Lecture note refrigeration cycle
-
date post
12-Sep-2014 -
Category
Education
-
view
456 -
download
14
description
Transcript of Lecture note refrigeration cycle
11/12/2013
1
Refrigeration Cycle
12/11/2013Refrigeration Cycle 1
Chapter Objective
To carry out first law analysis on a refrigeration
cycle in which the working fluid undergoes
changes of phase as it completes the cycle.
12/11/2013Refrigeration Cycle 2
11/12/2013
2
12/11/2013Refrigeration Cycle 3
What is Refrigerator?
� A reversed heat engine.
� Absorb heat QL from a low-temperature medium
and reject the heat QH to a high-temperature
medium.
� A working fluid called refrigerant flows through
components of the refrigerator, forming a
thermodynamic cycle called refrigeration cycle.
� To perform the heat absorption and rejection
processes, the refrigerator requires a work input,
W net, in.
12/11/2013Refrigeration Cycle 4
11/12/2013
3
12/11/2013 5
Environment
Reverse
Heat
Engine
COLD
refrigerated
space
W net, in = required input
QL = desired output
QH
WQQWQQ LHHL =−→−=−
LH
LLref
Q
W
QCOP
−==
12/11/2013Refrigeration Cycle 6
Total heat transfer to a cycle = Total work done by the cycle
∑ ∑= WQ
Coefficient of performance of a refrigerator,
(1)
11/12/2013
4
12/11/2013Refrigeration Cycle 7
The most efficient and
ideal refrigerator is the
one in which the
refrigerant undergoes a
reversed Carnot cycle
while working between
2 specified
temperatures.
Q23
condenser
engine compressor
evaporator
1
3 2
4
W12W34
Q41
Components of a refrigerator working on
reversed Carnot cycle
12/11/2013Refrigeration Cycle 8
Q41
Q23
W
s
T
T2 = T3
T4 = T1
s4 =s3 s1 =s2
14
3 2
T-s diagram for a refrigerator
working on reversed Carnot cycle
Q23
condenser
engine compressor
evaporator
1
3 2
4
W12W34
Q41
11/12/2013
5
12/11/2013Refrigeration Cycle 9
The processes shown on the T-s
diagram are as follows:
1-2 Wet vapor at state 1 enters
the compressor and is
compressed isentropically to
state 2. The required input is
denoted W12.
2-3 The vapor at state 2 and is
condensed at constant
pressure and temperature to
state 3, when it is completely
liquid. The heat rejected from
the refrigerant is denoted by
Q23.
Q41
Q23
W
s
T
T2 = T3
T4 = T1
s4 =s3 s1 =s2
14
3 2
12/11/2013Refrigeration Cycle 10
3-4 The liquid refrigerant at state 3
expands isentropically behind
the piston of an engine, doing
work of amount denoted by
W34.
4-1 The refrigerant at state 4 enters
the evaporator where it absorb
heat denoted by Q41 from the
cold space, until it reaches state
1.
Q41
Q23
W
s
T
T2 = T3
T4 = T1
s4 =s3 s1 =s2
14
3 2
11/12/2013
6
4123
41
Q
W
QCOP L
ref−
==∑
dsTdQT
dQds =→=
12/11/2013Refrigeration Cycle 11
Cycle’s Performance
The performance of the cycle is
measured by the Coefficient of
Performance (COP), defined as,
Q41
Q23
W
s
T
T2 = T3
T4 = T1
s4 =s3 s1 =s2
14
3 2
The definition of entropy change is,
( )41141 ssTQ −=∴
( )32223 ssTQ −=
( ) ( )3241 ssss −=−
12/11/2013Refrigeration Cycle 12
Q41
Q23
W
s
T
T2 = T3
T4 = T1
s4 =s3 s1 =s2
14
3 2
and
and
11/12/2013
7
( )( )( )4112
411
ssTT
ssTCOPref
−−
−=∴
( )12
1
TT
TCOPref
−=
12/11/2013Refrigeration Cycle 13
Q41
Q23
W
s
T
T2 = T3
T4 = T1
s4 =s3 s1 =s2
14
3 2
i.e.
