/4"

    28 15/16" 1-3/8" 1-7/8"

    30 1" 1-1/2" 2"

    Series Depth 16" oc 19.2" oc 24" oc

    Roof Dead Load 15 psf 20 psf 15 psf 20 psf 15 psf 20 psf

    9-1/2" 18'-6" 17'-7" 17'-5" 16'-6" 16'-2" 15'-3"

    LPI 20W 11-7/8" 22'-2" 21'-0" 20'-10" 19'-9" 19'-4" 18'-3"

    14" 25'-3" 23'-11" 23'-9" 22'-6" 22'-0" 20'-10"

    9-1/2" 20'-6" 19'-4" 19'-2" 18'-2" 17'-9" 16'-9"

    LPI 32W11-7/8" 24'-4" 23'-0" 22'-10" 21'-7" 21'-1" 20'-0"

    14" 27'-7" 26'-1" 25'-11" 24'-6" 23'-11" 22'-8"

    16" 30'-6" 28'-10" 28'-7" 27'-1" 26'-6" 25'-0"

    9-1/2" 17'-10" 17'-0" 16'-9" 15'-11" 15'-6" 14'-9"

    LPI 20W 11-7/8" 21'-4" 20'-4" 20'-0" 19'-1" 18'-7" 17'-7"

    14" 24'-3" 23'-1" 22'-10" 21'-9" 21'-0" 19'-6"

    9-1/2" 19'-8" 18'-9" 18'-5" 17'-7" 17'-1" 16'-3"

    LPI 32W11-7/8" 23'-5" 22'-3" 21'-11" 20'-10" 20'-3" 19'-3"

    14" 26'-6" 25'-3" 24'-11" 23'-8" 23'-0" 21'-10"

    16" 29'-3" 27'-10" 27'-6" 26'-2" 25'-5" 23'-8"

    9-1/2" 17'-2" 16'-5" 16'-2" 15'-5" 15'-0" 14'-4"

    LPI 20W 11-7/8" 20'-7" 19'-8" 19'-4" 18'-6" 17'-11" 16'-9"

    14" 23'-5" 22'-5" 22'-0" 20'-10" 19'-11" 18'-8"

    9-1/2" 19'-0" 18'-2" 17'-10" 17'-0" 16'-5" 15'-8"

    LPI 32W11-7/8" 22'-7" 21'-7" 21'-2" 20'-3" 19'-7" 18'-8"

    14" 25'-7" 24'-5" 24'-0" 22'-11" 22'-2" 20'-11"

    16" 28'-3" 27'-0" 26'-6" 25'-4" 24'-2" 22'-8"

    9-1/2" 16'-2" 15'-7" 15'-2" 14'-8" 14'-1" 13'-6"

    LPI 20W 11-7/8" 19'-4" 18'-8" 18'-2" 17'-4" 16'-4" 15'-6"

    14" 22'-0" 21'-1" 20'-4" 19'-3" 18'-2" 17'-3"

    9-1/2" 17'-10" 17'-2" 16'-8" 16'-1" 15'-5" 14'-10"

    LPI 32W11-7/8" 21'-2" 20'-5" 19'-11" 19'-1" 18'-4" 17'-1"

    14" 24'-0" 23'-2" 22'-6" 21'-7" 20'-4" 19'-3"

    16" 26'-7" 25'-7" 24'-9" 23'-5" 22'-1" 20'-0"

    9-1/2" 15'-4" 14'-10" 14'-5" 13'-11" 13'-3" 12'-7"

    LPI 20W 11-7/8" 18'-5" 17'-9" 17'-0" 16'-2" 15'-2" 14'-5"

    14" 20'-8" 19'-9" 18'-10" 18'-0" 16'-10" 16'-1"

    9-1/2" 16'-11" 16'-4" 15'-10" 15'-4" 14'-7" 13'-9"

    LPI 32W11-7/8" 20'-1" 19'-5" 18'-10" 18'-2" 16'-4" 14'-10"

    14" 22'-9" 22'-0" 21'-1" 20'-2" 18'-10" 17'-3"

    16" 25'-1" 23'-11" 22'-11" 21'-10" 19'-0" 17'-5"

    9-1/2" 14'-8" 14'-3" 13'-9" 13'-3" 12'-4" 11'-10"

    LPI 20W 11-7/8" 17'-5" 16'-8" 15'-10" 15'-3" 14'-2" 13'-2"

    14" 19'-4" 18'-7" 17'-8" 16'-11" 15'-9" 14'-10"

    9-1/2" 16'-1" 15'-8" 15'-1" 14'-8" 13'-1" 12'-2"

    LPI 32W11-7/8" 19'-2" 18'-7" 17'-10" 16'-6" 14'-4" 13'-2"

    14" 21'-8" 20'-9" 19'-9" 18'-11" 16'-6" 15'-3"

    16" 23'-6" 22'-7" 20'-8" 19'-3" 16'-6" 15'-4"

    TO USE:

    1. Select the appropriate set of tables based on roof slope.

    2. Select the section of that table that corresponds to the designlive load and load duration.

    3. Find a span that meets or exceeds the design span for theappropriate roof dead load (15 psf or 20 psf).

    4. Read the corresponding joist, depth and spacing.

    DESIGN ASSUMPTIONS:

    1. The spans listed are the horizontal clear distance between supports.Refer to the diagram below.

    2. The spans are based on uniform gravity loads only and havenotbeen evaluated for wind.

    3. These tables do notreflect any additional stiffness provided bythe roof sheathing.

    4. Live load deflection has been limited to L/240.

    5. Total load deflection has been limited to L/180.

    6. A load sharing (repetitive member) increase has been applied.This increase is based on the attachment of a proper deckto three or more joists, spaced no more than 24" oc.

