LOAD-SIDE VOLTAGE SAG ASSESSMENT: HANDS ON INVESTIGATION IN MALAYSIA INDUSTRIES AHMAD NIZAM BIN HASSAN A project report submitted in partial fulfilment of the requirements for the award of the degree of Master in Engineering (Electrical-Power) Faculty of Electrical Engineering Universiti Teknologi Malaysia NOVEMBER 2009

Transcript of LOAD-SIDE VOLTAGE SAG ASSESSMENT: HANDS ON...

Page 1: LOAD-SIDE VOLTAGE SAG ASSESSMENT: HANDS ON …eprints.utm.my/id/eprint/18393/1/AhmadNizamHassanMFKE2009.pdflink’ di dalam sistem peralatan di dalam industri. Data tahap sensitif

LOAD-SIDE VOLTAGE SAG ASSESSMENT:

HANDS ON INVESTIGATION IN MALAYSIA INDUSTRIES

AHMAD NIZAM BIN HASSAN

A project report submitted in partial fulfilment of the

requirements for the award of the degree of

Master in Engineering (Electrical-Power)

Faculty of Electrical Engineering

Universiti Teknologi Malaysia

NOVEMBER 2009

Page 2: LOAD-SIDE VOLTAGE SAG ASSESSMENT: HANDS ON …eprints.utm.my/id/eprint/18393/1/AhmadNizamHassanMFKE2009.pdflink’ di dalam sistem peralatan di dalam industri. Data tahap sensitif

iii

To my beloved parents, wife and children

who have been my greatest supports in life

Page 3: LOAD-SIDE VOLTAGE SAG ASSESSMENT: HANDS ON …eprints.utm.my/id/eprint/18393/1/AhmadNizamHassanMFKE2009.pdflink’ di dalam sistem peralatan di dalam industri. Data tahap sensitif

iv

ACKNOWLEDGEMENT

First of all, Praise to Allah, the Almighty Creator, the Most Gracious and the

Most Merciful.

Special thanks to my project supervisor, Assoc. Prof. Dr. Mohd Wazir bin

Mustafa, for his continuous supports, guidance and valuable feedback in doing this

project. His useful and wise suggestions have leaded this study to success.

My beloved parents, wife, son and daughter deserve my heartfelt thanks and

biggest gratitude for their endless love, support and belief in me. I would never come

up to this stage without them.

My sincere appreciation goes to TNB for providing test equipments for this

project, my colleagues and also everyone who has helped directly or indirectly in the

completion of this project.

Page 4: LOAD-SIDE VOLTAGE SAG ASSESSMENT: HANDS ON …eprints.utm.my/id/eprint/18393/1/AhmadNizamHassanMFKE2009.pdflink’ di dalam sistem peralatan di dalam industri. Data tahap sensitif

v

ABSTRACT

Voltage sag is short duration reduction of RMS voltage and it is recognized as

the most serious power quality problem for industries in Malaysia. The impact of

voltage sag to the industrial equipment depends on the severity of voltage sag and the

sensitivity level of equipments itself toward voltage sag. The concept of EMC for

voltage sag problem call for utilities, customers, equipment manufacturer and

regulators to play their role in order to minimize the impact of voltage sag by virtue

of complying to SEMI F47 and MS IEC 61000 curve. This project focuses on

determining the sensitivity level of selected industrial equipments by conducting

Ride through Test (RTT) using CHROMA 6530 Programmable AC Source and PSL

Industrial Power Corruptor. The industrial equipments selected are the production

machine for Semiconductor industries (Tester Machine, Wire Bond Machines and

Die Attached), Programmable Logic Controller (PLC) and Magnetic contactors. The

sensitivity or Immunity level data of the selected industrial equipments against

voltage sag has been established. Comparison on the sensitivity level among similar

type of equipments is also performed. It is evident from the RTT results, that

majority of semiconductor equipments are very sensitive to voltage sag. The RTT

results for PLCs and magnetic contactor also indicate that these two equipments are

very sensitive to voltage sag and establish themselves as one of the ‘weak links’ in

industrial equipment system. The established sensitivity data for the industrial

equipments is helpful in predicting estimated loss due to voltage sag and determining

the best cost effective voltage sag mitigation solution to the industrial equipments.

