Relion ® 670 series Line distance protection REL670 Pre-configured Product Guide

Transcript of Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670...

Page 1: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Relion® 670 series

Line distance protection REL670Pre-configuredProduct Guide

Page 2: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Contents

1. Application...........................................................3

2. Available functions...............................................5

3. Differential protection.........................................15

4. Impedance protection........................................15

5. Current protection..............................................17

6. Voltage protection..............................................19

7. Frequency protection.........................................20

8. Multipurpose protection.....................................20

9. Secondary system supervision..........................21

10. Control...............................................................21

11. Scheme communication....................................23

12. Logic..................................................................25

13. Monitoring.........................................................26

14. Metering............................................................28

15. Basic IED functions...........................................28

16. Human machine interface.................................29

17. Station communication ....................................29

18. Remote communication....................................30

19. Hardware description........................................31

20. Connection diagrams........................................34

21. Technical data...................................................43

22. Ordering..........................................................100

Disclaimer

The information in this document is subject to change without notice and should not be construed as a commitment by ABB AB. ABB AB assumesno responsibility for any errors that may appear in this document.

© Copyright 2010 ABB AB.

All rights reserved.

Trademarks

ABB and Relion are registered trademarks of ABB Group. All other brand or product names mentioned in this document may be trademarks orregistered trademarks of their respective holders.

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

2 ABB

Page 3: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

1. Application

REL670 is used for the protection, controland monitoring of overhead lines and cablesin solidly earthed networks. The IED can beused up to the high voltage levels. It issuitable for the protection of heavily loadedlines and multi-terminal lines where therequirement for tripping is one-, two-, and/orthree-phase. The IED is also suitable as back-up protection of power transformers, reactorsand so on.

The full scheme distance protection providesprotection of power lines with highsensitivity and low requirement on remoteend communication. The five zones havefully independent measuring and settingwhich gives high flexibility for all types oflines.

The modern technical solution offers fastoperating time of typically 1.5 cycles.

The REL670 also includes an alternative forused on not solidly earthed networks. Itincludes Phase Preference Logic to select andtrip only one line at cross-country faults.

The autoreclose for single-, two-, and/or three-phase reclose includes priority features formulti-breaker arrangements. It co-operateswith the synchrocheck function with high-speed or delayed reclosing.

A high impedance differential protection canbe used to protect T-feeders or line reactors.

High set instantaneous phase and earthovercurrent, four step directional or non-directional delayed phase and earthovercurrent, sensitive earth fault for notdirect earthed systems, thermal overload andtwo step under and overvoltage protectionare examples of the available functionsallowing the user to fulfill any applicationrequirement.

The distance and earth fault protection cancommunicate with remote end in anyteleprotection communication scheme. Withthe included remote communication,following the IEEE C37.94 standard, 6 x 32

channels for intertrip and binary signals areavailable per LDCM communication modulein the communication between the IEDs.

The IED can also be provided with full baycontrol and interlocking functionalityincluding co-operation with the synchrocheckfunction to allow integration of the main orback-up control.

Out of Step function is available to separatepower system sections close to electricalcentre at occurring out of step.

The advanced logic capability, where the userlogic is prepared with a graphical tool, allowsspecial applications such as automaticopening of disconnectors in multi-breakerarrangements, closing of breaker rings, loadtransfer logics and so on. The graphicalconfiguration tool with delay mode, ensuressimple and fast testing and commissioning.

Disturbance recording and fault locator areavailable to allow independent post-faultanalysis after primary disturbances.

Serial data communication is via opticalconnections to ensure immunity againstdisturbances.

The wide application flexibility makes thisproduct an excellent choice for both newinstallations and the refurbishment of existinginstallations.

Five packages has been defined for followingapplications:

• Single-breaker (double or single bus)with three phase tripping for high ohmicand resonance earthed systems (A21)

• Single-breaker (double or single bus)with three phase tripping (A31)

• Single-breaker (double or single bus)with single phase tripping (A32)

• Multi-breaker (one-and a half or ring)with three phase tripping (B31)

• Multi-breaker (one-and a half or ring)with single phase tripping (B32)

The packages are configured and ready fordirect use. Optional functions are notconfigured but a maximum configuration

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

Revision: -

ABB 3

Page 4: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

with all optional functions are available astemplate in the graphical configuration tool.Analogue and tripping IO has been pre-defined for basic use.

Add binary I/O as required for yourapplication at ordering. Other signals need tobe applied as required for each application.

For details on included basic functions referto section

"Basic IED functions"

The application on a high ohmic earthedsystem is shown in figure 1.

Refer to the Application manual for pre-configured analog and binary IO.

The applications are shown in figures 1 and2for single resp. multi-breaker arrangement.

Z <55

SC/VCO->I

3I>44

IN>44

I->O

CLOSE

TRIP

BUS A

BUS B

21

51/67

51N/67N

79 25

94/86

3I>50BF

TRIP BUSBAR

en05000276.vsd

3U>59

3U<27

2

22

2

IEC05000276-1 V1 EN

Figure 1. The single breaker packages for single- and three phase tripping typical arrangementfor one protection sub-system is shown here.

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

4 ABB

Page 5: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Z <55

SC/VCO->I

3I>44

IN>44

3U>22

3U<22

I->O

CLOSE

TRIP

BUS A

21

51/67

51N/67N

59

27

79 25

94/86

3I>50BF

TRIP BUSBAR & CB2

3I>50BF

S

SC/VCO->I

I->O CLO

SE

TRIP

25

94/86

79

IEC05000317-2-en.vsd

TRIP

CB1/3

CB1

CB2

IEC05000317 V2 EN

Figure 2. The multi breaker packages for single- and three phase tripping typical arrangementfor one protection sub-system is shown here. Auto-reclose, Synchrocheck and Breakerfailure functions are included for each of the two breakers.

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 5

Page 6: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

2. Available functions

Main protection functions

2 = number of basic instances

3-A03 = optional function included in packages A03 (refer to ordering details)

IEC 61850 ANSI Function description Line Distance

REL670 (

A21)

REL670 (

A31)

REL670 (

B31)

REL670 (

A32)

REL670 (

B32)

Differential protection

HZPDIF 87 1Ph high impedance differentialprotection

3-A02

3-A02

3-A02

3-A02

Impedance protection

ZMQPDIS,ZMQAPDIS

21 Distance protection zone,quadrilateral characteristic

5 5 5 5 5

ZDRDIR 21D Directional impedancequadrilateral

1 1 1 1 1

ZMCAPDIS Additional distance measuringzone, quadrilateral characteristic

1

FDPSPDIS 21 Phase selection, quadrilateralcharacteristic with fixed angle

2 2 2 2 2

ZMRPSB 78 Power swing detection 1 1 1 1

ZMRPSL Power swing logic 1-B03

1-B03

1-B03

1-B03

PSPPPAM 78 Pole slip/out-of-step protection 1-B21

1-B21

1-B21

1-B21

ZCVPSOF Automatic switch onto faultlogic, voltage and current based

1 1 1 1 1

PPLPHIZ Phase preference logic 1

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

6 ABB

Page 7: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Back-up protection functions

IEC 61850 ANSI Function description Line Distance

REL670 (A

21)

REL670 (A

31)

REL670 (B

31)

REL670 (A

32)

REL670 (B

32)

Current protection

PHPIOC 50 Instantaneous phaseovercurrent protection

1 1 1 1 1

OC4PTOC 51_67 Four step phase overcurrentprotection

1 1 1 1 1

EFPIOC 50N Instantaneous residualovercurrent protection

1 1 1 1 1

EF4PTOC 51N_67N

Four step residual overcurrentprotection

1 1 1 1

NS4PTOC 46I2 Four step directional negativephase sequence overcurrentprotection

1-C41

1-C41

1-C41

1-C41

SDEPSDE 67N Sensitive directional residualovercurrent and powerprotection

1 1-C16

1-C16

1-C16

1-C16

LPTTR 26 Thermal overload protection,one time constant

1 1 1 1 1

CCRBRF 50BF Breaker failure protection 1 1 2 1 2

STBPTOC 50STB Stub protection 1 1

CCRPLD 52PD Pole discordance protection 1 2 1 2

GUPPDUP 37 Directional underpowerprotection

1-C17

1-C17

1-C17

1-C17

GOPPDOP 32 Directional overpowerprotection

1-C17

1-C17

1-C17

1-C17

BRCPTOC 46 Broken conductor check 1 1 1 1 1

Voltage protection

UV2PTUV 27 Two step undervoltageprotection

1 1 1 1

OV2PTOV 59 Two step overvoltageprotection

1 1 1 1

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 7

Page 8: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

IEC 61850 ANSI Function description Line Distance

REL670 (

A21)

REL670 (

A31)

REL670 (

B31)

REL670 (

A32)

REL670 (

B32)

ROV2PTOV 59N Two step residual overvoltageprotection

1 1 1 1 1

OEXPVPH 24 Overexcitation protection 1-D03

1-D03

1-D03

1-D03

VDCPTOV 60 Voltage differential protection 2 2 2 2

LOVPTUV 27 Loss of voltage check 1 1 1 1 1

Frequency protection

SAPTUF 81 Underfrequency protection 2-E02 2-E02 2-E02 2-E02

SAPTOP 81 Overfrequency protection 2-E02 2-E02 2-E02 2-E02

SAPFRC 81 Rate-of-change frequencyprotection

2-E02 2-E02 2-E02 2-E02

Multipurpose protection

CVGAPC General current and voltageprotection

1 4-F01 4-F01 4-F01 4-F01

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

8 ABB

Page 9: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Control and monitoring functions

IEC 61850 ANSI Function description Line Distance

REL670 (

A21)

REL670 (

A31)

REL670 (

B31)

REL670 (

A32)

REL670 (

B32)

Control

SESRSYN 25 Synchrocheck, energizing checkand synchronizing

1 1 2 1 2

SMBRREC 79 Autorecloser 1 1-B,1-

H04

2-B,2-

H05

1-B,1-

H04

2-B,2-

H05

APC8 3 Apparatus control for singlebay, max 8 apparatuses (1CB)incl. interlocking

1-H07

1-H07

1-H07

APC15 3 Apparatus control for singlebay, max 15apparatuses (2CBs)incl. interlocking

1-H08

1-H08

QCBAY Apparatus control 1 1 1 1 1

LocalRemote

Handling of LRswitch positions 1 1 1 1 1

LocRemControl

LHMI control of PSTO 1 1 1 1 1

SLGGIO Logic rotating switch forfunction selection and LHMIpresentation

15 15 15 15 15

VSGGIO Selector mini switch 20 20 20 20 20

DPGGIO IEC61850 genericcommunication I/O functions

16 16 16 16 16

SPC8GGIO Single pole generic control 8signals

5 5 5 5 5

AutomationBits

AutomationBits, commandfunction for DNP3.0

3 3 3 3 3

Single command, 16 signals 4 4 4 4 4

Secondary system supervision

CCSRDIF 87 Current circuit supervision 1 2 1 2

SDDRFUF Fuse failure supervision 1 3 3 3 3

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 9

Page 10: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

IEC 61850 ANSI Function description Line Distance

REL670 (

A21)

REL670 (

A31)

REL670 (

B31)

REL670 (

A32)

REL670 (

B32)

Logic

SMPPTRC 94 Tripping logic 1 1 2 1 2

TMAGGIO Trip matrix logic 12 12 12 12 12

Configuration logic blocks 40 40 40 40 40

Fixed signal function blocks 1 1 1 1 1

B16I Boolean 16 to Integerconversion with Logic Noderepresentation

16 16 16 16 16

B16IFCVI Boolean 16 to Integerconversion with Logic Noderepresentation

16 16 16 16 16

IB16 Integer to Boolean 16conversion with Logic Noderepresentation

16 16 16 16 16

IB16FVCB Integer to Boolean 16conversion with Logic Noderepresentation

16 16 16 16 16

Monitoring

CVMMXN Measurements 6/10/6

6/10/6

6/10/6

6/10/6

6/10/6

CNTGGIO Event counter 5 5 5 5 5

Event Event function 20 20 20 20 20

DRPRDRE Disturbance report 1 1 1 1 1

SPGGIO IEC61850 genericcommunication I/O functions

64 64 64 64 64

SP16GGIO IEC61850 genericcommunication I/O functions16 inputs

16 16 16 16 16

MVGGIO IEC61850 genericcommunication I/O functions

24 24 24 24 24

BSStartReport

Logical signal status report 3 3 3 3 3

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

10 ABB

Page 11: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

IEC 61850 ANSI Function description Line Distance

REL670 (

A21)

REL670 (

A31)

REL670 (

B31)

REL670 (

A32)

REL670 (

B32)

RANGE_XP Measured value expander block 66 66 66 66 66

LMBRFLO Fault locator 1 1 1 1 1

Metering

PCGGIO Pulse-counter logic 16 16 16 16 16

ETPMMTR Function for energy calculationand demand handling

6 6 6 6 6

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 11

Page 12: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Designed to communicate

IEC 61850 ANSI Function description Line Distance

REL670 (

A21)

REL670 (

A31)

REL670 (

B31)

REL670 (

A32)

REL670 (

B32)

Station communication

SPA communication protocol 1 1 1 1 1

LON communication protocol 1 1 1 1 1

IEC60870-5-103 communicationprotocol

20/1 20/1 20/1 20/1 20/1

Operation selection betweenSPA and IEC60870-5-103 for SLM

1 1 1 1 1

DNP3.0 for TCP/IP and EIA-485communication protocol

1 1 1 1 1

DNP3.0 fault records for TCP/IPand EIA-485 communicationprotocol

1 1 1 1 1

Redundant station buscommunication IEC61850-8-1,PRP

1 1 1 1 1

Parameter setting function forIEC61850

1 1 1 1 1

IntlReceive Horizontal communication viaGOOSE for interlocking

59 59 59 59 59

Goose binary receive 10 10 10 10 10

Multiple command and transmit 60/10

60/10

60/10

60/10

60/10

Ethernet configuration of links 1 1 1 1 1

DUODRV Duo driver configuration 1-P01 1-P01 1-P01 1-P01 1-P01

Remote communication

Binary signal transfer receive/transmit

6/36 6/36 6/36 6/36 6/36

Transmission of analog datafrom LDCM

1 1 1 1 1

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

12 ABB

Page 13: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

IEC 61850 ANSI Function description Line Distance

REL670 (

A21)

REL670 (

A31)

REL670 (

B31)

REL670 (

A32)

REL670 (

B32)

Receive binary status fromremote LDCM

6/3/3 6/3/3 6/3/3 6/3/3 6/3/3

Scheme communication

ZCPSCH 85 Scheme communication logicfor distance or overcurrentprotection

1 1 1 1 1

ZC1PPSCH 85 Phase segregated schemecommunication logic fordistance protection

1-B05

1-B05

ZCRWPSCH 85 Current reversal and weak-endinfeed logic for distanceprotection

1 1 1 1 1

ZC1WPSCH Current reversal and weak-endinfeed logic for phasesegregated communication

1-B05

1-B05

ZCLCPLAL Local acceleration logic 1 1 1 1 1

ECPSCH 85 Scheme communication logicfor residual overcurrentprotection

1 1 1 1

ECRWPSCH 85 Current reversal and weak-endinfeed logic for residualovercurrent protection

1 1 1 1

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 13

Page 14: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Basic IED functions

IEC 61850 Function description

Basic functions included in all products

IntErrorSig Self supervision with internal event list 1

TIME Time and synchronization error 1

TimeSynch Time synchronization 1

ActiveGroup Parameter setting groups 1

Test Test mode functionality 1

ChangeLock Change lock function 1

TerminalID IED identifiers 1

Productinfo Product information 1

MiscBaseCommon Misc Base Common 1

IEDRuntimeComp IED Runtime Comp 1

RatedFreq Rated system frequency 1

SMBI Signal Matrix for binary inputs 40

SMBO Signal Matrix for binary outputs 40

SMMI Signal Matrix for mA inputs 4

SMAI Signal Matrix for analog inputs 24

Sum3Ph Summation block 3 phase 12

LocalHMI Parameter setting function for HMI in PCM600 1

LocalHMI Local HMI signals 1

AuthStatus Authority status 1

AuthorityCheck Authority check 1

AccessFTP FTP access with password 1

SPACommMap SPA communication mapping 1

DOSFRNT Denial of service, frame rate control for front port 1

DOSOEMAB Denial of service, frame rate control for OEM port AB 1

DOSOEMCD Denial of service, frame rate control for OEM port CD 1

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

14 ABB

Page 15: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

3. Differential protection

1Ph High impedance differentialprotection HZPDIF

The 1Ph High impedance differentialprotection (HZPDIF) function can be usedwhen the involved CT cores have the sameturn ratio and similar magnetizingcharacteristic. It utilizes an externalsummation of the phases and neutral currentand a series resistor and a voltage dependentresistor externally to the IED.

4. Impedance protection

Distance measuring zone,quadrilateral characteristicZMQPDIS, ZMQAPDIS

The line distance protection is a five zone fullscheme protection with three fault loops forphase-to-phase faults and three fault loopsfor phase-to-earth fault for each of theindependent zones. Individual settings foreach zone in resistive and reactive reachgives flexibility for use as back-up protectionfor transformer connected to overhead linesand cables of different types and lengths.

ZMQPDIS together with Phase selection withload encroachment FDPSPDIS hasfunctionality for load encroachment, whichincreases the possibility to detect highresistive faults on heavily loaded lines.

The independent measurement of impedancefor each fault loop together with a sensitiveand reliable built-in phase selection makesthe function suitable in applications withsingle-phase autoreclosing.

Built-in adaptive load compensationalgorithm prevents overreaching of zone 1 atload exporting end at phase-to-earth faults onheavily loaded power lines.

The distance protection zones can operateindependently of each other in directional

(forward or reverse) or non-directional mode.This makes them suitable, together withdifferent communication schemes, for theprotection of power lines and cables incomplex network configurations, such asparallel lines, multi-terminal lines, and so on.

Distance measuring zone,quadrilateral characteristic forseries compensated lines ZMCPDIS,ZMCAPDIS

The line distance protection is a zone fullscheme protection with three fault loops forphase-to-phase faults and three fault loopsfor phase-to-earth fault for each of theindependent zones. Individual settings foreach zone resistive and reactive reach giveflexibility for use on overhead lines andcables of different types and lengths.

Quadrilateral characteristic is available.

ZMCPDIS function has functionality for loadencroachment which increases the possibilityto detect high resistive faults on heavilyloaded lines.

en05000034.vsd

R

X

Forwardoperation

Reverseoperation

IEC05000034 V1 EN

Figure 3. Typical quadrilateral distanceprotection zone with loadencroachment function activated

The independent measurement of impedancefor each fault loop together with a sensitiveand reliable built in phase selection makes

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 15

Page 16: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

the function suitable in applications withsingle phase auto-reclosing.

