Outline
• Project Overview• Proposed Solutions• Accepted Solutions• Issues Encountered /Lessons Learned• Conclusion
2
![Page 3: Lighting Based Energy Efficiency Upgrades - Lessons Learned](https://reader035.fdocuments.in/reader035/viewer/2022062814/56816807550346895ddd8a37/html5/thumbnails/3.jpg)
Project Overview• ARRA-funded lighting
replacement and controls upgrade for GSA
• Project dates: January 2010 through August 2012
• Building size: Eight federal courthouses & office buildings in Alabama and Georgia, ~2.5 million ft2 combined.
• Four designs taken to implementation
3
![Page 4: Lighting Based Energy Efficiency Upgrades - Lessons Learned](https://reader035.fdocuments.in/reader035/viewer/2022062814/56816807550346895ddd8a37/html5/thumbnails/4.jpg)
Diverse Building Characteristics
• Ages– historical(1932) to modern (2002)
• Sizes– 100,000 SF to over 1million SF– 5 floors to 25 floors
• Uses– call centers, courtrooms, private offices, large
open offices, prisoner holding areas, etc.
4
![Page 5: Lighting Based Energy Efficiency Upgrades - Lessons Learned](https://reader035.fdocuments.in/reader035/viewer/2022062814/56816807550346895ddd8a37/html5/thumbnails/5.jpg)
Proposed Solutions
• Luminaire Replacements• Spectrally Enhanced Lighting• Relamping• Delamping• Controls– Local – Global– Daylight Harvesting
5
![Page 6: Lighting Based Energy Efficiency Upgrades - Lessons Learned](https://reader035.fdocuments.in/reader035/viewer/2022062814/56816807550346895ddd8a37/html5/thumbnails/6.jpg)
Luminaire Replacement
• Primary ECM: 3 lamp 32WT8 replaced with 2 lamp 28WT5 – Improved energy
performance
• Parabolic luminaires replaced with volumetric luminaires– improved light distribution
with no “cave effect”
6
![Page 7: Lighting Based Energy Efficiency Upgrades - Lessons Learned](https://reader035.fdocuments.in/reader035/viewer/2022062814/56816807550346895ddd8a37/html5/thumbnails/7.jpg)
Spectrally Enhanced Lighting• Take advantage of
human perception of brightness
• Use lamps with higher Color Temperature /CRI Lamps (e.g. 5000K 82 CRI vs more common 3500K 75CRI) more like natural daylight
• Use lower light intensity (Fc)
• Increased visual acuity
7
![Page 8: Lighting Based Energy Efficiency Upgrades - Lessons Learned](https://reader035.fdocuments.in/reader035/viewer/2022062814/56816807550346895ddd8a37/html5/thumbnails/8.jpg)
Spectrally Enhanced Lighting
• Lower light levels (fc) result in equal visual acuity and perceived brightness
• http://www1.eere.energy.gov/femp/news/news_detail.html?news_id=10382
8
![Page 9: Lighting Based Energy Efficiency Upgrades - Lessons Learned](https://reader035.fdocuments.in/reader035/viewer/2022062814/56816807550346895ddd8a37/html5/thumbnails/9.jpg)
Relamping and Delamping
• Relamping– Replace older technology lamps (e.g.
