Limitations of Simplified Load Calculation Procedures · Limitations of Simplified Load Calculation...

24
Limitations of Simplified Load Calculation Procedures Jeffrey D. Spitler, Ph.D., P.E. Ipseng (Calvin) Iu Oklahoma State University Building and Environmental Thermal Systems Research Group

Transcript of Limitations of Simplified Load Calculation Procedures · Limitations of Simplified Load Calculation...

Page 1: Limitations of Simplified Load Calculation Procedures · Limitations of Simplified Load Calculation Procedures Jeffrey D. Spitler, Ph.D., P.E. Ipseng (Calvin) Iu Oklahoma State University

Limitations of Simplified Load Calculation Procedures

Jeffrey D. Spitler, Ph.D., P.E.Ipseng (Calvin) IuOklahoma State UniversityBuilding and Environmental Thermal Systems Research Group

Page 2: Limitations of Simplified Load Calculation Procedures · Limitations of Simplified Load Calculation Procedures Jeffrey D. Spitler, Ph.D., P.E. Ipseng (Calvin) Iu Oklahoma State University

Introduction

Limitations – what limitations?Simplified ProceduresASHRAE 942-RPExamples (Primarily with RTS)

Page 3: Limitations of Simplified Load Calculation Procedures · Limitations of Simplified Load Calculation Procedures Jeffrey D. Spitler, Ph.D., P.E. Ipseng (Calvin) Iu Oklahoma State University

Approximations to the Heat Balance Method

Transfer Function Method (TFM)CLTD/SCL/CLF *TETD/TA *Radiant Time Series MethodAdmittance Method

* Both of these methods use data that are derived from TFM

Page 4: Limitations of Simplified Load Calculation Procedures · Limitations of Simplified Load Calculation Procedures Jeffrey D. Spitler, Ph.D., P.E. Ipseng (Calvin) Iu Oklahoma State University

Approximations to the Heat Balance Method

In general, simplified methods:Treat radiation and convection heat transfer together (particularly questionable when large glazing areas are involved).For the exterior surface, this involves the use of a sol-air temperature.The interior surfaces are assumed to convect and radiate to the room air temperature.

Page 5: Limitations of Simplified Load Calculation Procedures · Limitations of Simplified Load Calculation Procedures Jeffrey D. Spitler, Ph.D., P.E. Ipseng (Calvin) Iu Oklahoma State University

Approximations to the Heat Balance Method

In general, simplified methods:Use some form of precalculated response for energy storage/release in the zone.Often simplify treatment of transient conduction heat transfer through walls.Assume all heat gain becomes cooling load; i.e. no heat gain is conducted back out of the space. Tend to overpredict cooling loads.

Page 6: Limitations of Simplified Load Calculation Procedures · Limitations of Simplified Load Calculation Procedures Jeffrey D. Spitler, Ph.D., P.E. Ipseng (Calvin) Iu Oklahoma State University

Approximations to the Heat Balance Method

Benefits of approximate methods:Simpler to useGive component loads.Tend to overpredict cooling loads. ☺

Page 7: Limitations of Simplified Load Calculation Procedures · Limitations of Simplified Load Calculation Procedures Jeffrey D. Spitler, Ph.D., P.E. Ipseng (Calvin) Iu Oklahoma State University

ASHRAE 942-RP

Comparison of ASHRAE and CIBSE load calculation procedures.Compared results of procedures for thousands of different zones.

Page 8: Limitations of Simplified Load Calculation Procedures · Limitations of Simplified Load Calculation Procedures Jeffrey D. Spitler, Ph.D., P.E. Ipseng (Calvin) Iu Oklahoma State University

Sample Results

0

100

200

300

400

500

0 100 200 300 400 500

H eat B alance Peak Load (W /m 2)

RTS

Pea

k Lo

ad (

W/m

2 )

0

100

200

300

400

500

600

700

0 100 200 300 400 500 600 700

Heat Balance Peak Load (W /m2)

RTS

Pea

k Lo

ad (

W/m

2 )

Lightweight Zones Heavyweight Zones

Page 9: Limitations of Simplified Load Calculation Procedures · Limitations of Simplified Load Calculation Procedures Jeffrey D. Spitler, Ph.D., P.E. Ipseng (Calvin) Iu Oklahoma State University

Why does RTS over-predict?

The RTS procedure over-predicts most noticeably for cases with high % of single pane glazing. Two conditions must be present for significant over-prediction

Large amount of high conductance wall or windowLarge amount of radiant heat gain

Page 10: Limitations of Simplified Load Calculation Procedures · Limitations of Simplified Load Calculation Procedures Jeffrey D. Spitler, Ph.D., P.E. Ipseng (Calvin) Iu Oklahoma State University

Example

Two-story (+ basement) office building located in Chicago. Look at first floor, Northeast zone.Heavyweight walls: brick/concrete blockFloor: Lightweight layer on top of 4” concreteCeiling: 4” concrete, airspace, acoustic tileLightweight partitions: gypsum/studs

Page 11: Limitations of Simplified Load Calculation Procedures · Limitations of Simplified Load Calculation Procedures Jeffrey D. Spitler, Ph.D., P.E. Ipseng (Calvin) Iu Oklahoma State University

50'-0"

10'-0"

20'-0"

20'-0"

20'-0"

15'-0'' 15'-0"

Office Office

OfficeConferenceRoom

Storage

Corridor

Lobby

Toilet

1 2 3

4 5

6

7

8

50'-0"

