Korakot PHOTJANASUNTORN 1/95 Korakot PHOTJANASUNTORN 2/95 Motortronics MVC Plus Product Training...
-
Upload
francine-hudson -
Category
Documents
-
view
224 -
download
3
Transcript of Korakot PHOTJANASUNTORN 1/95 Korakot PHOTJANASUNTORN 2/95 Motortronics MVC Plus Product Training...
Korakot PHOTJANASUNTORN 1/951/95
Korakot PHOTJANASUNTORN 2/952/95
Motortronics MVC Plus Product TrainingStartup, Operation & Service Session
INTRODUCTION & OBJECTIVES OF SESSIONA
MVC PLUS DESCRIPTIONB
MVC PLUS FUNCTIONS - PROGRAMMINGC
COMMISSIONINGD
TROUBLESHOOTING & MAINTENANCEE
PROGRAMMING EXERCISE F
CONCLUSION G
Korakot PHOTJANASUNTORN 3/953/95
Objectives List - A
INTRODUCTION & OBJECTIVES OF SESSIONA
MVC PLUS DESCRIPTIONB
COMMISSIONINGD
TROUBLESHOOTING & MAINTENANCEE
PROGRAMMING EXERCISE F
CONCLUSION G
Motortronics MVC Plus Product TrainingStartup, Operation & Service Session
MVC PLUS FUNCTIONS - PROGRAMMINGC
Korakot PHOTJANASUNTORN 4/954/95
INTRODUCTION
Who Am I, & Who Are You?
What Do I Do ?
What Services Do You Typically Provide For Your Company (Sales, Field Service, Maintenance)?
Have You Already Worked With A Motortronics MVC Plus Soft Starter?
What Do You Expect To Gain From This Session?
Korakot PHOTJANASUNTORN 5/955/95
OBJECTIVES FOR THIS COURSE WORK
After Completion Of This Training Session,
Attendees Should Be Able To:
Describe The Functions And Typical Field Applications Of An MVC Plus Medium Voltage Soft Starter
Identify Key Components Of The Soft Starter
Define Input Connections & Default Settings
Successfully Commission An MVC Plus Soft Starter
Troubleshoot An MVC Plus Soft Starter
Find Needed Information In The Support Documentation
Korakot PHOTJANASUNTORN 6/956/95
Objectives List - B
INTRODUCTION & OBJECTIVES OF THIS SESSIONA
MVC PLUS DESCRIPTIONB
MVC PLUS FUNCTIONS - PROGRAMMINGC
COMMISSIONINGD
TROUBLESHOOTING & MAINTENANCEE
PROGRAMMING EXERCISE F
CONCLUSION G
Motortronics MVC Plus Product TrainingStartup, Operation & Service Session
Korakot PHOTJANASUNTORN 7/957/95
Abbreviations Used In This Presentation
CPU Central Processing Unit
DCU Digital Control Unit
FLA Full Load Amperes
FLC Full Load Current
GTO Gate Turn Off
HMI Human Machine Interface
HP Horse Power
IGBT Insulated Gate Bipolar Transistor
LRA Locked Ramp Amperes
MOV Metal Oxide Varistor
MVSS Medium Voltage Soft Starter
MVSS Medium Voltage Soft Starter
OL Over Load
RTD Resistance-Temperature Device
RVAT Reduced Voltage
Autotransformer
SCR Silicon Controlled Rectifier (Thyristor)
SF Service Factor
RVSS Reduced Voltage Soft Starter
TCB Terminal & Control Board
Korakot PHOTJANASUNTORN 8/958/95
Soft Starter - Basic Features
Isolation Switch (Disconnector)Isolation Switch (Disconnector)
Provides Isolation Of Soft Starter From Power Supply
Vacuum Isolation ContactorVacuum Isolation Contactor
Provides Start Sequence To SCR Stack Assembly
SCR Stack With ISCR Stack With I22t Overloadt Overload
Provides Voltage Ramp And Advanced Protection Features
Vacuum Bypass ContactorVacuum Bypass Contactor
Bypasses SCRS When Motor Reaches Full Speed
Isolated Low Voltage ControlIsolated Low Voltage Control
CPT & PTCPT & PT
TransformersTransformers
Supply Control Power And SCR Firing Detection
Main FusesMain Fuses
Medium Voltage
R-Style Motor Protection Fuses
Korakot PHOTJANASUNTORN 9/959/95
The MVC PLUS - Defined The MVC Plus Incorporates A Complete Reduced Voltage Soft Starter System
Within a NEMA 12R Drip-Proof Enclosure.
Reduced Voltage Solid-State Devices (SCRs) Vary The Amount Of The AC Sine Wave Sent To The Motor.
The MVC Plus Accelerates And Decelerates A Motor By Limiting The Current Through Voltage Phase Angle Control.
Once The Motor Is At Full Voltage, The Soft Starting System Is Bypassed With A Contactor.
Medium Voltage Soft Starters Are NOT Variable Speed Drives And Do Not Have The Functionality Of A Drive. They Are NOT Cheap Drives!
