Load Calculations

60
BUILDING LOAD CALCULATIONS BUILDING LOAD CALCULATIONS

Transcript of Load Calculations

Page 1: Load Calculations

BUILDING LOAD CALCULATIONSBUILDING LOAD CALCULATIONS

Page 2: Load Calculations

BUILDING LOAD CALCULATIONS

AgendaAgenda

• Heat Load Calculation Basics• Definitions• Thumb Rules• Questions

Page 3: Load Calculations

BUILDING LOAD CALCULATIONS

As an Example we will talk about theHeat Transfer SAY TO A HOTEL ROOMAs an Example we will talk about theHeat Transfer SAY TO A HOTEL ROOM

BUILDING LOAD CALCULATIONS

Page 4: Load Calculations

BUILDING LOAD CALCULATIONS

Heat Transfer SAY TO A HOTEL ROOMHeat Transfer SAY TO A HOTEL ROOM

BUILDING LOAD CALCULATIONS

AREA OF THIS ROOM IS 14.4 SQ M

WHAT IS THE WATTS / SQ M

WHAT IS THE AIR QUANTITY IN

L/S PER SQ .M

Page 5: Load Calculations

BUILDING LOAD CALCULATIONS

Sensible HeatSensible Heat

Heat which causes a change in temperature of a substance

Page 6: Load Calculations

BUILDING LOAD CALCULATIONS

Sensible HeatSensible Heat

Heat which causes a change in temperature of a substance

UNITS:

METRIC : JOULES ………………….. POWER IS ….. WATTS : Joules / Second

IMPERIAL : BTU ( IS HEAT REQUIRED TO RAISE 1 LB OF WATER THROUGH 1 DEGREE F)

POWER IS : BTU/ HR OR TONS

WE TAKE ABOUT MACHINE CAPACITY (POWER) IN ‘TONS’ OR KILOWATTS

1 TON = 12000 BTU/HR AND 1 BTU = 1055 JOULES

= 12000 X 1055 / 3600 = 3513 JOULES/SEC = 3513 WATT = 3.513 KW

Page 7: Load Calculations

BUILDING LOAD CALCULATIONS

Sensible HeatSensible Heat

Heat which causes a change in temperature of a substance

UNITS:

IN AN AIR-CONDITIONING SYSTEM :

TOTAL SENSIBLE HEAT = 1.23 X LITRES/ SECOND OF AIR X ( DB ENT – DB LEAVING)

IN A HOTEL ROOM CIRCULATING 154 LITRES / SECOND OF AIR

TOTAL SENSIBLE HEAT = 1.23 X 154 X (24 - 14.2 ) = 1856 WATTS

Page 8: Load Calculations

BUILDING LOAD CALCULATIONS

SAMPLE - HEAT LOAD CALCULATIONS

IMPORTANT EQUATIONS

SENSIBLE HEAT : 1.08 X CFM X T(°F) 1.23 X l/S X T(°C)

