LIRIK OC2 SE CAL 001_A (Perhitungan Oil Catcher)
Transcript of LIRIK OC2 SE CAL 001_A (Perhitungan Oil Catcher)
MODIFIKASI SISTEM PENYIMPANAN DAN PERBAIKAN
FASILITAS OPERASI DI TERMINAL BUATAN-FIELD LIRIK
PERHITUNGAN STRUKTUR
OIL CATCHER SHELTER (3x2x1)
DOCUMENT NUMBER : LIRIK-OC2-SE-CAL-001
REV DATE DESCRIPTION PREP’D CHK’D APP’D CLIENT.
A 23/04/10 Issued For Review ART YAW / ABS
MODIFIKASI SISTEM PENYIMPANAN DAN PERBAIKAN FASILITAS OPERASI DI TERMINAL
BUATAN‐FIELD LIRIK
LIRIK‐OC2‐SE‐CAL‐001 (Perhitungan Struktur
Oil Catcher Shelter (3x2x1))
Halaman i
DAFTAR ISI
1. PENGANTAR ............................................................................................................................................... 1 1.1. UMUM............................................................................................................................................................... 1 1.2. MAKSUD DAN TUJUAN ..................................................................................................................................... 1 1.3. LINGKUP KERJA ............................................................................................................................................... 1
2. KONDISI DISAIN ..................................................................................................................................... 2 2.1. KODE DAN STANDAR ....................................................................................................................................... 2 2.3. DATA DESAIN ................................................................................................................................................... 2
3. KONSEP DESAIN STRUKTUR ................................................................................................................... 3 3.1 UMUM............................................................................................................................................................... 3 3.2 STRUKTUR RENCANA ...................................................................................................................................... 3 3.3 MODEL STRUKTUR .......................................................................................................................................... 3 3.4 DIMENSI BANGUNAN ........................................................................................................................................ 4 3.5 METODE ANALISIS ........................................................................................................................................... 4 3.6 PROGRAM ANALISIS ........................................................................................................................................ 4
4. PEMBEBANAN DAN KOMBINASI PEMBEBANAN ................................................................................. 4 4.1 BEBAN MATI (DL) ............................................................................................................................................. 4 4.3 BEBAN GEMPA ................................................................................................................................................. 5 4.4 KOMBINASI PEMBEBANAN ............................................................................................................................... 7
5. DESAIN STRUKTUR ................................................................................................................................... 8 5.1 DESAIN KOLOM ................................................................................................................................................ 8 5.2 DESAIN BEAM ................................................................................................................................................ 10 5.3 REKAPITULASI RASIO STRUKTUR BAJA (OUTPUT DARI STAAD PRO 2007) ................................................. 13
6. DESAIN PONDASI ..................................................................................................................................... 13 6.1 REAKSI KOLOM .............................................................................................................................................. 13 6.2 PERHITUNGAN PONDASI SETEMPAT ............................................................................................................. 14
MODIFIKASI SISTEM PENYIMPANAN DAN PERBAIKAN FASILITAS OPERASI DI TERMINAL BUATAN‐FIELD LIRIK
LIRIK‐OC2‐SE‐CAL‐001 (Perhitungan Struktur
Oil Catcher Shelter (3x2x1))
Halaman 1
1. PENGANTAR
1.1. Umum
Salah satu pekerjaan Modifikasi Sistem Penyimpanan dan Perbaikan Fasilitas Operasi di
Terminal Buatan-Field Lirik adalah konstruksi Oil Catcher.
1.2. Maksud dan Tujuan
Maksud dan Tujuan dari pekerjaan detail enjiniring ini adalah untuk dijadikan acuan utama
dalam memasuki tahap konstruksi sehingga didapatkan nilai konstruksi yang ekonomis
namun tetap efektif dan efisien.