Main ContactorMain Contactor
LoadLoadProtectionProtection Soft StarterSoft Starter MotorMotor
Bypass ContactorBypass ContactorPo
wer
Net
wo
rk
Korakot PHOTJANASUNTORN 10/9510/95
Protect The Motor And Load
Reduce Mechanical Stress
Limit Starting Current
Reduce Stress On The Electrical Grid
Reduce Electrical System Disturbance
Provide Soft Stopping
Meter & Record
Communicate
Goals Beyond Simple On & Off Starting
Korakot PHOTJANASUNTORN 11/9511/95
MVC PLUS Metering Features
10 Current Based Metering Functions
6 Status Screens
Recorder for 60 Events with Time / Date Stamp
29 RTD Option Screens
Voltage Monitoring Functions– Including Line Voltage, Frequency, PF, kW, kW Demand,
kVAR, kVAR Demand, kWH, kVA, kVA Demand.
Statistical Data Capture With Demand Reset
Korakot PHOTJANASUNTORN 12/9512/95
Human / Machine Interface
Full Digital Control
– LCD Operator Interface
– Non-Volatile Memory
Digital Sequencer
– Ensures Proper Contactor Sequence
Fiber-Optic Isolation (Operator Protection)
Metering Functions
RS-422 Comunication Buss Between COM Board And CPU Board
Korakot PHOTJANASUNTORN 13/9513/95
Pump
Blower
Compressor
Chiller
Fans
Chipper
Ball Mill
Rod Mill
Conveyor
Power Conversion
HVAC
Shredder
MVC PLUS Medium Voltage Soft Starter Applications
Other Applications
Korakot PHOTJANASUNTORN 14/9514/95
Diodes have no gate input to control them. They simply allow current to flow in one direction and block current flowing from the opposite direction. The net output with an AC input is a ½ sine wave.
Several types of electrical devices can be used to manipulate power These devices are based on semi-conductor principles When used in industry, they are normally referred to as “Power
Electronics”
Input
Output
Gate
Diode Output
SCR Output
GTO Output
Description Of Solid State Devices
SCRs (Silicon Controlled Rectifier) have a gate input used to turn them on but then act like a diode. They cannot turn off until the AC current reverses direction in the next ½ alternation of the sine wave. Like a diode, they only work in one direction. Motor soft starters use SCRs almost exclusively.
GTO (Gate Turn Off) SCRs, IGBTs (Insulated Gate Bipolar Transistors) and similar devices can be turned on and off to create output waveforms independent of the zero crossing point of the half alternation of the sine wave. These devices work similar to the control valves of a fluid pumping system (On/Off). Like diodes and SCRs, they also only work in one direction.
Korakot PHOTJANASUNTORN 15/9515/95
To create an electrical device that can function on both halves of the sine wave, two devices are needed, one for each direction. Each gate drive needs to be electrically isolated since they are at completely different potentials in relation to the cathodes of the SCRs.
input
Output
gate
gate
c
R
Output
Input
SCR Switching Dampened By DV/DT (RC) Network
Solid State Devices – SCR Function
input Output
Waveform Direction
We can turn an SCR on at some point before the current zero crossing point of the sine wave. When the current of the ½ alternation of the sine wave crosses the zero point, the SCR will turn off. In order for the SCR to conduct for the next ½ alternation, the SCR must have a gate signal applied again before the next zero crossing point.
The SCR output is typically coupled to a DV/DT (RC) network to help reduce voltage switching transients. DV/DT networks are important because they help eliminate false triggering of SCRs.
Korakot PHOTJANASUNTORN 16/9516/95
SCR Control Assembly
Looking at a whole system as a unit, each phase of the medium voltage power supply connects to its own SCR ‘Stack Assembly’. The Digital Control Unit (DCU) controls the gate drive outputs in order to turn the SCRs on based on detecting the point where the current sine wave crosses the zero horizon.
This is a very basic block diagram an SCR control system, but is a good representation of its fundamental operation.
Phase C [L3] Input
Phase C [T3] Output
Gate Drive
DV/DT
Current / Temp / Voltage Feedback
Computerized Controller
Phase B [L2] Input
Phase B [T2] Output
Phase A [L1] Input
Phase A [T1] Output
DV/DTDV/DT
Korakot PHOTJANASUNTORN 17/9517/95
Rugged Gate Firing Circuit
Auto-Synchronizing To Line
Independent Phase Tracking
Best Sensing Circuit For Generator Power
Measure
Fire
Measure
Fire
Measure
Fire
Measure
Fire
Measure
Fire
Measure
Fire
Korakot PHOTJANASUNTORN 18/9518/95
Rugged Gate Firing Circuit
Competition Uses A Cheaper System
Measure Once (Bet You Can Guess The Rest!)
Susceptible To Frequency Drift, Noise
“Phase Locked Loop” Firing: 6 Pulses From One Signal
Measure Once
Fire Fire Fire
Korakot PHOTJANASUNTORN 19/9519/95
Anode
Cathode
Gate
Hockey Puck Style SCR
Informational Purposes ONLY SCRs Will Not Be Examined At This Level In The Field
Korakot PHOTJANASUNTORN 20/9520/95
Typical MVC PLUS SCR Stack Assembly
This SCR stack assembly is the lowest level that may be replaced at customer site.
