Single PackagedAir ConditionerSERVICE MANUALMODEL: LK-2580CH
Contents
— 2 —
Model Number Nomenclature
Model Number Nomenclature ................................................................................................. 2
General Data ............................................................................................................................. 3
Dimensions............................................................................................................................... 4
Refrigerant Circuit diagram......................................................................................................6
Wiring Diagram......................................................................................................................... 7
Trouble Shooting Guide........................................................................................................... 8
Electric Parts Trouble Shooting Guide................................................................................. 12
Feature of Controller............................................................................................................. 19
Exploded View and Replacement Parts List........................................................................ 24
Specification of Components ............................................................................................... 26
L K - 2 5 8 0 C HH: Horizontal Flow
C: Cooling Only
8 : 380-415V / 50Hz / 3Ø
Development Sequence
Nominal cooling capacity25 : 25 ton
LGSingle Package Air Conditioner
General Data
— 3 —
1) Test Condition of ARI Rated Cooling Capacity :Ambient:95°F , Air entering temperature : 80°F DB and 67°F WB
2) ARI standard210/240 or 360 for EER270 for Sound
3) Filters are standard supply.
Nominal ton (Ton) 25Models LK-2580CHElectrical Data ARI Net Cooling Capacity (BTU/hr) 260,000
(W) 76,198(Kcal/h ) 65,524
Voltage (V,PH) 380-415V,3ØM.C.A(with standard motor) Cooling (Amps) 70Power Input Cooling (Watt) 27,000
Performance Air Circulation Nominal CFM CFM 9,500EER Cooling (BTU/hr.W) 9.6Sound Rating Cooling bell 9.2
Features Wired Remote Controller �(Accessory)Time Delay Safety Function �Cooling Operation Mode �Heating Operation Mode(with E/Heater) �Soft Dry Operation �Timer Setting (24-Hour on/off) �Auto rastart mode �Humidifier function �Test function �Defrost -Hot Start -Self-Diagnosis Function �Filter type washable & Anti-fungus
Compressor Type ReciprocatingQuantity 3
Outdoor Coil Type High efficiencyTube size(O.D) (inch) 0.375
(mm) 9.52Row/FPI 2R/16FPILengh (inch) 78.7
(mm) 2,000Face area (sq.ft) 32.81
(m2) 3.05Indoor Coil Type High efficiency
Tube size(O.D) (inch) 0.375(mm) 9.52
Row/FPI 2R/16FPILengh (inch) 55.9
(mm) 1,420Face area (sq.ft) 23.29
(m2) 2.16Outdoor Fan Type Propeller
No. Used/Diameter(in.) 2EA/28Drive Type DirectCFM 12,500No. Motor/Motor output(Hp) 2/1.3Motor RPM 950
Indoor Fan Type centrifugal blower fanNo. Used 1EADiameter/Width(in.) 18/18Drive Type/Motor Step Belt/1No.motors 1EAMotor output(standard/oversized) 7.5Hp/N.AMotor rpm(Standard/oversized) 2890/N.A
Drain Connection Size(in.) 1Dimensions Indoor unit (WxHxD) (inch) 109.2*65.4*74.0
(mm) 2774*1660*1880Weight net (kg) 870
(lbs) 1,918
Dimensions
— 4 —
LK-2580CH
EF
D
C
Center Line of Hole A
B
CLEARANCE 34"
CLEARANCE 46"
CLEARANCE 16"(HORIZONTAL)
CLEARANCE 34"
2" Dia. Hole Power Wires1.5" Dia. Hole Other Purpose(3EA)
UNITS LK-2580CH
A
B
C
D
E
F
65.35(1660)
74.02(1880)
109.21(2774)
69.69(1770)
7.68(195)
11.89(302)
Unit: inch(mm)
H I J KL
M
SUPPLY
RETURN
Unit: inch(mm)
UNITS LK-2580CH
H
I
J
K
L
M
25.57(649.5)
15.28(388)
27.34(694.5)
2.40(61)
6.10(155)
57.09(1450)
— 5 —
Accessories
WeightsMaximum Unit and Corner Weights (Lbs) and Center of Gravity Dimensions (In.)
FRESH AIR HOOD(MANUAL)
Note: 1.Corner weights are given for information only.2. Weights are approximate.
E
CENTER OF GRAVITY
F
A
D
B
C
25 LK-2580CH 2,281 1,918 697 460 328 433 42 30
Tons UnitModel No.
