KN-2000W Series
Transcript of KN-2000W Series
KN-2000W Series
B-14
• Highaccuracywith16bitADC(±0.2%F.S.)• Max.displayrange: 19999to19999• Multi-input:Thermometer12types,RTD5types,analog(mV,V,mA)6types
• Autodisplaycolorchangefunction(forerrororalarm)• Variousoutputoptions:4EAor2EAalarmoutput,4-20mAtransmissionoutput(isolated),RS485communicationoutput
※Fulloutputoptionmodelisavailable.(alarmoutput4EA+RS485communicationoutput
+transmissionoutput)• Variousfunctions:High/Lowpeakmonitoring,sensorbreakalarmoutput(burn-out),inputcorrection,digitalinput(DI),userinputrange,displayscale,transmissionoutputscale,etc.
• Built-inpowersupplyforsensor(24VDC)
(unit:mm)
Min.116
92+0.60
+0.6
046
Min.52
W DINW96×H48mm
KN-2 MultiIndicator
0 100-240VAC50to60Hz1 24VDC
0 Nooption1 Transmissionoutput(4-20mA)4 RS485communicationoutput
5 Transmissionoutput(4-20mA)+RS485communicationoutput
0 Noalarmoutput2 2EAalarmoutput4 4EAalarmoutput
KN-2 0 0 0 W
Powersupply
Optionoutput
Alarmoutput
Item
Size
10
90
91
44.8
Panel cut-out
Please read “Caution for your safety” in operation manual before using this unit.
Features
Ordering information
Dimensions
96
48
108
Multi Indicator
B-15
A.Recorder
B. Indicator
C.Converter
D.Controller
E.Thyristorunit
F.Pressuretransmitter
G.Temp.transmitter
H.Accessories
KN-1000B
KN-2000W
KN-20 W KN-24 W KN-22 W
Series KN-2000W
Powersupply
ACvoltage 100-240VAC50to60Hz
DCvoltage 24VDC
Allowablevoltagerange 90to110%ofratedvoltage
Powercon-sumption
ACvoltage Max.8VA
DCvoltage Max.3W
Displaymethod 41/2digit:7SegmentLEDDisplay(selectablered,green,yellow),charactersize:W10mm×H17mm
Inputtype
RTD JPt100Ω,DPt100Ω,DPt50Ω,Cu50Ω,Cu100Ω(5types)
Thermocouple K,J,E,T,R,B,S,N,C(W5),L,U,PLII(12types)
Analog ·Voltage:±1.0000V,±50.00mV,±200.0mV, 1.000V-10.000V(4types)·Current:4.00-20.00mA,0.00-20.00mA(2types)
Digitalinput·Contactinput:Max.2kΩinON,Max.90kΩinOFF·Non-contactinput:Residualvoltagemax.1.0VinON,Leakagecurrentmax.0.03mAinOFF·Outflowcurrent:Approx.0.2mA
Suboutput
Alarmoutput 2-point:Relaycontactcapacity250VAC3A1c,4-point:Relaycontactcapacity250VAC1A1a
Transmissionoutput ISOLATEDDC4-20mA(PVtransmission)loadresistancemax.600Ω(accuracy:±0.2%F.S.,resolution:8000)
Communicationoutput RS485(ModbusRTU)
Displayaccuracy
±0.2%F.S.±1digit(25±5)±0.3%F.S.±1digit( 10to20,30to50)Incaseofthermocoupleandbelow-100°Cinput,[±0.4%F.S.]±1digit※TC-T,TC-Uismin.±2.0
Settingmethod Setbyfrontkeys,orRS485communication
Alarmoutputhysteresis SetON/OFFinterval(1to999digit)
Samplingcycle Analoginput:100ms,Temperaturesensorinput:250ms
Dielectricvoltage 2000VAC50/60Hzfor1min.(betweeninputterminalandpowerterminal)
Vibration 0.75mmamplitudeatfrequencyof5to55Hz(for1min.)ineachofX,Y,Zdirectionsfor2hours
Relaylifecycle
2-point Mechanical:Min.10,000,000,Electrical:Min.100,000(250VAC3Aresistanceload)
4-point Mechanical:Min.20,000,000,Electrical:Min.500,000(250VAC1Aresistanceload)
Insulationresistance Min.100MΩ(at500VDCmegger)
Noiseresistance Squareshapednoisebynoisesimulator(pulsewidth1)±2kV
Memoryretention Approx.10years(non-volatilesemiconductormemorytype)
Environ-ment
Ambienttemperature 10to50,storage: 20to60Ambienthumidity 35to85%RH,storage:35to85%RH
Approval
Unitweight Approx.200g
※Environmentresistanceisratedatnofreezingorcondensation.