    7. The spans are based on the minimum required bearings as listedon page 14.

    ADDITIONAL NOTES:

    1. Web stiffeners arenotrequired for any of the spans listed in these

    tables. Web stiffeners are required when using the birds mouthbearing detail. Web fillers are required for joists seated in hangersthat do not laterally support the top flange.

    2. The design of continuous spans is based on the longest span.The shortest span must not be less than 50% of the longest span.

    3. L/240 is the minimum deflection criteria allowed per code for roofjoists supporting non-plaster ceilings. Verify deflection limits withlocal code requirements.

    4. Roof joists must have a minimum slope of 1/4" per foot (1/4:12)for positive drainage.

    5. For conditions not shown, use the Uniform Roof Load (PLF) Tablesor contact your LP Engineered Wood Products distributor for assistance.

    6. Roof applications in high wind areas require special analysis whichmay result in reduced spans and special connectors to resist uplift.

    20psf

    125%

    Non-

    Snow

    25psf

    115%

    Snow

    30psf

    115%

    Snow

    40

    psf

    115%

    Snow

    50psf

    115%

    Snow

    60psf

    115%

    Snow

    ROOF

    LIVE

    LOAD

    Horizontal Span

    12

    Pitch

    edSpan

    ROOF JOIST SPAN

    Rise

    RoofSlope=R

    ise:

    12

  • 7/30/2019 lp_i-joists_20-32 (1).pdf

    8/16

    ROUND HOLES UP TO 40 PSF LIVE LOAD AND 25 PSF DEAD LOAD; UP TO 24" OC

    8 2005 Louisiana-Pacific Corporation

    Web Hole Specifications: Circular Holes

    TO USE:

    1. Select the required product from the left column.

    2. Determine the support condition for the nearest bearing: end support or interior support (including end supports with cantilevers).

    3. Select the row corresponding to the required span. For spans between those listed, use the next largest value.

    4 Select the column corresponding to the required hole diameter. For diameters between those listed, use the next largest value.5. The intersection of the Span row and Hole Diameter column gives the minimum distance from the inside face of bearing to the center of the circular hole.

    6. Double check the distance to the other support, using the appropriate support condition.

    Series Depth ClearDistance from End Support Distance from Interior or Cantilever-End Support

    Span (ft)Hole Diameter Hole Diameter

    2" 4" 6" 8" 10" 12" 14" 2" 4" 6" 8" 10" 12" 14"

    DESIGN ASSUMPTIONS:1. The hole locations listed above are valid for floor joists supporting only uniform loads as follows:

    For joists 16" deep and less, the total uniform load must not exceed 130 plf (e.g., 40 psf Live Load anda 25 psf Dead Load, spaced up to 24" oc). The uniform dead load must be at least 10 plf.

    2. Hole location is measured from the inside face of bearing to the center of a circular hole, from theclosest support.

    3. Clear Span has NOT been verified for these joists and is shown for informational purposes only! Verify thatthe joist selected will work for the span and loading conditions needed before checking hole location.

    4. Maximum hole depth for circular holes is Joist Depth less 4", not to exceed 14", except the maximum holedepth is 6" for 9-1/2", and 8" for 11-7/8" LP I-Joists.5. Holes cannot be located in the span where designated - without further analysis by a professional engineer.

    NOTES:1. CUT HOLES CAREFULLY! DO NOT OVERCUT HOLES! DO NOT CUT JOIST FLANGES!2. Holes may be placed anywhere within the depth of the joist. A minimum 1/4" clear distance is required

    between the hole and the flanges.3. Round holes up to 1-1/2" diameter may be placed anywhere in the web.4. Perforated knockouts may be neglected when locating web holes.5. Holes larger than 1-1/2" are not permitted in cantilevers without special engineering.

    6. Multiple holes must have a clear separation along the length of the joist of at least twice the length

    of the larger adjacent hole, or a minimum of 12" center-to-center, whichever is greater.7. Multiple holes may be spaced closer provided they fit within the boundary of an acceptable larger hole.

    Example: two 3" round holes aligned parallel to the joist length may be spaced 2" apart (clear distance)provided that a 3" high by 8" long rectangle or an 8" diameter round hole are acceptable for the joistdepth at that location and completely encompass the holes.

    8. Not all series are available in all depths. Check availability with a local LP Engineered WoodProducts distributor.

    9. Locating holes in joists with spans exceeding those in the tables or larger holes, greater uniform loadsor non-uniform loads, and closer proximity to supports and other holes may be possible with analysisusing LPs design software. Please contact your local LP Engineered Wood Products distributor formore information.

    6 1'-0" 1'-0" 1'-6" - - - - 1'-0" 1'-0" 1'-6" - - - -LPI 20W

    9-1/2"10 1'-0" 1'-0" 1'-6" - - - - 1'-0" 1'-0" 1'-6" - - - -

    &14 1'-0" 1'-0" 1'-6" - - - - 1'-0" 1'-8" 3'-5" - - - -

    LPI 32W18 1'-0" 1'-10" 3'-8" - - - - 2'-8" 4'-5" 6'-3" - - - -

    6 1'-0" 1'-0" 1'-6" 2'-0" - - - 1'-0" 1'-0" 1'-6" 2'-0" - - -LPI 20W

    11-7/8"10 1'-0" 1'-0" 1'-6" 2'-0" - - - 1'-0" 1'-0" 1'-6" 2'-0" - - -

    &14 1'-0" 1'-0" 1'-6" 2'-0" - - - 1'-0" 1'-0" 2'-5" 3'-10" - - -

    LPI 32W

    18 1'-0" 1'-5" 2'-9" 4'-1" - - - 2'-2" 3'-6" 5'-4" 6'-9" - - -8 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" - - 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" - -

