  • 1Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Module 4

    Lighting Calculations

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    ContentsContentsDetermining Average IlluminanceAverage Illuminance EquationThe Lumen MethodDetermining the Illuminance at a Point- Direct ComponentSample Calculations

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Determining Average IlluminanceDetermining Average IlluminanceThe standard lumen method formula is also used to calculate average illuminance levels when the Coefficient of Utilization (CUs) are taken from a utilization curve.

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Average Illuminance EquationAverage Illuminance Equation

    (TOTAL) x CU x LLF

    AwpEwp

    General equation for illuminance in space

    Ewp = average maintained illuminance on the work plane

    (TOTAL) = total system lamp lumen output

    CU = coefficient of utilization

    LLF = light loss factor

    Awp = area of the work plane

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    The Lumen MethodThe Lumen MethodMeans of determining the average workplane illuminance within a space with a given number of luminairesComponents

    Total system lamp lumen outputCoefficient of utilizationLoss factor determinationCalculated illuminanceSpacing criteria

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Total System Lamp OutputTotal System Lamp OutputLamp lumen output is the total initial luminous flux that the lamps emit as specified by the manufacturer.

    Example 1: In an office space 3m x 4.6m with a 2.6m ceiling height, there are 2 recessed fluorescent luminaires. Each luminaire has three (3) 32W 48 T8 fluorescent lamps. Manufacturers data shows that the initial lumen output of the lamp is 2900 lumens. What is the total lamp lumen output (TOTAL)?

    (TOTAL) = 2 luminaires x 3 lamps/luminaire x 2900 lumens/lamp= 17,400 lumens

  • 2Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Coefficient of Utilization (CU)Coefficient of Utilization (CU)Factors influencing coefficient of utilization:

    The efficiency of the luminaireThe luminaire distributionThe geometry of the spaceThe reflectances of the room surface

    Each luminaire has its own CU table specific to that luminaires light distribution and efficiency. CU values are listed in tables for different room geometries and room surface reflectances.

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Coefficients of Utilization (CU)Coefficients of Utilization (CU)Coefficient of utilization is based on room cavity ratio (RCR)RCR is five (5) times the ratio of total vertical surface area to total horizontal surface area within the room cavity, and therefore indicates the relative space proportions.

    Where, hRC = Room cavity heightL = Length of the roomW = Width of the room

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Coefficients of Utilization (CU)Cavity ratios :

    Ceiling cavity ratio is the space between the ceiling and luminaire plane computed using the equation below in relation to room cavity ratio:

    Floor cavity ratio is the space between the workplane and the floor computed using the equation below in relation to room cavity ratio:

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Coefficients of Utilization (CU)Coefficients of Utilization (CU)Cross section of a room showing room cavities.

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Coefficients of Utilization (CU)For a given room, the cavity ratios are in direct proportion to their respective cavity heights. For the case where the luminaires are mounted on the surface of the ceiling or are recessed into the ceiling, the ceiling cavity ratio is zero.

    Since the coefficient of utilization is based on the room cavity ratio, it is necessary to treat this cavity as if there were a ceiling surface at the luminaire plane and a floor surface at the workplane level.

    It is necessary to convert the actual ceiling reflectance into an effective ceiling cavity reflectance (pCC) and the actual floor reflectance must be converted to an effective floor cavity reflectance (pFC).

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    CU DeterminationCU DeterminationUsing Example 1 above, the following steps should be followed incalculating the coefficient of utilization.

    Step 1. Determine the room cavity ratio using the equation below

    Room cavity height (hRC) = Luminaire height Workplane height

    Assuming a workplane height of 0.76m (typical desk height)

    hRC = 2. 59 m 0.76m= 1.83m

  • 3Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    CU DeterminationCU DeterminationIn this example, the luminaires are recessed in the ceiling so the luminaire height is the as the ceiling height. Computing the room cavity ratio, we have:

    RCR = 5 x Room cavity height (Length + Width)

    Length x Width

    RCR = 5 x 1.83m (3.05m + 4.57m)

    3.05m x 4.57m

    RCR = 5

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    CU DeterminationCU DeterminationStep 2. Since the Lumen Method considers what occurs only within the room cavity, the ceiling and floor cavities are replaced with their effective reflectances.

