Kidde co2 product manual 050128

299

Click here to load reader

Transcript of Kidde co2 product manual 050128

Page 1: Kidde co2 product manual 050128

High PressureCarbon Dioxide

PRODUCT MANUAL

Contents:

1. Specification

2. Data sheets

3. Design manual

4. Installation, commissioning & maintenance manual

5. Software manual

6. Weight monitoring system

7. Direct Acting Solenoid

8. Owners Manual

9. Approvals

10. Information bulletins

Page 2: Kidde co2 product manual 050128

1

High PressureCarbon DioxideFire Protection Equipment

SPECIFICATIONS FORKIDDE CARBON DIOXIDEFIRE SUPPRESSION

December 2004

Page 3: Kidde co2 product manual 050128

2

PROPRIETARY RIGHTS NOTICE

This document and the information that it contains are the property of Kidde Fire Protection. Rights toduplicate or otherwise copy this document and rights to disclose the document and the information thatit contains to others and the right to use the information contained therein may be acquired only by writtenpermission signed by a duly authorised officer of Kidde Fire Protection.

© Copyright Kidde Fire Protection Services Ltd

Page 4: Kidde co2 product manual 050128

3

SPECIFICATION FOR KIDDE CARBON DIOXIDE FIRE SUPPRESSION

1.0 General Description

1.1 This specification defines the requirements for a Kidde carbon dioxide fire suppression system. Itshall be used as a standard for equipment, installation and acceptance testing.

2.0 Plans and Specifications

2.1 The carbon dioxide system(s) shall be manufactured by Kidde Fire Protection, Thame Park Road,Thame, Oxfordshire. OX9 3RT. UK

Major components of the detection and extinguishing control system, valves, cylinders, releasingdevices and nozzles shall be supplied by one manufacturer.

2.2 Major components of the carbon dioxide hardware shall be Factory Mutual approved.

2.3 To ensure system effectiveness, the contractor shall design, install and test the equipment inaccordance with either NFPA 12 or BS 5306, pt 4.

2.4 In addition to this specification, drawings shall be provided showing the general arrangement ofequipment within the protected areas. The contractor shall also provide a hazard analysis of theindividual risk areas.

3.0 Standards, Approvals and Quality Assurance

3.1 The carbon dioxide system shall be designed, installed and tested in accordance with BS 5306pt4 or NFPA 12, as defined by the client or their insurers. All equipment shall be procured from asingle manufacturer operating a quality scheme to : BS EN ISO 9001:2000.

4.0 Proposals and Submittals

4.1 The contractor shall supply manufacturers sales literature, data sheets and technical informationfor each major component of the system.

4.2 The contractor shall submit the following with their proposal:

4.2.1 Evidence of their qualifications (e.g. LPS 1204) to design, install, test, service and rechargethe manufacturers equipment AS APPROVED BY Kidde.

4.2.2 A complete bill of materials and description of the proposed installation including themanufacturers part number for each major item of equipment.

4.2.3 Evidence of their ability to supply spare parts to maintain the system.

4.3 Upon award of a contract the contractor shall supply the following:

4.3.1 Detailed scaled plans/drawings of the proposed system showing all items of equipment,routing of all pipes and cables. Flow calculations shall be shown detailing pipe size, nozzle sizeflow rate and terminal pressure.

Page 5: Kidde co2 product manual 050128

4

This information shall be generated by a suitable software package from the equipmentmanufacturer.

Care should be taken in locating the extinguishing agent containers as close as possible to thehazard to minimise the time for the agent to reach the fire.

4.3.2 Electrical system schematics in accordance with the relevant standard showing safetyinterlocks and a description of the sequence of operation.

4.3.3 Full sets of drawings and technical submittals, as required, shall be submitted to the clientand the consultant for approval prior to installation.

5.0 General Requirements

5.1 The carbon dioxide system shall be designed, engineered and installed for the proper protection ofthe hazard area(s). All major components shall be supplied by Kidde Fire Protection.

5.2 The design, installation and testing shall be in accordance with: BS5306 pt 4, NFPA 12 or FactoryMutual standards as appropriate.

In addition, the detection and alarm system shall be designed and installed to the appropriatestandard.

5.3 All major components shall be from one major manufacturer and the carbon dioxide componentsshall be Factory Mutual approved.