    LPI 20W

    14"12 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" - - 1'-0" 1'-0" 1'-6" 2'-0" 2'-8" - -

    &16 1'-0" 1'-0" 1'-6" 2'-1" 3'-8" - - 1'-0" 1'-11" 3'-2" 4'-4" 5'-7" - -

    LPI 32W20 1'-0" 2'-1" 3'-1" 4'-7" 6'-1" - - 3'-5" 4'-5" 6'-0" 7'-6" 9'-0" - -

    8 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" 3'-0" - 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" 3'-0" -

    16"12 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" 3'-0" - 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" 3'-3" -

    LPI 32W16 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" 3'-8" - 1'-0" 1'-6" 2'-9" 3'-7" 4'-9" 6'-0" -

    20 1'-0" 1'-7" 2'-7" 3'-7" 5'-1" 6'-7" - 2'-11" 4'-5" 5'-5" 6'-6" 8'-0" 9'-6" -

    Up to a 1-1/2" diameter holeallowed anywhere in the web.Closest spacing 12" oc.

    Diameter

    Closest distance (x) to center of circular hole

    FROM EITHER SUPPORT

    Uncut length of web between adjacent holesmust be at least twice the length of the larger hole

    or 12" center-to-center, whichever is larger.

    Closest distance (x) to center of circular hole

    FROM EITHER SUPPORT

    END SUPPORT INTERIOR OR CANTILEVER-END SUPPORT

  • 7/30/2019 lp_i-joists_20-32 (1).pdf

    9/16

    RECTANGULAR HOLES UP TO 40 PSF LIVE LOAD AND 25 PSF DEAD LOAD; UP TO 24" OC

    Web Hole Specifications: Rectangular Holes

    2005 Louisiana-Pacific Corporation9

    TO USE:

    1. Select the required product from the left column.

    2. Determine the support condition for the nearest bearing: end support or interior support (includes end supports with cantilevers).

    3. Select the row corresponding to the required span. For spans between those listed, use the next largest value.

    4. Select the column corresponding to the required hole dimension. For dimensions between those listed, use the next largest value.5. The intersection of the Span row and Hole Dimension column gives the minimum distance from the inside face of bearing to the nearest edge of the rectangular hole.

    6. Double check the distance to the other support, using the appropriate support condition.

    DESIGN ASSUMPTIONS:1. The hole locations listed above are valid for floor joists supporting only uniform loads as follows:

    For joists 16" deep and less, the total uniform load must not exceed 130 plf (e.g., 40 psf Live Load anda 25 psf Dead Load, spaced up to 24" oc). The uniform dead load must be at least 10 plf.

    2. Hole location is measured from the inside face of bearing to the nearest edge of a rectangular hole, from theclosest support.

    3. Clear Span has NOT been verified for these joists and is shown for informational purposes only! Verify thatthe joist selected will work for the span and loading conditions needed before checking hole location.

    4. Maximum hole depth for rectangular holes is Joist Depth less 4", not to exceed 14", except the maximum holedepth is 6" for 9-1/2", and 8" for 11-7/8" LP I-Joists. Maximum hole width for rectangular holes is 18". Wherethe Maximum Hole Dimension for rectangular holes exceeds the maximum hole depth, the dimension refers tohole width, and the hole depth is assumed to be the maximum for that joist depth.

    5. Holes cannot be located in the span where designated - without further analysis by a professional engineer.

    NOTES:1. CUT HOLES CAREFULLY! DO NOT OVERCUT HOLES! DO NOT CUT JOIST FLANGES!2. Holes may be placed anywhere within the depth of the joist. A minimum 1/4" clear distance is required

    between the hole and the flanges.3. Round holes up to 1-1/2" diameter may be placed anywhere in the web.4. Perforated knockouts may be neglected when locating web holes.

    5. Holes larger than 1-1/2" are not permitted in cantilevers without special engineering.6. Multiple holes must have a clear separation along the length of the joist of at least twice the length

    of the larger adjacent hole, or a minimum of 12" center-to-center, whichever is greater.7. Multiple holes may be spaced closer provided they fit within the boundary of an acceptable larger hole.

    Example: two 3" round holes aligned parallel to the joist length may be spaced 2" apart (clear distance)provided that a 3" high by 8" long rectangle or an 8" diameter round hole are acceptable for the joistdepth at that location and completely encompass the holes.

    8. Not all series are available in all depths. Check availability with a local LP Engineered WoodProducts distributor.

    9. Locating holes in joists with spans exceeding those in the tables or larger holes, greater uniform loadsor non-uniform loads, and closer proximity to supports and other holes may be possible with analysisusing LPs design software. Please contact your local LP Engineered Wood Products distributor formore information.

    Depth

    Closest distance (x) to edge of rectangular hole

    FROM EITHER SUPPORT

    Closest distance (x) to edge of rectangular hole

    FROM EITHER SUPPORT

    END SUPPORT INTERIOR OR CANTILEVER-END SUPPORT

    Width

    Uncut length of web between adjacent holesmust be at least twice the length of the larger hole

    or 12" center-to-center, whichever is larger.

