Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3...
Transcript of Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3...
![Page 1: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/1.jpg)
Load CalculationsHeat Balance Method - Example
Prof. Jeffrey D. SpitlerSchool of Mechanical and Aerospace Engineering, Oklahoma State University
![Page 2: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/2.jpg)
Weather
![Page 3: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/3.jpg)
50'-0"
10'-0
"
20'-0"
20'-0
"20
'-0"
15'-0'' 15'-0"
Office Office
OfficeConferenceRoom
Storage
Corridor
Lobby
Toilet
1 2 3
4 5
6
7
8
50'-0
"
![Page 4: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/4.jpg)
Building Layout
Area: 2500 square feetDivided into zones for convenience:
North Zone:Office 1, Office 3, Storage, Corridor, Toilet
South Zone:Conference Room, Office 2, Lobby
Basement
![Page 5: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/5.jpg)
Construction: North Wall
MPS 159, Fig. 5-9Layers: outside-inside:
Facing Brick 4”Sheathing; R-1Fiberglass insulation R-11Gypsum Wall Board0.5”
![Page 6: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/6.jpg)
Construction: North Wall
![Page 7: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/7.jpg)
Construction: W,S,E Walls
MPS 143Facing Brick 4”Cement Mortar 0.5”Concrete Block Cinder Aggregate 8”Air Gap / Furring strips 0.75”Gypsum Wall Board 0.5”
![Page 8: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/8.jpg)
Construction: W,S,E Walls
Items 5 & 6 are two materials in parallel: 1x3 furring, reflective airspaceTreat as a composite material with same resistance and capacitance
16” o.c.
Representative area
9”
![Page 9: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/9.jpg)
Composite Material: Equiv. k
Ffthrin.-Btu 0.38 ofty conductivi
a with material a toequivalent is this,0.75" thicknessIf
)Ffthr
Btu0.507(also
FhrBtu0.507
BtuFfthr0.94
0.208ft
BtuFfthr2.77
0.792ft
111
2
2
2
2
2
2
−−
=
−−=
−=
−−+
−−=
+=′
+′
=′ furring
furring
air
air
furringaire RA
RA
RRR
![Page 10: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/10.jpg)
Composite material: Equiv. ρcpFor composite material to have equivalent heat storage, (ρcpV)equivalent = Σ (ρcpV)
(ρcpV) air approximately zero
( )
33
33
ftlbm72.4
0.0625ftFlbm
Btu0.39F
Btu115.0compositeEquivalent
,Flbm
Btu0.39Leaving
FBtu115.0)(
FBtu115.0ft0.0098
FlbmBtu0.39
ftlbm30)(
=
−
=
−=
=
=
−
=
ρ
ρ
ρ
p
compositep
pinep
c
Vc
Vc
![Page 11: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/11.jpg)
Composite Material: Entry
But, was it important?
Note: This approach is “conservative”; particularly so with steel studs
![Page 12: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/12.jpg)
Construction: W,S,E Walls
![Page 13: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/13.jpg)
Construction: Roof
MPS 144, Table 5-4b(“insulated” version)Built Up Roofing 0.4”R-4 insulationConcrete Slab 2”Air Gap 4”Light Weight Aggregate Plaster 0.75”
![Page 14: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/14.jpg)
Construction: Interior partitions
Assume insulated for sound attenuation; ignore stud.
![Page 15: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/15.jpg)
Construction: Floor
Remember, layers are defined from “outside-to-inside”,
Or bottom to top for this case.
![Page 16: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/16.jpg)
Construction: Slab-on-Grade Floorand Basement Walls
12” dirt partly arbitrary.
![Page 17: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/17.jpg)
Construction: Windows
MPS 148, e=0.6 on one pane
![Page 18: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/18.jpg)
Construction: Doors
Door Info:Area = 20 square feetLW Emissivity in and out = 0.9U- Factor = 0.39
Added as a window, with SHGC=0.0
![Page 19: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/19.jpg)
Internal Heat Gains: Lighting
Best to use lighting plan.We assumed 1 W/ft2
![Page 20: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/20.jpg)
Internal Heat Gains: Equip.
