Liebert® GXT4™ 700VA - 3kVAIntelligent, Reliable UPS Protection

poweronaustralia.com.au 1300 662 435

Liebert® GXT4TM is a true on-line UPS that delivers continuous, high-quality AC power to connected equipment with no interruption when transferring to battery. It protects equipment from virtually all power disturbances due to blackouts, brownouts, sags, surges or noise interference.

For robust UPS protection up to 3kVA, the Liebert GXT4 UPS provides industry leading features in a compact design:

• On-line design means zero transfer time. When utilitypower fails, your critical load remains supported by aseamless �ow of power

• Active Eco Mode deliver best in class ef�ciency up to97% without compromising availability.

• Controllable power to multiple devices via twoindependently programmable pairs of outlets.

• ENERGY® STAR Certi�ed rating.• Intuitive color LCD interface

• User replaceable, hot-swappable batteries.

• Arrays of value added accessories bundled withstandard unit

Emerson Network Power offers a full range of power protections solutions suitable for every requirement or scenario. From desktop computing, network equipment, computer rooms to large scale data centers. we make sure you get the same level of protection the Fortune 500 companies enjoy with Emerson. It is our way of Bringing Enterprise Level IT expertise to your SMB.

Desktop

• Liebert PSP

• Liebert PSA

Network/Computer Room• Liebert PSI• Liebert GXT4• Liebert ITA

Data Center• Liebert ITA• Liebert NX• Liebert APM

Bringing our Enterprise Level IT Expertise to your SMB

The Liebert® GXT4TM UPS may require just a slim 2U of rack space, still it provides the capabilities often found only in larger systems. Get up to 3kVA of capacity and battery backup. External battery cabinets may be added for extended run time

• Power factor correction

• Internal batteries

• Frequency conversion

• Internal automatic bypass to protect against adverse conditions

• Manual bypass capability

• Support for up to six external battery cabinets

Libert GXT4 UPS includes:

ENERGY STARCertified® UPS models

Flexibility:

• Two Programmable OutletsCan be programmed for load sheddingand sequential restart if the UPS is inoverload or when selected backup timeremains

• Intuitive LCD Display PanelThe colored LCD display and controlpanel r otates 90 deg tore-adjust position matching t he UPSmount either on tower or rack.

• Automatic Frequency SensingThe UPS automatically adjusts to theinput frequency, 50Hz or 60Hz.

• Mounting FlexibilityRack rails and tower supports included

• Intelligent CommunicationsDCIM and BMS ready

The Protection You Need from Damaging power problems

Always Protected !

Pure Sine-Wave

Outages Sags Surges Spikes Noise

Transient FrequencyDeviation

Under-Voltage

Over-Voltage

Harmonics

On line, Double Conversion UPS For Best in Protection

DynamicBypass

UtilitySurge

Suppression

Power FactorCorrection/Recti�er

ChargerInverter Load

Battery

Liebert® GXT4TM UPS Flexible, Reliable and Low Total Cost Features

Liebert® GXT4TM UPS is a true on-line power source, which means power is always conditioned and supplied to the connected devices, whatever the quality of power coming in , a pure sinewave output results to ensure equipment is protected

High�Availablity:

• Advance Early Warning of UPS System StatusMultiple audible and visual alarms immediately alert you to critical issues.

• 3-11 minutes of Battery Backup Time at Full loadProvides ample time for an orderly shutdown.Optional matching external battery cabinets offeradditional backup time.

• Periodic Battery TestingProvides automatic and manual self-diagnosticbattery testing for peace of mind to indicate if thebattery is healthy

• Replaceable Hot Swappable BatteriesEasy to replace batteries to protect your investmentby extending the product life.

• Power-Factor CorrectionPrevents nosie, harmonics and distortion from beingpassed on to connected loads or from being fedback to the utility.

• Intelligent Battery ChargingIncludes efficient three-stage charging technique andcomprehensive discharging protection that extendbattery life

• Input Circuit BreakerProvides increased protection to ease recovery fromoverlaods

• Lightning and Surge ProtectionThe transient voltage surge suppression (TVSS)circuitry inside Liebert GXT4 UPS provides additionalprotection for the connected equipment

The Liebert GXT4 UPS contains internal batteries and supports up to six optional external battery cabinets that is only 2U thick to achieve longer backup times without taking up so much rack space.

Multiple Choices For Communication, Shutdown And ReportingWhen your computer system can�t be without power, even for scheduled UPS maintenance, the Liebert MicroPOD Maintenance Bypass and Output Distribution Unit ensures continuous uptime. It allows you to manually transfer connected equipment to utility power via a maintenance bypass switch, permitting scheduled service or UPS replacement without the need to shut down connected equipment. Features include:

• 2U height minimizes rack space requirements• Easy plug-and-play installation

Low total Cost Of OwnershipHigh Output Power

Liebert GXT4 UPS rated output power factor up to 0.9 better matches switch-mode power supplies used in today�s IT equipment, providing more ef�cient utilization of the UPS

Active ECO Mode

Connected equipment can be powered though the bypass while the inverter remains idle, reducing electricity consumption while raising ef�ciency up to 97% without compromise

Wide Input Voltage Window

Prolongs battery life by allowing the UPS to maximize the use of utility power before transferring to battery when input voltage exceeds speci�ed limits.

