KM 554e-20200110133908...Jan 15, 2020  · Chemical Analysis ** (Salts: -Cl , -Fl , +Na , SiO 44-)...

13

Transcript of KM 554e-20200110133908...Jan 15, 2020  · Chemical Analysis ** (Salts: -Cl , -Fl , +Na , SiO 44-)...

Page 1: KM 554e-20200110133908...Jan 15, 2020  · Chemical Analysis ** (Salts: -Cl , -Fl , +Na , SiO 44-) Results fall within acceptability limits of ASTM C795 ASTM C795 (C871) R-Value
Page 2: KM 554e-20200110133908...Jan 15, 2020  · Chemical Analysis ** (Salts: -Cl , -Fl , +Na , SiO 44-) Results fall within acceptability limits of ASTM C795 ASTM C795 (C871) R-Value
Page 3: KM 554e-20200110133908...Jan 15, 2020  · Chemical Analysis ** (Salts: -Cl , -Fl , +Na , SiO 44-) Results fall within acceptability limits of ASTM C795 ASTM C795 (C871) R-Value
Page 4: KM 554e-20200110133908...Jan 15, 2020  · Chemical Analysis ** (Salts: -Cl , -Fl , +Na , SiO 44-) Results fall within acceptability limits of ASTM C795 ASTM C795 (C871) R-Value
Page 5: KM 554e-20200110133908...Jan 15, 2020  · Chemical Analysis ** (Salts: -Cl , -Fl , +Na , SiO 44-) Results fall within acceptability limits of ASTM C795 ASTM C795 (C871) R-Value
Page 6: KM 554e-20200110133908...Jan 15, 2020  · Chemical Analysis ** (Salts: -Cl , -Fl , +Na , SiO 44-) Results fall within acceptability limits of ASTM C795 ASTM C795 (C871) R-Value
Page 7: KM 554e-20200110133908...Jan 15, 2020  · Chemical Analysis ** (Salts: -Cl , -Fl , +Na , SiO 44-) Results fall within acceptability limits of ASTM C795 ASTM C795 (C871) R-Value

 

 

 

RISE Engineering Pipe Insulation Bid Date: January 15, 2020 Facility: City of Providence-DOT Office Boiler room Location: 2 Capitol Hill, Providence RI 02903 GENERAL PROJECT DESCRIPTION

Insulate steam mains and headers, condensate line, receiver tank, domestic hot water lines and breeching where asbestos was abated.

Measure Details:

Insulate 155 lf of 8”, 7”, 6” and 4” steam main with 3” wall fiberglass with ASJ covering. Elbows to be covered with PVC covers with inserts. Total charge for this measure: $11,789

Insulate 48 lf of 2 1/2”, 2”, and 1 1/4” condensate line along the rear wall leading to the receiver

tank with 1 1/2” wall fiberglass with ASJ covering. Elbows to be covered with PVC covers with inserts. Total charge for this measure: $1,224

Insulate the 6’ x 32” receiver tank with 2.25”, ¾ # FSK fiberglass.

Total charge for this measure: $454

Insulate the 295 sf boiler breeching with 2” mineral wool Pipe and Tank wrap with FSK facing. Total charge for this measure: $5,671

Insulate 300 lf of 1 1/4” and 1” copper domestic hot water lines with 1” wall fiberglass with ASJ covering where accessible. Some areas will receive ½” wall insulation where space allows. Elbows to be covered with PVC covers with inserts. Total charge for this measure: $3,268

Total cost=$22,406  

Page 8: KM 554e-20200110133908...Jan 15, 2020  · Chemical Analysis ** (Salts: -Cl , -Fl , +Na , SiO 44-) Results fall within acceptability limits of ASTM C795 ASTM C795 (C871) R-Value
Page 9: KM 554e-20200110133908...Jan 15, 2020  · Chemical Analysis ** (Salts: -Cl , -Fl , +Na , SiO 44-) Results fall within acceptability limits of ASTM C795 ASTM C795 (C871) R-Value

06-10-16

Zeston 2000® Series White PVC Insulated Fitting Covers and Jacketing

Mechanical Insulations

MECH - 52

Features• Protect insulated or bare pipes• Meets most requirements for federal, state and local fire-safety codes• Accepted for commercial, institutional, industrial and residential

projects in all parts of the US• System is uncomplicated and easy to install• UV-resistant for outdoor applications• Long-lasting protection and an attractive finished appearance• Available with Hi-Lo Temp fiber glass inserts

Applications• Commercial, institutional and industrial applications

Construction• Covering and jacketing manufactured from high-impact, gloss white,

UV-resistant polyvinyl chloride jacketing

Application Recommendations• Wrap the Hi-Lo Temp fiber glass insert completely around the pipe

fitting without overly compressing it or leaving any voids• Ensure that the insulation insert covers all exposed surfaces• Install the Zeston PVC fitting cover over the pipe fitting and fiber glass

insert by securing the throat of the Zeston PVC insert using either serrated tacks, Perma-Weld adhesive or Zeston Z-Tape

