Logstrup Modular System - Elektrik Pano Üreticileri Dern Logstrup Modular System ... MW combined...
Transcript of Logstrup Modular System - Elektrik Pano Üreticileri Dern Logstrup Modular System ... MW combined...
1
Logstrup Modular System
The Logstrup Modular System is designed in modules of 190 mm. It is modular in all 3 axis, XYZ.
The system enables you to build nearly all possible configurations of Switchboards and Motor Control Centres with Fixed, Removable or Withdrawable outgoing units.
The Logstrup Modular System consists of: • Base frame• Framework (2 mm framework in aluzinc, 5 bends to ensure maximum strength)• Cladding (Plates, Doors in 1,5 mm or 2,0 mm steel)
– up to IP44 Standard (IP54 optional in fixed type)• a number of other items, e.g. Copper, Internal parts.
What is Logstrup?
The Logstrup modular system is equally suited for:
• Main Power distribution boards• Sub-distribution panels• Motor Control Centers• Control panels, Rack systems • Drive system enclosures
The Logstrup system:
• Meets (and exceeds) IEC requirements• Has UL and CSA approval• Approved by 5 major marine classes
What is Logstrup?
The Logstrup modular system is proven to be ”fit for purpose” in a large range of applications, industries and world wide locations.
• Critical process industries
• Food & Dairy
• Heavy power consumption (steel, mining, aluminium etc.)
• Petrochemical
• Off-shore and Marine
• ”Stress environments” (Dredging &naval vessels)
• Energy sector (Hydro-power, wind,nuclear, geothermal, ”fossile” etc.)
• Infrastructure
• Building services
4
Framework:Height: Max.: 12 modules (2280mm) (Standard 11 modules (2090mm)).
Width: Max.: 12 modules.
Depth: Standard: 3 or 4 modules.
Logstrup Dimensions
Base frame: Height: 95 mm.
Width: Max.: 12 modules.
Depth: Short (ABA) or Long (AZB).
Standard color RAL7032 Plain Structure – All colors available
5
Principle of the Logstrup System
Front view
Top view
Incommer Functional unit + Cable sectionFront Access
6
Principle of the Logstrup System
Front view
Top view
Functional unit + Cable sectionIncommerRear Access
12
XY or Z
Main Busbar
XY: The original design
The copper bars are placed on top of each other.Advantage: No bending is needed for the copper
connections.Disadvantage: The copper bars heat one another in
this position.
Z:By later investigations, it was discovered that you can
increase the rating by 25% when the copper bare are placed in Z direction.
13
Main Busbar
1. Horizontal Busbar Z + Vertical Busbar Flat
2. Horizontal Busbar Z + Vertical Busbar XY
5. Horizontal Busbar XY + Vertical Busbar Flat
4. Horizontal Busbar XY + Vertical Busbar XY
3. Horizontal Busbar Z + Vertical Busbar Z
14
Examples of Main Busbars Placements
Busbar rating can be delivered from 250A – 8500A fully type tested.
Short-time withstand current (Icw): 135 kA/secPeak withstand current Ipk): 300 kA
3 framesMain busbar built in a separate frame
Main Busbar: Z, 6300A Main Busbar: Z, 8500A
Main Busbar: XY, 3000A
15
Logstrup Copper is either 6 or 12 mm in width. (Catalogue Section 4)
6x6mm6x12mm12x12mm12x18mm12x24mm12x30mm12x42mm12x66mm12x90mm12x114mm12x150mm
Copper Busbar: Type BSDLength: 4.58 Meters
Logstrup Copper
1 module in height
2 modules in height
16
Logstrup Copper is either supported by Single or Double Support. (Catalogue Section 4)
6x6mm6x12mm12x12mm12x18mm12x24mm12x30mm12x42mm12x66mm12x90mm12x114mm12x150mm
Logstrup Busbar Support
Single Support 50kA/sec. or 65kA/sec.
Double 100kA/sec.
17
Logstrup Busbar System: (Catalogue Section 4)
• At the top.• At the bottom.• 2 parallel (2//) Is possible in 2, 3 or 4 modules depth.• 2+2 parallel (2+2//) Is only possible in 4 modules depth.