    Series Depth ClearDistance from End Support Distance from Interior or Cantilever-End Support

    Span (ft)Maximum Hole Dimension: Depth or Width Maximum Hole Dimension: Depth or Width

    2" 4" 6" 8" 10" 12" 14" 16" 18" 2" 4" 6" 8" 10" 12" 14" 16" 18"

    6 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" 3'-0" - - - 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" 3'-0" - - -LPI 20W

    9-1/2"10 1'-0" 1'-1" 2'-7" 3'-1" 3'-7" 4'-1" 4'-7" - - 1'-0" 2'-5" 4'-0" 4'-6" 5'-0" - - - -

    &14 1'-10" 3'-3" 5'-4" 5'-8" 6'-5" 6'-9" - - - 3'-10" 5'-3" - - - - - - -

    LPI 32W18 4'-1" 5'-11" 7'-9" 8'-8" - - - - - 6'-9" 8'-7" - - - - - - -

    6 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" 3'-0" - - - 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" 3'-0" - - -LPI 20W

    11-7/8"10 1'-0" 1'-0" 1'-10" 3'-4" 3'-10" 4'-4" 4'-10" - - 1'-0" 1'-11" 3'-3" 4'-9" - - - - -

    &14 1'-5" 2'-10" 4'-3" 6'-1" 6'-9" - - - - 3'-5" 4'-10" 6'-3" - - - - - -

    LPI 32W

    18 3'-8" 5'-6" 6'-10" 8'-8" - - - - - 6'-3" 8'-1" - - - - - - -8 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" 3'-0" 3'-6" 4'-0" - 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" 3'-0" 3'-10" - -

    LPI 20W

    14"12 1'-0" 1'-0" 1'-6" 2'-0" 3'-8" 4'-7" 5'-2" - - 1'-0" 1'-0" 1'-6" 3'-3" 5'-5" - - - -

    &16 1'-0" 1'-0" 2'-1" 4'-1" 6'-6" 7'-4" - - - 1'-0" 2'-4" 4'-4" 6'-5" - - - - -

    LPI 32W20 1'-0" 2'-7" 4'-7" 6'-7" 9'-1" - - - - 2'-11" 4'-11" 7'-0" 9'-6" - - - - -

    8 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" 3'-0" 3'-6" 4'-0" - 1'-0" 1'-0" 1'-6" 2'-0" 2'-6" 3'-5" - - -

    16"12 1'-0" 1'-0" 1'-6" 2'-0" 2'-9" 4'-11" 5'-10" - - 1'-0" 1'-0" 1'-6" 2'-8" 4'-6" - - - -

    LPI 32W16 1'-0" 1'-0" 1'-8" 3'-3" 5'-3" 7'-8" - - - 1'-0" 1'-11" 3'-7" 5'-7" 7'-7" - - - -

    20 1'-0" 2'-1" 3'-7" 5'-7" 8'-1" - - - - 2'-11" 4'-11" 6'-6" 8'-6" - - - - -

  • 7/30/2019 lp_i-joists_20-32 (1).pdf

    10/1610

    Load-Bearing Cantilever Tables: 9-1/2" & 11-7/8"

    2005 Louisiana-Pacific Corporation

    TO USE:

    1. Select the page (10 or 11) that corresponds to the required product.

    2. Select the row corresponding to the Roof Load and Truss Span needed.

    DESIGN ASSUMPTIONS:1. These tables are valid for joists selected from the Floor Span Tables in this design guide.2. The floor design loads mustnotexceed 40 psf Live and 25 psf Dead Load.

    3. The maximum cantilever length is 2' (the amount of overhang).4. The wall load is assumed to be 100 plf.

    5. Roof Load is the Total Load (Live plus Dead) on the roof trusses.6. Truss Span is the out-to-out distance of the truss bearing walls as shown above.

    7. A maximum overhang of 2' is allowed for the trusses.

    ADDITIONAL NOTES:1. The reinforcement (when required) must match the depth of the I-Joist.2. Where designated B/D, either detail (B or D) is valid.3. The closure at the end of the cantilever must be a minimum of 23/32" APA-Rated OSB (or equal).

    Certain codes may require a thicker pr oduct for lateral load transfer.

    4. For short cantilevers up to 6" long, use the Brick-Ledge Cantilever Tables on page 12.5. For conditions not shown, use LPs design software or contact your LP Engineered Wood Products

    distributor for assistance.

    6. Do not use a product where designated - without further analysis by a professional engineer.

    Roof Truss Span

    2'-0"

    2'-0"

    2'-0"max.

    APA-Rated 23/32" OSB(or equal) closure oras required by code

    LPIblocking

    2'-0"max.

    APA-Rated 23/32" OSB(or equal) closure oras required by code

    LPIblocking

    A: NO REINFORCEMENT REQUIRED W: WEB STIFFENERS ONLY

    3. Follow across the row to the required joist spacing.

    4. The letter represents the required detail.

    Roof Truss 9-1/2" LPI 20W 9-1/2" LPI 32W 11-7/8" LPI 20W 11-7/8" LPI 32W Truss RoofLoad Span (ft) 12" 16" 19.2" 24" 12" 16" 19.2" 24" 12" 16" 19.2" 24" 12" 16" 19.2" 24" Span (ft) Load

