Lecture 22: Primary System Loops in EnergyPlus
Material prepared by GARD Analytics, Inc. and University of Illinoisat Urbana-Champaign under contract to the National Renewable Energy
Laboratory. All material Copyright 2002-2003 U.S.D.O.E. - All rights reserved
2
Purpose of this Lecture
Gain an understanding of: Water (fluid) side loop structures in
EnergyPlus How to control fluid flow rates using
the EnergyPlus pump strategies
3
Defining Loops
Loops define the movement of mass and energy within an HVAC system Plant loop Condenser loop Heat recovery loop
Systems defined by the order of branches/components on the HVAC loop
4
Defining Loops (cont’d)
Main loops divided into “sub-loops” or “semi-loops” for organizational clarity & simulation logistics
Sub-loops are matched pairs that consist of half of the main loop.
For example, plant and condenser loops are broken into supply and demand sides.
5
Demand- & Supply-SideSub-Loops
Plant demand-side sub-loop contains equipment that creates a load on the plant.
Plant supply-side sub-loop contains equipment that meets these loads.
Each supply-side sub-loop must be connected to a demand-side loop.
6
Demand- & Supply-Side Loops (cont’d)
Boiler
Boiler Inlet Node
Boiler Outlet Node
Supply-Side LoopDemand-Side Loop
±HW Pump
Heating Coil
HW Supply inlet Node
HW Supply Outlet NodeHW Demand Inlet Node
HW DemandOutlet Node
Heating CoilInlet Node
HW Pump Outlet Node
Inlet PipeHeating Coil Outlet Node
Exit Pipe
HW Supply Outlet Pipe
7
Branches for Water-Side Loops
Maximum Branch Flow Rate (Ignored)
Comp1 TypeComp1 NameComp1 Inlet Node NameComp1 Outlet Node NameComp1 Branch Control Type
8
Branches for Water-Side Loops - Example
BRANCH,
Heating Supply Inlet Branch, !- Branch Name
, !- Maximum Branch Flow Rate {m3/s}
PUMP:VARIABLE SPEED, !- Comp1 Type
HW Circ Pump, !- Comp1 Name
HW Supply Inlet Node, !- Comp1 Inlet Node Name
HW Pump Outlet Node, !- Comp1 Outlet Node Name
ACTIVE; !- Comp1 Branch Control Type
9
Layout for Individual HVAC Supply or Demand Sub-
Loops Elements can be defined
in series, in parallel, or both with some restrictions
Branches are defined as individual legs within the loop structure
Segment between point A & B is defined as a branch, as is the section between points E and F
1 to mComponents
n Splitter
A
B
1 to iComponents
C1
... 1 to jComponents
Cn
D1 Dn
n Mixer
1 to kComponents
E
F
1 to mComponents
n Splitter
A
B
1 to i
1 to mComponents
n Splitter
A
B
1 to iComponents
C1
... 1 to jComponents
Cn
D1 Dn
n Mixer
1 to kComponents
E
F
10
Layout for Individual HVAC Supply or Demand Sub-
Loops The first supply side component between A & B must be the loop pump, which controls the loop flow.
There may be multiple branches between the splitter and mixer (between points C1 & D1 to Cn & Dn).
Each sub-loop may only have one splitter and one mixer.
1 to mComponents
n Splitter
A
B
1 to iComponents
C1
... 1 to jComponents
Cn
D1 Dn
n Mixer
1 to kComponents
E
F
1 to mComponents
n Splitter
A
B
1 to i
1 to mComponents
n Splitter
A
B
1 to iComponents
C1
... 1 to jComponents
Cn
D1 Dn
n Mixer
1 to kComponents
E
F
11
Layout for Individual HVAC Supply or Demand Sub-
Loops Equipment may be in
parallel between the mixer and splitter,
Within any branch, there can only be elements in series.
Sub-loops do not require a splitter or mixer, if all equipment on the sub-loop is in series—a single branch defines the entire sub-loop.
