Lecture 10 Analysis and Design of Waffle Slabs_2011

download Lecture 10 Analysis and Design of Waffle Slabs_2011

of 62

Transcript of Lecture 10 Analysis and Design of Waffle Slabs_2011

  • 1

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Lecture-10

    Analysis and Design of

    Two-way Slab Systems

    (Two Way Joist Slabs & Two-way Slab

    with Beams)

    By: Prof Dr. Qaisar Ali

    Civil Engineering Department

    UET Peshawar

    [email protected]

    1

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Topics Addressed

    Two-Way Joist Slab

    Introduction

    Behavior

    Characteristics

    Basic Steps for Structural Design

    Example

    2

  • 2

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Topics Addressed

    Moment Coefficient Method for Two Way Slab with

    Beams

    Introduction

    Cases

    Moment Coefficient Tables

    Reinforcement Requirements

    Steps

    Example

    3

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 4

    Two-Way Joist Slab

  • 3

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 5

    Introduction

    A two-way joist system, or waffle slab, comprises evenly

    spaced concrete joists spanning in both directions and a

    reinforced concrete slab cast integrally with the joists.

    Two-Way Joist

    Joist

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 6

    Introduction

    Like one-way joist system, a two way system will be called

    as two-way joist system if clear spacing between ribs (dome

    width) does not exceed 30 inches.

    Two-Way Joist

  • 4

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 7

    Introduction

    Two-Way Joist

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Introduction

    The joists are commonly formed by using standard square

    dome forms and the domes are omitted around the columns

    to form the solid heads.

    8

    Two-Way Joist

    Solid Head

  • 5

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two-Way Joist

    Introduction

    Standard Dome Data

    Generally the dome for waffle slab can be of any size. However the

    commonly used standard domes are discussed as follows:

    30-inch 30-inch square domes with 3-inch flanges; from which 6-

    inch wide joist ribs at 36-inch centers are formed: these are

    available in standard depths of 8, 10, 12, 14, 16 and 20 inches.

    19-inch 19-inch square domes with 2 -inch flanges, from which

    5-inch wide joist ribs at 24-inch centers are formed. These are

    available in standard depths of 8, 10, 12, 14 and 16 inches.

    9

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two-Way Joist

    Introduction

    Standard Dome Data

    10

  • 6

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Behavior

    The behavior of two-way joist slab is similar to a two way flat

    Slab system.

    Two-Way Joist

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Characteristics

    Dome voids reduce dead load.

    Attractive ceiling (waffle like appearance).

    Electrical fixtures can be placed in the voids.

    Particularly advantageous where the use of longer spans

    and/or heavier loads are desired without the use of

    deepened drop panels or supported beams.

    Two-Way Joist

  • 7

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Basic Steps for Structural Design

    Step No. 01 (Sizes): Sizes of all structural and non

    structural elements are decided.

    Step No. 02 (Loads): Loads on structure are determined

    based on occupational characteristics and functionality.

    Step No. 03 (Analysis): Effect of loads are calculated on all

    structural elements.

    Step No. 04 (Design): Structural elements are designed for

    the respective load effects following code provisions.

    13

    Two-Way Joist

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Sizes

    Minimum Joist Depth

    For Joist depth determination, waffle slabs are considered as flat slab

    (ACI 13.1.3, 13.1.4 & 9.5.3).

    The thickness of equivalent flat slab is taken from table 9.5 (c).

    The thickness of slab and depth of rib of waffle slab can be then

    computed by equalizing the moment of inertia of equivalent flat slab to

    that of waffle slab.

    However since this practice is time consuming, tables have been

    developed to determine the size of waffle slab from equivalent flat slab

    thickness.

    14

    Two-Way Joist

  • 8

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Sizes

    Minimum Joist Depth

    Equivalent Flat Slab Thickness

    ACI 318-05 Sect. 9.5.3

    Minimum thickness = ln/33

    15

    Two-Way Joist

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 16

    Sizes

    Minimum Joist Depth

    Slab and rib depth from equivalent flat slab thickness

    Two-Way Joist

    Table 01: Waffle flat slabs (19" 19" voids at 2'-0")-Equivalent thickness

    Rib + Slab Depths (in.) Equivalent Thickness te (in.)

    8 + 3 8.89

    8 + 4 10.11

    10 + 3 10.51

    10 + 4 11.75

    12 + 3 12.12

    12 + 4 13.38

    14 + 3 13.72

    14 + 4 15.02

    16 + 3 15.31

    16 + 4 16.64

    Reference: Table 11-2 of CRSI Design Handbook 2002.

    Note: Only first two columns of the table are reproduced here.

  • 9

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 17

    Sizes

    Minimum Joist Depth

    Slab and rib depth from equivalent flat slab thickness

    Two-Way Joist

    Table 02: Waffle flat slabs (30" 30" voids at 3'-0")-Equivalent thickness

    Rib + Slab Depths (in.) Equivalent Thickness te (in.)

    8 + 3 8.61

    8 + 4 9.79

    10 + 3 10.18

    10 + 4 11.37

    12 + 3 11.74

    12 + 4 12.95

    14 + 3 13.3

    14 + 4 14.54

    16 + 3 14.85

    16 + 4 16.12

    20 + 3 17.92

    20 + 4 19.26

    Reference: Table 11-2 of CRSI Design Handbook 2002.

    Note: Only first two columns of the table are reproduced here.

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 18

    Sizes

    Minimum Width of Rib

    ACI 8.11.2 states that ribs shall be not less than 4 inches in width.

    Maximum Depth of Rib

    ACI 8.11.2 also states that ribs shall have a depth of not more than 3

    times the minimum width of rib.

    Minimum Slab Thickness

    ACI 8.11.6.1 states that slab thickness shall be not less than one-

    twelfth the clear distance between ribs, nor less than 2 inch.

    Two-Way Joist

  • 10

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 19

    Sizes

    Solid Head

    Dimension of solid head on either side of column centerline is equal to

    l/6.

    The depth of the solid head is equal to the depth of the combined

    depth of ribs and top slab.

