    Automation in EnvironmentalEngineering

    dr in ! . Patryk Wjtowicz

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    2/45

    Automation - definition

    Automation is the use of control systems,equipment and informationtechnologies to reduce the need for humanparticipation in controlling processes

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    3/45

    Automation - definition

    Automation - 1. The implementation ofprocesses by automatic means. 2. Thetheory, art, or technique of making aprocess more automatic. 3. Theinvestigation, design, development, andapplication of methods for renderingprocesses automatic, self-moving, or self-

    controlling. 4. The conversion of aprocedure, a process, or equipment toautomatic operation

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    4/45

    Some more definitions

    Automatic control - The type of control inwhich there is no direct human action onthe controlling device

    Automate - To convert a procedure, aprocess, or equipment into an automaticoperation

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    5/45

    and more definitions...

    Automatic - 1. Self-acting or operating byits own mechanism when actuated bysome impersonal influence, as, forexample, a change in current strength,pressure, temperature, or mechanicalconfiguration 2. A machine that operatesautomatically. 3. Functioning without

    intervention by a human operator underspecified conditions, as of a process ordevice

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    6/45

    and more definitions... contd

    Regulation - The control of flow or of some other processvariable

    Control - 1. One or more of the components in any mechanismthat is responsible for interpreting and carrying out manuallyinitiated directions. 2. In some applications, a mathematicalcheck. 3. Instructions that determine conditional jumps oftenare referred to as "control instructions," and the timesequence of the execution of these instructions is called the"flow of control." 4. Any manual or automatic device forregulating a machine to keep it at normal operation. Ifautomatic, the device is motivated by variations intemperature, pressure, water level, time, light, or otherinfluences. 5. Maintaining a desired set point of steamtemperature during operation

    (The Automation, Systems, and Instrumentation Dictionary. 4 th ed. ISA 2005

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    7/45

    Control systems

    Control system - a device or set of devicesto manage, command, direct or regulatethe behavior of other devices or systems

    There are two common classes of controlsystems, with many variations andcombinations: logic (sequential controls) ,

    and feedback (linear controls) and fuzzylogic

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    8/45

    Logic control

    Logic controllers may respond toswitches, light sensors, pressure switchesetc. and can cause the equipment to startand stop various operations.

    In logic control systems weuse programmable logic controllers (PLC)

    or microcontrollers

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    9/45

    Onoff feedback control

    Onoff controller (a bangbang controller ),also known as a hysteresis controller, is afeedback controller that switches onlybetween two states (e.g. on and off)

    Typical examples are thermostat and aircompressor

    In thermostat we have negative-feedback control: when the temperature goes

    below a set point, the heater is switched on In air compressor when the pressure dropsbelow the certain threshold, the pump ispowered on

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    10/45

    Positive and negative feedback

    Negative feedback - Returning part of anoutput signal and using it to reduce thevalue of an input signal

    Positive feedback - a closed loop in whichany change is reinforced until a limit iseventually reached. (e.g. signal

    amplification)

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    11/45

    Linear control

    Linear control systemsuse linear negative feedback to produce acontrol signal mathematically based on other

    variables, in order to maintain the controlledprocess within an acceptable or desiredoperating range

    The output from a linear control system into

    the controlled process may be in the form ofa directly variable signal, such as a valveopen may vary between 0 and 100% or turn iton or off (pulse-width modulation)

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    12/45

    Fuzzy logic

    Fuzzy logic combines easy design of logiccontrollers while still controllingcontinuously-varying systems

    Fuzzy logic is a reasoning approach andcomputing method that is used to modellinguistic expressions (such as "somewhatmore than") that have nonbinary truth values

    Basically, a measurement in a fuzzy logic

    system can be partly true, that is if yes is 1and no is 0, a fuzzy measurement can bebetween 0 and 1.

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    13/45

    Piping and instrumentation diagrams

    Piping and instrumentation (PI) diagramsare of fundamental importance in processautomation

    P&I diagrams depict, from a process pointof view, measurements and controlschemes in relation to items of plant and

    their interconnecting pipework. They arerepresented by means of symbols and tagnumbers .

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    14/45

    Symbols

    Symbols are used to represent individualelements such as sensors and valves, orcombinations of elements such asmeasurement channels or control loops.

    Symbols are linked together by signal lines .

    Tag numbers are written inside circles ,referred to as bubbles or balloons .

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    15/45

    Letter codes and reference numbers

    Letter codes indicate the function of theelements and are generic.

    Reference numbers are specific toparticular elements and are used foridentification purposes.

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    16/45

    Simple P&I diagram of flow control loop

    Note that the elements of the loop are shown in their correct positions in afunctional sense, i.e. the control valve is downstream of the pump and theflow measurement is between the valve and the pump. However, the

    symbols do not necessarily indicate their relative positions in a physicalsense, e.g. the flow measurement and valve could be a long way from thepump.

    Arrows are normally put on the signals to indicate the direction of flow ofinformation. They may be omitted in obvious and simple diagrams

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    17/45

    Graphical representation of signal types

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    18/45

    Detailed P&I diagram of flow control loop

    sight-glass

    orifice controlvalve

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    19/45

    Detailed P&I diagram of flow control loop

    The pressure drop across the orifice plate is measured using a! p cell FT 47 which transmits the flowrate as an electricalsignal to the totaliser FQR 47, the low level switch FSL 47 andthe controller FIC 47.