1.3. Lingkup Kerja
Lingkup kerja pada pekerjaan Disain Detail Enjiniring ini meliputi :
Analisa dan disain struktur Shelter
MODIFIKASI SISTEM PENYIMPANAN DAN PERBAIKAN FASILITAS OPERASI DI TERMINAL BUATAN‐FIELD LIRIK
LIRIK‐OC2‐SE‐CAL‐001 (Perhitungan Struktur
Oil Catcher Shelter (3x2x1))
Halaman 2
2. KONDISI DISAIN
2.1. Kode dan Standar
Kode dan standar yang akan digunakan dalam disain enjiniring ini adalah seperti
tercantum di bawah ini tapi tidak terbatas pada:
• ACI Standard, “Building Code Requirements for Structural Concrete (ACI 318-02) and
Commentary (ACI 318R-02)”.
• AISC Standard, “Load and Resistance Factor Design Specification” (AISC-LRFD
1999).
• ASCE Standard, “Minimum Design Loads for Buildings and Other Structures”
(ASCE/SEI 7-05).
• Peraturan Gempa Indonesia, SNI-1726-2002.
2.3. Data Desain
Material yang digunakan untuk desain ini mengacu pada kode material yang telah dikenal
secara nasional dan internasional, seperti misalnya, namun tidak terbatas pada:
• Beton dengan kekuatan beton (f’c) minimal 25 MPa, sebagaimana ditentukan oleh
ASTM-C94, ASTM-C33, ASTM-C171, dan ACI-212.
• Beton bertulang dengan Tegangan leleh (fy) minimum 400 MPa untuk deformed, dan
240 MPa untuk baja polos seperti ditentukan pada ASTM-A185, dan AWS 121.
MODIFIKASI SISTEM PENYIMPANAN DAN PERBAIKAN FASILITAS OPERASI DI TERMINAL BUATAN‐FIELD LIRIK
LIRIK‐OC2‐SE‐CAL‐001 (Perhitungan Struktur
Oil Catcher Shelter (3x2x1))
Halaman 3
3. KONSEP DESAIN STRUKTUR
3.1 Umum
Oil Catcher merupakan struktur rangka baja dengan profil material Hollow Pipe
3.2 Struktur Rencana
3.3 Model Struktur
Struktur dimodelkan sebagai rangka 3 dimensi. Pendukung (Support) dimodelkan sebagai
sendi.
Struktur 3D
MODIFIKASI SISTEM PENYIMPANAN DAN PERBAIKAN FASILITAS OPERASI DI TERMINAL BUATAN‐FIELD LIRIK
LIRIK‐OC2‐SE‐CAL‐001 (Perhitungan Struktur
Oil Catcher Shelter (3x2x1))
Halaman 4
3.4 Dimensi Bangunan
Dimensi kolom (mm)
C1 : Pipe 140 x 4.5
Dimensi Balok (mm)
B1 : Pipe 140 x 4.5
B2 : Pipe 140 x 4.5
3.5 Metode Analisis
Desain kekuatan diaplikasikan mengikuti AISC ASD. Semua konstruksi didesain sesuai
ketentuan spesifikasi dalam AISC ASD.
3.6 Program Analisis
Oil catcher shelter dianalisis dengan menggunakan program komputer STAAD-Pro 2007.