    22 A A A B/D A A A B/D A A A A A A A A 22

    24 A A A B/D A A W B/D A A A A A A A A 24

    26 A A B/D B/D A A B/D B/D A A A W A A A W 26

    28 A A B/D B/D A A B/D B/D A A A W A A A W 28

    30 A A B/D B/D A A B/D B/D A A A W A A A W 30

    30 psf 32 A A B/D B/D A A B/D B/D A A A B/D A A A B/D 32 30 psf

    34 A W B/D B/D A B/D B/D B/D A A A B/D A A A B/D 34

    36 A B/D B/D B/D A B/D B/D B/D A A A B/D A A A B/D 36

    38 A B/D B/D C A B/D B/D C A A W B/D A A W B/D 38

    40 A B/D B/D C A B/D B/D C A A W B/D A A W B/D 40

    42 A B/D B/D C A B/D B/D C A A W C A A W C 42

    22 A A B/D B/D A A B/D B/D A A A W A A A W 22

    24 A W B/D B/D A W B/D B/D A A A B/D A A A B/D 24

    26 A B/D B/D B/D A B/D B/D B/D A A A B/D A A A B/D 26

    28 A B/D B/D C A B/D B/D C A A W B/D A A W B/D 28

    30 A B/D B/D C A B/D B/D C A A W C A A W C 30

    40 psf 32 A B/D B/D C A B/D B/D C A A W C A A W C 32 40 psf34 A B/D B/D - A B/D B/D C A A B/D C A A B/D C 34

    36 A B/D C - A B/D C - A W B/D C A W B/D C 36

    38 W B/D C - B/D B/D C - A W B/D C A W B/D C 38

    40 B/D B/D C - B/D B/D C - A W C - A W C - 40

    42 B/D B/D C - B/D B/D C - A B/D C - A B/D C - 42

    22 A B/D B/D C A B/D B/D C A A W B/D A A W B/D 22

    24 A B/D B/D C A B/D B/D C A A W C A A W C 24

    26 A B/D B/D C A B/D B/D C A A B/D C A A B/D C 26

    28 A B/D C - A B/D C - A W B/D C A W B/D C 28

    30 W B/D C - B/D B/D C - A W B/D - A W B/D - 30

    50 psf 32 B/D B/D C - B/D B/D C - A W C - A W C - 32 50 psf

    34 B/D B/D C - B/D B/D C - A B/D C - A B/D C - 34

    36 B/D C - - B/D C - - A B/D C - A B/D C - 36

    38 B/D C - - B/D C - - A B/D C - A B/D C - 38

    40 B/D C - - B/D C - - W C - - W C - - 40

    42 B/D C - - B/D C - - W C - - W C - - 42

    22 A B/D B/D - A B/D B/D - A W B/D C A W B/D C 22

    24 W B/D C - B/D B/D C - A W B/D C A W B/D C 24

    26 B/D B/D C - B/D B/D C - A W C - A W C - 26

    28 B/D B/D C - B/D B/D C - A B/D C - A B/D C - 28

    30 B/D C - - B/D C - - A B/D C - A B/D C - 30

    60 psf 32 B/D C - - B/D C - - W C C - W C C - 32 60 psf

    34 B/D C - - B/D C - - W C - - W C - - 34

    36 B/D C - - B/D C - - W C - - W C - - 36

    38 B/D - - - B/D - - - W C - - W C - - 38

    40 B/D - - - B/D - - - B/D C - - B/D C - - 40

    42 C - - - C - - - B/D - - - B/D - - - 42

    ROO

    FTRUSSSPANWITH2'OVERHANG

  • 7/30/2019 lp_i-joists_20-32 (1).pdf

    11/1611

    Load-Bearing Cantilever Tables: 14" & 16"

    2005 Louisiana-Pacific Corporation

    LPIblocking

    2'-0"max.

    APA-Rated 23/32" OSB(or equal) reinforcement

    one side, 4'-0" long min.

    Attach reinforcement to top andbottom flanges with 8d nails at 6" oc

    2'-0"min.

    APA-Rated 23/32" OSB(or equal) reinforcement

    both sides, 4'-0" long min.

    LPIblocking

    2'-0"max.2'-0"min.

    APA-Rated 23/32" OSB(or equal) closure or as

    required by code

    Attach reinforcement to top and bottom flangeswith 8d nails at 6" oc both sides with nails staggered to avoid splitting

    LP Rim Boardreinforcement one

    side, 4'-0" long min.

    LPIblocking

    2'-0"max.2'-0"min.

    Attach reinforcement to topand bottom flanges with 8d nails at 6" oc

    APA-Rated 23/32" OSB(or equal) closure or

    as required by code

    APA-Rated 23/32" OSB(or equal) closure or

    as required by code

    B: 23/32" OSB (OR EQUAL) REINFORCEMENTOne Side Only

    C: 23/32" OSB (OR EQUAL) REINFORCEMENTBoth Sides

    D: 1" OR 1-1/8" LP RIM BOARDMay be Substituted for Detail B

    ROO

    FTRUSSSPANWITH2'OVERHANG

    Roof Truss 14" LPI 20W 14" LPI 32W 16" LPI 32W Truss RoofLoad Span (ft) 12" 16" 19.2" 24" 12" 16" 19.2" 24" 12" 16" 19.2" 24" Sp an (ft ) Lo ad