Field service representatives will not be required to replace SCRs within this assembly in the field due to SCR matching requirements, specialty tooling and the specific compressive forces needed to properly clamp the SCRs into an assembly.
SCR
Korakot PHOTJANASUNTORN 21/9521/95
DV/DT Boards The DV/DT Boards are used to reduce voltage transients across the stack assemblies
MOV (Metal Oxide Varistor) BoardsThe primary function of the MOV Boards are to protect the Gate-to-Cathode interface within each individual SCR.
Temp/CT Boards Provides SCR temperature and 3-phase current data to the DCU
Gate Drive Boards Sends firing control signals to the SCRs
Soft Starter Medium Voltage Compartment
DV/DT Boards
MOV Boards
Temp/CT Board
Gate Drive Boards
Korakot PHOTJANASUNTORN 22/9522/95
Sensing Systems
= MV
MTRMTR
OpticalIsolation
= Fiber Optic
= 28V= 120V
Gate Drive
MVC PLUS Electrical Isolation Diagram
LVControls
Magnetic Isolation
Korakot PHOTJANASUNTORN 23/9523/95
Fiber Optics - Description
Internal Reflection
When a ray of light (at the correct wavelength) is introduced into the fiber-optic cable, it bounces down its length, striking the core-to-cladding surface at an angle that will reflect it back into the core. If the angle of reflection is correct, the reflected light continues to be reflected down the length of the fiber with minimal loss.
Introducing the Light Source
In a fiber optic cable, as light is introduced into the end of the fiber at an angle that is directly in line with its axis, the light is guided through the core to the opposite end. Due to its design, the fiber acts as an optical waveguide, bouncing the 660 nanometer (optical red) light at equal distances off of its walls.
Korakot PHOTJANASUNTORN 24/9524/95
Fiber Optics - DescriptionConstruction
Korakot PHOTJANASUNTORN 25/9525/95
Fiber Optics - DescriptionCladding - A Semi-Reflective Material
Korakot PHOTJANASUNTORN 26/9526/95
MVC PLUS - Fiber Optics Facts
1000 micron (1 millimeter) diameter core
Plastic Optical Fiber (POF)
Cladding is a semi-reflective coating on the core
660 nanometer wavelength, optical red light
Not a laser, will not damage eyesight
1 megabit maximum transmission rate, actual signal is 250 kHz max
Maximum 1 kilometer transmission length, less than 4 meters (per fiber length) in RVSS
SCR firing transmitters are 10mm water-clear LEDs (Light Emitting Diodes) mounted on the Main Board
Korakot PHOTJANASUNTORN 27/9527/95
MVC PLUS Controller - Additional Features
3 Level Non-Volatile Memory System– High speed RAM for system operation– EPROM for Factory Settings and Defaults– EEPROM for User Settings– No battery backup required for user settings
Real Time Clock– Used in protection and metering – 10+ year battery backup
Korakot PHOTJANASUNTORN 28/9528/95
MVC PLUS Controller - Communications
RS485 Modbus RTU Built-In
RS232 Windows Based Programming / Monitor Program
Korakot PHOTJANASUNTORN 29/9529/95
Motortronics MVC Plus Product TrainingStartup, Operation & Service Session
INTRODUCTION & OBJECTIVES OF SESSIONA
MVC PLUS DESCRIPTIONB
MVC PLUS FUNCTIONS - PROGRAMMINGC
COMMISSIONINGD
TROUBLESHOOTING & MAINTENANCEE
PROGRAMMING EXERCISE F
CONCLUSION G
Korakot PHOTJANASUNTORN 30/9530/95
MVC PLUS Setpoint Page 1 Where To Input Motor Nameplate Data
These Settings Include Data Used By The CPU For Motor Thermal Capacity Modeling
Motor FLA And Service Factor Are Governed By (SF x FLA) Calculation For Unit Maximum Current In Setpoint Page 13 (More Information Later)
Korakot PHOTJANASUNTORN 31/9531/95
MVC PLUS Setpoint Page 1Basic Overload Protection - Start Up (& Run)
NEMA / UL Pre-Programmed O/L Trip Curves Class 5 Through Class 30
10
100
600
100% 600%
%FLA%FLA
SecondSecondss
400%
Class 30Class 30
Class 20Class 20
Class 10Class 10
Korakot PHOTJANASUNTORN 32/9532/95
MVC PLUS Setpoint Page 2