    To find the effective reflectance of a floor or ceiling cavity, find the floor cavity ratio and ceiling cavity ratio using the equations below

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    CU DeterminationCU DeterminationStep 3. Find the effective cavity reflectances using cavity surface reflectances. The surface that is opposite the opening to the cavity is called the base cavity. The base reflectance, the wall reflectances, and the cavity ratio determine the effective cavity reflectance. Using the IESNA Lighting Handbook, look for the cavity reflectances and cavity ratios.

    For the ceiling cavity, the base reflectance is the actual ceiling surface reflectance while the floor cavity, the base reflectance is the actual floor surface reflectance.

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    CU DeterminationCU Determination

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    CU DeterminationCU DeterminationStep 4. Once all room cavity reflectances and the room cavity ratio are known, the CU value can be determined by selecting the appropriate value from the luminairesCU table. Continuing with Example 1, the following assumptions are made after consulting the IES Lighting Handbook Table on Effective Reflectances:

    Effective Ceiling Cavity Reflectance, CC = 0.70Wall Reflectance, W = 0.50Effective Floor Cavity Reflectance, FC = 0.20 RCR = 5 (calculated in Step 1)

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    CU DeterminationCU DeterminationCU = 0.50, which means that 50% of the lumens given off by the lamps reach the workplane and the other 50% are absorbed by the luminaire or the room surfaces and never reach the workplane.

  • 4Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Coefficients of Utilization for Some LuminaireCoefficients of Utilization for Some Luminaire

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Light Loss FactorTwo types of Light Loss Factor (LLF)

    RecoverableNon-recoverable

    Total Light Loss Factor (LLF) is the product of the individual light loss factors, recoverable and non- recoverable

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Light Loss FactorLight Loss FactorRecoverable LLF

    Lamp Lumen Depreciation (LLD)Lamp Burnout Factor (LBO)Luminaire Dirt Depreciation Factor (LDD)Room Surface Dirt Depreciation Factor (RSDD)Area of workplane (AWP)

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Lamp Lumen DepreciationLamp Lumen DepreciationThe lamp lumen depreciation factor is the fraction of initial lumens at a specific time during the life of the lampLamp lumen depreciation comes from aging and dirt accumulation on lamps, reflectors, lenses and room surfaces.Most lighting designs base calculations on maintained as opposed to initial lamp lumens

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Lamp Burnout FactorLamp Burnout FactorIf lamps are not replaced immediately after burnout, a lamp burnout factor should be applied to any analysis of the system.Unreplaced burned- out lamps will vary in quantity, depending on the kind of lamps and the relamping program used.This factor is simply the ratio of the number of lamps that would be burning o the total number of lamps in the system.

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Room Surface Dirt Depreciation

    Room Surface Dirt Depreciation Factor (RSDD) is influenced by:

    The amount of dirt in the environmentThe room cavity ratio (proportions of the room)Type of lighting equipment used

  • 5Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Room Surface Dirt DepreciationRoom Surface Dirt Depreciation

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Luminaire Dirt DepreciationLuminaire Dirt Depreciation Factor (LDD) depends on three (3) aspects of the situation:

    The amount and type of dirt in the environment (a clean office environment compared to a dirty manufacturing facility)The type of luminaire usedThe expected cleaning cycle for the equipment

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Luminaire Dirt DepreciationLuminaire Dirt Depreciation

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Area of Area of WorkplaneWorkplaneIs the area of the entire workplane, which is typically the same as the floor areaIlluminance will be greatest near the center of the room and slightly less toward the walls for a given uniform layout of luminaires

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Light Loss FactorLight Loss FactorNon- Recoverable LLF

    Luminaire Ambient Temperature FactorHeat Extraction Thermal FactorVoltage to Luminaire FactorBallast FactorBallast Lamp Photometer FactorEquioment operating FactorLamp Position (Tilt) FactorLuminaire Surface Depreciation Factor

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Luminaire Ambient TemperatureLuminaire Ambient TemperatureVariations in temperature, above those normally encountered in interiors, have little effect on the output of incandescent and high intensity discharge (HID) lamps, but can have a significant effect on light output of fluorescent lamps

  • 6Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Heat Extraction Thermal FactorHeat Extraction Thermal FactorHeat extraction factor is the fractional lumen loss or gain due to airflowAirflow has an effect on lamp temperature and lamp lumens especially those air handling fluorescent luminaires which are integrated with the HVAC system as a means of introducing or removing air from the room