(2)
Note: - where T1 = evaporator temperature
and T2 = condenser temperature
- only valid for reversed Carnot
cycle (for refrigerator)
- COP value is the maximum value
for a cycle
A vapor-compression refrigeration system operates on a
Carnot cycle, uses R-12 as the working fluid. The refrigerant
is dry saturated at entry to the condenser at 28°C, and
saturated liquid leaving the condenser. The evaporator
temperature is -10°C. Determine,
(a) The compressor input work (kJ/kg);
(b) The heat transfer in the evaporator (kJ/kg);
(c) The COP
Show the cycle on a T-s diagram.
12/11/2013Refrigeration Cycle 14
11/12/2013
8
12/11/2013Refrigeration Cycle 15
Q41
Q23
W
s
T
T2 = T3 = 28oC
T4 = T1 = -10oC
s4 =s3 s1 =s2
14
3 2
12/11/2013Refrigeration Cycle 16
Main components of
a household refrigerator
Evaporator coils
Freezer
compartment
11/12/2013
9
12/11/2013Refrigeration Cycle 17
Q23
condenser
engine compressor
evaporator
1
3 2
4
W12W34
Q41
T2
T1
T2’
T1’T2’ = T atmosphere
T1’ = T cold space
T2’ < T 2
T1’ > T 1
Therefore, Q23 can be
transferred from the
refrigerant to the atmosphere
and Q41 can be transferred
from the refrigerated space to
the refrigerant.
12/11/2013Refrigeration Cycle 18
T2’T2’ < T 2
Q41
Q23
s
T
T2
T11
4
3 2
T1’T1’ > T 1
11/12/2013
10
12/11/2013Refrigeration Cycle 19
Reversed Carnot cycle is not
practical since,
• All the reversible processes
cannot be achieved.
• Process 1-2 is bad for
compressor – low efficiency and
two phase compression is
impractical.
• It is difficult to stop evaporation
process at point 1 and
compressed it just to state 2.
To get practical cycle, modification
to the reversed Carnot cycle is
made.
Q41
Q23
W
s
T
T2 = T3
T4 = T1
s4 =s3 s1 =s2
14
3 2
12/11/2013Refrigeration Cycle 20
Carnot Cycle/
Ideal
Replacing the turbine
with a throttling
Valve
(Ideal/actual)
Throttling valve
+
Dry saturated or
superheated vapor at
entry to the
Compressor
(Ideal/actual)
Throttling valve
+
Dry saturated or
superheated vapor
at
entry to the
compressor
+
Under-cooling at
the condenser exit
(Ideal/actual)
Two or more
throttling valves
+
Flash chamber
+
2-stage
compression
(Ideal/actual)
11/12/2013
11
12/11/2013Refrigeration Cycle 21
Process 3-4 is replaced with a throttle valve.
s
Replacement of expansion cylinder with a throttle valve
q41
q23
T
T2
T1
s4 s1 =s2
14
3 2
Q in
Wc
Expansion
valve
Evaporator
Condenser
Compressor
Q out
Saturated or
superheated vapor
1
23
4 The expansion of the liquid refrigerant
through the throttle valve is represented
by a dashed line 3-4 since the process is
not reversible.
12/11/2013Refrigeration Cycle 22
s
4-1 Constant Pressure
Evaporation
Heat from a cold space is
absorbed by the refrigerant.
As a result, the refrigerant
evaporates at a constant
evaporator pressure, from
state 4 to become a drier
liquid-vapor mixture at state 1.
q41
q23
T
T2
T1
s4 s1 =s2
14
3 2
11/12/2013
12
12/11/2013Refrigeration Cycle 23
s
1-2 Isentropic compression
The liquid-vapor mixture is
compressed from the
evaporator pressure to the
condenser pressure, in a
reversible adiabatic manner.