• If applied in an outdoor setting or exposed to the sun, precautions should be taken to account for expansion joints

ZESTON 2000 SERIES WHITE PVC INSULATED FITTING COVERS AND JACKETING

Page 10: KM 554e-20200110133908...Jan 15, 2020  · Chemical Analysis ** (Salts: -Cl , -Fl , +Na , SiO 44-) Results fall within acceptability limits of ASTM C795 ASTM C795 (C871) R-Value

06-10-16

Zeston 2000® Series White PVC Insulated Fitting Covers and Jacketing

Mechanical Insulations

MECH - 52

P e r f o r m a n c e S P e c i f i c a t i o n S

Electrical Conductance Non-conductorElongation at Yield (MD), % 3.0Flame Spread 25 or less (up to 30 mil [0.8mm])Flexural Modulus, psi (kPa) 430,000 (2,964,750)Flexural Strength, psi (kPa) 11,000 (75,850)

Gardner – SPI Impact,in.lb./mil by Ductile Failure

10 mil (0.3 mm)1.315 mil (0.4 mm) 1.420 mil (0.5 mm) 1.530 mil (0.8 mm) 1.6

Smoke Developed 50 or less (up to 30 mil [0.8 mm])Specific Gravity 1.48Tensile Modulus, psi (kPa) 425,000 (2,930,270)Tensile Strength at Yield, psi (kPa) 6,000 (41,370)

S p e c i f i c a t i o n c o m p l i a n c e

ASTM D257 (Electrical surface resistance)D638 (Tensile strength)D790 (Flexural Strength)D792 (Density & specific gravity)D1784 (Specification for rigid PVC)D3679 (Specification for rigid PVC)E84 (Surface burning characteristics)E136 25/50 non-combustibility (fiber glass inserts)

Agriculture Canada Pass (Canada Department of Agriculture)Canada CGSB51-GP-53MCAN/ULC S102L-P*: Composition A, Type II, Grade GU

535E (Federal standard for PVC)1035A (US Army standard PVC)

New York City MEA #7-87 (Toxicity test)USDA US Department of Agriculture

c o m P r e S S e d t h e r m a l c o n d u c t i v i t y

Z e S t o n h i - l o t e m P i n S u l a t i o n i n S e r t S

Mean Temperature “K”°F °C BTU•in/(hr•ft2•°F) W/M•°C75 24 0.23 0.033150 66 0.27 0.039300 149 0.40 0.058

FOR ADDITIONAL INFORMATION CONSULT THE FULL PRODUCT MANUAL.The physical and chemical properties of PRODUCT listed herein represent typical, average values obtained in accordance with accepted test methods and are subject to normal manufacturing variations. They are supplied as technical service and are subject to change without notice. Numerical flame spread and smoke developed ratings are not intended to reflect hazards presented by these or any other materials under actual fire conditions. Check with the Regional Sales Office nearest you to assure current information. All Johns Manville products are sold subject to Johns Manville’s standard Terms and Conditions including Limited Warranty and Limitation of Remedy. For a copy of the Johns Manville standard Terms and Conditions, Limited warranty and Limitation of Remedy, and information on other Johns Manville thermal insulations and systems, call (800)-654-3103Limited Warranty and Limitation Remedy. For a copy of the Johns Manville standard Terms and Conditions, Limited Warranty and Limitation of Remedy, and information on other Johns Manville thermal insulations and systems, call (800) 654-3103.

Q u a l i f i c a t i o n S f o r u S e

Hot Systems• Use proper insulation thickness to ensure PVC covers are kept

below 150°F (66°C)• PVC covers should be kept away from contact with and/or exposure

to sources of direct or radiated heat• For fittings where operating temperatures exceed 250°F (121°C) or

where pipe insulation thickness is greater than 1½” (38mm), two or more layers of Hi-Lo Temp insulation inserts are required beneath the fitting cover (refer to MECH-261 Zeston Hi-Lo Temp Inserts)

Cold Systems• An approved vapor-barrier compatible with PVC must be applied

between pipe insulation and fitting cover and on fitting cover throat overlap seal. Please refer to Insulspec MECH-261 on jm.com

• For fittings where operating temperature is below 45°F (7°C) or where the pipe insulation thickness is greater than 1½ “ (38mm), two or more layers of Hi-Lo Temp insulation inserts are required beneath fitting cover (refer to MECH-261 Zeston Hi-Lo Temp Inserts)

Refrigerant Systems and Cold Systems In Severe Ambient Conditioning• Mitered pipe insulation segments, fabricated or pre-molded

insulation shapes may be used in lieu of Hi-Lo temp insulation inserts

• An intermediate vapor-barrier compatible with PVC is required to completely seaL the insulation prior to installing the Zeston 2000 PVC fitting cover