Logstrup Busbar System
N, L3, L2, L1
N, L3, L2, L1 + N, L3, L2, L1
Front
Front
19
Functional unit + Cable section
Vertical Busbar Box
Main busbar placed at the top Main busbar placed at the bottom
4 sizes:
• 6 x 50 mm (800A) (Ik = 50kA/sec)• 6 x 80 mm (1000A) (Ik = 50kA/sec)• 6 x 100 mm (1250A) (Ik = 70kA/sec)• 6 x 50 mm + 6 x 100 mm (1600A) (Ik = 70kA/sec)
Ratings based on:Ambient Temp. 35° C & Max. Busbar Temp. 120° C
Vertical Busbars:Tin coveredIP2X protected
20
The Logstrup Switchgear and Controlgear System offers unlimited flexibility with a large range of unit types:
1. Withdrawable Units (WDU)2. Removable Units (RMU)3. Mini-withdrawable Units (MDU)4. Slimline Units (ABB Slimline and Jean Muller Sasil Products)
• Accommodates components from all manufacturers • High protection against contact• Fully re-configurable while live• High operational safety
Unit Types
1. WDU 2. RMU
3. MDU 4. Slimline
21
Incoming side: Power plugs directly connected with the vertical busbars.160A: 160A Power plugs 400A: 400A Power plugs 630A: 2x400A Power plugs
Outgoing side: Power plugs and Harting plugs (Power and/or control plugs).60A: 60A Harting80A: 80A Harting160A: 160A Power plugs 250A: 400A Power plugs 400A: 400A Power plugs 630A: 2x400A Power plugs
Module sizes: X = 3, 4. Y = ½, 1, 1½, 2, 2½, 3, 3½, 4
• Rating up to 630A / 250 kW• Unique safety interlocking mechanism• Front or rear access• DeviceNet & ProfiBus compatible
WDU – Withdrawable Units
22
WDU – Withdrawable Units
Top view Rear viewOutgoing side: Power plugs
Rear viewOutgoing side: Harting plugs(Power and/or control plugs)
Front view
23
Incoming side: Power plugs directly connected with the vertical busbars.160A: 160A Power plugs 400A: 400A Power plugs 630A: 2x400A Power plugs
Outgoing side: Connection with cables (no plugs).
Module sizes: X = 3, 4. Y = 1, 1½, 2, 2½, 3, 3½, 4
• Rating up to 630A / 250 kW• Unique safety interlocking mechanism• Front or rear access• DeviceNet & ProfiBus compatible
RMU – Removable Units
24
RMU – Removable Units
Top view Rear viewOutgoing side: Connection with cables
Rear viewOutgoing side: Connection with cables
Front view
25
Incoming side: Interface box with Power plugs directly connected with the vertical busbars.160A: 160A Power plugs
Outgoing side: Connection with cables to the Interface box.
• Up to 80A power plugs with 46 control pins• Removable interface box• Interface box can be pre-wired• DeviceNet & ProfiBus compatible
Module sizes:Y = 1
X = 1 (7,5 kW)X = 1½ (15kW)X = 2 (22kW)X = 3 (30kW)
MDU – Mini Withdrawable Units
26
Two Solutions for the Switch:1. Kraus & Naimer switch
• Includes a mechanical test function• Works by a disc• Is offered from Logstrup
• Incl. disc, bracket, shaft, handle.
2. GV2 solution• Does not include a mechanical test funtion.
• Test function should be made electrically
• Works by a triangular key• Electrical GV2 component is purchased locally
(not offered from Logstrup)
MDU – Mini Withdrawable Unit
27
Main breaker disconnected position1. Main breaker disconnected position2. Control contact “open”3. Main contact “open”.4. Drawer mechanically independent from the frame.
Main breaker Off position1. Main breaker Off position2. Control contact “open”3. Main contact “open”.4. Drawer mechanically locked in the frame.
Main breaker test position1. Main breaker test position2. Control contact “closed ”a. Contact test “closed ”3. Main contact “open”.4. Drawer mechanically locked in the frame.
Main breaker electric power position 1. Main breaker electric power position2. Control contact “closed ”a. Contact test “open”3. Main contact “closed”.4. Drawer mechanically locked in the frame.
MDU – With Kraus & Naimer Switch
28
Section Arc Control:When a Section Arc Control occurs, the pressure is released through flaps in the top.
Logstrup Arc Control System
Unit Arc Control: Flaps close in the chimney when a Unit Arc Control occurs, the pressure is released through the chimney and then through flaps in the top.