F.G.
RTD/TC/mV/±1V
-1to+10V
0to20mA
Connections
Specifications
KN-2000W Series
B-16
①Displaypart(red)Runmode:Displayscurrentmeasurementvalue.Parametersetmode:DisplaysparameterandSV.②Unitindicator:Displaysthesetunit.③Alarmoutputindicator:TurnsONwhenthealarmisON.④(key:Usedtoenterparametersetmode,movetoparameters,saveSVandreturntoRUNmode.⑤1,4,3key:UsedtochangeparameterSV.⑥D.IN3:Pressthe4and3keyskeysfor3sec.atthesametime,itoperatesthesetfunction(alarmclear,displayhold,zero-pointadjustment)at[DI-K]atprogrammode.
Inputtype Parameter Inputrange() Inputrange()
Thermocouple
K(CA) TC-K 200.0 to1350.0 328 to2462
J(IC) TC-J 200.0 to800.0 328.0 to1472.0
E(CR) TC-E 200.0 to800.0 328.0 to1472.0
T(CC) TC-T 200.0 to400.0 328.0 to752.0
R(PR) TC-R 0.0 to1750.0 32 to3182
B(PR)* TC-B 400.0 to1800.0 752 to3272
S(PR)* TC-S 0.0 to1750.0 32 to3182
N(NN)* TC-N 200.0 to1300.0 328 to2372
C(W5)* TC-C 0 to2300 32 to4172
L(IC)* TC-L 200.0 to900.0 328.0 to1652.0
U(CC)* TC-U 200.0 to400.0 328.0 to752.0
PlatinelII* TC-P 0.0 to1390.0 32 to2534
RTD
Cu50Ω* Cu50 200.0 to200.0 328.0 to392.0
Cu100Ω* Cu10 200.0 to200.0 328.0 to392.0
JPt100Ω JPt1 200.0 to600.0 328.0 to1112.0
DPt50Ω DPt5 200.0 to600.0 328.0 to1112.0
DPt100Ω DPt1 200.0 to850.0 328.0 to1530.0
Analog
Current0.00 - 20.00mA aMA1
19999to19999(displayrangedependsonthedecimalpointposition)
4.00 - 20.00mA aMA2
Voltage
50.00 - 50.00mV aMV1
200.0 - 200.0mV aMV2
1.0000 - 1.0000V A-V1
1.000 - 10.000V A-V2
※Aboveinputtypeswhichhavethe*markarenotdisplayed.Todisplaytheaboveinputtypes,supplythepowerwithpressingthe(key.
٧٧ Input type selection switch
0-20mA:Selectitfor0(4)-20mAinput
1-10V:Selectitfor 1V-10Vinput
TD/TC/mV/±1V:SelectitforRTD,TCtemperaturesensoror±1V,mVinput
Thisunitismultiinputproduct.SelecttheproperinputwiththeinputtypeselectionswitchandselectthisinputtypeinIN-Pinprogrammode.ThesettingofinputtypeselectionswitchandtheinputtypeIN-Pparametershouldbesameanditcandisplaythepropermeasurementvalue.Factorydefaultis4-20mA.
Input type and range
Part descriptions
①
②③
④ ⑥
⑤
Multi Indicator
B-17
A.Recorder
B. Indicator
C.Converter
D.Controller
E.Thyristorunit
F.Pressuretransmitter
G.Temp.transmitter
H.Accessories
KN-1000B
KN-2000W
Alarm [ AL-1, AL-2, AL-3, AL-4 ]Thisproducthas2or4alarmstooperateindividuallywhenthevalueistoohighorlow.Alarmfunctionissetbythecombinationofalarmmodeandalarmoption.Toclearalarm,usedigitalinputfunction(setting 야DI-T, DI-K as AlRE)orturnthepowerOFFandON.※Forthemodel(KN-20 W)withoutalarmoutput,theseparametersarenotdisplayed.