1 to mComponents
n Splitter
A
B
1 to iComponents
C1
... 1 to jComponents
Cn
D1 Dn
n Mixer
1 to kComponents
E
F
1 to mComponents
n Splitter
A
B
1 to i
1 to mComponents
n Splitter
A
B
1 to iComponents
C1
... 1 to jComponents
Cn
D1 Dn
n Mixer
1 to kComponents
E
F
12
Pumping Rules
Pumps must be on the supply side
Pumps can operate as constant or variable flow
Pumps can run continuously or intermittently
Splitter
Mixer
Components
Loop Pump
From Demand-Side Sub-Loop
To Demand-Side Sub-Loop
Supply-Side Sub-Loop
13
Pumping Rules (cont’d)
Single boiler/chiller with NO bypass, PUMP:CONSTANT SPEED Boiler/chiller should be constant flow Pump should be intermittent
Single boiler/chiller with NO bypass, PUMP:VARIABLE SPEED Boiler/chiller should be variable flow, regardless of
whether pump is intermittent or continuous (runs at the minimum if demand is less than minimum, this includes zero.)
14
Pumping Rules (cont’d)
Single boiler/chiller with bypass, PUMP:CONSTANT SPEED Boiler/chiller can be constant or variable
flow Pump may be intermittent or continuous as
long as the bypass can handle the entire pump volume when the boiler is not operating
15
Pumping Rules (cont’d)
Multiple branches add more complexity, but it is nothing more than continuity.
If the pump is putting out flow then it has to have a branch to flow down whether it is a chiller or a bypass.
16
Pumping Rules (cont’d)
You are always safer adding the bypass for a simulation. If the active machines require the flow the bypass will be dry
Thermodynamically it does not make any difference if the flow goes through a machine that is OFF or it flows down the bypass.
There is no pressure simulation and flow losses are not accounted for.
17
Summary of Loop Limitations
Each sub-loop allowed one splitter and one mixer
One bypass on each sub-loop optionalNo other components may be in series
with a bypassEquipment may be in parallel only
between the splitter and mixerEquipment may be in series in each
branch
18
3-Zone VAV SystemWe are going to look at this system input Loop by Loop
North
Zone
East
Zone
Resistive
Zone
Plant Supply SideCooling Loop
CW Pump
CoolingTower
Cond . Pump
Cond . Supply Side Loop
ChillerBypass
Supply Fan
Retu
rn A
ir M
ixe
r
Zon
e A
ir Sp
litter
Plant Demand SideCooling Loop
Pla
nt D
em
an
d S
ide
Hea
ting
Loo
p
CC
Byp
ass
CondenserBypass
VAV Box: ReHeat
VAV Box: ReHeat
Retu
rn H
ot
Wa
ter M
ixer
Bypass
Cond . DemandSide Loop
CondenserBypass
Hot W
ate
r
Sp
litter
Mixed OutsideAir Box
Relief Air
Outside Air
VAV Box: ReHeatBoiler
Plant Supply SideHeating Loop
HW Pump
North
Zone
East
Zone
Resistive
Zone
Plant Supply SideCooling Loop
CW Pump
CoolingTower
Cond . Pump
Cond . Supply Side Loop
ChillerBypass
Supply Fan
Retu
rn A
ir M
ixe
r
Zon
e A
ir Sp
litter
Plant Demand SideCooling Loop
Pla
nt D
em
an
d S
ide
Hea