5.4 Release of the carbon dioxide system shall be possible by electrical solenoid attached to a systemcontrol head operating together to release a pilot nitrogen supply.

The nitrogen pilot gas shall be capable of operating up to 36 Klem valve actuators.

The control head shall also have facilities for manual release locally and remotely by mechanicalpull cable. As an option the control head shall have integral switches to indicate :

Operated - Control head fired.Isolated - Control head isolating pin inserted.

5.5 The system discharge time shall be designed in accordance with the design code selected for theproject. Particular attention shall be given to determining the classification of the hazard andprotection method employed.

5.6 The carbon dioxide storage cylinders and valves shall be “π“marked in accordance with EuropeanTPED Legislation 99/36/EC. Each cylinder shall be fitted with a Kidde Klem servo assisted valve.The valves shall be fitted with a safety burst disc designed to operate at 190 bar. The cylindershall be painted red. The cylinder assembly shall be Factory Mutual approved.

5.7 Where multiple cylinders are required for one or more hazard areas a common manifold shall beused. To prevent appreciable loss of gas, in the case of a cylinder being removed and the systemdischarging, an approved check valve shall be fitted to prevent loss of gas. Each cylindersupplying a common manifold shall be of a common size and fill.

5.8 Where more than one risk is protected from a bank of cylinders, consideration shall be given tosupplying a reserve supply of gas suitable to protect the largest risk.

The reserve bank shall be connected to the same manifold as the primary set using Factory

Page 6: Kidde co2 product manual 050128

5

Mutual approved check valves.

5.9 System piping shall be in accordance with the requirements of BS 5306 pt 4 (NFPA 12, ifapplicable).

5.10 Discharge nozzles shall be selected from the range of Kidde Fire Protection Factory MutualApproved designs and shall be suitably sized for the flow rates required.

5.11 System design shall be verified using the Kidde Fire Protection CO2 calculation program. A fullprint out shall be submitted for approval.

6.0 System Components

6.1 Cylinders - shall be, filled with 45 kg of carbon dioxide and fitted with the Kidde Klem valve. Theassembly shall be Factory Mutual approved. Valves shall be both proof tested and leak tested aspart of the manufacturing process.

6.2 Valve actuator (K62341) - this is the valve operating device and is attached to the valve by a 'U'shaped securing pin. The actuators can be removed for system testing without operating thecylinder valve with the associated risks of losing gas. The actuator is operated by pilot gaspressure or manually by a lever. The actuator shall be FM (Factory Mutual) approved.

6.3 Copper loop K21578 - provides a solid connection between the Klem valve and manifold checkvalve. The copper loop shall be Factory Mutual approved.

6.4 Flexible loop K97112 - an alternative flexible connection between the Klem valve and manifoldcheck valve.

6.5 Pilot loops K93433 and K93434 - high pressure flexible tube used to connect between the pilotgas supply and cylinder valve actuators. Pilot loops shall be tested to 210 bar (3000 PSI).

6.6 Pilot vent K24051 - this device is a safety feature designed to slowly relieve pilot gas pressurefollowing the main CO2 discharge.

6.7 Manifolds - shall be manufactured from schedule 80 pipe , galvanised and tested to 120 bar (2000PSI). Manifolds shall be FM approved and available in the following sizes for 2,3,4,5 cylinder(s) 1"nominal bore or 1¼" nominal bore schedule 80 pipe.

6.8 Cylinder racking - shall be formed from steel components designed specifically for supporting CO2cylinders during a discharge. Where double rows of cylinders are used a wooden central spacershall be used. Racking shall be supplied in modules of 2 or 3 cylinder sets. Two sets of rackingshall be used for each bank of cylinders.

6.9 Control heads K62303 and 62304 - provide the electro/mechanical interface between thedetection control panel and CO2 extinguishing hardware. The control head together with the pilotcylinder K62462, solenoid K62422B and wall mount K62487, forms the system actuator andprovides the pilot gas supply to operate the main cylinder bank. Operation of the control head maybe achieved electrically, pneumatically or mechanically by remote pull cable.

6.10 Push to fire button K62412 - provides direct manual control to fire the CO2 cylinder bank from thesystems actuator.

6.11 Safety pin K62401 - this fits into the control head to reset the device following operation. It alsoprovides an isolation facility when left in position. Remote indication of the isolated condition isavailable via contacts within the control head.

