Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3...

38
Load Calculations Heat Balance Method - Example Prof. Jeffrey D. Spitler School of Mechanical and Aerospace Engineering, Oklahoma State University

Transcript of Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3...

Page 1: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Load CalculationsHeat Balance Method - Example

Prof. Jeffrey D. SpitlerSchool of Mechanical and Aerospace Engineering, Oklahoma State University

Page 2: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Weather

Page 3: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

50'-0"

10'-0

"

20'-0"

20'-0

"20

'-0"

15'-0'' 15'-0"

Office Office

OfficeConferenceRoom

Storage

Corridor

Lobby

Toilet

1 2 3

4 5

6

7

8

50'-0

"

Page 4: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Building Layout

Area: 2500 square feetDivided into zones for convenience:

North Zone:Office 1, Office 3, Storage, Corridor, Toilet

South Zone:Conference Room, Office 2, Lobby

Basement

Page 5: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Construction: North Wall

MPS 159, Fig. 5-9Layers: outside-inside:

Facing Brick 4”Sheathing; R-1Fiberglass insulation R-11Gypsum Wall Board0.5”

Page 6: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Construction: North Wall

Page 7: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Construction: W,S,E Walls

MPS 143Facing Brick 4”Cement Mortar 0.5”Concrete Block Cinder Aggregate 8”Air Gap / Furring strips 0.75”Gypsum Wall Board 0.5”

Page 8: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Construction: W,S,E Walls

Items 5 & 6 are two materials in parallel: 1x3 furring, reflective airspaceTreat as a composite material with same resistance and capacitance

16” o.c.

Representative area

9”

Page 9: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Composite Material: Equiv. k

Ffthrin.-Btu 0.38 ofty conductivi

a with material a toequivalent is this,0.75" thicknessIf

)Ffthr

Btu0.507(also

FhrBtu0.507

BtuFfthr0.94

0.208ft

BtuFfthr2.77

0.792ft

111

2

2

2

2

2

2

−−

=

−−=

−=

−−+

−−=

+=′

+′

=′ furring

furring

air

air

furringaire RA

RA

RRR

Page 10: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Composite material: Equiv. ρcpFor composite material to have equivalent heat storage, (ρcpV)equivalent = Σ (ρcpV)

(ρcpV) air approximately zero

( )

33

33

ftlbm72.4

0.0625ftFlbm

Btu0.39F

Btu115.0compositeEquivalent

,Flbm

Btu0.39Leaving

FBtu115.0)(

FBtu115.0ft0.0098

FlbmBtu0.39

ftlbm30)(

=

=

−=

=

=

=

ρ

ρ

ρ

p

compositep

pinep

c

Vc

Vc

Page 11: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Composite Material: Entry

But, was it important?

Note: This approach is “conservative”; particularly so with steel studs

Page 12: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Construction: W,S,E Walls

Page 13: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Construction: Roof

MPS 144, Table 5-4b(“insulated” version)Built Up Roofing 0.4”R-4 insulationConcrete Slab 2”Air Gap 4”Light Weight Aggregate Plaster 0.75”

Page 14: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Construction: Interior partitions

Assume insulated for sound attenuation; ignore stud.

Page 15: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Construction: Floor

Remember, layers are defined from “outside-to-inside”,

Or bottom to top for this case.

Page 16: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Construction: Slab-on-Grade Floorand Basement Walls

12” dirt partly arbitrary.

Page 17: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Construction: Windows

MPS 148, e=0.6 on one pane

Page 18: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Construction: Doors

Door Info:Area = 20 square feetLW Emissivity in and out = 0.9U- Factor = 0.39

Added as a window, with SHGC=0.0

Page 19: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Internal Heat Gains: Lighting

Best to use lighting plan.We assumed 1 W/ft2

Page 20: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Internal Heat Gains: Equip.

We assumed 1 W/ft2

Page 21: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Internal Heat Gains: People

Office 1: 3 peopleOffices 2,3: 2 peopleConf. rm.: 20 people

Page 22: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

InfiltrationAssume 0.5 ACH0.1 (?)ACH basement

Page 23: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Ventilation SummaryChicago ordinances specify required ventilation; outdoor air (ODA) may be 1/3 of the required ventilation rate. This requirement may be met by bringing in 450 CFM ODA. The ODA (ACH) values given below were entered as ventilation heat gains for each of the corresponding rooms.

Room # NameFloor Area (sq. ft.)

ODA CFM/sq.. Ft.

ODA (CFM) ODA (ACH)

ODA Fraction

1 Office 400 0.2 80 1.2 18%2 Storage 300 0.1666667 50 1 24%3 Office 300 0.2 60 1.2 22%4 Conference Room 400 0.5 200 3 33%5 Office 300 0.2 60 1.2 22%6 Corridor 400 0 0 0 0%7 Lobby 250 0 0 0 0%8 Toilet 150 0 0 0 0%9 Basement 2500 0 0 0 0%

Sum 5000 450

Page 24: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Airflow Rates

Airflow rates are calculated to meet sensible loads in space, given hot deck / cold deck temperature.

Page 25: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Results of Interest

HeatingRoom LoadsRoom AirflowsZone Loads/ Airflows /Coil LoadsBuilding Coil Loads

CoolingRoom LoadsRoom AirflowsZone Loads/ Airflows /Coil LoadsBuilding Coil Loads

Page 26: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Reports

Page 27: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Cooling Load (w/o ventilation)

Page 28: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Airflow Rates Required

Page 29: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Room-by-Room Summary

Room # Name

Sens. Cooling Coil Load (Btu/hr)

Supply Flow Rate (CFM)

1 Office 9626 4462 Storage 4435 2063 Office 5881 2734 Conference Room 12938 6005 Office 5765 2676 Corridor 5925 2757 Lobby 12166 5648 Toilet 3408 1589 Basement 33085 1533

Sum of peaks 93229 4322

Page 30: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Total Building Coil Load (w/ ventilation)

Page 31: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Building Heating Load

Page 32: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Questions?

Page 33: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Appendix: Step-by-step procedure

Step1: Open a new file by clicking either the new file icon or menu itemStep2: Specify weather cooling or heating load calculation is desiredStep3: Click the location button and specify the location of the building Step4: specify the outside air temperature by clicking the special outside conditions button, then press ok

Page 34: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Appendix: Step-by-step procedure

Step5: on the tree structure select the building and under the operations menu click add or click the add icon on the toolbarStep6: enter the zone information that is supply air temperature , the interior set point temperature and the orientation with respect to North and press okStep7: now select the zone and do the add procedure; this time the software adds a room. Enter the room height. Step8: Select the room and once again doing the add procedure we get the option of adding different heat gain types such as people, equipment, infiltration, lights , the wall elements etc.

Page 35: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Appendix: Step-by-step procedure

Step9: enter the wall layer and window type information in the wall element. Step10: subsequently enter the light, infiltration, equipment, etc. information.Step11: when all the information is entered under the calculate menu item, execute for building or execute for room, whichever is desirable.Step12: to view the results under the calculate menu item, click view output for building.

Page 36: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Importing room-by-room results into Excel (1)

Page 37: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Importing room-by-room results into Excel (2)

Page 38: Load Calculations...Coil Load (Btu/hr) Supply Flow Rate (CFM) 1 Office 9626 446 2 Storage 4435 206 3 Office 5881 273 4 Conference Room 12938 600 5 Office 5765 267 6 Corridor 5925 275

Importing room-by-room results into Excel (3)