    Two-Way Joist

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 20

    Loads

    Floor dead load for two-way joist with certain dome size, dome depth can

    be calculated from the table shown for two options of slab thicknesses (3

    inches and 4 inches).

    Two-Way Joist

    Table 03: Standard Dome Dimensions and other Data

    Dome Size Dome Depth

    (inches)

    Volume of Void

    (ft3)

    Floor Dead Load (psf) per slab

    thickness

    3 inches 4 inches

    30 inches

    8 3.98 71 90

    10 4.92 80 99

    12 5.84 90 109

    14 6.74 100 119

    16 7.61 111 129

    20 9.3 132 151

    19 inches

    8 1.56 79 98

    10 1.91 91 110

    12 2.25 103 122

    14 2.58 116 134

    16 2.9 129 148 Reference: Table 11-1, CRSI Design Handbook 2002

  • 11

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 21

    Loads

    Floor dead load (wdj) for two-way joist can also be

    calculated as follows:

    Two-Way Joist

    36

    8

    3

    30

    Volume of solid:

    Vsolid = (36 36 11)/1728 = 8.24 ft3

    Volume of void:

    Vvoid = (30 30 8)/1728 = 4.166 ft3

    Total Load of joists per dome:

    wdj = (Vsolid Vvoid) conc = ( 8.24 4.166) 0.15 = 0.61 kips/ dome

    Total Load of joists per sq. ft:

    wdj/ (dome area) = 0.61/ (3 3) = 0.0679 ksf

    = 68 psf 71 psf (from table 03)

    The difference is because sloped ribs are not considered. Plan

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 22

    Loads

    Taking a panel out of the system:

    Two-Way Joist

    l2

    l1 wdj

    wdj + wsh

    l1

    a a

    b l2

    wdj = Dead load at joist (load/ area)

    wsh = Dead load of solid head (load/ area)

    wdj + wsh

  • 12

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 23

    Loads

    If the complete area l1 l2 is assumed to occupy joists

    alone, then the dead load in the area l1 l2 will be wdj.

    However since there are solid head regions present,

    therefore additional dead load due to solid head region shall

    be:

    wdsh = hsolid conc - wdj

    Two-Way Joist

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 24

    Loads

    Factored loads can be calculated as:

    If wL = live load (load/area)

    wdj = dead load at joists, then

    Factored load due to joists (wj)

    wuj = 1.2 wdj + 1.6wL

    Factored load due to solid head (wsh)

    wush = 1.2(wdsh wdj)

    Two-Way Joist

    wj wsh

    l1

    a a

    b

    wsh

    l2

  • 13

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Analysis

    ACI code allows use of DDM for analysis of waffle slabs (ACI

    R13.1). In such a case, waffle slabs are considered as flat

    slabs, with the solid head acting as drop panels (ACI 13.1.3).

    25

    Two-Way Joist

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Analysis

    Static moment calculation for DDM analysis:

    26

    Two-Way Joist

    wuj

    ln

    Moj = wujl2ln2/8

    wush

    ln a a

    wush

    Mosh = wushba2/2

    Moj Mosh

    Mo = Moj + Mosh

    b l2

    ln

  • 14

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Design

    Design of slab for punching shear

    The solid head shall be checked against punching shear.

    The critical section for punching shear is taken at a section d/2 from face

    of the column, where d is the effective depth at solid head.

    27

    Two-Way Joist

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Design

    Design of slab for

    punching shear

    Load on tributary area will

    cause punch out shear.

    Within tributary area, two

    types of loads are acting:

    Solid head load

    Joist load

    Both types shall be

    considered while calculating

    punching shear demand

    28

    Two-Way Joist

    l2 d/2

    l1

  • 15

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Design

    Design of slab for punching

    shear

    Total area (At) = l1 l2

    Solid head area = Asolid

    Critical perimeter area = Acp

    Vu =At wuj + Asolid (wish wuj)

    Where,

    wuj = Factored load considering

    joist alone

    wsh = Factored solid head dead

    load

    29

    Two-Way Joist

    l2 d/2

    l1

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 30

    Design

    Shear Strength of Slab in Punching Shear:

    Vn = Vc + Vs

    Vc is least of:

    4 (fc)bod

    (2 + 4/c) (fc)bod

    {(sd/bo +2} (fc)bod

    c = longer side of column/shorter side of column

    s = 40 for interior column, 30 for edge column, 20 for corner columns

    Two-Way Joist

  • 16

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 31

    Design

    Design of Joist for Beam Shear:

    Beam Shear Demand

    Beam shear is not usually a problem in slabs including waffle slabs.

    However for completion of design beam shear may also be

    checked. Beam shear can cause problem in case where larger

    spans and heavier loads with relatively shallow waffle slabs are

    used.

    The critical section for beam shear is taken at a section d from face

    of the column, where d is the effective depth at solid head.

    Two-Way Joist

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 32

    Design

    Design of Joist for Beam Shear:

    Beam shear capacity of concrete joist:

    Vn = Vc + Vs

    Vc is least of:

    2 (fc)bribd

    Vs = Avfy/bribs

    For joist construction, contribution of concrete to shear strength Vc shall be

    permitted to be 10 percent more than that specified in Chapter 11.

    If required, one or two single legged stirrups are provided in the rib to

    increase the shear capacity of waffle slab.

    Two-Way Joist

    Stirrup

  • 17

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Design

    Design for Flexure

    The design of waffle slab for flexure is done by usual procedures.

    However, certain reinforcement requirements apply discussed next.

    33

    Two-Way Joist

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    ACI Recommendations on Reinforcement

    Requirement of Waffle Slab:

    Recommendations for Ribs:

    ACI 10.6.7 states that if the effective depth d of a beam or joist

    exceeds 36 inches, longitudinal skin reinforcement shall be provided as

    per ACI section 10.6.7.

    34

    Two-Way Joist

  • 18

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    ACI Recommendations on Reinforcement

    Requirement of Waffle Slab:

    Recommendations for Slab:

    According to ACI 13.3.2, for cellular or ribbed construction reinforcement

    shall not be less than the requirements of ACI 7.12.