Maximum Weights (lbs) Corner Weights (lbs) Center of Gravity (In.)
Shipping2 Net A B C D E F
Rdfrigerant Circuit Diagram
— 6 —
Comp A
Comp B
Comp C
High Pressure Switch(Optional)
Service Valve
Service Valve
Suction Line
Capilliary
Indoor Coil
Outdoor Coil
Circuit A
Circuit B
Circuit C
Low Pressure Switch
: Refrigerant Flow
Wiring Diagram
— 7 —
WIR
ING
DIA
GR
AM
HU
MID
IFIE
RT
ER
MIN
AL
B
LOC
K
US
ING
ELE
CT
RIC
HE
ATE
R(O
PT
ION
)E
HT
ER
MIN
AL
B
LOC
K
TE
RM
INA
L B
LOC
K
TE
RM
INA
L B
LOC
K1
TE
RM
INA
L B
LOC
K2
1 2
3 4
N T S R
N T S R
EH
3Ø
4W
IRE
38
0/4
15
V5
0H
zP
OW
ER
SU
PP
LY
3Ø
4W
IRE
38
0/4
15
V5
0H
zP
OW
ER
SU
PP
LY
3Ø
4W
IRE
38
0/
41
5V
50
Hz
PO
WE
RS
UP
PLY
CA
NN
OT
BE
US
ED
WH
EN
US
ING
TH
ER
MO
STA
T
RE
MO
VE
JU
MP
WIR
E W
HE
NC
ON
NE
CT
ING
FIR
E A
LAR
MS
YS
TE
M
FIR
E A
LAR
M
ELE
CT
RO
-ME
CH
AN
ICA
L
TH
ER
MO
STA
T
TR
AN
S
TR
AN
S FAN
OU
T(B
)O
UT
(A)
CO
MP
(A)
CO
MP
(B)
CO
MP
HU
MID
IN
CN
CN
38
54
A2
00
52
B
PO
WE
R
Ry
Ry
Ry
Ry
Ry
Ry
Ry
Ry
HE
ATE
R
(A)
(B)
FU
SE
FU
SE
FU
SE
(5A
250
V)
(5A
250
V)
250V
/3.1
5A
ME
CH
AN
ICA
LT
HE
RM
OS
TAT
AC
24V FA
N
L N 1 2 3 4 5 R G 1 2 Y Y1 W2
W1
CO
MP
1
CO
MP
2
HE
ATE
R1
HE
ATE
R2
AC
24V
AC
13V
AC
24V
MA
IN P
CB
AS
M
FAN
CO
MP
1
CU
T A
ND
RE
MO
VE
AN
TIC
IPAT
OR
(RE
SIS
TOR
)C
ON
NE
CT
ING
WH
TH
CO
NTA
CT
IN
PA
RA
LLE
L
CO
MP
2H
EAT
ER
1H
EAT
ER
2
RE
MO
VE
JU
MP
WIR
E W
HE
NC
ON
NE
CT
ING
TH
ER
MO
STA
T
RE
MO
TE
CO
NT
RO
LLE
RF
ILLE
R T
ER
MIN
AL
4
FIL
LER
T
ER
MIN
AL
3
FIL
LER
T
ER
MIN
AL
2
FIL
LER
T
ER
MIN
AL
1
BR
BR
RD
RD
YL
YL
YL
YL
BL
RD
RD
WH
WH
WH
WH
WHW
H
WH
WH WH
WH
WH
WH
WH
WH
WH
WH
BK
BK
BK
BK
BK
BK
BK
BK
BK C
OM
P(A
)
NO
TE
FIE
LD W
IRIN
G
FAC
TOR
Y W
IRIN
G
BK
: BLA
CK
BR
: BR
OW
NO
R: O
RA
NG
EB
L: B
LUE
RD
: RE
DW
H: W
HIT
EY
L: Y
ELL
OW
MO
TOR
IN
CO
MP
(B)
CO
MP
(C)
CA
PAC
ITO
R
CAP
ACIT
OR
BK
BK
CR
AN
KC
AS
EH
EAT
ER
(A)
CR
AN
KC
AS
EH
EAT
ER
(B)
CR
AN
KC
AS
EH
EAT
ER
(C)
BK
BK
BK
BK
BR
BK
BR
T1
T2
T3
T1
T2
T3
T1
T2
T3
RD
RD
WH
BK
RD
BL
BL
YLBRORBK
BKBK
BKBK
BKORBRYL
12
6
62 4
81
POWER RELAY2
0
62 4
81
POWER RELAY2
0
84
0
BR
BK BKBKBK
BKBK
RDWHBK
RD
MAGNETIC CONTACT(A)
MAGNETIC CONTACT(B)
MAGNETIC CONTACT(C)
POWER RELAY1
BK
BK
RD
WH
BK
RD
BK
BK
BK
LOW
PR
ES
SU
RE
SW
ITC
H(A
-Cyc
le)
LOW
PR
ES
SU
RE
SW
ITC
H(C
-Cyc
le)
LOW
PR
ES
SU
RE
SW
ITC
H(B
-Cyc
le)
THE
RM
ISTO
RIN
(B)
THE
RM
ISTO
RIN
(A)
THE
RM
ISTO
RO
UT
AIR
T.P
MO
TOR
OU
T(A
)T.