Built-in adaptive load compensationalgorithm for the quadrilateral functionprevents overreaching of zone1 at loadexporting end at phase to earth-faults onheavily loaded power lines.

The distance protection zones can operate,independent of each other, in directional(forward or reverse) or non-directional mode.This makes them suitable, together withdifferent communication schemes, for theprotection of power lines and cables incomplex network configurations, such asparallel lines, multi-terminal lines.

Phase selection, quadrilateralcharacteristic with fixed angleFDPSPDIS

The operation of transmission networkstoday is in many cases close to the stabilitylimit. Due to environmental considerations,the rate of expansion and reinforcement ofthe power system is reduced, for example,difficulties to get permission to build newpower lines. The ability to accurately andreliably classify the different types of fault, sothat single pole tripping and autoreclosingcan be used plays an important role in thismatter. Phase selection, quadrilateralcharacteristic with fixed angle FDPSPDIS isdesigned to accurately select the proper faultloop in the distance function dependent onthe fault type.

The heavy load transfer that is common inmany transmission networks may make faultresistance coverage difficult to achieve.Therefore, FDPSPDIS has a built-in algorithmfor load encroachment, which gives thepossibility to enlarge the resistive setting ofboth the phase selection and the measuringzones without interfering with the load.

The extensive output signals from the phaseselection gives also important informationabout faulty phase(s), which can be used forfault analysis.

A current-based phase selection is alsoincluded. The measuring elementscontinuously measure three phase currentsand the residual current and, compare themwith the set values.

Power swing detection ZMRPSB

Power swings may occur after disconnectionof heavy loads or trip of big generation plants.

Power swing detection function (ZMRPSB) isused to detect power swings and initiateblock of selected distance protection zones.Occurrence of earth-fault currents during apower swing can block ZMRPSB function toallow fault clearance.

Power swing logic ZMRPSL

Additional logic is available to secure trippingfor faults during power swings and preventtripping at power swings started by a fault inthe network.

Pole slip protection PSPPPAM

Sudden events in an electrical power systemsuch as large changes in load, faultoccurrence or fault clearance, can causepower oscillations referred to as powerswings. In a non-recoverable situation, thepower swings become so severe that thesynchronism is lost, a condition referred to aspole slipping. The main purpose of the poleslip protection (PSPPPAM) is to detect,evaluate, and take the required action forpole slipping occurrences in the powersystem. The electrical system parts swingingto each other can be separated with the line/sclosest to the centre of the power swingallowing the two systems to be stable asseparated islands.

Automatic switch onto fault logic,voltage and current based ZCVPSOF

Automatic switch onto fault logic (ZCVPSOF)is a function that gives an instantaneous tripat closing of breaker onto a fault. A dead linedetection check is provided to activate thefunction when the line is dead.

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

16 ABB

Page 17: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Phase preference logic PPLPHIZ

The optional phase preference logic mainpurpose is to provide a selective tripping forcross-country faults in isolated or highimpedance-earthed networks.

5. Current protection

Instantaneous phase overcurrentprotection PHPIOC

The instantaneous three phase overcurrentfunction has a low transient overreach andshort tripping time to allow use as a high setshort-circuit protection function.

Four step phase overcurrentprotection OC4PTOC

The four step phase overcurrent protectionfunction OC4PTOC has an inverse or definitetime delay independent for each stepseparately.

All IEC and ANSI time delayed characteristicsare available together with an optional userdefined time characteristic.

The directional function is voltage polarizedwith memory. The function can be set to bedirectional or non-directional independentlyfor each of the steps.

A 2nd harmonic blocking can be setindividually for each step.

Instantaneous residual overcurrentprotection EFPIOC

The Instantaneous residual overcurrentprotection EFPIOC has a low transientoverreach and short tripping times to allowthe use for instantaneous earth-faultprotection, with the reach limited to less thantypical eighty percent of the line at minimumsource impedance. EFPIOC can be configuredto measure the residual current from the three-phase current inputs or the current from aseparate current input. EFPIOC can beblocked by activating the input BLOCK.

Four step residual overcurrentprotection EF4PTOC

The four step residual overcurrent protectionEF4PTOC has an inverse or definite timedelay independent for each step separately.

All IEC and ANSI time delayed characteristicsare available together with an optional userdefined characteristic.

The directional function is voltage polarized,current polarized or dual polarized.

EF4PTOC can be set directional or non-directional independently for each of the steps.

A second harmonic blocking can be setindividually for each step.

EF4PTOC can be used as main protection forphase-to-earth faults.

EF4PTOC can also be used to provide asystem back-up for example, in the case ofthe primary protection being out of servicedue to communication or voltage transformercircuit failure.

Directional operation can be combinedtogether with corresponding communicationlogic in permissive or blocking teleprotectionscheme. Current reversal and weak-endinfeed functionality are available as well.

EF4PTOC can be configured to measure theresidual current from the three-phase currentinputs or the current from a separate currentinput.

Four step negative sequenceovercurrent protection NS4PTOC

Four step negative sequence overcurrentprotection (NS4PTOC) has an inverse ordefinite time delay independent for each stepseparately.

All IEC and ANSI time delayed characteristicsare available together with an optional userdefined characteristic.

The directional function is voltage polarizedor dual polarized.

NS4PTOC can be set directional or non-directional independently for each of the steps.

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 17

Page 18: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

NS4PTOC can be used as main protection forunsymmetrical fault; phase-phase shortcircuits, phase-phase-earth short circuits andsingle phase earth faults.

NS4PTOC can also be used to provide asystem back-up for example, in the case ofthe primary protection being out of servicedue to communication or voltage transformercircuit failure.

Directional operation can be combinedtogether with corresponding communicationlogic in permissive or blocking teleprotectionscheme. The same logic as for directionalzero sequence current can be used. Currentreversal and weak-end infeed functionalityare available.

Sensitive directional residualovercurrent and power protectionSDEPSDE

In isolated networks or in networks withhigh impedance earthing, the earth faultcurrent is significantly smaller than the shortcircuit currents. In addition to this, themagnitude of the fault current is almostindependent on the fault location in thenetwork. The protection can be selected touse either the residual current or residualpower component 3U0·3I0·cos j, foroperating quantity with maintained shortcircuit capacity. There is also available onenondirectional 3I0 step and one 3U0overvoltage tripping step.

Thermal overload protection, onetime constant LPTTR

The increasing utilizing of the power systemcloser to the thermal limits has generated aneed of a thermal overload protection alsofor power lines.

A thermal overload will often not be detectedby other protection functions and theintroduction of the thermal overloadprotection can allow the protected circuit tooperate closer to the thermal limits.

The three-phase current measuring protection

has an I2t characteristic with settable timeconstant and a thermal memory.

An alarm level gives early warning to allowoperators to take action well before the lineis tripped.

Breaker failure protection CCRBRF

Breaker failure protection (CCRBRF) ensuresfast back-up tripping of surrounding breakersin case of own breaker failure to open.CCRBRF can be current based, contact based,or adaptive combination between these twoprinciples.

A current check with extremely short resettime is used as check criteria to achieve ahigh security against unnecessary operation.

A contact check criteria can be used wherethe fault current through the breaker is small.

CCRBRF can be single- or three-phaseinitiated to allow use with single phasetripping applications. For the three-phaseversion of CCRBRF the current criteria can beset to operate only if two out of four forexample, two phases or one phase plus theresidual current start. This gives a highersecurity to the back-up trip command.

CCRBRF function can be programmed to givea single- or three-phase re-trip of the ownbreaker to avoid unnecessary tripping ofsurrounding breakers at an incorrectinitiation due to mistakes during testing.

Stub protection STBPTOC

When a power line is taken out of service formaintenance and the line disconnector isopened in multi-breaker arrangements thevoltage transformers will mostly be outsideon the disconnected part. The primary linedistance protection will thus not be able tooperate and must be blocked.

The stub protection STBPTOC covers thezone between the current transformers andthe open disconnector. The three-phaseinstantaneous overcurrent function isreleased from a normally open, NO (b)auxiliary contact on the line disconnector.

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

18 ABB

Page 19: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Pole discordance protectionCCRPLD

This can cause negative and zero sequencecurrents which gives thermal stress onrotating machines and can cause unwantedoperation of zero sequence or negativesequence current functions.

Normally the own breaker is tripped tocorrect such a situation. If the situationpersists the surrounding breaker should betripped to clear the unsymmetrical loadsituation.

The Polediscordance protection functionCCRPLD operates based on information fromauxiliary contacts of the circuit breaker forthe three phases with additional criteria fromunsymmetrical phase current when required.

Directional over/underpowerprotection GOPPDOP/GUPPDUP

The directional over-/under-power protection(GOPPDOP/GUPPDUP) can be usedwherever a high/low active, reactive orapparent power protection or alarming isrequired. The functions can alternatively beused to check the direction of active orreactive power flow in the power system.There are number of applications where suchfunctionality is needed. Some of them are:

• detection of reversed active power flow• detection of high reactive power flow

Each function has two steps with definitetime delay. Reset times for every step can beset as well.

Broken conductor check BRCPTOC

The main purpose of the function Brokenconductor check (BRCPTOC) is the detectionof broken conductors on protected powerlines and cables (series faults). Detection canbe used to give alarm only or trip the linebreaker.

6. Voltage protection

Two step undervoltage protectionUV2PTUV

Undervoltages can occur in the power systemduring faults or abnormal conditions. Twostep undervoltage protection (UV2PTUV)function can be used to open circuit breakersto prepare for system restoration at poweroutages or as long-time delayed back-up toprimary protection.

UV2PTUV has two voltage steps, each withinverse or definite time delay.

Two step overvoltage protectionOV2PTOV

Overvoltages may occur in the power systemduring abnormal conditions, such as, suddenpower loss, tap changer regulating failures,open line ends on long lines.

Two step overvoltage protection OV2PTOVcan be used as open line end detector,normally then combined with directionalreactive over-power function or as systemvoltage supervision, normally then givingalarm only or switching in reactors or switchout capacitor banks to control the voltage.

OV2PTOV has two voltage steps, each ofthem with inverse or definite time delayed.

OV2PTOV has an extremely high reset ratioto allow setting close to system service voltage.

Two step residual overvoltageprotection ROV2PTOV

Residual voltages may occur in the powersystem during earth faults.

Two step residual overvoltage protectionROV2PTOV calculates the residual voltagefrom the three-phase voltage inputtransformers or from a single-phase voltageinput transformer fed from an open delta orneutral point voltage transformer.

ROV2PTOV has two voltage steps, each withinverse or definite time delayed.

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 19

Page 20: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Overexcitation protectionOEXPVPH

When the laminated core of a powertransformer or generator is subjected to amagnetic flux density beyond its designlimits, stray flux will flow into non-laminatedcomponents not designed to carry flux andcause eddy currents to flow. The eddycurrents can cause excessive heating andsevere damage to insulation and adjacentparts in a relatively short time. Overexcitationprotection OEXPVPH has settable inverseoperating curve and independent alarm stage.

Voltage differential protectionVDCPTOV

A voltage differential monitoring function isavailable. It compares the voltages from twothree phase sets of voltage transformers andhas one sensitive alarm step and one tripstep. It can be used to supervise the voltagefrom two fuse groups or two different voltagetransformers fuses as a fuse/MCB supervisionfunction.

Loss of voltage check LOVPTUV

Loss of voltage check (LOVPTUV) is suitablefor use in networks with an automatic systemrestoration function. LOVPTUV issues a three-pole trip command to the circuit breaker, ifall three phase voltages fall below the setvalue for a time longer than the set time andthe circuit breaker remains closed.

7. Frequency protection

Underfrequency protection SAPTUF

Underfrequency occurs as a result of lack ofgeneration in the network.

Underfrequency protection SAPTUF is usedfor load shedding systems, remedial actionschemes, gas turbine startup and so on.

SAPTUF is provided with an under voltageblocking.

The operation may be based on single-phase,phase-to-phase or positive-sequence voltagemeasurement.

Overfrequency protection SAPTOF

Overfrequency protection function SAPTOF isapplicable in all situations, where reliabledetection of high fundamental power systemfrequency is needed.

Overfrequency occurs at sudden load dropsor shunt faults in the power network. Closeto the generating plant, generator governorproblems can also cause over frequency.

SAPTOF is used mainly for generationshedding and remedial action schemes. It isalso used as a frequency stage initiating loadrestoring.

SAPTOF is provided with an undervoltageblocking. The operation is based on single-phase, phase-to-phase or positive-sequencevoltage measurement.

Rate-of-change frequencyprotection SAPFRC

Rate-of-change frequency protection function(SAPFRC) gives an early indication of a maindisturbance in the system. SAPFRC can beused for generation shedding, load shedding,remedial action schemes. SAPFRC candiscriminate between positive or negativechange of frequency.

SAPFRC is provided with an undervoltageblocking. The operation may be based onsingle-phase, phase-to-phase or positive-sequence voltage measurement.

8. Multipurposeprotection

General current and voltageprotection CVGAPC

The General current and voltage protection(CVGAPC) can be utilized as a negativesequence current protection detecting

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

20 ABB

Page 21: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

unsymmetrical conditions such as open phaseor unsymmetrical faults.

CVGAPC can also be used to improve phaseselection for high resistive earth faults,outside the distance protection reach, for thetransmission line. Three functions are used,which measures the neutral current and eachof the three phase voltages. This will give anindependence from load currents and thisphase selection will be used in conjunctionwith the detection of the earth fault from thedirectional earth fault protection function.

9. Secondary systemsupervision

Current circuit supervisionCCSRDIF

Open or short circuited current transformercores can cause unwanted operation of manyprotection functions such as differential,earth-fault current and negative-sequencecurrent functions.

It must be remembered that a blocking ofprotection functions at an occurrence of openCT circuit will mean that the situation willremain and extremely high voltages willstress the secondary circuit.

Current circuit supervision (CCSRDIF)compares the residual current from a threephase set of current transformer cores withthe neutral point current on a separate inputtaken from another set of cores on thecurrent transformer.

A detection of a difference indicates a fault inthe circuit and is used as alarm or to blockprotection functions expected to giveunwanted tripping.

Fuse failure supervision SDDRFUF

The aim of the fuse failure supervisionfunction (SDDRFUF) is to block voltagemeasuring functions at failures in thesecondary circuits between the voltage

transformer and the IED in order to avoidunwanted operations that otherwise mightoccur.

The fuse failure supervision function basicallyhas two different algorithms, negativesequence and zero sequence based algorithmand an additional delta voltage and deltacurrent algorithm.

The negative sequence detection algorithm isrecommended for IEDs used in isolated orhigh-impedance earthed networks. It is basedon the negative-sequence measuringquantities, a high value of voltage 3U2

without the presence of the negative-sequence current 3I2.

The zero sequence detection algorithm isrecommended for IEDs used in directly orlow impedance earthed networks. It is basedon the zero sequence measuring quantities, ahigh value of voltage 3U0 without the

presence of the residual current 3I0.

A criterion based on delta current and deltavoltage measurements can be added to thefuse failure supervision function in order todetect a three phase fuse failure, which inpractice is more associated with voltagetransformer switching during stationoperations.

For better adaptation to system requirements,an operation mode setting has beenintroduced which makes it possible to selectthe operating conditions for negativesequence and zero sequence based function.The selection of different operation modesmakes it possible to choose differentinteraction possibilities between the negativesequence and zero sequence based algorithm.

10. Control

Synchronizing, synchrocheck andenergizing check SESRSYN

The Synchronizing function allows closing ofasynchronous networks at the correct

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 21

Page 22: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

moment including the breaker closing time.The systems can thus be reconnected after anautoreclose or manual closing, whichimproves the network stability.

Synchrocheck, energizing check (SESRSYN)function checks that the voltages on bothsides of the circuit breaker are insynchronism, or with at least one side deadto ensure that closing can be done safely.

SESRSYN function includes a built-in voltageselection scheme for double bus and 1½breaker or ring busbar arrangements.

Manual closing as well as automatic reclosingcan be checked by the function and can havedifferent settings.

For systems which are running asynchronousa synchronizing function is provided. Themain purpose of the synchronizing functionis to provide controlled closing of circuitbreakers when two asynchronous systems aregoing to be connected. It is used for slipfrequencies that are larger than those forsynchrocheck and lower than a set maximumlevel for the synchronizing function.

Autorecloser SMBRREC

The autorecloser (SMBRREC) functionprovides high-speed and/or delayed auto-reclosing for single or multi-breakerapplications.

Up to five reclosing attempts can beprogrammed. The first attempt can be single-,two and/or three phase for single phase ormulti-phase faults respectively.

Multiple autoreclosing functions are providedfor multi-breaker arrangements. A prioritycircuit allows one circuit breaker to close firstand the second will only close if the faultproved to be transient.

Each autoreclosing function can beconfigured to co-operate with a synchrocheckfunction.

Apparatus control APC

The apparatus control is a function forcontrol and supervision of circuit breakers,disconnectors and earthing switches within a

bay. Permission to operate is given afterevaluation of conditions from other functionssuch as interlocking, synchrocheck, operatorplace selection and external or internalblockings.

Features in the apparatus control function:

• Select-Execute principle to give highreliability

• Selection function to prevent simultaneousoperation

• Selection and supervision of operator place• Command supervision• Block/deblock of operation• Block/deblock of updating of position

indications• Substitution of position indications• Overriding of interlocking functions• Overriding of synchrocheck• Operation counter• Suppression of Mid position

Two types of command models can be used:

• Direct with normal security• SBO (Select-Before-Operate) with enhanced

security

Normal security means that only thecommand is evaluated and the resultingposition is not supervised. Enhanced securitymeans that the command is evaluated with anadditional supervision of the status value ofthe control object. The command securitywith enhanced security is always terminatedby a CommandTermination service primitive.

Control operation can be performed from thelocal HMI under authority control if so defined.

Interlocking

The interlocking function blocks thepossibility to operate primary switchingdevices, for instance when a disconnector isunder load, in order to prevent materialdamage and/or accidental human injury.

Each apparatus control function hasinterlocking modules included for differentswitchyard arrangements, where eachfunction handles interlocking of one bay. Theinterlocking function is distributed to each

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

22 ABB

Page 23: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

IED and is not dependent on any centralfunction. For the station-wide interlocking,the IEDs communicate via the system-wideinterbay bus (IEC 61850-8-1) or by using hardwired binary inputs/outputs. The interlockingconditions depend on the circuitconfiguration and apparatus position status atany given time.

For easy and safe implementation of theinterlocking function, the IED is deliveredwith standardized and tested softwareinterlocking modules containing logic for theinterlocking conditions. The interlockingconditions can be altered, to meet thecustomer’s specific requirements, by addingconfigurable logic by means of the graphicalconfiguration tool.

