Level 1 Report

10
Hotel Hallway Analysis Date: 08 / 20 / 2012 Operator: Weber Analytics

Transcript of Level 1 Report

Page 1: Level 1 Report

Hotel Hallway Analysis

Date: 08 / 20 / 2012Operator: Weber Analytics

Page 2: Level 1 Report

Hotel Hallway Analysis08 / 20 / 2012

Weber Analytics432 North Main Street, Suite 200Blacksburg, VA 24060

Operator Weber AnalyticsTelephone 540.553.6171

Faxe-Mail [email protected]

Table of contents

Hotel Hallway AnalysisProject Cover 1Table of contents 2ZUMTOBEL STAFF LIGHTING S5D7108 7108RC S5; S5D; SPEC-5; FORMED STEE...

Luminaire Data Sheet 3OCL ORIGINAL CAST LIGHTING INC - ST. LOUIS, MO IEM-ICS4-10-7-X-2BP-...

Luminaire Data Sheet 4Typical of Four (4) Fixtures in Front of Guest Doors

Summary 53D Rendering 6False Color Rendering 7Room Surfaces

Hallway @ 36"Isolines (E, Perpendicular) 8

Guest Entry Detail @ 36"Isolines (E, Perpendicular) 9

FloorIsolines (E) 10

w w w . w e b e r a n a l y t i c s . c o m Page 2

Page 3: Level 1 Report

Hotel Hallway Analysis08 / 20 / 2012

Weber Analytics432 North Main Street, Suite 200Blacksburg, VA 24060

Operator Weber AnalyticsTelephone 540.553.6171

Faxe-Mail [email protected]

ZUMTOBEL STAFF LIGHTING S5D7108 7108RC S5; S5D; SPEC-5; FORMED STEEL HOUSING, FORMED SPECULAR ALUMINUM NO ENCLOSURE. HORIZONTAL LAMP

ORIENTATION. / Luminaire Data Sheet

See our luminaire catalog for an image of the luminaire.

Luminous emittance 1:

200

300

500

cd/klm 63%C0 - C180 C90 - C270

0° 15° 30°

45°

60°

75°

90°

105°105°

90°

75°

60°

45°

30° 15° 0°

Luminaire classification according to CIE: 100CIE flux code: 84 100 100 100 64

Due to missing symmetry properties, no UGR table can be displayed for this luminaire.

w w w . w e b e r a n a l y t i c s . c o m Page 3

Page 4: Level 1 Report

Hotel Hallway Analysis08 / 20 / 2012

Weber Analytics432 North Main Street, Suite 200Blacksburg, VA 24060

Operator Weber AnalyticsTelephone 540.553.6171

Faxe-Mail [email protected]

OCL ORIGINAL CAST LIGHTING INC - ST. LOUIS, MO IEM-ICS4-10-7-X-2BP-1 WATTS=51 REFL=87% UNIVERSAL BALLAST #C2642UNVSE & BODINE EMERGENCY

#B94 / Luminaire Data Sheet

See our luminaire catalog for an image of the luminaire.

Luminous emittance 1:

30

45

60

75

cd/klm 30%C0 - C180 C90 - C270

0° 15° 30° 45°

60°

75°

90°

105°

120°

135°150°165°180°165°150°135°

120°

105°

90°

75°

60°

45° 30° 15° 0°

Luminaire classification according to CIE: 54CIE flux code: 15 40 69 54 30

Due to missing symmetry properties, no UGR table can be displayed for this luminaire.

w w w . w e b e r a n a l y t i c s . c o m Page 4

Page 5: Level 1 Report

Hotel Hallway Analysis08 / 20 / 2012

Weber Analytics432 North Main Street, Suite 200Blacksburg, VA 24060

Operator Weber AnalyticsTelephone 540.553.6171

Faxe-Mail [email protected]

Typical of Four (4) Fixtures in Front of Guest Doors / Summary

1020 2025 25 40

70.00 ft0.00

6.00 ft

0.002.004.00

Height of Room: 9.500 ft, Light loss factor: 0.80 Values in Footcandles, Scale 1:153

Surface [%] Eav [fc] Emin [fc] Emax [fc] u0

Workplane / 25 4.94 49 0.198Floor 10 18 3.14 32 0.177Ceilings (11) 75 4.07 1.98 7.12 /Walls (4) 40 9.02 1.59 139 /

Workplane:Height: 2.500 ftGrid: 128 x 8 Points Boundary Zone: 2.001 ft

Illuminance Quotient (according to LG7): Walls / Working Plane: 0.383, Ceiling / Working Plane: 0.163.