A blanking plug shall be used to prevent ingress of dirt into the control head when the safety pin isnot in situ.

Page 7: Kidde co2 product manual 050128

6

6.12 Manual release interface K62478 - allows remote release of the control head by means of a pullbox K1114 and phosphor bronze pre - stretched cable K9002 . To allow easy change of directioncorner pulleys K1122 shall be used. The cable shall be run in ½" o.d. galvanised conduit formechanical protection.

6.13 Pressure operated direction valves K24175 - (typical) - This is a 1¼" nominal bore valve and shallbe used to control the flow of carbon dioxide to the specific hazard in a system designed to protectmultiple risks from a common bank of cylinders. The valve shall be capable of opening under fullCO2 pressure. A manual lever shall be supplied for emergency control.

The valve shall be Factory Mutual approved. A switch shall be fitted to the valve where indicationthat the valve is open is required (e.g. K24630).

(P.O.D. valves may be provided in sizes: ¾", 1", 1¼", 1½", 2", 3", and 4").

6.14 Safety outlet K 921 - shall be used where gas may be trapped between two closed valves toprevent a dangerous rupture of the pipework e.g. when directional valves or isolating valves areused.

6.15 Pressure switch K60218 - shall be used to provide electrical contacts rated at 10amp. To providethe following facilities:

• Plant shut down• Remote alarm signalling• Discharged indication• Gas in manifold - should direction valve not open.

(The switch shall be Factory Mutual approved).

6.16 Pressure trip K17554 - shall be used to automatically release weight operated dampers, fuelvalves etc upon CO2 discharge. The pressure trip shall be Factory Mutual approved.

6.17 CO2 siren K18307 - shall be used to give audible warning of impending CO2 discharge prior to themain direction valve opening.

6.18 CO2 discharge delay K23650/30 - shall be used in conjunction with the siren to give a 30 secondpre-alarm to allow safe evacuation of a CO2 protected space. The discharge delay shall beFactory Mutual approved.

6.19 Time delay by-pass K60736 - shall allow emergency manual control of the CO2 discharge, by-passing the 30 second delay.

6.20 Odouriser assembly K62586 - shall be used to introduce a pungent lemon smell into a protectedhazard area upon operation of the CO2 extinguishing system. It shall be used in conjunction with acheck valve K22152.

6.21 Continuous weight monitoring unit E8731-402 shall be used to monitor the CO2 cylinders forweight loss. Should a cylinder lose 5% - 10 % of its weight then this device shall automaticallysignal a fault condition to the system control panel via a micro switch.

7.0 System Design

7.1 For total flooding applications care shall be taken to ensure that the room is reasonably gas tightwith all ventilation shut down. Failing this, adequate provision shall be made for leakagecompensation in accordance with the design standard.

Page 8: Kidde co2 product manual 050128

7

7.2 All doors or windows which may be open shall be arranged to close automatically upon CO2discharge to prevent undue loss of gas.

7.3 The carbon dioxide system design shall be based upon accurate drawings of the hazard or in theabsence of drawings a detailed site survey. The hazard analysis shall define the designconcentration used and temperature applicable.

7.4 Warning signs shall be fitted to all appropriate doors into the hazard area and any areas whereCO2 may build up and form a hazardous concentration.

7.5 All equipment shall be installed to the manufacturer's manuals and due consideration for serviceand maintenance of the system shall be given.

7.6 The system shall meet the requirements of either BS5306 pt 4 or NFPA 12 as determined by theclient/consultant or their insurers.

8.0 Equipment Manufacturer

The system components, design manuals and flow calculation programme shall be provided by:Kidde Fire Protection, Thame Park Road, Thame, Oxfordshire, OX9 3RT. UK