LATENT HEAT : 0.68 X CFM X W (gr/LB) 3010 X M3/S X W(kg/kg)

```````````````````````````````````````````````````````````````````````````or 3.01 x l/s x DeltaW(kg/kg)

TOTAL HEAT : 4.45 X CFM X H (BTU/LB) 1.20 X M3/S X H(KJ/KG)

Page 9: Load Calculations

BUILDING LOAD CALCULATIONS

Latent HeatLatent Heat

Heat energy absorbed in the process of changing form of a substance without a change in temperature or pressure. Heat energy that cannot be measured with a thermometer.

32o

Page 10: Load Calculations

BUILDING LOAD CALCULATIONS

Latent or Sensible?Latent or Sensible?

• What changed from previous slide

• What type of heat was involved

32o

Page 11: Load Calculations

BUILDING LOAD CALCULATIONS

Latent or Sensible?Latent or Sensible?

• What changed from previous slide

• What type of heat was involved

32o

LATENT HEAT IN AIRCONDITIONING SYSTEM =

2.96 X LITRES/SECOND OF AIR X GMS/KG DIFFERENCE

FOR A HOTEL ROOM THAT CIRCULATES 154 L/S OF AIR WITH ENTERING GMS/KG MOISTURE OF 9.32 AND LEAVING THE COIL WITH 8.82, THE LATENT LOAD = 2.96 X 154 X (9.32-8.82)

= 231 WATTS

Page 12: Load Calculations
Page 13: Load Calculations

BUILDING LOAD CALCULATIONS

What all information should we gather before we start with the Heat Transfer

calculation of this HOTEL ROOM

What all information should we gather before we start with the Heat Transfer

calculation of this HOTEL ROOM

BUILDING LOAD CALCULATIONS

Page 14: Load Calculations

BUILDING LOAD CALCULATIONS

INITIAL DESIGN CONSIDERATION

• BUILDING CHARATERISTICS

•CONFIGURATION

•OUTDOOR DESIGN CONDITIONS

•INDOOR DESIGN CONDITIONS

•OPERATING SCHEDULES

•ADDITIONAL CONSIDERATIONS LIKE FAN ENERGY,DUCT LEAKAGE,TYPE OF RA SYSTEM

(c) 1997 ASHRAE Handbook, Fundamentals, Chapter 28

Page 15: Load Calculations

BUILDING LOAD CALCULATIONS

HEAT GAIN CALCULATION CONCEPTS •GAIN THROUGH BUILDING FENESTRATION ( GLAZING AND ITS COMPONENTS)…. EXTERNAL SHADING

•OTHER EXTERIOR SURFACES

•SOL AIR TEMPERATURE

•INTERNAL GAIN THROUGH PARTITIONS

•SOURCES IN CONDITIONED SPACE LIKE PEOPLE,LIGHTING,APPLIANCES OR OFFICE EQUIPMENT

•INFILTRATION AND VENTILATION HEAT GAIN

•LATENT HEAT GAIN FROM MOISTURE THROUGH PERMEABLE BUILDING

•MISC… FAN…. DUCT HEAT GAIN

HEAT STORAGE CAPACITY OF ROOM IS IMPORTANT IN CONVERTING HEAT GAIN TO COOLING LOAD

(c) 1997 ASHRAE Handbook, Fundamentals, Chapter 28

Page 16: Load Calculations

BUILDING LOAD CALCULATIONS

• Load Calculations:• Space Sensible Load Calculations

• ‘SOLAR LOAD’• ‘TRANSMISSION AND CONDUCTION LOAD’• LIGHTING• EQUIPMENT LOAD• PEOPLE LOAD

• Calculating airflow based on Space Sensible Load• ‘Internal Loads’• ‘Skin Loads’

• Fresh air Load and therefore Cooling Coil Load

We will talk about :

Page 17: Load Calculations

BUILDING LOAD CALCULATIONS

Typical Ambient conditions

35°C @ 80% RH45°C @ 30% RH35°C @ 20% RH20°C @ 90% RH

45°C @ 30% RH

35°C @ 80% RH