ting
Loo
p
CC
Byp
ass
CondenserBypass
VAV Box: ReHeat
VAV Box: ReHeat
Retu
rn H
ot
Wa
ter M
ixer
Bypass
Cond . DemandSide Loop
CondenserBypass
Hot W
ate
r
Sp
litter
Mixed OutsideAir Box
Relief Air
Outside Air
VAV Box: ReHeatBoiler
Plant Supply SideHeating Loop
HW Pump
Boiler
Plant Supply SideHeating Loop
HW Pump
19
Cooling Coil & Chilled Water Demand Side
North
Zone
East
Zone
Resistive
Zone
Plant Supply SideCooling Loop
CW Pump
CoolingTower
Cond . Pump
Cond . Supply Side Loop
ChillerBypass
Supply Fan
Retu
rn A
ir M
ixe
r
Zone A
ir Splitte
r
Plant Demand SideCooling Loop
Pla
nt D
em
and S
ide
Heatin
g L
oop
CC
Byp
ass
CondenserBypass
VAV Box: ReHeat
VAV Box: ReHeat
Retu
rn H
ot
Wate
r Mixe
r
Bypass
Cond . DemandSide Loop
CondenserBypass
Hot W
ate
r
Splitte
r
Mixed OutsideAir Box
Relief Air
Outside Air
VAV Box: ReHeatBoiler
Plant Supply SideHeating Loop
HW Pump
North
Zone
East
Zone
Resistive
Zone
Plant Supply SideCooling Loop
CW Pump
CoolingTower
Cond . Pump
Cond . Supply Side Loop
ChillerBypass
Supply Fan
Retu
rn A
ir M
ixe
r
Zone A
ir Splitte
r
Plant Demand SideCooling Loop
Pla
nt D
em
and S
ide
Heatin
g L
oop
CC
Byp
ass
CondenserBypass
VAV Box: ReHeat
VAV Box: ReHeat
Retu
rn H
ot
Wate
r Mixe
r
Bypass
Cond . DemandSide Loop
CondenserBypass
Hot W
ate
r
Splitte
r
Mixed OutsideAir Box
Relief Air
Outside Air
VAV Box: ReHeatBoiler
Plant Supply SideHeating Loop
HW Pump
Boiler
Plant Supply SideHeating Loop
HW Pump
20
Cooling Coil & Chilled Water Demand Side
Objects required: BRANCH LIST CONNECTOR LIST SPLITTER MIXER BRANCH, VAV Sys 1 ChW-Branch
COIL:Water:DetailedFlatCooling, VAV SYS 1 Cooling Coil
BypassChilled Water Demand -Side Outlet Node
Chilled Water Demand -Side Inlet Note
CC Cooling Coil
BypassChilled Water Demand -Side Outlet Node
Chilled Water Demand -Side Inlet Note
CC Cooling Coil
21
Cooling Coil & Chilled Water Demand Side
(cont’d)
Objects required (cont’d): BRANCH, Chilled Water Loop 1 CHW Inlet Branch
PIPE
BRANCH, Chilled Water Loop 1 CHW Outlet Branch PIPE
BRANCH, Chilled Water Loop 1 CHW Bypass Branch PIPE
BypassChilled Water Demand -Side Outlet Node
Chilled Water Demand -Side Inlet Note
CC Cooling Coil
BypassChilled Water Demand -Side Outlet Node
Chilled Water Demand -Side Inlet Note
CC Cooling Coil
22
Hot Water Demand Side
North
Zone
East
Zone
Resistive
Zone
Plant Supply SideCooling Loop
CW Pump
CoolingTower
Cond . Pump
Cond . Supply Side Loop
ChillerBypass
Supply Fan
Re
turn
Air
Mix
er
Zo
ne A
ir Sp
litter
Plant Demand SideCooling Loop
Pla
nt D
em
an
d S
ide
Hea
ting
Loo
p
CC
Byp
ass
CondenserBypass
VAV Box: ReHeat
VAV Box: ReHeat
Retu
rn H
ot
Wa
ter M
ixer
Bypass
Cond . DemandSide Loop
CondenserBypass
Hot W
ate
r
Sp
litter
Mixed OutsideAir Box
Relief Air
Outside Air
VAV Box: ReHeatBoiler
Plant Supply SideHeating Loop
HW Pump
North
Zone
East
Zone
Resistive
