Web code: C0CY 26 • ESEER with Adaptive Function Plus up to 4,1 Low consumption Compact-Y range TCAEY-THAEY 115÷238 Cooling capacity: 15,4÷38,8 kW - Heating capacity: 16,8÷41,7 kW Packaged air-cooled water chillers and reversible heat pumps with axial fans. Range with hermetic Scroll compressors and R410A refrigerant gas. Construction features • Compressor: hermetic, rotary Scroll compressor, complete with thermal protection and crankcase heater for mod. 127÷238. • Water side heat exchanger: adequately insulated stainless steel plate exchanger, complete with antifreeze heater and water flow differential pressure switch. • Air side heat exchanger: featuring finned coil with copper pipes and aluminium fins, complete with protection grille. • Fan: electric axial fan with external rotor, equipped with internal thermal protection and complete with protection grille. • Control: microprocessor electronic control, iDRHOSS compatible, with Adaptive Function Plus logic. • Structure: in galvanised and painted sheet steel, complete with condensation drain pan. Models • TCAEY: unit designed for cooling only. • THAEY: heat pump unit. STANDARD unit (for mod. 133÷238) • Without pump assembly and water buffer tank. PUMP unit • Pump assembly complete with: circulation pump, expansion tank with membrane, manual bleed valve and safety valve, pressure gauge. TANK & PUMP unit • Pump assembly complete with: inertial water buffer tank, circulation pump, expansion tank with membrane, manual air bleed valve, automatic air bleed valve, safety valve, pressure gauge. FACTORY FITTED ACCESSORIES • Soft-start device. • Silenced installation. • -10°C condensation control. • Antifreeze electric heater on the buffer tank. • Crankcase heater compressor (mod. 115÷124). • Unit base antifreeze electric heater for operation in heat pump mode at low external air temperatures (mod. 115÷130). • Desuperheater 15% (mod. 133-233). • 100% heat recovery (mod. 133-233). • Pump with increased head pressure (mod. 133÷238) or circulator with low head pressure (mod. 115÷233). • Pump with increased head pressure (mod. 133÷238) or circulator with low head pressure (mod. 115÷233) + buffer tank. • Digital input for double set-point • 4-20 mA analogue input for shifting set-point. ACCESSORIES SUPPLIED LOOSE • Antivibration rubber mountings. • -10°C condensation control. • Water filter. • 3-way valve for the production of hot water (mod. 115÷133). • External air temperature probe for set-point compensation. • Additional electric heater for heat pump, managed by regulation. • Remote keyboard with display. • Clock card • Serial interfaces for connection to BMS (proprietary protocol, Modbus RTU, LonWorks). • Serial interface (CAN-bus - Controller Area Network) for the iDRHOSS system. • Serial converters (RS485/RS232, RS485/USB) in the case of centralised unit management. • GSM 900/1800 modem kit for remote unit management. • RHOSS supervision software for unit monitoring and remote management.

Transcript of Low consumption Compact-Y range TCAEY-THAEY 115÷238 · Web code: CHCY 28 • Hydraulic equipment...

Page 1: Low consumption Compact-Y range TCAEY-THAEY 115÷238 · Web code: CHCY 28 • Hydraulic equipment for radiant applications • ESEER with Adaptive Function Plus up to 3,9 Low consumption

Web code: C0CY

26

• ESEER with Adaptive Function Plus up to 4,1

Low consumption Compact-Y range

TCAEY-THAEY 115÷238

Cooling capacity: 15,4÷38,8 kW - Heating capacity: 16,8÷41,7 kW

Packaged air-cooled water chillers and reversible heat pumps with axial fans.Range with hermetic Scroll compressors and R410A refrigerant gas.

Construction features• Compressor: hermetic, rotary Scroll compressor, complete with

thermal protection and crankcase heater for mod. 127÷238.• Water side heat exchanger: adequately insulated stainless steel

plate exchanger, complete with antifreeze heater and water fl ow diff erential pressure switch.

• Air side heat exchanger: featuring fi nned coil with copper pipes and aluminium fi ns, complete with protection grille.

