Lancement Gamme Zelio - IBT

18
Eco-efficiency

Transcript of Lancement Gamme Zelio - IBT

Page 1: Lancement Gamme Zelio - IBT

Eco-efficiency

Page 2: Lancement Gamme Zelio - IBT

Schneider Electric 2 - Industrial – Eurotherm – Date

Why Eco-efficiency

Schneider Electric – Eurotherm - mai 2014

●As a premium brand, Eurotherm is keen on promoting value

added solutions for industrial customers.

●Today the key challenge for our customers is the cost of energy,

Oil, Gas and electricity. For instance the price of the Brent was

multiplied by 3 (from 25€ to more than 80€) during the past

twelve years and the trend recently is from mid 20’s and is now

late 40’s and rising

Page 3: Lancement Gamme Zelio - IBT

Schneider Electric 3 - Industrial – Eurotherm – Date

Why Eco-efficiency?

Schneider Electric – Eurotherm - mai 2014

●For instance a furnace will cost more in energy consumption

than its capital cost.

● Cost of a Glass Boosting 3MWatt = 300k€.

● Average consumption 2MWatt / 24h / 365days / 1year :

o Contract = 246.000€

o Power Consumption = 2.190.000€

o Cost of 1kWh = 10ct€

● If we save 10% on the Energy bill, the payback of the boosting

system will be less than 18 months.

●10% of Saving means 328.500€ of saving after 18 months

●The furnace will last more than 12 years :

Page 4: Lancement Gamme Zelio - IBT

What is Eco-efficiency ?

Page 5: Lancement Gamme Zelio - IBT

Schneider Electric 5 - Industrial – Eurotherm – Date

Our strategy for eco-efficiency

Schneider Electric – Eurotherm - mai 2014

●During the past years, the Power Applications Department has

developed new power management solutions on Boosting, Furnaces

and Bushing applications.

●The goal of these developments was to reduce the cost of ownership

through efficiency improvements and the capital cost through the

improvement of the power line design.

●Our strategy is based on

Power Factor and the THDI

(Harmonics) improvements

through the promotion of the

burst firing mode or the Load

Tap Changing instead of the

Phase Angle mode.

L T C : 1 e n r o u l e m e n t s

0

0 , 2

0 , 4

0 , 6

0 , 8

1

1 , 2

0 0 , 1 0 , 2 0 , 3 0 , 4 0 , 5 0 , 6 0 , 7 0 , 8 0 , 9 1

P u i s s a n c e

Ha

rm

on

iq

ue

s

H 3

H 5

H 7

H 9

H 1 1

H 1 3

H 1 5

H 1 7

H 1 9

Page 6: Lancement Gamme Zelio - IBT

Schneider Electric 6 - Industrial – Eurotherm – Date

Our strategy for eco-efficiency

Schneider Electric – Eurotherm - mai 2014

●The concept was validated on many applications where the heaters

are driven by a Thyristor in phase angle mode through a transformer.

●Bushing : The Thyristor drives a primary side of a transformer

and the secondary side is connected to the Bushing plate.

●Glass Boosting : Through a transformer, the Thyristor drives the

electrodes diving into the molten glass.

●Heat treatment and Vacuum furnaces : The Thyristor

controls the primary side of the transformer and the

secondary side is connected to the heating elements.

Page 7: Lancement Gamme Zelio - IBT

Schneider Electric 7 - Industrial – Eurotherm – Date

EPower : A revolution in the power management

• FLEXIBILITY : A unique product that

fits all the applications

• PEACE OF MIND: Reliability, an

efficient control of the process

• EFFICIENCY : Energy cost reduction

and optimisation of the owner cost

thanks to new functionalities :

• Burst Firing

• PLM (Predictive Load

Management)

Page 8: Lancement Gamme Zelio - IBT

Burst Firing and Eco-efficiency

Page 9: Lancement Gamme Zelio - IBT

Schneider Electric 9 - Industrial – Eurotherm – Date

Phase Angle mode

•In phase angle mode we cut the sinus voltage delivered by the grid.

•The energy delivered to the load depends on the delay : ∏ - θ.

•The Phase Angle mode impacts the Power factor.