AT!A
Alarmoption
Alarmoperation
٧٧ Alarm operation
٧٧ Alarm option
Alarm output hysteresis [ Program mode: A-HY ]SettheintervalofON/OFFalarmoutput.ThesethysteresisisappliedtoAL1toAL4anditisasbelow.※Ex)A-HY:4,highlimitalarmvalue:800,lowlimitalarmvalue:200
Highlimitalarmvalue800
800ON
796OFF
A-HY:4
Lowlimitalarmvalue200
200ON
204OFF
A-HY:4
Error
High/Low peak monitoring [ Monitoring mode: H.PEK, L.PEK ]
Thisfunctionistosavehigh/lowpeaktochecktheinvisibleabnormalconditionofsystemat[hPEK]or[lPEK]inmonitoringmode.Whenthehigh/lowpeakisoutofthetemperaturerange,itdisplaysHHHHorLLLL.Toinitializehigh/lowpeak,pressthe3,4keysatthesametimefor3sec.at[hPEK]or[lPEK].Inthiscase,peakvalueisthepresentinputvalue.
Display Descriptions Troubleshooting
LLLLFlasheswhenmeasuredsensorinputislowerthanthetemperaturerange.
Wheninputismovedwithinthetemperaturerange,itiscleared.HHHH
Flasheswhenmeasuredsensorinputishigherthanthetemperaturerange
BURN Flasheswhenthesensorisbreakornotconnected.
Checktemperaturesensorconnection.
ERRFlasheswhenthereiserrortoSV
Checksetconditionsandre-setit.
ERR1FlasheswhenIN-P settingandinputtypeselectionswitchsettingarenotsame.
Checkinputtype.
Mode Name Alarmoperation Descriptions
AT)_ ㅡ ㅡ Noalarmoperation
AT! HighlimitalarmHighlimtalarmvalue:800
OFF ON
PV
HPV≥alarmtemperature,alarmisON
AT@ Lowlimitalarm
Lowlimtalarmvalue:200
OFFON
PV
HPV≤alarmtemperature,alarmisON
SBa_ Sensorbreakalarm ㅡ ItwillbeONwhenitdetectssensordisconnection.Sensorbreakalarmdoesnothavealarmoption.
Mode Name Descriptions
AT .A Standardalarm Ifitisanalarmcondition,alarmoutputisON.Unlessanalarmcondition,alarmoutputisOFF.
AT .B Alarmlatch Ifitisanalarmcondition,alarmoutputisON.Beforeclearingthealarm,anONconditionislatched.(Holdingthealarmoutput)
AT .C StandbysequenceFirstalarmconditionisignored.Fromthesecondalarmcondition,standardalarmoperates.WhenpowerisONanditisanalarmcondition,itisignored.Fromthesecondalarmcondition,standardalarmoperates.
AT .DAlarmlatchandstandbysequence
Ifitisanalarmcondition,itoperatesbothalarmlatchandstandbysequence.WhenpowerisONanditisanalarmcondition,itisignored.Fromthesecondalarmcondition,alarmlatchoperates.
※H:Alarmoutputhysteresis
Functions
KN-2000W Series
B-18
Parameter initialization
Temperature unit [ Program mode : UNIT ]
Input and transmission output extension [ Program mode: ExIO ]
Front display unit [ Program mode : dUNT ]
User input range [ Program mode : L-RG, H-RG ]
Thisfunctionistoextendanaloginputand4to20mAtransmissionoutputto5%or10%range.
※Thisparameterisdisplayedonlyfortransmissionoutput(4-20mA)model.Butitisnotdisplayedwhenselectingtemperaturesensorinput.
Toinitializeallparameterasfactorydefault,supplythepowertotheproductwithpressingthe(and1keysatthesametimeanditentersinitializationparameter.
Temperatureunit(/)isselectable.Whenchangingtemperatureunit,userinputrange,displayscale,outputscale,alarmSVareinitialized.Youshouldsettheparam-etersagainforyourpurpose.※Whenselectinganaloginput,temperatureunit[UNIT]
parameterisnotdisplayed.
Whenselectinganaloginput,selecttheunit(%,°C,°F,notdisplay)ofdisplayvalue.※Whennotdisplayingunit,setOFF anditturnsOFFall
indicators.※Whenselectingtemperaturesensorinput,thisparam-
eter[dUNT]isnotdisplayed.