incandescent) with newer, more efficient lamp types (e.g. CFL or LED), cost permitting
• Delamping– Remove lamps in over lit areas to comply with
recent energy guidelines (AHRAE 90.1)– Replace 3 lamp luminaires with 2 lamp luminaires
9
![Page 10: Lighting Based Energy Efficiency Upgrades - Lessons Learned](https://reader035.fdocuments.in/reader035/viewer/2022062814/56816807550346895ddd8a37/html5/thumbnails/10.jpg)
Improved Controls
• Local – Occupancy and Vacancy Sensors• Global – Building wide lighting controllers
(multiple OFF sweeps per day based on time)• Daylight Harvesting – Dimming or extinguishing lightings during times
of abundant natural light
10
![Page 11: Lighting Based Energy Efficiency Upgrades - Lessons Learned](https://reader035.fdocuments.in/reader035/viewer/2022062814/56816807550346895ddd8a37/html5/thumbnails/11.jpg)
Accepted Solutions
• Luminaire Replacements Retrofits• Spectrally Enhanced Lighting• Relamping• Delamping• Controls– Local – Global Rezoning– Daylight Harvesting
11
![Page 12: Lighting Based Energy Efficiency Upgrades - Lessons Learned](https://reader035.fdocuments.in/reader035/viewer/2022062814/56816807550346895ddd8a37/html5/thumbnails/12.jpg)
• Less costly than full luminaire replacements• Structural parts of the original luminaire remain• Kits still allow for
conversion from parabolic to volumetric
• Kits still allow for3 lamp to 2 lampconversion
Retrofit Kits
12
![Page 13: Lighting Based Energy Efficiency Upgrades - Lessons Learned](https://reader035.fdocuments.in/reader035/viewer/2022062814/56816807550346895ddd8a37/html5/thumbnails/13.jpg)
Rejection of SEL
• GSA disapproved SEL due to unproven nature of the approach
• GSA did approve conversion to consistent higher color temperature lamps (4100K vs 5000K for SEL and the original 3500K for most existing lamps)
13
![Page 14: Lighting Based Energy Efficiency Upgrades - Lessons Learned](https://reader035.fdocuments.in/reader035/viewer/2022062814/56816807550346895ddd8a37/html5/thumbnails/14.jpg)
Local Controls
14
DT Ceiling Mounted Sensor
PIRSwitchSensor
![Page 15: Lighting Based Energy Efficiency Upgrades - Lessons Learned](https://reader035.fdocuments.in/reader035/viewer/2022062814/56816807550346895ddd8a37/html5/thumbnails/15.jpg)
Rezoning
Goal is to reduce the number of lights energized for a single person or small group working in an area of the building outside of normal business hours.
With flour globally controllable zones per floor, only a quarter of a floor
15
![Page 16: Lighting Based Energy Efficiency Upgrades - Lessons Learned](https://reader035.fdocuments.in/reader035/viewer/2022062814/56816807550346895ddd8a37/html5/thumbnails/16.jpg)
Zone Layout
Existing wiring and cost restriction limited the project to two zones (vs proposed four) per floor. 16
![Page 17: Lighting Based Energy Efficiency Upgrades - Lessons Learned](https://reader035.fdocuments.in/reader035/viewer/2022062814/56816807550346895ddd8a37/html5/thumbnails/17.jpg)
ISSUES ENCOUNTERED ANDLESSONS LEARNED
17
![Page 18: Lighting Based Energy Efficiency Upgrades - Lessons Learned](https://reader035.fdocuments.in/reader035/viewer/2022062814/56816807550346895ddd8a37/html5/thumbnails/18.jpg)
Retrofit kits
• Kit Installation was an issues. Not all 2x4 recessed luminaires are created equal
• Historic building contained a large variety of luminaire styles and sizes• Some sites had “metric” 2x4 (600mm x 1200mm)• Had to resocket and reballast in some locations as kits would simply
not fit.
18
![Page 19: Lighting Based Energy Efficiency Upgrades - Lessons Learned](https://reader035.fdocuments.in/reader035/viewer/2022062814/56816807550346895ddd8a37/html5/thumbnails/19.jpg)
Occupancy and Vacancy Sensors• Sensor density (Cost vs. Coverage)• Ceiling height (wall mounted vs ceiling mounted)• High walled cubicles• “Added” walls during remodel• Doors, furniture and other obstructions• White noise generator• Sensor settings
– Occupancy mode (auto on) or vacancy mode (manual )– Dual Tech trigger setting (e.g. both to trigger on, either to hold on)– Time delay settings– Sensitivity
19
![Page 20: Lighting Based Energy Efficiency Upgrades - Lessons Learned](https://reader035.fdocuments.in/reader035/viewer/2022062814/56816807550346895ddd8a37/html5/thumbnails/20.jpg)
General
• Wiring– Renovations make existing circuits poor zone
choices for control zones (local or global)– Wiring not up to code– No neutrals a switch location (can’t use most