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Voltage to Luminaire FactorVoltage to Luminaire FactorHigh or low voltage at the luminaire will affect the lumen output of lampsHigh voltage condition will increase the lumen output of lamps over their rated outputLow voltage condition will reduce the lumen outputThe rate of change of lumen output with a voltage change varies with each light source, but has the greatest effect on incandescent lamps

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Ballast FactorBallast FactorBallast used for a specific application is usually different from the ballast used to determine the rated lumen output for a lampBallast factor corrects this difference to maintain the arc within the lampBallast factor is the ratio of the lamp lumens generated on commercial ballasts to those generated on the test quality ballasts . The ballast factor for good quality fluorescent ballast is nominally is 0.95while electronic ballasts can have ballast factors ranging from 0.70 to 1.28

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Ballast Lamp Photometer FactorBallast Lamp Photometer Factor

    Ballast Lamp Photometer Factor adjusts the lumen output when a different lamp ballast combination is used other than the manufacturers set- upTemperature effects within the luminaire may cause the lamp to operate at less than the rated output and should be considered in the determination of the luminaires coefficient of utilization

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Equipment Operating FactorEquipment Operating FactorEffects on the lumen output of lamps caused by the ballast, the lamp operating position and the effect of power reflected from the luminaire back onto the lamp are collectively incorporated into the equipment operating factor

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Lamp Position FactorLamp Position FactorLumen output is sensitive to the lamp orientation especially for high intensity discharge (HID) lamps when they are tilted from their rated horizontal or vertical positionLamp position factor adjusts the lumen output and is defined as the ratio of luminous flux in the given operating position to that in the test position

  • 7Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Luminaire Surface DepreciationLuminaire Surface DepreciationLuminaire surface depreciation results from adverse changes in metal, paint and plastic components that result in permanently reduced light outputLuminaire surface depreciation factor adjusts light output to original reflectance

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Loss Factor DeterminationLoss Factor DeterminationExample 2. LLF Determination

    Detailed description of the determination of the light loss factors can be found in the IESNA Lighting Handbook. The product of the recoverable factors and the non-recoverable factors will give us the total light loss factor.

    Recoverable Factors

    Lamp Lumen Depreciation (LDD) 0.90

    Lamp Burnout Factor (LBO) 1.00

    Luminaire Dirt Depreciation Factor (LDD) 0.94

    Room Surface Dirt Depreciation Factor (RSDD) 0.96

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Loss Factor DeterminationLoss Factor DeterminationNonrecoverable Factors

    Ballast Factor 0.93

    Other Non Recoverable Factors 1.00

    LLFTOTAL = Recoverable Factors x Nonrecoverable Factors

    LLFTOTAL = 0.90 x 1.00 x 0.94 x 0.96 x 0.93 x 1.00

    LLFTOTAL = 0.75

    Total Light Loss Factor (LLF) is 0.75, which means that 25% (100%-75%) of the luminous flux that might otherwise reach the workplane is lost due to ballast factor, dirty luminaires, room surfaces, and aged lamps.

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Calculated IlluminanceCalculated Illuminance

    (TOTAL) x CU x LLF

    AwpEwp

    At this point it is possible to calculate the illuminance on the workplane:

    Ewp = average maintained illuminance on the work plane

    (TOTAL) = total system lamp lumen output

    CU = coefficient of utilization

    LLF = light loss factor

    Awp = area of the work plane

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Calculated IlluminanceSubstituting all the computed values in Example 1and using the equation for average illuminance on the workplane, we have:

    EWP = 17,400 lm x 0.50 x 0.75

    3.05m x 4.57m

    = 468 lm/m2 or 486 lux (Maintained)

    The average initial illuminance on the workplane can be determined by substituting only the non-recoverable light loss factors for the total light loss factor.