    As per ACI 7.12, Spacing of top bars cannot exceed 5h or 18 inches.

    35

    Two-Way Joist

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Other Important Points:

    The amount of reinforcement and, if necessary, the top slab

    thickness can be changed to vary the load capacities for

    different spans, areas, or floors of a structure.

    Each joist rib contains two bottom bars. Straight bars are

    supplied over the column centerlines for negative factored

    moment.

    36

    Two-Way Joist

    Bottom bar

  • 19

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Other Important Points:

    For layouts that do not meet the standard 2-feet and 3-feet

    modules, it is preferable that the required additional width be

    obtained by increasing the width of the ribs framing into the

    solid column head.

    37

    Two-Way Joist

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Other Important Points:

    The designer should sketch out the spacing for a typical panel

    and correlate with the column spacing as a part of the early

    planning.

    38

    Two-Way Joist

  • 20

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Example: Design the slab system of hall shown in figure as waffle

    slab, according to ACI 318. Use Direct Design Method for slab

    analysis.

    fc = 4 ksi

    fy = 60 ksi

    Live load = 100 psf

    39

    Two-Way Joist

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Solution:

    A 108 144 building, divided into twelve (12) panels, supported at

    their ends on columns. Each panel is 36 36.

    The given slab system satisfies all the necessary limitations for Direct

    Design Method to be applicable.

    40

    Two-Way Joist

  • 21

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 01: Sizes

    Columns

    Let all columns be 18 18.

    Slab

    Adopt 30 30 standard dome.

    Minimum equivalent flat slab thickness (hf) can be found using ACI Table

    9.5 (c):

    Exterior panel governs. Therefore,

    hf = ln/33

    ln = 36 (2 18/2)/12 = 34.5

    hf = (34.5/33) 12 = 12.45

    41

    Two-Way Joist

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 01: Sizes

    Slab

    The closest depth of doom that will fulfill the requirement of equivalent

    thickness of flat slab equal to 12.45 is 12 in. with a slab thickness of 4

    in. for a dome size of 30-in.

    42

    Table: Waffle flat slabs (30" 30" voids at 3'-0")-Equivalent thickness

    Rib + Slab Depths (in.) Equivalent Thickness te (in.)

    8 + 3 8.61

    8 + 4 9.79

    10 + 3 10.18

    10 + 4 11.37

    12 + 3 11.74

    12 + 4 12.95

    14 + 3 13.3

    14 + 4 14.54

    16 + 3 14.85

    16 + 4 16.12

    20 + 3 17.92

    20 + 4 19.26

    Two-Way Joist

  • 22

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 01: Sizes

    Planning of Joist layout

    43

    Two-Way Joist

    l = 36-0 = 432

    Standard module = 36 36

    No. of modules in 36-0:

    n = 432/36 = 12

    Planning:

    First joist is placed on interior column

    centerline with progressive placing of

    other joists towards exterior ends of

    panel. To flush the last joist with

    external column, the width of exterior

    joist comes out to be 15 (6+Column

    size /2) as shown in plan view.

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 01: Sizes

    Solid Head

    Solid head dimension from column centerline = l/6 = 36/6 = 6

    Total required length of solid head= 2 6 = 12

    As 3 3 module is selected, therefore 4 voids including joist witdh will

    make an interior solid head of 12.5 12.5. (Length of solid head = c/c

    distance between rib + rib width )

    Depth of the solid head = Depth of standard module = 12 + 4.5 = 16.5

    44

    Two-Way Joist

  • 23

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 02: Loads

    Floor (joist) dead load (wdj) = 109 psf = 0.109 ksf

    45

    Table: Standard Dome Dimensions and other Data

    Dome Size Dome Depth (in.) Volume of Void

    (ft3)

    Floor Dead Load (psf) per slab

    thickness

    3 inches 4 inches

    30-in

    8 3.98 71 90

    10 4.92 80 99

    12 5.84 90 109

    14 6.74 100 119

    16 7.61 111 129

    20 9.3 132 151

    19-in

    8 1.56 79 98

    10 1.91 91 110

    12 2.25 103 122

    14 2.58 116 134

    16 2.9 129 148 Reference: Table 11-1, CRSI Design Handbook 2002

    Two-Way Joist

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 46

    Step No 02: Loads

    Floor (joist) dead load (wdj) = 109 psf = 0.109 ksf

    Solid Head dead load (wsh) = chsh wdj

    = 0.15 {(12 + 4.5)/12} 0.109 = 0.097 ksf

    Two-Way Joist

    wdj Wdj+sh

    l1

    a a

    b

    Wdj+sh

    l2 a = 5.25 ft

    b = 12.5 ft

  • 24

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 47

    Step No 02: Loads

    wL = 100 psf = 0.100 ksf

    Load due to joists plus LL (wuj)

    wuj = 1.2 wdj + 1.6wL

    = 1.2 0.109 + 1.60.100

    = 0.291 ksf

    Load due to solid head dead load (wush)

    wush = 1.2wsh

    = 1.2 0.097 = 0.1164 ksf

    Two-Way Joist

    wush

    l1

    a a

    b l2

    wuj

    wush

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 03: Frame Analysis (E-W Interior Frame)

    Step 1: Marking E-W Interior Frame:

    48

    Two-Way Joist

    l2 = 36

  • 25

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 03: Frame Analysis (E-W Interior Frame)

    Step 2: Marking of Column and Middle Strips:

    49

    Two-Way Joist

    l2 = 36 CS/2 = Least of l1/4 or l2/4

    l2/4 = 36/4 = 9

    CS/2 = 9

    MS/2 = 9

    MS/2 = 9 CS/2 = 9

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 03: Frame Analysis (E-W Interior Frame)

    Step 03: Static Moment Calculation

    Moj (due to joists) = wojl2ln2/8

    = 0.291 36 34.52/8 = 1557.56 ft-kip

    Mosh (due to solid head excluding joists) = wush ba2/2

    = 0.116412.55.252/2 = 20 ft-kip

    Mo (total static moment) = Moj + Mosh = 1557.56 + 20 = 1577.56 ft-kip

    Note: Since normally, Mosh is much smaller than Moj the former can be

    conveniently ignored in design calculations.