Intelligent Fan OperationAutomatically changes rotation speed depending on system requirements to decrease power consumption and Noise

Arrays of accessories with standard model Extended amount of accessories bundled with standard model saves capital expenses . such as Rail kit, IS-webcard etc.

POD configuration with UPSPOWERSOURCE MicroPOD

LOADEQUIPMENT

UPS

Liebert MicroPOD

Multiple Choices For Communication, Shutdown And ReportingSNMP And Web-Based Communication Options

Liebert IntelliSlot Web Card provides SNMP (including SNMPv3) and IPv.6 and web-based management to your Liebert GXT4 UPS. Provides ability to monitor and control your UPS from your network management system or any PC running Microsoft Internet Explorer.

• Sends both SNMP traps and emails for eventnoti�cation, and automatically emails a daily UPS history

• Auto-sens 10M/100M Ethernet

The Liebert GXT4 UPS is also fully compati ble with

• Liebert MultilinkTM shutdown software-includedwith the Liebert GXT4 UPS

• Liebert NformTM monitoring software• Liebert Multiport multiplexing unit• Liebert Intellislot Relay Interface Card• Liebert SiteScanTM

• TrellisTM Platform• USB Communications

While today�s smaller, rack-based UPS system offer relatively trouble-free operation, the growing criticality of the systems they support has increased the cost of downtime. As a result, the need to maintain these smaller UPS systems is increasingly important.

Extended WarrantyFive year protection plan with 100% parts coverage and 7x24 emergency service that assures long term worry-free maintenance and lower total cost of ownership(TCO)

Start-uphassle-free multi-site deployment management and offers convenience in the disposal of hazardous materials of existing UPS, when applicable

Preventive maintenanceTo increase equipment reliability thus higher availability

On-site serviceShould you experience a problem, we will dispatch a certi�ed Emerson Network Power Customer Engineer to repair or replace, your equipment, response guaranteed.

Our Extended Service packages offer you complete peace of mind

BatteryIndicator

InverterIndicator

FaultIndicator

LCD Panel

ESC Button

BypassIndicator

Programmable outlet1 indicator

Programmable outlet2 indicator

ECO mode indicator

ENTER button

UP button Down button

GXT4-UPS 3kVA

O/P : 230V 50Hz 11.7A I/P : 230V 50Hz 13.1A BATT :100%3MINS LOAD: 0%

USB PortLiebertInstelliSlot Port Input Circuit Breaker C14 Input

Outlet1 Receptacles (Programmable)

Outlet ReceptaclesProgrammable

GeneralOutput

External BatteryConnector

CoolingFan

Rs232 Port

DryrContacts

C20 InputProgrammable Outlets #1

ProgrammaOutlets #2

Non-Programmable Outlets

USB PortLiebertInstelliSlot Port

TerminalCommunications

CoolingFan

Rs232 Port

External BatteryConnector

Input Circuit Breaker

Output Circuit Breakers

Programmable Outlets #1

Programmable Outlets #2

USB PortLiebertInstelliSlot Port

TerminalCommunications

CoolingFan

Rs232 Port

External BatteryConnector

Input Circuit Breaker

GeneralOutput

Non-ProgrammableOutlets

Rear View 1500VA Rear View 3000VA

Rear View 2000VA

Intuitive and intelligent Operation

USB PortInput CircuitBreaker

LiebertInstelliSlot Port

Input ReceptacleProgrammable Output Receptacle #1-2

External BatteryConnector

CoolingFan

Rs232 Port

TerminalBlock

General Output Receptacle, 2

ProgrammableOutputReceptacle #2,2

Rear View 700VA-1000VA

Model Number

Used with UPS Model GXT4-700RT230,GXT4-1000RT230GXT4-1500RT230, GXT4-2000RT230

Dimensions, W x D x H, mm(in)Unit (with bezel)

Unit 32 (70.5)Battery ParametersType Valve-regulated, non-spillable, lead acidQuantity x V 2 x 4 x 12V x 9.0Ah

Operating Temp, °C (°F) 0 to 40 (32 to 104)Storage Temp, °C (°F) Relative HumidityOperating Elevation

-15 to 40 (19 to 104)0-95% non-condensing

Up to 3000m (10,000 ft.) at 40°C (104°F)

Agency

Safety IEC/EN/AS 62040-1:2008, GS markTransportation FCC PART 15, Class A=CISPR22 Class A

Load(%)

GXT4-48VBATT GXT4-72VBATT

GXT4-3000RT230

430 x 497 x 85 (16.9 x 19.7 x 3.3) 30 x 602 x 85 (16.9 x 23.6 x 3.3)

Environmental

42 (92.6)Weight, kg (lb)

