Line Protection Basics

download Line Protection Basics

of 3

Transcript of Line Protection Basics

  • 7/28/2019 Line Protection Basics

    1/3

    LINE PROTECTION

    Objectives of relay protection

    Protects apparatus in power system

    Protects person & equipment in the surrounding of the powersystem

    Separates faulty parts from the rest of the power system to facilitate the operationof the healthy part of the system.

    FAULT STATISTICS (generally)

    Single phase to ground 80%

    Two phase to ground 10%Phase to phase 5%

    Three phase fault 5%

    The probability of line fault caused by lightening are 2-3 faults /100 km and year.FAULT TYPES

    Transient faults

    Are common on transmission lines ,approximately 80-85%

    Lightning are the most common reason

    Can also be caused by bird , trees ,swinging lines etc..

    Will disappear after short dead interval.

    Persistant fault.

    Can be caused broken conductor fallen down.

    Can be by tree falling on line

    Must be repaired before normal service

    MAIN REQUIREMENTS ON LINE PROTECTION

    Speed

    Sensitivity

    Selectivity

    Dependability

    Security

    MEASURING PRINCIPLES

    Over current protection

    Differential protection

    Phase comparison

    Distance protection

    OVER CURRENT PROTECTION

    Are normally used in radial networks with system voltage below 70KV where

    relatively long operating time is acceptable. On transmission line directional or non directional relays are used as back up

    protection

    The reach of overcurrent relay is function of source impedance & fault impedance

    which varies considerably making it difficult to get fast & selective tripping.

    PILOT WIRE DIFFERENTIAL PROTECTION

    Pilot wire can be in soil or on towers

    GETCO (TR) ZONE GONDAL

  • 7/28/2019 Line Protection Basics

    2/3

    The resistance in the wire will limit the use on longer lines .the use is mostly

    restricted to distance upto 10 km

    PHASE COMPARISION

    phase comparision relay compare the angle difference between the two currents at

    both ends of the line.

    The measured time for zero crossing is transmitted to the other endDISTANCE PROTECTION

    Power lines have impedance of value 0.3-o.4 ohm/km & normal angles of 60-85

    degrees in 50 Hz system

    Measurement base on impedance is immune to source impedance & other

    problems ,permits fast and selective tripping.

    Z=V/I

    Switched scheme

    This type of schemes consists of start relay to select the measuring loop to the

    single measuring relay & range of same measuring unit is extended to Z2 &Z3

    after time delay by switching. Non switch scheme

    This type of scheme has a measuring element for each measuring loop & for each

    zone

    Types of characteristics

    A) self polarized Mho:-self polarized mho charct.is circle & passes through

    origine.it is less prone to power swing, & inherently directional.

    B) cross polarized mho:-this charact. is also suitable for short length lines as it

    provides enhanced resistive coverage.

    C) offset mho:-the offset mho relay encloses origin & provides some coverage

    for faults in reverse direction this type of reverse offset is used to for Z3 to give

    back protection to busbar.

    D) Reactance :- it is represented by line parallel to resistive axis.It is ideally

    suitable for short length line. It is non directional hence required to use withdirectional characteristic.

    E) Lenticular :-its shape is like lens it provide required coverage of impedance &

    restricted coverage of resistance.this type of charact. is suitable for long & heavily

    loaded line.

    F) Quadrilateral :-its shape is quadrilateral & it is directional both reactive &

    resistive reaches are independently adjustable.it is ideally suitable for short length

    line.

    Basic setting philosophy

    Zone 1: 80% of protected line

    Zone 2: 100% of protected line+ 50% of adjacent shortest line

    Zone 3: 100% of protected line+100% of adjacent longest line

    Zone4 reverse: 10% of zone 3 forward to cover bus etc..

    Check should be made for reach to transformer adjacent to protected line section

    Switch on to fault

    GETCO (TR) ZONE GONDAL

  • 7/28/2019 Line Protection Basics

    3/3

    When energizing a power line into a forgotten earthing no measuring voltage

    available & if it is at opp end then it will trip in Z2 time in such situation

    protection may not operate & in other case operation will be delayed.

    A special SOTF function is provided so as relay to operate in Z1 time Different

    principles can be used ,from one phase current to unidirectional impedance

    measuring Power swing blocking

    A power swing can be started by sudden load change due to fault in the network

    During power swing 3phase symmetrical V & I variation occurs.

    It is either recoverable or non recoverable

    Normally tripping is prevented if it enter upto Z2 & remain there for max 2 sec

    Tripping is allowed if it enters Z1 locus.

    Vt fuse failure

    As Z=V/I hence if VT fuse blows Z will be zero and distance relay may trip

    A special function VT fuse failure prevent tripping in such condition

    Carrier intertrip As Z1 covers 80% of line , various carrier tripping schemes are used to protect

    remaining portion of line in almost Z1 time .

    Some type of schemes are as under

    Permissive underreach transfer trip(PUR) generally this scheme is utilized in our

    network.

    Permissive overreach transfer trip(POR) generally utilized for short length line

    upto 10 kms.

    Blocking

    GETCO (TR) ZONE GONDAL