Zone
Plant Supply SideCooling Loop
CW Pump
CoolingTower
Cond . Pump
Cond . Supply Side Loop
ChillerBypass
Supply Fan
Re
turn
Air
Mix
er
Zo
ne A
ir Sp
litter
Plant Demand SideCooling Loop
Pla
nt D
em
an
d S
ide
Hea
ting
Loo
p
CC
Byp
ass
CondenserBypass
VAV Box: ReHeat
VAV Box: ReHeat
Retu
rn H
ot
Wa
ter M
ixer
Bypass
Cond . DemandSide Loop
CondenserBypass
Hot W
ate
r
Sp
litter
Mixed OutsideAir Box
Relief Air
Outside Air
VAV Box: ReHeatBoiler
Plant Supply SideHeating Loop
HW Pump
Boiler
Plant Supply SideHeating Loop
HW Pump
23
Hot Water Coils & Demand Side
Objects required: BRANCH LIST CONNECTOR LIST SPLITTER MIXER BRANCH,Zone X Reheat
Branch (3) COIL:Water:SimpleHeating(
3) BRANCH, HW Outlet Branch
PIPE BRANCH, HW Inlet Branch
PIPE BRANCH, HW Bypass Branch
PIPE
Zo
ne
Air S
plitte
r
Pla
nt D
em
an
d S
ide
Hea
ting
Lo
op
Retu
rn H
W M
ixer
Byp
ass
HW
Sp
litter
VAV Box:Reheat
VAV Box:Reheat
VAV Box:Reheat
Zo
ne
Air S
plitte
r
Pla
nt D
em
an
d S
ide
Hea
ting
Lo
op
Retu
rn H
W M
ixer
Byp
ass
HW
Sp
litter
VAV Box:Reheat
VAV Box:Reheat
VAV Box:Reheat
24
Hot Water Loop Supply Side
North
Zone
East
Zone
Resistive
Zone
Plant Supply SideCooling Loop
CW Pump
CoolingTower
Cond . Pump
Cond . Supply Side Loop
ChillerBypass
Supply Fan
Retu
rn A
ir M
ixe
r
Zone A
ir Splitte
r
Plant Demand SideCooling Loop
Pla
nt D
em
and S
ide
Heatin
g L
oop
CC
Byp
ass
CondenserBypass
VAV Box:ReHeat
VAV Box:ReHeat
Retu
rn H
ot
Wate
r Mixe
r
Bypass
Cond . DemandSide Loop
CondenserBypass
Hot W
ate
r
Splitte
r
Mixed OutsideAir Box
Relief Air
Outside Air
VAV Box:ReHeatBoiler
Plant Supply SideHeating Loop
HW Pump
North
Zone
East
Zone
Resistive
Zone
Plant Supply SideCooling Loop
CW Pump
CoolingTower
Cond . Pump
Cond . Supply Side Loop
ChillerBypass
Supply Fan
Retu
rn A
ir M
ixe
r
Zone A
ir Splitte
r
Plant Demand SideCooling Loop
Pla
nt D
em
and S
ide
Heatin
g L
oop
CC
Byp
ass
CondenserBypass
VAV Box:ReHeat
VAV Box:ReHeat
Retu
rn H
ot
Wate
r Mixe
r
Bypass
Cond . DemandSide Loop
CondenserBypass
Hot W
ate
r
Splitte
r
Mixed OutsideAir Box
Relief Air
Outside Air
VAV Box:ReHeatBoiler
Plant Supply SideHeating Loop
HW Pump
Boiler
Plant Supply SideHeating Loop
HW Pump
25
Hot Water Loop Supply Side
Hot Water Loop Supply Side
Objects required: PLANT LOOP BRANCH LIST CONNECTOR LIST SPLITTER MIXER BRANCH, Supply Inlet
Branch PUMP:VARIABLE SPEED
Boiler
Pla
nt
De
ma
nd
Sid
eH
ea
ting
Lo
op
Boiler Outlet Node
HW Pump
HW PumpOutlet Node
Byp
ass
BoilerInlet Node
HW SupplyInlet Node
HW SupplyOutlet Node
26
Objects required: BRANCH, Boiler Branch
BOILER:SIMPLE BRANCH, Supply Bypass Branch
PIPE BRANCH, Supply Outlet Branch
PIPE PLANT OPERATION SCHEME
HEATING LOAD RANGE BASED OPERATION
HEATING LOAD RANGE EQUIPMENT LIST
Hot Water Loop Supply Side
Hot Water Loop Supply Side (cont’d)
Boiler
Pla
nt
De
ma
nd
Sid
eH
ea
ting
Lo
op