    22 A A A A A A A A A A A A 22

    24 A A A A A A A A A A A A 24

    26 A A A A A A A A A A A A 26

    28 A A A A A A A A A A A A 28

    30 A A A A A A A A A A A W 30

    30 psf 32 A A A W A A A W A A A W 32 30 psf

    34 A A A W A A A W A A A W 34

    36 A A A W A A A W A A A W 36

    38 A A A W A A A W A A A W 38

    40 A A A W A A A W A A A W 40

    42 A A A B/D A A A B/D A A W W 42

    22 A A A A A A A A A A A W 22

    24 A A A W A A A W A A A W 24

    26 A A A W A A A W A A A W 26

    28 A A A W A A A W A A A W 28

    30 A A A W A A A W A A W W 30

    40 psf 32 A A W B/D A A W B/D A A W B/D 32 40 psf34 A A W B/D A A W B/D A A W B/D 34

    36 A A W B/D A A W B/D A A W B/D 36

    38 A A W C A A W C A A W B/D 38

    40 A A W C A A W C A W W B/D 40

    42 A W B/D C A W B/D C A W W B/D 42

    22 A A A W A A A W A A A W 22

    24 A A A B/D A A A B/D A A W W 24

    26 A A W B/D A A W B/D A A W B/D 26

    28 A A W B/D A A W B/D A A W B/D 28

    30 A A W C A A W C A A W B/D 30

    50 psf 32 A A W C A A W C A W W B/D 32 50 psf

    34 A W B/D C A W B/D C A W W C 34

    36 A W B/D C A W B/D C A W B/D C 36

    38 A W B/D - A W B/D - A W B/D - 38

    40 A W C - A W C - A W B/D - 40

    42 A W C - A W C - A W B/D - 42

    22 A A W B/D A A W B/D A A W B/D 22

    24 A A W C A A W C A A W B/D 24

    26 A A W C A A W C A W W B/D 26

    28 A W B/D C A W B/D C A W B/D C 28

    30 A W B/D - A W B/D - A W B/D - 30

    60 psf 32 A W C - A W C - A W B/D - 32 60 psf

    34 A W C - A W C - A W B/D - 34

    36 A B/D C - A B/D C - A B/D C - 36

    38 A B/D C - A B/D C - W B/D C - 38

    40 W C - - W C - - W B/D - - 40

    42 W C - - W C - - W B/D - - 42

    DESIGN ASSUMPTIONS:1. These tables are valid for joists selected from the Floor Span Tables in this design guide.2. The floor design loads mustnotexceed 40 psf Live and 25 psf Dead Load.

    3. The maximum cantilever length is 2' (the amount of overhang).4. The wall load is assumed to be 100 plf.

    5. Roof Load is the Total Load (Live plus Dead) on the roof trusses.6. Truss Span is the out-to-out distance of the truss bearing walls as shown on page 10.

    7. A maximum overhang of 2' is allowed for the trusses.

    ADDITIONAL NOTES:1. The reinforcement (when required) must match the depth of the I-Joist.2. Where designated B/D, either detail (B or D) is valid.3. The closure at the end of the cantilever must be a minimum of 23/32" APA-Rated OSB (or equal).

    Certain codes may require a thicker product for lateral load transfer.

    4. For short cantilevers up to 6" long, use the Brick-Ledge Cantilever Tables on page 12.5. For conditions not shown, use LPs design software or contact your LP Engineered Wood Products

    distributor for assistance.

    6. Do not use a product where designated - without further analysis by a professional engineer.

  • 7/30/2019 lp_i-joists_20-32 (1).pdf

    12/1612

    Brick-Ledge Cantilevers

    2005 Louisiana-Pacific Corporation

    LP Rim Board orLPI blocking panel between I-Joists

    Closure and/orflashing may be

    required per localbuilding code

    Full depth reinforcing

    Web filler reinforcing

    Provide vapor barrier/house wrapper local building code

    Wall framing sheathing air gap

    No reinforcing

    Total Joist Reaction

    Calculation

    LP I-Joists can cantilever up to 6" to support a

    load-bearing wall over a brick finish. Depending

    on the Total Joist Reaction (TJR), the joists may

    require reinforcement. If the TJR is less than the

    End Bearing W/out Stiffeners (page 14), then no

    reinforcement is required. If the TJR is greater

    than the End Bearing W/out Stiffeners, but less

    than the End Bearing With Stiffeners, then web

    stiffeners must be installed at the bearing.

    Otherwise, one of the reinforcing details from

    below must be used.

    Total Joist Reaction, TJR = FLR + WLR + RLR

    Where: FLR = Floor Load Reaction

    WLR = Wall Load Reaction

    RLR = Roof Load Reaction,including any other floor,

    ceiling or attic loads imposed

    on wall

    Blocking panels are required at the bearing, but are not shown for clarity* NOTE: Pilot holes required when using screws

    Blocking panels are required at the bearing, but are not shown for clarity

    WEB FILLER REINFORCING

    23/32" APA-Rated OSB(or equal) fillers (both sides)

    6"max.

    Nail web filler with two rows of 3-10dor 12d box or equivalent gun nail, clinched

    Use construction adhesive between surfaces

    12"min.Leave

    1/8" gap

    For 14" and 16" I-Joists, web filler

    (both sides) and OSB or plywoodreinforcing are required.(See left.)

    Nail or screw reinforcing with3-6d or 8d box nails or 6 x 1-1/2"wood screws into both flanges*

    Reinforcing mustbe same depth

    as I-Joist

    Construction adhesive is recommendedbetween surfaces

    2" min. fromI-Joist end

    6"max.

    23/32"reinforcing-12"min.

    1"reinforcing-18"min.

    FULL-DEPTH REINFORCINGOne Side

    SeriesWeb Filler Thickness Reaction Capacity

    (in) (lbs)

    LPI 20W 23/32" APA-Rated OSB (or Equal) 2600

    LPI 32W 23/32" APA-Rated OSB (or Equal) 2600

    SeriesReaction Capacity (lbs)

    23/32 " APA -Rated O SB ( or E qu al ) 1 " or 1 -1 /8 " LP R im Board

    LPI 20W 3500 3800

    LPI 32W 3500 3800

  • 7/30/2019 lp_i-joists_20-32 (1).pdf

    13/16

    EXAMPLE 1:

    Brick-Ledge Cantilevers

    2005 Louisiana-Pacific Corporation13

    I-Joist: 9-1/2" LPI20W Allowable End Bearing = 950 lbs. W/out Stiffeners, 1230 lbs. With Stiffeners (page 14)

    Design Loads: Floor:40/10 psf Floor System: Joist Span = 11' Roof System: Roof Span = 22'

    Roof: 20/10 psf Joist Overhang = 5" Roof Overhang = 1'

    Wall: 80 plf Joist Spacing = 16"

    FLR = (Joist Span / 2 + Joist Overhang / 12) * Design Floor Load * (Joist Spacing / 12)= (11' / 2 + 5" / 12) * (40 psf + 10 psf) * (16" / 12)

    = 394 lbs.