The refrigerant exits the
compressor as a saturated
vapor at state 2.
q41
q23
T
T2
T1
s4 s1 =s2
14
3 2
12/11/2013Refrigeration Cycle 24
s
2-3 Constant Pressure
Condensation
Heat is rejected from the
refrigerant to a warm space. As a
result, the refrigerant condenses
at a constant condenser
pressure until it becomes a
saturated liquid at state 3.
q41
q23
T
T2
T1
s4 s1 =s2
14
3 2
11/12/2013
13
12/11/2013Refrigeration Cycle 25
s
3-4 Constant Enthalpy
Expansion
The refrigerant expands
through the throttle valve
adiabatically. As a result, it’s
pressure drops from the
condenser to the evaporator
pressure. The enthalpy is
constant during the process,
i.e. h3 = h4.
Note: The expansion process is highly irreversible, thus making
the vapor-compression cycle an irreversible cycle.
q41
q23
T
T2
T1
s4 s1 =s2
14
3 2
12/11/2013Refrigeration Cycle 26
s
Effects of using an expansion
valve
i) A throttling process is an
expansion process with
constant enthalpy, (h3 = h4).
Therefore, no work done by
the cycle, i.e. w34 = 0.
ii) The refrigeration effect, q41
decreases.
q41
q23
T
T2
T1
s4 s1 =s2
14
3 2
11/12/2013
14
12/11/2013Refrigeration Cycle 27
s
Analysis of the Cycle
The cycle operates as steady flow.
So, each component of the vapor-
compression refrigeration cycle
applies the steady flow energy
equation (SFEE) to analyze the
energy interaction. The changes in
the kinetic and potential energy are
ignored.
q41
q23
T
T2
T1
s4 s1 =s2
14
3 2
1212 hhw −=
4141 hhq −=
12/11/2013Refrigeration Cycle 28
s
q41
q23
T
T2
T1
s4 s1 =s2
14
3 2
Analysis of the Cycle
Evaporation process (4-1):
(3)
(Refrigerating effect /
heat absorbed by the refrigerant)
Compression process (1-2):
(4)
(input work to the compressor)
11/12/2013
15
43 hh =
3223 hhq −=
12/11/2013Refrigeration Cycle 29
s
Analysis of the Cycle
Condensation process (2-3):
(5)
(heat rejected from the refrigerant)
Expansion process (3-4):
(6)
(constant enthalpy process)
q41
q23
T
T2
T1
s4 s1 =s2
14
3 2
12
41
12
41
hh
hh
w
qCOPref
−
−==
12/11/2013Refrigeration Cycle 30
s
Performance of the Cycle
The performance of the vapor-
compression refrigeration cycle
is measured by the coefficient of
performance of refrigerator,
COPref, defined as,
(7)
q41
q23
T
T2
T1
s4 s1 =s2
14
3 2
11/12/2013
16
An ideal vapor-compression refrigeration cycle uses R-134a as the
working fluid. The evaporator and condenser operate at –20oC and
1000 kPa respectively. The refrigerant is dry saturated at entry to the
compressor and saturated liquid at the condenser outlet. The mass
flow of the refrigerant is 3 kg/min. Determine,
(a) The COPref;
(b) The refrigerating effect (kW);
(c) The COPhp;
(d) The heat transfer to the cooling water in the condenser (kW).
Show the cycle on a T-s diagram.
12/11/2013Refrigeration Cycle 31
12/11/2013Refrigeration Cycle 32
Q41
Q23
T
T2
T1 = -20oC
s4 s1 =s2
14
3
2
P2 = P3 = 1000 kPa
s
11/12/2013
17
12/11/2013Refrigeration Cycle 33
To make full use of the specific enthalpy of evaporation of the
refrigerant, the evaporation process is continued until the refrigerant
becomes a saturated vapor at 1.
q41
q23
T
T2
T11
4
3
2
sThe refrigerant exits the evaporator
as a saturated vapor
12/11/2013Refrigeration Cycle 34
In actual condition, the
refrigerant evaporates until it
becomes superheated vapor at
state 1. This is to prevent the
carry-over of liquid refrigerant
into the compressor. However,
the amount of superheat is
usually kept to minimum.
q41
q23
T
T2
T11
4
3
2
s
11/12/2013
18
12/11/2013Refrigeration Cycle 35
q41
q23
T
T2
T1 14
3
2
s
Effects of This Process
1. The refrigerant becomes
superheated vapor as it exits
the compressor.