    EWP = 17,400 lm x 0.50 x 0.0.93

    3.05m x 4.57m

    = 581 lm/m2 or 581 lux (Initial)

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Calculated IlluminanceCalculated IlluminanceAn average maintained illuminance of 468 lumens per square meter will strike the area covered by the workplane in a completely empty spaceSome points on the workplane will have an illuminancehigher than 468 while others will have an illuminancelower than this valueDuring first time that this system will be turned on, wherein the lamps are new and the surfaces are clean, the average initial illuminance will be greater than the maintained value, which is computed as 582 lumens per square meter (lux)

  • 8Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Calculated IlluminanceBy rearranging the Lumen Method equation, it is possible to find the number of luminaires required to meet a specific average illuminance level:

    (lumens/lamp) x (lamps/luminaire) x (no. of luminaires)x CU x LLFTOTAL

    EWP = AWP

    AWP x EWPNo. of = luminaires (lumens/lamp) x (lamps/luminaires)

    x CU x LLFTOTAL

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Calculated IlluminanceCalculated IlluminanceExample 2. Find the number of luminaires needed in a room given the following:

    Room dimensions: 9.15m by 9.15m by 3.5m

    Target Illuminance: 300 lux average maintained

    Working Plane Height: 0.76m

    Luminaire: Recessed round

    Lamp: 70 watt metal halide, 5600 lumen initial output

    Reflectances (): Ceiling cavity 0.70Walls 0.30

    Floor Cavity 0.20

    Assume LLFTOTAL = 0.75

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Calculated IlluminanceCalculated IlluminanceStep 1. Calculate RCR

    Using the equation for RCR, we get 3 as the answer.

    Step 2. Determine Cavity ratios for ceiling and floor

    Step 3. Obtain Effective Ceiling Cavity Reflectance (CC) using Tables in CU determination for metal halide lamps

    Step 4. Obtain Effective Floor Cavity Reflectance (FC) using Tables in CU determination for metal halide lamps

    Step 5. Obtain Coefficient of Utilization (CU) from Manufacturers Data

    The CU based on calculated value of RCR and the given reflectances, we get 0.55 as the answer.

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Calculated IlluminanceCalculated IlluminanceUsing the equation below, and substituting all the known values:

    Number of luminaires = AWP x EWPlumens/lamp x lamps/luminaires x CU x LLFTOTAL

    Number of luminaires = 9.15m by 9.15m by 3.5m x 300 lux

    5600 lumen x 1 x 0.55 x 0.75Number of luminaires = 10.9

    In this example, 12 fixtures can be spaced uniformly in a 3 by 4 pattern. Although 12 is more than the calculated value of 10.9 fixtures, results within a 10% margin is generally acceptable for meeting this target criterion

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Spacing CriteriaSpacing Criteria

    Spacing Criteria is the maximum ratio of spacing to mounting height of the luminaire above the workplane that provides reasonable uniformity of illumination within the space

    Spacing ratios for specific luminaires are given in the data sheets published by each manufacturer. This number, usually between 0.5 to 1.5, when multiplied with the mounting height, gives the maximum distance that the luminaires maybe separated and provide uniform illuminance on the workplane

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Spacing CriteriaSpacing CriteriaFor luminaires using essentially point sources of light, such as incandescent or HID lamps, the number of luminaires per row should be in proportion to the width-to-length ratio of the room

  • 9Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Spacing CriteriaSpacing CriteriaFor fluorescent luminaires, it is necessary to first establish the

    maximum number that can be installed in one row. the maximum number is calculated by subtracting at least 0.3 meter from the room length and then dividing by the length of the luminaire.

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Spacing CriteriaSpacing CriteriaThe exact spacing between rows is calculated by dividing the room width by the number of rows

    Spacing between luminaires in each row is calculated by dividing the room length by the number of luminaires per row.spacing between the outer luminaires and the adjacent wall is one-half of the luminaire spacingIf desks or other work areas are to be located alongside the walls, then the wall-to-luminaires spacing should be reduced to one-third of the luminaire spacing

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Spacing CriteriaSpacing Criteria

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Illuminance at a PointIlluminance at a Point--Direct ComponentDirect Component

    Examples:What is the illuminance on a wall display from a spotlight aimed at the display?How much light is striking a point on the faade of a building or in a parking lot from a floodlight?

    Factors to considerLuminous intensityDistanceOrientation of the surface

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Luminous IntensityLuminous Intensity

    I

    w

    dw

    Luminous Flux in a certain direction, radiated per unit of solid angle

    Unit : Candela

    Symbol : II = Luminous flux

    Solid Angle=

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Luminous IntensityLuminous Intensity

    Rotational symmetrical

    Light distribution same in all planes

    Usually Circular or Bowl shaped luminaire

  • 10

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Luminous IntensityLuminous Intensity

    Planar symmetrical

    Luminaire distribution is confined to two vertical planes separately

    Typical distribution for Fluorescent Lamp luminaires and Road Lighting

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Luminous IntensityLuminous Intensity

    Asymmetrical

    Asymmetry present in one of the Planes of measurement.

