Lecture 10: Zone and Modeling Controls, Simple HVAC for Load Calculations Material prepared by GARD...
-
Upload
patrick-rasor -
Category
Documents
-
view
239 -
download
6
Transcript of Lecture 10: Zone and Modeling Controls, Simple HVAC for Load Calculations Material prepared by GARD...
Lecture 10: Zone and Modeling Controls, Simple HVAC for Load Calculations
Material prepared by GARD Analytics, Inc. and University of Illinoisat Urbana-Champaign under contract to the National Renewable Energy
Laboratory. All material Copyright 2002-2003 U.S.D.O.E. - All rights reserved
2
Importance of this Lecture to the Simulation of Buildings
Almost all buildings are “controlled thermal environments”
To calculate how much energy is required to maintain the appropriate thermal environment, an energy simulation program needs the control strategy
Resulting heating and cooling loads can be a good basis for comparing different envelope designs before addressing HVAC issues
Simulation programs always have “details”—this lecture discusses some of the simulation parameters that might be of importance to some runs
3
Purpose of this Lecture
Gain an understanding of how to: Obtain heating and cooling loads for
zones without defining an entire HVAC system
Calculate approximate air flow rates for zones
Control some of the modeling details of a thermal simulation using EnergyPlus
4
Keywords Covered in this Lecture
Zone Control:ThermostaticSingle Heating Setpoint, Single Cooling
Setpoint, Dual Setpoint With DeadbandSchedule (review)Purchased Air (and some affiliated input)Simulation Control Parameters: TimeStep
in Hour, Inside/Outside Convection Algorithm, Sky Radiance Distribution, Solution Algorithm, Shadowing Calculation, Convection Coefficients
5
Thermostatic Control
Controls zone to a specified temperature
Control options include:0 – Uncontrolled
1 – Single heating setpoint
2 – Single cooling setpoint
3 – Single heating/cooling setpoint
4 – Dual setpoint with deadband
No heating or cooling, zone “floats”
Heats to setpoint, no coolingCools to setpoint, no heating
“Perfect” control
Heating below lower setpoint,Cooling above higher setpoint,Zone “floats” in deadband between setpoints
6
Zone Thermostat
Basic Format of EnergyPlus Input:ZONE CONTROL:THERMOSTATIC,
Zone Name,
Control Type SCHEDULE Name,
Control Type #1,
!-Single Heating Setpoint Control type sched = 1
!-Single Cooling SetPoint Control type sched = 2
!-Single Heating Cooling Setpoint Control type sched = 3
!-Dual Setpoint with Deadband Control type sched = 4
Control Type Name #1,
…(Repeat for each thermostatic control type in zone)… ;
7
Zone Thermostat - Example
ZONE CONTROL:THERMOSTATIC,
SPACE1-1 Control, !- Thermostat Name
SPACE1-1, !- Zone Name
Zone Control Type Sched, !- Control Type SCHEDULE Name
Single Cooling Setpoint, !- Control Type
Cooling Setpoint with Setback, !- Control Type Name
Single Heating Setpoint, !- Control Type
Heating Setpoint with Setback; !- Control Type Name
Schedules of setpoint temperatures (example on slide 9); allows setpoint temperature to vary (i.e., setback)
Schedule of control type parameter (0-4);determines which control type is valid at a particular time
8
Zone ThermostatControl Type Schedule
DAYSCHEDULE, Summer Control Type Day Sch, Control Type, 2,2,2,2,2,2,2,2,2,2,2,2,2,2,2,2,2,2,2,2,2,2,2,2; ! 2=single cool SP
DAYSCHEDULE, Winter Control Type Day Sch, Control Type, 1,1,1,1,1,1,1,1,1,1,1,1,1,1,1,1,1,1,1,1,1,1,1,1; ! 1=single heat SP