2. More work needs to be
supplied to the compressor to
compress the refrigerant.
3. The condensation process still
occurs at a constant condenser
pressure, but not at a constant
temperature.
4. More heat needs to be rejected
from the refrigerant to the
warm region.
12/11/2013Refrigeration Cycle 36
The refrigerant is condensed until it’s temperature is lower than
the saturation temperature at the condenser pressure, when it
exits the condenser.
Under-cooling of the refrigerant in the
condenser
q41
q23
T
Tsat 2
1
4
3
2
s
Saturation temperature
at condenser pressure
P evaporator
P condenser
Degree
of sub-cooling
Degree
of superheat
Tsat 1
11/12/2013
19
12/11/2013Refrigeration Cycle 37
Effects of This Process
• The line 3-4 representing the expansion process is shifted to the left,
thus line 4-1 representing the evaporation process increases in length.
• Therefore, under-cooling of the refrigerant increases the refrigerating
effect of the cycle, which is a desirable effect.
q41
q23
T
Tsat 2
1
4
3
2
s
Saturation temperature
at condenser pressure
P evaporator
P condenser
Degree
of sub-cooling
Degree
of superheat
Tsat 1
( )41 1 4q h h= −
( )12 2 1w h h= −
12/11/2013Refrigeration Cycle 38
Analysis of the Cycle
Evaporation process (4-1):
(8)
Compression process (1-2):
(9)
q41
q23
T
Tsat 2
1
4
3
2
s
Saturation temperature
at condenser pressure
P evaporator
P condenser
Degree
of sub-cooling
Degree
of superheat
Tsat 1
11/12/2013
20
( )23 2 3q h h= −
43 hh =
12/11/2013Refrigeration Cycle 39
Analysis of the Cycle
Condensation process (2-3):
(10)
Expansion process (3-4):
(11)
q41
q23
T
Tsat 2
1
4
3
2
s
Saturation temperature
at condenser pressure
P evaporator
P condenser
Degree
of sub-cooling
Degree
of superheat
Tsat 1
( )( )1 441
12 2 1
ref
h hqCOP
w h h
−= =
−
12/11/2013Refrigeration Cycle 40
Performance of the Cycle
Performance of the vapor-compression refrigeration
cycle is measured by the Coefficient of Performance of
refrigerator, COPref, defined as,
(12)
11/12/2013
21
12/11/2013Refrigeration Cycle 41
The p-h diagram
Another diagram frequently used
in the analysis of vapor-
compression refrigeration cycles is
the P-h diagram.
Three of the four processes appear
as straight lines.
The heat transfer in the condenser
and the evaporator is proportional
to the lengths of the corresponding
process curves.
P, (bar)
h
1
2 2’3
4
T sat condenser
T sat evaporator
The air temperature inside a cold room is controlled at a constant
value using a vapor compression refrigeration system with R-134a as
the refrigerant. The refrigerant leaves the evaporator dry saturated
and is compressed to 1 MPa. The refrigerant leaves the condenser at
35oC. The refrigerant is then throttled to the evaporator pressure of
240 kPa. The isentropic efficiency of the compressor is 85%. The
refrigeration load is 100 kW. Determine,
(a) The temperature of the refrigerant which leaves the compressor
(oC);
(b) The mass flow rate of the refrigerant (kg/s);
(c) The coefficient of performance of the refrigeration system.
Show the cycle on a p-h diagram.