    WLR = Design Wall Load * (Joist Spacing / 12)

    = 80 plf * (16" / 12)

    = 107 lbs.

    RLR = (Roof Span / 2 + Roof Overhang) * Design Roof Load * (Joist Spacing / 12)

    = (22' / 2 + 1') * (20 psf + 10 psf) * (16" / 12)

    = 480 lbs.

    TJR = 394 + 107 + 480

    = 981 lbs.

    Since the Total Joist Reaction, 981 lbs., is greater than the End Bearing W/out Stiffeners, 950 lbs., but less than End Bearing With Stiffeners, 1230 lbs.,this joist only requires the installation of web stiffeners at the bearing.

    EXAMPLE 2:

    I-Joist: 11-7/8" LPI 32W Allowable End Bearing = 1025 lbs. W/out Stiffeners, 1350 lbs. With Stiffeners (page 14)

    Design Loads: Floor:40/15 psf Floor System: Joist Span = 16' Roof System: Roof Span = 32'

    Roof: 30/15 psf Joist Overhang = 5" Roof Overhang = 2'

    Wall: 100 plf Joist Spacing = 24"

    FLR = (Joist Span / 2 + Joist Overhang / 12) * Design Floor Load * (Joist Spacing / 12)

    = (16' / 2 + 5" / 12) * (40 psf + 15 psf) * (24" / 12)

    = 926 lbs.

    WLR = Design Wall Load * (Joist Spacing / 12)

    = 100 plf * (24" / 12)

    = 200 lbs.

    RLR = (Roof Span / 2 + Roof Overhang) * Design Roof Load * (Joist Spacing / 12)

    = (32' / 2 + 2') * (30 psf + 15 psf) * (24" / 12)

    = 1620 lbs.

    TJR = 926 + 200 + 1620

    = 2746 lbs.

    Since the Total Joist Reaction, 2746 lbs., is greater than the End Bearing With Stiffeners, 1350 lbs., this joist needs reinforcing.The Full-Depth Reinforcing detail has a capacity of 3500 lbs. with 23/32" APA-Rated OSB (or Equal) attached to one side.

  • 7/30/2019 lp_i-joists_20-32 (1).pdf

    14/1614 2005 Louisiana-Pacific Corporation

    Product Specifications & Design Values

    * Nail Size is for common or box nails.

    RIM AND BLOCKING CAPACITY

    NOTES:1. Lateral Load Capacity for all series above = 200 plf.2. For LPI Rim or Blocking used for lateral load transfer, nail to bearing plate with same nail schedule as the deck-to-rim connection.

    Uniform

    Depth Load

    (plf)

    9-1/2" 1900

    11-7/8" 1760

    14" 1600

    9-1/2" 2200

    11-7/8" 2200

    14" 1600

    16" 1500

    Series

    LPI 20W

    LPI 32W

    RIM AND BLOCKING NAIL SCHEDULE

    Series

    LPI 20W

    &

    LPI 32W

    LPI 20W

    LPI 32W

    2-1/2"

    9-1/2,"

    11-7/8"

    or 14""

    3/8"

    1-1/2"

    2-1/2"

    9-1/2,"

    11-7/8",

    14"" or 16"

    3/8"

    1-1/2"

    *Includes 16d Sinker (3-1/4")

    NOTES:1. Moment, Shear and Reaction Capacity values are for normal load duration and may be adjusted according to code.

    2. When calculating deflection, both bending and shear deformation must be determined as follows:

    For simple span, uniform load: = + Where: = deflection in inches EI= bending sti ffness from table

    w = uni for m load i n p lf K = shear s ti ffness f rom tab leL = design span in feet

    3. The Moment capacity may be increased 7% for repetitive member applications.4. These design values are based on the product being used in a dry, well ventilated environment where the moisture content will not exceed 16% such as

    in most covered structures. These products are intended to resist the effects of moisture on structural performance from normal construction delays but arenot intended for permanent exposure to the weather.

    22.5wL4

    wL2

    El K

    DESIGN VALUES

    Series

    LPI 20W

    LPI 32W

    Weight Moment EI (x 106) K (x 10

    6) Shear

    Reaction Capacity (lbs)

    Depth End Bearing (1-1/2" min.) Interior Bearing (3-1/2" min.)

    (plf) (lb-ft) (lb-in2) (lb-ft/in) (lbs) W/out Stiffeners With Stiffeners W/out Stiffeners With Stiffeners

    9-1/2" 2.6 2600 176 0.358 1230 950 1230 2000 2025

    11-7/8" 2.9 3406 300 0.438 1350 1025 1350 2350 2525

    14" 3.1 4200 441 0.512 1620 1190 1620 2425 3490

    9-1/2" 2.6 3195 243 0.213 1250 950 1250 2000 2025

    11-7/8" 2.9 4275 406 0.267 1350 1025 1350 2350 2525

    14" 3.1 5255 589 0.313 1620 1190 1620 2500 349016" 3.3 6180 791 0.358 1800 1200 1800 2500 3700

    Nail SizeMinimum Nail Distance

    OC End

    8d (2-1/2") Box 2" 1"