WEEKSCHEDULE, Summer Control Type Week Sch, Summer Control Type Day Sch, . . . ;
WEEKSCHEDULE, Winter Control Type Week Sch, Winter Control Type Day Sch, . . . ;
SCHEDULE, Zone Control Type Sched, Control Type, Winter Control Type Week Sch, 1,1, 3,31, Summer Control Type Week Sch, 4,1, 9,30, Winter Control Type Week Sch, 10,1, 12,31;
Values can change hourly if necessary (0-4) to model situations such as heating/cooling during the day and heating only at night for freeze protection
J F M A M J J A S O N D
Control Type Schedule
heating cooling heating
9
Zone ThermostatHeating Setpoint Object
SINGLE HEATING SETPOINT, Heating Setpoint with Setback, !- Setpoint control object nameHeating Setpoints; !- Setpoint schedule
DAYSCHEDULE, Heating Setpoint Day Sch, Temperature, 15.,15.,15.,15.,15.,15.,15.,20.,20.,20.,20.,20.,20.,20.,20.,20.,20., 15.,15.,15.,15.,15.,15.,15.;
WEEKSCHEDULE, Heating Setpoint Week Sch, !- Name Heating Setpoint Day Sch, !- Sunday DAYSCHEDULE Name Heating Setpoint Day Sch, !- Monday DAYSCHEDULE Name Heating Setpoint Day Sch, !- Tuesday DAYSCHEDULE Name Heating Setpoint Day Sch, !- Wednesday DAYSCHEDULE Name Heating Setpoint Day Sch, !- Thursday DAYSCHEDULE Name Heating Setpoint Day Sch, !- Friday DAYSCHEDULE Name Heating Setpoint Day Sch, !- Saturday DAYSCHEDULE Name Heating Setpoint Day Sch, !- Holiday DAYSCHEDULE Name Heating Setpoint Day Sch, !- SummerDesignDay DAYSCHEDULE Name Heating Setpoint Day Sch, !- WinterDesignDay DAYSCHEDULE Name Heating Setpoint Day Sch, !- CustomDay1 DAYSCHEDULE Name Heating Setpoint Day Sch; !- CustomDay2 DAYSCHEDULE Name
SCHEDULE, Heating Setpoints, Temperature, Heating Setpoint Week Sch, 1,1, 12,31;
midnight 6am noon 6pm
1520
heating
no conditioning
10
Set Point Objects - Examples
SINGLE HEATING SETPOINT,
HeatingSetpoint, !- Name
Htg-SetP-Sch; !- Setpoint Temp SCHEDULE Name
SINGLE COOLING SETPOINT,
CoolingSetpoint, !- Name
Clg-SetP-Sch; !- Setpoint Temp SCHEDULE Name
DUAL SETPOINT WITH DEADBAND,
DualSetPoint, !- Name
Htg-SetP-Sch, !- Heating Setpoint Temp SCHEDULE Name
Clg-SetP-Sch; !- Cooling Setpoint Temp SCHEDULE Name
11
Purchased Air
Used to compute zone heating/cooling loads without modeling an HVAC system
Unlimited capacity at specified temperature and humidity
Controls only Zone dry bulb temperatureResulting humidity level calculatedControlled by Zone thermostat (dry bulb
setpoint)Calculates required flow rate at specified
supply air temperature
12
Purchased Air – Example
PURCHASED AIR, Zone1Air, !- Purchased Air Name NODE_1, !- Zone Supply Air Node Name 50, !- Heating Supply Air Temp {C} 15, !- Cooling Supply Air Temp {C} 0.02, !- Heating Supply Air Humidity Ratio {kg-H20/kg-air} 0.02; !- Cooling Supply Air Humidity Ratio {kg-H20/kg-air}CONTROLLED ZONE EQUIP CONFIGURATION, RESISTIVE ZONE, Zone1Equipment, Zone1Inlets, , NODE_4,NODE_5;ZONE EQUIPMENT LIST, Zone1Equipment, PURCHASED AIR, Zone1Air, 1, 1;NODE LIST, Zone1Inlets, NODE_1;
These keywords will be discussed in more detail in a future lecture; all are required to get purchased air to work
Note that the colors in the above example denote the interconnections of these different statements
13
Complete Purchased Air Example (Everything you need to condition a zone)