Whenselectinganaloginput,youcansettheinputrangeforyourpurpose.Setlowlimitinputvalue[L-RG]andhighlimitinputvalue[H-RG]tolimittheinputrange.• Setconditions: Lowlimitinputvalue[L-RG]+20%F.S.<Highlimitinputvalue[H-RG]
Display scale [ Program mode : L-SC, H-SC ]Foranaloginput,thisfunctionistoset(-19999to19999)forparticularhigh/lowlimitvalueinordertodisplayhigh/lowlimitvalueofmeasurementinput.Ifmeasurementinputsare‘a’and‘b’andparticularvaluesare‘A’and‘B’,itwilldisplaya=A,b=Basbelowgraphs.
Displayscalefunctionisabletochangedisplayvalueformax./min.measuredinputbysettinghighlimitscale[H-SC]andlowlimitscale[L-SC]inprogrammode.※Ex)Sethigh/lowscalevalue(inputrangeis0to10V)
※Whenchanging input type,high/lowscale ischangedasfactorydefault.
• L-SC=)00
• H-SC=%00,1)00,1%00,`)00
• L-SC=1)00,H-SC=`)00
• L-SC=-%00,H-SC=%00
B
Displayvalue
Inputvalue
A
a b
BDisplayvalue
Inputvalue
A
a b
BDisplayvalue
Inputvalue
A
a b
Displayvalue
Inputvalue%00
0 10V
1)00
`)00
1%00
1)00
`)00
1%00
Displayvalue
Inputvalue0 10V
Mode Operation
0P Outputs4to20mAwithinanaloginputrange.
5POutputs3.2to20.8mAfor5%outoftheanaloginputrange.
10POutputs2.4to21.6mAfor10%outoftheanaloginputrange.
%00
1)00
1%00
Displayvalue
Inputvalue0 10V
-%00
CLR
NO YES
(
(
Pressthe(+1keysatthesametime.
Supplythepower.
Completesinitialization.
BDisplayvalue
Inputvalue
Aba
B
Displayvalue
Inputvalue
A
a b
B
Displayvalue
Inputvalue
Aba
Multi Indicator
B-19
A.Recorder
B. Indicator
C.Converter
D.Controller
E.Thyristorunit
F.Pressuretransmitter
G.Temp.transmitter
H.Accessories
KN-1000B
KN-2000WParameter Functions Graph Applications
LINOutputsasinputvalue
Display
Input
Y=AX+B Standardcharacteristics.Inputforlinearity.
ROOT
Outputstherooted(√)inputvalue
Display
Input
Y=0(X<0)
Y=A(X)+B(X≥0)
Usedformeasuringflowsbypressuresignal.
SQAR
Outputsthesquaredinputvalue
Display
Input
Y=A(X)2+B(X>0)
Y=-A(X)2+B(X<0)
Usedforoutputtingdifferentialpressurebyflowsignal.
TUF Referto‘Twounitfunction’
Transmission output scale [ Program mode : lOUT, hOUT ]
For4-20mAcurrentoutput,thisfunctionistosetthedis-playvaluefor4mA[lOUT]andthedisplayvaluefor20mA[hOUT].TheintervalbetweenlOUT andhOUTis10%F.S.Ifitisbelow10%,itisfixedas10%ofSV.
Decimal point [ Program mode: dP ]
Itisabletochangedecimalpointpositionforhigh/lowlimitscalevalue.Itchangesdecimalpointpositionofdisplayvalue.
※Relationamonginputrange,userinputrange,displayscale,andtransmissionscale
Thebelowfigureistheexamplefor4to20mA.
Input special function [ Program mode: InSF ]
Whenselectinganaloginput,thisfunctionistodisplaythecalculatedactualvaluebysquare,root(√),ortwounitfunction(TUF)asdisplayvalue.
Whenconnectingapressuresensor,compoundpressurewhichisbelowatmosphericpressure(0)isforvacuumasmmHgandwhichisatmosphericpressureoroveritisforpositivepressureaskg/cm2.Atmosphericpressureis0kg/cm2.Whenthisunitdoesnotdisplay0kg/cm2,youcancorrectzero-pointadjustmentfunction.Whenusingtwounitfunction,L-SC isfixedas-760.L-SC parameterisdisplayedbutyoucannotsetthis.YoucansetH-SC within0to19999range.
Ex)Whenpressurerangeis 760.0mmHgto3.000kg/cm2,andpressuretransmitteroutputs4-20mA,setthescaleasH-SC:3000,dP:)000.Thisunitdisplaysfor4mAinputas-76)0,andfor20mAinputas#000.