Page 5: LOAD-SIDE VOLTAGE SAG ASSESSMENT: HANDS ON …eprints.utm.my/id/eprint/18393/1/AhmadNizamHassanMFKE2009.pdflink’ di dalam sistem peralatan di dalam industri. Data tahap sensitif

vi

ABSTRAK

Voltan lendut adalah pengurangan voltan RMS untuk seketika dan telah

dikenali sebagai satu masalah kualiti kuasa yang paling serius bagi industri di

Malaysia. Kesan voltan lendut terhadap peralatan industri bergantung kepada tahap

voltan lendut dan aras sensitif peralatan tersebut terhadap voltan lendut. Konsep

EMC berpandukan SEMI F47 dan MS IEC 61000 Standard terhadap kejadian voltan

lendut telah membawa kepada kerjasama antara pihak pembekal tenaga elektrik,

pengguna dan pembuat peralatan memainkan peranan masing-masing bagi

mengurangkan kesan voltan lendut ini. Projek ini bertumpu kepada mengenalpasti

tahap sensitif peralatan industri yang dipilih dengan menjalankan ujian ‘Ride-

through Test (RTT)’ menggunakan ‘CHROMA 6530 Programmable AC Source’ dan

‘PSL Industrial Power Corruptor’. Peralatan industri yang dipilih untuk kajian

adalah peralatan Industri Semikonduktor (Tester Machine, Wire Bond Machines and

Die Attached), Programmable Logic Controller (PLC) dan Magnetic Contactor.

Data tahap atau aras sensitif peralatan tersebut terhadap voltan lendut telah

ditentukan. Perbandingan tahap sensitif antara peralatan yang sama jenis juga telah

dijalankan. Berdasarkan keputusan RTT, kebanyakan peralatan Industri

Semikonduktor adalah sangat sensitive terhadap voltan lendut. Keputusan RTT

untuk PLC dan magnetic contactor juga menunjukan peralatan tersebut adalah sangat

sensitif terhadap voltan lendut dan ini juga megesahkan peralatan ini sebagai ’weak

link’ di dalam sistem peralatan di dalam industri. Data tahap sensitif peralatan yang

telah di kumpul boleh membantu dalam membuat tafsiran tahap kerugian akibat

kejadian voltan lendut dan juga boleh membantu industri dalam menentukan kaedah

mitigasi yang paling menguntungkan bagi menangani kesan voltan lendut.

Page 6: LOAD-SIDE VOLTAGE SAG ASSESSMENT: HANDS ON …eprints.utm.my/id/eprint/18393/1/AhmadNizamHassanMFKE2009.pdflink’ di dalam sistem peralatan di dalam industri. Data tahap sensitif

vii

TABLE OF CONTENTS

CHAPTER TITLE

PAGE

DECLARATION

DEDICATION

ACKNOWLEDGEMENT

ABSTRACT

ABSTRAK

TABLE OF CONTENTS

LIST OF TABLES

LIST OF FIGURES

LIST OF SYMBOLS

LIST OF APPENDICES

ii

iii

iv

v

vi

vii

x

xi

xiii

xiv

1 INTDODUCTION

1.1 Project Background

1.2 Problem Statement

1.3 Literature Review

1.4 Project Objectives

1.5 Scope of project

1.6 Importance of project

1.7 Report Organization

1

3

3

5

5

6

6

2 POWER QUALITY AND VOLTAGE SAG

2.1 Introduction

2.2 Power Quality

8

8

Page 7: LOAD-SIDE VOLTAGE SAG ASSESSMENT: HANDS ON …eprints.utm.my/id/eprint/18393/1/AhmadNizamHassanMFKE2009.pdflink’ di dalam sistem peralatan di dalam industri. Data tahap sensitif