SCHEDULETYPE,ControlType,0:4,DISCRETE;DAYSCHEDULE,Zone Control Day, ControlType,4,4,4,4,4,4,4,4,4,4,4,4,4,4,4,4,4,4,4,4,4,4,4,4;WEEKSCHEDULE, Zone Control Week, Zone Control Day,Zone Control Day,Zone Control Day,Zone Control Day,Zone Control Day,Zone Control Day, Zone Control Day,Zone Control Day,Zone Control Day,Zone Control Day,Zone Control Day,Zone Control Day;SCHEDULE, Zone Control Type Schedule, ControlType, Zone Control Week,1,1,12,31;DAYSCHEDULE,Heat Temp 5,Temperature, 20.0, 20.0, 20.0, 20.0, 20.0, 20.0, 20.0, 20.0, 20.0, 20.0, 20.0,
20.0, 20.0, 20.0, 20.0, 20.0, 20.0, 20.0, 20.0, 20.0, 20.0, 20.0, 20.0, 20.0;DAYSCHEDULE,Cool Temp 5,Temperature, 25.6, 25.6, 25.6, 25.6, 25.6, 25.6, 25.6, 25.6, 25.6, 25.6, 25.6,
25.6, 25.6, 25.6, 25.6, 25.6, 25.6, 25.6, 25.6, 25.6, 25.6, 25.6, 25.6, 25.6;WEEKSCHEDULE,HEAT-DEAD BAND, Heat Temp 5, Heat Temp 5, Heat Temp 5, Heat Temp 5, Heat Temp 5, Heat Temp 5,
Heat Temp 5, Heat Temp 5, Heat Temp 5, Heat Temp 5, Heat Temp 5, Heat Temp 5;WEEKSCHEDULE,COOL-DEAD BAND, Cool Temp 5, Cool Temp 5, Cool Temp 5, Cool Temp 5, Cool Temp 5, Cool Temp 5,
Cool Temp 5, Cool Temp 5, Cool Temp 5, Cool Temp 5, Cool Temp 5, Cool Temp 5;SCHEDULE,ZONE 1 Heating Setpoints,Temperature,HEAT-DEAD BAND, 1, 1,12,31;SCHEDULE,ZONE 1 Cooling Setpoints,Temperature,COOL-DEAD BAND, 1, 1,12,31;
ZONE CONTROL:THERMOSTATIC, ZONE 1 CONTROLS, ZONE 1,Zone Control Type Schedule,DUAL SETPOINT WITH DEADBAND, ZONE 1 SETPOINTS;
DUAL SETPOINT WITH DEADBAND, ZONE 1 SETPOINTS,ZONE 1 Heating Setpoints,ZONE 1 Cooling Setpoints;PURCHASED AIR, ZONE 1 PURCHASED AIR, ZONE 1 INLETS, !- Zone Supply Air Node 50, !- Heating Supply Air Temperature {C} 13, !- Cooling Supply Air Temperature {C} 0.015, !- Heating Supply Air Humidity Ratio {kg-H2O/kg-Air} 0.010; !- Cooling Supply Air Humidity Ratio {kg-H2O/kg-Air}CONTROLLED ZONE EQUIP CONFIGURATION, ZONE 1, ZONE 1 EQUIPMENT, ZONE 1 INLETS,, ZONE 1 NODE, ZONE 1 OUTLET;ZONE EQUIPMENT LIST, ZONE 1 EQUIPMENT, PURCHASED AIR, ZONE 1 PURCHASED AIR, 1, 1;NODE LIST, ZONE 1 INLETS,ZONE 1 INLET;
14
TimeStep in Hour
EnergyPlus is a “sub-hourly” simulation program—capable of simulating the building at time steps of less than one hour
Example:TIMESTEP IN HOUR, 4; !- Number of time steps in an hour--validity 1 to 6--4 suggested
Sets time step for zone portion of simulation to 15 minutes;HVAC may run at time steps of less than 15 minutes to insure the stability of the system response (adaptive time step discussed in future lecture)
15
Solution Algorithm
User has ability to control the details of the simulation algorithm Options include standard heat
transfer only, heat and mass transfer, and detailed (layer-by-layer) heat and mass transferSOLUTION ALGORITHM,
\memo Determines which Heat Balance Algorithm will be used \unique-object A1 ; \field Solution Algorithm \required-field \type choice \key CTF—Conduction Transfer Functions (heat transfer only) \key MTF—Moisture Transfer Functions (detailed heat+mass) \key EMPD—Effective Moisture Penetration Depth (heat+mass) \default CTF
Note that requesting heat and mass transfer simulations can significantly increase execution time
16
Inside Convection Algorithm
User may selection the inside convection correlation from following options: Simple—constant natural convection Detailed—variable natural convection CeilingDiffuser—ACH-based correlation TrombeWall—closed rectangular cavity
from ASHRAE
from research
17
Inside Convection Algorithm (cont’d)
ASHRAE Simple Correlation for Interior Convection Cool floor or warm ceiling: hconv = 0.948 W/m2-K Tilted surface, reduced: hconv = 2.281 W/m2-K
where reduced means a surface tilted in such a way as to mimic the poorer conditions for natural convection as in the cool floor/warm ceiling situation