Page 9: Kidde co2 product manual 050128

High PressureCarbon DioxideFire Protection Equipment

CO2 DATA SHEETS

Page 10: Kidde co2 product manual 050128

CO2 DATA SHEETS

CO2 Nozzle ........................................................................................................ 418ACheck valve assy ..................................................................................................426Pressure trip, typical installation ...................................................................811-500045kg cylinder & klem valve assy...................................................................811-90046.8kg cylinder & klem valve assy.......................................................... 811-9004(6.8)22.7kg cylinder & klem valve assy...................................................... 811-9004(22.7)¾” Safety Outlet ...........................................................................................811-9016Multi-container racking .................................................................................811-90201” (25mm) bore, cylinder check, valve manifold ...........................................811-902211/4” (32mm) bore, cylinder check, valve manifold ......................................811-9023Flexible loop .................................................................................................811-9026Valve actuator (pneumatic/manual)..............................................................811 9031Lever actuator link ........................................................................................811-9032Cable clamp assy .........................................................................................811-9033Klem valve....................................................................................................811-9038Pilot loops.....................................................................................................811-9040Pilot bleed.................................................................................................. 811-9040A¾” P.O.D. valve ............................................................................................811-9067¾” P.O.D. valve c/w indicator switch ............................................................811-90681” P.O.D. valves ...........................................................................................811-90711” P.O.D. valve c/w indicator switch .............................................................811-907211/4” P.O.D. valve ........................................................................................811-907511/4” P.O.D. valve c/w indicator switch ........................................................811-907611/2”” P.O.D. ................................................................................................811-907911/2” P.O.D. valve c/w indicator switch ........................................................811-90802” P.O.D. ......................................................................................................811-90832” P.O.D. valve c/w indicator switch .............................................................811-90843”, 4” & 6” P.O.D. valves ..............................................................................811-9090CO2 Discharge delay unit .............................................................................811-9112Universal pressure switch assy ....................................................................811-9119

Page 11: Kidde co2 product manual 050128

Pressure Trip................................................................................................811-9123Nozzle, CO2, flanged horn............................................................................811-9139Nozzle, CO2, with horn .................................................................................811-9148Nozzle, CO2, & duct adaptor ........................................................................811-9151Manual Pull Box assy ...................................................................................811-9220Manual Pull box instruction plate..................................................................811-9225CO2 door plate .............................................................................................811-9237Control head options ....................................................................................823-9250Electric control head.....................................................................................823-9521Flameproof solenoid................................................................................. 823-9522/AStandard solenoid .................................................................................... 823-9522/BPneumatic diaphragm .............................................................................. 823-9522/CSafety & Reset pin, Manual release .............................................................823-9523Pilot valve & cylinder assy......................................................................... 823-9524AControl head bracket ................................................................................. 823-9524BMounting bracket - control head (FM) ....................................................... 823-9524CTypical arrangement, 3 cylinders..................................................................841-5025Typical arrangement, including manual pull .................................................841-5027Pilot tube connections to inlet of P.O.D. valves ............................................841-5036

Page 12: Kidde co2 product manual 050128
Page 13: Kidde co2 product manual 050128
Page 14: Kidde co2 product manual 050128
Page 15: Kidde co2 product manual 050128
Page 16: Kidde co2 product manual 050128
Page 17: Kidde co2 product manual 050128
Page 18: Kidde co2 product manual 050128
Page 19: Kidde co2 product manual 050128
Page 20: Kidde co2 product manual 050128
Page 21: Kidde co2 product manual 050128
Page 22: Kidde co2 product manual 050128
Page 23: Kidde co2 product manual 050128
Page 24: Kidde co2 product manual 050128
Page 25: Kidde co2 product manual 050128
Page 26: Kidde co2 product manual 050128
Page 27: Kidde co2 product manual 050128
Page 28: Kidde co2 product manual 050128
Page 29: Kidde co2 product manual 050128
Page 30: Kidde co2 product manual 050128
Page 31: Kidde co2 product manual 050128
Page 32: Kidde co2 product manual 050128
Page 33: Kidde co2 product manual 050128
Page 34: Kidde co2 product manual 050128
Page 35: Kidde co2 product manual 050128
Page 36: Kidde co2 product manual 050128
Page 37: Kidde co2 product manual 050128
Page 38: Kidde co2 product manual 050128
Page 39: Kidde co2 product manual 050128
Page 40: Kidde co2 product manual 050128
Page 41: Kidde co2 product manual 050128
Page 42: Kidde co2 product manual 050128
Page 43: Kidde co2 product manual 050128
Page 44: Kidde co2 product manual 050128
Page 45: Kidde co2 product manual 050128
Page 46: Kidde co2 product manual 050128
Page 47: Kidde co2 product manual 050128
Page 48: Kidde co2 product manual 050128
Page 49: Kidde co2 product manual 050128
Page 50: Kidde co2 product manual 050128
Page 51: Kidde co2 product manual 050128
Page 52: Kidde co2 product manual 050128
Page 53: Kidde co2 product manual 050128
Page 54: Kidde co2 product manual 050128
Page 55: Kidde co2 product manual 050128
Page 56: Kidde co2 product manual 050128
Page 57: Kidde co2 product manual 050128
Page 58: Kidde co2 product manual 050128
Page 59: Kidde co2 product manual 050128
Page 60: Kidde co2 product manual 050128
Page 61: Kidde co2 product manual 050128
Page 62: Kidde co2 product manual 050128
Page 63: Kidde co2 product manual 050128

