KIDDE FIRE PROTECTION Vega Peer to Peer Networking.
-
Upload
victoria-black -
Category
Documents
-
view
237 -
download
2
Transcript of KIDDE FIRE PROTECTION Vega Peer to Peer Networking.
![Page 1: KIDDE FIRE PROTECTION Vega Peer to Peer Networking.](https://reader031.fdocuments.in/reader031/viewer/2022031821/56649ec85503460f94bd5201/html5/thumbnails/1.jpg)
KIDDE FIRE PROTECTION
Vega
Peer to Peer Networking
![Page 2: KIDDE FIRE PROTECTION Vega Peer to Peer Networking.](https://reader031.fdocuments.in/reader031/viewer/2022031821/56649ec85503460f94bd5201/html5/thumbnails/2.jpg)
Applications
• High rise buildings
• Multi-building complex
• Multi-loop applications
• Conventional system upgrade to analogue addressable
Vega - Peer to Peer Networking
![Page 3: KIDDE FIRE PROTECTION Vega Peer to Peer Networking.](https://reader031.fdocuments.in/reader031/viewer/2022031821/56649ec85503460f94bd5201/html5/thumbnails/3.jpg)
Benefits
• Reduced installation costs
• Distributed intelligence
• Remote indication & control
• Distributed risk complete with autonomous operation
Vega - Peer to Peer Networking
![Page 4: KIDDE FIRE PROTECTION Vega Peer to Peer Networking.](https://reader031.fdocuments.in/reader031/viewer/2022031821/56649ec85503460f94bd5201/html5/thumbnails/4.jpg)
Vega - Peer to Peer Networking
48
![Page 5: KIDDE FIRE PROTECTION Vega Peer to Peer Networking.](https://reader031.fdocuments.in/reader031/viewer/2022031821/56649ec85503460f94bd5201/html5/thumbnails/5.jpg)
Vega - Peer to Peer Networking
• Shared zone/plant principle - Zone/plant to group programming across network
• System configuration from 2 to 48 panels
• Support for Vega options: repeaters & motherboards
• Up to 2km between nodes
![Page 6: KIDDE FIRE PROTECTION Vega Peer to Peer Networking.](https://reader031.fdocuments.in/reader031/viewer/2022031821/56649ec85503460f94bd5201/html5/thumbnails/6.jpg)
Vega - Peer to Peer Networking
• Zone to group programming across the network
• Latching & non-latching alarms
• 512 event log entries local & network
• Zone isolations across network
![Page 7: KIDDE FIRE PROTECTION Vega Peer to Peer Networking.](https://reader031.fdocuments.in/reader031/viewer/2022031821/56649ec85503460f94bd5201/html5/thumbnails/7.jpg)
Vega - Peer to Peer NetworkingNetwork information:
• RS 422 communications
• Twin twisted pair cable
• Up to 2km between nodes
• Reliable & proven communications
![Page 8: KIDDE FIRE PROTECTION Vega Peer to Peer Networking.](https://reader031.fdocuments.in/reader031/viewer/2022031821/56649ec85503460f94bd5201/html5/thumbnails/8.jpg)
Vega - Peer to Peer Networking
• System configuration via Viper or via the Membrane
• Selectable options for unique configurations per system
• Selectable options for priority level transmit & receive
![Page 9: KIDDE FIRE PROTECTION Vega Peer to Peer Networking.](https://reader031.fdocuments.in/reader031/viewer/2022031821/56649ec85503460f94bd5201/html5/thumbnails/9.jpg)
Vega - Peer to Peer Networking
Configuration options:
• Number Attached Panels
Selectable in Viper, each panel must be programmed
with the correct number of network panels
![Page 10: KIDDE FIRE PROTECTION Vega Peer to Peer Networking.](https://reader031.fdocuments.in/reader031/viewer/2022031821/56649ec85503460f94bd5201/html5/thumbnails/10.jpg)
Vega - Peer to Peer Networking
Configuration options:
• Display & Broadcast Alarms
If set to No, the panel will inhibit the transmission &
receipt of all network alarms
![Page 11: KIDDE FIRE PROTECTION Vega Peer to Peer Networking.](https://reader031.fdocuments.in/reader031/viewer/2022031821/56649ec85503460f94bd5201/html5/thumbnails/11.jpg)