Motor Starting, Deceleration And Ramp Type Settings
Most Starting Situations Require Only VOLTAGE RAMP With CURRENT LIMIT Starting Profile
The INITIAL VOLTAGE Setting Is Used To Move The Rotor From A Standstill And Nothing More
The RAMP TIME Setting Is An Approach Vector Between INITIAL VOLTAGE Setting And CURRENT LIMIT Setting. A Long RAMP TIME Setting Delays The Time For The MVC Plus To Settle Into CURRENT LIMIT Mode
The CURRENT LIMIT Setting Is Where The “Real Work” Begins. The Maximum Power (Setpoint Limited) That Is Applied To The Motor When The MVC Plus Is Operating In CURRENT LIMIT. If The Starter Trips On Acceleration Time Trip, Increase CURRENT LIMIT To Reduce The Starting Time
Korakot PHOTJANASUNTORN 33/9533/95
Typical Starting ProfileVoltage Ramp With Current Limit
TIME
VOLTS / AMPS
AT SPEEDINITIAL VOLTAGE
Initial Voltage - Setpoint 2.3.V1Initial Voltage - Setpoint 2.3.V1
RAMP TIME
Ramp Time - Setpoint 2.3.V2Ramp Time - Setpoint 2.3.V2
CURRENT LIMIT
Current Limit - Setpoint 2.3.V3Current Limit - Setpoint 2.3.V3
Korakot PHOTJANASUNTORN 34/9534/95
MVC PLUS Setpoint Page 2Advanced Ramp Features
Ramp Features– Voltage Ramp w/ Current Limit– Current Limit / Current Step– Closed Loop Current / Torque Ramp– Tach. Feedback Speed Ramp
Custom Ramp Profiling Dual Ramps Pump Control / Deceleration
Korakot PHOTJANASUNTORN 35/9535/95
MVC PLUS Setpoint Page 2Dual Ramp - Soft Start
Start Ramp 1 Selected
Ramp 1 - Voltage Ramp w/ Current Limit
Ramp
Time
Current Limit Setting
Current Limit overrides Ramp Time
Current Level Held to Limit Setting
Full Speed
RampStart
Korakot PHOTJANASUNTORN 36/9536/95
MVC PLUS Setpoint Page 2Dual Ramp - Near ATL
Start Ramp 2 Selected
Ramp 2 - Loaded Restart,“Near Across-the-Line”
Almost Full-Voltage Start, No Ramp Time
High Current Near Full-Torque Starting
Korakot PHOTJANASUNTORN 37/9537/95
MVC PLUS Setpoint Page 2Uses For Dual Ramp Profiles
Loaded Restart After a Power outage– Conveyors, Crushers
Higher Torque for Occasional Starting Requirements
– Specialized Machinery – Design C Motors– Two-Speed Motors (To Start At Either Speed)
Korakot PHOTJANASUNTORN 38/9538/95
MVC PLUS Setpoint Page 2Shorted Load Protection During Start
“Toe-in-the-Water” Circuit
– First 1/4 second of ramp time
– Checks rate of current rise
– Prevents collateral damage
MOTOR VOLTSCURRENT Trip
Start
Initial TorqueSetting
1/4 Second
Korakot PHOTJANASUNTORN 39/9539/95
MVC PLUS Setpoint Page 2Flexible Deceleration - Pump Control
Allows Full Adjustment
Independent of Acceleration Ramp
Automatic Stop Level - Prevents excessive heating in the motor
Voltage
RunStart Ramp StopBegin Decel
Torque (Coast)
Valve Closes Here
Korakot PHOTJANASUNTORN 40/9540/95
PUMP OFF
Pump Control - Hydraulic System Problems
Trapping the kinetic energy of moving water causes “WATER HAMMER”
– Check valves keep head pressure from pushing fluids backwards into the pump
HEAD PRESSUREPUMP FLOWPUMP FLOW
PUMP ONPUMP ONVALVE CLOSED
Korakot PHOTJANASUNTORN 41/9541/95
Pump Control - Hydraulic System Problems
Trapping the kinetic energy of moving water causes “WATER HAMMER”
– Check valves keep head pressure from pushing fluids backwards into the pump.
HEAD PRESSURE
PUMP ONPUMP ONVALVE OPENS
PUMP FLOWPUMP FLOW PUMP PRESSURE / FLOWPUMP PRESSURE / FLOW
Korakot PHOTJANASUNTORN 42/9542/95
Pump Control - Hydraulic System Problems
PUMPPUMP OFFOFFVALVE CLOSES
PUMP FLOW`PUMP FLOW` HEAD PRESSURE
Korakot PHOTJANASUNTORN 43/9543/95
Pump Control - Hydraulic System Problems
The energy of the back-flowing water is trapped, creating a SHOCK WAVE traveling at the speed of sound
Liquids don’t compress, so energy is forced onto piping, fittings and seals
PUMP OFFPUMP OFFVALVE CLOSES
Trapping the kinetic energy of moving water causes “WATER HAMMER”
– When the pump suddenly stops, flow reverses until check valve closes.