viii

2.3 Voltage Sag

2.3.1 Fault Clearing Time

2.3.2 Fault Location and Sag Magnitude

2.4 Voltage Sag Standards and Guidelines

2.5 Summary

10

14

15

16

18

3 LOAD-SIDE VOLTAGE SAG ASSESSMENT

3.1 Introduction

3.2 Generic Methodology

3.3 Test Equipment or Sag Generator

3.3.1 CHROMA Programmable AC Source

3.3.2 PSL Industrial Power Corruptor

3.4 Summary

19

19

20

20

21

24

4 RESULTS AND DISCUSSION

4.1 Introduction

4.2 Industries Affected by Voltage Sag

4.3 Semiconductor Industries

4.3.1 RTT results for Semiconductors Industries

4.3.2 Discussion

4.4 Non-semiconductor Industries

4.4.1 Magnetic Contactors

4.4.2 RTT Results for Magnetic Contactor

4.4.3 Discussion

4.4.4 Programmable Logic Controller (PLC)

4.4.5 RTT Results for PLC

4.4.6 Discussion

4.5 Summary

25

25

27

27

33

34

36

37

39

40

41

42

43

5 CONCLUSION AND FUTURE WORKS

5.1 Conclusion

5.2 Recommendation for Future Works

44

45

Page 8: LOAD-SIDE VOLTAGE SAG ASSESSMENT: HANDS ON …eprints.utm.my/id/eprint/18393/1/AhmadNizamHassanMFKE2009.pdflink’ di dalam sistem peralatan di dalam industri. Data tahap sensitif

ix

REFERENCES

47

Appendices A - D 50 - 53

Page 9: LOAD-SIDE VOLTAGE SAG ASSESSMENT: HANDS ON …eprints.utm.my/id/eprint/18393/1/AhmadNizamHassanMFKE2009.pdflink’ di dalam sistem peralatan di dalam industri. Data tahap sensitif

x

LIST OF TABLES

TABLE NO. TITLE

PAGE

4.1 Industries in Malaysia Affected by Voltage Sag 26

4.2 RTT results for Semiconductor Plant A 28

4.3 RTT results for Semiconductor Plant B 29

4.4 RTT results for Semiconductor Plant C 29

4.5 RTT results for Magnetic Contactors 38

4.6 RTT results for PLC

41

Page 10: LOAD-SIDE VOLTAGE SAG ASSESSMENT: HANDS ON …eprints.utm.my/id/eprint/18393/1/AhmadNizamHassanMFKE2009.pdflink’ di dalam sistem peralatan di dalam industri. Data tahap sensitif

xi

LIST OF FIGURES

FIGURE NO. TITLE

PAGE

2.1 Definition of Voltage Disturbances (IEEE 1159:1995)

11

2.2 Example of voltage sag (40% voltage sag for 400ms)

12

2.3 Example of voltage sag due to fault in the supply network

13

2.4 Relation between point of fault and Sag magnitude

15

2.5 MS IEC 61000 and SEMI F47 Curve

17

3.1 PSL Industrial Power Corruptor (IPC-480V-200A)

22

3.2 PSL IPC is used to simulate voltage sag for 1-phase equipment

23

3.3 PSL IPC is used to simulate voltage sag for 3-phase equipment

23

4.1 Voltage Sag Immunity level vs. SEMI F47 for Wire Bond Machines

30

4.2 Voltage Sag Immunity level vs. SEMI F47 for Die Attached Machine

30

4.3 Voltage Sag Immunity level vs. SEMI F47 for MOLD TOWA

31

4.4 Voltage Sag Immunity level vs. SEMI F47 for Catalyst 13

31

4.5 ADVANTEST T5585

32

4.6 RTT to the Power Conditioner of ADVANTEST

32

Page 11: LOAD-SIDE VOLTAGE SAG ASSESSMENT: HANDS ON …eprints.utm.my/id/eprint/18393/1/AhmadNizamHassanMFKE2009.pdflink’ di dalam sistem peralatan di dalam industri. Data tahap sensitif