i Manual No 59812-401

High PressureCarbon DioxideFire Protection Equipment

DESIGN MANUAL

Issue 5 December 2004 Manual No 59812-401

Page 64: Kidde co2 product manual 050128

ii Manual No 59812-401

PROPRIETARY RIGHTS NOTICE

This document and the information that it contains are the property of Kidde Fire Protection. Rights toduplicate or otherwise copy this document and rights to disclose the document and the informationthat it contains to others and the right to use the information contained therein may be acquired onlyby written permission signed by a duly authorised officer of Kidde Fire Protection.

© Copyright Kidde Fire Protection Services Ltd

Page 65: Kidde co2 product manual 050128

iii Manual No 59812-401

TABLE OF CONTENTSChapter Page

INTRODUCTION ..................................................................................................11 TOTAL FLOODING SYSTEMS....................................................................2

1.1 EXAMPLES OF HAZARDS..................................................................21.2 TYPE OF FIRES ..................................................................................21.3 WHERE CO2 IS NOT EFFECTIVE ......................................................2

2 CO2 REQUIREMENTS FOR SURFACE FIRES...........................................32.1 BASIC QUANTITY ...............................................................................32.2 UNCLOSEABLE OPENINGS...............................................................3

2.2.1 Limits of Uncloseable Openings ................................................32.2.2 Compensation ...........................................................................4

2.3 MATERIAL CONVERSION FACTOR ..................................................42.4 TEMPERATURE CORRECTION.........................................................62.5 FORCED VENTILATION .....................................................................62.6 INTERCONNECTED VOLUMES .........................................................72.7 VENTING FOR SURFACE FIRE SYSTEMS .......................................7

3 CO2 REQUIREMENTS FOR DEEP SEATED FIRES...................................83.1 BASIC QUANTITY ...............................................................................83.2 OPENINGS ..........................................................................................83.3 FORCED VENTILATION .....................................................................83.4 INTERCONNECTED VOLUMES .........................................................83.5 EXTENDED DISCHARGE .................................................................10

3.5.1 Venting for Deep Seated Fire Systems ...................................104 DISCHARGE RATES FOR TOTAL FLOODING SYSTEMS......................12

4.1 SURFACE FIRES ..............................................................................124.2 DEEP SEATED FIRES ......................................................................12

5 NOZZLE DISTRIBUTION...........................................................................136 LOCAL APPLICATION SYSTEMS............................................................14

6.1 EXAMPLES OF HAZARDS................................................................146.2 GENERAL..........................................................................................146.3 CO2 QUANTITIES..............................................................................14

6.3.1 Duration of Discharge..............................................................156.3.2 Material Conversion Factor......................................................15

7 RATE BY AREA METHOD ........................................................................16

Page 66: Kidde co2 product manual 050128

iv Manual No 59812-401

7.1 CO2 QUANTITY .................................................................................167.2 HORN DISPOSITIONS ......................................................................18

8 RATE BY VOLUME METHOD...................................................................208.1 ASSUMED ENCLOSURE ..................................................................208.2 CO2 QUANTITY .................................................................................208.3 HORN DISPOSITIONS ......................................................................21

9 PIPE SELECTION......................................................................................229.1 RATE OF APPLICATION...................................................................229.2 PIPE SIZE ESTIMATES.....................................................................229.3 NOZZLE SIZES..................................................................................23

10 STORAGE CONTAINER LOCATION........................................................2411 DISTRIBUTION VALVES...........................................................................2512 AUTOMATIC OPERATION........................................................................2613 MANUAL CONTROL .................................................................................27