Korakot PHOTJANASUNTORN 44/9544/95
Controlled Deceleration can reduce Water Hammer Reduced pump pressure closes valves more
slowly, at near-neutral pressure– Kinetic energy is slowly dissipated– Shock wave is not created
VALVE OPENPUMP ONPUMP ON
VALVE CLOSINGSOFT STOPSOFT STOPPUMP OFFPUMP OFF
VALVE CLOSED
Pump Control - Hydraulic System Problems
Korakot PHOTJANASUNTORN 45/9545/95
MVC PLUS Setpoint Page 3
Phase and Ground Detection Settings
All Trip and Alarm Settings can be enabled / disabled and Values for Trip / Alarm are programmed here *
* With the exception of Acceleration Time Trip Setting located in Setpoint Page 8 and RTD / Thermal Capacity Alarm Settings in Setpoint Page 12
Korakot PHOTJANASUNTORN 46/9546/95
MVC PLUS Setpoint Page 3Electrical Protection Features
Over Voltage
Under Voltage
Frequency Window
Phase Current Loss
Phase Current Imbalance
Shorted Load Protection
Zero Sequence Ground Fault Option
Korakot PHOTJANASUNTORN 47/9547/95
MVC PLUS Setpoint Page 3Load Protection
Over Current – Jam relay, electronic shear pin
Under Current – Load loss, broken belt, loss of prime
Phase Sequence– ABC, ACB, or Disabled
Anti-Oscillation Control– Prevents surging in pump systems
Korakot PHOTJANASUNTORN 48/9548/95
MVC PLUS Setpoint Page 4
Output Relay Assignments.
Up to 3 Relays can be assigned per Trip / Alarm function.
Dedicated Relays
– Aux 1 = Trip
– Aux 2 = Alarm
– Aux 3 = Run Indication – When current is above 7% of programmed FLA
– Aux 4 = Bypass Contactor
Korakot PHOTJANASUNTORN 49/9549/95
MVC PLUS Setpoint Page 5 Output Relay Configuration.
Output Relays can be assigned for failsafe and whether Latched or Not.
Aux 1 (Trip) must be Latched.
First 4 Relays are pre-assigned from the factory.
Relays 5 – 8 can be assigned to Trip / Alarm functions and wired as needed.
Korakot PHOTJANASUNTORN 50/9550/95
MVC PLUS Setpoint Page 6
User Input / Output Configuration.
4-20 mA Tachometer Input.
4-20 mA Analog Outputs 1 & 2.
4 Programmable External Input Trip Channels
Korakot PHOTJANASUNTORN 51/9551/95
MVC PLUS Setpoint Page 6Programmable Input / Output Features
120V Inputs– 2 wire or 3 wire control, external trip.
1 Analog Tachometer Input– 4-20mA signal. The pickup for the signal generator to the starter must be at
least 4 pulses/rotation from the motor shaft.
4 Programmable External Input Trip Channels– 1, 3 & 4 are for Factory Use Only. This is a +5VDC loop. Use dry contacts
only, do not apply AC power to this loop.
8 Digital Outputs – Each can be assigned to alarms and/or trips– Not used in Start/Stop circuit
2ea 4-20ma Analog Outputs– Programmable for RMS Current, % Motor Load, Bearing Temperature, Stator
Temperature, or RPM
Korakot PHOTJANASUNTORN 52/9552/95
MVC PLUS Setpoint Page 7
Custom Acceleration Curve.
3 Separate Curves - A, B & C.
8 Programmable Steps – Voltage and Duration for each step.
Maximum Current Threshold Set point.
Korakot PHOTJANASUNTORN 53/9553/95
MVC PLUS Setpoint Page 7 Custom Ramp Profiles
3 Programmable Custom Curves
8 Data Points in Each Enter Voltage, Current, Time
– Match ramp profile to practically any application
Korakot PHOTJANASUNTORN 54/9554/95
MVC PLUS Setpoint Page 83 Overload Protection Choices During Start-up
Basic Overload Protection for Start (& Run)– Programmable overload Class 5 – 30
–
Measured Start Capacity– I2t thermal capacity from data
Learned Curve Protection– Starter learns from recorded data
Korakot PHOTJANASUNTORN 55/9555/95
Class 20 I2t curve
Area Under Curve protectionArea Under Curve protection
MVC PLUS Setpoint Page 8Measured Start Capacity For Start Up Uses basic overload curve as programmed
User enters maximum I2t value from motor manufacturer or commissioning data
Basic curve is altered
Matches motor more closely
Measured I2t capacity
Korakot PHOTJANASUNTORN 56/9556/95
MVC PLUS Setpoint Page 8Overload Protection Benefits
Provides “Trip Free” Overload (No over-ride)– Cannot be defeated by cycling power
– Not all solid state overloads do this!
Prevents Motor Damage– Protection from careless operators.
Korakot PHOTJANASUNTORN 57/9557/95
MVC PLUS Setpoint Page 82 Overload Protection Choices During Run
Basic Overload Protection– Run Overload is programmed the same as for Starting
Custom (Modified) Curve
Korakot PHOTJANASUNTORN 58/9558/95
Modified CurveModified Curve
Example:Example:
New LRA = New LRA = 400%400%
Time = 25 sec.Time = 25 sec.
10
100
600
100% 600% %FLA%FLA
Secon
dS
econ
dss
400%
Class 20 Class 20 Curve:Curve:
LRA= 600%LRA= 600%
Time = 20 Time = 20 sec. sec.
Overload Protection - During RunCustom (Modified) Curve Protection
Begin with Class 5 through Class 30 Program 2 data points
– Locked rotor amps (LRA) and trip time
Creates a Custom Curve by modifying the Basic curve
Korakot PHOTJANASUNTORN 59/9559/95
MVC PLUS Setpoint Page 8Learned Curve Protection For Start-Up
Starter placed in “Learn Mode”
CPU samples I/t data points – Time slice programmable from 1-300 sec.– Learned curve is stored and compared at each start.