20°C @ 90% RH

35°C @ 20% RH

35°C @ 80% RH45°C @ 30% RH35°C @ 20% RH20°C @ 90% RH

Page 18: Load Calculations

BUILDING LOAD CALCULATIONS

Comfort conditions

45°C @ 30% RH

35°C @ 80% RH

20°C @ 90% RH

35°C @ 20% RH

Comfort condition,20 to 24°C,

40 to 70% RH

Page 19: Load Calculations

BUILDING LOAD CALCULATIONS

Control the Humidity

Source: ASHRAE HVAC Systems and Equipment Handbook

Page 20: Load Calculations

BUILDING LOAD CALCULATIONS

All sensible loads downstream of the supply air ductwork and before the return air grill are part of the space sensible load!

Space Sensible Load - Well Mixed System

BUILDING LOAD CALCULATIONS

Page 21: Load Calculations

BUILDING LOAD CALCULATIONS

LETS TALK ABOUT Sun Loads

BUILDING LOAD CALCULATIONS

Page 22: Load Calculations

BUILDING LOAD CALCULATIONS

LETS TALK ABOUT Sun Loads

BUILDING LOAD CALCULATIONS

SOLAR LOAD:

• DEPENDS ON DIRECTION AND WHERE YOU ARE LOCATED

•DEPENDS ON AREA OF GLASS

•SHADING CO-EFFICIENT

•SOLAR HEAT GAIN FACTOR OF THAT LOCATION AND TIME

•COOLING LOAD FACTOR

Page 23: Load Calculations

BUILDING LOAD CALCULATIONS

LETS TALK ABOUT Sun Loads

BUILDING LOAD CALCULATIONS

SOLAR LOAD:

• DEPENDS ON DIRECTION AND WHERE YOU ARE LOCATED

•DEPENDS ON AREA OF GLASS

•SHADING CO-EFFICIENT

•SOLAR HEAT GAIN FACTOR OF THAT LOCATION AND TIME

•COOLING LOAD FACTOR

FOR OUR EXAMPLE HOTEL ROOM :

GLASS AREA IS 4.8 SQ.M

SHADING CO.EFF IS 0.42

GLASS FACES WEST AND THE COMPUTER CALCULATES THE SOLAR HEAT GAIN FACTOR AS 694 WATTS / SQ. M

AND THE LOAD FACTOR OF 0.64

THEREFORE HEAT GAIN =

4.8 X 0.42 X 694 X 0.64 = 895 WATTS

THIS IS THE LARGEST LOAD

Page 24: Load Calculations

BUILDING LOAD CALCULATIONSBUILDING LOAD CALCULATIONS

Page 25: Load Calculations

BUILDING LOAD CALCULATIONS

Sun Loads

BUILDING LOAD CALCULATIONS

Page 26: Load Calculations

BUILDING LOAD CALCULATIONS

Ø = e. S. (T1-T2)

T

T1

T2

e

Ø

Ø (W) heat flux (W/m.K) thermal conductivityT1 (K) higher temperatureT2 (K) lower temperaturee (m) distance in xS (m²) Surface of exchange

Ø = e. S. (T1-T2)

CONDUCTION

BUILDING LOAD CALCULATIONS

WE WILL TALK ABOUT

Conduction gain – WALL AND GLASS

Page 27: Load Calculations

Typical Values of Thermal Conductivity

Typical Values of Thermal Conductivity

0.01 0.1 1 10 100 1000

GasesGases

InsulationInsulation

AlloysAlloys

Pure MetalsPure Metals

CO2 H2

Oils Hg

Foams Fibers

Plastics Oxides

Ni Al

Zn Ag

LiquidsLiquids

Nonmetallic SolidsNonmetallic Solids

H2O

Ice

(W/m*K)BUILDING LOAD CALCULATIONS

Page 28: Load Calculations

BUILDING LOAD CALCULATIONS

T

T1

T2

e

Ø

SIMPLY :

AREA X U FACTOR X COOLING LOAD TEMP DIFF

BUILDING LOAD CALCULATIONS

HOTEL ROOM EXAMPLE :

WALL AREA( FIRST WALL = 10 SQ M

U VALUE = 0.57 WATT/ SQ.M / DEG C

CLTD = 18

SCF = 0.65

GAIN WATTS = 10 X 0.65 X 18.8 X 0.57 = 103 WATTS

WALL 2 SIMILARLY IS 140 WATTS ONLY