    50

    Two-Way Joist

  • 26

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 03: Frame Analysis (E-W Interior Frame)

    Step 03: Static Moment Calculation.

    51

    Two-Way Joist

    l2 = 36

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 03: Frame Analysis (E-W Interior Frame)

    Step 04: Longitudinal distribution of Total static moment (Mo).

    52

    Two-Way Joist

    l2 = 36 0.26

    0.52

    0.70 0.65

    0.35

    0.65 0.70 0.26

    0.52 Longitudinal

    distribution

    factors (D.F)L

  • 27

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 03: Frame Analysis (E-W Interior Frame)

    Step 04: Longitudinal distribution of Total static moment (Mo).

    53

    Two-Way Joist

    l2 = 36 410

    820

    1104 1025

    552

    1025 1104 410

    820

    Units: ft-kip

    ML = Mo (D.F)L

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 03: Frame Analysis (E-W Interior Frame)

    Step 05: Lateral Distribution of Longitudinal moment (L.M).

    54

    Two-Way Joist

    l2 = 36 0.60

    Lateral

    distribution

    factors (D.F)Lat 1.00 0.75 0.75 0.75

    0.60 0.60

    1.00 0.75

  • 28

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 03: Frame Analysis (E-W Interior Frame)

    Step 05: Lateral Distribution of Longitudinal moment (L.M).

    55

    Two-Way Joist

    l2 = 36 492

    410 828 769 769

    331 492

    410 828 MLat = ML (D.F)Lat

    ML,ext- = 410 kip-ft

    ML,ext+ = 820 kip-ft

    ML,int- = 1104 kip-ft

    ML,- = 1025 kip-ft

    ML,+ = 552 kip-ft

    328/2 328/2

    328/2 328/2

    0 0

    0 0

    276/2

    276/2

    276/2

    276/2

    221/2

    221/2

    256/2

    256/2

    256/2

    256/2

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 03: Frame Analysis (E-W Interior Frame)

    Step 05: Lateral Distribution of Longitudinal moment (L.M).

    56

    Two-Way Joist

    l2 = 36 27.3

    22.8 46 42.7 42.7

    18.38 27.3

    22.8 46 MLat per foot = Mlat/strip width

    ML,ext- = 410 kip-ft

    ML,ext+ = 820 kip-ft

    ML,int- = 1104 kip-ft

    ML,- = 1025 kip-ft

    ML,+ = 552 kip-ft

    18.22 18.22

    18.22 18.22

    0 0

    0 0

    15.33

    15.33

    15.33

    15.33

    12.3

    12.3

    14.22

    14.22

    14.22

    14.22

  • 29

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 03: Frame Analysis (E-W Exterior Frame)

    Step 03: Static Moment Calculation

    Moj (due to joists) = wojl2ln2/8

    = 0.291 18.75 34.52/8 = 811.78 ft-kip

    Mosh (due to solid head excluding joists) = wush ba2/2

    = 0.116475.252/2 = 12.83 ft-kip

    Mo (total static moment) = Moj + Mosh = 811.78 + 12.83 = 825 ft-kip

    Note: Since normally, Mosh is much smaller than Moj the former can be

    conveniently ignored in design calculations.

    57

    Two-Way Joist

    l2 = 18 + c/2

    = 18 + (18/12)/2

    = 18.75

    c = column dimension

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 03: Frame Analysis (E-W Exterior Frame)

    Step 03: Static Moment Calculation.

    58

    Two-Way Joist

    l2 = 18.75

  • 30

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 03: Frame Analysis (E-W Exterior Frame)

    Step 04: Longitudinal distribution of Total static moment (Mo).

    59

    Two-Way Joist

    0.26

    0.52 0.70 0.65

    0.35 0.65 0.70 0.26

    0.52

    Longitudinal

    distribution

    factors (D.F)L

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 03: Frame Analysis (E-W Exterior Frame)

    Step 04: Longitudinal distribution of Total static moment (Mo).

    60

    Two-Way Joist

    215

    429 578 536

    289 536 578 215

    429

    Units: ft-kip

    ML = Mo (D.F)L

  • 31

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 03: Frame Analysis (E-W Exterior Frame)

    Step 05: Lateral Distribution of Longitudinal moment (L.M).

    61

    Two-Way Joist

    0.60

    Lateral

    distribution

    factors (D.F)Lat

    1.00 0.75 0.75 0.75

    0.60 0.60

    1.00 0.75

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 03: Frame Analysis (E-W Exterior Frame)

    Step 05: Lateral Distribution of Longitudinal moment (L.M).

    62

    Two-Way Joist

    215 434 402 769 215 402

    MLat = ML (D.F)Lat

    ML,ext- = 215 kip-ft

    ML,ext+ = 429 kip-ft

    ML,int- = 578 kip-ft

    ML,- = 536 kip-ft

    ML,+ = 289 kip-ft

    172 172 0 0 144 144 116 134 134

    257 173 257

  • 32

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 03: Frame Analysis (E-W Exterior Frame)

    Step 05: Lateral Distribution of Longitudinal moment (L.M).

    63

    Two-Way Joist

    23.8 48.2 44.7 44.7 23.8 48.2

    ML,ext- = 215 kip-ft

    ML,ext+ = 429 kip-ft

    ML,int- = 578 kip-ft

    ML,- = 536 kip-ft

    ML,+ = 289 kip-ft

    17.64 17.64 0 0 14.76 14.76 11.89 13.74 13.74

    28.6 19.2 28.6

    MLat per foot = Mlat/strip width

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 03: Frame Analysis

    Analysis of N-S Interior and Exterior Frame will be same as E-W respective

    frames due to square panels.