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    DistanceDistanceDistance between a surface and the source affects the illuminance (luminous flux per unit of area) striking that surfaceSurface of a given area that is closer to the source captures a larger portion of the flux in the cone than a surface of the same given area that is further awayConsidering the luminous intensity as the luminous flux (lumens)leaving a source in a cone traveling in a specific direction, as the area increases the iluminance decreases while the luminous flux remains the sameInverse Square Law states that the cross-sectional area of the cone increases with the square of the distance from the source. Therefore, the illuminance on this surface varies inversely with the square of the distance from the source

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    DistanceDistance

    PA

    w

    Light Source

    Solid Angle

    Plane

    Distance

    d

    E = I/ d2

    I

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    DistanceDistanceInverse Square Law

    E = I/ d2

    Where:

    E = Illuminance on the surface

    I = Luminous intensity of the source in the direction

    of the surface

    d = Distance from the source to the surface

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Orientation of the SurfaceOrientation of the SurfaceSurface orientation is included in the Inverse Square Law by adding a cos term:

    E = I/ d2 cos

    is the angle between the light ray coming from the source to the point, and a line that is perpendicular (normal) to the plane or surface on which the illuminance is being measured or calculated

  • 11

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Orientation of the SurfaceOrientation of the Surface

    P

    Light Source

    Plane

    Distance, dCosine LawCosine Law

    IE = I / d2 cos E = I / d2 cos

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Illuminance at a PointIlluminance at a Point--Direct ComponentDirect Component

    Example 1. This example will consider the illuminance at a single point on a horizontal surface from a single luminaire straight down. An assumed LLF of 0.85 will be used.

    D = 2.13 m

    = 15LLF = 0.85

    I = 2200 candelas

    The luminous intensity (I) is determined using the photometric data for the specific luminaire used and the angular relationship between the luminaire aiming direction and the direction from the luminaire to the calculation point.

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Illuminance at a PointIlluminance at a Point--Direct ComponentDirect Component

    Using the equation;

    E = I/ d2 x cos x LLFTOTALE = 2200 cd x cos 15 x 0.85

    2.13 m2

    E = 398 lux (maintained)

    This tells us that 398 lux will strike the point in question directly from the luminaire and no reflected light is calculated. The answer is a maintained illuminance level since a light loss factor of 0.85 was included to account for the loss of light over time due to reduced lumen output of the lamp and dirt on the luminaire surfaces.

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Illuminance at a PointIlluminance at a Point--Direct ComponentDirect Component

    Example 2. This example will consider the illuminance at a single point on a horizontal surface from two luminaires aimed straight down. An assumed LLF of 0.85 will be used and Luminaire #1 is the same inExample 1.

    D1 = 2.13m 1 = 15D2 = 2.29m 2 = 251 = 15 I1 = 2200 cd2 = 25 I2 = 2000 cdE1 = 398 lux (from previous calculation)

    E2 = 291 lux (from calculations)

    ETOTAL = E1 + E2 = 689 lux

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Illuminance at a PointIlluminance at a Point--Direct ComponentDirect Component

    Example 3. This example will consider the illuminance at multiple points on a vertical surface from a luminaire aimed at the surface. An assumed LLF of 0.85 will be used.

    Table 1. Components of Example 3

    The luminaire is now aimed at the vertical surface so is no longer measured from straight down, and and are no longer equal. Illuminance is calculated using the same equation as the prior examples.

    194 lux0.85210011562.293893 lux0.85222518271.372463 lux0.8523000451.741

    EmaintainedLLFICCDistance, mPoint

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Illuminance at a Point-Direct Component

    In Table 1, illuminance at point 2 is greater than at point 1 and illuminance at point 3 is the least. This is because the distance at point 2 is less than point 1 and the angle theta ( ) at point 2 is less than at point 1, despite the fact that the intensity in that direction is less.

    Similar reasoning can be used with regard to point 3. These two factors cause the illuminance at point 2 to be greater than the illuminance at point 3.

  • 12

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample Calculations

    The calculations presented using various tables and figures are only meant to give the user of this module a general overview of the design of lighting system, showing individual steps from the selection of the recommended luminance level, to the design of lighting layout.