GLASS CONDUCTION IS 4.8 X 19 X 2.1 = 194 WATTS

Page 29: Load Calculations

BUILDING LOAD CALCULATIONS

• Load Calculations:• Space Sensible Load Calculations

• ‘SOLAR LOAD’• ‘TRANSMISSION AND CONDUCTION LOAD’• LIGHTING• EQUIPMENT LOAD• PEOPLE LOAD

• Calculating airflow based on Space Sensible Load• ‘Internal Loads’• ‘Skin Loads’

• Fresh air Load and therefore Cooling Coil Load

We will talk about :

Page 30: Load Calculations

BUILDING LOAD CALCULATIONS

• Internal Space Sensible Loads are comprised of several items:

• Lighting• People• Small Power

• Computer• Printers and copiers• Task Lighting• Coffee pots, microwaves and

refrigerators

‘Internal’ Space Sensible Loads

Page 31: Load Calculations

BUILDING LOAD CALCULATIONSBUILDING LOAD CALCULATIONS

Lighting load :

• RESIDENTIAL : 10 WATTS / SQ. M

•SHOPS AND SHOWROOMS : 20 WATTS / SQ.M

Page 32: Load Calculations

BUILDING LOAD CALCULATIONSBUILDING LOAD CALCULATIONS

Lighting load :

• RESIDENTIAL : 10 WATTS / SQ. M

•SHOPS AND SHOWROOMS : 20 WATTS / SQ.M

FOR OUR HOTEL ROOM WE ASSUME THAT WE HAVE A LIGHT OF 205 WATTS

Page 33: Load Calculations

BUILDING LOAD CALCULATIONSBUILDING LOAD CALCULATIONS

REFER TO ASHRAE OR CHVAC PROGRAM

HOTEL EXAMPLE

4 PERSONS AT 70 WATT / PERSON ……… TOTAL 280 WATTS SENSIBLE

4 PERSONS AT 55 WATT / PERSON LATENT……… TOTAL 220 WATTS LATENT

Page 34: Load Calculations

BUILDING LOAD CALCULATIONS

Heat Transfer SAY TO A HOTEL ROOMHeat Transfer SAY TO A HOTEL ROOM

BUILDING LOAD CALCULATIONS

WE NOW ADD ALL THIS UP AND TRY TO FIND THE

‘TOTAL SENSIBLE HEAT’

WALL1 =103

WALL2=140

GLASS TRANS =194

GLASS SOLAR=895

LIGHTS=205

EQUIPMENT=27

PEOPLE SENS =280

WE TAKE A SAFETY OF 5% AND THE TOTAL SENSIBLE LOAD IS 1845 WATTS

Page 35: Load Calculations

BUILDING LOAD CALCULATIONS

Cooling and Dehumidifying Process Example

L/s = Space Sensible Load (watts)

1.232 x (T setpoint - T supply)

L/s = 1845

1.232 X ( 24-14.3 ) = 154 L/s

Page 36: Load Calculations

BUILDING LOAD CALCULATIONSBUILDING LOAD CALCULATIONS

VERY

IMPORTANT

FOR

DX

SYSTEMS

Page 37: Load Calculations

BUILDING LOAD CALCULATIONSBUILDING LOAD CALCULATIONS

VERY

IMPORTANT

FOR

DX

SYSTEMS

FOR VENTILATION RATES

REFER ASHRAE

RECCOMENDED:

•ONE FRESH AIR CHANGE/HR

•OR

•7.5 L/S PER PESON

FRESH AIR IN THE MIDDLE EAST IS VERY EXPENSIVE

Page 38: Load Calculations

BUILDING LOAD CALCULATIONSBUILDING LOAD CALCULATIONS

VERY

IMPORTANT

FOR

DX

SYSTEMS

ASSUME ONLY 12 L/S FOR OUR HOTEL ROOM

BASED ON

NORMALLY I TO 2 PERSONS NORMALLY OCCUPY

CALCULATE SENSIBLE AND LATENT HEAT PORTIONS

Page 39: Load Calculations

BUILDING LOAD CALCULATIONSBUILDING LOAD CALCULATIONS

VERY

IMPORTANT

FOR

DX

SYSTEMS

ASSUME ONLY 12 L/S FOR OUR HOTEL ROOM

BASED ON

NORMALLY I TO 2 PERSONS NORMALLY OCCUPY

CALCULATE SENSIBLE AND LATENT HEAT PORTIONS

PROGRAM GIVES US 372 WATTS LATENT AND 284 WATTS SENSIBLE