2 x 6 x 12V x 9.0Ah

Operating Elevation 15000m (50,000 ft.) maximum

Safety IEC62040-2 2nd Ed.:2006Transportation ISTA Procedure 1E

Internal Battery

Internal Battery +1 External Battery Cabinet

700VA 1kVA 2kVA1.5kVA 3kVA

102030405060708090100

42730316414512610694786961

334166138108927256484037

33016012897725446383431

2221379466493934282320

3021399566484134272321

Load (%)

Internal Battery +2 External Battery Cabinet

700VA 1kVA 2kVA1.5kVA 3kVA

102030405060708090

100

408434329273203164153142

121

457333224166151135113103

78

4473151861511311079274

53

42620114912497756150

38

43120515012497766350

41

Load(%)

Internal Battery +3 External Battery Cabinet

700VA 1kVA 2kVA1.5kVA 3kVA

102030405060708090

100

480461439345323300213189163156

480442337305208166155144132122

4674243111991601461311119983

45132219515413611196786856

45532519615513611298797060

Load(%)

Internal Battery +4 External Battery Cabinet700VA 1kVA 2kVA1.5kVA 3kVA

102030405060708090100

480480458442425336319301213197

480460436340315218195165156147

480444340309205165153141130112

4664213061921571421271079580

4084233071921571431281099781

Load (%)

Internal Battery +5 External Battery Cabinet700VA 1kVA 2kVA1.5kVA 3kVA

102030405060708090

100

480480465452438425344329315301

480467447428341320227208189164

480457431333307208167158148139

480438331224189158146133120104

480440332225189159147135122106

Load(%)

Internal Battery +6 External Battery Cabinet700VA 1kVA 2kVA1.5kVA 3kVA

102030405060708090

100

480480480462451440428368336325

480480458442426341323306217201

480466444422328305209184161153

480450420319217486159148137126

480452421319217487160150139128

131 92 64 41 45

Load (%)

10

20

30

40

50

60

70

80

90

100

105

62

37

32

27

22

18

15

13

11

91

38

31

23

17

14

11

9

8

6

700VA 1kVA 2kVA

112

51

34

23

18

14

11

9

7

6

1.5kVA

81

37

23

13

12

9

7

5

4

3

91

39

23

16

12

9

7

5

4

3

3kVA

*Models Runtime measured in minutes (mIn.)

External Battery Specification

Battery Run-timee Chart

Input Power Receptacle

Charger Current,Amperes

Storage Temp

Operating Elevation

Audible Nosie

Operating Temp

Voltage

Frequency

Waveform

Output AC

Environment Parameters

Rating

Dimensions, W x D x H, mm (in)

Weight, kg (lb)

Mechanical Parameters

Voltage Range(typical)

Frequency Range

Output Receptacles

Input AC

230VAC nominal; variable based on output load

40Hz ~ 70Hz; Auto Sensing

C14 C20

Mains (AC)Mode Overload

C13 x 6 C13 x 6; C19 x 1

200/208/220/230/240VAC (user con�gurable); ±3%

50Hz or 60Hz

Pure Sinewave

The inverter shall be capable of supplying current and voltage for overloads exceeding 100%, and 105-130% for 1 minute, 131-150% 10 seconds, 151-200% for 1 seconds,

and up to >200% for 5 cycles of full load current.

1.3 1.88 2.71 2.5

Recharge Time

Battery

Type

Qty x V x Rating

Valve-regulated, nonspillable, lead acid

4 x 12V x 5.0Ah 6 x 12 x 9.0Ah

4 hours

4 x 12V x 9.0Ah3 hours to 90% capacity after full discharge with 100% load till UPS

auto-shutdown(Internal Batteries Only)3 hours

700VA/630W 1000VA/900W 1500VA/1350W 2000VA/1800W 3000VA/2700W

0°C to +40°C (+32°F to 104°F)

-15°C to +50°C (5°F to 122°F)

Up to 3000m (10,000 ft.) at 25°C (77°F) without derating

< 46 dBA at 1 meter(3.2ft) from the rear; < 43dBA, at 1 meter (3.2 ft)

from the front or side

< 45 dBA at 1 meter (3.2ft) from the rear; < 46dBA, at 1 meter

(3.2 ft) rear

< 48 dBA at 1 meter(3.2ft) from the rear;

< 48dBA, at 1 meter (3.2 ft) rear

Safety

Agency

Surge Immunity

RFI/EMI

IEC/EN/AS 62040-1:2008, GS MARK

IEC/EN/AS 62040-2 2nd Ed. ( Category C2) = CISPR22 Class A

IEC/EN 62040-2 2nd Ed ( IEC/EN 61000-4-5)

430x 497x 85(16.9 x 19.6 x 3.3)

430 x 408 x 85 ((16.9 x 16.2 x 3.4)

430 x 602x 85(16.9 x 23.7x 3.3)

18.2 (40) 23.2 (51.1) 25.5 (56.1) 32.4 (71.4)

GXT4-700RT230* GXT4-1000RT230* GXT4-1500RT230* GXT4-2000RT230* GXT4-3000RT230*

* Standard model includes the Rail kit for UPS and battery models

* Speci�cations are subject to change without any prior noti�cation

Liebert® GXT4 Technical Specicfications