P
MO
TOR
OU
T(B
)T.
P
THE
RM
ISTO
RR
ETU
TN A
IR(O
PTI
ON
)
BK
BK
BK
OR
BR
CN-THERMOSTAT
YL
YLBRORBK
BKBK
BKBK
YLBRORBK
Troubleshooting Guide
— 8 —
PACKAGE AIR CONDITIONER VOLTAGE LIMITS
1. No cooling and heating operation performed1) Both the blower and the compressor do not work
NAME PLATE RATING MINIMUM MAXIMUM
380 - 415V 342V 456V
2) Only Indoor blowers do not work
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY
Other parts except theunit
Magnetic switch forcompressor & fan motor
Operating switch
• Electric supply interrupted• Defective power wiring• Cut off power fuse
Too low voltage
Control point is oncondition of "OFF" due totrouble.
Troubled or defectivecontactor
Measure power sypplywith a tester in case thatthe same power source issupplied to otherequipment except the unit,what and where troubledcan be discovered bychecking the operation ofother equipment.
Measure it with a tester.
Make short-circuit, thenmeasure it with tester.
Check it with the eyes ortester.
• Repair a switch boxand relative instrument.
• Replacement of fuse
• Request a power supplier to repair.
Check the power source.Use a thick cable ifnecessary.
Replace it if necessary.
Repair or replace it.
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY
Motor
Electric wiring
• Over heated• Wiring short
• Cut- OFF of wiring• Short circuited on
operation
Check it with tester
Check it with a tester.
Repair or replace it.
Rewiring or Repair.
— 9 —
3) Only outdoor fan does not work
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY
Motor
Electric Wiring
Capacitor Defected Check it with tester. Replace it.
• Over-heated• Wire short
Cut off of wiring
Short circuited on operation
Check how it is insulated.
Check it with a tester.
Repair or replace it.
Rewiring or repair.
4) Only compressor does not work
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY
Magnetic switch forcompressor motor
Compressor motor
High pressure switch(Option part)
Electric circuit
Defective contact, magnetic coil troubled.
Troubled over-heated (layer short)
Troubled or defective contact or operating
Defective connection ordisconnection of the circuitfor compressor.
Check it with the eyes onwith a tester.
Check how it is insulated.
Check it with a tester.
Check it with a tester.
Repair or replace it.
Replace or repair thecompressor.
Replace it ifnecessary.
Rewiring or pushreset button.
— 10 —
Note: Use an appropriate measuring instrument for readjustment.
*1: High-pressure switch moves.
*2: Low- pressure switch moves.
2. The Units discontinue after the operation started
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY
Outdoor coil
In-condensable gasblended.
High pressure switch(Option part)
Refrigerant
Outdoor Fan
Coil is dirty *1
Air intruded into the refrigerant pipe line *1
Improper adjustment
A shortage of refrigerantamount. * 2
Check pressure
Reverse rotation of fan Obstacle
Air short circuit *1
Checking
In the event that difference between thesaturating temperaturecorresponding to highpressure and the temperature of air discharged from the outdoor coil is more than15°C, incondensable gasmay be blended.
Check it with a pressuregauge.
Confirm the wind blowingout upward.
Check it with eyes.
Wash it by means ofsomething like chemicalwashing.
Extract air by vacuumpump, then replenish(charge) the refrigerant.
Read just it to normaloperating pressure. (Note)Don't alternate the specified adjusting pressure. If the adjustedpressure exceed thespecified range, it willcause a great accident.
Replenish the refrigerant. Repair thespot where it is leaked.