    10d (3") & 12d (3-1/4") Box 2" 1"

    10d (3") & 12d (3-1/4") Common* 3" 1-1/2"

    16d (3-1/2") Common 4" 4"

    WEB STIFFENER REQUIREMENTS

    DepthMinimum Maximum

    Nail Size* Nail QtyThickness Height

    9-1/2" 23/32" 6-3/8" 8d (2-1/2") 3

    11-7/8" 23/32" 8-3/4" 8d (2-1/2") 3

    14" 23/32" 10-7/8" 8d (2-1/2") 3

    16" 23/32" 12-7/8" 8d (2-1/2") 3

    Series

    LPI 20W

    &

    LPI 32W

    NOTES:1. Web stiffeners, when required, must be installed

    in pairs one to each side of the web. Webstiffeners are always required for the BirdsMouth roof bearing detail.

    2. Web stiffeners should be cut to fit between theflanges of the I-Joist, leaving a minimum 1/8"gap (1" maximum). At bearing locations, thestiffeners should be installed tight to the bottom

    flange with the gap to the top flange. At locationsof concentrated loads, the stiffeners should beinstalled tight to the top flange with the gap tothe bottom flange.

    3. Web stiffeners should be cut from APA-Rated OSB(or equal). 2X lumber is permissible. Do NOT use1X lumber as it tends to split.

    4. Web stiffeners should be the same width as thebearing surface, with a minimum of 3-1/2".

    5. See Web Stiffener Requirements table above forminimum stiffener thickness, maximum stiffenerheight and required nailing.

    End support

    min. 1-1/2" bearing

    Intermediate support

    min. 3-1/2" bearing

    Nails to be equallyspaced, staggered and driven

    alternately from each face.Clinch nails where possible.

    1/8" min. gap

    1/8" min. gap1/8" min. gap

    1/8" min. gapConcentrated load

    WEB STIFFENER REQUIREMENTS

  • 7/30/2019 lp_i-joists_20-32 (1).pdf

    15/16 2005 Louisiana-Pacific Corporation15

    TOP-MOUNT FACE-MOUNT45 RAFTER- RAFTER-

    SKEWED TO-RIDGE TO-PLATE

    Framing Connectors

    Series DepthTop-Mount Face-Mount 45 Skewed Rafter-To-Ridge Rafter-To-Plate

    Single Double Single Double Single Single Single

    9-1/2" ITT39.5 MIT39.5-2 IUT310 HU310-2* SUR/L310* LSSUH310* VPA3

    LPI 20W 11-7/8" ITT311.88 MIT311.88-2 IUT312 HU312-2* SUR/L310* LSSUH310* VPA3

    14" ITT314 MIT314-2 IUT314 HU314-2* SUR/L314* LSSUH310* VPA3

    9-1/2" ITT39.5 MIT39.5-2 IUT310 HU310-2* SUR/L310* LSSUH310* VPA3

    11-7/8" ITT311.88 MIT311.88-2 IUT312 HU312-2* SUR/L310* LSSUH310* VPA3LPI 32W

    14" ITT314 MIT314-2 IUT314 HU314-2* SUR/L314* LSSUH310* VPA3

    16" ITT316 WPI316-2* IUT316 HU314-2* SUR/L314* LSSUH310* ** VPA3

    Series DepthTop-Mount Face-Mount 45 Skewed Rafter-To-Ridge Rafter-To-Plate

    Single Double Single Double Single Single Single

    9-1/2" THO25950 THO25950-2* THF25925 THF25925-2* SKH310R/L* TMU25* TMP25 or TMPH25*

    LPI 20W 11-7/8" THO25118 THO25118-2* THF25112 THF25112-2* SKH312R/L* TMU25* TMP25 or TMPH25*

    14" THO25140 THO25140-2* THF25140 THF25140-2* SKH312R/L* TMU25* TMP25 or TMPH25*

    9-1/2" THO25950 THO25950-2* THF25925 THF25925-2* SKH310R/L* TMU25* TMP25 or TMPH25*

    11-7/8" THO25118 THO25118-2* THF25112 THF25112-2* SKH312R/L* TMU25* TMP25 or TMPH25*LPI 32W

    14" THO25140 THO25140-2* THF25140 THF25140-2* SKH312R/L* TMU25* TMP25 or TMPH25*

    16" THO25160 THO25160-2* THF25160 THF25160-2* SKH312R/L* TMU25* ** TMP25 or TMPH25*

    USP LUMBER CONNECTORS

    The above connectors are manufactured by Simpson Strong-Tie Co., Inc.To verify connector suitability for a particular application, refer to the current Simpson St rong-Tie Connector catalog.

    The above connectors are manufactured by USP (United Steel Products Company).To verify connector suitability for a particular application, refer to the current USP Lumber Connectors catalog.

    GENERAL NOTES:

    * Web fillers required for properinstallation of hanger.Refer to Engineered WoodProduct Guide for filler sizes.

    ** Hanger is less than 60% of joistdepth. Additional rotationresistance is required.Refer to the appropriate hangermanufacturers catalog for details.

    SIMPSON STRONG-TIE

  • 7/30/2019 lp_i-joists_20-32 (1).pdf

    16/16

    LP is a registered trademark of Louisiana-Pacific Corporation. 2005

    Louisiana-Pacific Corporation. All rights reserved. Printed in USA. MW 10M

    Specifications (details) subject to change without notice.

    EW6120BR 4/05

    For more information on the full line of

    LP Engineered Wood Products or the nearest

    distributor, please contact 1.800.999.9105

    or e-mail [email protected].

    Visit our web site at www.lpcorp.com .