LH Datasheet Moore Industries J - Signal Conditioners · lh / 1 / n / s [p] When ordering the LH...

2
Demand Moore Reliability LH Connection Heads for Head-Mount Instruments Perfect for Head-Mount Instruments The LH connection heads are ideal for use with head-mount transmitters such as Moore Industries’ TRX/TRY PC-Programmable and THZ 2 Smart HART ® Temperature Transmitters. The LH heads also protect terminal blocks used for sensor wire terminations. Safeguards Expensive Instruments Meeting NEMA 4X, IP66 ratings, both LH heads are resistant to ultraviolet rays and corrosive chemicals. Their high-impact materials protect instruments installed in harsh eld conditions. The LH2 features a locking cover safety mechanism. NPT, Metric and G½ (BSP) Entry Ports The dual entry port LH heads connect to standard conduit types and temperature assembly components. See Ordering Information for more information. Complete Temperature Assemblies We offer complete lines of transmitters, RTDs, thermocouples, thermowells, connection heads and ttings at competitive prices. For information, ask your Moore Industries Sales Engineer. For Explosion-Proof, Hazardous and General Locations Available LH models meet standards for enclosing indoor and outdoor electronic instruments that are approved for use in Explosion-Proof, Intrinsically-Safe and Non-Incendive locations. April 2016 Complete temperature assembly features LH connection head with standard black cover. Factory Mutual Approvals Explosion-Proof* Class I, Division 1, Groups A*, B, C, D Dust-Ignition Proof Class II & III, Division 1, Groups E, F, G NEMA 4X; IP66 ATEX Directive 2014/34/EU (ISSeP): Flameproof II 2G Ex d IIC II 2D Ex tD A21 IP66 Test Safe - ANZEx (Australia) Flameproof Ex d IIC T6 (Tamb 60°C) IP66 ANZEx 07.3027 CSA International Explosion-Proof* Class I, Division 1, Groups A*, B, C, D Class II, Division 1, Groups E, F, G Class III, Division 1 IP66 Factory Mutual Approvals NEMA 4X; IP66 LH1 Certications LH2 Certications *Group A only: Seal all conduit within 18". HART is a registered trademark of the HART Communication Foundation. ANZEx US C 700-710-97J ©2016 Moore Industries-International, Inc.

Transcript of LH Datasheet Moore Industries J - Signal Conditioners · lh / 1 / n / s [p] When ordering the LH...

Demand Moore Reliability

LHConnection Heads for

Head-Mount Instruments

Perfect for Head-Mount Instruments The LH connection heads are ideal for use with head-mount transmitters such as Moore Industries’ TRX/TRY PC-Programmable and THZ2 Smart HART® Temperature Transmitters. The LH heads also protect terminal blocks used for sensor wire terminations.

Safeguards Expensive Instruments Meeting NEMA 4X, IP66 ratings, both LH heads are resistant to ultraviolet rays and corrosive chemicals. Their high-impact materials protect instruments installed in harsh fi eld conditions. The LH2 features a locking cover safety mechanism.

NPT, Metric and G½ (BSP) Entry Ports The dual entry port LH heads connect to standard conduit types and temperature assembly components. See Ordering Information for more information.

Complete Temperature Assemblies We offer complete lines of transmitters, RTDs, thermocouples, thermowells, connection heads and fi ttings at competitive prices. For information, ask your Moore Industries Sales Engineer.

For Explosion-Proof, Hazardous and General Locations Available LH models meet standards for enclosing indoor and outdoor electronic instruments that are approved for use in Explosion-Proof, Intrinsically-Safe and Non-Incendive locations.

April 2016

Complete temperature assembly features LH connection head with standard black cover.

Factory Mutual Approvals Explosion-Proof* Class I, Division 1, Groups A*, B, C, D Dust-Ignition Proof Class II & III, Division 1, Groups E, F, G NEMA 4X; IP66 ATEX Directive 2014/34/EU (ISSeP): Flameproof II 2G Ex d IIC II 2D Ex tD A21 IP66

Test Safe - ANZEx (Australia) Flameproof Ex d IIC T6 (Tamb 60°C) IP66 ANZEx 07.3027

CSA International Explosion-Proof* Class I, Division 1, Groups A*, B, C, D Class II, Division 1, Groups E, F, G Class III, Division 1 IP66

Factory Mutual Approvals NEMA 4X; IP66

LH1 Certifi cations

LH2 Certifi cations

*Group A only: Seal all conduit within 18".