• Care should be taken to ensure the vapor barrier mastic is applied between the pipe insulation and the fitting cover and on the fitting cover throat overlap seam

Totally Sealed Systems (USDA Approval) • 20 or 30 mil (0.5 mm or 0.8mm) Zeston PVC jacketing should be

applied to pipe insulation in conjunction with Zeston PVC fitting covers

• Circumferential and longitudinal jacket and fitting cover seams should be sealed with Zeston Perma-Weld solvent welding adhesive

• Circumferential seams should be a minimum of 1” (25mm) overlap and longitudinal seams should be 1½”- 2” (38mm to 51mm) overlap

• Upon completion, all seams should visually be checked for seal and, if necessary, touched up

• Slip joints are periodically required between fixed supports and on continuous long runs of straight piping.

• To implement a slip joint, increase the circumferential overlap to 8” to 10” (203 mm to 254 mm) and apply a flexible white caulking in the overlap area to maintain a sealed system

• Refer to Zeston installation instructions CI-35 at www.jm.com

Page 11: KM 554e-20200110133908...Jan 15, 2020  · Chemical Analysis ** (Salts: -Cl , -Fl , +Na , SiO 44-) Results fall within acceptability limits of ASTM C795 ASTM C795 (C871) R-Value
Page 12: KM 554e-20200110133908...Jan 15, 2020  · Chemical Analysis ** (Salts: -Cl , -Fl , +Na , SiO 44-) Results fall within acceptability limits of ASTM C795 ASTM C795 (C871) R-Value
Page 13: KM 554e-20200110133908...Jan 15, 2020  · Chemical Analysis ** (Salts: -Cl , -Fl , +Na , SiO 44-) Results fall within acceptability limits of ASTM C795 ASTM C795 (C871) R-Value

PRODUCT DATA SHEET: ENERWRAP® MA 960NAIssued: 05-06-2014 Supersedes: 06-05-2012

Performance

Thermal conductivity

Maximum ServiceTemperature

Hot Surface Performance: 1200 °F- (650 °C)Non-Combustible

Linear Shrinkage: ≤ 2 % at 1200 °F- (650 °C)

ASTM C411 ASTM E136 / CAN4 S114

ASTM C356

Surface burning characteristicsFlame spread index = 0 ; Smoke development index = 0

ASTM E84 (UL 723)CAN/ULC S102

ASTM C177

Norms

ENERWRAP® MA 960NA Old name: ENERWRAP® 80

Product description & applicationENERWRAP® MA 960NA is a rolled and faced mineral wool (stone wool) insulation wrap/mat designed for high temperature industrial applications where flexibility is required.Product is ideal for large diameter piping, vessels, ducts and equipment subject to light mechanical loads.

Surface Burning Characteristics: UL Listed to Canadian standard CAN/ULC S102 ; UL Classified to UL 723

ROXUL®ProRox® - Industrial Insulation

Product properties in accordance with ASTM C553

NEWNAME

Tm (°F) 100 200 300 400 500 600 700

l (BTU.in/hr.ft².°F) 0.25 0.30 0.34 0.40 0.48 0.58 0.68

Tm (°C) 38 93 150 204 260 316 371

l (W/mK) 0.036 0.043 0.049 0.058 0.069 0.084 0.098

Reaction to fire

Actual Density = 5.68 lb/ft³ - (91 kg/m³)Nominal Density = 8.0 lb/ft3

ASTM 167Density

Stress Corrosion Cracking Tendency of Austenitic Stainless Steel = PassedCorrosion of Steel = Passed

ASTM C692ASTM C665

Corrosion resistance **

(Salts: Cl- , Fl- , Na+ , SiO44-) Results fall within acceptability limits of ASTM C795 ASTM C795 (C871)Chemical Analysis **

R-Value / inch @ 75 °FRSI value / 25.4mm @ 24 °C

4.2 hr.ft2.°F/BTU0.74 m2 K/W

ASTM C518 (C177)Thermal Resistance

< 1 % Weight ASTM C1104Water Absorption/Vapor Sorption

Complies with Type: VII ASTM C553Compliance

ROXUL offers a wide range of facings, dimensions and thicknesses. Please contact ROXUL for further information.

ROXUL INC.Milton, OntarioTel: 1-800-265-6878Tel: 905-878-8474Fax:1-800-991-0110Fax: 905-878-8077Email: [email protected]

NOTE: ** Provisions for lot testing may be requried,consult manufacturer.As ROXUL® Inc has no control over installation design and workmanship, accessory materials or application conditions, ROXUL® Inc. does not warranty theperformance or results of any installation containing ROXUL® Inc's products. ROXUL® Inc's overall liability and the remedies available are limited by the generalterms and conditions of sale. This warranty is in lieu of all other warranties and conditions expressed or implied, including the warranties of merchantability andfitness for a particular purpose.®/TM: US - owner Rockwool International A/S used under license; Canada - owner Roxul Inc.