4. PEMBEBANAN DAN KOMBINASI PEMBEBANAN
4.1 Beban mati (DL)
Berat material yang digunakan dalam perancangan desain struktur, diantaranya:
Berat sendiri struktur dihitung secar aotomatis oleh software Berat sendiri Purlin dan Plat atap diambil 5 kg/m2
DL
MODIFIKASI SISTEM PENYIMPANAN DAN PERBAIKAN FASILITAS OPERASI DI TERMINAL BUATAN‐FIELD LIRIK
LIRIK‐OC2‐SE‐CAL‐001 (Perhitungan Struktur
Oil Catcher Shelter (3x2x1))
Halaman 5
4.2 Beban Hidup Beban Hidup pada atap diambil 20 kg/m2
Beban = 6 m x 1m x 20 = 120 kg/m’
LL
4.3 Beban Gempa
Wt : Total Dead Load (include self weight) + Live LoadFrom STAAD Pro Reaction Obtained :
MODIFIKASI SISTEM PENYIMPANAN DAN PERBAIKAN FASILITAS OPERASI DI TERMINAL BUATAN‐FIELD LIRIK
LIRIK‐OC2‐SE‐CAL‐001 (Perhitungan Struktur
Oil Catcher Shelter (3x2x1))
Halaman 6
- Joint Column 1 = kN 2- Joint Column 3 = kN 4- Joint Column 12 = kN 13- Joint Column 14 = kN 15
Wt kN28.02
7.136.717.097.09
From STAAD Pro Rayleigh Frequency Analysis, obtained that:
Rayleigh Frequency in X direction = cps From StaadRayleigh Frequency in Z direction = cps
cps = cicle per secondNatural Periode in X direction (TX) = secNatural Periode in Y direction (TZ) = sec
For Zone 3. Soft Soil, obtained thatCx =Cz =
Eartquake Constant (Ecx)I = 1.4R = 5.6Ecx = C x I/R
=
Eartquake Constant (Ecz)I = 1.4R = 5.6Ecz = C x I/R
=
V = (C * I * Wt) / R= 5.3 kN
Fi = ( Wi * Zi / Σwi*Zi ) * V
1.291.64
0.78
0.75
0.61
0.75
0.1875
0.1875
Fi1.34
Wi * Zi26.73
26.57
1.261.331.33
25.1626.59
Zi3.753.753.753.757.09
Wi7.136.717.09
2 FX 1.3 2 FZ 1.34 FX 1.3 4 FZ 1.3
13 FX 1.3 13 FZ 1.315 FX 1.3 15 FZ 1.3
FOR STAAD
MODIFIKASI SISTEM PENYIMPANAN DAN PERBAIKAN FASILITAS OPERASI DI TERMINAL BUATAN‐FIELD LIRIK
LIRIK‐OC2‐SE‐CAL‐001 (Perhitungan Struktur
Oil Catcher Shelter (3x2x1))
Halaman 7
EQX dan EQZ
4.4 Kombinasi Pembebanan
Kombinasi pembebanan mengikuti standar SNI 03-2847-2002 & S-200 mengenai pembebanan
minimum untuk bangunan dan struktur lainnya.
1) Pembebanan dan Simbol Gaya
Beban Mati DL
Beban Hidup LL
Beban Gempa EQ (EQX, EQZ)
2) Kombinasi Pembebanan untuk struktur baja (shelter)
1. 1.0 D
2. 1.0 DL+ 1.0 LL + 1.0 LR
3. 1.0 DL+ 1.0 LL + 1.0 LR + 0.7 EQX + 0.21 EQZ
4. 1.0 DL+ 1.0 LL + 1.0 LR + 0.21 EQX + 0.7 EQZ
5. 1.0 DL+ 0.5 LL + 0.5 LR + 0.7 EQX + 0.21 EQZ
6. 1.0 DL+ 0.5 LL + 0.5 LR + 0.21 EQX + 0.7 EQZ
MODIFIKASI SISTEM PENYIMPANAN DAN PERBAIKAN FASILITAS OPERASI DI TERMINAL BUATAN‐FIELD LIRIK
LIRIK‐OC2‐SE‐CAL‐001 (Perhitungan Struktur