Boiler Outlet Node
HW Pump
HW PumpOutlet Node
Byp
ass
BoilerInlet Node
HW SupplyInlet Node
HW SupplyOutlet Node
27
Chilled Water Supply Side
North
Zone
East
Zone
Resistive
Zone
Plant Supply SideCooling Loop
CW Pump
CoolingTower
Cond . Pump
Cond . Supply Side Loop
ChillerBypass
Supply Fan
Re
turn
Air
Mix
er
Zon
e A
ir Sp
litter
Plant Demand SideCooling Loop
Pla
nt D
em
an
d S
ide
He
atin
g L
oop
CC
Byp
ass
CondenserBypass
VAV Box: ReHeat
VAV Box: ReHeat
Re
turn
Ho
t
Wate
r Mixe
rBypass
Cond . DemandSide Loop
CondenserBypass
Ho
t Wate
r
Sp
litter
Mixed OutsideAir Box
Relief Air
Outside Air
VAV Box: ReHeatBoiler
Plant Supply SideHeating Loop
HW Pump
North
Zone
East
Zone
Resistive
Zone
Plant Supply SideCooling Loop
CW Pump
CoolingTower
Cond . Pump
Cond . Supply Side Loop
ChillerBypass
Supply Fan
Re
turn
Air
Mix
er
Zon
e A
ir Sp
litter
Plant Demand SideCooling Loop
Pla
nt D
em
an
d S
ide
He
atin
g L
oop
CC
Byp
ass
CondenserBypass
VAV Box: ReHeat
VAV Box: ReHeat
Re
turn
Ho
t
Wate
r Mixe
rBypass
Cond . DemandSide Loop
CondenserBypass
Ho
t Wate
r
Sp
litter
Mixed OutsideAir Box
Relief Air
Outside Air
VAV Box: ReHeatBoiler
Plant Supply SideHeating Loop
HW Pump
Boiler
Plant Supply SideHeating Loop
HW Pump
28
Plant Supply SideCooling LoopCW Pump
Chiller
Byp
ass
Plant Demand SideCooling Loop
Objects required: PLANT LOOP, Chiller Plant Chilled Water Loop BRANCH LIST CONNECTOR LIST SPLITTER MIXER
Chilled Water Supply Side
29
Objects required (cont’d): BRANCH, Chiller Plant Cooling Supply Inlet Branch
PUMP:VARIABLE SPEED BRANCH, Chiller Plant Chiller Branch
CHILLER:Electric BRANCH, Chiller Plant Cooling Supply Bypass Branch
PIPE
Chilled Water Supply Side (cont’d)
Plant Supply SideCooling LoopCW Pump
Chiller
Byp
ass
Plant Demand SideCooling Loop
30
Objects required (cont’d): BRANCH, Chiller Plant Cooling Supply Outlet Branch
PIPE PLANT OPERATION SCHEMES
COOLING LOAD RANGE BASED OPERATION COOLING LOAD RANGE EQUIPMENT LIST
Chilled Water Supply Side (cont’d)
Plant Supply SideCooling LoopCW Pump
Chiller
Byp
ass
Plant Demand SideCooling Loop
31
Condenser Loop Demand Side
North
Zone
East
Zone
Resistive
Zone
Plant Supply SideCooling Loop
CW Pump
CoolingTower
Cond . Pump
Cond . Supply Side Loop
ChillerBypass
Supply Fan
Retu
rn A
ir M
ixe
r
Zo
ne A
ir Sp
litter
Plant Demand SideCooling Loop
Pla
nt D
em
an
d S
ide
Hea
ting
Loo
p
CC
Byp
ass
CondenserBypass
VAV Box: ReHeat
VAV Box: ReHeat
Retu
rn H
ot
Wa
ter M
ixer
Bypass
Cond . DemandSide Loop
CondenserBypass
Hot W
ate
r
Sp
litter
Mixed OutsideAir Box
Relief Air
Outside Air
VAV Box: ReHeatBoiler
Plant Supply SideHeating Loop
HW Pump
North
Zone
East
Zone
Resistive
Zone
Plant Supply SideCooling Loop
CW Pump
CoolingTower
Cond . Pump
Cond . Supply Side Loop
ChillerBypass
Supply Fan
Retu
rn A
ir M
ixe
r
Zo
ne A
ir Sp
litter
Plant Demand SideCooling Loop