    64

    N-S

    Interior

    Frame

    l2 = 36-0

    N-S

    Exterior

    Frame

    l2 = 18-9

    Two-Way Joist

  • 33

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 04: Design

    For E-W Interior Slab Strip:

    65

    Two-Way Joist

    l2 = 36 27.3

    22.8 46 42.7 42.7

    18.38 27.3

    22.8 46

    18.22 18.22

    18.22 18.22

    0 0

    0 0

    15.33

    15.33

    15.33

    15.33

    12.3

    12.3

    14.22

    14.22

    14.22

    14.22

    Selective values

    are used for design.

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 04: Design

    E-W Exterior Frame.

    66

    Two-Way Joist

    23.8 48.2 23.8 48.2

    17.64 17.64 0 0 14.76 14.76 11.89

    28.6 19.2 28.6

    Selective values

    are used for

    design

  • 34

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 04: Design

    Design of N-S Interior and Exterior Frame will be same as E-

    W respective frames due to square panels and also for the

    reason that davg is used in design.

    davg = 16.5 (0.75 inch (cover) + inch (Assumed bar

    diameter) = 15 inch

    This will be used for both directions positive as well as

    negative reinforcement.

    67

    Two-Way Joist

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 05: Detailing (E-W Frames)

    68

    #6 @ 12 #6 @ 6 #6 @ 6 #6 @ 12

    #6 @ 12 #6 @ 6 #6 @ 6 #6 @ 12

    #6 @ 18 #6 @ 18 #6 @ 18 #6 @ 18

    Two-Way Joist

    Negative Reinforcement in

    E-W direction

    For M = 46 ft-k =46 x12

    = 552 in-k

    d = 15

    fy = 60 ksi

    As = 0.7 in2

  • 35

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 05: Detailing (N-S Frames)

    69

    #6 @ 6

    #6 @ 12

    #6 @ 6

    #6 @ 18

    #6 @ 18

    #6 @ 18

    #6 @ 12

    #6 @ 6

    #6 @ 6

    Two-Way Joist

    Negative Reinforcement

    in N-S direction

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 05: Detailing (N-S Frames)

    Positive reinforcement

    For M = 27 ft-k =27x12 = 324in-k

    d = 15

    fy = 60 ksi

    As = 0.373 in2 This is per foot reinforcement. For 18 feet col strip, this will

    be equal to 0.373 x 18 = 6.714 in2

    There are 6 joists in 18 feet with. Therefore per rib reinforcement = 1.12

    Using # 7 bars, 2 bars per joist rib will be provided.

    70

    Two-Way Joist

  • 36

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 05: Detailing (E-W Interior Frame)

    71

    Column Strip (Interior Frame); section taken over support

    Column Strip (Exterior Frame); section taken over support

    #6 @ 12 c/c

    #6 @ 6 c/c

    2 #7 Bars

    18-0

    2 #7 Bars

    Two-Way Joist

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 05: Detailing (E-W Interior Frame)

    72

    Middle Strip (Interior Frame); Section taken over column line

    Middle Strip (Exterior Frame); Section taken over column line

    #6 @ 18 c/c

    #6 @ 18 c/c

    2 #7 Bars

    18-0

    2 #7 Bars

    Two-Way Joist

  • 37

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 05: Detailing (E-W Exterior Frame)

    73

    Column Strip (Interior Frame); section over support

    #6 @ 6 c/c

    2 #7 Bars

    9-0

    Column Strip (Exterior Frame); section over support

    #6 @ 12 c/c

    2 #7 Bars

    Two-Way Joist

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 05: Detailing (E-W Exterior Frame)

    74

    Middle Strip (Interior Frame) ; section over support

    #6 @ 18 c/c

    2 #7 Bars

    9-0

    Middle Strip (Exterior Frame); section over support

    #6 @ 18 c/c

    2 #7 Bars

    Two-Way Joist

  • 38

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Step No 04: Design

    Note: For the completion of design problem, the waffle slab

    should also be checked for beam shear and punching shear.

    75

    Two-Way Joist

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011 76

    Moment Coefficient

    Method

  • 39

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    Moment Coefficient Method (Introduction)

    The Moment Coefficient Method included for the first time in

    1963 ACI Code is applicable to two-way slabs supported on

    four sides of each slab panel by walls, steel beams relatively

    deep, stiff, edge beams (h = 3hf).

    Although, not included in 1977 and later versions of ACI code,

    its continued use is permissible under the ACI 318-08 code

    provision (13.5.1). Visit ACI 13.5.1.

    77

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    Moment Coefficient Method

    Moments:

    Ma, neg = Ca, negwula2

    Mb, neg = Cb, negwulb2

    Ma, pos, (dl + ll) = M a, pos, dl + M a, pos, ll = Ca, pos, dl wu, dl la2 + Ca, pos, ll wu, ll la

    2

    Mb, pos, (dl + ll) = Mb, pos, dl + Mb, pos, ll = Cb, pos, dl wu, dl lb2 + Cb, pos, ll wu, ll lb

    2

    Where Ca, Cb = Tabulated moment coefficients

    wu = Ultimate uniform load, psf

    la, lb = length of clear spans in short and long directions respectively.

    78

    Ma,neg lb

    la

    Ma,neg

    Ma,pos Mb,neg Mb,neg

    Mb,pos

  • 40

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    4 spans @ 25-0

    3 sp

    ans @

    20

    -0

    Two Way Slabs

    Moment Coefficient Method: Cases

    Depending on the support conditions, several cases are possible:

    79

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    Moment Coefficient Method: Cases

    Depending on the support conditions, several cases are possible:

    80

    4 spans @ 25-0

    3 sp

    ans @

    20

    -0

  • 41

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    Moment Coefficient Method: Cases

    Depending on the support conditions, several cases are possible:

    81

    4 spans @ 25-0

    3 sp

    ans @

    20

    -0

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    4 spans @ 25-0

    3 sp

    ans @

    20

    -0

    Two Way Slabs

    Moment Coefficient Method: Cases

    Depending on the support conditions, several cases are possible:

    82

  • 42

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    Moment Coefficient Tables:

    83

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    Moment Coefficient Tables:

    84

  • 43

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    Moment Coefficient Tables:

    85

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    Moment Coefficient Tables:

    86

  • 44

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    Moment Coefficient Tables:

    87

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    Moment Coefficient Tables:

    88

  • 45

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    Load Coefficient Table:

    89

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    90

    Maximum Spacing and Minimum Reinforcement

    Requirement:

    Maximum spacing (ACI 13.3.2):

    smax = 2 hf in each direction.

