Liquiflo Relief Valve Manual

3
 RELIEF VALVE INSTRUCTION MANUAL Standard Models: RV 1000 RV 1001 RV 2000 RV 2001 RV 1000-LP RV 1001-LP RV 2000-LP RV 2001-LP RV 1000-HP RV 1001-HP © Oct. 2014 Liquiflo, All rights reserved Document No.: 3.20.100 443 North Avenue, Garwood, NJ 07027 USA Tel: 908-518-0777 Fax: 908-518-1847 www.liquiflo.com TM

Transcript of Liquiflo Relief Valve Manual

Page 1: Liquiflo Relief Valve Manual

7/25/2019 Liquiflo Relief Valve Manual

http://slidepdf.com/reader/full/liquiflo-relief-valve-manual 1/3

 

RELIEF VALVE INSTRUCTION MANUAL

Standard Models:

RV 1000 RV 1001 RV 2000 RV 2001

RV 1000-LP RV 1001-LP RV 2000-LP RV 2001-LP

RV 1000-HP RV 1001-HP

© Oct. 2014 Liquiflo, All rights reserved Document No.: 3.20.100

443 North Avenue, Garwood, NJ 07027 USA Tel: 908-518-0777 Fax: 908-518-1847 www.liquiflo.com

TM

Page 2: Liquiflo Relief Valve Manual

7/25/2019 Liquiflo Relief Valve Manual

http://slidepdf.com/reader/full/liquiflo-relief-valve-manual 2/3

LIQUIFLO  Relief Valve Instruction Manual

2

Relief Valve Instructions: (Refer to diagram on page 3.)

Your new Liquiflo Relief Valve is maintenance free.

The only adjustment on the valve is the resetting of the relieving point. This is done by loosening thelock nut (2) and rotating the large cap (1). (Turn cap COUNTERCLOCKWISE for lower relief setting;turn CLOCKWISE for higher relief setting.) A general guideline for pressure setting is 10-15 PSIabove the system operating pressure. The relief valve should be installed as close to the pump aspossible and without any valves or accessories between the relief valve and the pump.

If, for any reason, the valve must be disassembled, this can easily be done by loosening the lock nut(2) and unscrewing the adjusting cap (1). Remove the safety pin (7) and pull out the internal springcap (8). This exposes the spring (4) and valve pin (5) assembly.

For reassembly, simply reverse the above action. (Push in the internal spring cap with spring andvalve pin, replace the safety pin, etc.)

CAUTION:

ALWAYS MAKE SURE THERE IS NO PRESSURE IN THE SYSTEM BEFOREDISASSEMBLING THE VALVE. IT IS BEST TO REMOVE THE VALVE FROMTHE SYSTEM.

Always flush the system before disassembling to eliminate the chance ofgetting harmful materials on the skin or in the eyes.

Standard Available Models:

Liquiflo manufactures 2 sizes of relief valves in both 316 SS and Alloy-C. 10 standard Liquiflo ReliefValve models are available, based on the body material, the port size and the pressure setting range(see table below). Models RV1000, RV1001, RV2000 and RV2001 are factory preset to discharge at100 PSI (7 bar) unless a different pressure setting was requested when ordering; other models arepreset to the pressure setting specified when ordering. For any further information, please consultthe factory.

LIQUIFLO Standard Relief Valves 

Model # MaterialPort Size& Type

PressureSetting (PSI)

Approximate Flow @ 25%above Pressure Setting

Min Max USGPM LPM

RV1000-LP 316 SS ½” NPT 25 65 7.5 28RV1000 316 SS ½” NPT 50 135 7.5 28

RV1000-HP 316 SS ½” NPT 75 200 7.5 28

RV1001-LP Alloy-C ½” NPT 25 65 7.5 28

RV1001 Alloy-C ½” NPT 50 135 7.5 28

RV1001-HP Alloy-C ½” NPT 75 200 7.5 28

RV2000-LP 316 SS 1” NPT 25 75 25 95

RV2000 316 SS 1” NPT 50 175 25 95

RV2001 Alloy-C 1” NPT 50 175 25 95

LP = Low Pressure HP = High Pressure

Page 3: Liquiflo Relief Valve Manual

7/25/2019 Liquiflo Relief Valve Manual

http://slidepdf.com/reader/full/liquiflo-relief-valve-manual 3/3

LIQUIFLO  Relief Valve Instruction Manual

3

Outlet½” or 1” NPT 

(6) Teflon O-RingGives Liquiflo Relief Valvea unique advantage byallowing adjustment whilein service without leakage

(3) BodyAvailable in

316 SS or Alloy-C

(4) SpringDetermines dischargepressure setting range

(matches metallurgy ofRelief Valve Body)

(8) Internal Spring CapRetains Spring in conjunctionwith Safety Lock Pin(matches metallurgy ofRelief Valve Body)

(7) Safety Lock PinEnsures parts will notseparate even if Adjusting

Cap is removed

(2) Lock NutLocks Adjusting

Cap in place

Inlet½” or 1” NPT

(5) Valve PinOpens when dischargepressure exceeds pressuresetting (matches metallurgyof Relief Valve Body)

(1) Adjusting CapDischarge pressureadjustment can be

performed while theRelief Valve is in service

without leakage 

Liquiflo Relief Valve Cross-Sectional Diagram