xii

4.7 Typical schematic circuit configuration for motor

35

4.8 Sample of Magnetic Contactor

37

4.9 Voltage Sag Immunity level vs. MS IEC 61000 for Magnetic Contactors

39

4.10 Sample of PLC

40

4.11 Voltage Sag Immunity level vs. MS IEC 61000 for PLCs

42

Page 12: LOAD-SIDE VOLTAGE SAG ASSESSMENT: HANDS ON …eprints.utm.my/id/eprint/18393/1/AhmadNizamHassanMFKE2009.pdflink’ di dalam sistem peralatan di dalam industri. Data tahap sensitif

xiii

LIST OF SYMBOLS

pu - Per unit

PCC - Point of Common Coupling

sV - Supply Voltage

PCCV - Voltage at PCC

CustBV - Voltage at Customer B

fZ - Fault Impedance

SZ - Source Impedance

Page 13: LOAD-SIDE VOLTAGE SAG ASSESSMENT: HANDS ON …eprints.utm.my/id/eprint/18393/1/AhmadNizamHassanMFKE2009.pdflink’ di dalam sistem peralatan di dalam industri. Data tahap sensitif

xiv

LIST OF APPENDICES

APPENDIX TITLE

PAGE

A CHROMA Programmable AC Source Specification

50

B PSL Industrial Power Corruptor General Specifications

51

C Sample of Single line schematic diagram: Machine 1

52

D Sample of Single line schematic diagram: Machine 2

53

Page 14: LOAD-SIDE VOLTAGE SAG ASSESSMENT: HANDS ON …eprints.utm.my/id/eprint/18393/1/AhmadNizamHassanMFKE2009.pdflink’ di dalam sistem peralatan di dalam industri. Data tahap sensitif

CHAPTER 1

INTRODUCTION

1.1 Project Background

Electric utilities, major end users of electric power or industrial customers,

equipment manufacturers and even regulators are becoming increasingly concerned

about the quality of electric power since the late 1980s. This was due to mainly to

the newer generation of equipments used in the industries that consists of

microprocessor based control and power electronics devices. These new and high-

tech equipments do not tolerate well with any variations in the quality of the supply

such as voltage sag (or voltage dip). Over the past decade, voltage sag has emerged

as the most serious Power Quality problem especially in the context of industries in

Malaysia. Not only have industrial equipments become more sensitive, industries

have also become intolerant to loss of production time due to their reduced profit

margins and competitiveness.

With the consensus that Power Quality problem such as voltage sag is a

compatibility problem, all parties (utilities, customers, equipment manufacturer and

regulators) have started working together to minimize the impact of voltage sag. In

the context of Malaysia environment, the understanding of industries and other end

users on the compatibility issues is still relatively low.

Page 15: LOAD-SIDE VOLTAGE SAG ASSESSMENT: HANDS ON …eprints.utm.my/id/eprint/18393/1/AhmadNizamHassanMFKE2009.pdflink’ di dalam sistem peralatan di dalam industri. Data tahap sensitif

2

Industries in Malaysia are always challenging the utility company, Tenaga

Nasional Berhad (TNB) to improve the quality of power delivered. As one of the

initiatives to assist its customers to mitigate the impact of voltage sag, TNB has

offered load-side voltage sag assessment. This project is based on the load-side

voltage sag assessment that has been performed to industries in Malaysia.

Determining the sensitivity or immunity level of the equipments against

voltage sag is the main output of the Load-side voltage sag assessment. Generally

there are three (3) methods that can be used to ascertain the sensitivity level of the

equipment [1, 4]. The first method is from the manufacturer’s specification of the

equipment. Unfortunately, not every manufacturer spells out the ride through

capability of the equipments towards voltage sag in the specifications. The second

method is by monitoring voltage sag events using power quality recorder install as

the incoming supply of the equipment. This method requires continuous monitoring

and could take a long period of time. The last method is by conducting immunity or

ride-through test (RTT) on the equipments which is the main activity in the Load-

side voltage sag assessment or investigation. The RTT is conducted by injecting

voltage sag (or voltage dips) of specified depths and duration into the equipments.