    Minimum Reinforcement (ACI 7.12.2.1):

    Asmin = 0.0018 b hf for grade 60.

    Asmin = 0.002 b hf for grade 40 and 50.

  • 46

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    Special Reinforcement at Exterior Corner of Slab

    The reinforcement at exterior ends of the slab shall be provided as per ACI

    13.3.6 in top and bottom layers as shown.

    The positive and negative reinforcement in any case, should be of a size and

    spacing equivalent to that required for the maximum positive moment (per foot

    of width) in the panel.

    91

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    Moment Coefficient Method

    Steps

    Find hmin = perimeter/ 180 = 2(la + lb)/180

    Calculate loads on slab (force / area)

    Calculate m = la/ lb

    Decide about case of slab,

    Use table to pick moment coefficients,

    Calculate moments and then design.

    Apply reinforcement requirements (smax = 2hf, ACI 13.3.2)

    92

  • 47

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    Moment Coefficient Method: Example 1

    A 100 60, 3-storey commercial building is to be designed.

    The grids of column plan are fixed by the architect.

    93

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    Moment Coefficient Method: Example 1

    Complete analysis of the slab is done by analyzing four panels

    94

    Panel I Panel I

    Panel I Panel I

    Panel II Panel II

    Panel III Panel III

    Panel III Panel III

    Panel IV Panel IV

    4 spans @ 25-0

    3 sp

    ans @

    20

    -0

  • 48

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    Moment Coefficient Method: Example 1

    A 100 60, 3-storey commercial building: Sizes and Loads.

    Sizes:

    Minimum slab thickness = perimeter/180 = 2 (20+25)/180 = 6

    However, for the purpose of comparison, take hf = 7

    Columns = 14 14 (assumed)

    Beams = 14 20 (assumed)

    Loads:

    S.D.L = Nil ; Self Weight = 0.15 x (7/12) = 0.0875 ksf

    L.L = 144 psf ; wu = 0.336 ksf

    95

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    4 spans @ 25-0

    3 sp

    ans @

    20

    -0

    Two Way Slabs

    Moment Coefficient Method: Example 1

    Panels are analyzed using Moment Coefficient Method

    96

    Case = 4

    m = la/lb = 0.8

    Mb,neg Mb,neg Mb,pos Ma,neg

    Ma,pos

    Ma,neg

  • 49

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    Moment Coefficient Method: Example 1

    Panels are analyzed using Moment Coefficient Method

    97

    Case = 4

    m = la/lb = 0.8

    Ca,neg = 0.071

    Cb,neg = 0.029

    Ca,posLL = 0.048

    Cb,posLL = 0.020

    Ca,posDL = 0.039

    Cb,posDL = 0.016

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    Moment Coefficient Method: Example 1

    Panels are analyzed using Moment Coefficient Method

    98

    Case = 4

    m = la/lb = 0.8

    Ca,neg = 0.071

    Cb,neg = 0.029

    Ca,posLL = 0.048

    Cb,posLL = 0.020

    Ca,posDL = 0.039

    Cb,posDL = 0.016

  • 50

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    Moment Coefficient Method: Example 1

    Panels are analyzed using Moment Coefficient Method

    99

    Case = 4

    m = la/lb = 0.8

    Ca,neg = 0.071

    Cb,neg = 0.029

    Ca,posLL = 0.048

    Cb,posLL = 0.020

    Ca,posDL = 0.039

    Cb,posDL = 0.016

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    Moment Coefficient Method: Example 1

    Panels are analyzed using Moment Coefficient Method

    100

    Case = 4

    m = la/lb = 0.8

    Ca,neg = 0.071

    Cb,neg = 0.029

    Ca,posLL = 0.048

    Cb,posLL = 0.020

    Ca,posDL = 0.039

    Cb,posDL = 0.016

  • 51

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    Moment Coefficient Method: Example 1

    Panels are analyzed using Moment Coefficient Method

    101

    Case = 4

    m = la/lb = 0.8

    Ca,neg = 0.071

    Cb,neg = 0.029

    Ca,posLL = 0.048

    Cb,posLL = 0.020

    Ca,posDL = 0.039

    Cb,posDL = 0.016

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    Moment Coefficient Method: Example 1