HART is a registered trademark of the HART Communication Foundation.

ANZEx

USC

700-710-97J©2016 Moore Industries-International, Inc.

LHConnection Heads forHead-Mount Instruments

Copper-free aluminum with chromatic conversion seal undercoat and TGIC Polyester powdercoat

Black PBT Polyester (Flame retardant to UL V-O and U.V. stabilized for extended outdoor use)LH2 Cover: Copper-free aluminum

Specifi cationsBody with chromatic conversion seal undercoat

TGIC Polyester powdercoat

Anodized aluminum (LH1 when ordered with instrument; standard on the LH2)

LH1: 333 g (11.66 oz)

Cover (cont.)

LH1 & LH2 Installation and Mounting Dimensions

Tag

Weight

Cover

Specifi cations and information subject to change. Printed in U.S.A.

LH2: 553 g (19.36 oz)

United States • [email protected]: (818) 894-7111 • FAX: (818) 891-2816

Australia • [email protected]: (02) 8536-7200 • FAX: (02) 9525-7296

Belgium • [email protected]: 03/448.10.18 • FAX: 03/440.17.97The Netherlands • [email protected]

Tel: (0)344-617971 • FAX: (0)344-615920

China • [email protected]: 86-21-62491499 • FAX: 86-21-62490635

United Kingdom • [email protected]: 01293 514488 • FAX: 01293 536852

Ordering InformationEnclosure Enclosure Type Conduit Entry Port Type

LH for head-mount instruments

1 Connection head2 Explosion-Proof† connection head† Only N & M conduit types are certifi ed as explosion-proof

N Two entry ports: both ½-inch NPT (FM approved)

M Two entry ports: M20 cable and ½-inch NPT process (FM approved)

C Two entry ports: M20 cable and G½ (BSP) process††

†† G½ seal must be provided on outside surface

Cover Materials and Colors

For LH1: S Standard black PBT polyester cover

Options

P Hardware for mounting the LH1 or LH2 on a standard 2-inch pipe*P Pipe mounting hardware not required

LH2 only:E LH2 is ISSeP ATEX - Exd approved†

A LH2 is Test Safe - ANZEx approved†

†Units with the E or A option come equipped as standard with 2-inch pipe mount hardware.

For LH2: S Standard black painted metal (aluminum) cover

When ordering the LH housing without instrumentation or as part of a line item order, specify:Enclosure / Enclosure Type / Conduit Entry Port / Cover [Options]Model number example: LH / 1 / N / S [P]

When ordering the LH housing as part of a transmitter order (such as a TDZ3), place this condensed model number (with brackets or strokes removed) within brackets at the end of the transmitter model number or refer to the transmitter data sheet:Model number example: TDZ3 / TPRG / 4-20MA / 12-42DC [LH1NSP]

93mm(3.68 in)

9mm(0.35 in)

87mm(3.44 in)

ConduitEntry Port

Process Connection1/2-inch NPT (N and M models)

or G½ (BSP) (C models)

61mm(2.40 in)

10-32Mounting Holes (2)

51mm(2.00 in)

Safety Lock(LH2 only)

Metal Tag

BOTTOM

2-INCH PIPEMOUNTING HARDWARE

30mm(1.20 in)

72mm DIA.(2.85 in DIA.)

INSIDE InstrumentMounting Holes40mm (1.56 in)

InstrumentMountingHoles33mm(1.30 in)

I.D. 62mm x 19mm Deep(2.43 in x 0.76 in Deep)

Ground

M4.0 x 0.7 (4 places)

FRONT*

SIDE*

89mm(3.50 in)

84mm(3.30 in)

CL

61mm(2.40 in)

2-inch Pipe Bracket Mounting Holes (4)

61mm(2.40 in)

*LH1 ConnectionHead Shown