This is the easiest and quickest way to determine the sensitivity or immunity level of

the equipments. Knowing the sensitivity level of the equipments will help the

industries to predict estimated losses due to voltage sag more accurately and also

help in deciding the best cost effective mitigation solution to alleviate the affect of

voltage sag to their industry.

Page 16: LOAD-SIDE VOLTAGE SAG ASSESSMENT: HANDS ON …eprints.utm.my/id/eprint/18393/1/AhmadNizamHassanMFKE2009.pdflink’ di dalam sistem peralatan di dalam industri. Data tahap sensitif

3

1.2 Problem Statement

This project involves identification of critical and industrial equipments or

components in industrial machines that are sensitive to voltage sag. Sensitivity or

immunity level data of the selected equipments or components can be determined

and established by performing Ride-Through Test (RTT). The RTT is performed by

using two (2) Test Equipments according to ratings and capacity of the equipments or

components. The benefit of the equipment sensitivity data will be discussed and

highlighted. Recommendation for further work will also be proposed.

1.3 Literature Review

Appreciation on the sensitivity towards voltage sag of modern industrial

processes such as Adjustable Speed Drives (ASD), Programmable Logic Controller

(PLC), computer, motor contactors etc. has started way in 1993 [7]. There is a need

to know the exact sensitivity level of the equipments to predict losses. Information

about the sensitivity level of individual equipment can be obtained either from

equipment manufacturer’s specification or through comprehensive laboratory test [4].

Since most equipment manufacturers do not specify the equipments sensitivity level

towards voltage sag, testing of the equipments ride through capability is the best

option.

Introduction of the Electromagnetic Compatibility (EMC) concept for Power

Quality [24] further encouraged the investigation or assessment to determine the

sensitivity level of equipments by customers or end users. Over the years,

investigation to determine sensitivity level of individual equipments has been done

Page 17: LOAD-SIDE VOLTAGE SAG ASSESSMENT: HANDS ON …eprints.utm.my/id/eprint/18393/1/AhmadNizamHassanMFKE2009.pdflink’ di dalam sistem peralatan di dalam industri. Data tahap sensitif

4

namely for Personal Computer, AC Coil Contactors and Adjustable Speed Drive [11-

13]. These sensitivity levels of equipments are important and used in loss assessment

(financial loss) due to voltage sag [5, 6]. In Malaysia environment, load-side voltage

sag assessment was proposed in [1]. It is actually one of initiatives by the utility

Tenaga Nasional Berhad (TNB) to assist its customer to mitigate voltage sag affect to

the industries. Further investigation on the sensitivity level of equipment was

performed by [14]. The investigation focused on finding the immunity level of

Personal Computers.

This project is based on the load-side voltage sag assessment that has been

performed on behalf of TNB to various industries in Malaysia. The sensitivity level

data of critical industrial equipments are established. Critical industrial equipments

studied were divided into two (2) categories namely the Semiconductor industries

and the Non-semiconductor industries. As for Non-semiconductor industries, PLC

and magnetic contactor are chosen to be studied. Semiconductor industries are well

known for its affect by voltage sag and it is valuable to know the exact sensitivity

level of the semiconductor production equipments. Even with sensitivity level of

magnetic contactors and PLCs have been studied before, there is still a need to study

the sensitivity on actual industrial PLCs and magnetic contactors that are being used

(in operation) in most industries in Malaysia.

Page 18: LOAD-SIDE VOLTAGE SAG ASSESSMENT: HANDS ON …eprints.utm.my/id/eprint/18393/1/AhmadNizamHassanMFKE2009.pdflink’ di dalam sistem peralatan di dalam industri. Data tahap sensitif

5

1.4 Project Objectives

The objectives of this project are as follows:-

i) To identify what industries in Malaysia that are affected by voltage sag

ii) To identify what types of equipments or components of equipments in

industries that are sensitive to voltage sag

iii) To establish the voltage sag immunity level of the equipments or

components in equipment i.e. equipments or components sensitivity data.