Oil Catcher Shelter (3x2x1))
Halaman 8
5. DESAIN STRUKTUR
5.1 Desain Kolom
MODIFIKASI SISTEM PENYIMPANAN DAN PERBAIKAN FASILITAS OPERASI DI TERMINAL BUATAN‐FIELD LIRIK
LIRIK‐OC2‐SE‐CAL‐001 (Perhitungan Struktur
Oil Catcher Shelter (3x2x1))
Halaman 9
C1 Pipe 140 x 4.5
STAAD.PRO CODE CHECKING - (AISC 9TH EDITION)
********************************************
|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CMS UNIT |
| * |=============================| ------------ |
|MEMBER 1 * | JAPANESE SECTIONS | AX = 19.13 |
| * | ST PIP139.8X4.5 | --Z AY = 9.57 |
|DESIGN CODE * | | AZ = 9.57 |
| AISC-1989 * =============================== SY = 62.66 |
| * SZ = 62.66 |
| * |<---LENGTH (M)= 3.10 --->| RY = 4.78 |
|************* RZ = 4.78 |
| |
| 3.4 (KNS-METRE) |
|PARAMETER | L3 STRESSES |
|IN KNS CMS | L3 L3 IN NEWTON MMS|
|--------------- + L3 -------------|
| KL/R-Y= 64.79 | L3 FA = 144.00 |
| KL/R-Z= 64.79 + fa = 0.73 |
| UNL = 310.00 | L3 L3 FCZ = 158.40 |
| CB = 1.00 + FTZ = 158.40 |
| CMY = 0.85 | L3 L3 FCY = 158.40 |
| CMZ = 0.85 + L3 FTY = 158.40 |
| FYLD = 24.00 |L0 fbz = 54.23 |
| NSF = 1.00 +---+---+---+---+---+---+---+---+---+---| fby = 0.00 |
| DFF = 0.00 -0.2 Fey = 251.50 |
| dff= 0.00 ABSOLUTE MZ ENVELOPE Fez = 251.50 |
| (WITH LOAD NO.) FV = 96.00 |
| fv = 1.15 |
| |
| MAX FORCE/ MOMENT SUMMARY (KNS-METRE) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 5.7 1.1 1.0 0.0 3.4 |
| LOCATION 0.0 0.0 0.0 0.0 3.1 |
| LOADING 30 3 4 0 3 |
| |
MODIFIKASI SISTEM PENYIMPANAN DAN PERBAIKAN FASILITAS OPERASI DI TERMINAL BUATAN‐FIELD LIRIK
LIRIK‐OC2‐SE‐CAL‐001 (Perhitungan Struktur
Oil Catcher Shelter (3x2x1))
Halaman 10
|**************************************************************************|
|* *|
|* DESIGN SUMMARY (KNS-METRE) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS AISC- H2-1 0.347 3 |
| 1.39 T -0.01 -3.40 3.10 |
|* *|
|**************************************************************************|
5.2 Desain Beam
B1 : Pipe 140 x 4.5
STAAD.PRO CODE CHECKING - (AISC 9TH EDITION)
********************************************
|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CMS UNIT |
| * |=============================| ------------ |
|MEMBER 11 * | JAPANESE SECTIONS | AX = 19.13 |
| * | ST PIP139.8X4.5 | --Z AY = 9.57 |
|DESIGN CODE * | | AZ = 9.57 |
| AISC-1989 * =============================== SY = 62.66 |
| * SZ = 62.66 |
| * |<---LENGTH (M)= 5.75 --->| RY = 4.78 |