12/11/2013Refrigeration Cycle 42
11/12/2013
22
12/11/2013Refrigeration Cycle 43
P, (bar)
h
10.84
2.610
Ts = 45oC
1
2 2’3
4
It is proposed to use a heat pump working on the ideal vapor-compression cycle for the purpose of heating the air supply to anincubation room from 25oC to 37oC at a rate of 1.06 kg/s. The supplyof heat is taken from a refrigerated room at 7oC. For the air, take cp
=1.005 kJ/kgK.
The refrigerant is R12 which is dry saturated leaving the evaporator.A temperature difference of 17 K is necessary for the transfer of heatfrom the refrigerated room to the refrigerant in the evaporator. Thedelivery pressure of the compressor is 10.84 bar and there is 5 K ofunder-cooling of refrigerant in the condenser.
12/11/2013Refrigeration Cycle 44
11/12/2013
23
Show the schematic diagram of the components and the cycle on a
T-s diagram and p-h diagram. Calculate,
(a) The heat load (kW);
(b) The mass flow of the refrigerant (kg/s);
(c) The refrigerating effect (kW);
(d)The motor power required to drive the compressor if the
mechanical efficiency is 87%;
(e) The COPhp;
(f) The COPref.
12/11/2013Refrigeration Cycle 45
12/11/2013Refrigeration Cycle 46
Q41
Q23
T
Tsat
14
3
2
s
5K
17K
-10oC
10.84 bar
P
h
4 1
23
2’
2’
11/12/2013
24
• The most important quantity in refrigeration or
freezing application is the total of heat required to be
moved from a cold space.
• This heat is called refrigerating load.
• Measured in `ton’ or kilowatt or Btu/min.
• Unit conversion: 1 ton = 200 Btu/min = 3.516 kW.
12/11/2013Refrigeration Cycle 47
( )414141hhmQxmQ refref −==
•••
∴
( )( )skg
hh
Qmref /
41
41
−=
••
12/11/2013Refrigeration Cycle 48
(13)
Refrigerating load is,
The mass flow rate of the refrigerant is,
11/12/2013
25
12/11/2013Refrigeration Cycle 49
Features of the diagram
It is more convenient to
represent the vapor-
compression refrigeration
cycle on a pressure-enthalpy
(p-h) diagram, because the
enthalpies required for the
calculation can be read off
directly from the diagram.
Enthalpy (kJ/kg)
Pressure (bar)
12/11/2013Refrigeration Cycle 50
Figure shows the vapor-
compression refrigeration cycle
shown on a p-h diagram. Note that
the cycle shown is with under-
cooling of the refrigerant at the
exit of the condenser.
Q1 = (h1 – h4)
W =
(h2 – h1)
Vapor-compression cycle on a p-h diagram
11/12/2013
26
12/11/2013Refrigeration Cycle 51
What is Flash Chamber?
• Flash chamber is a device used
to separate vapor refrigerant
from the liquid refrigerant.
• When a flash chamber is used,
the compression process needs
to be carried out in two stages.
Schematic diagram of a refrigeration
plant with two-stage compression
and a flash chamber.
Wc
Expansion
valve 1
Condenser
Compressor
Q out
3
5
6
WcExpansion
valve 2
Evaporator
Flash
chamber
Compressor
1
2
(1)
8
Direct contact
heat exchanger
9
(1)
(1)
(x)
(1-x)27(1-x)
4
(1-x)
Qin
12/11/2013Refrigeration Cycle 52
The refrigerant leaving the
expansion valve 1 as a mixture of
vapor and liquid (wet vapor). The
vapor refrigerant has no more
capability to absorb heat in the
evaporator. Thus, it is no use to pass
the vapor through the evaporator.
It is more practical to separate the
vapor from the mixture at some
intermediate pressure, pi and allow
only the liquid refrigerant to flow
through the evaporator. The liquid
refrigerant has full capability to
absorb the heat in the evaporator.