Two Unit Function [ Program mode: TUF ]
Input correction [ Program mode: IN-B ]
Thisfunctionistocorrecttheerroroccurringfromather-mocouple,aRTDoranaloginputoutofallowableerrorrangeofthisunit.Thisisalsoavailabletocorrecterrorwhenasensorcan-notcontactthesubjectpositionbycalculatingtheerrortemperature.Variabletemperaturesensorshaveaccuracylevel.Be-causehighaccuracytypeisexpansive,standardthermo-couplesaregenerallyused.Inthiscase,temperaturesensormayoccurerror.Byexecutingthisfunction,youcangetmoreaccuratetemperature.Whenexecutinginputcorrectionfunction,youshouldmeasuretheerrorfromasensoraccurately.Ifthemea-surederrorisnotcorrect,errormaybegreater.(IfInSF=TUF,IN-B asatmosphericpressureinputvaluenotasinputcorrectionfunction.RefertoTwounitfunc-tion.)Ex)Whenmeasuredtemperatureis4andactual
temperatureis0.SetIN-B as-4,andanddisplayvalueis0.
Display
Output
4mA
20mA
lOUT hOUTDisplay
Output
4mA
20mA
lOUT hOUT
※DisplayvalueandmAoutputvalueforSQAR:
※DisplayvalueandmAoutputvalueforROOT:
Displayvalue=()×(H-SC-L-SC)+L-SC(outputvalue)
Inputvalue-L-RG
H-RG- L-RG
Displayvalue=()×(H-SC-L-SC)+L-SC(outputvalue)
Inputvalue- L-RG
H-RG- L-RG
2
Display
Input
4mA 20mAInputrange
Userinputrange
Displayscale(displayvalue)
Transmissionoutputscale
L-RG=6 H-RG=16
L-SC=0 H-SC=1000LLLL HHHH
4mAtransmission
20mAtransmission
lOUT=100 hOUT=900
KN-2000W Series
B-20
Digital input [ Program mode: DI-T, DI-K ]
Bydigitalinputterminal[DI-T](no.6,7terminals)ordigitalinputkey[DI-K](D.IN3:4+3for3sec.),oneofthreefunctionsexecutesasthebelowtable.
Display color [ Program mode: CLOR/ C-AL ]
Thisfunctionistochangedisplaycolorforoccurringerror,operatingalarmautomatically.Usercancheckthestatusofthisunitdirectly.※Colorofmonitoringmode,programmodeisred.
٧٧ RUN mode and error display color [ Program mode: CLOR ]
Parameter Displaycolor
SV RUN Error
RED Red Red
GRN Green Green
YELO Yellow Yellow
R--G Red Green
G--R Green Red
٧٧ Alarm display color[ Program mode: C-AL ]
Alarm output for disconnecting input sensor [ Program mode: BURN ]
Whendisconnectinginputsensor,youcansetthestatusoftransmissionoutput.
Parameter SVTransmissionoutput(4-20mA)
Alarmoutput
BURN
ON 20mA+5%output HighlimitalarmON
LowlimitalarmOFF
OFF 4mA-5%output HighlimitalarmOFF
LowlimitalarmON
Lock [ Program mode: LOCK ]Itlimitstocheckparametersetvalueandtochangeit.
OFF LOC1 LOC2
Programmode
Monitoringmode
:Enabletocheck/set :Enabletocheck,disabletoset, :Disabletocheck
※InLOC2,onlyLOCK parameterdisplaysinprogrammode.
• Whenalarmiscleared,ortwoalarmsoperateatthesametime,thelatestalarm’scolorisapplied.
• Whenerroroccurs[HHHH,LLLL,BURN,ERR,ERR1]duringalarm,thesetcolorofCLOR isapplied.
Digital filter [ Program mode: MAvF ]Movingaveragedigitalfilterisabletostablydisplayandoutputthenoisefrominputlineandirregularsignalsassoftware.•Filtersetrange:01to16(Whensettingas01,digitalfilterfunctiondoesnotrun.)※Displaycycleissamewhenexecutingmovingaveragedigitalfilter.
Function Operaiton
AlRE Alarmclear
WhenalarmisONinRUNmode,itclearsalarmforcibly.(Itappliesonlyforalarmlatch,alarmlatchandstandbysequenceoptions.)Alarmclearoperatesonlywhenthevalueisoutofthealarmvaluerange.Afterclearingalarm,alarmoperatesitsoptionnormally.※Forthemodelwithoutalarmoutput(KN-20 W),thisparameterisnotdisplayed.