Pla
nt D
em
an
d S
ide
Hea
ting
Loo
p
CC
Byp
ass
CondenserBypass
VAV Box: ReHeat
VAV Box: ReHeat
Retu
rn H
ot
Wa
ter M
ixer
Bypass
Cond . DemandSide Loop
CondenserBypass
Hot W
ate
r
Sp
litter
Mixed OutsideAir Box
Relief Air
Outside Air
VAV Box: ReHeatBoiler
Plant Supply SideHeating Loop
HW Pump
Boiler
Plant Supply SideHeating Loop
HW Pump
32
Plant Supply SideCooling Loop
Chiller
Condenser SupplySide Loop
Condenser Bypass
Objects required: BRANCH LIST CONNECTOR LIST SPLITTER MIXER BRANCH, Condenser Demand Inlet
Branch PIPE
BRANCH, Chiller Condenser Branch CHILLER:Electric
BRANCH, Cond. Demand Bypass Branch PIPE
BRANCH, Cond. Demand Outlet Branch PIPE
Condenser Loop Demand Side
33
Condenser Supply Side
North
Zone
East
Zone
Resistive
Zone
Plant Supply SideCooling Loop
CW Pump
CoolingTower
Cond . Pump
Cond . Supply Side Loop
ChillerBypass
Supply Fan
Retu
rn A
ir M
ixe
r
Zone A
ir Splitte
r
Plant Demand SideCooling Loop
Pla
nt D
em
and S
ide
Heatin
g L
oop
CC
Byp
ass
CondenserBypass
VAV Box:ReHeat
VAV Box:ReHeat
Retu
rn H
ot
Wate
r Mixe
rBypass
Cond . DemandSide Loop
CondenserBypass
Hot W
ate
r
Splitte
r
Mixed OutsideAir Box
Relief Air
Outside Air
VAV Box:ReHeatBoiler
Plant Supply SideHeating Loop
HW Pump
North
Zone
East
Zone
Resistive
Zone
Plant Supply SideCooling Loop
CW Pump
CoolingTower
Cond . Pump
Cond . Supply Side Loop
ChillerBypass
Supply Fan
Retu
rn A
ir M
ixe
r
Zone A
ir Splitte
r
Plant Demand SideCooling Loop
Pla
nt D
em
and S
ide
Heatin
g L
oop
CC
Byp
ass
CondenserBypass
VAV Box:ReHeat
VAV Box:ReHeat
Retu
rn H
ot
Wate
r Mixe
rBypass
Cond . DemandSide Loop
CondenserBypass
Hot W
ate
r
Splitte
r
Mixed OutsideAir Box
Relief Air
Outside Air
VAV Box:ReHeatBoiler
Plant Supply SideHeating Loop
HW Pump
Boiler
Plant Supply SideHeating Loop
HW Pump
34
Condenser Supply Side
Cooling Tower
CondenserPump
Condenser Bypass
Condenser DemandSide LoopObjects required:
CONDENSER LOOP BRANCH LIST CONNECTOR LIST SPLITTER MIXER BRANCH, Supply Inlet Branch
PIPE BRANCH, Condenser Branch
COOLING TOWER:Single Speed
Condenser Loop Supply Side
35
Condenser Supply Side
Cooling Tower
CondenserPump
Condenser Bypass
Condenser DemandSide LoopObjects required (cont’d):
BRANCH, Cond. Supply Bypass Branch
PIPE BRANCH, Supply Output Branch
PIPE CONDENSER OPERATION
SCHEMES COOLING LOAD RANGE BASED
OPERATION LOAD RANGE EQUIPMENT LIST
Condenser Loop Supply Side (cont’d)
36
Summary
Loops are backbone of HVAC simulation all equipment attached to air or fluid loops
Loop structure permits assembly of any system through input—not hardwired
Primary system may consist of four different loops: plant supply and demand, condenser supply and demand
Pumps regulate flow while attempting to meet requests on both sides of each loop pair
Individual loops may have components in series and parallel with some limitations