Page 40: Load Calculations

BUILDING LOAD CALCULATIONS

Heat Transfer SAY TO A HOTEL ROOMHeat Transfer SAY TO A HOTEL ROOM

BUILDING LOAD CALCULATIONS

NOW CALCULATE THE TOTAL SENSIBLE AND TOTAL LATENT LOAD TO DETERMINE THE COIL COOLING CAPACITY

ANSWER:

2860 WATTS

AIR QUANTITY : 165 L/S

Page 41: Load Calculations

BUILDING LOAD CALCULATIONS

Heat Transfer SAY TO A HOTEL ROOMHeat Transfer SAY TO A HOTEL ROOM

BUILDING LOAD CALCULATIONS

AREA OF THIS ROOM IS 14.4 SQ M

WHAT IS THE WATTS / SQ M

WHAT IS THE AIR QUANTITY IN

L/S PER SQ .M

Page 42: Load Calculations

BUILDING LOAD CALCULATIONS

Heat Transfer SAY TO A HOTEL ROOMHeat Transfer SAY TO A HOTEL ROOM

BUILDING LOAD CALCULATIONS

BE CAREFUL OF NOISE AND TURBULANCE WHEN YOU CROSS 14 LITRES/ SEC PER SQUARE M

•NOISE IS HIGH

•PEOPLE CAN FEEL A ‘DRAFT’

Page 43: Load Calculations

BUILDING LOAD CALCULATIONS

SAMPLE - HEAT LOAD CALCULATIONS

IMPORTANT EQUATIONS

SENSIBLE HEAT : 1.08 X CFM X T(°F) 1.23 X l/S X T(°C)

LATENT HEAT : 0.68 X CFM X W (gr/LB) 3010 X M3/S X W(kg/kg)

TOTAL HEAT : 4.45 X CFM X H (BTU/LB) 1.20 X M3/S X H(KJ/KG)

Page 44: Load Calculations

BUILDING LOAD CALCULATIONS

• Load Calculations:• Space Sensible Load Calculations

• ‘SOLAR LOAD’• ‘TRANSMISSION AND CONDUCTION LOAD’• LIGHTING• EQUIPMENT LOAD• PEOPLE LOAD

• Calculating airflow based on Space Sensible Load• ‘Internal Loads’• ‘Skin Loads’

• Fresh air Load and therefore Cooling Coil Load

We talked about :

Page 45: Load Calculations

BUILDING LOAD CALCULATIONS

CONCEPTS

•Sensible Heat Ratio, Re-heat considerations, Bypass Factors and Cooling Coil types

•Variable Air Volume

•Air-Flow rate as a ratio to Floor Space and its importance – Relationship to ‘Noise’ and ‘Turbulence’

•Energy Considerations and benefits of Modulating Airflow

•Importance of Leaving Air Temperature and Humidity Control

•Part Load Considerations

•Apparatus Dew-point

•INDOOR AIR QUALITY

(c) 1997 ASHRAE Handbook, Fundamentals, Chapter 28

Page 46: Load Calculations

BUILDING LOAD CALCULATIONS

Overhead Delivery

Page 47: Load Calculations

BUILDING LOAD CALCULATIONSBUILDING LOAD CALCULATIONS

Page 48: Load Calculations

BUILDING LOAD CALCULATIONS

Page 49: Load Calculations

BUILDING LOAD CALCULATIONS

Assigning Loads to Occupied Space

BUILDING LOAD CALCULATIONS

Page 50: Load Calculations

BUILDING LOAD CALCULATIONS

• ENERGY STAR Label Requires IAQ Compliance

• ... Then a professional engineer needs to submit verification that the building meets 3 standards for the indoor environment: ASHRAE Standard 62-2001; ASHRAE Standard 55-1992 for thermal comfort; and IESNA Lighting Handbook for lighting quality. The ENERGY STAR Label for Buildings is offered to the top 25% of buildings. The Label recognizes one year of performance, and encourages facility managers to apply annually. The Label was just introduced in January, 1999.