13.1 MANUAL RELEASE...........................................................................2714 ALARMS ....................................................................................................2815 ELECTROSTATIC DISCHARGE ...............................................................2916 DETECTION...............................................................................................30

16.1 PNEUMATIC DETECTION - HEAT ACTUATED DEVICES...............3016.1.1 General....................................................................................3016.1.2 Location of HADs on Smooth Flat Ceilings..............................3116.1.3 Fixed Temperature HAD..........................................................32

17 SAFETY REQUIREMENTS........................................................................3317.1 TOTAL FLOODING SYSTEMS..........................................................3317.2 LOCAL APPLICATION SYSTEMS.....................................................33

18 FACTORY MUTUAL RULES.....................................................................34

Page 67: Kidde co2 product manual 050128

v Manual No 59812-401

LIST OF ILLUSTRATIONS

Figure PageFigure 1 Aiming Position for Angled Discharge Horns............................................18Figure 2 Discharge Rate, per kg per min per m3 ....................................................20

LIST OF TABLES

Table PageTable 1 Volume Factors ..........................................................................................3Table 2 Minimum Carbon Dioxide Concentration for Extinction ..............................5Table 3 Hazard Factors ...........................................................................................9Table 4 Extended Discharge Gas Quantities for Enclosed Circulation: Rotating

Electrical Machines...................................................................................11Table 5 Horn Selection and CO2 Quantity .............................................................17Table 6 Aiming Factors for Nozzles Installed at an Angle (based on 150 mm

Freeboard)................................................................................................19Table 7 Pipe Size Estimates..................................................................................22

Page 68: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-4011

INTRODUCTIONThis manual describes the design principles to be used on all carbon dioxide (CO2) systems.

General requirements and design criteria are based on British Standard (BS) 5306 Part 4, but onsome occasions National Fire Protection Association (NFPA) 12 may be used as the base document.

Detailed information on components is given in the individual CO2 Engineering Data Sheets.

The importance of proper design cannot be over stressed as design concentrations and applicationrates are critical for successful extinguishing.

The recommendations given in this document represent the best known technical data, but while theaim has been to anticipate all considerations, the recommendations should be applied in practicalsituations with discretion and due regard to local circumstances.

Full requirements for the design of CO2 fire fighting systems are given in BS5306 Part 4.

Page 69: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-4012

TOTAL FLOODING SYSTEMS

1 TOTAL FLOODING SYSTEMS

CO2 total flooding systems are based on creating an extinguishing concentration of CO2 within anenclosed space containing the combustible materials. The quantity of CO2 is determined by applyingan appropriate flooding factor to the volume being protected.

The efficiency of a total flooding system depends upon maintaining the concentration for as long aspossible, so before total flooding can be considered as a method of extinguishing, the protected spacemust be reasonably well enclosed. It is always advisable for an integrity test to be conducted to verifythe rate of leakage.

A fixed supply of CO2 is permanently connected to fixed piping and discharge nozzles are arranged todischarge CO2 into the protected space.

1.1 Examples of Hazards

Rooms, vaults, enclosed machines, ovens, dust collectors, floor and ceiling voids and fume extractionducts.

1.2 Type of Fires

Fires that can be extinguished by total flooding methods are:

(a) Surface fires that can be extinguished quickly, such as those involving flammable liquids andvapours.

(b) Deep seated fires that require cooling time in order to be extinguished, e.g. fires involving bulkpaper and other solids.

1.3 Where CO2 is NOT Effective

(a) Materials that contain their own oxygen supply and liberate oxygen when burning, e.g. cellulosenitrate.

(b) Reactive metals e.g. sodium, potassium, magnesium, titanium, zirconium, uranium andplutonium.

(c) Metal hydrides.

While CO2 may not extinguish these fires, it will not react dangerously or increase the burning rate.CO2 will protect adjacent combustibles and will also extinguish fires of other materials in which thereactive metals are often stored.

Example:

(a) Sodium stored or used under Kerosene.

(b) Cellulose nitrate in a solvent.

(c) Magnesium chips covered with heavy oil.

Page 70: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-4013

CO2 REQUIREMENTS FOR SURFACE FIRES

2 CO2 REQUIREMENTS FOR SURFACE FIRES

2.1 Basic Quantity

Multiply the volume to be protected (cubic metres) by the appropriate volume factor given in Table 1.