Vega - Peer to Peer Networking
Configuration options:
• Global Evacuate
If set to Yes, the panel will transmit locally generated
evacuate signals & receive evacuate signals from the
network
![Page 12: KIDDE FIRE PROTECTION Vega Peer to Peer Networking.](https://reader031.fdocuments.in/reader031/viewer/2022031821/56649ec85503460f94bd5201/html5/thumbnails/12.jpg)
Vega - Peer to Peer Networking
Configuration options:
• Act on T1 / T2
If set to Yes, the panel will shall respond to any network
timer acknowledge signals
![Page 13: KIDDE FIRE PROTECTION Vega Peer to Peer Networking.](https://reader031.fdocuments.in/reader031/viewer/2022031821/56649ec85503460f94bd5201/html5/thumbnails/13.jpg)
Vega - Peer to Peer Networking
Configuration options:
• Global Silence / Reset
If set to Yes, the panel will transmit & receive all
silence & reset commands
![Page 14: KIDDE FIRE PROTECTION Vega Peer to Peer Networking.](https://reader031.fdocuments.in/reader031/viewer/2022031821/56649ec85503460f94bd5201/html5/thumbnails/14.jpg)
Vega - Peer to Peer Networking
Configuration options:
• Global Output Control
If set to Yes, the panel will respond to & transmit
all network commands relating to output control
![Page 15: KIDDE FIRE PROTECTION Vega Peer to Peer Networking.](https://reader031.fdocuments.in/reader031/viewer/2022031821/56649ec85503460f94bd5201/html5/thumbnails/15.jpg)
Configuration Options:
• Panel of origin S/R override
• Selection of this option allows a network panel to silence and reset the panel of origin
Vega - Peer to Peer Networking
![Page 16: KIDDE FIRE PROTECTION Vega Peer to Peer Networking.](https://reader031.fdocuments.in/reader031/viewer/2022031821/56649ec85503460f94bd5201/html5/thumbnails/16.jpg)
Vega - Peer to Peer Networking
Priority Text Tx Rx0 Evac Y Y1 Fire Y Y2 Alert N N3 Pre-alarm N N4 Fault N N
Transmit / Receive Options
![Page 17: KIDDE FIRE PROTECTION Vega Peer to Peer Networking.](https://reader031.fdocuments.in/reader031/viewer/2022031821/56649ec85503460f94bd5201/html5/thumbnails/17.jpg)
Vega - Peer to Peer Networking
Priority Text Tx Rx5 Unassigned N N6 Unassigned N N7 Unassigned N N8 Unassigned N N9 Unassigned N N
Transmit / Receive Options
![Page 18: KIDDE FIRE PROTECTION Vega Peer to Peer Networking.](https://reader031.fdocuments.in/reader031/viewer/2022031821/56649ec85503460f94bd5201/html5/thumbnails/18.jpg)
Vega - Peer to Peer Networking
Connection Details
Panel 01 Panel 02 Panel 02 Panel 03Talk out (+) (+) Listen in Listen out (+) (+) Listen inTalk out (-) (-) Listen in Listen out (-) (-) Listen inListen in (+) (+) Talk out Talk in (+) (+) Talk outListen in (-) (-) Talk out Talk in (-) (-) Talk out
![Page 19: KIDDE FIRE PROTECTION Vega Peer to Peer Networking.](https://reader031.fdocuments.in/reader031/viewer/2022031821/56649ec85503460f94bd5201/html5/thumbnails/19.jpg)
Vega Peer to PeerPanel of Origin
FIRETotal 01
Access Level 1
1st Z001 Ground Floor East Wing
Operate to list devices
![Page 20: KIDDE FIRE PROTECTION Vega Peer to Peer Networking.](https://reader031.fdocuments.in/reader031/viewer/2022031821/56649ec85503460f94bd5201/html5/thumbnails/20.jpg)
Vega Peer to PeerNetwork Panel
FIRETotal 01
Access Level 1
1st Z001 Ground Floor East Wing
Operate to list devices
Network Event
![Page 21: KIDDE FIRE PROTECTION Vega Peer to Peer Networking.](https://reader031.fdocuments.in/reader031/viewer/2022031821/56649ec85503460f94bd5201/html5/thumbnails/21.jpg)
Vega Peer to PeerPanel of Origin
FIRETotal 01
1st Z001 Ground Floor East Wing
Dev 01:001.1 Outside room 101
Panel 01 Accommodation on block #1
![Page 22: KIDDE FIRE PROTECTION Vega Peer to Peer Networking.](https://reader031.fdocuments.in/reader031/viewer/2022031821/56649ec85503460f94bd5201/html5/thumbnails/22.jpg)