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsSample Calculation 1:

    The room to be lighted is as follows:

    Type of building : Commercial

    Area/activity : Drafting/tracing paper, low contrast

    Average age of worker : 35 years

    Demand for speed and/or accuracy : Important

    Task background reflectance : 75%

    Size of room : 10.0 by 13.25 meters; 2.91 m ceiling

    Height of work plane : 0.91 m

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsReflectance factors : Ceiling 80%, walls 50%, and floor 30%

    Luminaire type : Type 2, IES Lighting Handbook Table ; 300 mm

    wide with two lamps

    Lamps : 430 mA, 40 W, 1200 mm, warm white, rapid start tubular

    fluorescent lamps

    Atmosphere : Clean

    Interval between cleaning : 12 months

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsSolution:

    Step 1: Determine the recommended illuminance level:

    From Illuminance Table (IES Lighting Handbook) , the illuminance category is F.

    From the IES Lighting Handbook Table, the recommended level is 1000 lux

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample Calculations

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsStep 2: Draw a cross section of the room and determine cavity

    heights. Note there is no ceiling cavity.

  • 13

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsStep 3: Calculate the cavity ratios using Equations and indicate

    dimensions.

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsStep 4: Determine the effective floor cavity reflectance (pFC) from IES

    Lighting Handbook Table. Note that the effective ceiling cavity reflectance is the same as the actual ceiling reflectance.

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsStep 5: Determine the coefficient of utilization:

    It is necessary to interpolate for RCR = 1.75

    For luminaire 2, CC= 80% and W = 50%

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample Calculations30% 1.070 (from above)

    28% (interpolate) 1.056

    20% 1.00

    - Multiply by factor 0.9 as per note on IES Lighting Handbook Table for luminaire 2, 300 mm wide using two lamps.

    Final Coefficient of Utilization

    (CU) = 0.61 x 1.056 x 0.9 = 0.58

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsStep 6: Calculate the light loss factor (LLF):

    - Ballast factor = 0.95

    - LLD from IES Lighting Handbook Table is 84% (use 0.84)

    - From IES Lighting Handbook Table, luminaire 2 is category V.

    - LDD is 0.88

    - RSDD: the light output is all down (direct distribution) the luminaire is direct. From the graph in IES Lighting Handbook Table , for a clean atmosphere at 12 months, the percent expected dirt depreciation is 12%(use10%) and RSDD is 0.98.

    LLF = 0.95 x 0.84 x 0.88 x 0.98 = 0.69 (two figure accuracy is acceptable)

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample Calculations

  • 14

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsStep 7: Calculate the total initial lamp lumens (TILL) using the

    equation below:

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsStep 8: Calculate the required number of luminaires using equation

    below. From IES Lighting Handbook Table, the initial lumens are 3175 and there are two lamps per luminaire.

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsStep 9: Select a practical layout for the luminaire:

    - Assume continuous rows are required

    - Calculate the maximum number per row lengthwise in the room as in figure below for 1200-mm long luminaires.

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample Calculations

    - Number of rows required is 52/10 = 5

    - Select 5 rows of 10 = 50

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsStep 10: Calculate the luminaire spacing using the figure below:

    Sw = 10/5 = 2.0 m

    Total length of each row = 10 x 1.2 = 12.0 m

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample Calculations

  • 15

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsStep 11: Check the maximum spacing allowed between rows:

    - From the IES Lighting Handbook Table, for luminaire 2, SC is 1.4 for crosswise spacing.

    - Maximum spacing = 1.4 x hRC = 1.4 x 2.0 = 2.8 m

    - 2.0 m is within the limits

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsStep 12: Draw plan of the room and indicate the locations of

    luminaires

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsStep 13: Calculate the actual minimum maintained lighting level:

    (within 4% of target value)

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsStep 14: Calculate the unit power density (UPD); From the IES

    Lighting Handbook table, the power input to the ballast for each luminaire (two 430 mA, 1200 mm lamps) is 95 watts.

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsThe unit power density (UPD) of 35.85 W/m2 (3.33 watts per

    square foot) is high. Before the advent of the energy shortage, this value was accepted as normal. Todays practices, however dictatethat the lighting load be kept as low as possible by using energy-saving lamps and ballast.