|************* RZ = 4.78 |
| |
| 2.7 (KNS-METRE) |
|PARAMETER |L4 STRESSES |
|IN KNS CMS | IN NEWTON MMS|
|--------------- + L4 L4 -------------|
| KL/R-Y= 120.17 | L4 L4 FA = 144.00 |
| KL/R-Z= 120.17 + fa = 0.03 |
| UNL = 575.00 | L4 L4 FCZ = 158.40 |
| CB = 1.00 + L4 L4 FTZ = 158.40 |
MODIFIKASI SISTEM PENYIMPANAN DAN PERBAIKAN FASILITAS OPERASI DI TERMINAL BUATAN‐FIELD LIRIK
LIRIK‐OC2‐SE‐CAL‐001 (Perhitungan Struktur
Oil Catcher Shelter (3x2x1))
Halaman 11
| CMY = 0.85 | FCY = 158.40 |
| CMZ = 0.85 + L4 FTY = 158.40 |
| FYLD = 24.00 | L34 fbz = 43.56 |
| NSF = 1.00 +---+---+---+---+---+---+---+---+---+---| fby = 0.00 |
| DFF = 0.00 0.2 Fey = 73.10 |
| dff= 0.00 ABSOLUTE MZ ENVELOPE Fez = 73.10 |
| (WITH LOAD NO.) FV = 96.00 |
| fv = 0.91 |
| |
| MAX FORCE/ MOMENT SUMMARY (KNS-METRE) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE 0.1 0.9 0.0 0.0 2.7 |
| LOCATION 0.0 5.8 0.0 0.0 0.0 |
| LOADING 34 34 4 0 4 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY (KNS-METRE) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS AISC- H2-1 0.275 4 |
| 0.06 T -0.11 2.73 0.00 |
|* *|
|**************************************************************************|
B2 : Pipe 140 x 4.5
STAAD.PRO CODE CHECKING - (AISC 9TH EDITION)
********************************************
|--------------------------------------------------------------------------|
| Y PROPERTIES |
|************* | IN CMS UNIT |
| * |=============================| ------------ |
|MEMBER 21 * | JAPANESE SECTIONS | AX = 19.13 |
| * | ST PIP139.8X4.5 | --Z AY = 9.57 |
MODIFIKASI SISTEM PENYIMPANAN DAN PERBAIKAN FASILITAS OPERASI DI TERMINAL BUATAN‐FIELD LIRIK
LIRIK‐OC2‐SE‐CAL‐001 (Perhitungan Struktur
Oil Catcher Shelter (3x2x1))
Halaman 12
|DESIGN CODE * | | AZ = 9.57 |
| AISC-1989 * =============================== SY = 62.66 |
| * SZ = 62.66 |
| * |<---LENGTH (M)= 4.00 --->| RY = 4.78 |
|************* RZ = 4.78 |
| |
| 2.2 (KNS-METRE) |
|PARAMETER |L3 STRESSES |
|IN KNS CMS | IN NEWTON MMS|
|--------------- + L3 L3 -------------|
| KL/R-Y= 83.60 | L3 FA = 101.49 |
| KL/R-Z= 83.60 + L3 fa = 0.00 |
| UNL = 400.00 | L3 FCZ = 158.40 |
| CB = 1.00 + L29 L3 FTZ = 158.40 |
| CMY = 0.85 | L3 FCY = 158.40 |
| CMZ = 0.85 + FTY = 158.40 |
| FYLD = 24.00 | L28 L3 fbz = 35.28 |
| NSF = 1.00 +---+---+---+---+---+---+---+---+---+---| fby = 0.00 |
| DFF = 0.00 0.3 Fey = 151.06 |
| dff= 0.00 ABSOLUTE MZ ENVELOPE Fez = 151.06 |
| (WITH LOAD NO.) FV = 96.00 |