HOLDDisplayHOLD
Temporarilyindicatedvalueisstoppedinordertocheckindicatedvalueinunstableinput.
ZEROZero-pointadjustment
Setpresetdisplayvalueas0.Thisfunctionisrelatedwithinputcorrection[IN-B].Whenexecutingzeroadjustmentfunctionindisplayvalueas4,inputcorrectionvalue[IN-B]issetas-4automatically.
D4=S1+S2+S3+S4
4
D6=S3+S4+S5+S6
4
D8=S5+S6+S7+S8
4
D5=S2+S3+S4+S5
4
D7=S4+S5+S6+S7
4
D1=S1,D2=S2,D3=S3:Initialoperationbeforeaveraging4
Thisparameterisdisplayedonlyforthealarmoutputmodels(KN-22 W,KN24 W).• Thenumberofsetdigitissameasthenumberofalarmoutput.
[2alarmoutputs(KN-22 W)]S
[4alarmoutputs(KN-24 W)]S
• Setcolorforeachalarm.ItchangesasR→G→Y→Rinturn.
※Ex) S :Pressanyoneamongthe1,3,4keys.
S RUNmodecolorisgreen.
AL-4colorAL-3colorAL-2colorAL-1color
S
①AL-1isON,displayisgreen→yellow.②AL-2isON,displayisyellow→red.③AL-3isON,displayisred→green.④AL-4isON,displayisgreen→red.
S1
D1 D2 D3 D4 D5 D6 D7 D8
S2 S3
100ms
S4 S5 S6 S7 S8 S9
Sn:SamplingvalueDn:Displayvalue
Multi Indicator
B-21
A.Recorder
B. Indicator
C.Converter
D.Controller
E.Thyristorunit
F.Pressuretransmitter
G.Temp.transmitter
H.Accessories
KN-1000B
KN-2000W
Communication set [ Program mode: ADDR, BAUD ]
Communication write enable/disable [ Program mode: COmW ]
Youcansetcommunicationaddress[ADDR]andcommu-nicationspeed[BAUD]forRS485communication.
Youcansettoenable[EnA]ordisable[DIsA]orwritingparametersettingbyRS485communication.
RefertocommunicationmanualforRS485communication.Visitourwebsite(www.autonics.com)todownloadcommunicationmanualandsoftware[Integrateddevicemanagementprogram:DAQMaster].
Communication specifications
Communication manual
Item Specifications
Communicationmethod RS4852-wirehalfduplex
Communicationspeed(BPS) 9600,4800,2400,1200
Converter ConverterbuiltinRS232
Max.connections 32units
Communicationdistance
Max.1200m(within700mrecommended)
Protocol MODBUS1.1RTU
Parity None
StopBit 1Bit
Datalength 8Bit
Communications
Integrated device management program ( DAQMaster)
DAQMasteristheintegrateddevicemanagementprogramtosetparametersandmanagemonitoringdata.Visitourwebsite(www.autonics.com)todownloadusermanualandintegrateddevicemanagementprogram.
<DAQMasterscreen>
<Computerspecificationforusingsoftware>
Item Minimumrequirements
System IBMPCcompatiblecomputerwithIntelPentiumⅢorabove
Operatingsystem MicrosoftWindows98/NT/XP/Vista/7
Memory 256MBormore
Harddisk Morethan1GBoffreeharddiskspace
VGA 1024×768orhigherresolutiondisplay
Others RS-232serialport(9-pin),USBport
KN-2000W Series
B-22
※1. S :Pressanykeyamongthe1,3,4.※2.1:Movesdigits/4,3:ChangesSV.※3.Pressthe MODE keyafterchecking/changingSVineachparameter.Thevalueflashestwiceandissaved.Itmovestonextparameter.
※Afterenteringsettinggroup,pressthe MODE keyfor3sec.orthereisnoadditionalkeyoperationin30sec.,itreturnstoRUNmode.
※ :Thisparametermayormaynotappear,dependingontheotherparametersettings.
AL1 09(9
AL2 09(9
AL3 00)1
AL4 00)1
hPEK ----
lPEK ----
MODE
S
S
S
S
S
S
MODE
MODE
MODE
MODE
MODE
MODE
Alarm1value
Alarm2value
Alarm3value
Alarm4value
Highpeakvalue
Lowpeakvalue
※1 ※2
※3
Displayshigh/lowpeakvalue.※High/Lowpeakvalueisavailableonlytocheckandinitializeit. (Referto‘High/Lowpeakmonitoring’forinitialization.)※Initialhigh/lowpeakissavedafter2sec.fromsupplyingthepower.