If reversed, connectinterchanged wires toeach terminal. Power wirings.
— 11 —
3. The unit is working, but not cooling and heating sufficiently(Both blower and compressor are working)
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY
Load
Air flow
Short air volume
Refrigerant
Air passage
Air filter
Much Cooling or Heatingload
Obstacle disturbs Intakeof uniform airflow.
Reverse rotation of blower.
Shortage in the chargedrefrigerant.
Improper or foreign bodies
Clogged with dust
Heat load increased. Window or door has manycracks or gaps.
Checking
Checking
Coil inlet pipe is frosted
Checking
Checking
Do necessary disposalrespectively.
Correct it.
Correct it.
Recharge it. (Repair the leakage spot).
Correct or clear the foreign bodies.
Cleaning
4. All the functions are performed as specified, but very noisy and vibrant
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY
Compressor
Blower
Screws
Electric troubles(Magnetic contactor)
Others
• Checking
Checking
Checking
Checking
Improper installation Checking
• Replace the compressor
Repair or replace it.Clear the foreign bodies.
Correct
Repair and clean orreplace it.
Correct it.
Liquid refrigerant floodingback from the evaporator.
Faulty Discharge valveand suction valve.
Fan broken.
Foreign matters intruded.
Looseness or fail-off ofscrews
Defective contact.Defective contact point.Rusting and foreignmatters in the iron corecontact face. Defectivecontact of the operating switch.
• Check for refrigerant over-charge.• Check to see if the intake air temperature is
extremely cold.• Check for insufficient air flow quantity.
Electronic parts Troubleshooting Guide
— 12 —
YES
YES
YES
NO
YES
Is the input voltage oftransformer AC220V?
Is the output voltageof IC02D(7805) on the
main PCB DC5V?
1. Check the Fuse.2. Check the wiring of AC220V.
Is the output voltageof IC01D(7812 ) on the
main PCB DC12V?
OSC01B vibration?
1. Exchange main PCB ASS'Y
1. Exchange remote-controller2. Check or exchange the Main PCB ASS'Y.
YES
NO 1. Exchange the transformer.2. Check the connector of transformer.
NO
NO
NO
YES
Is the output voltageof IC01A(7036) on the
main PCB DC5V?
NO
1. Exchange IC01D(7812) on the main PCB.2. Check the D01D~D05D, R05C on the main PCB.
1. Exchange IC01A(7036) on the main PCB.
Is the output voltage oftransformer AC24V & AC13V?
1. Exchange OSC01B.2. Check the pattern around OSC01B on the main PCB.
Is the input voltageof remote-controller
DC12V?
YES
NO
YES
Is the power ON?NO
1. Check the FUSE.2. Check the input voltage of Main PCB ASS'Y.
1. Check or exchange the IC01D on the Main PCB.2. Check or exchange the Connector (RED, BROWN) of the remote controller.
1. Exchange IC02D(7805) on the main PCB.2. Check the D01D~D05D, R05C on the main PCB.
Possible trouble 1 : The unit does not operate.
Possible trouble 2 : The remote-controller does not operate.
— 13 —
YES
NO
YES
NO
NO
Is the connection betweenMAIN PCB and remote-controller
correct?
Is there Check(F**) onthe remote controller LCD?
1. Check or repair Connector wiring.2. Exchange the Connector.
Is the input power voltage ofremote-controller DC12V?
Do Keys have troubles?
Exchange remote-controller.
Exchange remote-controller.
NO
YES 1. Replace the pressed key.2. Exchange the Knob or Key.
YES
NO
1. Remove cause of Check.2. Reenergize the power supply.
YES
YES
Is there OSC01B vibration on the remote-controller
PCB?
NO
1. Check or exchange IC01D (7812) on the MAIN PCB.
1. Exchange OSC01B2. Check the pattern around OSC01B on the remote-controller PCB.
Is any key on the remote-controllerkeeping pressed?
1. Check Keys.2. Repair or exchange Key.
Is there trouble in theremote-controller PCB
ASS'Y?
NO
YES
NO
Are there trouble inLCD parts?
YES1. Check crack, damage of LCD.2. Check LCD pattern.
1. Check or repair all IC with dust or moisture on the PCB.2. Exchange remote-controller PCB.
Possible trouble 3 : Key input of remote-controller does not respond.
Possible trouble 4 : LCD display on the remote-controller shows some trouble.