    In this example, the designer should start over with F32T8 or F36T8 lamps operated with electronic ballasts and go through thecalculations again to reduce the UPD.

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsSample Calculation 2. Illustrations in calculating illumination levels

    (Lux) on certain lighting layout configurations:

    Illumination of a conference room with OSRAM DULUX CARR EL/D

    2 x 24 W, with two DULUX L 24 W compact fluorescent lamps.

    Room dimensions:

    L = 15.00 m (length)

    W = 8.00 m (width)

    H = 3.40 m (ceiling-to-floor height)

    h = 2.55 m (luminaire-to-work plane height)

  • 16

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsRequired quality of light:

    Conference room: Light color ww or nw, Ra group 2A

    Illuminance

    E = 300 lux

    Selected lamp:

    2 DULUX L 24 W,

    Light color LUMILUX Warm

    (LF 31/830), Ra group 1B,

    Luminous flux per lamp

    n= 1800 lumen

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsLighting design data is available in EULUMDAT format for most OSRAM luminaires. EULUMDAT data can be read by a wide range of programs for lighting design, including DIALUX (Version 2.0 and higher), RELUX, SPECTRAL n LUMAGIC and RADEMACHER BELWIN.The table below shows the room utilization factor for numerous combinations of room factors and reflectances(always assuming ideal dispersion). The illuminance E required in a room of area L x W is achieved with n luminaires that have an efficiency LBand with lamps with a luminous flux .

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample Calculations

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsLuminaire efficiency and light distribution:

    OSRAM DULUX CARR EL/D 2 X 24 W

    Light distribution A40.2 hLB = 0.58

    Reflectances:

    Ceiling = 0.8

    Wall = 0.5

    Work surface = 0.3

    Room utilization factor:

    From the LiTG Table

    For A40.2 (Table 1)

    R = 0.91

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsCalculation:

    Result:

    24 luminaires ( is rounded up)

    Recommended arrangement:

    3 rows of 8 luminaries

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample Calculations

  • 17

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsSample Calculation 3. Given are the following :

    Width = 15 m

    Length = 100 m

    Ceiling height = 3.5 m

    Desired Illumination = 400 lux

    Type of Luminaire = 200mf Downlight w/ 26W TC-D Lamp

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsGeneral Information:

    Project Identification: Shopping Mall

    Average maintained Illuminance: 400 lux or 400 lux /1lux x 10.76fc

    = 37.17 fc

    Lamp data: 26W TC-D (compact fluorescent lamp)

    Lamp flux: 1800 lumen (as per manufacturers data)

    Luminaire data:

    Manufacturer: Zumtobel Staff (Fumaco)

    Model No: Panos HG 2/26W TC-D VVG 200

    w = 50%

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsSelection of Coefficient of Utilization:

    Step 1: Fill in all information in sketch

    L (Length) = 100 m

    W (width) = 15 m

    h (height) = 3.5 m

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsStep 2: Determine Cavity Ratio

    If from manufacturers data, CU table are given based on Room Cavity Ratio

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsIf from manufacturer's data, CU table are given based on Room Index

    where:

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsStep 3: Obtain effective cavity reflectance:

    Ceiling : cc = 70%

    Wall : w = 50%

    Floor : fc = 20%

  • 18

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsStep 4: Obtain Coefficient of Utilization from manufacturer's data:

    Based on Fig. 9-28 of IESNA Handbook @ RCR 1.34 @ 70/50/20 reflectance

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample Calculationsby interpolation CU @ 1.34:

    RCR = 0.64

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsStep 5: Compute for the Light Loss Factor (LLF)

    LLF = Ballast factor x LLD x LDD x RSDD

    Ballast Factor = 0.95

    LLD (as per Figure 6.3 of IESNA Handbook) = Lumen maintenance (LLD) of compact fluorescent lamp double Biax (TC-D) is LLD =

    85%

    LDD under luminaire maintenance category I @ very clean room using Table 6-2 where maintenance frequency is every 12 months LDD = 0.96

    Since luminaire is Direct downlight (as per Figure 6.4 of ELI handbook) % Room Surface Dirt Depreciation (RSDDF) is = 12%

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample Calculations

    by Interpolation, x = 0.976 (RSDD)

    LLF = 0.95 x 0.85 x 0.96 x 0.976

    LLF = 0.76

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsStep 6: Compute for Initial Lamp Lumens (TILL) using equation below:

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsStep 7: Calculate the required no. of luminaries using equation below. From table lamp manufacturers data, the initial lamp lumens of 26W TC-D lamp = 1,800 lumens

  • 19

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsStep 8: Select a practical lay out for the luminaire.