• Fan: electric axial fan with external rotor, equipped with internal thermal protection and complete with protection grille.

• Control: microprocessor electronic control, iDRHOSS compatible, with Adaptive Function Plus logic.

• Structure: in galvanised and painted sheet steel, complete with condensation drain pan.

Models• TCAEY: unit designed for cooling only.• THAEY: heat pump unit.

STANDARD unit (for mod. 133÷238)• Without pump assembly and water buff er tank.

PUMP unit• Pump assembly complete with: circulation pump, expansion tank

with membrane, manual bleed valve and safety valve, pressure gauge.

TANK & PUMP unit• Pump assembly complete with: inertial water buff er tank,

circulation pump, expansion tank with membrane, manual air bleed valve, automatic air bleed valve, safety valve, pressure gauge.

FACTORY FITTED ACCESSORIES• Soft-start device.• Silenced installation.• -10°C condensation control.• Antifreeze electric heater on the buff er tank.• Crankcase heater compressor (mod. 115÷124).• Unit base antifreeze electric heater for operation in

heat pump mode at low external air temperatures (mod. 115÷130).

• Desuperheater 15% (mod. 133-233).• 100% heat recovery (mod. 133-233).• Pump with increased head pressure (mod. 133÷238) or

circulator with low head pressure (mod. 115÷233).• Pump with increased head pressure (mod. 133÷238) or circulator

with low head pressure (mod. 115÷233) + buff er tank.• Digital input for double set-point• 4-20 mA analogue input for shifting set-point.

ACCESSORIES SUPPLIED LOOSE• Antivibration rubber mountings.• -10°C condensation control.• Water fi lter.• 3-way valve for the production of hot water (mod. 115÷133).• External air temperature probe for

set-point compensation.• Additional electric heater for heat pump, managed by regulation.• Remote keyboard with display.• Clock card• Serial interfaces for connection to BMS (proprietary protocol,

Modbus RTU, LonWorks).• Serial interface (CAN-bus - Controller Area Network) for the

iDRHOSS system.• Serial converters (RS485/RS232, RS485/USB) in the case of

centralised unit management.• GSM 900/1800 modem kit for remote unit management.• RHOSS supervision software for unit monitoring and remote

management.

Page 2: Low consumption Compact-Y range TCAEY-THAEY 115÷238 · Web code: CHCY 28 • Hydraulic equipment for radiant applications • ESEER with Adaptive Function Plus up to 3,9 Low consumption

E.S.E.E.R.+ 3,49 3,42 3,82 3,41 3,50 3,20 3,19 4,11 4,12

27

WAT

ER C

HIL

LER

SH

EAT

PU

MP

SA

IR c

oole

dA

XIA

L fa

ns

WAT

ER C

HIL

LER

SH

EAT

PU

MP

SA

IR c

oole

dCE

NTR

IFU

GA

L fa

ns

WAT

ER C

HIL

LER

SH

EAT

PU

MP

SW

ATER

coo

led

CON

DEN

SER

LESS

UN

ITS

IND

UST

RIA

L &

PR

OCE

SS C

OO

LIN

GEX

PP

olyv

alen

t sy

stem

sCO

ND

ENSI

NG

UN

ITS

SYST

EM A

CCES

SOR

IES

FAN

CO

IL U

NIT

STE

RM

INA

L U

NIT

S

In the following conditions:

Air: 35°C - Water: 12/7°C.

Air: 7°C D.B. - 6°C W.B. - Water: 40/45°C.

5 m from the unit in free fi eld (Q = 2).

The weight refers to the unit in its most complete form.

ESEER (European Seasonal EER) - Average European seasonal effi ciency.

ESEER with Adaptive Function Plus software.

(*) Unit without circulator pump.

(**) Reference for the tax credit for the French market.

(***) Energy indices for versions with a standard head pump, calculated in compliance

with that envisaged by the EN 14511:2004 Standard, in the conditions prescribed by

the Finance Act, Italian market.

TCAEY-THAEY MODEL

Nominal cooling capacity kW

E.E.R.