— 14 —
YES
YES
YES
NO
YES
Is the cooling mode?
Is the outputvoltage of IC02D on the MAIN
PCB DC5V?
1. Press cooling operation key.2. After reenergizing power supply, press power "ON/OFF" button.
YES
NOIs the unit operating? 1. Press power ON/OFF button.
Is the outputvoltage of IC01M's 13/12(COMP B)PIN
on the MAIN PCB DC0V?
Is the magnetic contactorfor compressor ON?
1. Check Compressor and Capacitor for Compressor.
NOTE: 3ø model has not capacitor for compressor.
YES
NO 1. Set following. 'Set Temp. < Room Temp.'
NO
NO
1. Check or exchange IC01D, IC02D on the MAIN PCB.
NO
YES
Is the voltagebetween A/B(COMP B) of CN-COMP
and NEUTRAL 220V?
NO
1. Check or exchange IC01M.2. Check 3-minutes time delay.
1. Check or exchange RY4/RY5(COMP B).
Set Temp. < Room Temp.?
1. Check the wiring of Magnetic contactor.2. Exchange Magnetic contactor.
Possible trouble 5 : No cooling operation performed.
— 15 —
Is the heater LCD "ON"?
Is the outputvoltage of IC02D on the
MAIN PCB DC5V?
1. Reconnecting power supply.Press Heater Key.
Is the heater operation? 1. Select heater operation mode.
Is the outputvoltage of IC02M's 11PIN on the
MAIN PCB 0V?
Is the magnetic contactor forheater ON?
Check or exchange E/Heater.
1. Set following. 'Set temp. > Room temp.'
1. Check or exchange IC01D, IC02D on the MAIN PCB.
Is the voltagebetween A/B(Heat B) of CN-HEAT(CN6)
and NEUTRAL 220V?
1. Check or exchange IC02M.
1. Check or exchange RY13/RY14(Heat B).
Set temp. > Room temp.?
1. Check the wiring of Magnetic contactor.2. Exchange Magnetic contactor.
YES
YES
YES
NO
YES
YES
NO
YES
NO
NO
NO
NO
YES
NO
Possible trouble 6 : No heater operation performed.
— 16 —
Is the indoor fan operation?
Is the outputvoltage of IC02D on the
MAIN PCB DC5V?
1. Press cooling or fan operation or heater operation key.
Is the outputvoltage of IC02M's 12PIN on
the MAIN PCB 0V?
Is the magneticcontactor for humidifier ON?
Check the humidifier.
1. Press humidifier Key.
1. Check or exchange IC01D. IC02D on the MAIN PCB.
Is the voltagebetween 1PIN of CN-HUMID and
NEUTRAL 220V?
1. Check or exchange IC02M.
1. Check or exchange RY3.
Is the HUMID LCD "ON"?
1. Check the wiring or Magnetic contactor.2. Exchange Magnetic contactor.
YES
YES
YES
NO
YES
YES
NO
NO
NO
NO
YES
NO
Possible trouble 7 : No humidifier operation performed.
— 17 —
Is the unit operating?
Is the outputvoltage of IC02M's 14PIN on
the MAIN PCB 0V?
Is the "Power relay" forindoor motor ON?
Check the indoor motor.
1. Press power ON/OFF button.2. Reconnect the power supply.
1. Check or exchange IC01M.
1. Check the wiring of "Power relay".2. Exchange "Power relay".
YES
YES
YES
NO
NO
NO
YES
Is the voltagebetween 1PIN(IN) of CN-FAN(IN) and
NEUTRAL 220V?1. Check or exchange RY10.
NO
Is the compressor operating?
Is it cooling operation? 1. Press power "ON/OFF" button.2. Select cooling operation.
1. Set following. Set temp. < Room temp.2. Wait, if the unit has operating with 3-minute time delay.
YES
NO
YES
NO
Is the outputvoltage of IC02M's 13/12(OUT FAN B)
on the MAIN PCB 0V?
Is the "Power relay" foroutdoor motor ON?
Check the outdoor motor A/B.
1. Check or exchange IC02M.
1. Check the wiring of "Power relay".2. Exchange "Power relay".
YES
YES
NO
NO
Is the voltagebetween OUT A/B of CN-FAN and
NEUTRAL 220V?1. Check or exchange
RY11/RY12(OUT FAN B).
YES
NO
Possible trouble 8 : Indoor motor does not operate.
Possible trouble 9 : Outdoor motor does not operate.