Luminaire Parts List

Specific connected load: 1.09 W/sq ft = 0.44 W/sq ft/10 fc (Ground area: 420.01 sq ft)

No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]

1 4

OCL ORIGINAL CAST LIGHTING INC - ST. LOUIS, MO IEM-ICS4-10-7-X-2BP-1 WATTS=51 REFL=87% UNIVERSAL BALLAST #C2642UNVSE & BODINE EMERGENCY #B94 (1.000)

1094 3600 51.0

2 14

ZUMTOBEL STAFF LIGHTING S5D4312S1 4311RC S5; S5D; SPEC-5; FORMED STEEL HOUSING, FORMED SPECULAR ALUMINUM REFLECTOR, NO ENCLOSURE. VERTICAL LAMP ORIENTATION. (1.800)

564 1250 18.0

Total: 12269 Total: 31900 456.0

w w w . w e b e r a n a l y t i c s . c o m Page 5

Page 6: Level 1 Report

Hotel Hallway Analysis08 / 20 / 2012

Weber Analytics432 North Main Street, Suite 200Blacksburg, VA 24060

Operator Weber AnalyticsTelephone 540.553.6171

Faxe-Mail [email protected]

Typical of Four (4) Fixtures in Front of Guest Doors / 3D Rendering

w w w . w e b e r a n a l y t i c s . c o m Page 6

Page 7: Level 1 Report

Hotel Hallway Analysis08 / 20 / 2012

Weber Analytics432 North Main Street, Suite 200Blacksburg, VA 24060

Operator Weber AnalyticsTelephone 540.553.6171

Faxe-Mail [email protected]

Typical of Four (4) Fixtures in Front of Guest Doors / False Color Rendering

0 1.00 3.00 5.00 10.00 15.00 20.00 25.00 50.00 fc

w w w . w e b e r a n a l y t i c s . c o m Page 7

Page 8: Level 1 Report

Hotel Hallway Analysis08 / 20 / 2012

Weber Analytics432 North Main Street, Suite 200Blacksburg, VA 24060

Operator Weber AnalyticsTelephone 540.553.6171

Faxe-Mail [email protected]

Typical of Four (4) Fixtures in Front of Guest Doors / Hallway @ 36" / Isolines (E, Perpendicular)

5 510 10 10

101015 15 15

20 2020 20 20 2025

2525

25

30 3030

30 3035

3535 35 35

4040

40 40 40

4040

70.00 ft0.00

6.00 ft

0.00

Values in Footcandles, Scale 1 : 153Position of surface in room:Marked point:(0.000 ft, 0.000 ft, 3.000 ft)

Grid: 128 x 32 Points

Eav [fc] Emin [fc] Emax [fc] u0 Emin / Emax24 2.70 66 0.114 0.041

w w w . w e b e r a n a l y t i c s . c o m Page 8

Page 9: Level 1 Report

Hotel Hallway Analysis08 / 20 / 2012

Weber Analytics432 North Main Street, Suite 200Blacksburg, VA 24060

Operator Weber AnalyticsTelephone 540.553.6171

Faxe-Mail [email protected]

Typical of Four (4) Fixtures in Front of Guest Doors / Guest Entry Detail @ 36" / Isolines (E, Perpendicular)

2525

30

30

30

30

30

30

30

35

35

3535

35

35

35

35

35

35

35

40

40

40 40

40

40

40

4040

40

40

4545 45

4545

4545

9.00 ft0.00

6.00 ft

0.00

Values in Footcandles, Scale 1 : 20Position of surface in room:Marked point:(35.500 ft, 0.000 ft, 3.000 ft)

Grid: 32 x 32 Points

Eav [fc] Emin [fc] Emax [fc] u0 Emin / Emax34 20 46 0.598 0.446

w w w . w e b e r a n a l y t i c s . c o m Page 9

Page 10: Level 1 Report

Hotel Hallway Analysis08 / 20 / 2012

Weber Analytics432 North Main Street, Suite 200Blacksburg, VA 24060

Operator Weber AnalyticsTelephone 540.553.6171

Faxe-Mail [email protected]

Typical of Four (4) Fixtures in Front of Guest Doors / Floor / Isolines (E)

5 10 10 101515

1515 15

2020 20

2020

202025 25 25 25

252525

25

2530 30

30

70.00 ft0.00

6.00 ft

0.00

Values in Footcandles, Scale 1 : 153Position of surface in room:Marked point:(0.000 ft, 0.000 ft, 0.000 ft)

Grid: 128 x 32 Points

Eav [fc] Emin [fc] Emax [fc] u0 Emin / Emax18 3.14 32 0.177 0.097

w w w . w e b e r a n a l y t i c s . c o m Page 10