    Spacing Criterion, SC = spacing distance/mounting height

    As per Figure 9-28 of IESNA Handbook, for 8" open reflector using 2-26 CFL, SC = 1.5

    Spacing distance = 1.5 x 3.5 m = 5.25 m

    For this distance, 343 luminaires required to achieve 400 luxillumination cannot be placed for the given area.

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsStep 9: Calculate Luminaire Spacing

    Number of luminaires per row = (15m-5.25m)/5.25 = ~ 2

    Number of luminaires per column = 343/2 = 172 luminaires x 5.25 m (spacing) = 903 m which exceeded 150 m.

    Spacing criterion with this case is not applicable

    Assuming spacing at end rows = 1 m

    Number of luminaires/row = 15-2(1)/2 = 6.5 ~ 7 luminaires/row

    Transverse spacing = 15-2(l)/6= 2.17 m

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample Calculations

    Total length at each row = 6 x 2.17 m = 13 m

    Space at end rows = 15-13/2 = 1 m

    Number of luminaires/column = 343/7 = 49 luminaires/column

    Longitudinal spacing = 100-2(1)/48 = 2.04 m

    Total length at each column = 48 x 2.04 m = 98 m

    Space at end rows = 100m-98m/2 = 1 m

    Total luminaires = 7 x 49 = 343 luminaires

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsStep 10: Draw plan of the room and indicate the locations of luminaries:

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsStep 11: Calculate the actual minimum maintained lighting level:

    E = 343/343 x 400 lux = 400 lux (within the target value)

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsStep 12: Calculate the power density (UPD) or connected load.

    From manufacturers data, the power consumption of 2 x 26W TC-D lamp using conventional ballast = 90watts, in using electronic ballast = 70 watts

  • 20

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsSample Calculation 4. Given the following data:

    Width = 15 m

    Length = 100 m

    Ceiling height = 3.5 m

    Desired Illumination = 400 lux

    Type of Luminaire = 200mf Downlight w/ 26W TC-D Lamp

    Luminaire : 8" Downlight with 70W Metal Halide Lamp

    Lamp Flux : 6600 lumens (from manufacturers data) from Table (Figure 9-28) of IESNA handbook CU of metal halide downlight #10 @ 70/50/20 reflectance & RCR of 1.34

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample Calculations

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsCompute for the Light Loss Factor (LLF)

    LLF = Ballast factor x LLD x LDD x RSDD

    Ballast factor = 0.95

    LLD of metal halide lamp = 0.85

    LDD = 0.96

    RSDDF = 0.976

    LLF = 0.95 x 0.85 x 0.96 x 0.976

    LLF = 0.76

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsCompute for the the total initial lamp lumens (TILL)

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsCompute for the number of luminaires

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsCompute for the number of luminaires/row

    Spacing Criterion = 1.2, does not apply since total of 179 luminaires cannot be placed on the given area.

    Assuming spacing criterion = 0.9

    Spacing distance between luminaries = MH x SC

    Spacing (Longitudinal) = 3.5 m x 0.9 = 3.15

    Number of luminaires/column = 100/3.15 = 31 luminaires

    Total length of column = 31 x 3.15 = 97.65 m

    Space at end of column = (100-97.65)/2 = 1.175 m

    Total luminaires at each row = 179/31 = 5.7 ~ 6 luminaires

  • 21

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsTransverse spacing = 15m - 2(1.175m)/5

    = 2.53 m

    Total length of each row = 5 x 2.53m

    = 12.65 m

    Space at ends of row = (15 - 12.65)/2

    = 1.175m

    Total number of luminaries = 6 x 31

    = 186 luminaires

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsDraw plan of the room and indicate the locations of luminaries.

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsCalculate the actual maintained lighting level.

    Philippine Efficient Lighting Market Transformation Project (PELMATP)

    Module 4 Lighting Calculations

    Sample CalculationsSample CalculationsCalculate the unit power density (connected load), from lamp manufacturers data, the power input of 70W metal halide lamp

    = 81.5 Watts.