※Displayedonlyforalarmoutputmodels.
Seteachalarmvalue;[AL-1toAL-4]inprogrammode.•Setrange:Temperaturesensorinput→withintemperaturerangeAnaloginput→L-SCtoH-SC※Whenalarmmode[AL-1toAL-4]inprogrammodeisnoalarm[AT)_]orsensorbreakalarm[SBa_],theseparametersarenotdisplayed.
※For2EAalarmoutputmodel(KN-22 W),AL3,AL4 arenotdisplayed.
RUN mode
MODEPress key.
Monitoring mode
Program mode
※1. S :Pressanykeyamongthe1,3,4.※2.1:Movesdigits/4,3:ChangesSV.※3.Pressthe MODE keyafterchecking/changingSVineachparameter.Thevalueflashestwiceandissaved.Itmovestonextparameter.
※Afterenteringsettinggroup,pressthe MODE keyfor3sec.orthereisnoadditionalkeyoperationin30sec.,itreturnstoRUNmode.
※ :Thisparametermayormaynotappear,dependingontheotherparametersettings.
IN-P aMA2S
MODE
UNIT ?CS
MODE
dUNT ?/OS
MODE
L-RG 0$00S
MODE
H-RG 2)00S
MODE
Selectinputtype.(Referto「Inputtypeandrange」.)
Selecttemperatureunit.
Selectfrontdisplayunit.
※Displayedonlywhenselectinganaloginputtype.
?C ?F
?/O ?COFF ?F
Setlowlimitofinputrange.•Setrange:withinanaloginputtyperange
Sethighlimitofinputrange.•Setrange:withinanaloginputtyperange
Inputtype
Temperatureunit
Lowlimitinputvalue
Frontdisplayunit
Highlimitinputvalue
※1 ※2
MODE ※3
※Displayedonlywhenselectingtemperaturesensorinputtype.
RUN mode
MODEPress keyfor3sec.
Multi Indicator
B-23
A.Recorder
B. Indicator
C.Converter
D.Controller
E.Thyristorunit
F.Pressuretransmitter
G.Temp.transmitter
H.Accessories
KN-1000B
KN-2000W
4mAoutputscalevalue
20mAoutputscalevalue
Inputandtransmissionoutputextension
AL1mode
AL2mode
AL3mode
AL4mode
EX.I0 SPS
MODE
AL-1 AT!AS
MODE
AL-2 AT!AS
MODE
lOUT 00)0S
MODE
AL-3 AT@AS
MODE
hOUT 10)0S
MODE
AL-4 AT@AS
MODE
※Displayedonlyfortransmissionoutputmodel.
※Displayedonlyforalarmoutputmodels.
Setoutputscalevaluefor4mA.•Setrange:Temperaturesensorinput→withintemperaturerange,Analoginput→L-SCtoH-SC
Setoutputscalevaluefor20mA.•Setrange:Temperaturesensorinput→withintemperaturerange,Analoginput→L-SCtoH-SC
Selectextensionrangeof4-20mAinputandtransmissionoutput.
S
MODE
MODE
MODE
MODE
MODE
Nextparameter
AL-1
AL-2
AL-3
AL-4
SetAL1toAL4alarmmodeandoption.
10PSP 0P
ALoutputhysteresis
Inputspecialfunction
Inputcorrection
InSF LINS
MODE
IN-B 0000S
MODE
A-HY 001S
MODE
Selectinputspecialfunction.
Setinputcorrectionvalue.•Setrange:-999to999
Setalarmoutputhysteresis.•Setrange:001to999
LIN SQARROOT TUF
dP )0MODE
L-SC 00)0MODE
H-SC 10)0MODE
S
S
S
Selectdecimalpointpositionofdisplayscalevalue.
)0 )000)00 0
Setlowlimitscalevalue.•Setrange:-19999to19999
Sethighlimitscalevalue.•Setrange:-19999to19999
Decimalpoint
Lowlimitscalevalue
Highlimitscalevalue
※Displayedonlywhenselectinganaloginputtype.
※Displayedonlywhenselectinganaloginputtype.