0
100
200
300
400
500
% of Nameplate FLA
Korakot PHOTJANASUNTORN 60/9560/95
MVC PLUS Setpoint Page 8Duty Cycle Protection
Coast Down Lockout Timer– Back spin lockout
Starts-per-Hour Lockout
Time-Between-Starts Lockout
Korakot PHOTJANASUNTORN 61/9561/95
MVC PLUS Setpoint Page 8Coast Down Lockout Timer
Backspin Lockout– Keeps motor from restarting while spinning
On
OffStartStart
Coast Down Time
Stop
Begin Timing
Run Time
Start
Korakot PHOTJANASUNTORN 62/9562/95
Start
MVC PLUS Setpoint Page 8Duty Cycle Protection
Starts-per-Hour Lockout Timer– Prevents “Short Cycle” motor damage
Time Between Starts Lockout– Minimum time before start attempts
(used with Starts / Hour lockout)
StartStart
Time Between Starts
Start
Time Between Starts
Start
Time Between Starts
Start
Starts / Hour Lockout
(if set at 3)
Start
Korakot PHOTJANASUNTORN 63/9563/95
MVC PLUS Setpoint Page 9
Up To 12 Flexible RTD Inputs – Configurable for any RTD type.
RTD Biasing of Thermal Register.
RTD Voting.
Max Temp Recording
Field Installable - See Instructions
for RTD calibration
RTD Option Card
Front Bearing (Cu)
Stator A1 (Pt)Stator B1 (Pt)Stator C1 (Pt)Back Bearing (Cu)Ambient (Ni)
Stator B2 (Pt)Stator C2 (Pt)
Bearing Box (Cu)Stator A1 (Pt)
Oil ReservoirSpare
CPU
Korakot PHOTJANASUNTORN 64/9564/95
MVC PLUS Setpoint Page 10
Security / Passwords
Factory Level 2 Password = 100 - One with two zeros.
Factory Level 3 Password = 1000 - One with three zeros.
Password for Setpoint Page 13 (Factory Setting) is not documented.
Level 2 & 3 Passwords can be changed. If customer forgets his password, only Factory Password will regain control.
Korakot PHOTJANASUNTORN 65/9565/95
MVC PLUS Setpoint Page 11
Communications Settings
Modbus Baud Rate and Addressing.
RS232 Baud Rate.
RS485 (Modbus) Channel is pipelined over RS422 (Display) Channel. Polling too much or too fast can cause “Wait To Communicate” to be displayed.
Korakot PHOTJANASUNTORN 66/9566/95
MVC PLUS Setpoint Page 12
System Set points
Setup Default Screen Display during Run.
Thermal Register Setup.
RTD Failure Alarm Settings.
Thermal Register Alarm Settings.
Clear Thermal Register.
Korakot PHOTJANASUNTORN 67/9567/95
MVC PLUS Setpoint Page 12 Custom Motor Overload Protection
Motor Thermal Modeling – With retentive memory
Dynamic Reset Capacity – With “True Time” cooling rates
Dual Protection Modes– Separate settings for Start & Run
– Example: Class 30 for starting and Class 10 for running
– Great for long haul conveyor applications
Korakot PHOTJANASUNTORN 68/9568/95
MVC PLUS Setpoint Page 12 Motor Thermal Modeling
Thermal Register – In processor memory
– Mathematical representation of the motor
Created from Nameplate Data– Adjusts to starting / running conditions
Dual Use– Warning and/or tripping
Korakot PHOTJANASUNTORN 69/9569/95
MVC PLUS Setpoint Page 12 Retentive Thermal Memory
CPU – Tracks the motor’s thermal state
Records thermal state when power fails
Automatically stored in non-volatile memory– EEPROM, no batteries needed
Returns to normal on power-up
Re-calibrates for elapsed off-time
Korakot PHOTJANASUNTORN 70/9570/95
Thermal Register in
Non Volatile Memory
0%0%(Over Load)(Over Load)
25%25%
50%50%
75%75%
100%100%(Cold)(Cold)
Example:
Thermal Capacity used in Starting
Cooling Rate Cooling Rate while while
RunningRunning
Remaining Thermal Capacity
MVC PLUS Setpoint Page 12 Motor Thermal Modeling
Korakot PHOTJANASUNTORN 71/9571/95
Thermal Register in
Non Volatile Memory
0%0%(Over Load)(Over Load)
25%25%
50%50%
75%75%
100%100%(Cold)(Cold)
Example:
Thermal Capacity used in Starting
Power Fail!Power Fail!