| fv = 1.04 |
| |
| MAX FORCE/ MOMENT SUMMARY (KNS-METRE) |
| ------------------------- |
| |
| AXIAL SHEAR-Y SHEAR-Z MOMENT-Y MOMENT-Z |
| |
| VALUE -1.6 1.1 0.1 0.0 2.2 |
| LOCATION 0.0 4.0 0.0 0.0 0.0 |
| LOADING 22 29 4 0 3 |
| |
|**************************************************************************|
|* *|
|* DESIGN SUMMARY (KNS-METRE) *|
|* -------------- *|
|* *|
|* RESULT/ CRITICAL COND/ RATIO/ LOADING/ *|
| FX MY MZ LOCATION |
| ====================================================== |
| PASS AISC- H1-3 0.223 3 |
| 0.01 C -0.03 -2.21 0.00 |
|* *|
MODIFIKASI SISTEM PENYIMPANAN DAN PERBAIKAN FASILITAS OPERASI DI TERMINAL BUATAN‐FIELD LIRIK
LIRIK‐OC2‐SE‐CAL‐001 (Perhitungan Struktur
Oil Catcher Shelter (3x2x1))
Halaman 13
5.3 Rekapitulasi Rasio Struktur Baja (Output dari Staad Pro 2007)
Beam Number
Analysis Property
Design Property
Ratio Clause L/C Ax cm2 Iz cm4 Iy cm4 Ix cm4
1 PIP139.8X4.5 PIP139.8X4.5 0.413 AISC- H2-1 3 19.13 4.38E+02 4.38E+02 8.76E+022 PIP139.8X4.5 PIP139.8X4.5 0.415 AISC- H1-3 3 19.13 4.38E+02 4.38E+02 8.76E+023 PIP139.8X4.5 PIP139.8X4.5 0.149 AISC- H1-3 30 19.13 4.38E+02 4.38E+02 8.76E+024 PIP139.8X4.5 PIP139.8X4.5 0.154 AISC- H1-3 28 19.13 438 438 8765 PIP139.8X4.5 PIP139.8X4.5 0.097 AISC- H2-1 22 19.13 438 438 8.76E+026 PIP139.8X4.5 PIP139.8X4.5 0.211 AISC- H1-3 28 19.13 438 438 8.76E+029 PIP139.8X4.5 PIP139.8X4.5 0.221 AISC- H1-3 30 19.13 438 438 8.76E+0210 PIP139.8X4.5 PIP139.8X4.5 0.08 AISC- H2-1 22 19.13 438 438 8.76E+0211 PIP139.8X4.5 PIP139.8X4.5 0.267 AISC- H1-3 3 19.13 438 438 8.76E+0212 PIP139.8X4.5 PIP139.8X4.5 0.413 AISC- H2-1 3 19.13 438 438 8.76E+0213 PIP139.8X4.5 PIP139.8X4.5 0.415 AISC- H1-3 3 19.13 438 438 8.76E+0214 PIP139.8X4.5 PIP139.8X4.5 0.148 AISC- H1-3 31 19.13 438 438 87615 PIP139.8X4.5 PIP139.8X4.5 0.148 AISC- H1-3 29 19.13 438 438 87616 PIP139.8X4.5 PIP139.8X4.5 0.097 AISC- H2-1 22 19.13 438 438 87617 PIP139.8X4.5 PIP139.8X4.5 0.22 AISC- H1-3 29 19.13 438 438 87618 PIP139.8X4.5 PIP139.8X4.5 0.22 AISC- H1-3 31 19.13 438 438 87619 PIP139.8X4.5 PIP139.8X4.5 0.097 AISC- H2-1 22 19.13 438 438 87620 PIP139.8X4.5 PIP139.8X4.5 0.267 AISC- H1-3 3 19.13 438 438 87621 PIP139.8X4.5 PIP139.8X4.5 0.342 AISC- H1-3 4 19.13 438 438 87622 PIP139.8X4.5 PIP139.8X4.5 0.342 AISC- H1-3 4 19.13 438 438 87623 PIP139.8X4.5 PIP139.8X4.5 0.129 AISC- H1-3 4 19.13 438 438 876
6. DESAIN Pondasi
6.1 Reaksi Kolom
Horizontal Vertical Horizontal