<Alarmmode> <Alarmoption>
AT!A
AT@A
SBa_
AT)_
AT!A
AT!B
AT!C
AT!D
※야 SVchangingmethodofAL-2toAL-4issameasAL-1’s.※For2EAalarmoutputmodel(KN-22 ٧W),AL3,AL4 arenotdisplayed.
※Noalarm[AT)_],sensorbreakalarm[SBa_]donothavealarmoption.※Setalarmvalue[AL1toAL4]inmonitoringmode.
※Whenalarmmode[AL-1toAL-4]inprogrammodeisnoalarm[AT)_]orsensorbreakalarm[SBa_],thisparameterisnotdisplayed.
※Displayedonlywhenselectinganaloginputtype.
KN-2000W Series
B-24
COmW EnAS
LOCK OFFS
ADDR 01S
BAUD (6KS
※DisplayedonlyforRS485communicationoutputmodel.
Setcommunicationaddress.•Setrange:01to99
Selectcommunicationspeed(baudrate).
Selectlockfunction.
Selectenable/disabletocommunicationwrite.(EnA:enabletowrite,DIsA:disabletowrite)
BURN ONS Selectoutputstatuswhensensordisconnection.
Sensorbreakalarmoutput
Communicationaddress
Communicationspeed
Communicationwrite
Lock
ON OFF
EnA DIsA
LOC1OFF LOC2
(6K @4K!2K1(2K $8K
Digitalinputterminal
Digitalinputkey
Displaycolor
Alarmdisplaycolor
CLOR REDS
DI-T HOLDS
DI-K HOLDS
C-AL RRRRS
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
Selectdigitalinputfunctionbyno.6and7.※Forthemodelwithoutalarmoutput(KN-20 ٧W),AlRE isnotdisplayed.
Selectdigitalinputfunctionbyfrontkeys.※Pressthe4,3keysfor3sec.atthesametimeanditexecutestheselectedfunction.※Forthemodelwithoutalarmoutput(KN-20 ٧W),AlRE isnotdisplayed.
SelectdisplaypartcolorforRUNmodeanderror.※Referto「Displaycolor」.
Selectdisplaypartcolorforalarm.※Referto「Displaycolor」.
ZEROHOLD AlRE
ZEROHOLD AlRE
RED GRN YELO R--G G--R
Digitalfilter
MAvF 04S
MODE
Setthenumberofmovingaveragedigitalfilters.
•Setrange:01to16
※Displayedonlyforalarmoutputmodels.
※Displayedonlyforalarm,transmissionoutputmodels.
Multi Indicator
B-25
A.Recorder
B. Indicator
C.Converter
D.Controller
E.Thyristorunit
F.Pressuretransmitter
G.Temp.transmitter
H.Accessories
KN-1000B
KN-2000W
Parameter Default Parameter Default Parameter Default Parameter Default
IN-P aMA2 lOUT 00)0 InSF LIN ADDR 01
UNIT ?C hOUT 10)0 IN-B 0000 BAUD (6K
dUNT ?/O ExI0 5P MAuF 04 COMW EnA
L-RG 0$00 AL-1 AT!A DI-T HOLD LOCK OFF
H-RG 2)00 AL-2 AT!A DI-K HOLD
dP )0 AL-3 AT@A CLOR RED
L-SC 00)0 AL-4 AT@A C-AL RRRR
H-SC 10)0 A-HY 001 BURN ON
Parameter Default Parameter Default Parameter Default
AL1 09(9 AL3 00)1 hPEK ----
AL2 09(9 AL4 00)1 lPEK ----
Caution for using
Proper usage
• Forconnectingthepower,useacrimpterminal(M3.5,min.7.2mm).
• Theconnectionofthisunitshouldbeseparatedfromthepowerlineandhighvoltagelineinordertopreventinductivenoise.
• Installapowerswitchoracircuitbreakertosupplyorcutoffthepower.
• Switchorcircuitbreakershouldbeinstallednearbyusersforconvenientcontrol.
• Donotusethisunitnearthehighfrequencyinstruments(highfrequencyweldingmachine&sewingmachine,largecapacitySCRcontroller).
• Whensupplyinginput,ifHHHHorLLLLisdisplayed,measuredinputmayhaveproblem.Turnoffthepowerandchecktheline.
• Installationenvironment. ①Itshallbeusedindoor. ②PollutionDegree2 ③Altitudemax.2,000m ④InstallationcategoryⅡ• Itmaycausemalfunctionifaboveinstructionsarenotfollowed.
Factory default
Program mode
Monitoring mode