Vega Peer to PeerNetwork Panel
FIRETotal 01
1st Z001 Ground Floor East Wing
Break glass outside room 101
Loop 01 Dev 001.1 Zone 001 tot 001/001
![Page 23: KIDDE FIRE PROTECTION Vega Peer to Peer Networking.](https://reader031.fdocuments.in/reader031/viewer/2022031821/56649ec85503460f94bd5201/html5/thumbnails/23.jpg)
Vega Peer to PeerPanel of Origin
EVACUATE Access level 3
![Page 24: KIDDE FIRE PROTECTION Vega Peer to Peer Networking.](https://reader031.fdocuments.in/reader031/viewer/2022031821/56649ec85503460f94bd5201/html5/thumbnails/24.jpg)
Vega Peer to PeerNetwork Panel
REMOTE EVACUATE Access level 1
![Page 25: KIDDE FIRE PROTECTION Vega Peer to Peer Networking.](https://reader031.fdocuments.in/reader031/viewer/2022031821/56649ec85503460f94bd5201/html5/thumbnails/25.jpg)
Vega Peer to PeerPanel of Origin
FAULTTotal 01
Zone Z001 Ground Floor East Wing
Optical Room G121 Switch room 02
Loop 01 Dev 008.1 Zone 001 tot 001/001
Access level 1
![Page 26: KIDDE FIRE PROTECTION Vega Peer to Peer Networking.](https://reader031.fdocuments.in/reader031/viewer/2022031821/56649ec85503460f94bd5201/html5/thumbnails/26.jpg)
Vega Peer to PeerNetwork Panel
FAULTTotal 01
Zone Z001 Ground Floor East Wing
Device 01:998.1 Room G121 Switch room 02
Panel 01 Accommodation block #1
Access level 1
![Page 27: KIDDE FIRE PROTECTION Vega Peer to Peer Networking.](https://reader031.fdocuments.in/reader031/viewer/2022031821/56649ec85503460f94bd5201/html5/thumbnails/27.jpg)
Vega Peer to PeerEvent Log - Network Event
Access level 3 List event logEvent 007 Network eventFire Priority 1Panel 01 Accommodation block #1Zone 001 Ground floor east wingDevice 01:001.1 Room G121 Switch room11:38am Monday 14 Aug 2000 to scroll, + to quit
![Page 28: KIDDE FIRE PROTECTION Vega Peer to Peer Networking.](https://reader031.fdocuments.in/reader031/viewer/2022031821/56649ec85503460f94bd5201/html5/thumbnails/28.jpg)
Vega Peer to PeerEvent Log - Local Event
Access level 3 List event logEvent 003 Network eventFire Priority 1Zone 003 Second floor east wingD001.1 Loop 01Break glass Central staircase11:39am Monday 14 Aug 2000 to scroll, + to quit
![Page 29: KIDDE FIRE PROTECTION Vega Peer to Peer Networking.](https://reader031.fdocuments.in/reader031/viewer/2022031821/56649ec85503460f94bd5201/html5/thumbnails/29.jpg)
Vega Peer to Peer - Example #1
SPECIFICATION
1. Panel 3 manual evacuate sounders constant, panels 2 & 4 sounders pulsed panels 1 & 5 silent.
2. Silence alarms & reset from panel 4.
3. Fault on panel 5 signalled locally & to panel 1 only.
4. Pre-alarm on panel 4 signalled locally & to panel 1 only.
5. Pre-alarm on panel 3 signalled locally & to panel 1 only.
1 2 3 4 5
![Page 30: KIDDE FIRE PROTECTION Vega Peer to Peer Networking.](https://reader031.fdocuments.in/reader031/viewer/2022031821/56649ec85503460f94bd5201/html5/thumbnails/30.jpg)
Vega Peer to Peer - Example #2
SPECIFICATION
1. Panel of origin sounders constant network panels pulsed with 2 min timer to evacuate.
2. Output to operate in each panel to shutdown the air conditioning.
3. Network panels to have ability to silence own sounders only.
1 2 3
![Page 31: KIDDE FIRE PROTECTION Vega Peer to Peer Networking.](https://reader031.fdocuments.in/reader031/viewer/2022031821/56649ec85503460f94bd5201/html5/thumbnails/31.jpg)
Vega Peer to Peer - Example #3
SPECIFICATION
1. Alarm On Panel 3 T1, 60s T2 180s, after ex area of T2 panel 3 sounders evacuate panels 2 & 4 sounders pulse for 180s & panels 1 & 5 silent.
2. After 180s panels 2 & 4 evacuate & panels 1 & 5 pulse for 180s then evacuate.
1 2 3 4 5