Logic rotating switch for functionselection and LHMI presentationSLGGIO

The logic rotating switch for functionselection and LHMI presentation function(SLGGIO) (or the selector switch functionblock) is used to get a selector switchfunctionality similar with the one provided bya hardware selector switch. Hardwareselector switches are used extensively byutilities, in order to have different functionsoperating on pre-set values. Hardwareswitches are however sources formaintenance issues, lower system reliabilityand extended purchase portfolio. The virtualselector switches eliminate all these problems.

Selector mini switch VSGGIO

Selector mini switch (VSGGIO) functionblock is a multipurpose function used in theconfiguration tool in PCM600 for a variety ofapplications, as a general purpose switch.

VSGGIO can be controlled from the menu orfrom a symbol on the single line diagram(SLD) on the local HMI.

Single point generic control 8signals SPC8GGIO

The Single point generic control 8 signals(SPC8GGIO) function block is a collection of8 single point commands, designed to bring

in commands from REMOTE (SCADA) tothose parts of the logic configuration that donot need complicated function blocks thathave the capability to receive commands (forexample, SCSWI). In this way, simplecommands can be sent directly to the IEDoutputs, without confirmation. Confirmation(status) of the result of the commands issupposed to be achieved by other means,such as binary inputs and SPGGIO functionblocks.

Single command, 16 signals

The IEDs can receive commands either froma substation automation system or from thelocal HMI. The command function block hasoutputs that can be used, for example, tocontrol high voltage apparatuses or for otheruser defined functionality.

11. Schemecommunication

Scheme communication logic fordistance or overcurrent protectionZCPSCH

To achieve instantaneous fault clearance forall line faults, a scheme communication logicis provided. All types of communicationschemes for example, permissiveunderreaching, permissive overreaching,blocking, unblocking, intertrip are available.

The built-in communication module (LDCM)can be used for scheme communicationsignaling when included.

Phase segregated schemecommunication logic for distanceprotection ZC1PPSCH

Communication between line ends is used toachieve fault clearance for all faults on apower line. All possible types ofcommunication schemes for example,permissive underreach, permissive overreachand blocking schemes are available. To

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 23

Page 24: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

manage problems with simultaneous faultson parallel power lines phase segregatedcommunication is needed. This will thenreplace the standard Scheme communicationlogic for distance or Overcurrent protection(ZCPSCH) on important lines where threecommunication channels (in each subsystem)are available for the distance protectioncommunication.

The main purpose of the Phase segregatedscheme communication logic for distanceprotection (ZC1PPSCH) function is tosupplement the distance protection functionsuch that:

• fast clearance of faults is also achieved atthe line end for which the faults are onthe part of the line not covered by itsunderreaching zone.

• correct phase selection can bemaintained to support single-poletripping for faults occurring anywhere onthe entire length of a double circuit line.

To accomplish this, three separatecommunication channels, that is, one perphase, each capable of transmitting a signalin each direction is required.

ZC1PPSCH can be completed with thecurrent reversal and WEI logic for phasesegregated communication, when foundnecessary in Blocking and Permissiveoverreaching schemes.

Current reversal and weak-endinfeed logic for distance protectionZCRWPSCH

The current reversal function is used toprevent unwanted operations due to currentreversal when using permissive overreachprotection schemes in application withparallel lines when the overreach from thetwo ends overlap on the parallel line.

The weak-end infeed logic is used in caseswhere the apparent power behind theprotection can be too low to activate thedistance protection function. When activated,received carrier signal together with localunder voltage criteria and no reverse zone

operation gives an instantaneous trip. Thereceived signal is also echoed back toaccelerate the sending end.

Three phase or phase segregated schemelogic is available.

Current reversal and weak-endinfeed logic for phase segregatedcommunication ZC1WPSCH

Current reversal and weak-end infeed logicfor phase segregated communication(ZC1WPSCH) function is used to preventunwanted operations due to current reversalwhen using permissive overreach protectionschemes in application with parallel lineswhen the overreach from the two endsoverlaps on the parallel line.

The weak-end infeed logic is used in caseswhere the apparent power behind theprotection can be too low to activate thedistance protection function. When activated,received carrier signal together with localunder voltage criteria and no reverse zoneoperation gives an instantaneous trip. Thereceived signal is also echoed back toaccelerate the sending end.

Local acceleration logic ZCLCPLAL

To achieve fast clearing of faults on thewhole line, when no communication channelis available, local acceleration logic(ZCLCPLAL) can be used. This logic enablesfast fault clearing during certain conditions,but naturally, it can not fully replace acommunication channel.

The logic can be controlled either by theautorecloser (zone extension) or by the loss-of-load current (loss-of-load acceleration).

Scheme communication logic forresidual overcurrent protectionECPSCH

To achieve fast fault clearance of earth faultson the part of the line not covered by theinstantaneous step of the residual overcurrentprotection, the directional residualovercurrent protection can be supported witha logic that uses communication channels.

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

24 ABB

Page 25: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

In the directional scheme, information of thefault current direction must be transmitted tothe other line end. With directionalcomparison, a short operates time of theprotection including a channel transmissiontime, can be achieved. This short operatetime enables rapid autoreclosing functionafter the fault clearance.

The communication logic module fordirectional residual current protectionenables blocking as well as permissive under/overreaching schemes. The logic can also besupported by additional logic for weak-endinfeed and current reversal, included inCurrent reversal and weak-end infeed logicfor residual overcurrent protection Currentreversal and weak-end infeed logic forresidual overcurrent protection (ECRWPSCH)function.

Current reversal and weak-endinfeed logic for residualovercurrent protection ECRWPSCH

The Current reversal and weak-end infeedlogic for residual overcurrent protectionECRWPSCH is a supplement to Schemecommunication logic for residual overcurrentprotection ECPSCH.

To achieve fast fault clearing for all earthfaults on the line, the directional earth-faultprotection function can be supported withlogic that uses communication channels.

The 670 series IEDs have for this reasonavailable additions to scheme communicationlogic.

If parallel lines are connected to commonbusbars at both terminals, overreachingpermissive communication schemes can tripunselectively due to fault current reversal.This unwanted tripping affects the healthyline when a fault is cleared on the other line.This lack of security can result in a total lossof interconnection between the two buses. Toavoid this type of disturbance, a fault currentreversal logic (transient blocking logic) canbe used.

Permissive communication schemes forresidual overcurrent protection can basicallyoperate only when the protection in theremote IED can detect the fault. Thedetection requires a sufficient minimumresidual fault current, out from this IED. Thefault current can be too low due to anopened breaker or high-positive and/or zero-sequence source impedance behind this IED.To overcome these conditions, weak-endinfeed (WEI) echo logic is used.

12. Logic

Tripping logic SMPPTRC

A function block for protection tripping isprovided for each circuit breaker involved inthe tripping of the fault. It provides the pulseprolongation to ensure a trip pulse ofsufficient length, as well as all functionalitynecessary for correct co-operation withautoreclosing functions.

The trip function block includes functionalityfor evolving faults and breaker lock-out.

Trip matrix logic TMAGGIO

Trip matrix logic (TMAGGIO) function isused to route trip signals and/or other logicaloutput signals to different output contacts onthe IED.

TMAGGIO output signals and the physicaloutputs are available in PCM600 and thisallows the user to adapt the signals to thephysical tripping outputs according to thespecific application needs.

Fixed signal function block

The Fixed signals function (FXDSIGN)generates a number of pre-set (fixed) signalsthat can be used in the configuration of anIED, either for forcing the unused inputs inother function blocks to a certain level/value,or for creating a certain logic.

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 25

Page 26: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

13. Monitoring

Measurements CVMMXN

The service value function is used to get on-line information from the IED. These servicevalues makes it possible to display on-lineinformation on the local HMI and on theSubstation automation system about:

• measured voltages, currents, frequency,active, reactive and apparent power andpower factor

• the primary and secondary phasors• differential currents, bias currents• positive, negative and zero sequence

currents and voltages• mA, input currents• pulse counters• event counters• measured values and other information

of the different parameters for includedfunctions

• logical values of all binary in- andoutputs and

• general IED information.

Supervision of mA input signals

The main purpose of the function is tomeasure and process signals from differentmeasuring transducers. Many devices used inprocess control represent various parameterssuch as frequency, temperature and DCbattery voltage as low current values, usuallyin the range 4-20 mA or 0-20 mA.

Alarm limits can be set and used as triggers,e.g. to generate trip or alarm signals.

The function requires that the IED isequipped with the mA input module.

Disturbance report DRPRDRE

Complete and reliable information aboutdisturbances in the primary and/or in thesecondary system together with continuousevent-logging is accomplished by thedisturbance report functionality.

Disturbance report DRPRDRE, alwaysincluded in the IED, acquires sampled data of

all selected analog input and binary signalsconnected to the function block that is,maximum 40 analog and 96 binary signals.

Disturbance report functionality is a commonname for several functions:

• Event list• Indications• Event recorder• Trip value recorder• Disturbance recorder• Fault locator

Disturbance report function is characterizedby great flexibility regarding configuration,starting conditions, recording times and largestorage capacity.

A disturbance is defined as an activation ofan input in the AxRADR or BxRBDR functionblocks, which is set to trigger the disturbancerecorder. All signals from start of pre-faulttime to the end of post-fault time will beincluded in the recording.

Every disturbance report recording is savedin the IED in the standard Comtrade format.The same applies to all events, which arecontinuously saved in a ring-buffer. The localHMI is used to get information about therecordings, but the disturbance report filesmay be uploaded to PCM600 and furtheranalysis using the disturbance handling tool.

Event list DRPRDRE

Continuous event-logging is useful formonitoring of the system from an overviewperspective and is a complement to specificdisturbance recorder functions.

The event list logs all binary input signalsconnected to the Disturbance report function.The list may contain of up to 1000 time-tagged events stored in a ring-buffer.

Indications DRPRDRE

To get fast, condensed and reliableinformation about disturbances in theprimary and/or in the secondary system it isimportant to know, for example binarysignals that have changed status during adisturbance. This information is used in the

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

26 ABB

Page 27: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

short perspective to get information via thelocal HMI in a straightforward way.

There are three LEDs on the local HMI(green, yellow and red), which will displaystatus information about the IED and theDisturbance report function (trigged).

The Indication list function shows all selectedbinary input signals connected to theDisturbance report function that havechanged status during a disturbance.

Event recorder DRPRDRE

Quick, complete and reliable informationabout disturbances in the primary and/or inthe secondary system is vital, for example,time tagged events logged duringdisturbances. This information is used fordifferent purposes in the short term (forexample corrective actions) and in the longterm (for example Functional Analysis).

The event recorder logs all selected binaryinput signals connected to the Disturbancereport function. Each recording can containup to 150 time-tagged events.

The event recorder information is availablefor the disturbances locally in the IED.

The event recording information is anintegrated part of the disturbance record(Comtrade file).

Trip value recorder DRPRDRE

Information about the pre-fault and faultvalues for currents and voltages are vital forthe disturbance evaluation.

The Trip value recorder calculates the valuesof all selected analog input signals connectedto the Disturbance report function. The resultis magnitude and phase angle before andduring the fault for each analog input signal.

The trip value recorder information isavailable for the disturbances locally in theIED.

The trip value recorder information is anintegrated part of the disturbance record(Comtrade file).

Disturbance recorder DRPRDRE

The Disturbance recorder function suppliesfast, complete and reliable information aboutdisturbances in the power system. Itfacilitates understanding system behavior andrelated primary and secondary equipmentduring and after a disturbance. Recordedinformation is used for different purposes inthe short perspective (for example correctiveactions) and long perspective (for exampleFunctional Analysis).

The Disturbance recorder acquires sampleddata from all selected analog input andbinary signals connected to the Disturbancereport function (maximum 40 analog and 96binary signals). The binary signals are thesame signals as available under the eventrecorder function.

The function is characterized by greatflexibility and is not dependent on theoperation of protection functions. It canrecord disturbances not detected byprotection functions.

The disturbance recorder information for thelast 100 disturbances are saved in the IEDand the local HMI is used to view the list ofrecordings.

Event function

When using a Substation Automation systemwith LON or SPA communication, time-tagged events can be sent at change orcyclically from the IED to the station level.These events are created from any availablesignal in the IED that is connected to theEvent function (EVENT). The event functionblock is used for LON and SPAcommunication.

Analog and double indication values are alsotransferred through EVENT function.

IEC61850 generic communication I/O function SPGGIO

IEC61850 generic communication I/Ofunctions (SPGGIO) is used to send onesingle logical signal to other systems orequipment in the substation.

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 27

Page 28: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

IEC61850 generic communication I/O functions MVGGIO

IEC61850 generic communication I/Ofunctions (MVGGIO) function is used to sendthe instantaneous value of an analog outputto other systems or equipment in thesubstation. It can also be used inside thesame IED, to attach a RANGE aspect to ananalog value and to permit measurementsupervision on that value.

Measured value expander blockRANGE_XP

The current and voltage measurementsfunctions (CVMMXN, CMMXU, VMMXU andVNMMXU), current and voltage sequencemeasurement functions (CMSQI and VMSQI)and IEC 61850 generic communication I/Ofunctions (MVGGIO) are provided withmeasurement supervision functionality. Allmeasured values can be supervised with foursettable limits that is low-low limit, low limit,high limit and high-high limit. The measurevalue expander block (RANGE_XP) has beenintroduced to be able to translate the integeroutput signal from the measuring functions to5 binary signals that is below low-low limit,below low limit, normal, above high-highlimit or above high limit. The output signalscan be used as conditions in the configurablelogic.

Fault locator LMBRFLO

The accurate fault locator is an essentialcomponent to minimize the outages after apersistent fault and/or to pin-point a weakspot on the line.

The fault locator is an impedance measuringfunction giving the distance to the fault inpercent, km or miles. The main advantage isthe high accuracy achieved by compensatingfor load current.

The compensation includes setting of theremote and local sources and calculation ofthe distribution of fault currents from eachside. This distribution of fault current,together with recorded load (pre-fault)currents, is used to exactly calculate the fault

position. The fault can be recalculated withnew source data at the actual fault to furtherincrease the accuracy.

Especially on heavily loaded long lines(where the fault locator is most important)where the source voltage angles can be up to35-40 degrees apart the accuracy can be stillmaintained with the advanced compensationincluded in fault locator.

14. Metering

Pulse counter logic PCGGIO

Pulse counter (PCGGIO) function countsexternally generated binary pulses, forinstance pulses coming from an externalenergy meter, for calculation of energyconsumption values. The pulses are capturedby the binary input module and then read bythe function. A scaled service value isavailable over the station bus. The specialBinary input module with enhanced pulsecounting capabilities must be ordered toachieve this functionality.

Function for energy calculation anddemand handling ETPMMTR

Outputs from Measurements (CVMMXN)function can be used to calculate energy.Active as well as reactive values arecalculated in import and export direction.Values can be read or generated as pulses.Maximum demand power values are alsocalculated by the function.

15. Basic IED functions

Time synchronization

Use the time synchronization source selectorto select a common source of absolute timefor the IED when it is a part of a protectionsystem. This makes comparison of events and

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

28 ABB

Page 29: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

disturbance data between all IEDs in a stationautomation system possible.

16. Human machineinterface

Human machine interface

The local HMI is divided into zones withdifferent functionality.

• Status indication LEDs.• Alarm indication LEDs, which consist of

15 LEDs (6 red and 9 yellow) with userprintable label. All LEDs are configurablefrom PCM600.

• Liquid crystal display (LCD).• Keypad with push buttons for control

and navigation purposes, switch forselection between local and remotecontrol and reset.

• Isolated RJ45 communication port.

IEC05000056-LITEN V1 EN

Figure 4. Medium graphic HMI, 15controllable objects

17. Stationcommunication

Overview

Each IED is provided with a communicationinterface, enabling it to connect to one ormany substation level systems or equipment,either on the Substation Automation (SA) busor Substation Monitoring (SM) bus.

Following communication protocols areavailable:

• IEC 61850-8-1 communication protocol• LON communication protocol• SPA or IEC 60870-5-103 communication

protocol• DNP3.0 communication protocol

Theoretically, several protocols can becombined in the same IED.

IEC 61850-8-1 communicationprotocol

The IED is equipped with single or doubleoptical Ethernet rear ports (order dependent)for IEC 61850-8-1 station bus communication.IEC 61850-8-1 communication is also possiblefrom the optical Ethernet front port. IEC61850-8-1 protocol allows intelligent electricaldevices (IEDs) from different vendors toexchange information and simplifies systemengineering. Peer-to-peer communicationaccording to GOOSE is part of the standard.Disturbance files uploading is provided.

Serial communication, LON

Existing stations with ABB station bus LONcan be extended with use of the optical LONinterface. This allows full SA functionalityincluding peer-to-peer messaging andcooperation between existing ABB IED's andthe new IED 670.

SPA communication protocol

A single glass or plastic port is provided forthe ABB SPA protocol. This allows extensionsof simple substation automation systems but

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 29

Page 30: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

the main use is for Substation MonitoringSystems SMS.

IEC 60870-5-103 communicationprotocol

A single glass or plastic port is provided forthe IEC60870-5-103 standard. This allowsdesign of simple substation automationsystems including equipment from differentvendors. Disturbance files uploading isprovided.

DNP3.0 communication protocol

An electrical RS485 and an optical Ethernetport is available for the DNP3.0communication. DNP3.0 Level 2communication with unsolicited events, timesynchronizing and disturbance reporting isprovided for communication to RTUs,Gateways or HMI systems.

Multiple command and transmit

When 670 IED's are used in SubstationAutomation systems with LON, SPA orIEC60870-5-103 communication protocols theEvent and Multiple Command function blocksare used as the communication interface forvertical communication to station HMI andgateway and as interface for horizontal peer-to-peer communication (over LON only).

Duo driver configuration DUODRV

Redundant station bus communication isused to assure communication, even thoughone communication channels might not beavailable for some reason. Redundantcommunication over station bus running IEC61850-8-1 use both port AB and CD on OEMmodule and IEC 62439-PRP protocol.

18. Remotecommunication

Analog and binary signal transferto remote end

Three analog and eight binary signals can beexchanged between two IEDs. Thisfunctionality is mainly used for the linedifferential protection. However it can beused in other products as well. An IED cancommunicate with up to 4 remote IEDs.

Binary signal transfer to remoteend, 192 signals

If the communication channel is used fortransfer of binary signals only, up to 192binary signals can be exchanged betweentwo IEDs. For example, this functionality canbe used to send information such as status ofprimary switchgear apparatus or intertrippingsignals to the remote IED. An IED cancommunicate with up to 4 remote IEDs.

Line data communication module,short, medium and long rangeLDCM

The line data communication module (LDCM)is used for communication between the IEDssituated at distances <110 km or from theIED to optical to electrical converter with G.703 or G.703E1 interface located on adistances <3 km away. The LDCM modulesends and receives data, to and from anotherLDCM module. The IEEE/ANSI C37.94standard format is used.