Vertical surface: hconv = 3.076 W/m2-K Warm floor or cool ceiling: hconv = 4.040 W/m2-K Tilted surface, enhanced: hconv = 3.870 W/m2-K
where enhanced means a surface tilted in such a way as to mimic the better conditions for natural convection as in the warm floor/cool ceiling situation
18
Inside Convection Algorithm (cont’d)
ASHRAE Detailed Correlation for Interior Convection
Reduced convection:
Vertical surface:
Enhanced convection:
surf
3airsurf
conv cos382.1
TT81.1h
3airsurfconv TT31.1h
surf
3airsurf
conv cos283.7
TT482.9h
where surf is the tilt of the surface(surf=0 for roof, =90 for vertical wall, =180 for floor)
19
Inside Convection Algorithm (cont’d)
Ceiling Diffuser Correlation
Floor:
Wall:
Ceiling:
98.0conv ACH082.0873.3h
where ACH is the air changes per hour of the HVAC system
604.0conv ACH012.1208.1h
503.0conv ACH099.4234.2h
20
Outside Convection Algorithm
User may selection the outside convection correlation from following options: Simple—constant natural convection
where D, E, and F vary with surface roughness
Detailed—variable natural convection
where A incorporates surface and wind direction factors while B takes roughness into account and hnatural is identical to the natural convection correlation for the detailed inside convection algorithm
2windroughwindroughroughconv VFVEDh
windroughsurfnaturalconv VBAhh
21
ConvectionCoefficients
Allows user to set interior and/or exterior convection coefficients Could be used for comparison to other
programs or to determine influence of convection coefficients on simulation
ConvectionCoefficients, A1, \field SurfaceName A2, \field Convection Type #1 (either “Interior” or “Exterior”) A3, \field Convection Value Type #1 (either “Value” or “Schedule”) N1, \field Convection value #1 (W/m2-K, only used if A3 is Value) A4, \field Convection Schedule #1 (only used if A3 is Schedule) A5, \field Convection Type #2 (either “Interior” or “Exterior”) A6, \field Convection Value Type #2 (either “Value” or “Schedule”) N2, \field Convection value #2 (W/m2-K, only used if A3 is Value) A7; \field Convection Schedule #2 (only used if A3 is Schedule)
Two per surface to allow specification of both interior and exterior
22
Shadowing Calculation
EnergyPlus does shadowing calculation for periods of time and assumes that the shadow casting over this time period is the same each day
User can control how often this is done through Shadowing Calculation input Can force EnergyPlus to do this every day Shorter shadowing periods result in longer
run times for EnergyPlus
SHADOWING CALCULATIONS, N1 ; \field Shadowing period length in days (0 will use E+ default)
23
Airflow Model
This parameter is only needed if the user is trying to do detailed airflow studies using the EnergyPlus link to COMIS
This statement tells EnergyPlus to do the COMIS simulation but much more input data is required (see next lecture)
Airflow Model, COMIS; !- Airflow model type (COMIS or Simple, default is Simple)
24
Summary
Zone Thermostat input allows control of the air temperature within individual zones—control setpoint can change on an hourly basis
Purchased Air can be used as a simple HVAC system when doing initial studies or trying to determine the size of the air handling system
User has the option to control various details of the simulation such as time step, convection algorithms, shading calculations, and air flow modeling