Wc
Expansion
valve 1
Condenser
Compressor
Q out
3
5
6
WcExpansion
valve 2
Evaporator
Flash
chamber
Compressor
1
2
(1)
8
Direct contact
heat exchanger
9
(1)
(1)
(x)
(1-x)27(1-x)
4
(1-x)
Qin
11/12/2013
27
12/11/2013Refrigeration Cycle 53
Process
Suppose 1 kg of refrigerant flowing
through the condenser. At the flash
chamber, x kg of dry saturated vapor at
pressure pi and enthalpy hgi is bled off
to the inter-sage of the compressor.
The remaining mass of (1-x) kg of liquid
with enthalpy hfi passes through the
throttle valve 2 and then to the
evaporator.
At the intermediate pressure pi , (1-x)
kg of vapor at state 2 is mixed with x kg
of flash vapor of enthalpy hgi . The
resultant mixture at state 3 is
compressed in the second stage
compressor, to state 4.
Wc
Expansion
valve 1
Condenser
Compressor
Q out
3
5
6
WcExpansion
valve 2
Evaporator
Flash
chamber
Compressor
1
2
(1)
8
Direct contact
heat exchanger
9
(1)
(1)
(x)
(1-x)27(1-x)
4
(1-x)
Qin
12/11/2013Refrigeration Cycle 54
• 2 compressors, 1 evaporator, 1
condenser, and 1 flash chamber.
• Point 2, 3, 6, 7 and 9 are located on
the same intermediate pressure pi . pi
is chosen so that the compressor
work is minimum.
pi = (p1 . p4)1/2
• The flash chamber pressure = The
intermediate pressure, pi .
Vapor-compression refrigeration cycle
with two-stage compression and a flash
chamber on a p-h diagram
P
h
1
4
3
9
267
5
8
(1-x) kg
(x) kg
(1) kg
11/12/2013
28
12/11/2013Refrigeration Cycle 55
• Saturated liquid enter the 2nd
expansion valve at point 7.
• The flash chamber contains
mixture of saturated water and
vapor.
• The dry saturated vapor from
the flash chamber at point 9 mix
with the superheated vapor
from the 1st stage compressor at
point 2 to yield superheated
vapor at point 3.
• The superheated vapor at point 3
is compressed to point 4
through the 2nd stage
compressor.
P
h
1
4
3
9
267
5
8
(1-x) kg
(x) kg
(1) kg
fgifi hxhhh )(56 +==
12/11/2013Refrigeration Cycle 56
The amount of dry saturated
vapor bled off is given by the
dryness fraction x at state 6, at
the intermediate pressure pi .
Since the enthalpy of the
refrigerant at state 6 is equal to
the enthalpy at state 5, we
have,
P
h
1
4
3
9
267
5
8
(1-x) kg
(x) kg
(1) kg
11/12/2013
29
fgi
fi
h
hhx
−=
5
12/11/2013Refrigeration Cycle 57
Thus,
(14)
P
h
1
4
3
9
267
5
8
(1-x) kg
(x) kg
(1) kg
( )[ ]293 .1..10 hxhxh
HHWQ inletexit
−+−=
−=/−/
( )9223 . hhxhh −−=
12/11/2013Refrigeration Cycle 58
Thus,
(15)
9
(x) kg
2
3
(1-x) kg
(1) kg
P
h
1
4
3
9
267
5
8
(1-x) kg
(x) kg
(1) kg
11/12/2013
30
∑ += 3412 WWWin
( )( ) ( )34121 hhhhxWin −+−−=∑
12/11/2013Refrigeration Cycle 59
a) Total work input to the
compressors
Since the compression process is
carried out in two stages, the total
work input to the cycle is,
P
h
1
4
3
9
267
5
8
(1-x) kg
(x) kg
(1) kg
i.e.