Internal Arc Test according to IEC 61641
Korinthos Power S.A, Greece
MCCRating: 4000AType: WDUNo. Of units: 48Year: 2010
The major Power Plant project of Korinthos Power S.A. has been equipped with the new and innovative ‘Omega’ Draw-out system.
The key characteristics of the project is the engineering, procurement, construction and commissioning of a 436.6 MW combined cycle gas turbine power plant with an efficiency higher than 57%. Requirements for safety and minimum downtime have been essential when choosing the OMEGA system.
This new unit presents a number of significant advantages, as it will be one of the most modern power plants to operate in Greece with very high energy efficiency. It is located near regions with high energy consumption requirements and uses existing infrastructure for its interconnection to the power grid and the Natural Gas system.
30
Nalco Aluminium Plant, India
MCCRating: 890AType: WDU & MDUNetwork: ProfibusNo. of units: 50Year: 2008
This Omega Withdrawable project was manufactured in Germany and supplied to Nalco’s Aluminium Smelter Expansion Project in Angul, India. All the large drives had air-conditioning built into the drawers, as the ambient temperature is 50 degree Celsius.
Nalco has plans to set up an Aluminium Park in Angul, as a joint venture with Orissa Industrial Infrastructure Development Corporation (IDCO).
Switchboard built by Kreutzpointner, Germnay
31
Mondi Paper Mill, Slovakia
MCC – Rear AccessRating: 1600AType: WDU & MDUNo. Of units: 56Year: 2007
Mondi Paper Mill is located in the town of Ruzomberok in the Northern part of Slovakia in the Tatra Mountains. The abundance of the raw materials such as wood, water and energy in this area has had a favourable influence on the development of the mill.
Switchboard built by 3D, Slovakia
32
Ostroleka Coal Burning Plant, Poland
SwitchboardRating: 2.500AType: WDUNo. Of units: 48Year: 2006
The Power Plant Complex is situated in the city of Ostroleka in the North-Eastern part of Poland about 120 km from Warsaw. The installation of the switchboard is a part of the modernization and adjustment process of the power plant in order to comply with EU standards.
The coal burning Power Plant Complex consists of a thermal power station with an output of 367 MW each. With a position among the top 15 of over 50 power plants in Poland, Ostroleka is a respected player in the market.
Switchboard built by Elektromontaz Poznan, Poland
33
L-Shaped draw-out MCC, Dredging vessel for U.A.E
Switchboard built by Bakker Sliedricht, Netherlands
34
Omega Withdrawable Panel for Luxury Yacht
Switchboard built by AAU Lübeck, Germany
Type: WDUProtection: MCCBMCC: XRating: 1000A
35
36
Power Generation, Russia
MCC / Power distributionRear Access.Rating: 4000AType: WDU & No. of Units: 30Year: 2008
Great Belt Bridge, Denmark
Over 1 km of switchboards - panels placed next to each other.
Switchboard built by Logstrup Denmark.
37
Different solutions
Face to face with busbar duct. Switchboard for Computer servers
Swedish Newspaper Stockholm
40
Klärwerk Gut-Grosslappen
Switchboard built by ELG Elektroanlagen, Germany
•Wastewater treatment
•WDU
45
SARCELLE Incineration Plant outside Paris
• 3 lines with each MSB1 , MSB2 and COM of 4000A
• 60 Drawers in total
• Intelligent panels using profibus
• supplied from logstrup and ready to be installed in 12 weeks
Built by Group Reyes Construction Eurocablage
46
NGHE SUGAR MILL FACTORY in VIETNAM
• 1600 A main busbar
•IP 44
• WDU with 46 aucilliary control signals
•Form 4b
• Supplied as partly build from Ireland
Build by Sang Tao Joint stock company Hochimin
47
PTT oil and GAS Thailand
• 960 A main busbar
•IP 44
• WDU with 24 aucilliary control signals
•Form 4b
•Rear access and arch fault protection
Build by TIC Modular systems Bankok
48
CEVITAL ALGERIE (sugar plant)
• 3500 A main busbar back to back
•IP 44
• WDU with 24 aucilliary control signals
•Form 3b
Build by EDBS Marocco
49
BARKA (Qatar desalination plant)
• 5500 2+2//12*90
•IP 54
• WDU with 24 aucilliary control signals
•Form 4b
Build by Soreel SAS France installateur DEGREMONT SAS