    Panels are analyzed using Moment Coefficient Method

    102

    Case = 4

    m = la/lb = 0.8

    Ca,neg = 0.071

    Cb,neg = 0.029

    Ca,posLL = 0.048

    Cb,posLL = 0.020

    Ca,posDL = 0.039

    Cb,posDL = 0.016

  • 52

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    4 spans @ 25-0

    3 sp

    ans @

    20

    -0

    Two Way Slabs

    Moment Coefficient Method: Example 1

    Panels are analyzed using Moment Coefficient Method

    103

    Panel I

    Case = 4

    m = la/lb = 0.8

    Ca,neg = 0.071

    Cb,neg = 0.029

    Ca,posLL = 0.048

    Cb,posLL = 0.020

    Ca,posDL = 0.039

    Cb,posDL = 0.016

    Ma,neg = 9.5 k-ft

    Ma,pos = 6.1 k-ft

    Mb,neg = 6.1 k-ft

    Mb,pos = 3.9 k-ft

    Mb,neg Mb,neg Mb,pos Ma,neg

    Ma,pos

    Ma,neg

    For slab supported on Spandrals, Mneg,ext = 1/3Mpos

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    4 spans @ 25-0

    3 sp

    ans @

    20

    -0

    Two Way Slabs

    Moment Coefficient Method: Example 1

    Panels are analyzed using Moment Coefficient Method

    104

    Panel II

    Case = 9

    m = la/lb = 0.8

    Ca,neg = 0.075

    Cb,neg = 0.017

    Ca,posLL = 0.042

    Cb,posLL = 0.017

    Ca,posDL = 0.029

    Cb,posDL = 0.010

    Ma,neg = 10.1 k-ft

    Ma,pos = 5.1 k-ft

    Mb,neg = 3.6 k-ft

    Mb,pos = 3.1 k-ft

    Mb,neg Mb,neg Mb,pos

    Ma,neg

    Ma,pos

    Ma,neg

  • 53

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    4 spans @ 25-0

    3 sp

    ans @

    20

    -0

    Two Way Slabs

    Moment Coefficient Method: Example 1

    Panels are analyzed using Moment Coefficient Method

    105

    Panel III

    Case = 8

    m = la/lb = 0.8

    Ca,neg = 0.055

    Cb,neg = 0.041

    Ca,posLL = 0.044

    Cb,posLL = 0.019

    Ca,posDL = 0.032

    Cb,posDL = 0.015

    Ma,neg = 7.4 k-ft

    Ma,pos = 5.4 k-ft

    Mb,neg = 8.6 k-ft

    Mb,pos = 3.7 k-ft

    Mb,neg Mb,neg Mb,pos

    Ma,neg

    Ma,pos

    Ma,neg

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    4 spans @ 25-0

    3 sp

    ans @

    20

    -0

    Two Way Slabs

    Moment Coefficient Method: Example 1

    Panels are analyzed using Moment Coefficient Method

    106

    Panel IV

    Case = 2

    m = la/lb = 0.8

    Ca,neg = 0.065

    Cb,neg = 0.027

    Ca,posLL = 0.041

    Cb,posLL = 0.017

    Ca,posDL = 0.026

    Cb,posDL = 0.011

    Ma,neg = 8.7 k-ft

    Ma,pos = 4.9 k-ft

    Mb,neg = 5.7 k-ft

    Mb,pos = 3.2 k-ft

    Mb,neg Mb,neg Mb,pos

    Ma,neg

    Ma,pos

    Ma,neg

  • 54

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    4 spans @ 25-0

    3 sp

    ans @

    20

    -0

    Two Way Slabs

    Moment Coefficient Method: Example 1

    Slab analysis summary

    107

    3.2

    4.9 5.7 5.7

    8.7

    8.7

    7.4

    7.4

    8.6 8.6 5.4

    3.7

    3.2

    5.1 3.6

    10.1

    10.1

    9.5

    9.5

    6.1 6.1

    3.9

    6.1

    3.6

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    Moment Coefficient Method: Example 1

    Slab Reinforcement Details

    108

    A

    B B B

    C

    C

    C

    C C B

    A

    A

    B A

    C

    C

    C

    B B

    A

    A= #4 @ 12

    B = #4 @ 6

    C = #4 @ 4

    4 spans @ 25-0

    3 sp

    ans @

    20

    -0

  • 55

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    Moment Coefficient Method: Example 1

    Load On Beams from coefficient tables

    109

    Table: Load on beam in panel I, using

    Coefficients

    (wu = 0.336 ksf)

    Bea

    m

    Length

    (ft)

    Width

    (bs) of

    slab

    panel

    support

    ed by

    beam

    Wa Wb

    Load

    due to

    slab,

    Wwubs

    (k/ft)

    B1 25 10 0.71 - 2.39

    B2 25 10 0.71 - 2.39

    B3 20 12.5 - 0.29 1.22

    B4 20 12.5 - 0.29 1.22

    Panel I

    4 spans @ 25-0

    3 sp

    ans @

    20

    -0

    B1

    B1

    B2

    B2

    B3 B3 B3 B4 B4

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    B1

    B1

    B2

    B2

    B3 B3 B3 B4 B4

    4 spans @ 25-0

    3 sp

    ans @

    20

    -0

    Panel I

    Two Way Slabs

    Moment Coefficient Method: Example 1

    Load On Beams from coefficient tables

    110

    Table: Load on beam in panel I, using

    Coefficients

    (wu = 0.336 ksf)

    Bea

    m

    Length

    (ft)

    Width

    (bs) of

    slab

    panel

    support

    ed by

    beam

    Wa Wb

    Load

    due to

    slab,

    Wwubs

    (k/ft)

    B1 25 10 0.71 - 2.39

    B2 25 10 0.71 - 2.39

    B3 20 12.5 - 0.29 1.22

    B4 20 12.5 - 0.29 1.22

  • 56

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    Moment Coefficient Method: Example 1

    Load On Beams from coefficient tables

    111

    Table: Load on beam in panel I, using

    Coefficients

    (wu = 0.336 ksf)

    Bea

    m

    Length

    (ft)

    Width

    (bs) of

    slab

    panel

    support

    ed by

    beam

    Wa Wb

    Load

    due to

    slab,

    Wwubs

    (k/ft)

    B1 25 10 0.83 - 2.78

    B3 20 12.5 - 0.17 0.714

    B4 20 12.5 - 0.17 0.714

    Panel II

    4 spans @ 25-0

    3 sp

    ans @

    20

    -0

    B1

    B1

    B2

    B2

    B3 B3 B3 B4 B4

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    B1

    B1

    B2

    B2

    B3 B3 B3 B4 B4

    Panel II

    4 spans @ 25-0

    3 sp

    ans @

    20

    -0

    Two Way Slabs

    Moment Coefficient Method: Example 1

    Load On Beams from coefficient tables

    112

    Table: Load on beam in panel I, using

    Coefficients

    (wu = 0.336 ksf)

    Bea

    m

    Length

    (ft)

    Width

    (bs) of

    slab

    panel

    support

    ed by

    beam

    Wa Wb

    Load

    due to

    slab,

    Wwubs

    (k/ft)

    B1 25 10 0.83 - 2.78

    B3 20 12.5 - 0.17 0.714

    B4 20 12.5 - 0.17 0.714

  • 57

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    Moment Coefficient Method: Example 1