E.S.E.E.R.

Absorbed power (*) kW

Nominal heating capacity kW

C.O.P.

Absorbed power (*) kW

E.E.R. (EN 14511:2004) (***)

C.O.P. (EN 14511:2004) (***)

C.O.P. (**)

Sound pressure level dB(A)

Silenced version sound pressure level dB(A)

Scroll/step compressor no.

Circuits no.

Water buffer tank content l

Available nominal head pressure of circulator pump/standard kPa

Mains supply V-ph-Hz

DIMENSIONS AND WEIGHTS

L - Width STANDARD mm

W - Width PUMP mm

L - Width TANK & PUMP mm

H - Height mm

D - Depth mm

Weight TCAEY kg

Weight THAEY kg

115 117 122 124 127 130 133 233 238

15,4 17,4 22,7 24,3 26,9 29,1 34,0 32,5 38,8

2,76 2,67 2,76 2,62 2,59 2,44 2,56 2,64 3,06

3,15 3,11 3,44 3,09 3,18 2,89 2,85 3,67 3,69

5,6 6,5 8,2 9,3 10,4 11,9 13,3 12,3 12,7

16,8 17,9 23,9 26,1 30,7 34,4 39,1 37,5 41,7

3,05 2,94 3,02 2,92 3,07 3,10 2,94 3,05 3,26

5,5 6,1 7,9 8,9 10,0 11,1 13,3 12,3 12,8

– – – – – – – 3,33 4,03

– – – – – – – 4,00 4,26

3,74 3,77 3,93 3,76 3,94 3,86 3,67 3,96 4,16

50 50 52 52 53 53 54 54 54

46 46 49 49 50 50 51 51 51

1/1 1/1 1/1 1/1 1/1 1/1 1/1 2/2 2/2

1 1 1 1 1 1 1 1 1

35 35 45 45 45 45 80 80 150

74/147 63/130 64/130 66/125 61/110 57/105 65/134 69/134 130

400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50

115 117 122 124 127 130 133 233 238

– – – – – – 1,660 1,660 2,260

1.230 1.230 1.230 1.230 1.535 1.535 1.660 1.660 2.260

1.522 1.522 1.522 1.522 1.822 1.822 1.660 1.660 2.260

1.090 1.090 1.280 1.280 1.510 1.510 1.570 1.570 1.570

580 580 600 600 695 695 1.000 1.000 1.000

210 220 270 280 310 370 450 465 625

215 225 278 288 320 380 460 475 645

COOLINGONLY

HEAT PUMP OUTDOOR INSTALLATION

Page 3: Low consumption Compact-Y range TCAEY-THAEY 115÷238 · Web code: CHCY 28 • Hydraulic equipment for radiant applications • ESEER with Adaptive Function Plus up to 3,9 Low consumption

Web code: CHCY

28

• Hydraulic equipment for radiant applications

• ESEER with Adaptive Function Plus up to 3,9

Low consumption Compact-Y range

TCAEY-THAEY 118÷136 H.E.

Cooling capacity: 13,2÷27,8 kW - Heating capacity: 15,6÷31,7 kW

High energy effi ciency packaged air-cooled water chillers and reversible heat pumpswith axial fans. Range with hermetic Scroll compressorsand R410A refrigerant gas.

Construction features • Compressor: hermetic, rotary Scroll compressor, complete with

thermal protection and crankcase heater.• Water side heat exchanger: adequately insulated stainless steel

plate exchanger, complete with antifreeze heater and water fl ow diff erential pressure switch.

• Air side heat exchanger: featuring fi nned coil with copper pipes and aluminium fi ns, complete with protection grille.

• Fan: electric axial fans with external rotor, equipped with internal thermal protection, protection grilles and proportional electronic device for continuous fan rotation speed regulation.

• Control: microprocessor electronic control, iDRHOSS compatible, with Adaptive Function Plus logic.

• Structure: in galvanised and painted sheet steel, complete with condensation drain pan for THAEY.

Models • TCAEY: unit designed for cooling only.• THAEY: heat pump unit.