Cooling Rate Cooling Rate while Offwhile Off
Recalculated
Remaining Thermal Capacity
Power RestoredPower Restored
MVC PLUS Setpoint Page 12Retentive Thermal Memory With Real Time Clock
Korakot PHOTJANASUNTORN 72/9572/95
MVC PLUS Setpoint Page 12 Benefits
Makes Full Use of Motor Data– Takes advantage of quicker cooling
Eliminates Guess Work or Compromises – Helps prevent premature restarting and failed starts
Korakot PHOTJANASUNTORN 73/9573/95
MVC PLUS Setpoint Page 12 Dynamic Reset Capacity
CPU “Learns” the Motor and Load
Records Thermal Capacity Needed – Averages previous successful starts
Inhibits Reset – Until enough thermal capacity is recovered
Korakot PHOTJANASUNTORN 74/9574/95
Thermal Register in
Non Volatile Memory
0%0%(Over Load)(Over Load)
25%25%
50%50%
75%75%
100%100%(Cold)(Cold)
Thermal Capacity used in
Successful Start
Example:Example:
Running Overload
10% 10% RemainingRemaining
CoolingRateWhile
OffFrom
Over LoadTrip
No Reset until No Reset until 90% remaining 90% remaining based on based on capacity used in capacity used in previous previous successfulsuccessful start. start.
RESETRESETRESET
MVC PLUS Setpoint Page 12 Dynamic Reset Capacity
Korakot PHOTJANASUNTORN 75/9575/95
MotoMotor r
TempTemp
Cooling RateCooling Rate LowLow
HighHigh
MVC PLUS Setpoint Page 12 True Time® Cool-Down Rates
Non-linear rate of cooling– Based on Thermal Model values
Accounts for extra convection– Hot motors cool more quickly at first– Cooling rate slows as it cools
True TimeTrue Time® Variable Cool Variable Cool
RateRate
Typical OL Typical OL Relay Relay
Cool Down Cool Down RateRate
Korakot PHOTJANASUNTORN 76/9576/95
MVC PLUS Setpoint Page 12 Benefits Dynamic Reset Capacity
Avoids Exhausting Starts/Hour Rating– Prevents having to wait longer for reset
– Takes the “guesswork” away from the operator
Saves Operating Costs– Helps prevent motor damage
– Decreases downtime
Korakot PHOTJANASUNTORN 77/9577/95
MVC PLUS Setpoint Page 13
Unit Factory Settings
Password for Setpoint Page 13 = 48562
(Not Documented).
Unit Maximum Current – Use SF X FLA calculation to enable correct settings in Setpoint Page 1.
Phase CT Primary Ratio – Value of CTs located inside of red box in MVC Plus enclosure. Set from the factory.
Ground CT Primary Ratio Setting.
PT / VT Primary Ratio Setting.
Korakot PHOTJANASUNTORN 78/9578/95
MVC PLUS Setpoint Page 13 - Continued
Sync Bypass Close – Sets triggering of bypass contactor - Firing Angle and/or Current Drop Off.
Bypass Drop Out Delay – Programmable delay for the opening of bypass contactor after stopping.
Bypass Discrepancy – Not used, Future Option.
Shunt Trip – Not Used, Future Option.
Starter Settings – Offset adjustment factors to correct current & voltage limit output during starting. Not normally accessed.
Tachometer Input Offset – Adjustment factors for compensation.
Korakot PHOTJANASUNTORN 79/9579/95
MVC PLUS Setpoint Page 13 - Continued
Analog Outputs 1 &2 Offset – Programmable output control.
RTD Calibration – Refer to procedure
Short Circuit Limit Adjustment and Delay.
Reset all relays – No longer needed.
Factory Reset – Refer to Factory Reset Procedure.
Korakot PHOTJANASUNTORN 80/9580/95
INTRODUCTION & OBJECTIVES OF SESSIONA
MVC PLUS DESCRIPTIONB
MVC PLUS FUNCTIONS - PROGRAMMINGC
COMMISSIONINGD
TROUBLESHOOTING & MAINTENANCEE
PROGRAMMING EXERCISE F
CONCLUSION G
Motortronics MVC Plus Product TrainingStartup, Operation & Service Session
Korakot PHOTJANASUNTORN 81/9581/95
MVC PLUS - Service Manual Documents
Tab 1 – Theory of Operation – How The MVC Plus Works
Tab 2 – MVC Plus Manual – Soft Starter Document
Tab 3 – Electrical Drawings – Soft Starter Kit Drawings
Tab 4 – Application Information – Common Issues Seen In The Field
Tab 5 – Communications – MODBUS RTU Using RS-485
Tab 6 – Service Procedures – Alignments And Adjustments
Tab 7 – RTD Data Sheets – Temp / Resistance Maps
Korakot PHOTJANASUNTORN 82/9582/95
MVC PLUS CommissioningFinal Inspection Before Start Up
Collect Data for Set Point Programming– Collect Nameplate Data from: Motor, Transformer, Load, Gearbox
Medium voltage cable Hi-Pot tests performed and successful
Check all control wiring
Verify all connections, fuses, current transformer circuit
Verify that all protective & timing relays have been set
With disconnect switch closed, verify MV door cannot be opened
Verify LV compartment plugs are connected
Verify that all insulating barriers are clean & dry
Inspect the equipment for loose parts, litter, tools …
Review any key interlocking schemes
Verify that all barriers and doors are secured
Korakot PHOTJANASUNTORN 83/9583/95
MOTOR
LOAD?