•The Phase Angle mode generates harmonics

● The Phase Angle has an impact on the power factor

Page 10: Lancement Gamme Zelio - IBT

Schneider Electric 10 - Industrial – Eurotherm – Date

Burst Firing mode

•In Burst we consume the full sinus delivered by the grid.

•The energy delivered to the load depends on : Ton / (Ton + Toff)

•The burst mode doesn’t impact the Power factor

•The burst mode doesn't generate harmonics

• The Burst Firing mode has a no impact on the power factor

Page 11: Lancement Gamme Zelio - IBT

Schneider Electric 11 - Industrial – Eurotherm – Date

Power factor and Tan(fi)

•The phase angle firing mode has a direct impact on the power factor

and the tan(fi).

•The energy providers apply penalties when

FP < 0.93 or Tan(fi) > 0,4

•A process running in Phase angle mode needs to use capacitors

in order to improve the power factor and the Tan(fi).

● The Burst Firing mode has a no impact on the power factor

Current

Power

supply Power

supply

Load voltage (resistive) Load voltage (inductive)

Φ

Φ

Current

Φ

Page 12: Lancement Gamme Zelio - IBT

Schneider Electric 12 - Industrial – Eurotherm – Date

Impact on the efficiency

A Phase angle firing mode has an impact on the efficiency:

● Loss in transformer efficiency (Joules and Hysteresys losses)

● Integration of the capacitors losses (Power factor improvement).

● Heating of the Wires

● Reduction of the life-time of the installation

Current

Power

supply Power

supply

Load voltage (resistive) Load voltage (inductive)

Φ

Φ

Current

Φ

Page 13: Lancement Gamme Zelio - IBT

PLM and

Energy efficiency

Page 14: Lancement Gamme Zelio - IBT

Schneider Electric 14 - Industrial – Eurotherm – Date

PLM – Predicitive Load Management

● ENERGY EFFICIENCY

● Load sequencing

Energy where you need it

● Load sharing (power smoothing)

Energy when you need it

● Load shedding

Energy where and when you need it

● Energy counter

● Up to 64 zones

● AUTOMATIC CHOICE OF THE MASTER AND REDUNDANCY

• Reliability insured

Predictive Load

Management Module

Page 15: Lancement Gamme Zelio - IBT

Schneider Electric 15 - Industrial – Eurotherm – Date

PLM – Typical power demand

Energy where you need it but not when you need it • Still power demand peaks • The average power consumption is below the maximum power • The energy bill depends on the time, the season and your power contract

You are paying more

You are paying less

Page 16: Lancement Gamme Zelio - IBT

Schneider Electric 16 - Industrial – Eurotherm – Date

PLM : a revolutionary power management

Energy where you need it and when you need it

• The suppression of the power peaks demands enables to reduce the fixed part of your energy bill

• the dynamic modification of the power limitation enables to reduce the variable part of your energy bill

You are paying less

You are paying nothing more

Page 17: Lancement Gamme Zelio - IBT

Schneider Electric 17 - Industrial – Eurotherm – Date

PLM and Eco-efficiency

The firing synchronization of the different channels generates a smoothing of the

power consumption. This feature impacts favourably the global efficiency of the

process.

How ? : by reducing the heating losses in the electrical equipments , like cables,

TGBT, transformers…etc.

Load n°2 Load

n°1

SCR n°2 SCR n°1

U1

∆U

Uload

Page 18: Lancement Gamme Zelio - IBT

Schneider Electric 18 - Industrial – Eurotherm – Date

PLM and Eco-efficiency

Effectively, the heating losses in the resistive

components (cables, transformers…etc.) are

proportional to the square of the current :

•Pj1 = R x I2 x T

•Pj2 = R x (2I)2 x T/2 = 2 (R x I2 x T)

• => Pj2 = 2 x Pj1

Current

Load 1 Load 2

Imax/2

With PLM

Current

Load 1

Imax/2

Without PLM

Load 2

Imax

Why? : because it is better to consume at equivalent power, a current equal to ‘I’ during a ‘T’ period instead of a current equal to ‘2xI’ during a ‘T/2’ period .