The answer will be in kilograms of CO2. This will protect an enclosure containing materials requiring adesign concentration of up to 34%.

The volume to be used is the gross volume of the enclosure but you are permitted to deductpermanent, impermeable elements of the building structure i.e. beams, stanchions, solid stairways andfoundations.

Table 1 Volume Factors

Volume of Space Volume Factor Calculated Minimumm3 kg CO2/m3 kg

<4 1.15>4 <14 1.07 4.5>14 <45 1.01 16.0>45 <126 0.90 45.0>126 <1400 0.80 110.0>1400 0.74 1100.0

» NOTE 1 Table 1 Volume Factors, must ONLY be used for SURFACE FIRES.» NOTE 2 For DEEP SEATED FIRES refer to Chapter 3.

Example:Room: 6 m x 9 m x 3m = 162 m3

162 m3 x 0.80 kg/m3 = 129.6 kg

2.2 Uncloseable Openings

Openings shall be arranged to close automatically before or simultaneously with the start of the CO2discharge. This can be done by self-closing door devices, fire curtains or steel shutters, refer to DataSheet 811-5000.

If it is not possible to seal the opening it is permissible for small openings to remain open providedthey do not exceed the limits shown below, and are compensated by the addition of extra carbondioxide.

2.2.1 Limits of Uncloseable OpeningsThe maximum area permitted is the smaller result of the following calculations:

(a) An area in square metres, which is numerically equivalent to 10% of the volume in cubic metres.

(b) 10% of the total area of all sides, top and bottom in square metres.

When uncloseable openings exceed this limitation, the system should be designed by a localapplication method.

Page 71: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-4014

CO2 REQUIREMENTS FOR SURFACE FIRES

2.2.2 CompensationAdditional gas at the rate of 5 kg/m2 of opening.

Where necessary this quantity should be multiplied by the appropriate Material ConversionFactor (MCF), refer to Section 2.3.

The additional quantity should be discharged through the regular pipework system and the flow rateincreased accordingly so that the additional quantity is discharged within the time specified in BS5306Part 4.

2.3 Material Conversion Factor

For materials requiring a design concentration over 34%, the basic quantity of carbon dioxidecalculated, i.e. the result of using Table 1, plus the addition for losses through limited openings, shallbe increased by multiplying this quantity by the appropriate conversion factor in Table 2.

The most hazardous material in the enclosure must be selected no matter what the quantity of thatmaterial.

For materials not listed consult Kidde Fire Protection as the design concentration may have to bedetermined by test.

Example:Room: 6 m x 9 m x 3 m high = 162 m3

162m3 x 0.80kg/m3 = 129.6kgUncloseable opening = 1.0 m2 = 5.0 kgBasic quantity = 134.6 kgIf room contains butadiene as the most hazardous material: MCF = 1.3134.6 kg x 1.3 = 175kg

Page 72: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-4015

CO2 REQUIREMENTS FOR SURFACE FIRES

Table 2 Minimum Carbon Dioxide Concentration for Extinction

Minimum MaterialMaterial Design CO2 Conversion

Concentration (%) FactorAcetaldehyde 34 1.0Acetylene 66 2.5Amyl Acetate 34 1.0Acetone 31 1.0Amyl Alcohol 34 1.0Benzol, Benzene 37 1.1Butadiene 41 1.3Butane 34 1.0Butyl Acetate 34 1.0Butyl Alcohol 34 1.0Carbon Disulphide 66 2.5Carbon Monoxide 64 2.4Coal Gas or Natural Gas 37 1.1Cyclopropane 37 1.1Diesel Fuel 34 1.0Dowtherm 46 1.5Ethane 40 1.2Ethyl Ether 46 1.5Ethyl Alcohol 43 1.3Ethylene 49 1.6Ethylene Dichloride 25 1.0Ethylene Oxide 53 1.75Hexane 35 1.1Hydrogen 74 3.2Isobutane 36 1.1Kerosene 34 1.0Lube oils 34 1.0Methane 30 1.0Methyl Alcohol 40 1.2Paint 34 1.0Pentane 35 1.1Petroleum Spirit 34 1.0Propane 36 1.1Propylene 36 1.1Quench, Lube Oils 34 1.0Tar 34 1.0Toluol 34 1.0Turpentine 34 1.0Transformer Oil 34 1.0

For materials not listed please contact Kidde Fire Protection

Page 73: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-4016

CO2 REQUIREMENTS FOR SURFACE FIRES

2.4 Temperature Correction

Additional quantities of CO2 are needed to compensate for the effects of abnormal temperature.