PUMP unit• Pump assembly complete with: circulation pump, expansion tank

with membrane, manual bleed valve and safety valve, pressure gauge.

TANK & PUMP unit• With tank and pump.• With tank, pump and water bypass between primary and

secondary circuit. Pump assembly complete with: circulation pump and water

buff er tank or circulation pump, water buff er tank and water bypass which disconnects the primary from the secondary water circuit, expansion tank with membrane, manual air bleed valve, automatic air bleed valve, safety valve and pressure gauge.

FACTORY FITTED ACCESSORIES• Circulator pump with low head pressure.• Circulator pump with low head pressure + water

buff er tank.• Circulator pump with low head pressure

+ water buff er tank + delivery and return pipe bypass.• Soft-start device.• Silenced installation.• Antifreeze electric heater on the buff er tank.• Unit base antifreeze electric heater for operation in heat pump

mode at low external air temperatures.• Digital input for double set-point• 4-20 mA analogue input for shifting set-point.

ACCESSORIES SUPPLIED LOOSE• 3-way valve for the production of hot water.• External air temperature probe for

set-point compensation.• Additional electric heater for heat pump, managed by regulation.• Antivibration rubber mountings.• Water fi lter.• Remote keyboard with display.• Clock card• Serial interfaces for connection to BMS (proprietary protocol,

Modbus RTU, LonWorks).• Serial converters (RS485/RS232, RS485/USB) in the case of

centralised unit management.• Serial interface (CAN-bus - Controller Area Network) for the

iDRHOSS system.• GSM 900/1800 modem kit for remote unit management.• RHOSS supervision software for unit monitoring and remote

management.

Page 4: Low consumption Compact-Y range TCAEY-THAEY 115÷238 · Web code: CHCY 28 • Hydraulic equipment for radiant applications • ESEER with Adaptive Function Plus up to 3,9 Low consumption

E.S.E.E.R.+ 3,86 3,89 3,80 3,78 3,94 3,67

29

WAT

ER C

HIL

LER

SH

EAT

PU

MP

SA

IR c

oole

dA

XIA

L fa

ns

WAT

ER C

HIL

LER

SH

EAT

PU

MP

SA

IR c

oole

dCE

NTR

IFU

GA

L fa

ns

WAT

ER C

HIL

LER

SH

EAT

PU

MP

SW

ATER

coo

led

CON

DEN

SER

LESS

UN

ITS

IND

UST

RIA

L &

PR

OCE

SS C

OO

LIN

GEX

PP

olyv

alen

t sy

stem

sCO

ND

ENSI

NG

UN

ITS

SYST

EM A

CCES

SOR

IES

FAN

CO

IL U

NIT

STE

RM

INA

L U

NIT

S

In the following conditions:

Air: 35°C - Water: 23/18°C.

Air: 7°C D.B. - 6°C W.B. - Water: 30/35°C.

Air: 35°C - Water: 12/7°C

Air: 7°C D.B. - 6°C W.B. - Water: 40/45°C.

5 m from the unit in free fi eld (Q = 2).

TCAEY-THAEY H.E. MODEL

Nominal cooling capacity (radiating) kW

E.E.R. (radiating)

Absorbed power (radiating) (*) kW

Nominal heating capacity (radiating) kW

C.O.P. (radiating)

C.O.P. (**)

Absorbed power (radiating) (*) kW

Cooling capacity kW

E.E.R.

E.S.E.E.R.

E.S.E.E.R.+

Absorbed power (*) kW

Heating capacity kW

C.O.P.

Absorbed power (*) kW

Sound pressure level dB(A)

Silenced version sound pressure level dB(A)

Scroll/step compressor no.

Circuits no.