Galvanic X.21 line datacommunication module X.21-LDCM

A module with built-in galvanic X.21converter which e.g. can be connected tomodems for pilot wires is also available.

Galvanic interface G.703 resp G.703E1

The external galvanic data communicationconverter G.703/G.703E1 makes an optical-to-galvanic conversion for connection to a

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

30 ABB

Page 31: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

multiplexer. These units are designed for 64kbit/s resp 2Mbit/s operation. The converteris delivered with 19” rack mountingaccessories.

19. Hardware description

Hardware modules

Power supply module PSM

The power supply module is used to providethe correct internal voltages and full isolationbetween the terminal and the battery system.An internal fail alarm output is available.

Binary input module BIM

The binary input module has 16 opticallyisolated inputs and is available in twoversions, one standard and one withenhanced pulse counting capabilities on theinputs to be used with the pulse counterfunction. The binary inputs are freelyprogrammable and can be used for the inputof logical signals to any of the functions.They can also be included in the disturbancerecording and event-recording functions. Thisenables extensive monitoring and evaluationof operation of the IED and for all associatedelectrical circuits.

Binary output module BOM

The binary output module has 24independent output relays and is used fortrip output or any signaling purpose.

Static binary output module SOM

The static binary output module has six faststatic outputs and six change over outputrelays for use in applications with high speedrequirements.

Binary input/output module IOM

The binary input/output module is usedwhen only a few input and output channelsare needed. The ten standard output channelsare used for trip output or any signaling

purpose. The two high speed signal outputchannels are used for applications whereshort operating time is essential. Eightoptically isolated binary inputs cater forrequired binary input information.

mA input module MIM

The milli-ampere input module is used tointerface transducer signals in the –20 to +20mA range from for example OLTC position,temperature or pressure transducers. Themodule has six independent, galvanicallyseparated channels.

Optical ethernet module OEM

The optical fast-ethernet module is used toconnect an IED to the communication buses(like the station bus) that use the IEC61850-8-1 protocol (port A, B). The modulehas one or two optical ports with STconnectors.

Serial and LON communication module,supports SPA/IEC 60870-5-103, LON andDNP 3.0

The serial and LON communication module(SLM) is used for SPA, IEC 60870-5-103,DNP3 and LON communication. The modulehas two optical communication ports forplastic/plastic, plastic/glass or glass/glass.One port is used for serial communication(SPA, IEC 60870-5-103 and DNP3) and oneport is dedicated for LON communication.

Line data communication module LDCM

Each module has one optical port, one foreach remote end to which the IEDcommunicates.

Alternative cards for Long range (1550 nmsingle mode), Medium range (1310 nm singlemode) and Short range (850 nm multi mode)are available.

Galvanic X.21 line data communicationmodule X.21-LDCM

The galvanic X.21 line data communicationmodule is used for connection totelecommunication equipment, for example

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 31

Page 32: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

leased telephone lines. The module supports64 kbit/s data communication between IEDs.

Examples of applications:

• Line differential protection• Binary signal transfer

Galvanic RS485 serial communicationmodule

The Galvanic RS485 communication module(RS485) is used for DNP3.0 communication.The module has one RS485 communicationport. The RS485 is a balanced serialcommunication that can be used either in 2-wire or 4-wire connections. A 2-wireconnection uses the same signal for RX andTX and is a multidrop communication withno dedicated Master or slave. This variantrequires however a control of the output. The4-wire connection has separated signals forRX and TX multidrop communication with adedicated Master and the rest are slaves. Nospecial control signal is needed in this case.

GPS time synchronization module GTM

This module includes a GPS receiver used fortime synchronization. The GPS has one SMAcontact for connection to an antenna. It alsoincludes an optical PPS ST-connector output.

IRIG-B Time synchronizing module

The IRIG-B time synchronizing module isused for accurate time synchronizing of theIED from a station clock.

Electrical (BNC) and optical connection (ST)for 0XX and 12X IRIG-B support.

Transformer input module TRM

The transformer input module is used togalvanically separate and transform thesecondary currents and voltages generated bythe measuring transformers. The module hastwelve inputs in different combinations ofcurrents and voltage inputs.

Alternative connectors of Ring lug orCompression type can be ordered.

High impedance resistor unit

The high impedance resistor unit, withresistors for pick-up value setting and avoltage dependent resistor, is available in asingle phase unit and a three phase unit.Both are mounted on a 1/1 19 inch apparatusplate with compression type terminals.

Layout and dimensions

Dimensions

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

32 ABB

Page 33: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

xx05000003.vsd

CB

E

F

A

D

IEC05000003 V1 EN

Figure 5. 1/2 x 19” case with rear cover

xx05000004.vsd

IEC05000004 V1 EN

Figure 6. Side-by-side mounting

Case size A B C D E F

6U, 1/2 x 19” 265.9 223.7 201.1 242.1 252.9 205.7

6U, 3/4 x 19” 265.9 336.0 201.1 242.1 252.9 318.0

6U, 1/1 x 19” 265.9 448.1 201.1 242.1 252.9 430.3

(mm)

Mounting alternatives

Following mounting alternatives (IP40protection from the front) are available:

• 19” rack mounting kit• Flush mounting kit with cut-out

dimensions:

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 33

Page 34: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

1/2 case size (h) 254.3 mm10.01inches (w) 210.1 mm

3/4 case size (h) 254.3 mm (w) 322.4mm

1/1 case size (h) 254.3 mm (w) 434.7mm

• Wall mounting kit

See ordering for details about availablemounting alternatives.

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

34 ABB

Page 35: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

20. Connection diagrams

Table 1. Designations for 1/2 x 19” casing with 1 TRM slot

1MRK002801-AC 2 670 1.2 PG V1 EN

Module Rear Positions

PSM X11

BIM, BOM, SOM, IOM orMIM

X31 and X32 etc. to X51and X52

SLM X301:A, B, C, D

LDCM, IRIG-B or RS485 X302

LDCM or RS485 X303

OEM X311:A, B, C, D

LDCM, RS485 or GTM X312, 313

TRM X401

Table 2. Designations for 3/4 x 19” casing with 2 TRM slot

1MRK002801-AC 4 670 1.2 PG V1 EN

Module Rear Positions

PSM X11

BIM, BOM, SOM, IOM orMIM

X31 and X32 etc. to X71 andX72

SLM X301:A, B, C, D

LDCM, IRIG-B or RS485 X302

LDCM or RS485 X303

OEM X311:A, B, C, D

LDCM, RS485 or GTM X312, X313, X322, X323

TRM 1 X401

TRM 2 X411

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 35

Page 36: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 3. Designations for 1/1 x 19” casing with 2 TRM slots

1MRK002801-AC 6 670 1.2 PG V1 EN

Module Rear Positions

PSM X11

BIM, BOM, SOM,IOM or MIM

X31 and X32 etc. to X131and X132

SLM X301:A, B, C, D

LDCM, IRIG-B orRS485

X302

LDCM or RS485 X303

OEM X311:A, B, C, D

LDCM, RS485 orGTM

X312, X313, X322, X323

TRM 1 X401

TRM 2 X411

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

36 ABB

Page 37: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

1MRK002801-AC 10 670 1.2 PG V1 EN

Figure 7. Transformer input module (TRM)

Indicates high polarity

CT/VT-input designation according to figure 7

Curr

ent/

volt

age

confi

gura

tion

(50/

60 H

z)

AI01 AI02 AI03 AI04 AI05 AI06 AI07 AI08 AI09 AI10 AI11 AI12

9I+3U,1A

1A 1A 1A 1A 1A 1A 1A 1A 1A 110-220V 110-220V 110-220V

9I+3U,5A

5A 5A 5A 5A 5A 5A 5A 5A 5A 110-220V 110-220V 110-220V

5I, 1A+4I, 5A+3U

1A 1A 1A 1A 1A 5A 5A 5A 5A 110-220V 110-220V 110-220V

7I+5U,1A

1A 1A 1A 1A 1A 1A 1A 110-220V 110-220V 110-220V 110-220V 110-220V

7I+5U,5A

5A 5A 5A 5A 5A 5A 5A 110-220V 110-220V 110-220V 110-220V 110-220V

6I+6U,1A

1A 1A 1A 1A 1A 1A 110-220V 110-220V 110-220V 110-220V 110-220V 110-220V

6I+6U,5A

5A 5A 5A 5A 5A 5A 110-220V 110-220V 110-220V 110-220V 110-220V 110-220V

3I, 5A+3I, 1A+6U

5 A 5 A 5 A 1A 1A 1A 110-220V 110-220V 110-220V 110-220V 110-220V 110-220V

6I, 1A 1A 1A 1A 1A 1A 1A - - - - - -

6I, 5A 5A 5A 5A 5A 5A 5A - - - - - -

*) Metering

Note that internal polarity can be adjusted by setting of analog input CT neutral direction and/or on SMAI pre-processing function blocks.

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 37

Page 38: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

1MRK002801-AC 11 670 1.2 PG V1 EN

Figure 8. Binary input module (BIM). Inputcontacts named XA corresponds torear position X31, X41, and so on,and input contacts named XB torear position X32, X42, and so on.

1MRK002801-AC 15 670 1.2 PG V1 EN

Figure 9. mA input module (MIM)

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

38 ABB

Page 39: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

1MRK002801-AC 8 670 1.2 PG V1 EN

Figure 10. IED with basic functionality and communication interfaces

1MRK002801-AC 7 670 1.2 PG V1 EN

Figure 11. Power supply module (PSM)

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 39

Page 40: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

1MRK002801-AC 12 670 1.2 PG V1 EN

Figure 12. Binary output module (BOM). Output contacts named XA corresponds to rearposition X31, X41, and so on, and output contacts named XB to rear positionX32, X42, and so on.

1MRK002801-AC 13 670 1.2 PG V1 EN

Figure 13. Static output module (SOM)

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

40 ABB

Page 41: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

1MRK002801-AC 14 670 1.2 PG V1 EN

Figure 14. Binary in/out module (IOM). Input contacts named XA corresponds to rear positionX31, X41, and so on, and output contacts named XB to rear position X32, X42,and so on.

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 41

Page 42: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

CC

TC

TC

P1

-QB1-QB2

-QA1

-BI1

QB1-OPENQB1-CLQB2-OPENQB2-CL

QA1-OPENQA1-CL

QA1-SPR UNCH

QA1-PD

CLOSE QA1

TRIP QA1 L1,L2,L3

MAIN 2 TRIP

-QB9

MCB-OK

MCB-OK

BUS ABUS B

QB9-OPENQB9-CL

BBP-TRIP

ST BFP L1

ST BFP 3PH

START AR

INHIBIT AR

3PH TRIP

1PH AR IN PROG

CR Z<

CS Z<

CR DEF

CS DEF

CR DIT

CS DIT

TO/F

RO

M P

LC/M

UX

FAU

LTSI

GN

ALLI

NG

REMOTE ENDCOMMUNICATION

O

TO MAIN 2 RELAY

TO BUS PROT

MCB ORFUSE

MCB-OK

- +IRF

MAN CLOSE

BUSBAR TRIP

TRIP Reinf

CLOSE Reinf

TRM1:1-3

TRM1:7-9

TRM1:10

TRM1:11

NOTE! CB CLosed isCB Closed L1&L2&L3CB Open is CB Open

L1 OR L2 OR L3

-BU1

TRM1:5 Reserved for parallal lineIN at mutual comp of FL

PERMIT 1PHTRIP MAIN 2

IN TEST

en05000261.vsd

*)*)*)

*)

*)

*)

*)*)

REL/RED 3 Phase

ST BFP L2ST BFP L3

X11 2X113 5 4

*) is only valid for single phase tripping arrangementsIEC05000261 V1 EN

Figure 15. Typical connection diagram for a single breaker arrangement with control integrated.

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

42 ABB

Page 43: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

CC

TC

TC

=3-QA1

QA1-OPENQA1-CL

QA1-SPRUNCH

QA1-PD

CLOSE QA1

TRIP QA1 L1,L2,L3

MAIN 2 TRIP

CC

TC

TC

P1

-QB1

=1-QA1

-BI1

QB1-OPENQB1-CL

QB6-OPENQB6-CL

QA1-OPENQA1-CL

QA1-SPR UNCH

QA1-PD

CLOSE QA1

TRIP QA1 L1,L2,L3

MAIN 2 TRIP

-QB9

MCB-OK

MCB-OK

BUS A

BUS B

BBP-TRIP

ST BFP L1ST BFP L2ST BFP L3

ST BFP 3PH

START AR

INHIBIT AR

3PH TRIP

1PH AR IN PROG

CR Z<

CS Z<

CR DEF

CS DEF

CR DIT

CS DIT

TO/F

RO

M P

LC/M

UX

FAU

LTSI

GN

ALLI

NG

REMOTE ENDCOMMUNICATION

O

TO MAIN 2 RELAY

TO BUS PROT

MCB ORFUSE

MCB-OK

- +IRF

MAN CLOSE =1

P1

-BI1TO MAIN 2 RELAY

-QB9MCB-OK

MCB ORFUSE

-QB6

MCB ORFUSE

ST BFP L1ST BFP L2ST BFP L3

ST BFP 3PH

START AR

INHIBIT AR

3PH TRIP

BUSBAR TRIP

TRIP =2-QA1

DIT2 Line 2 =2-QA1

TRIP Reinf

CLOSE Reinf

TRIP Reinf

CLOSE Reinf

QB9-OPENQB9-CL

TRM1:1-3

TRM2:1-3

TRM1:7-9

TRM1:11

TRM2:11

TRM1:12

NOTE! CB CLosed isCB Closed L1&L2&L3CB Open is CB Open

L1 OR L2 OR L3

-BU1

-BU1

-BU1

-BU1

-QB61

-QB62

-QB6

-QB2

MCB ORFUSE

TRM1:5Reserved for parallal line IN

at mutual comp of FLPERMIT 1PH TRIPMAIN 2, =1

=2-QB9-OPEN=2-QB9-CL

=2-QA1-OPEN=2-QA1-CL

For Voltageselection

PERMIT 1PH TRIPMAIN 2, =3

IN TEST

MAN CLOSE =3

en05000267.vsd

*)*)*)

*)

*)

*)

*)

X11 2X113 5 4

*)*)

REL/RED 3 Phase

*) is only valid for single phase tripping arrangements

IEC05000267 V1 EN

Figure 16. Typical connection diagram for a multi breaker arrangement (1 1/2 CB) withcontrol integrated.

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 43

Page 44: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

21. Technical data

General

Definitions

Referencevalue

The specified value of an influencing factor to which are referred thecharacteristics of the equipment

Nominalrange

The range of values of an influencing quantity (factor) within which, underspecified conditions, the equipment meets the specified requirements

Operativerange

The range of values of a given energizing quantity for which the equipment,under specified conditions, is able to perform its intended functionsaccording to the specified requirements

Energizing quantities, rated valuesand limits

Analog inputs

Table 4. TRM - Energizing quantities, rated values and limits for protection transformermodules

Quantity Rated value Nominal range

Current Ir = 1 or 5 A (0.2-40) × Ir

Operative range (0-100) x Ir

Permissive overload 4 × Ir cont.

100 × Ir for 1 s *)

Burden < 150 mVA at Ir = 5 A

< 20 mVA at Ir = 1 A

Ac voltage Ur = 110 V 0.5–288 V

Operative range (0–340) V

Permissive overload 420 V cont.450 V 10 s

Burden < 20 mVA at 110 V

Frequency fr = 50/60 Hz ± 5%

*) max. 350 A for 1 s when COMBITEST test switch is included.

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

44 ABB

Page 45: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 5. TRM - Energizing quantities, rated values and limits for measuring transformermodules

Quantity Rated value Nominal range

Current Ir = 1 or 5 A (0-1.8) × Irat Ir = 1 A

(0-1.6) × Irat Ir = 5 A

Permissive overload 1.1 × Ir cont.

1.8 × Ir for 30 min at Ir =

1 A1.6 × Ir for 30 min at Ir =

5 A

Burden < 350 mVA at Ir = 5 A

< 200 mVA at Ir = 1 A

Ac voltage Ur = 110 V 0.5–288 V

Operative range (0–340) V

Permissive overload 420 V cont.450 V 10 s

Burden < 20 mVA at 110 V

Frequency fr = 50/60 Hz ± 5%

Table 6. MIM - mA input module

Quantity: Rated value: Nominal range:

Input resistance Rin = 194 Ohm -

Input range ± 5, ± 10, ± 20mA0-5, 0-10, 0-20, 4-20mA

-

Power consumptioneach mA-boardeach mA input

£ 2 W£ 0.1 W

-

Table 7. OEM - Optical ethernet module

Quantity Rated value

Number of channels 1 or 2

Standard IEEE 802.3u 100BASE-FX

Type of fiber 62.5/125 mm multimode fibre

Wave length 1300 nm

Optical connector Type ST

Communication speed Fast Ethernet 100 MB

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 45

Page 46: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Auxiliary DC voltage

Table 8. PSM - Power supply module

Quantity Rated value Nominal range

Auxiliary dc voltage, EL (input) EL = (24 - 60) VEL = (90 - 250) V

EL ± 20%EL ± 20%

Power consumption 50 W typically -

Auxiliary DC power in-rush < 5 A during 0.1 s -

Binary inputs and outputs

Table 9. BIM - Binary input module

Quantity Rated value Nominal range

Binary inputs 16 -

DC voltage, RL 24/30 V48/60 V110/125 V220/250 V

RL ± 20%RL ± 20%RL ± 20%RL ± 20%

Power consumption24/30 V48/60 V110/125 V220/250 V

max. 0.05 W/inputmax. 0.1 W/inputmax. 0.2 W/inputmax. 0.4 W/input

-

Counter input frequency 10 pulses/s max -

Oscillating signal discriminator Blocking settable 1–40 HzRelease settable 1–30 Hz

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

46 ABB

Page 47: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 10. BIM - Binary input module with enhanced pulse counting capabilities

Quantity Rated value Nominal range

Binary inputs 16 -

DC voltage, RL 24/30 V48/60 V110/125 V220/250 V

RL ± 20%RL ± 20%RL ± 20%RL ± 20%

Power consumption24/30 V48/60 V110/125 V220/250 V

max. 0.05 W/inputmax. 0.1 W/inputmax. 0.2 W/inputmax. 0.4 W/input

-

Counter input frequency 10 pulses/s max -

Balanced counter input frequency 40 pulses/s max -

Oscillating signal discriminator Blocking settable 1–40 HzRelease settable 1–30 Hz

Table 11. IOM - Binary input/output module

Quantity Rated value Nominal range

Binary inputs 8 -

DC voltage, RL 24/30 V48/60 V110/125 V220/250 V

RL ± 20%RL ± 20%RL ± 20%RL ± 20%

Power consumption24/30 V48/60 V110/125 V220/250 V

max. 0.05 W/inputmax. 0.1 W/inputmax. 0.2 W/inputmax. 0.4 W/input

-

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 47

Page 48: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 12. IOM - Binary input/output module contact data (reference standard: IEC61810-2)