iv) To check compliancy of the equipments or components in equipments

against recommended guidelines or standards such as SEMI F47 and MS

IEC 61000

1.5 Scope of project

The scope of this project can be categorised into several subtasks as follows:-

i) To study the voltage sag and its attributes that relevant to Malaysia

environment

ii) To study types of industries that are affected with voltage sag in Malaysia

Industries

iii) To study the types of equipments or components in the industries that are

sensitive for the industries

iv) To determine the voltage sag immunity level of the equipment by

performing Ride-Through Test (RTT)

Page 19: LOAD-SIDE VOLTAGE SAG ASSESSMENT: HANDS ON …eprints.utm.my/id/eprint/18393/1/AhmadNizamHassanMFKE2009.pdflink’ di dalam sistem peralatan di dalam industri. Data tahap sensitif

6

1.6 Importance of project

The significance of this project is to establish Sensitivity Data for equipments

in Malaysia Industries by performing RTT. The equipments tested are practical

equipments that are in operation or utilized in actual Malaysia Industries.

Semiconductor industries equipments, magnetic contactor and PLC are selected for

this project i.e. three (3) equipments sensitivity data are established. The equipment

sensitivity data established, among others can be used for by industries to evaluate

their susceptibility to voltage sag, predicting unwanted loss due to voltage sag events

and assist the industries to seek the best cost effective mitigation solution.

Equipment manufacturer can also evaluate their product and be encouraged to further

improve their product performance against voltage sag or developing different range

of product that performs better against voltage sag. This action by several parties

will in the end contribute significantly to minimize the impact of voltage to the

industries.

1.7 Report Organization

This report has been divided into five (5) chapters. This chapter brief the

introduction of the Load-side Voltage Sag Assessment and the purpose of the project.

This chapter also includes the literature review regarding the assessment of

sensitivity or immunity level of industrial equipment.

Chapter 2 discuss on the voltage sag as part of Power Quality problem or

issue. Characterization of voltage sag together with related standards or guidelines is

also discussed.

Page 20: LOAD-SIDE VOLTAGE SAG ASSESSMENT: HANDS ON …eprints.utm.my/id/eprint/18393/1/AhmadNizamHassanMFKE2009.pdflink’ di dalam sistem peralatan di dalam industri. Data tahap sensitif

7

Chapter 3 covers the methodology of assessment used especially on the Ride-

through Test (RTT) activity. Brief explanation on the type of Test Equipments used

for the RTT is also presented

Chapter 4 presents the results of this project that covers type of industries

investigated, equipment selected for the RTT and the sensitivity or immunity level

data towards voltage sag of the equipments that have been established.

Chapter 5 is the last chapter that discusses and highlights the key conclusions

established from this project together with some recommendation for future work.

Finally, the report is ended by listing all the references and appendices.

Page 21: LOAD-SIDE VOLTAGE SAG ASSESSMENT: HANDS ON …eprints.utm.my/id/eprint/18393/1/AhmadNizamHassanMFKE2009.pdflink’ di dalam sistem peralatan di dalam industri. Data tahap sensitif

47

REFERENCES

1. H.Ali and W.N.Wan Mahmood, “Load-side Power Quality Assessment Study

– TNB’s Experience”, CIRED, Asia Pacific Regional Power Quality Seminar,

Malaysia 28-31 March 2005.