Water buffer tank content l

Available nominal head pressure of circulator pump/pump kPa

Mains supply V-ph-Hz

DIMENSIONS AND WEIGHTS

W - Width PUMP mm

W - Width TANK & PUMP mm

H - Height mm

D - Depth mm

Weight TCAEY kg

Weight THAEY kg

118 120 125 129 132 136

18,0 20,6 24,6 28,8 31,5 40,5

3,52 3,56 3,51 3,54 3,58 3,53

5,10 5,78 7,00 8,13 8,78 11,46

16,1 17,7 20,7 24,5 28,4 33,5

4,28 4,23 4,25 4,12 4,12 4,10

3,96 3,95 4,04 3,98 3,93 3,96

3,75 4,18 4,87 5,94 6,90 8,18

13,4 15,5 18,7 22,6 24,3 27,8

2,70 2,92 2,97 2,97 2,96 2,74

3,48 3,51 3,45 3,42 3,58 3,31

4,95 5,33 6,30 7,61 8,20 10,12

15,6 16,1 20,3 23,8 27,7 31,7

3,14 3,09 3,32 3,19 3,20 3,13

4,97 5,23 6,10 7,48 8,63 10,12

48 50 52 52 53 53

44 46 49 49 50 50

1/1 1/1 1/1 1/1 1/1 1/1

1 1 1 1 1 1

35 35 45 45 45 45

63/129 45/108 55/116 45/98 42/95 47/81

400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50

118 120 125 129 132 136

1.230 1.230 1.230 1.230 1.535 1.535

1.522 1.522 1.522 1.522 1.822 1.822

1.090 1.090 1.280 1.280 1.510 1.510

580 580 600 600 695 695

210 220 270 280 310 370

215 225 278 288 320 380

COOLINGONLY

HEAT PUMP OUTDOOR INSTALLATION

ESEER (European Seasonal EER) - Average European seasonal effi ciency.

ESEER with Adaptive Function Plus software.

(*) Unit without pump.

(**) Reference for the tax credit for the French market.

Page 5: Low consumption Compact-Y range TCAEY-THAEY 115÷238 · Web code: CHCY 28 • Hydraulic equipment for radiant applications • ESEER with Adaptive Function Plus up to 3,9 Low consumption

Web code: C1CY

30

• 3 capacity steps

• ESEER with Adaptive Function Plus up to 5

Low consumption Compact-Y range

TCAEY-THAEY 245÷265

Cooling capacity: 44,2÷64 kW - Heating capacity: 47,8÷67,9 kW

Packaged air-cooled water chillers and reversible heat pumps with axial fans.Range with hermetic Scroll compressors and R410A refrigerant gas.

Construction features• Compressor: hermetic, rotary Scroll compressor, complete with

thermal protection and crankcase heater. 3 capacity steps with high effi ciency at partial loads.

• Water side heat exchanger: adequately insulated stainless steel plate exchanger, complete with antifreeze heater and water fl ow diff erential pressure switch.

• Air side heat exchanger: featuring fi nned coil with copper pipes and aluminium fi ns, complete with protection grille.

• Fan: electric axial fans with external rotor, equipped with internal thermal protection, protection grilles and proportional electronic device for continuous fan rotation speed regulation.

• Control: microprocessor electronic control, iDRHOSS compatible, with Adaptive Function Plus logic.

• Structure: in galvanised and painted sheet steel.

Models• TCAEY: unit designed for cooling only.• THAEY: heat pump unit.

FACTORY FITTED ACCESSORIES• PUMP with single or double pump, including an automatic pump

in standby, complete with expansion tank, air bleed valve, safety valve and water pressure gauge. The pumps are available in the low or high pressure versions.

• TANK&PUMP with water buff er tank and single or double pump, including an automatic pump in standby, complete with expansion tank, air bleed valve, safety valve and water pressure gauge. The pumps are available in the low or high pressure versions.

• Soft-start device.• Silenced installation.• 15% desuperheater.• 100% heat recovery.• Refrigerant circuit high and low pressure gauges.• Antifreeze electric heater for buff er tank and pumps.• Digital input for double set-point 4-20 mA analogue

input for shifting set-point.