Function or quantity Trip and signal relays Fast signal relays(parallel reed relay)

Binary outputs 10 2

Max system voltage 250 V AC, DC 250 V AC, DC

Test voltage across open contact, 1 min 1000 V rms 800 V DC

Current carrying capacityContinuous1 s

8 A10 A

8 A10 A

Making capacity at inductive load withL/R>10 ms0.2 s1.0 s

30 A10 A

0.4 A0.4 A

Breaking capacity for AC, cos φ > 0.4 250 V/8.0 A 250 V/8.0 A

Breaking capacity for DC with L/R < 40ms

48 V/1 A110 V/0.4 A125 V/0.35 A220 V/0.2 A250 V/0.15 A

48 V/1 A110 V/0.4 A125 V/0.35 A220 V/0.2 A250 V/0.15 A

Maximum capacitive load - 10 nF

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

48 ABB

Page 49: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 13. SOM - Static Output Module (reference standard: IEC 61810-2): Static binaryoutputs

Function of quantity Static binary output trip

Rated voltage 48 - 60 VDC 110 - 250 VDC

Number of outputs 6 6

Impedance open state ~300 kΩ ~810 kΩ

Test voltage across opencontact, 1 min

No galvanic separation No galvanic separation

Current carrying capacity:

Continuous 5A 5A

1.0s 10A 10A

Making capacity at capacitiveload with the maximumcapacitance of 0.2 μF :

0.2s 30A 30A

1.0s 10A 10A

Breaking capacity for DC with L/R ≤ 40ms

48V / 1A 110V / 0.4A

60V / 0,75A 125V / 0.35A

220V / 0.2A

250V / 0.15A

Operating time <1ms <1ms

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 49

Page 50: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 14. SOM - Static Output module data (reference standard: IEC 61810-2):Electromechanical relay outputs

Function of quantity Trip and signal relays

Max system voltage 250V AC/DC

Number of outputs 6

Test voltage across open contact, 1 min 1000V rms

Current carrying capacity:

Continuous 8A

1.0s 10A

Making capacity at capacitive load with themaximum capacitance of 0.2 μF:

0.2s 30A

1.0s 10A

Breaking capacity for DC with L/R ≤ 40ms 48V / 1A

110V / 0.4A

125V / 0,35A

220V / 0,2A

250V / 0.15A

Table 15. BOM - Binary output module contact data (reference standard: IEC 61810-2)

Function or quantity Trip and Signal relays

Binary outputs 24

Max system voltage 250 V AC, DC

Test voltage across open contact, 1 min 1000 V rms

Current carrying capacityContinuous1 s

8 A10 A

Making capacity at inductive load with L/R>10 ms0.2 s1.0 s

30 A10 A

Breaking capacity for AC, cos j>0.4 250 V/8.0 A

Breaking capacity for DC with L/R < 40 ms 48 V/1 A110 V/0.4 A125 V/0.35 A220 V/0.2 A250 V/0.15 A

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

50 ABB

Page 51: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Influencing factors

Table 16. Temperature and humidity influence

Parameter Reference value Nominal range Influence

Ambienttemperature, operatevalue

+20 °C -10 °C to +55 °C 0.02% /°C

Relative humidityOperative range

10%-90%0%-95%

10%-90% -

Storage temperature -40 °C to +70 °C - -

Table 17. Auxiliary DC supply voltage influence on functionality during operation

Dependence on Referencevalue

Withinnominal range

Influence

Ripple, in DC auxiliary voltageOperative range

max. 2%Full waverectified

15% of EL 0.01% /%

Auxiliary voltage dependence,operate value

± 20% of EL 0.01% /%

Interrupted auxiliary DC voltage

24-60 V DC ±20%90-250 V DC ±20%

Interruptioninterval0–50 ms

No restart

0–∞ s Correct behaviour atpower down

Restart time <180 s

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 51

Page 52: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 18. Frequency influence (reference standard: IEC 60255–1)

Dependence on Within nominal range Influence

Frequency dependence, operatevalue

fr ± 2.5 Hz for 50 Hz

fr ± 3.0 Hz for 60 Hz

± 1.0% / Hz

Frequency dependence fordistance protection operate value

fr ± 2.5 Hz for 50 Hz

fr ± 3.0 Hz for 60 Hz

±2.0% / Hz

Harmonic frequencydependence (20% content)

2nd, 3rd and 5th harmonic of fr ± 1.0%

Harmonic frequencydependence for distanceprotection (10% content)

2nd, 3rd and 5th harmonic of fr ± 6.0%

Harmonic frequencydependence for high impedancedifferential protection (10%content)

2nd, 3rd and 5th harmonic of fr ±5.0%

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

52 ABB

Page 53: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Type tests according to standards

Table 19. Electromagnetic compatibility

Test Type test values Reference standards

1 MHz burst disturbance 2.5 kV IEC 60255-22-1

100 kHz slow damped oscillatorywave immunity test

2.5 kV IEC 61000-4-18, Class III

Ring wave immunity test, 100 kHz 2-4 kV IEC 61000-4-12, Class IV

Surge withstand capability test 2.5 kV, oscillatory4.0 kV, fast transient

IEEE/ANSI C37.90.1

Electrostatic dischargeDirect applicationIndirect application

15 kV air discharge8 kV contact discharge8 kV contact discharge

IEC 60255-22-2, Class IV IEC 61000-4-2, Class IV

Electrostatic dischargeDirect applicationIndirect application

15 kV air discharge8 kV contact discharge8 kV contact discharge

IEEE/ANSI C37.90.1

Fast transient disturbance 4 kV IEC 60255-22-4, Class A

Surge immunity test 1-2 kV, 1.2/50 mshigh energy

IEC 60255-22-5

Power frequency immunity test 150-300 V,50 Hz

IEC 60255-22-7, Class A

Conducted common modeimmunity test

15 Hz-150 kHz IEC 61000-4-16, Class IV

Power frequency magnetic field test 1000 A/m, 3 s100 A/m, cont.

IEC 61000-4-8, Class V

Damped oscillatory magnetic fieldtest

100 A/m IEC 61000-4-10, Class V

Radiated electromagnetic fielddisturbance

20 V/m, 80-1000 MHz 1.4-2.7 GHz

IEC 60255-22-3

Radiated electromagnetic fielddisturbance

35 V/m26-1000 MHz

IEEE/ANSI C37.90.2

Conducted electromagnetic fielddisturbance

10 V, 0.15-80 MHz IEC 60255-22-6

Radiated emission 30-1000 MHz IEC 60255-25

Conducted emission 0.15-30 MHz IEC 60255-25

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 53

Page 54: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 20. Insulation

Test Type test values Reference standard

Dielectric test 2.0 kV AC, 1 min. IEC 60255-5

Impulse voltage test 5 kV, 1.2/50 ms, 0.5 J

Insulation resistance >100 MW at 500 VDC

Table 21. Environmental tests

Test Type test value Reference standard

Cold test Test Ad for 16 h at -25°C IEC 60068-2-1

Storage test Test Ad for 16 h at -40°C IEC 60068-2-1

Dry heat test Test Bd for 16 h at +70°C IEC 60068-2-2

Damp heat test, steady state Test Ca for 4 days at +40 °C andhumidity 93%

IEC 60068-2-78

Damp heat test, cyclic Test Db for 6 cycles at +25 to +55°C and humidity 93 to 95% (1 cycle= 24 hours)

IEC 60068-2-30

Table 22. CE compliance

Test According to

Immunity EN 50263

Emissivity EN 50263

Low voltage directive EN 50178

Table 23. Mechanical tests

Test Type test values Reference standards

Vibration response test Class II IEC 60255-21-1

Vibration endurance test Class I IEC 60255-21-1

Shock response test Class II IEC 60255-21-2

Shock withstand test Class I IEC 60255-21-2

Bump test Class I IEC 60255-21-2

Seismic test Class II IEC 60255-21-3

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

54 ABB

Page 55: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Differential protection

Table 24. 1Ph High impedance differential protection HZPDIF

Function Range or value Accuracy

Operate voltage (20-400) V ± 1.0% of Ur for U < Ur

± 1.0% of U for U > Ur

Reset ratio >95% -

Maximum continuous voltage U>Trip2/series resistor ≤200 W -

Operate time 10 ms typically at 0 to 10 x Ud -

Reset time 90 ms typically at 10 to 0 x Ud -

Critical impulse time 2 ms typically at 0 to 10 x Ud -

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 55

Page 56: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Impedance protection

Table 25. Distance measuring zone, Quad ZMQPDIS

Function Range or value Accuracy

Number of zones 5 with selectabledirection

-

Minimum operateresidual current, zone 1

(5-1000)% ofIBase

-

Minimum operate current,phase-to-phase and phase-to-earth

(10-1000)% ofIBase

-

Positive sequencereactance

(0.10-3000.00) Ω/phase

± 2.0% static accuracy± 2.0 degrees static angular accuracyConditions:Voltage range: (0.1-1.1) x Ur

Current range: (0.5-30) x IrAngle: at 0 degrees and 85 degrees

Positive sequenceresistance

(0.01-1000.00) Ω/phase

Zero sequence reactance (0.10-9000.00) Ω/phase

Zero sequence resistance (0.01-3000.00) Ω/phase

Fault resistance, phase-to-earth

(0.10-9000.00) Ω/loop

Fault resistance, phase-to-phase

(0.10-3000.00) Ω/loop

Dynamic overreach <5% at 85degreesmeasured withCVT’s and0.5<SIR<30

-

Impedance zone timers (0.000-60.000) s ± 0.5% ± 10 ms

Operate time 24 ms typically -

Reset ratio 105% typically -

Reset time 30 ms typically -

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

56 ABB

Page 57: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 26. Distance measuring zone, quadrilateral characteristic for series compensatedlines ZMCPDIS, ZMCAPDIS

Function Range or value Accuracy

Number of zones with selectable direction -

Minimum operateresidual current, zone 1

(5-1000)% of IBase -

Minimum operate current,Ph-Ph and Ph-E

(10-1000)% of IBase -

Positive sequencereactance

(0.10-3000.00) Ω/phase ± 2.0% static accuracy± 2.0 degrees static angular accuracyConditions:Voltage range: (0.1-1.1) x Ur

Current range: (0.5-30) x IrAngle: at 0 degrees and 85 degrees

Positive sequenceresistance

(0.10-1000.00) Ω/phase

Zero sequence reactance (0.01-9000.00) Ω/phase

Zero sequence resistance (0.01-3000.00) Ω/phase

Fault resistance, Ph-E (0.10-9000.00) Ω/loop

Fault resistance, Ph-Ph (0.10-3000.00) Ω/loop

Dynamic overreach <5% at 85 degreesmeasured with CCVT’sand 0.5<SIR<30

-

Impedance zone timers (0.000-60.000) s ± 0.5% ± 10 ms

Operate time 24 ms typically -

Reset ratio 105% typically -

Reset time 30 ms typically -

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 57

Page 58: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 27. Phase selection, quadrilateral characteristic with fixed angle FDPSPDIS

Function Range or value Accuracy

Minimum operate current (5-500)% of IBase -

Reactive reach, positivesequence

(0.50–3000.00) Ω/phase ± 2.0% static accuracy± 2.0 degrees static angular accuracyConditions:Voltage range: (0.1-1.1) x Ur

Current range: (0.5-30) x IrAngle: at 0 degrees and 85 degrees

Resistive reach, positivesequence

(0.10–1000.00) Ω/phase

Reactive reach, zerosequence

(0.50–9000.00) Ω/phase

Resistive reach, zerosequence

(0.50–3000.00) Ω/phase

Fault resistance, phase-to-earth faults, forward andreverse

(1.00–9000.00) Ω/loop

Fault resistance, phase-to-phase faults, forward andreverse

(0.50–3000.00) Ω/loop

Load encroachmentcriteria:Load resistance, forwardand reverseSafety load impedanceangle

(1.00–3000.00) Ω/phase(5-70) degrees

Reset ratio 105% typically -

Table 28. Power swing detection ZMRPSB

Function Range or value Accuracy

Reactive reach (0.10-3000.00) W/phase

± 2.0% static accuracyConditions:Voltage range: (0.1-1.1) x Ur

Current range: (0.5-30) x IrAngle: at 0 degrees and 85 degreesResistive reach (0.10–1000.00)W/loop

Timers (0.000-60.000) s ± 0.5% ± 10 ms

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

58 ABB

Page 59: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 29. Pole slip protection PSPPPAM

Function Range or value Accuracy

Impedance reach (0.00–1000.00)% of Zbase ± 2.0% of Ur/Ir

Characteristic angle (72.00–90.00) degrees ± 5.0 degrees

Start and trip angles (0.0–180.0) degrees ± 5.0 degrees

Zone 1 and Zone 2 tripcounters

(1-20) -

Table 30. Phase preference logic PPLPHIZ

Function Range or value Accuracy

Operate value, phase-to-phase and phase-to-neutral undervoltage

(10.0 - 100.0)% of UBase ± 0,5% of Ur

Reset ratio, undervoltage < 105% -

Operate value, residualvoltage

(5.0 - 70.0)% of UBase ± 0,5% of Ur

Reset ratio, residualvoltage

> 95% -

Operate value, residualcurrent

(10 - 200)% of IBase ± 1,0% of Ir for I < Ir

± 1,0% of I for I > Ir

Reset ratio, residualcurrent

> 95% -

Timers (0.000 - 60.000) s ± 0,5% ± 10ms

Operating mode No Filter, NoPrefCyclic: 1231c, 1321cAcyclic: 123a, 132a, 213a,231a, 312a, 321a

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 59

Page 60: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 31. Automatic switch onto fault logic, voltage and current based ZCVPSOF

Parameter Range orvalue

Accuracy

Operate voltage, detection of dead line (1–100)% ofUBase

± 0.5% of Ur

Operate current, detection of dead line (1–100)% ofIBase

± 1.0% of Ir

Delay following dead line detectioninput before Automatic switch into faultlogic function is automatically turned On

(0.000–60.000) s

± 0.5% ± 10 ms

Time period after circuit breaker closurein which Automatic switch into faultlogic function is active

(0.000–60.000) s

± 0.5% ± 10 ms

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

60 ABB

Page 61: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Current protection

Table 32. Instantaneous phase overcurrent protection PHPIOC

Function Range or value Accuracy

Operate current (1-2500)% of lBase ± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir

Reset ratio > 95% -

Operate time 25 ms typically at 0 to 2 x Iset -

Reset time 25 ms typically at 2 to 0 x Iset -

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Operate time 10 ms typically at 0 to 10 x Iset -

Reset time 35 ms typically at 10 to 0 x Iset -

Critical impulse time 2 ms typically at 0 to 10 x Iset -

Dynamic overreach < 5% at t = 100 ms -

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 61

Page 62: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 33. Four step phase overcurrent protection OC4PTOC

Function Setting range Accuracy

Operate current (1-2500)% of lBase ± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir

Reset ratio > 95% -

Min. operating current (1-100)% of lBase ± 1.0% of Ir

Relay characteristic angle(RCA)

(-70.0– -50.0) degrees ± 2.0 degrees

Maximum forward angle (40.0–70.0) degrees ± 2.0 degrees

Minimum forward angle (75.0–90.0) degrees ± 2.0 degrees

2nd harmonic blocking (5–100)% of fundamental ± 2.0% of Ir

Independent time delay (0.000-60.000) s ± 0.5% ± 10 ms

Minimum operate time (0.000-60.000) s ± 0.5% ± 10 ms

Inverse characteristics,see table 98, table 99 andtable 100

19 curve types See table 98, table 99 andtable 100

Operate time, startfunction

25 ms typically at 0 to 2 x Iset -

Reset time, start function 25 ms typically at 2 to 0 x Iset -

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

62 ABB

Page 63: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 34. Instantaneous residual overcurrent protection EFPIOC

Function Range or value Accuracy

Operate current (1-2500)% of lBase ± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir

Reset ratio > 95% -

Operate time 25 ms typically at 0 to 2 x Iset -

Reset time 25 ms typically at 2 to 0 x Iset -

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Operate time 10 ms typically at 0 to 10 x Iset -

Reset time 35 ms typically at 10 to 0 x Iset -

Critical impulse time 2 ms typically at 0 to 10 x Iset -

Dynamic overreach < 5% at t = 100 ms -

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 63

Page 64: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 35. Four step residual overcurrent protection EF4PTOC

Function Range or value Accuracy

Operate current (1-2500)% of lBase ± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir

Reset ratio > 95% -

Operate current fordirectional comparison

(1–100)% of lBase ± 1.0% of Ir

Timers (0.000-60.000) s ± 0.5% ± 10 ms

Inverse characteristics,see table 98, table 99 andtable 100

18 curve types See table 98, table 99 andtable 100

Second harmonic restrainoperation

(5–100)% of fundamental ± 2.0% of Ir

Relay characteristic angle (-180 to 180) degrees ± 2.0 degrees

Minimum polarizingvoltage

(1–100)% of UBase ± 0.5% of Ur

Minimum polarizingcurrent

(1-30)% of IBase ±0.25% of Ir

Real part of source Zused for currentpolarization

(0.50-1000.00) W/phase -

Imaginary part of sourceZ used for currentpolarization

(0.50–3000.00) W/phase -

Operate time, startfunction

25 ms typically at 0 to 2 x Iset -

Reset time, start function 25 ms typically at 2 to 0 x Iset -

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

64 ABB

Page 65: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 36. Four step negative sequence overcurrent protection NS4PTOC

Function Range or value Accuracy

Operate value, negativesequence current, step 1-4

(1-2500)% of lBase ± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir

Reset ratio > 95% -

Timers (0.000-60.000) s ± 0.5% ± 10 ms

Inverse characteristics,see table 98, table 99 andtable 100

18 curve types See table 98, table 99 andtable 100

Minimum operate currentfor step 1 - 4

(1.00 - 10000.00)% of IBase ± 1.0% of Ir at I < Ir± 1.0% of I at I > Ir

Operate value, negativecurrent for directionalrelease

(1–100)% of IBase ± 1.0% of Ir

Relay characteristic angle (-180 to 180) degrees ± 2.0 degrees

Minimum polarizingvoltage

(1–100)% of UBase ± 0.5% of Ur

Minimum polarizingcurrent

(2-100)% of IBase ±1.0% of Ir

Real part of negativesequence sourceimpedance used forcurrent polarization

(0.50-1000.00) W/phase -

Imaginary part ofnegative sequence sourceimpedance used forcurrent polarization

(0.50–3000.00) W/phase -

Operate time, startfunction

25 ms typically at 0.5 to 2 x Iset -

Reset time, start function 25 ms typically at 2 to 0.5 x Iset -

Critical impulse time, startfunction

10 ms typically at 0 to 2 x Iset -

Impulse margin time,start function

15 ms typically -

Transient overreach <10% at τ = 100 ms -

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 65

Page 66: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 37. Sensitive directional residual overcurrent and power protection SDEPSDE