We assumed 1 W/ft2
![Page 21: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/21.jpg)
Internal Heat Gains: People
Office 1: 3 peopleOffices 2,3: 2 peopleConf. rm.: 20 people
![Page 22: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/22.jpg)
InfiltrationAssume 0.5 ACH0.1 (?)ACH basement
![Page 23: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/23.jpg)
Ventilation SummaryChicago ordinances specify required ventilation; outdoor air (ODA) may be 1/3 of the required ventilation rate. This requirement may be met by bringing in 450 CFM ODA. The ODA (ACH) values given below were entered as ventilation heat gains for each of the corresponding rooms.
Room # NameFloor Area (sq. ft.)
ODA CFM/sq.. Ft.
ODA (CFM) ODA (ACH)
ODA Fraction
1 Office 400 0.2 80 1.2 18%2 Storage 300 0.1666667 50 1 24%3 Office 300 0.2 60 1.2 22%4 Conference Room 400 0.5 200 3 33%5 Office 300 0.2 60 1.2 22%6 Corridor 400 0 0 0 0%7 Lobby 250 0 0 0 0%8 Toilet 150 0 0 0 0%9 Basement 2500 0 0 0 0%
Sum 5000 450
![Page 24: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/24.jpg)
Airflow Rates
Airflow rates are calculated to meet sensible loads in space, given hot deck / cold deck temperature.
![Page 25: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/25.jpg)
Results of Interest
HeatingRoom LoadsRoom AirflowsZone Loads/ Airflows /Coil LoadsBuilding Coil Loads
CoolingRoom LoadsRoom AirflowsZone Loads/ Airflows /Coil LoadsBuilding Coil Loads
![Page 26: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/26.jpg)
Reports
![Page 27: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/27.jpg)
Cooling Load (w/o ventilation)
![Page 28: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/28.jpg)
Airflow Rates Required
![Page 29: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/29.jpg)
Room-by-Room Summary
Room # Name
Sens. Cooling Coil Load (Btu/hr)
Supply Flow Rate (CFM)
1 Office 9626 4462 Storage 4435 2063 Office 5881 2734 Conference Room 12938 6005 Office 5765 2676 Corridor 5925 2757 Lobby 12166 5648 Toilet 3408 1589 Basement 33085 1533
Sum of peaks 93229 4322
![Page 30: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/30.jpg)
Total Building Coil Load (w/ ventilation)
![Page 31: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/31.jpg)
Building Heating Load
![Page 32: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/32.jpg)
Questions?
![Page 33: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/33.jpg)
Appendix: Step-by-step procedure
Step1: Open a new file by clicking either the new file icon or menu itemStep2: Specify weather cooling or heating load calculation is desiredStep3: Click the location button and specify the location of the building Step4: specify the outside air temperature by clicking the special outside conditions button, then press ok
![Page 34: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/34.jpg)
Appendix: Step-by-step procedure
Step5: on the tree structure select the building and under the operations menu click add or click the add icon on the toolbarStep6: enter the zone information that is supply air temperature , the interior set point temperature and the orientation with respect to North and press okStep7: now select the zone and do the add procedure; this time the software adds a room. Enter the room height. Step8: Select the room and once again doing the add procedure we get the option of adding different heat gain types such as people, equipment, infiltration, lights , the wall elements etc.
![Page 35: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/35.jpg)
Appendix: Step-by-step procedure
Step9: enter the wall layer and window type information in the wall element. Step10: subsequently enter the light, infiltration, equipment, etc. information.Step11: when all the information is entered under the calculate menu item, execute for building or execute for room, whichever is desirable.Step12: to view the results under the calculate menu item, click view output for building.
![Page 36: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/36.jpg)
Importing room-by-room results into Excel (1)
![Page 37: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/37.jpg)
Importing room-by-room results into Excel (2)
![Page 38: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275](https://reader034.fdocuments.in/reader034/viewer/2022042711/5f781371ef877c4b41056fc6/html5/thumbnails/38.jpg)
Importing room-by-room results into Excel (3)