ACCESSORIES SUPPLIED LOOSE• External air temperature probe for

set-point compensation.• Additional electric heater for heat pump, managed by regulation.• Antivibration rubber mountings.• Water fi lter.• Remote keyboard with display.• Clock card• Serial interfaces for connection to BMS (proprietary protocol,

Modbus RTU, LonWorks).• Serial interface (CAN-bus - Controller Area Network) for the

iDRHOSS system.• Serial converters (RS485/RS232, RS485/USB) in the case of

centralised unit management.• GSM 900/1800 modem kit for remote unit management.• RHOSS supervision software for unit monitoring and remote

management.

josepftufo
New Stamp
Page 6: Low consumption Compact-Y range TCAEY-THAEY 115÷238 · Web code: CHCY 28 • Hydraulic equipment for radiant applications • ESEER with Adaptive Function Plus up to 3,9 Low consumption

E.S.E.E.R.+ 4,38 4,98 5,04 4,72

31

WAT

ER C

HIL

LER

SH

EAT

PU

MP

SA

IR c

oole

dA

XIA

L fa

ns

WAT

ER C

HIL

LER

SH

EAT

PU

MP

SA

IR c

oole

dCE

NTR

IFU

GA

L fa

ns

WAT

ER C

HIL

LER

SH

EAT

PU

MP

SW

ATER

coo

led

CON

DEN

SER

LESS

UN

ITS

IND

UST

RIA

L &

PR

OCE

SS C

OO

LIN

GEX

PP

olyv

alen

t sy

stem

sCO

ND

ENSI

NG

UN

ITS

SYST

EM A

CCES

SOR

IES

FAN

CO

IL U

NIT

STE

RM

INA

L U

NIT

S

TCAEY-THAEY MODEL

Nominal cooling capacity kW

E.E.R.

E.S.E.E.R.

Absorbed power (*) kW

Nominal heating capacity kW

C.O.P.

Absorbed power (*) kW

E.E.R. (EN 14511:2004) (***)

C.O.P. (EN 14511:2004) (**) (***)

Sound pressure level dB(A)

Silenced version sound pressure level dB(A)

Scroll/step compressor no.

Circuits no.

Mains supply V-ph-Hz

DIMENSIONS AND WEIGHTS

W - Width mm

H - Height mm

D - Depth mm

Weight TCAEY kg

Weight THAEY kg

TANK & PUMP

TCAEY-THAEY MODEL

Nominal flow l/h

Water tank content l

Pump available head pressure

Pump P1 KPa

Pump P2 KPa

PUMP

TCAEY-THAEY MODEL

Nominal flow l/h

Pump available head pressure

Pump P1 KPa

Pump P2 KPa

245 250 260 265

44,2 51,3 59,2 64,0

2,55 2,60 2,68 2,67

3,78 4,31 4,38 4,03

17,4 19,7 22,1 24,0

47,8 55,8 62,2 67,9

2,89 3,00 3,04 2,91

16,6 18,6 20,5 23,3

3,36 3,34 3,39 3,44

3,93 3,94 3,93 3,97

56 56 57 57

53 53 54 54

2/3 2/3 2/3 2/3

1 1 1 1

400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50

245 250 260 265

2.260 2.260 2.260 2.260

1.570 1.570 1.570 1.570

1.000 1.000 1.000 1.000

725 750 775 820

745 770 795 840

245 250 260 265

7.600 8.800 10.200 11.000

150 150 150 150

113 103 88 75

186 179 169 150

245 250 260 265

7.600 8.800 10.200 11.000

122 114 102 92

195 190 184 167

COOLINGONLY

HEAT PUMP OUTDOOR INSTALLATION

In the following conditions:

Air: 35°C - Water: 12/7°C.

Air: 7°C D.B. - 6°C W.B. - Water: 40/45°C.

5 m from the unit in free fi eld (Q = 2).

The weight refers to the unit in its most complete form.

ESEER (European Seasonal EER) - Average European seasonal effi ciency.

ESEER with Adaptive Function Plus software.

(*) Unit without pump.

(**) Reference for the tax credit for the French market.

(***) Energy indices calculated in compliance with that envisaged by

EN 14511: 2004 Standard, in the conditions prescribed by the Finance Act, Italian

market.