Function Range or value Accuracy

Operate level for 3I0·cosjdirectional residualovercurrent

(0.25-200.00)% of lBase At low setting:(2.5-10) mA(10-50) mA

± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir ±0.5 mA±1.0 mA

Operate level for 3I0·3U0

· cosj directional residualpower

(0.25-200.00)% of SBase At low setting:(0.25-5.00)% of SBase

± 1.0% of Sr at S £ Sr

± 1.0% of S at S > Sr

± 10% of set value

Operate level for 3I0 and

j residual overcurrent

(0.25-200.00)% of lBase At low setting:(2.5-10) mA(10-50) mA

± 1.0% of Ir at £ Ir± 1.0% of I at I > Ir ±0.5 mA±1.0 mA

Operate level for nondirectional overcurrent

(1.00-400.00)% of lBase At low setting:(10-50) mA

± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir ± 1.0 mA

Operate level for nondirectional residualovervoltage

(1.00-200.00)% of UBase ± 0.5% of Ur at U£Ur

± 0.5% of U at U > Ur

Residual release currentfor all directional modes

(0.25-200.00)% of lBase At low setting:(2.5-10) mA(10-50) mA

± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir ±0.5 mA± 1.0 mA

Residual release voltagefor all directional modes

(0.01-200.00)% of UBase ± 0.5% of Ur at U£Ur

± 0.5% of U at U > Ur

Reset ratio > 95% -

Timers (0.000-60.000) s ± 0.5% ± 10 ms

Inverse characteristics,see table 98, table 99 andtable 100

19 curve types See table 98, table 99 andtable 100

Relay characteristic angleRCA

(-179 to 180) degrees ± 2.0 degrees

Relay open angle ROA (0-90) degrees ± 2.0 degrees

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

66 ABB

Page 67: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 37. Sensitive directional residual overcurrent and power protection SDEPSDE ,continued

Function Range or value Accuracy

Operate time, nondirectional residual overcurrent

60 ms typically at 0 to 2 x Iset -

Reset time, nondirectional residual overcurrent

60 ms typically at 2 to 0 x Iset -

Operate time, startfunction

150 ms typically at 0 to 2 x Iset -

Reset time, start function 50 ms typically at 2 to 0 x Iset -

Table 38. Thermal overload protection, one time constant LPTTR

Function Range or value Accuracy

Reference current (0-400)% of IBase ± 1.0% of Ir

Start temperaturereference

(0-400)°C ± 1.0°C

Operate time:

2 2

2 2ln p

b

I It

I It

æ ö-ç ÷= ×ç ÷-è ø

EQUATION1356 V1 EN (Equation 1)

I = actual measuredcurrentIp = load current before

overload occursIb = base current, IBase

Time constant t = (0–1000) minutes

IEC 60255-8, class 5 + 200 ms

Alarm temperature (0-200)°C ± 2.0% of heat content trip

Trip temperature (0-400)°C ± 2.0% of heat content trip

Reset level temperature (0-400)°C ± 2.0% of heat content trip

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 67

Page 68: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 39. Breaker failure protection CCRBRF

Function Range or value Accuracy

Operate phase current (5-200)% of lBase ± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir

Reset ratio, phase current > 95% -

Operate residual current (2-200)% of lBase ± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir

Reset ratio, residual current > 95% -

Phase current level forblocking of contact function

(5-200)% of lBase ± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir

Reset ratio > 95% -

Timers (0.000-60.000) s ± 0.5% ± 10 ms

Operate time for currentdetection

10 ms typically -

Reset time for currentdetection

15 ms maximum -

Table 40. Stub protection STBPTOC

Function Range or value Accuracy

Operating current (1-2500)% of IBase ± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir

Reset ratio > 95% -

Definite time (0.000-60.000) s ± 0.5% ± 10 ms

Operating time, start function 20 ms typically at 0 to 2 x Iset -

Resetting time, startfunction 25 ms typically at 2 to 0 x Iset -

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -

Table 41. Pole discordance protection CCRPLD

Function Range or value Accuracy

Operate current (0–100)% of IBase ± 1.0% of Ir

Time delay (0.000-60.000) s ± 0.5% ± 10 ms

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

68 ABB

Page 69: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 42. Directional underpower protection GUPPDUP

Function Range or value Accuracy

Power level (0.0–500.0)% of SBase At low setting:(0.5-2.0)% of SBase(2.0-10)% of SBase

± 1.0% of Sr at S < Sr

± 1.0% of S at S > Sr

< ± 50% of set value< ± 20% of set value

Characteristic angle (-180.0–180.0) degrees 2 degrees

Timers (0.00-6000.00) s ± 0.5% ± 10 ms

Table 43. Directional overpower protection GOPPDOP

Function Range or value Accuracy

Power level (0.0–500.0)% of Sbase

At low setting:(0.5-2.0)% of Sbase

(2.0-10)% of Sbase

± 1.0% of Sr at S < Sr

± 1.0% of S at S > Sr

< ± 50% of set value< ± 20% of set value

Characteristic angle (-180.0–180.0) degrees 2 degrees

Timers (0.00-6000.00) s ± 0.5% ± 10 ms

Table 44. Broken conductor check BRCPTOC

Function Range or value Accuracy

Minimum phase currentfor operation

(5–100)% of IBase ± 0.1% of Ir

Unbalance currentoperation

(0–100)% of maximumcurrent

± 0.1% of Ir

Timer (0.00-6000.00) s ± 0.5% ± 10 ms

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 69

Page 70: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Voltage protection

Table 45. Two step undervoltage protection UV2PTUV

Function Range or value Accuracy

Operate voltage, low andhigh step

(1–100)% of UBase ± 0.5% of Ur

Absolute hysteresis (0–100)% of UBase ± 0.5% of Ur

Internal blocking level, lowand high step

(1–100)% of UBase ± 0.5% of Ur

Inverse time characteristicsfor low and high step, seetable 102

- See table 102

Definite time delays (0.000-60.000) s ± 0.5% ±10 ms

Minimum operate time,inverse characteristics

(0.000–60.000) s ± 0.5% ± 10 ms

Operate time, start function 25 ms typically at 2 to 0 x Uset -

Reset time, start function 25 ms typically at 0 to 2 x Uset -

Critical impulse time 10 ms typically at 1.2 to 0.8 x Uset -

Impulse margin time 15 ms typically -

Table 46. Two step overvoltage protection OV2PTOV

Function Range or value Accuracy

Operate voltage, low andhigh step

(1-200)% of UBase ± 0.5% of Ur at U < Ur

± 0.5% of U at U > Ur

Absolute hysteresis (0–100)% of UBase ± 0.5% of Ur at U < Ur

± 0.5% of U at U > Ur

Inverse time characteristicsfor low and high step, seetable 101

- See table 101

Definite time delays (0.000-60.000) s ± 0.5% ± 10 ms

Minimum operate time,Inverse characteristics

(0.000-60.000) s ± 0.5% ± 10 ms

Operate time, start function 25 ms typically at 0 to 2 x Uset -

Reset time, start function 25 ms typically at 2 to 0 x Uset -

Critical impulse time 10 ms typically at 0 to 2 x Uset -

Impulse margin time 15 ms typically -

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

70 ABB

Page 71: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 47. Two step residual overvoltage protection ROV2PTOV

Function Range or value Accuracy

Operate voltage, low andhigh step

(1-200)% of UBase ± 0.5% of Ur at U < Ur

± 1.0% of U at U > Ur

Absolute hysteresis (0–100)% of UBase ± 0.5% of Ur at U < Ur

± 1.0% of U at U > Ur

Inverse time characteristicsfor low and high step, seetable 103

- See table 103

Definite time setting (0.000–60.000) s ± 0.5% ± 10 ms

Minimum operate time (0.000-60.000) s ± 0.5% ± 10 ms

Operate time, start function 25 ms typically at 0 to 2 x Uset -

Reset time, start function 25 ms typically at 2 to 0 x Uset -

Critical impulse time 10 ms typically at 0 to 2 x Uset -

Impulse margin time 15 ms typically -

Table 48. Overexcitation protection OEXPVPH

Function Range or value Accuracy

Operate value, start (100–180)% of (UBase/frated) ± 0.5% of U

Operate value, alarm (50–120)% of start level ± 0.5% of Ur at U ≤ Ur

± 0.5% of U at U > Ur

Operate value, high level (100–200)% of (UBase/frated) ± 0.5% of U

Curve type IEEE or customer defined

2

(0.18 ):

( 1)k

IEEE tM

×=

-

EQUATION1319 V1 EN (Equation 2)

where M = (E/f)/(Ur/fr)

Class 5 + 40 ms

Minimum time delay forinverse function

(0.000–60.000) s ± 0.5% ± 10 ms

Maximum time delay forinverse function

(0.00–9000.00) s ± 0.5% ± 10 ms

Alarm time delay (0.000–60.000) s ± 0.5% ± 10 ms

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 71

Page 72: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 49. Voltage differential protection VDCPTOV

Function Range or value Accuracy

Voltage difference foralarm and trip

(0.0–100.0) % of UBase ± 0.5 % of Ur

Under voltage level (0.0–100.0) % of UBase ± 0.5% of Ur

Timers (0.000–60.000)s ± 0.5% ± 10 ms

Table 50. Loss of voltage check LOVPTUV

Function Range or value Accuracy

Operate voltage (0–100)% of UBase ± 0.5% of Ur

Pulse timer (0.050–60.000) s ± 0.5% ± 10 ms

Timers (0.000–60.000) s ± 0.5% ± 10 ms

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

72 ABB

Page 73: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Frequency protection

Table 51. Underfrequency protection SAPTUF

Function Range or value Accuracy

Operate value, start function (35.00-75.00) Hz ± 2.0 mHz

Operate time, start function 100 ms typically -

Reset time, start function 100 ms typically -

Operate time, definite time function (0.000-60.000)s ± 0.5% ± 10 ms

Reset time, definite time function (0.000-60.000)s ± 0.5% ± 10 ms

Voltage dependent time delay

( )ExponentU UMin

t tMax tMin tMinUNom UMin

-= × - +

-é ùê úë û

EQUATION1182 V1 EN (Equation 3)

U=Umeasured

Settings:UNom=(50-150)% ofUbase

UMin=(50-150)% of Ubase

Exponent=0.0-5.0tMax=(0.000-60.000)stMin=(0.000-60.000)s

Class 5 + 200 ms

Table 52. Overfrequency protection SAPTOF

Function Range or value Accuracy

Operate value, start function (35.00-75.00) Hz ± 2.0 mHz at symmetricalthree-phase voltage

Operate time, start function 100 ms typically -

Reset time, start function 100 ms typically -

Operate time, definite time function (0.000-60.000)s ± 0.5% ± 10 ms

Reset time, definite time function (0.000-60.000)s ± 0.5% ± 10 ms

Table 53. Rate-of-change frequency protection SAPFRC

Function Range or value Accuracy

Operate value, start function (-10.00-10.00) Hz/s ± 10.0 mHz/s

Operate value, internal blockinglevel

(0-100)% of UBase ± 0.5% of Ur

Operate time, start function 100 ms typically -

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 73

Page 74: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Multipurpose protection

Table 54. General current and voltage protection CVGAPC

Function Range or value Accuracy

Measuring current input phase1, phase2, phase3,PosSeq, NegSeq, 3*ZeroSeq,MaxPh, MinPh, UnbalancePh,phase1-phase2, phase2-phase3,phase3-phase1, MaxPh-Ph,MinPh-Ph, UnbalancePh-Ph

-

Base current (1 - 99999) A -

Measuring voltage input phase1, phase2, phase3,PosSeq, -NegSeq, -3*ZeroSeq,MaxPh, MinPh, UnbalancePh,phase1-phase2, phase2-phase3,phase3-phase1, MaxPh-Ph,MinPh-Ph, UnbalancePh-Ph

-

Base voltage (0.05 - 2000.00) kV -

Start overcurrent, step 1 and 2 (2 - 5000)% of IBase ± 1.0% of Ir for I<Ir± 1.0% of I for I>Ir

Start undercurrent, step 1and 2

(2 - 150)% of IBase ± 1.0% of Ir for I<Ir± 1.0% of I for I>Ir

Definite time delay (0.00 - 6000.00) s ± 0.5% ± 10 ms

Operate time startovercurrent

25 ms typically at 0 to 2 x Iset -

Reset time start overcurrent 25 ms typically at 2 to 0 x Iset -

Operate time startundercurrent

25 ms typically at 2 to 0 x Iset -

Reset time start undercurrent 25 ms typically at 0 to 2 x Iset -

See table 98 and table 99 Parameter ranges for customerdefined characteristic no 17:k: 0.05 - 999.00A: 0.0000 - 999.0000B: 0.0000 - 99.0000C: 0.0000 - 1.0000P: 0.0001 - 10.0000PR: 0.005 - 3.000TR: 0.005 - 600.000CR: 0.1 - 10.0

See table 98 and table 99

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

74 ABB

Page 75: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 54. General current and voltage protection CVGAPC , continued

Function Range or value Accuracy

Voltage level where voltagememory takes over

(0.0 - 5.0)% of UBase ± 0.5% of Ur

Start overvoltage, step 1 and 2 (2.0 - 200.0)% of UBase ± 0.5% of Ur for U<Ur

± 0.5% of U for U>Ur

Start undervoltage, step 1and 2

(2.0 - 150.0)% of UBase ± 0.5% of Ur for U<Ur

± 0.5% of U for U>Ur

Operate time, startovervoltage

25 ms typically at 0 to 2 x Uset -

Reset time, start overvoltage 25 ms typically at 2 to 0 x Uset -

Operate time startundervoltage

25 ms typically 2 to 0 x Uset -

Reset time start undervoltage 25 ms typically at 0 to 2 x Uset -

High and low voltage limit,voltage dependent operation

(1.0 - 200.0)% of UBase ± 1.0% of Ur for U<Ur

± 1.0% of U for U>Ur

Directional function Settable: NonDir, forward andreverse

-

Relay characteristic angle (-180 to +180) degrees ± 2.0 degrees

Relay operate angle (1 to 90) degrees ± 2.0 degrees

Reset ratio, overcurrent > 95% -

Reset ratio, undercurrent < 105% -

Reset ratio, overvoltage > 95% -

Reset ratio, undervoltage < 105% -

Overcurrent:

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -

Undercurrent:

Critical impulse time 10 ms typically at 2 to 0 x Iset -

Impulse margin time 15 ms typically -

Overvoltage:

Critical impulse time 10 ms typically at 0 to 2 x Uset -

Impulse margin time 15 ms typically -

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 75

Page 76: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 54. General current and voltage protection CVGAPC , continued

Function Range or value Accuracy

Undervoltage:

Critical impulse time 10 ms typically at 2 to 0 x Uset -

Impulse margin time 15 ms typically -

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

76 ABB

Page 77: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Secondary system supervision

Table 55. Current circuit supervision CCSRDIF

Function Range or value Accuracy

Operate current (5-200)% of Ir ± 10.0% of Ir at I £ Ir± 10.0% of I at I > Ir

Block current (5-500)% of Ir ± 5.0% of Ir at I £ Ir± 5.0% of I at I > Ir

Table 56. Fuse failure supervision SDDRFUF

Function Range or value Accuracy

Operate voltage, zero sequence (1-100)% of UBase ± 0.5% of Ur

Operate current, zero sequence (1–100)% of IBase ± 1.0% of Ir

Operate voltage, negativesequence

(1–100)% of UBase ± 0.5% of Ur

Operate current, negativesequence

(1–100)% of IBase ± 1.0% of Ir

Operate voltage change level (1–100)% of UBase ± 5.0% of Ur

Operate current change level (1–100)% of IBase ± 5.0% of Ir

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 77

Page 78: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Control

Table 57. Synchronizing, synchrocheck and energizing check SESRSYN

Function Range or value Accuracy

Phase shift, jline - jbus (-180 to 180) degrees -

Voltage ratio, Ubus/Uline (0.40-25.000) % ofUBaseBus and UBaseLIne

-

Voltage high limit for synchronizingand synchrocheck

(50.0-120.0)% ofUBaseBus and UBaseLIne

± 0.5% of Ur at U ≤ Ur

± 0.5% of U at U >Ur

Reset ratio, synchrocheck > 95% -

Frequency difference limit betweenbus and line

(0.003-1.000) Hz ± 2.0 mHz

Phase angle difference limitbetween bus and line

(5.0-90.0) degrees ± 2.0 degrees

Voltage difference limit betweenbus and line

(0.02-0.5) p.u ± 0.5% of Ur

Time delay output for synchrocheck (0.000-60.000) s ± 0.5% ± 10 ms

Voltage high limit for energizingcheck

(50.0-120.0)% ofUBaseBus and UBaseLIne

± 0.5% of Ur at U ≤ Ur

± 0.5% of U at U >Ur

Reset ratio, voltage high limit > 95% -

Voltage low limit for energizingcheck

(10.0-80.0)% of UBase ± 0.5% of Ur

Reset ratio, voltage low limit < 105% -

Maximum voltage for energizing (50.0-180.0)% ofUBaseBus and/orUBaseLIne

± 0.5% of Ur at U ≤ Ur

± 0.5% of U at U >Ur

Time delay for energizing check (0.000-60.000) s ± 0.5% ± 10 ms

Operate time for synchrocheckfunction

160 ms typically -

Operate time for energizing function 80 ms typically -

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

78 ABB

Page 79: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 58. Autorecloser SMBRREC

Function Range or value Accuracy

Number of autoreclosing shots 1 - 5 -

Autoreclosing open time:shot 1 - t1 1Phshot 1 - t1 2Phshot 1 - t1 3PhHSshot 1 - t1 3PhDld

(0.000-60.000) s

± 0.5% ± 10 ms

shot 2 - t2shot 3 - t3shot 4 - t4shot 5 - t5

(0.00-6000.00) s

Extended autorecloser open time (0.000-60.000) s

Autorecloser maximum wait time for sync (0.00-6000.00) s

Maximum trip pulse duration (0.000-60.000) s

Inhibit reset time (0.000-60.000) s

Reclaim time (0.00-6000.00) s

Minimum time CB must be closed before ARbecomes ready for autoreclosing cycle

(0.00-6000.00) s

Circuit breaker closing pulse length (0.000-60.000) s

CB check time before unsuccessful (0.00-6000.00) s

Wait for master release (0.00-6000.00) s

Wait time after close command beforeproceeding to next shot

(0.000-60.000) s

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 79

Page 80: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Scheme communication

Table 59. Scheme communication logic for distance or overcurrent protection ZCPSCH