2. Y.Li, C.Mao “Voltage Sag Study for a Practical Industrial Distribution

Network”, IEEE 2006 Internatinal Conference on Power Technology, pp. 1-4

3. J.Schlabbach, D.Blume, T.Stephanblome ”Voltage Quality in Electrical

System”, London UK, The Institution of Electrical Engineers, IEE 2001

4. M.H.J. Bollen ”Understanding Power Quality Problems: Voltage Sags and

Interrruption”, New York, IEEE Press Oct 1999, ISBN:0780347137

5. Jovica V. Milanovic, Chandra P. Gupta, ”Probalistic Assessment of Financial

Losses due to Interrruptions and Voltage Sags – Part I: The Methodology”,

IEEE Tran. Power Delivery, Vol 21, no. 2, pp. 918-924, Apr 2006

6. Chandra P. Gupta, Jovica V. Milanovic, ”Probalistic Assessment of

Equipment Trips due to Voltage Sags”, IEEE Tran. Power Delivery, Vol 21,

no. 2, pp. 711-718, Apr 2006

7. M.F.McGranaghan, D.R.Mueller and M.J.Samotyj, ”Voltage sags in industrial

systems”, IEEE Tran. Ind. Appl., Vol 29, no. 2, pp. 397-402, Mar/Apr 1993

Page 22: LOAD-SIDE VOLTAGE SAG ASSESSMENT: HANDS ON …eprints.utm.my/id/eprint/18393/1/AhmadNizamHassanMFKE2009.pdflink’ di dalam sistem peralatan di dalam industri. Data tahap sensitif

48

8. John Horak,”Power Quality: Measurements of Sags and Interrruptions,”

9. Andreas Eberhard, Alex McEachern,”New Developments in Power Quality

Immunity and Voltage Sag Standards: Hands-on Applications in North

America, Asia and Europe,” 9th International Conference, Electrical Power

Quality & Utilisation, Barcelona, 9-11 Oct 2007.

10. S.T.Chang, K.Y.Chua, C.C.Siew, T.L.Tan,”Power Quality Initiatives in

Singapore”, IEE Conference Publication 2001.

11. S.Z.Djokic, J.Desmet, G.Vanalme, J.V.Milanovic & K.Stockman,”Sensitivity

of AC adjustable speed drives to voltage sags, short interruptions and under-

voltage transients”, IEEE Trans. Power Del. Vol.20. no. 1, pp. 494-505,

Jan.2005

12. S.Z.Djokic, J.Desmet, G.Vanalme, J.V.Milanovic & K.Stockman,”Sensitivity

of personal computers to voltage sag, short interruptions”, IEEE Trans. Power

Del. Vol.20. no. 1, pp. 375-383, Jan.2005

13. S.Z.Djokic, J.V.Milanovic & D.S. Kirshen,”Sensitivity of AC coil contactors

to voltage sag, short interruptions and under-voltage transients”, IEEE Trans.

Power Del. Vol.19. no. 3, pp. 1299-1307, Jul.2004

14. Hussain Sharef, Azah Mohamed, Nazri Marzuki,”Immunity Level of Personal

Computers to Voltage Sag in the 240V/50Hz Distribution Systems” Journal of

Applied Sciences 9(5),pp931-937 2009

15. Mike Johnson,”Finding Immunity to Voltage Sags”, EPRI

16. SEMI F47-0200, Specification for semiconductor processing equipment

voltage sag immuniy, SEMI, USA, 02-2000

Page 23: LOAD-SIDE VOLTAGE SAG ASSESSMENT: HANDS ON …eprints.utm.my/id/eprint/18393/1/AhmadNizamHassanMFKE2009.pdflink’ di dalam sistem peralatan di dalam industri. Data tahap sensitif

49

17. International Standard CEI IEC 61000-4-34 Electromagnetic compatibility

(EMC) Part 4-34. Testing and measurement techniques – voltage dips, short

interruptions and voltage variations immunity tests for equipment with input

current more than 16A per phase

18. International Standard CEI IEC 61000-4-11 Electromagnetic compatibility

(EMC) Part 4-34. Testing and measurement techniques – voltage dips, short

interruptions and voltage variations immunity tests for equipment with input

current less than 16A per phase

19. Industrial Power Corruptor User Manual 1.00

20. CHROMA Programmable AC Source 6500 Series User Manual

21. Electrical Power Systems Quality, Roger C. Dugan, Mark McGranaghan,

Wayne Beaty, McGraw-Hill Inc 1996

22. Working Together in Managing Power Quality: Power Quality Guidebook, SP

Powergrid Limited, Singapore, 2005

23. Power Quality Guidebook: Voltage Sag Solutions for Industrial Customers,

TNB Malaysia, 2007

24. Cahier technique no. 149. EMC: electromagnetic compatibility by Jacques

Delaballe, 2001.