(16)
( )( )8181 1 hhxQ −−=
12/11/2013Refrigeration Cycle 60
b) Refrigerating effects
The refrigerating effects of the
cycle is
(17)
P
h
1
4
3
9
267
5
8
(1-x) kg
(x) kg
(1) kg
11/12/2013
31
( )5445 hhQ −=
12/11/2013Refrigeration Cycle 61
c) Heat rejected in the condenser
The heat rejected from the
refrigerant is
(18)
P
h
1
4
3
9
267
5
8
(1-x) kg
(x) kg
(1) kg
( )( )( )( ) ( )3412
81
1
1
hhhhx
hhxCOPref
−+−−
−−=
∑=
in
refW
QCOP 81
12/11/2013Refrigeration Cycle 62
d) Coefficient of performance
The coefficient of performance of the
cycle is
(19)
P
h
1
4
3
9
267
5
8
(1-x) kg
(x) kg
(1) kg
11/12/2013
32
• Increase in refrigerating effects of the cycle.
• Lower amount of compression work.
• Increase in the coefficient of performance.
12/11/2013Refrigeration Cycle 63
• The refrigeration system becomes more complex
since there are more equipments and piping
system required.
• Higher capital costs for setting up the plant
• Higher maintenance costs.
12/11/2013Refrigeration Cycle 64
11/12/2013
33
12/11/2013Refrigeration Cycle 65
A two-stage vapor-compression refrigeration system uses Refrigerant-
134a as the working fluid. Saturated vapor enters the first compressor
stage at -30oC and saturated liquid leaves the condenser at 11.595 bar.
The system is equipped with a flash chamber, which operates at a
pressure of 4.1459 bar. If each compressor stage operates
isentropically and the refrigerating capacity of the system is 10 tons,
determine,
(a) the mass flow rate of the refrigerant through the evaporator
kg/s;
(b) the power input to each compressor (kW);
(c) The coefficient of performance.
Show the cycle on a T-s diagram. (1 ton refrigeration = 3.516 kW)
12/11/2013Refrigeration Cycle 66
4
T oC
s
1
5
3
2
6 97
8
(1)
(x)
(1-x)
11/12/2013
34
12/11/2013Refrigeration Cycle 67
A vapor-compression refrigeration plant uses refrigerant R134a and
has a suction saturation temperature of -5oC and a condenser
saturation temperature of 45oC. The vapor is dry saturated on entering
the compressor and there is no under-cooling of the condensate. The
compression is carried out isentropically in two stages and a flash
chamber is employed at an intersage saturation temperature of 15oC.
Determine:
a) the amount of vapor bled off at the flash chamber;
b) the state of vapor at inlet to the 2nd compressor stage;
c) the refrigerating effect;
d) the work input;
e) the COPref.
A two-stage compression refrigeration system is to operate
between the pressure limits of 1 MPa and 0.1 MPa. The working
fluid is Refrigerant-134a. The refrigerant leaves the condenser as
a saturated liquid and is throttled to a flash chamber operating at
0.32 MPa. Part of the refrigerant evaporates leaving the low
flashing process, and this vapour mixed with the refrigerant
leaving the low-pressure compressor. The mixture is then
compressed to the condenser pressure by the high-pressure
compressor. The liquid in the flash chamber is throttled to the
evaporator pressure and cools the refrigerated space as it
vaporizes in the evaporator. Assuming the refrigerant leaves the
evaporator as a saturated vapour and both compressors are
isentropic, determine:
12/11/2013Refrigeration Cycle 68
11/12/2013
35
(a) The fraction of the refrigerant which evaporatesas it throttled to the flash chamber;
(b) The amount of heat removed from therefrigerated space (kJ/kg);
(c) The compressor work (kJ/kg);
(d) The COPref.
Illustrated the schematic layout of the refrigerationsystem showing clearly the respective componentsand also its p-h diagram.
12/11/2013Refrigeration Cycle 69
12/11/2013Refrigeration Cycle 70
4
T oC
s
1
5
3
2
6 97
8
(1)
(x)
(1-x)
Wc
Expansion
valve 1
Condenser
Compressor
Q out
3
5
6
WcExpansion
valve 2
Evaporator
Flash
chamber
Compressor
1
2
(1)
8
Direct contact
heat exchanger
9
(1)
(1)
(x)
(1-x)27(1-x)
4
(1-x)
Qin