Function Range or value Accuracy

Scheme type IntertripPermissive UnderreachPermissive OverreachBlocking

-

Co-ordination time forblocking communicationscheme

(0.000-60.000) s ± 0.5% ± 10 ms

Minimum duration of a sendsignal

(0.000-60.000) s ± 0.5% ± 10 ms

Security timer for loss ofguard signal detection

(0.000-60.000) s ± 0.5% ± 10 ms

Operation mode ofunblocking logic

OffNoRestartRestart

-

Table 60. Phase segregated scheme communication logic for distance protectionZC1PPSCH

Function Range or value Accuracy

Scheme type IntertripPermissive URPermissive ORBlocking

-

Co-ordination time forblocking communicationscheme

(0.000-60.000) s ± 0.5% ± 10 ms

Minimum duration of acarrier send signal

(0.000-60.000) s ± 0.5% ± 10 ms

Security timer for loss ofcarrier guard detection

(0.000-60.000) s ± 0.5% ± 10 ms

Operation mode ofunblocking logic

OffNoRestartRestart

-

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

80 ABB

Page 81: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 61. Current reversal and weak-end infeed logic for distance protectionZCRWPSCH

Function Range or value Accuracy

Detection level phase-to-neutral voltage

(10-90)% of UBase ± 0.5% of Ur

Detection level phase-to-phase voltage

(10-90)% of UBase ± 0.5% of Ur

Reset ratio <105% -

Operate time for currentreversal logic

(0.000-60.000) s ± 0.5% ± 10 ms

Delay time for currentreversal

(0.000-60.000) s ± 0.5% ± 10 ms

Coordination time forweak-end infeed logic

(0.000-60.000) s ± 0.5% ± 10 ms

Table 62. Current reversal and weak-end infeed logic for phase segregatedcommunication ZC1WPSCH

Function Range or value Accuracy

Detection level phase toneutral voltage

(10-90)% of UBase ± 0.5% of Ur

Detection level phase tophase voltage

(10-90)% of UBase ± 0.5% of Ur

Reset ratio <105% -

Operate time for currentreversal

(0.000-60.000) s ± 0.5% ± 10 ms

Delay time for currentreversal

(0.000-60.000) s ± 0.5% ± 10 ms

Coordination time forweak-end infeed logic

(0.000-60.000) s ± 0.5% ± 10 ms

Table 63. Scheme communication logic for residual overcurrent protection ECPSCH

Function Range or value Accuracy

Scheme type Permissive UnderreachingPermissive OverreachingBlocking

-

Communication schemecoordination time

(0.000-60.000) s ± 0.5% ± 10 ms

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 81

Page 82: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 64. Current reversal and weak-end infeed logic for residual overcurrent protectionECRWPSCH

Function Range or value Accuracy

Operating mode of WEIlogic

OffEchoEcho & Trip

-

Operate voltage 3Uo for

WEI trip

(5-70)% of UBase ± 0.5% of Ur

Reset ratio >95% -

Operate time for currentreversal logic

(0.000-60.000) s ± 0.5% ± 10 ms

Delay time for currentreversal

(0.000-60.000) s ± 0.5% ± 10 ms

Coordination time forweak-end infeed logic

(0.000–60.000) s ± 0.5% ± 10 ms

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

82 ABB

Page 83: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Logic

Table 65. Tripping logic SMPPTRC

Function Range or value Accuracy

Trip action 3-ph, 1/3-ph, 1/2/3-ph -

Minimum trip pulse length (0.000-60.000) s ± 0.5% ± 10 ms

Timers (0.000-60.000) s ± 0.5% ± 10 ms

Table 66. Configurable logic blocks

Logic block Quantity with cycle time Range or value Accuracy

fast medium normal

LogicAND 60 60 160 - -

LogicOR 60 60 160 - -

LogicXOR 10 10 20 - -

LogicInverter 30 30 80 - -

LogicSRMemory 10 10 20 - -

LogicRSMemory 10 10 20 - -

LogicGate 10 10 20 - -

LogicTimer 10 10 20 (0.000–90000.000) s ± 0.5% ± 10 ms

LogicPulseTimer 10 10 20 (0.000–90000.000) s ± 0.5% ± 10 ms

LogicTimerSet 10 10 20 (0.000–90000.000) s ± 0.5% ± 10 ms

LogicLoopDelay 10 10 20 (0.000–90000.000) s ± 0.5% ± 10 ms

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 83

Page 84: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Monitoring

Table 67. Measurements CVMMXN

Function Range or value Accuracy

Frequency (0.95-1.05) × fr ± 2.0 mHz

Voltage (0.1-1.5) ×Ur ± 0.5% of Ur at U£Ur

± 0.5% of U at U > Ur

Connected current (0.2-4.0) × Ir ± 0.5% of Ir at I £ Ir± 0.5% of I at I > Ir

Active power, P 0.1 x Ur< U < 1.5 x Ur

0.2 x Ir < I < 4.0 x Ir

± 1.0% of Sr at S ≤ Sr

± 1.0% of S at S > Sr

Conditions:0.8 x Ur < U < 1.2 Ur

0.2 x Ir < I < 1.2 Ir

Reactive power, Q 0.1 x Ur< U < 1.5 x Ur

0.2 x Ir < I < 4.0 x Ir

Apparent power, S 0.1 x Ur < U < 1.5 x Ur

0.2 x Ir< I < 4.0 x Ir

Power factor, cos (φ) 0.1 x Ur < U < 1.5 x Ur

0.2 x Ir< I < 4.0 x Ir

± 0.02

Table 68. Supervision of mA input signals

Function Range or value Accuracy

mA measuring function ± 5, ± 10, ± 20 mA0-5, 0-10, 0-20, 4-20 mA

± 0.1 % of set value ± 0.005 mA

Max current oftransducer to input

(-20.00 to +20.00) mA

Min current oftransducer to input

(-20.00 to +20.00) mA

Alarm level for input (-20.00 to +20.00) mA

Warning level for input (-20.00 to +20.00) mA

Alarm hysteresis forinput

(0.0-20.0) mA

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

84 ABB

Page 85: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 69. Disturbance report DRPRDRE

Function Range or value Accuracy

Pre-fault time (0.05–1.00) s -

Post-fault time (0.1–10.0) s -

Limit time (0.5–10.0) s -

Maximum number of recordings 100 -

Time tagging resolution 1 ms See table 94

Maximum number of analog inputs 30 + 10 (external +internally derived)

-

Maximum number of binary inputs 96 -

Maximum number of phasors in the TripValue recorder per recording

30 -

Maximum number of indications in adisturbance report

96 -

Maximum number of events in the Eventrecording per recording

150 -

Maximum number of events in the Eventlist

1000, first in - first out -

Maximum total recording time (3.4 srecording time and maximum number ofchannels, typical value)

340 seconds (100recordings) at 50 Hz, 280seconds (80 recordings)at 60 Hz

-

Sampling rate 1 kHz at 50 Hz1.2 kHz at 60 Hz

-

Recording bandwidth (5-300) Hz -

Table 70. Fault locator LMBRFLO

Function Value or range Accuracy

Reactive and resistivereach

(0.001-1500.000) Ω/phase ± 2.0% static accuracy± 2.0% degrees static angularaccuracyConditions:Voltage range: (0.1-1.1) x Ur

Current range: (0.5-30) x Ir

Phase selection According to input signals -

Maximum number of faultlocations

100 -

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 85

Page 86: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 71. Event list

Function Value

Buffer capacity Maximum number of events inthe list

1000

Resolution 1 ms

Accuracy Depending on timesynchronizing

Table 72. Indications

Function Value

Buffer capacity Maximum number of indications presentedfor single disturbance

96

Maximum number of recorded disturbances 100

Table 73. Event recorder

Function Value

Buffer capacity Maximum number of events in disturbance report 150

Maximum number of disturbance reports 100

Resolution 1 ms

Accuracy Depending ontimesynchronizing

Table 74. Trip value recorder

Function Value

Buffer capacity

Maximum number of analog inputs 30

Maximum number of disturbance reports 100

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

86 ABB

Page 87: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 75. Disturbance recorder

Function Value

Buffer capacity Maximum number of analog inputs 40

Maximum number of binary inputs 96

Maximum number of disturbance reports 100

Maximum total recording time (3.4 s recording time andmaximum number of channels, typical value)

340 seconds (100 recordings)at 50 Hz280 seconds (80 recordings) at60 Hz

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 87

Page 88: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Metering

Table 76. Pulse counter PCGGIO

Function Setting range Accuracy

Input frequency See Binary Input Module (BIM) -

Cycle time for report ofcounter value

(1–3600) s -

Table 77. Energy metering ETPMMTR

Function Range or value Accuracy

Energy metering kWh Export/Import,kvarh Export/Import

Input from MMXU. No extra errorat steady load

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

88 ABB

Page 89: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Station communication

Table 78. IEC 61850-8-1 communication protocol

Function Value

Protocol IEC 61850-8-1

Communication speed for the IEDs 100BASE-FX

Table 79. LON communication protocol

Function Value

Protocol LON

Communication speed 1.25 Mbit/s

Table 80. SPA communication protocol

Function Value

Protocol SPA

Communication speed 300, 1200, 2400, 4800, 9600, 19200 or 38400 Bd

Slave number 1 to 899

Table 81. IEC60870-5-103 communication protocol

Function Value

Protocol IEC 60870-5-103

Communication speed 9600, 19200 Bd

Table 82. SLM – LON port

Quantity Range or value

Optical connector Glass fibre: type STPlastic fibre: type HFBR snap-in

Fibre, optical budget Glass fibre: 11 dB (1000 m typically *)Plastic fibre: 7 dB (10 m typically *)

Fibre diameter Glass fibre: 62.5/125 mmPlastic fibre: 1 mm

*) depending on optical budget calculation

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 89

Page 90: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 83. SLM – SPA/IEC 60870-5-103/DNP3 port

Quantity Range or value

Optical connector Glass fibre: type STPlastic fibre: type HFBR snap-in

Fibre, optical budget Glass fibre: 11 dB (3000ft/1000 m typically *)Plastic fibre: 7 dB (80ft/25 m typically *)

Fibre diameter Glass fibre: 62.5/125 mmPlastic fibre: 1 mm

*) depending on optical budget calculation

Table 84. Galvanic X.21 line data communication module (X.21-LDCM)

Quantity Range or value

Connector, X.21 Micro D-sub, 15-pole male, 1.27 mm (0.050") pitch

Connector, ground selection 2 pole screw terminal

Standard CCITT X21

Communication speed 64 kbit/s

Insulation 1 kV

Maximum cable length 100 m

Table 85. Galvanic RS485 communication module

Quantity Range or value

Communication speed 2400–19200 bauds

External connectors RS-485 6-pole connectorSoft ground 2-pole connector

Table 86. Duo driver configuration DUODRV

Function Value

Protocol IEC 61850-8-1

Communication speed 100 Base-FX

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

90 ABB

Page 91: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Remote communication

Table 87. Line data communication module

Characteristic Range or value

Type of LDCM Short range(SR)

Medium range(MR)

Long range (LR)

Type of fibre Graded-indexmultimode62.5/125 µmor 50/125 µm

Singlemode9/125 µm

Singlemode 9/125 µm

Wave length 850 nm 1310 nm 1550 nm

Optical budgetGraded-index multimode62.5/125 mm, Graded-index multimode50/125 mm

13 dB (typicaldistanceabout 3 km *)9 dB (typicaldistanceabout 2 km *)

22 dB (typicaldistance 80 km *)

26 dB (typical distance110 km *)

Optical connector Type ST Type FC/PC Type FC/PC

Protocol C37.94 C37.94implementation**)

C37.94 implementation **)

Data transmission Synchronous Synchronous Synchronous

Transmission rate / Data rate 2 Mb/s / 64kbit/s

2 Mb/s / 64 kbit/s

2 Mb/s / 64 kbit/s

Clock source Internal orderived fromreceivedsignal

Internal orderived fromreceived signal

Internal or derived fromreceived signal

*) depending on optical budget calculation**) C37.94 originally defined just for multimode; using same header, configuration and dataformat as C37.94

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 91

Page 92: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Hardware

IED

Table 88. Case

Material Steel sheet

Front plate Steel sheet profile with cut-out for HMI

Surface treatment Aluzink preplated steel

Finish Light grey (RAL 7035)

Table 89. Water and dust protection level according to IEC 60529

Front IP40 (IP54 with sealing strip)

Rear, sides, topand bottom

IP20

Table 90. Weight

Case size Weight

6U, 1/2 x 19” £ 10 kg

6U, 3/4 x 19” £ 15 kg

6U, 1/1 x 19” £ 18 kg

Connection system

Table 91. CT and VT circuit connectors

Connector type Rated voltage andcurrent

Maximum conductorarea

Screw compression type 250 V AC, 20 A 4 mm2

2 x 2.5 mm2

Terminal blocks suitable for ringlug terminals

250 V AC, 20 A 4 mm2

Table 92. Binary I/O connection system

Connector type Rated voltage Maximum conductorarea

Screw compression type 250 V AC 2.5 mm2

2 × 1 mm2

Terminal blocks suitable for ringlug terminals

300 V AC 3 mm2

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

92 ABB

Page 93: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Basic IED functions

Table 93. Self supervision with internal event list

Data Value

Recording manner Continuous, event controlled

List size 1000 events, first in-first out

Table 94. Time synchronization, time tagging

Function Value

Time tagging resolution, events and sampled measurement values 1 ms

Time tagging error with synchronization once/min (minute pulsesynchronization), events and sampled measurement values

± 1.0 ms typically

Time tagging error with SNTP synchronization, sampledmeasurement values

± 1.0 ms typically

Table 95. GPS time synchronization module (GTM)

Function Range or value Accuracy

Receiver – ±1µs relative UTC

Time to reliable time reference withantenna in new position or after powerloss longer than 1 month

<30 minutes –

Time to reliable time reference after apower loss longer than 48 hours

<15 minutes –

Time to reliable time reference after apower loss shorter than 48 hours

<5 minutes –

Table 96. GPS – Antenna and cable

Function Value

Max antenna cable attenuation 26 db @ 1.6 GHz

Antenna cable impedance 50 ohm

Lightning protection Must be provided externally

Antenna cable connector SMA in receiver endTNC in antenna end

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 93

Page 94: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 97. IRIG-B

Quantity Rated value

Number of channels IRIG-B 1

Number of channels PPS 1

Electrical connector IRIG-B BNC

Optical connector PPS and IRIG-B Type ST

Type of fibre 62.5/125 μm multimode fibre

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

94 ABB

Page 95: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Inverse characteristic

Table 98. ANSI Inverse time characteristics

Function Range or value Accuracy

Operating characteristic:

( )1= + ×

-

æ öç ÷ç ÷è ø

P

At B k

I

EQUATION1249-SMALL V1 EN

Reset characteristic:

( )2 1= ×

-

trt kI

EQUATION1250-SMALL V1 EN

I = Imeasured/Iset

k = (0.05-999) in steps of 0.01unless otherwise stated

-

ANSI Extremely Inverse A=28.2, B=0.1217, P=2.0 , tr=29.1 ANSI/IEEE C37.112,class 5 + 40 ms

ANSI Very inverse A=19.61, B=0.491, P=2.0 , tr=21.6

ANSI Normal Inverse A=0.0086, B=0.0185, P=0.02, tr=0.46

ANSI Moderately Inverse A=0.0515, B=0.1140, P=0.02, tr=4.85

ANSI Long Time ExtremelyInverse

A=64.07, B=0.250, P=2.0, tr=30

ANSI Long Time Very Inverse A=28.55, B=0.712, P=2.0, tr=13.46

ANSI Long Time Inverse k=(0.05-999) in steps of 0.01A=0.086, B=0.185, P=0.02, tr=4.6

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 95

Page 96: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 99. IEC Inverse time characteristics

Function Range or value Accuracy

Operating characteristic:

( )1= ×

-

æ öç ÷ç ÷è ø

P

At k

I

EQUATION1251-SMALL V1 EN

I = Imeasured/Iset

k = (0.05-999) in steps of 0.01 -

Time delay to reset, IEC inversetime

(0.000-60.000) s ± 0.5% of set time ±10 ms

IEC Normal Inverse A=0.14, P=0.02 IEC 60255-3, class 5+ 40 ms

IEC Very inverse A=13.5, P=1.0

IEC Inverse A=0.14, P=0.02

IEC Extremely inverse A=80.0, P=2.0

IEC Short time inverse A=0.05, P=0.04

IEC Long time inverse A=120, P=1.0

Programmable characteristicOperate characteristic:

( )= + ×

-

æ öç ÷ç ÷è ø

P

At B k

I C

EQUATION1370-SMALL V1 EN

Reset characteristic:

( )= ×

-PR

TRt k

I CR

EQUATION1253-SMALL V1 EN

I = Imeasured/Iset

k = (0.05-999) in steps of 0.01A=(0.005-200.000) in steps of 0.001B=(0.00-20.00) in steps of 0.01C=(0.1-10.0) in steps of 0.1P=(0.005-3.000) in steps of 0.001TR=(0.005-100.000) in steps of 0.001CR=(0.1-10.0) in steps of 0.1PR=(0.005-3.000) in steps of 0.001

IEC 60255, class 5 +40 ms

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

96 ABB

Page 97: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 100. RI and RD type inverse time characteristics

Function Range or value Accuracy

RI type inverse characteristic

1

0.2360.339

= ×

-

t k

I

EQUATION1137-SMALL V1 EN

I = Imeasured/Iset

k = (0.05-999) in steps of 0.01 IEC 60255-3, class 5+ 40 ms

RD type logarithmic inversecharacteristic

5.8 1.35= - ×æ öç ÷è ø

tI

Ink

EQUATION1138-SMALL V1 EN

I = Imeasured/Iset

k = (0.05-999) in steps of 0.01 IEC 60255-3, class 5+ 40 ms

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 97

Page 98: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 101. Inverse time characteristics for overvoltage protection

Function Range or value Accuracy

Type A curve:

=- >

>

æ öç ÷è ø

tk

U U

U

EQUATION1436-SMALL V1 EN

U> = Uset

U = Umeasured

k = (0.05-1.10) in steps of0.01 unless otherwise stated

Class 5 +40 ms

Type B curve:

2.0

480

32 0.5 0.035

- >× - -

>

æ öç ÷è ø

tk

U U

U

EQUATION1437-SMALL V1 EN

k = (0.05-1.10) in steps of0.01 unless otherwise stated

Type C curve:

3.0

480

32 0.5 0.035

- >× - -

>

æ öç ÷è ø

tk

U U

U

EQUATION1438-SMALL V1 EN

k = (0.05-1.10) in steps of0.01 unless otherwise stated

Programmable curve:

×= +

- >× -

>

æ öç ÷è ø

P

k At D

U UB C

U

EQUATION1439-SMALL V1 EN

k = (0.05-1.10) in steps of0.01 unless otherwise statedA = (0.005-200.000) in stepsof 0.001B = (0.50-100.00) in steps of0.01C = (0.0-1.0) in steps of 0.1D = (0.000-60.000) in stepsof 0.001P = (0.000-3.000) in steps of0.001

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

98 ABB

Page 99: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 102. Inverse time characteristics for undervoltage protection

Function Range or value Accuracy

Type A curve:

=< -

<

æ öç ÷è ø

kt

U U

U

EQUATION1431-SMALL V1 EN

U< = Uset

U = UVmeasured

k = (0.05-1.10) in steps of0.01 unless otherwise stated

Class 5 +40 ms

Type B curve:

2.0

4800.055

32 0.5

×= +

< -× -

<

æ öç ÷è ø

kt

U U

U

EQUATION1432-SMALL V1 EN

U< = Uset

U = Umeasured

k = (0.05-1.10) in steps of0.01 unless otherwise stated

Programmable curve:

×= +

< -× -

<

é ùê úê úê úæ öê úç ÷ë è ø û

P

k At D

U UB C

U

EQUATION1433-SMALL V1 EN

U< = Uset

U = Umeasured

k = (0.05-1.10) in steps of0.01 unless otherwise statedA = (0.005-200.000) in stepsof 0.001B = (0.50-100.00) in steps of0.01C = (0.0-1.0) in steps of 0.1D = (0.000-60.000) in stepsof 0.001P = (0.000-3.000) in steps of0.001

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 99

Page 100: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Table 103. Inverse time characteristics for residual overvoltage protection

Function Range or value Accuracy

Type A curve:

=- >

>

æ öç ÷è ø

tk

U U

U

EQUATION1436-SMALL V1 EN

U> = Uset

U = Umeasured

k = (0.05-1.10) insteps of 0.01

Class 5 +40 ms

Type B curve:

2.0

480

32 0.5 0.035

- >× - -

>

æ öç ÷è ø

tk

U U

U

EQUATION1437-SMALL V1 EN

k = (0.05-1.10) insteps of 0.01

Type C curve:

3.0

480

32 0.5 0.035

- >× - -

>

æ öç ÷è ø

tk

U U

U

EQUATION1438-SMALL V1 EN

k = (0.05-1.10) insteps of 0.01

Programmable curve:

×= +

- >× -

>

æ öç ÷è ø

P

k At D

U UB C

U

EQUATION1439-SMALL V1 EN

k = (0.05-1.10) insteps of 0.01A = (0.005-200.000)in steps of 0.001B = (0.50-100.00) insteps of 0.01C = (0.0-1.0) insteps of 0.1D = (0.000-60.000)in steps of 0.001P = (0.000-3.000) insteps of 0.001

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

100 ABB

Page 101: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

22. Ordering

GuidelinesCarefully read and follow the set of rules to ensure problem-free order management.Please refer to the available functions table for included application functions.PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.

To obtain the complete ordering code, please combine code from the tables, as given in the example below.

Example code: REL670*1.2-A31A02E02F01-X0-A-A-B-A-A7X0-DAX-X-XD. Using the code of each position #1-12 specified asREL670*1-2 2-3 3 3 3 3 3 3 3-4-5-6-7 7-8-9 9 9-10 10 10 10 10 10 10 10 10 10 10-11 11 11 11 11 11-12 12

# 1 - 2 - 3 - 4 - 5 6 - 7 - 8 - 9 -

REL670* - - - - - . - -

- 10 - 11 - 12

- . -

Posi

tion

SOFTWARE #1 Notes and Rules

Version number

Version no 1.2

Selection for position #1.

Configuration alternatives #2 Notes and Rules

Resistance earthed systems A21

Single breaker, 3-phase tripping A31

Multi breaker, 3-phase tripping B31

Single breaker, 1-phase tripping A32

Multi breaker, 1-phase tripping B32

ACT configuration

ABB standard configuration X00

Selection for position #2.

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 101

Page 102: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Software options #3 Notes and Rules

No option X00 All fields in the ordering form donot need to be filled in

1Ph high impedance differentialprotection - 3 blocks

A02 Note: B05 only for A32/B32Note: A02, B03. B21, C16, C17,C41, E02 and F01 only for A31/B31/A32/B32

Power swing logic B03

Phase segregated schemecommunication

B05

Pole slip/out-of-step protection B21

Sensitive directional residualovercurrent and power protection

C16

Directional power protection C17

Four step directional negative phasesequence overcurrent protection

C41

Overexcitation protection, 2windings

D03

Frequency protection E02

General current and voltageprotection

F01

Autorecloser, 1 circuit breaker H04 Note: H04 only for A31/A32

Autorecloser, 2 circuit breakers H05 Note: H05 only for B31/B32

Apparatus control 8 objects H07 Note: Only one Apparatuscontrol can be orderedNote: H07 only for A21/A31/A32. H08 only for B31/B32

Apparatus control 15 objects H08

Duo driver configuration P01

Selection for position #3

First local HMI user dialogue language #4 Notes and Rules

HMI language, English IEC B1

HMI language, English US B2

Selection for position #4.

Casing #5 Notes and Rules

1/2 x 19" case A Note: Only 1/2 case for A21

3/4 x 19" case 2 TRM slots C

1/1 x 19" case 2 TRM slots E

Selection for position #5.

Mounting details with IP40 of protection from the front #6 Notes and Rules

No mounting kit included X

19" rack mounting kit for 1/2 x 19" case of 2xRHGS6 or RHGS12 A

19" rack mounting kit for 3/4 x 19" case or 3xRGHS6 B

19" rack mounting kit for 1/1 x 19" case C

Wall mounting kit D Note: Wall mounting notrecommended withcommunication modules withfibre connection (SLM, OEM,LDCM)

Flush mounting kit E

Flush mounting kit + IP54 mounting seal F

Selection for position #6.

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

102 ABB

Page 103: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Connection type for Power supply, Input/output and Communication modules #7 Notes and Rules

Compression terminals K

Auxiliary power supply

24-60 VDC A

90-250 VDC B

Selection for position #7.

Human machine hardware interface #8 Notes and Rules

Small size - text only, IEC keypad symbols A

Medium size - graphic display, IEC keypad symbols B

Medium size - graphic display, ANSI keypad symbols C

Selection for position #8.

Connection type for Analog modules #9 Notes and Rules

Compression terminals A

Ringlug terminals B

Analog system

First TRM, 6I+6U 1A, 110/220V 6

First TRM, 6I+6U 5A, 110/220V 7

First TRM, 3I, 5A + 3I, 1A + 6U, 50/60 Hz 16 Note: Only for A21/A31/A32

No second TRM included X0 Note: Second TRM only for A31/A32/B31/B32

Second TRM, 9I+3U 1A, 110/220V 3

Second TRM, 9I+3U 5A, 110/220V 4

Second TRM, 5I, 1A+4I, 5A+3U, 110/220V 5

First TRM, 6I+6U 1A, 110/220V 6

First TRM, 6I+6U 5A, 110/220V 7

Second TRM, 6I, 1A, 110/220V 8

Second TRM, 6I, 5A, 110/220V 9

Second TRM, 7I+5U 1A, 110/220V 12

Second TRM, 7I+5U 5A, 110/220V 13

Second TRM, 3I, 5A+3I, 1A+6U, 110/220V 16

Selection for position #9.

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 103

Page 104: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Binary input/output module,mA and time synchronizationboards. Note: 1BIM and 1BOM included In A31/A32/B31/B32, 1 IOM basic in A21.

#10 Notes and Rules

Slot position (rear view)X

31

X41

X51

X61

X71

X81

X91

X10

1

X11

1

X12

1

X13

1 Note: Max 3 positions in 1/2rack and 5 in 3/4 rack with 2TRM and 11 in 1/1 rack with 2TRM.

1/2 Case with 1 TRM Note: Only 1/2 case for A21.* Only in A21

3/4 Case with 2 TRM

1/1 Case with 2 TRM

No board in slot X X X X X X X X X

Binary output module 24output relays (BOM)

A A A A A A A A A A Note: Maximum 4 (BOM+SOM+MIM) boards.

BIM 16 inputs, RL24-30 VDC,30 mA

B B* B B B B B B B B B

BIM 16 inputs, RL48-60 VDC,30 mA

C C* C C C C C C C C C

BIM 16 inputs, RL110-125VDC, 30 mA

D D* D D D D D D D D D

BIM 16 inputs, RL220-250VDC, 30 mA

E E* E E E E E E E E E

BIM 16 inputs, RL24-30 VDC,50 mA

B1 B1* B1

B1

B1

B1

B1

B1

B1

B1

B1

BIM 16 inputs, RL48-60 VDC,50 mA

C1 C1* C1

C1

C1

C1

C1

C1

C1

C1

C1

BIM 16 inputs, RL110-125VDC, 50 mA

D1 D1* D1

D1

D1

D1

D1

D1

D1

D1

D1

BIM 16 inputs, RL220-250VDC, 50 mA

E1 E1* E1 E1 E1 E1 E1 E1 E1 E1 E1

BIMp 16 inputs, RL24-30 VDCfor pulse counting

F* F F F F F F F F F

BIMp 16 inputs, RL48-60 VDCfor pulse counting

G* G G G G G G G G G

BIMp 16 inputs, RL110-125VDC for pulse counting

H* H H H H H H H H H

BIMp 16 inputs, RL220-250VDC for pulse counting

K* K K K K K K K K K

IOM 8 inputs, 10+2 output,RL24-30 VDC

L* L* L L L L L L L L L

IOM 8 inputs, 10+2 output,RL48-60 VDC

M* M* M M M M M M M M M

IOM 8 inputs, 10+2 output,RL110-125 VDC

N* N* N N N N N N N N N

IOM 8 inputs, 10+2 output,RL220-250 VDC

P* P* P P P P P P P P P

IOM 8 inputs, 10+2 output,RL24-30 VDC, 50 mA

L1* L1* L1 L1 L1 L1 L1 L1 L1 L1 L1

IOM 8 inputs, 10+2 output,RL48-60 VDC, 50 mA

M1* M1* M1

M1

M1

M1

M1

M1

M1

M1

M1

IOM 8 inputs, 10+2 output,RL110-125 VDC, 50 mA

N1* N1* N1

N1

N1

N1

N1

N1

N1

N1

N1

IOM 8 inputs, 10+2 output,RL220-250 VDC, 50 mA

P1* P1* P1 P1 P1 P1 P1 P1 P1 P1 P1

IOM with MOV 8 inputs, 10-2output, 24-30 VDC

U* U* U U U U U U U U U

IOM with MOV 8 inputs, 10-2output, 48-60 VDC

V* V* V V V V V V V V V

IOM with MOV 8 inputs, 10-2output, 110-125 VDC

W* W* W W W W W W W W W

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

104 ABB

Page 105: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Binary input/output module,mA and time synchronizationboards. Note: 1BIM and 1BOM included In A31/A32/B31/B32, 1 IOM basic in A21.

#10 Notes and Rules

IOM with MOV 8 inputs, 10-2output, 220-250 VDC

Y* Y* Y Y Y Y Y Y Y Y Y

mA input module MIM 6channels

R R R R R R R R R Note: No MIM board in 1/2 case

SOM Static output module, 12outputs, 48-60 VDC

T1 T1 T1 T1 T1 T1 T1 T1 T1

SOM static outputs module, 12outputs, 110-250 VDC

T2 T2 T2 T2 T2 T2 T2 T2 T2

Selection for position #10.

Remote end communication, DNP serial comm.and time synchronization modules

#11 Notes and Rules

Slot position (rear view)

X31

2

X31

3

X30

2

X30

3

X32

2

X32

3

Available slots in 1/2 case with 1TRM Note: Max 1 LDCM in 1/2 case

Available slots in 3/4 & 1/1 case with 2 TRM Note: Max 2 LDCM in 3/4 and1/1 case

No remote communication board included X X X X X X

Optical short range LDCM A A A A A A Note: Not in A21Note: Max 2 LDCM (same ordifferent type) can be selected

Optical medium range, LDCM 1310 nm B B B B B B

Optical long range, LDCM 1550 nm C C C C C C

Galvanic X21 line data communication module E E E E E E

GPS Time Module, GTM S S S S

IRIG-B Time synchronization module F

Galvanic RS485 communication module G G G G G G

Selection for position #11.

Serial communication unit for station communication #12 Notes and Rules

Slot position (rear view)

X30

1

X31

1

No first communication board included X

No second communication board included X

Serial LON communication module (plastic) A Note: Optical ethernet module, 2channel glass is not allowedtogether with SLM.

Serial (plastic) and LON (glass) communication module B

Serial and LON communication module (glass) C

Optical ethernet module, 1 channel glass D

Optical ethernet module, 2 channel glass E

Selection for position #12.

Guidelines

Carefully read and follow the set of rules to ensure problem-free order management. Be aware that certainfunctions can only be ordered in combination with other functions and that some functions require specifichardware selections.

Please refer to the available functions table for included application functions.

Accessories

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 105

Page 106: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

GPS antenna and mounting details

GPS antenna, including mounting kits Quantity: 1MRK 001 640-AA

Cable for antenna, 20 m Quantity: 1MRK 001 665-AA

Cable for antenna, 40 m Quantity: 1MRK 001 665-BA

Interface converter (for remote end data communication)

External interface converter from C37.94 to G703 Quantity: 1 2 1MRK 002 245-AA

External interface converter from C37.94 to G703.E1 Quantity: 1 2 1MRK 002 245-BA

Test switch

The test system COMBITEST intended for usewith the IED 670 products is described in1MRK 512 001-BEN and 1MRK 001024-CA.Please refer to the website: www.abb.com/substationautomation for detailed information.

Due to the high flexibility of our product andthe wide variety of applications possible thetest switches needs to be selected for eachspecific application.

Select your suitable test switch base on theavailable contacts arrangements shown in thereference documentation.

However our proposals for suitable variantsare;

Single breaker/Single or Three Phase tripwith internal neutral on current circuits(ordering number RK926 315-AK).

Single breaker/Single or Three Phase tripwith external neutral on current circuits(ordering number RK926 315-AC).

Multi-breaker/Single or Three Phase trip withinternal neutral on current circuits (orderingnumber RK926 315-BE).

Multi-breaker/Single or Three Phase trip withexternal neutral on current circuit (orderingnumber RK926 315-BV).

The normally open "In test mode" contact29-30 on the RTXP test switches should beconnected to the input of the test functionblock to allow activation of functionsindividually during testing.

Test switches type RTXP 24 is orderedseparately. Please refer to Section "Relateddocuments" for reference to correspondingdocuments.

RHGS 6 Case or RHGS 12 Case with mountedRTXP 24 and the on/off switch for dc-supplyare ordered separately. Please refer to Section"Related documents" for reference tocorresponding documents.

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

106 ABB

Page 107: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Protection cover

Protective cover for rear side of RHGS6, 6U, 1/4 x 19” Quantity: 1MRK 002 420-AE

Protective cover for rear side of terminal, 6U, 1/2 x 19” Quantity: 1MRK 002 420-AC

Protective cover for rear side of terminal, 6U, 3/4 x 19” Quantity: 1MRK 002 420-AB

Protective cover for rear side of terminal, 6U, 1/1 x 19” Quantity: 1MRK 002 420-AA

External resistor unit

High impedance resistor unit 1-ph with resistor and voltagedependent resistor for 20-100V operating voltage

Quantity:

1 2 3 RK795101-MA

High impedance resistor unit 3-ph with resistor and voltagedependent resistor for 20-100V operating voltage

Quantity: RK795101-MB

High impedance resistor unit 1-ph with resistor and voltagedependent resistor for 100-400V operating voltage

Quantity:

1 2 3 RK795101-CB

High impedance resistor unit 3-ph with resistor and voltagedependent resistor for 100-400V operating voltage

Quantity: RK795101-DC

Combiflex

Key switch for lock-out of settings via LCD-HMI Quantity: 1MRK 000 611-A

Note: To connect the key switch, leads with 10 A Combiflex socket on one end must be used.

Side-by-side mounting kit Quantity: 1MRK 002 420-Z

Configuration and monitoring tools

Front connection cable between LCD-HMI and PC Quantity: 1MRK 001 665-CA

LED Label special paper A4, 1 pc Quantity: 1MRK 002 038-CA

LED Label special paper Letter, 1 pc Quantity: 1MRK 002 038-DA

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 107

Page 108: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Manuals

Note: One (1) IED Connect CD containing user documentation (Operator’s manual, Technical referencemanual, Installation and commissioning manual, Application manual and Getting started guide),Connectivity packages and LED label template is always included for each IED.

Rule: Specify additional quantity of IED Connect CD requested. Quantity: 1MRK 002 290-BA

User documentation

Rule: Specify the number of printed manuals requestedOperator’s manual

IEC Quantity: 1MRK 506 313-UEN

ANSI Quantity: 1MRK 506 313-UUS

Technical reference manual IEC Quantity: 1MRK 506 312-UEN

ANSI Quantity: 1MRK 506 312-UUS

Installation and commissioning manual IEC Quantity: 1MRK 506 314-UEN

ANSI Quantity: 1MRK 506 314-UUS

Application manual IEC Quantity: 1MRK 506 315-UEN

ANSI Quantity: 1MRK 506 315-UUS

Engineering guide IED 670 products Quantity: 1MRK 511 179-UEN

Reference information

For our reference and statistics we would be pleased to be provided with the following application data:

Country: End user:

Station name: Voltage level: kV

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

108 ABB

Page 109: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

Related documents

Documents related to REL670 Identity number

Operator’s manual 1MRK 506 313-UEN

Installation and commissioning manual 1MRK 506 314-UEN

Technical reference manual 1MRK 506 312-UEN

Application manual 1MRK 506 315-UEN

Product guide customized 1MRK 506 316-BEN

Product guide pre-configured 1MRK 506 317-BEN

Product guide IEC 61850-9-2 1MRK 506 320-BEN

Sample specification SA2005-001282

Connection and Installation components 1MRK 513 003-BEN

Test system, COMBITEST 1MRK 512 001-BEN

Accessories for 670 series IEDs 1MRK 514 012-BEN

670 series SPA and signal list 1MRK 500 092-WEN

IEC 61850 Data objects list for 670 series 1MRK 500 091-WEN

Engineering manual 670 series 1MRK 511 240-UEN

Communication set-up for Relion 670 series 1MRK 505 260-UEN

More information can be found on www.abb.com/substationautomation.

Line distance protection REL670 1MRK 506 317-BEN -Pre-configuredProduct version: 1.2 Issued: May 2010

ABB 109

Page 110: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide

110

Page 111: Line distance protection REL670 Pre-configured Product …€¦ ·  · 2011-03-15Relion® 670 series Line distance protection REL670 Pre-configured Product Guide