Page 51: Load Calculations

BUILDING LOAD CALCULATIONS

• External Space Sensible Loads include:• Glass Transmission• Solar Radiation• Infiltration• Wall Transmission

‘External’ Space Sensible Loads

Page 52: Load Calculations

BUILDING LOAD CALCULATIONS

• Coil Loads include:• ‘Internal’ loads• ‘External’ loads• Roof load• Ductwork heat losses or gains• Fan motor heat gains• Ventilation loads• Any other loads put on the system

which do not occur in the occupied space

Coil Loads

Page 53: Load Calculations

BUILDING LOAD CALCULATIONS

• Every HVAC System must take into account Space Sensible Loads.

• The particular method of handling loads changes, but the load remains the same.

Space Sensible Loads

Page 54: Load Calculations

BUILDING LOAD CALCULATIONS

CIRCULATIONZONE

Light GainTo Room

Ceiling GainTo Room

Occupants GainSensible & Latent

MiscellaneousEquipment Gain

PERIMETERZONE

INTERIORZONE

Light Gain to Return Air

Roof Solar & Transmission Gain to Return Plenum

Ceiling GainTo Room from

Lower Floor

Space Loads - Well Mixed System

Page 55: Load Calculations

BUILDING LOAD CALCULATIONS

Load Item Well-Mixed Loadto Space

CEV Load toSpace

Lights 12.9 watts/m2 9.0 watts/ m2 (70%) 2.6 watts/ m2 (20%)People 8.6 watts/ m2 8.6 watts/ m2 (100%) 8.6 watts/ m2 (100%)

Small Pwr. 32.3 watts/ m2 32.3 watts/ m2 (100%) 32.3 watts/ m2 (100%)

Raised Floor N/A <6.5 watts/ m2>

Total ‘Internal’ Load 49.9 watts/ m2 37 watts/ m2

Glass Solar253 watts/lm

253 watts/ lm (100%) 151.8 watts/ lm (60%)

Glass Transmission49 watts/ lm

49 watts/ lm (100%) 29.4 watts/ lm (60%)

Wall Transmission17.4 watts/ lm

17.4 watts/ lm (100%) 17.4 watts/ lm (100%)

Infiltration12.1 watts/ lm

12.1 watts/ lm (100%) 7.3 watts/ lm (60%)

Total ‘External’ Load 331.5 watts/ lm 205.9 watts/ lm

Typical Assignment of Loads to Space

Page 56: Load Calculations

BUILDING LOAD CALCULATIONS

Psychrometric Analysis

BUILDING LOAD CALCULATIONS

Page 57: Load Calculations

BUILDING LOAD CALCULATIONS

Typical Values of Thermal Conductivity for Metals

Used in Heat Exchangers

Typical Values of Thermal Conductivity for Metals

Used in Heat Exchangers

Aluminum alloy 120 160 180 -

Steel, carbon - 43 42 36

Stainless steel 16 17 19 19

Copper 407 380 374 350

Brass 88 100 120 140

Nickel/chrome 12 13 16 18

-80°C -20°C 40°C 200°CW/(m.K)

Page 58: Load Calculations

BUILDING LOAD CALCULATIONS

Summary – Building Load CalculationSummary – Building Load Calculation

Factors that affect the Building Load

Overall Heat Transfer Co-efficient

External Loads

Internal Loads

Ventilation requirement and Indoor Air Quality

Air Quantity and Cooling Capacity

Load on the cooling coil

Page 59: Load Calculations

BUILDING LOAD CALCULATIONS

Overhead Delivery

Questions ?????

Page 60: Load Calculations

BUILDING LOAD CALCULATIONS

UPG TAINING FEB’2006

!