    Load On Beams from coefficient tables

    113

    Table: Load on beam in panel I, using

    Coefficients

    (wu = 0.336 ksf)

    Bea

    m

    Length

    (ft)

    Width

    (bs) of

    slab

    panel

    support

    ed by

    beam

    Wa Wb

    Load

    due to

    slab,

    Wwubs

    (k/ft)

    B1 25 10 0.55 - 1.84

    B3 20 12.5 - 0.45 1.89

    Panel III

    4 spans @ 25-0

    3 sp

    ans @

    20

    -0

    B1

    B1

    B2

    B2

    B3 B3 B3 B4 B4

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    B1

    B1

    B2

    B2

    B3 B3 B3 B4 B4

    Panel III

    4 spans @ 25-0

    3 sp

    ans @

    20

    -0

    Two Way Slabs

    Moment Coefficient Method: Example 1

    Load On Beams from coefficient tables

    114

    Table: Load on beam in panel I, using

    Coefficients

    (wu = 0.336 ksf)

    Bea

    m

    Length

    (ft)

    Width

    (bs) of

    slab

    panel

    support

    ed by

    beam

    Wa Wb

    Load

    due to

    slab,

    Wwubs

    (k/ft)

    B1 25 10 0.55 - 1.84

    B3 20 12.5 - 0.45 1.89

  • 58

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    Moment Coefficient Method: Example 1

    Load On Beams from coefficient tables

    115

    Table: Load on beam in panel I, using

    Coefficients

    (wu = 0.336 ksf)

    Bea

    m

    Length

    (ft)

    Width

    (bs) of

    slab

    panel

    support

    ed by

    beam

    Wa Wb

    Load

    due to

    slab,

    Wwubs

    (k/ft)

    B1 25 10 0.71 - 2.39

    B3 20 12.5 - 0.29 1.22

    Panel IV

    4 spans @ 25-0

    3 sp

    ans @

    20

    -0

    B1

    B1

    B2

    B2

    B3 B3 B3 B4 B4

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    B1

    B1

    B2

    B2

    B3 B3 B3 B4 B4

    Panel IV

    4 spans @ 25-0

    3 sp

    ans @

    20

    -0

    Two Way Slabs

    Moment Coefficient Method: Example 1

    Load On Beams from coefficient tables

    116

    Table: Load on beam in panel I, using

    Coefficients

    (wu = 0.336 ksf)

    Bea

    m

    Length

    (ft)

    Width

    (bs) of

    slab

    panel

    support

    ed by

    beam

    Wa Wb

    Load

    due to

    slab,

    Wwubs

    (k/ft)

    B1 25 10 0.71 - 2.39

    B3 20 12.5 - 0.29 1.22

  • 59

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    Moment Coefficient Method: Example 1

    Load On Beams

    117

    2.39 k/ft

    1.22 k/ft

    2.39 k/ft

    1.22 k/ft

    2.77 k/ft

    2.77 k/ft

    0.71 k/ft 0.71 k/ft

    1.84 k/ft

    1.89 k/ft

    1.84 k/ft

    1.89 k/ft

    2.39 k/ft

    1.22 k/ft

    2.39 k/ft

    1.22 k/ft

    4 spans @ 25-0

    3 sp

    ans @

    20

    -0

    B1

    B1

    B2

    B2

    B3 B3 B3 B4 B4

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    Moment Coefficient Method: Example 1

    Load On Beams

    118

    1.45 k/ft

    2.62 k/ft

    5.39 k/ft

    0.94 k/ft

    3.34 k/ft

    2.07 k/ft

    2.16 k/ft

    4.46 k/ft

    4 spans @ 25-0

    3 sp

    ans @

    20

    -0

    B1

    B1

    B2

    B2

    B3 B3 B3 B4 B4

    Loads

    including self

    weight of

    beams 0.23

    kip/ft

  • 60

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    Moment Coefficient Method: Example 2

    Similarly, slab analysis results of 25 20 structure.

    119

    Panel I Panel I

    Panel I Panel I

    Panel II Panel II

    Panel III Panel III

    Panel III Panel III

    Panel IV Panel IV

    4 spans @ 25-0

    3 sp

    ans @

    20

    -0

    Slab thickness = 6

    SDL = 40 psf

    LL = 60 psf

    fc =3 ksi

    fy = 40 ksi

    wu = 0.234 ksf

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    4 spans @ 25-0

    3 sp

    ans @

    20

    -0

    Two Way Slabs

    Moment Coefficient Method: Example 2

    Slab analysis summary

    120

    2.0

    3.0 3.9 3.9

    6.1

    6.1

    5.1

    5.1

    6.0 6.0 3.5

    2.4

    1.9

    3.2 2.5

    7

    7

    6.6

    6.6

    4.2 4.0

    2.6

    4.2

    2.5

  • 61

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    Two Way Slabs

    Moment Coefficient Method: Example 3

    Similarly, slab analysis results of 20 15 structure.

    121

    Panel I Panel I

    Panel I Panel I

    Panel II Panel II

    Panel III Panel III

    Panel III Panel III

    Panel IV Panel IV

    4 spans @ 20-0

    3 sp

    ans @

    15

    -0

    Slab thickness = 6

    SDL = 40 psf

    LL = 60 psf

    fc =3 ksi

    fy = 40 ksi

    wu = 0.234 ksf

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    4 spans @ 25-0

    3 sp

    ans @

    20

    -0

    Two Way Slabs

    Moment Coefficient Method: Example 3

    Slab analysis summary

    122

    1.0

    1.8 2.1 2.1

    3.6

    3.6

    3.2

    3.2

    3.4 3.4 2.2

    1.3

    0.9

    2.0 1.3

    4.1

    4.1

    4

    4

    2.2 2.5

    1.3

    2.2

    1.3

  • 62

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    References

    CRSI Design Handbook

    ACI 318

    Design of Concrete Structures 13th Ed. by Nilson, Darwin and Dolan.

    123

    Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan

    Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures Fall 2011

    The End

    124