Page 12: Limitations of Simplified Load Calculation Procedures · Limitations of Simplified Load Calculation Procedures Jeffrey D. Spitler, Ph.D., P.E. Ipseng (Calvin) Iu Oklahoma State University

Example

North wall (150 sq. ft. total) has 40 sq. ft. of double-pane windowsEast wall (200 sq. ft. total) has 60 sq. ft. of double-pane windows.4 people on office schedule1 W/sq. ft. equipment on office schedule1 W/sq. ft. fluorescent lightingNo infiltration.Overly high design condition: high of 96 F, 19 F range

Page 13: Limitations of Simplified Load Calculation Procedures · Limitations of Simplified Load Calculation Procedures Jeffrey D. Spitler, Ph.D., P.E. Ipseng (Calvin) Iu Oklahoma State University

Base caseBase - Chicago

0

2000

4000

6000

8000

10000

12000

14000

16000

1 5 9 13 17 21Time (hrs)

Clg

. Loa

d (B

tu/h

r)

HBMRTS

13% high at peak

Page 14: Limitations of Simplified Load Calculation Procedures · Limitations of Simplified Load Calculation Procedures Jeffrey D. Spitler, Ph.D., P.E. Ipseng (Calvin) Iu Oklahoma State University

Glazing area and type

More glass: 50%, 100%, 200% more.Change glass from double pane to single pane.

Page 15: Limitations of Simplified Load Calculation Procedures · Limitations of Simplified Load Calculation Procedures Jeffrey D. Spitler, Ph.D., P.E. Ipseng (Calvin) Iu Oklahoma State University

Mostly glass facade200% Extra Glass Area (DP) -- Chicago

-5000

0

5000

10000

15000

20000

25000

30000

35000

40000

1 5 9 13 17 21

Time (hrs)

Clg

. Loa

d (B

tu/h

r)

HBMRTS

19% high at peak

Page 16: Limitations of Simplified Load Calculation Procedures · Limitations of Simplified Load Calculation Procedures Jeffrey D. Spitler, Ph.D., P.E. Ipseng (Calvin) Iu Oklahoma State University

Single pane glass facadeBase+200 - SP - Chicago

-5000

0

5000

10000

15000

20000

25000

30000

35000

40000

45000

1 5 9 13 17 21

Time (hrs)

Clg

. Loa

d (B

tu/h

r)

HBMRTS

33% high at peak

Page 17: Limitations of Simplified Load Calculation Procedures · Limitations of Simplified Load Calculation Procedures Jeffrey D. Spitler, Ph.D., P.E. Ipseng (Calvin) Iu Oklahoma State University

Summary - Chicago

Chicago

0%

5%

10%

15%

20%

25%

30%

35%

Base Base+50% Base+100% Base+200%

Ove

rpre

dict

ion

DPSP

Page 18: Limitations of Simplified Load Calculation Procedures · Limitations of Simplified Load Calculation Procedures Jeffrey D. Spitler, Ph.D., P.E. Ipseng (Calvin) Iu Oklahoma State University

Move Building to Seattle

Chicago had a high temperature of 96 F, low of 77 FUsing Seattle 2% design conditions: high of 78 F, low of 60 FNote that a similar effect might be obtained for zones with winter peaks.

Page 19: Limitations of Simplified Load Calculation Procedures · Limitations of Simplified Load Calculation Procedures Jeffrey D. Spitler, Ph.D., P.E. Ipseng (Calvin) Iu Oklahoma State University

Seattle – SP Glass FacadeBase+200 - SP - Seattle

-10000

-5000

0

5000

10000

15000

20000

25000

30000

35000

40000

1 5 9 13 17 21

Time (hrs)

Clg

. Loa

d (B

tu/h

r)

HBMRTS

34% high at peak

Page 20: Limitations of Simplified Load Calculation Procedures · Limitations of Simplified Load Calculation Procedures Jeffrey D. Spitler, Ph.D., P.E. Ipseng (Calvin) Iu Oklahoma State University

Seattle SummarySeattle

0%

5%

10%

15%

20%

25%

30%

35%

40%

Base Base+50% Base+100% Base+200%

Ove

rpre

dict

ion

DPSP

Page 21: Limitations of Simplified Load Calculation Procedures · Limitations of Simplified Load Calculation Procedures Jeffrey D. Spitler, Ph.D., P.E. Ipseng (Calvin) Iu Oklahoma State University

What about TFM?

Difference between RTS and TFM depend primarily on tabulated factors.How close is actual zone to tabulated zones? Weighting factors were grouped, adding another (variable) overprediction.

Page 22: Limitations of Simplified Load Calculation Procedures · Limitations of Simplified Load Calculation Procedures Jeffrey D. Spitler, Ph.D., P.E. Ipseng (Calvin) Iu Oklahoma State University

626-RP Tabulated WF

Page 23: Limitations of Simplified Load Calculation Procedures · Limitations of Simplified Load Calculation Procedures Jeffrey D. Spitler, Ph.D., P.E. Ipseng (Calvin) Iu Oklahoma State University

Chicago Base CaseComparison of Three Methods

0

2000

4000

6000

8000

10000

12000

14000

16000

18000

1 5 9 13 17 21

Hour

Coo

ling

Load

(Btu

/hr)

HBMRTSTFM

+29%

Page 24: Limitations of Simplified Load Calculation Procedures · Limitations of Simplified Load Calculation Procedures Jeffrey D. Spitler, Ph.D., P.E. Ipseng (Calvin) Iu Oklahoma State University

Conclusions

RTS procedure works well for many zones.RTS procedure may over predict for zones with high amounts of glazing Exacerbating factors include:

Single pane glassLow outdoor design temperatures