    If the flow drops below some pre-set lower limit the flowswitch FSL 47 will activate a low level alarm FAL 47. FV 47 is a pneumatically actuated diaphragm type of

    regulatory valve. It has a positioner attached, as indicated bythe box on the stem of the valve symbol

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    20/45

    Bubbles

    Information about the location of an element isindicated by the presence or otherwise of a linethrough its bubble.

    No line means that the element is field mounted,i.e. it is installed on or adjacent to a pipe, vesselor some other item of plant.

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    21/45

    Bubbles

    A single line through the bubble, as with FAL47 and FIC 47, means that the element islocated in a central control room.

    A double line, as with FQR 47, means that it

    is panel mounted elsewhere, say on a fieldtermination cabinet.

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    22/45

    Tags

    There are several national standards whichrelate to the representation ofinstrumentation and control schemes. Themost important English language ones are BS1646 and ISA S5.1 (ISA - The Instrumentation,Systems, and Automation Society)

    Recommended and commonly used inpractice is notation according to ISA standard

    Note that the basic symbols and letter codestructure are essentially the same for allstandards

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    23/45

    Letter codes

    Letter codes are configured according tofunction.

    The first letter corresponds to the measured

    variable and, if necessary, may be qualifiedby a modifier. Succeeding letters describe an elements

    readout or control functions; these maythemselves have modifiers.

    The first letter of all elements within a loopis that of the measured variable (i.e. F forFlow).

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    24/45

    ISA letter codes for tag numbers

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    25/45

    If a loop contains two or more elements with the samefunction they may be distinguished by means ofsuffixes (e.g. A , B ...)

    Sometimes the letter code is insufficient to give an

    adequate description of the function of an element.Additional information may be provided, either in abox attached to its bubble or as adjacent text.

    For example, FT 47 has a square root function tocompensate for the square relationship inherent in theflow measurement by the orifice plate. The total flowcomputed by FQR 47 is obtained by means of anintegral function

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    26/45

    Additional functions for use with tag

    numbers

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    27/45

    Function designation

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    28/45

    Function designation

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    29/45

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    30/45

    Serial vs parallel numbering

    In serial numbering each channel, loop orscheme has assigned a unique number

    In parallel numbering convention, blocksof numbers are allocated according toinstrument type or function, depending onits letter code. This results in similar

    elements in different loops havingcontiguous numbers

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    31/45

    Distributed Control Systems (DCS)

    A solid line across the symbol means that the function has ashared, screen based display: the absence of a line means thatthe function is inaccessible to the operator.

    Visible (on screendisplay)

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    32/45

    Distributed Control Systems (DCS)

    A solid line across the symbol means thatthe function has a shared, screen baseddisplay: the absence of a line means thatthe function is inaccessible to theoperator.

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    33/45

    Block diagrams

    Block diagram depicts the structure of asystem and shows the functionalrelationship between its various elements

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    34/45

    Symbols and notation used in block

    diagrams Block relate to the elements and

    represent functions (combinations ofconversion or scaling, factors anddynamics)

    Lines between the blocks represent signals Arrows indicates direction of flow of

    information Addition or subtraction of signals is

    represented by circles with signs (no sign =+)

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    35/45

    Block diagrams

    Typical feedback control system (levelcontrol system)

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    36/45

    The general layout of the block diagram

    By convention the controlled variablecomes out on the right hand side andexternal inputs are normally shownentering from the left

    Signals are represented by single arrows(e.g. they can be physically two or more

    wires of electrical wiring) The size of the blocks in diagrams doesntrelate to the physical size of the elements

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    37/45

    Block diagram of level control system

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    38/45

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    39/45

    Block diagram of level control system

    The controlled variable ( level h ) is measured and fedback to the controller where it is compared with thereference signal h r (set point ), to produce the errorsignal e (deviation from set point)

    The controller produces an output u (as a function of

    error) which manipulate valve opening and the outletflow f 0 The resultant level in the tank (h) depends upon the

    combined effect of its outlet flow and anydisturbances in its inlet flow f 1.

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    40/45

    Comprehensive block diagram of level

    control system

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    41/45

    Sub-systems

    The control , manipulation and plant sub-systems are often referred to as thefeedforward path , and the measurement sub-system is referred to as the feedbackpath

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    42/45

    Process and load - definition

    Process is defined to be the way in which themanipulated variable (MV) affects the controlledvariable (CV)

    Load is defined as the relationship between adisturbance (DV) and the controlled variable(CV).

    There may be various sources of disturbance theremay be several different loads

    According to the principle of superposition, the

    net change in controlled variable is the sum of theindividual effects of the process on themanipulated variable and the loads on thedisturbance variables.

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    43/45

    Modes of operation

    Most controllers have an auto and manual modes

    In automatic the controller output variesaccording to how the PID handles the error

    In manual mode the output is not relatedto the error and can be adjusted by hand

    to any desired value

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    44/45

    PID

    PID controller - ProportionalIntegralDerivative controller is a generic controlloop feedback mechanism (controller)

    PID controller calculates an " error " (E -deviation) value as the difference betweena measured process variable and adesired setpoint (SP)

    The controller attempts to minimize theerror by adjusting the process controlinputs

  • 8/10/2019 Lecture 1: Automation in Environmental Engineering Lecture 1

    45/45

    Open vs closed control loops

    The operation of a control loop may bedescribed as being either closed or open

    Closed loop - all the elements of a loopare functioning interconnected and thecontroller is in auto such that automaticcontrol occurs

    When a controller is switched into manual the loop is opened