Node L/C Fx kN Fy kN Fz kN
1 22 COMBINATION LOAD CASE -0.083 7.129 -0.071
3 22 COMBINATION LOAD CASE 0.082 6.709 -0.073
12 22 COMBINATION LOAD CASE -0.084 7.091 0.073
14 22 COMBINATION LOAD CASE 0.085 7.086 0.071
MODIFIKASI SISTEM PENYIMPANAN DAN PERBAIKAN FASILITAS OPERASI DI TERMINAL BUATAN‐FIELD LIRIK
LIRIK‐OC2‐SE‐CAL‐001 (Perhitungan Struktur
Oil Catcher Shelter (3x2x1))
Halaman 14
6.2 Perhitungan Pondasi Setempat
Perhitungan Pondasi Shelter Oil Catcher 2
0.25 m
Pedestal
Footing
1. Pembebanan
1.1. Beban Vertikal1.1.1. Reaksi Struktur Atas = 0.71 ton
0.6 m
0.8
m
0.25
m
0.6
m
0.2 m
MODIFIKASI SISTEM PENYIMPANAN DAN PERBAIKAN FASILITAS OPERASI DI TERMINAL BUATAN‐FIELD LIRIK
LIRIK‐OC2‐SE‐CAL‐001 (Perhitungan Struktur
Oil Catcher Shelter (3x2x1))
Halaman 15
1.1.2. Berat Sendiri Pondasi γ beton = 2.4 ton/m3
Berat Pedestal = 0.25 x 0.25 x 0.8 x 2.4 = 0.12 tonBerat Footing = 0.6 x 0.6 x 0.2 x 2.4 = 0.1728 ton
Total = 0.2928 ton
1.1.3. Total Beban VertikalReaksi Struktur Atas + Berat Sendiri Pondasi = 1.0057 ton
1.2. Beban Horisontal
H Reaksi Struktur Atas = 0.0085 ton
P
1.3. Beban Momen
My = Mx = H x (0.2 + 0.8) = 0.0085 ton.m
2. Cek Eksentrisitasex =My/P = 0.0085 m
ey =Mx/P = 0.0085 m1/6 By = 0.1 m ,1/6 Bx = 0.1 m
Cek:
ex =My/P < 1/6 Bx ? OK
ey =Mx/P < 1/6 By ? OK
MODIFIKASI SISTEM PENYIMPANAN DAN PERBAIKAN FASILITAS OPERASI DI TERMINAL BUATAN‐FIELD LIRIK
LIRIK‐OC2‐SE‐CAL‐001 (Perhitungan Struktur
Oil Catcher Shelter (3x2x1))
Halaman 16
3. Cek Stabilitas
qall = 4 ton/m2
= 2.7936 ton/m2
= 0.236 ton/m2
= 0.236 ton/m2
= 3.266 ton/m2
? OK
4. Penulangan
4.1. Penulangan FootingTinjauan kritikal pada potongan A - A
qult = 1.4σ = 4.5722 ton/m2
Mu = 0.5qult.l2 = 0.7001 kN.m
Mn = Mu/0.9 = 0.7779 kN.m
f'c = 20 Mpaβ = 0.85fy = 400 Mpa
Menggunakan tulangan D 13 mm , A = 132.732 mm2
Ketebalan efektif, d = hfooting - 75 = 125 mm
= 0.0830
= 23.529
bL
A
A
d
MODIFIKASI SISTEM PENYIMPANAN DAN PERBAIKAN FASILITAS OPERASI DI TERMINAL BUATAN‐FIELD LIRIK
LIRIK‐OC2‐SE‐CAL‐001 (Perhitungan Struktur
Oil Catcher Shelter (3x2x1))
Halaman 17
= 0.000208
= 0.0035
nilai ρ terbesar yang dipakai untuk menghitung tulangan perlu, yaitu ρmin
Tulangan perlu,0.0035 x 600 x 125 = 262.5 mm2
2Tulangan yang digunakan D13-200
Tulangan susut= 52.5 mm2
1Tulangan yang digunakan D13-250
4.2. Penulangan Pedestal
Penulangan Sleeper menggunakan = 0.0035
Tulangan perlu,0.0035 x 300 x 250 = 218.75 mm2
2Tulangan yang digunakan 4D13Sengkang menggunakan D10-150