— 18 —
Is the heater LCD "ON"?
Is the outputvoltage of IC02D on the
MAIN PCB DC5V?
1. Reconnecting power supply.Press Heater Key.
Is the heater operation? 1. Select heater operation mode.
Is the outputvoltage of IC01M's 16PIN on the
MAIN PCB 0V?
Is the magnetic contactor forheater OK?
Check or exchange E/Heater.
1. Set following. 'Set temp. > Room temp.'
1. Check or exchange IC01D, IC02D on the MAIN PCB.
Is the voltagebetween 1PIN of CN5 and
NEUTRAL 220V?
1. Check or exchange IC01M.
1. Check or exchange RY1.
Set temp. > Room temp.?
1. Check the wiring of Magnetic contactor.2. Exchange Magnetic contactor.
YES
YES
YES
NO
YES
YES
NO
YES
NO
NO
NO
NO
YES
NO
Possible trouble 10 : No heater operation performed.
Features of Controller
— 19 —
1. Main Controller Circuit Diagram
— 20 —
2. Feature of Main Controller
— 21 —
3. Feature of Remote-Controller PCB ASS'Y
4. Feature of Remote-Controller LCD
— 22 —
5. Error Mode & Corrective Method
6. Principal part list of controller
7. Principal part list of Main PCB ASM 8. Principal part list of Remote Controller
Error mode
F01
F04
F05
F02
F03
Cause of error
OPEN/SHORT ofroom temp. sensor
OPEN/SHORT ofoutdoor pipe sensor
OPEN/SHORT ofindoor pipe temp. sensor
OPEN/SHORT ofoutdoor roomtemp. sensor
CommunicationError
RemarkSensing condition of error
Voltage of sensing: Over 4.8VVoltage of sensing: Less than
0.5V
Voltage of sensing: Over 4.8VVoltage of sensing: Less than
0.5V
1. Check the voltage of "CO1H"on the remote controller.
2. Check the temp. sensor ofremtote controller.
1. Check the voltage between PIN1 and 2 of CN-A cycle/CN-Bcycle ON the main PCB.
2. Check the temp. sensor ofremtote controller.
1. Check the voltage between PIN 3and 4 of CN-A cycle/CN-B cycle.
2. Check the temp. sensor ofindoor pipe.
1. Check the voltage betweenPIN 1 and 3 of CN-TEMPOUT on the main PCB.
2. Check the temp. sensor ofoutdoor room.
1. Check the connecting wirebetween main PCB remotecontroller.
2. Check the input voltage ofremote-controller.
3. Check the wiring of remote-controller.
Roomtemp.(25°C) = DC 2.5V
Pipe temp.(25°C) = DC 2.5V
Pipe temp.(25°C) = DC 2.2V
Roomtemp.(25°C) = DC 2.2V
Input voltage ofremote-controller
= DC 12V
Voltage of sensing: Over 4.8VVoltage of sensing: Less than
0.5V
Voltage of sensing: Over 4.8VVoltage of sensing: Less than
0.5V
Communication interruptionbetween remote controller andMain PCB for 2 minutes.
Method of SVC
LK-2580CH 6871A20085E 6711A20007B 6323AQ2333T 6323AQ2333U6323AQ3214M
6323AQ3214H 6171AQ2138E Cooling Only(OPTIONAL)
Model Main PCBASM
Remotecontroller
Pipe Sensor A
Pipe Sensor A/B
Return AirSensor
OutdoorRoom Sensor
PowerTrans Remark
No Part No Part Name Remarks1 0ITO874000E MICOM(Main) MICOM2 6920AQ9033F Relay3 6212AQ9002J Oscillator4 6900AQ9028D Fuse5 6102A90001A Varistor
No Part No Part Name Remark1 OITO641010B MICOM(Remote Controller) MICOM2 6304A30001C LCD3 6871A20043A Remote C PCB ASM Cooling Only4 6871A20043H Remote C PCB ASM Heat Pump
— 23 —
9. Explanation of principal function■ Flow Chart
Power ON?
Cooling Mode?
Time delay mode
Cooling operating
Set Temp. < Indoor Temp.
YES
YES
YES
NO
YES
YES
Stop condition?
YES
1. Initialize "micom".2. A/D convert.3. Main PCB: Waiting cooling operation.4. Remote controller: Waiting input.
YES
START(Power supply)
Go to A
Fan only operating
Stop condition?
YES
Go to A
Dehumidification Mode?