TRANSFORMER
Due to a lack of understanding, the MVC Plus is the first thing to be blamed when something doesn’t seem to work right during commissioning
Many times, the end-user has to be educated in order to become comfortable with the MVC PLUS. Primarily, the end-user needs to realize that the MVC PLUS does not make power. It works similar to a fluid control valve, slowly building up voltage and current to the motor
If the system power is weak and the voltage drops so low as to reduce the
Motor Torque below the Load Torque, the system will not come up to rated speed
The Misunderstood MVC PLUS
Korakot PHOTJANASUNTORN 84/9584/95
Motor Torque produced is proportional to both the Field and Rotor Voltages. This means that Motor Torque is proportional to the square of the Motor Terminal Voltage
The system will never make it to rated speed if not enough torque is available from the motor to overcome the Load Torque
The box beside can be manipulated, but the Amount of Output must create sufficient Motor Torque
MVC PLUS - 3 Dimensional Box Theory
TIME
AMPS
VOLTS MOTOR TORQUE
Korakot PHOTJANASUNTORN 85/9585/95
Motortronics MVC Plus Product TrainingStartup, Operation & Service Session
INTRODUCTION & OBJECTIVES OF SESSIONA
MVC PLUS DESCRIPTIONB
MVC PLUS FUNCTIONS - PROGRAMMINGC
COMMISSIONINGD
TROUBLESHOOTING & MAINTENANCEE
PROGRAMMING EXERCISE F
CONCLUSION G
Korakot PHOTJANASUNTORN 86/9586/95
Most troubleshooting is done primarily with the supplied MVC Plus Service Manual and the Soft Starter drawings
Hands-on troubleshooting with an actual MVC Plus chassis unit will be performed later
MVC PLUS - Troubleshooting Outline
Korakot PHOTJANASUNTORN 87/9587/95
Test To Perform Ohm Meter Reading Test Result
From Position A to Position B Greater than 10K Ohm Pass
Less than 10K Ohm Fail
From Position B to Position C Greater than 10K Ohm Pass
Less than 10K Ohm Fail
Gate (G) to Cathode (K) for each SCR 8 to 100 Ohms Pass (Typical 8 to 20 Ohms)
Less than 8 or greater than 100 Ohms Fail
Troubleshooting & Maintenance - SCR Test Procedure When the condition of the SCRs is suspected, a resistance check can be
performed on the SCR heat sink assemblies in the right-hand cabinet to confirm if they have been damaged. This test is to be performed on each individual assembly per phase (there are 3 SCR heat sink assemblies per phase).
Note: Allow 15 minutes after shutdown for the stack assembly DV/DT networks to discharge any stored DC voltages.
Refer to the image to the right for test connection references.
Korakot PHOTJANASUNTORN 88/9588/95
Fiber Optic Troubleshooting - Connectors
Be sure to check all connections and block orientations as shown.
Ensure all fiber-optic connectors are fully seated in their proper assemblies on the circuit boards (SCR Stack Assembly).
Ensure indexing dot in the fiber-optic block is placed over the white silk-screened mark on the Main Board.
Korakot PHOTJANASUNTORN 89/9589/95
Minimum bend radius of the optical fiber used in the Limitamp MVC Plus is 2” [51mm].
If a bend radius is too small, the fiber core will have tiny cracks on the outer portion of radius.
Straightening a fiber after too tight of a bend has been made will not fix it.
Fiber Optic Troubleshooting – Bend Radius
Korakot PHOTJANASUNTORN 90/9590/95
The clear fiber optic core has a lower melting point than the jacket
Heat damage can cause a minor distortion or slight swelling that is barely visible on the surface of the jacket
The damage can be felt with the fingers, simply by pinching fiber lightly between index finger & thumb, then drag fingers North/South, East/West down length of fiber
Use caution when routing fibers through starter and around circuit boards
Melted / Swelled Fiber Optic Cables From Heat Shrinking Wire Markers Near Fiber Optic Harness
Fiber Optic Troubleshooting – Heat Damage
Korakot PHOTJANASUNTORN 91/9591/95
Motortronics MVC Plus Product TrainingStartup, Operation & Service Session
INTRODUCTION & OBJECTIVES OF SESSIONA
MVC PLUS DESCRIPTIONB
MVC PLUS FUNCTIONS - PROGRAMMINGC
COMMISSIONINGD
TROUBLESHOOTING & MAINTENANCEE
PROGRAMMING EXERCISE F
CONCLUSION G
Korakot PHOTJANASUNTORN 92/9592/95
MVC PLUS Setpoint Programming Exercise
Refer To Programming Exercise Presentation
Korakot PHOTJANASUNTORN 93/9593/95
Motortronics MVC Plus Product TrainingStartup, Operation & Service Session
INTRODUCTION & OBJECTIVES OF SESSIONA
MVC PLUS DESCRIPTIONB
MVC PLUS FUNCTIONS - PROGRAMMINGC
COMMISSIONINGD
TROUBLESHOOTING & MAINTENANCEE
PROGRAMMING EXERCISE F
CONCLUSION G
Korakot PHOTJANASUNTORN 94/9594/95
QQuestions & Answers
Korakot PHOTJANASUNTORN 95/9595/95
For your attentionThanks