Dehumidification operating
YES
Stop condition?
YES
Go to A
Set Temp. > Indoor Temp.
Heater operating
YES
Heater operation mode?
YES
Stop condition?
YES
NO
NO
NO NO
NO
NO
NO
NO
A
YES
Go to A
Exploded View and Replacement Parts List
— 24 —
• Exploded View
346810
249950
261704546810
549610
268714
554031
669200
554031
267110
W0CZZ
666000
559010
152302
354210
263230
330870
263230
435311
359011
342800
552101
— 25 —
152302 FILTER(MECH), A/C 5230A20003H
249950 CONTROL BOX ASSEMBLY, SINGLE 4995A10022B
261704 TRANSFORMER, POWER 6171AQ2138E
263230 THERMISTOR ASSY 6323AQ2333T
263230 THERMISTOR ASSY 6323AQ2333U
263230 THERMISTOR ASSY 6323AQ3214H
267110 REMOTE CONTROLLER ASSEMBLY 6711A20007B
268714 PWB(PCB) ASSY, MAIN 6871A20085E
330870 DRAIN PAN ASSEMBLY 3087A20006D
342800 BEARING 4A00131B
346810 MOTOR ASSEMBLY, INDOOR 4681A20031E
354210 EVAPORATOR ASSEMBLY, FIRST 5421A20035F
359011 FAN ASSY, BLOWER 5835A20003D
435311 GRILLE ASSEMBLY, DISCHARGE(OUTDOOR) 2A00144L
546810 MOTOR ASSY, OUTDOOR 4681A20026D
546810 MOTOR ASSY, OUTDOOR 4681A20026E
549610 MOUNT ASSEMBLY, MOTOR(OUTDOOR) 4961A20007A
552101 TUBE, CAPILLARY 3H01535Z
554031 CONDENSER ASSY, BENT 5403A20023G
554031 CONDENSER ASSY, BENT 5403A20023J
554160 COMPRESSOR ASSY, FINAL 5417A20007F
559010 FAN ASSY, PROPELLER 5901A20004D
566000 SWITCH, PRESSURE 6600A20004C
666000 SWITCH, MAGNET 2A01031A
669200 RELAY 6920AP3400A
W0CZZ CAPACITOR, DRAWING 0CZZA20001E
• Replacement Parts List
LOCATION DESCRIPTION PART No. REMARKSNo.
Specification of Components
— 26 —
COMP P/No 5417A20007FModel name H25G104DBVE
*RLA (A) 14.5**LRA (A) 115
Q'ty 3INDOOR MOTOR P/No 4681A20031E
Output 7.5 (Hp)Shaft Dia 28 (mm)
RPM 2890OUTDOOR MOTOR P/No 4681A20026D, 4681A20026E
Output 1.3 (Hp)Shaft Dia 19 (mm)
RPM 950Q'ty 1/1
OUTDOOR FAN P/No 5901A20004DDiameter O.D 710 (mm)
INDOOR BLOWER P/No 5835A20003DDiameter*width 450*454 (mm)
MOTOR PULLY P/No 3A00217SType VARIABLE
BLOWER PULLY P/No 4561A30003EType "REC-B" TYPE
Outside Dia. 406(mm)V-VELT P/No 4400A30002N
Type "REC-B" TYPELength 30.3 (inch)
LOWER PRESSURE SWITCH P/No 6600A20004CSpec. OFF : 2.0kgf/ON : 3.5kgf
Rated Voltage DC 24VMaker SAGINOMIYA
CAPACITOR for COMP P/No -Spec. -
CAPACITOR for ***IDM P/No -Spec. -
CAPACITOR for ****ODM P/No 0CZZA20001ESpec. 20µF/450V
FILTER P/No 5230A20003HSize 750*717(mm)Q'ty 4
CAPILLIARY TUBE P/No 3H01535ZSpec. I.D1.2*720(mm)Q'ty 30
TRANS FORMER P/No 6171AQ2138ESpec. AC 220V, 450mA
CONTACTOR for COMP. P/No 2A01031ASpec. 30A, 220V CONTROL
RELAY for IDM P/No 6920AP3400ASpec. 220V, 25A
RELAY for ODM P/No 6920AP3400ASpec. 220V, 25A
MODEL LK-2580CH
*RLA : RATED LOAD AMPER**LRA : LOCK LOAD AMPER
P/No.: 3828A20134A
September, 2001
Printed in Korea