Hazards which operate at temperatures above 100°C may be more likely to re-ignite so it is necessaryto hold the extinguishing concentration for a longer period to assist cooling.

Add 2% carbon dioxide for each 5°C above 100°C.

Example:Oven: 3 m x 1.5 m x 1.8 m = 8.1 m3

If the normal working temperature is 204°C:204-100 = 104/5 = 20.820.8 x 2% = 41.6%8.1m3 x 1.07 kg/m3 = 8.66 (basic quantity) x 1.416 (temp correction)= 12.26 kg

CO2 has a lower expansion ratio at lower temperatures so it will be more dense and leakage would begreater than normal.

Where the normal temperature of the enclosure is below -20°C, add 2% of CO2 for each 1°C below-20°C.

Example:Refrigerated space:3 m x 6 m x 3 m = 54 m3 with a normal operating temperature of -23°C.23°C - 20°C = 3°C x 2% = 6%54 m3 x 0.90 kg/m3 = 48.6 kg (basic quantity) x 1.06 (temp correction)= 51 .5 kg

If an addition has been made to the basic CO2 quantity to compensate for openings or application ofan MCF, the total quantity should be used in place of the basic quantity in the above examples.

2.5 Forced VentilationWhen forced air ventilation systems are used, they shall, if possible, be shutdown before, orsimultaneously, with the start of the CO2 discharge. If this cannot be done, additional CO2 must beapplied.

If there is a short run down time but the quantity of air removed is significant, additional CO2 must beapplied. The additional CO2 must be discharged within the time specified in BS5306 Part 4.

For calculation purposes the volume of air removed in one minute will be replaced with CO2 at thedesign concentration being used.

Example:Refer to the example in Section 2.3.Assume the room has 30 m3 of air removed by the ventilation system in one minute.

30 m3 x 0.80 kg/m3 = 24 kg x 1.3 (MCF) = 31.2 kg + 175.0 kg (original) = 206.2 kg

Services such as heating, fuel supplies, paint spraying, conveyors etc. must also be shutdown beforeor simultaneously, with the CO2 discharge.

Page 74: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-4017

CO2 REQUIREMENTS FOR SURFACE FIRES

2.6 Interconnected Volumes

In two or more interconnected volumes where free flow of CO2 can occur, the CO2 quantity shall bethe sum of the quantities calculated for each volume, using its respective volume factor. If one volumerequires greater than normal concentration, the higher concentration shall be used for allinterconnected volumes.

2.7 Venting for Surface Fire Systems

Leakage around doors and windows often provides sufficient pressure relief without specialarrangements being required. It is possible to calculate the area of free venting needed for very tightenclosures but it is recommended you provide the customer with the formula and CO2 flow rate so thathis architect can take the responsibility.

P

Q

where:X is the free venting area (in mm2).Q is the calculated carbon dioxide flow rate (in kg/min).P is the permissible strength (internal pressure) of enclosure (in bar).

X=23.9

Page 75: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-4018

CO2 REQUIREMENTS FOR DEEP SEATED FIRES

3 CO2 REQUIREMENTS FOR DEEP SEATED FIRES

3.1 Basic Quantity

Multiply the volume to be protected (cubic metres) by the flooding factor given in Table 3.

Example:Paper documents storage room:6m x 6m x 3m high = 108m3

108 m3 x 2 kg/m3 CO2 = 216 kg

3.2 Openings

Total flooding systems protecting solid materials cannot tolerate the degree of openings permitted forsurface fire protection.

The design concentration must be maintainable over a long period, so low level openings are notpracticable. Small openings at or near the ceiling are ideal because:

(a) Compensation for losses involves only reasonable quantities of additional CO2.

(b) They allow the escape of hot gases.

(c) They prevent pressure increases that can stress the enclosure structure.

Any openings that cannot be closed shall be compensated for by the addition of CO2 equal in volumeto the expected loss during the extinguishing and holding time.

3.3 Forced Ventilation

When forced air ventilation systems are used, they shall, if possible, be shutdown before, orsimultaneously, with the start of the CO2 discharge. If this cannot be done, additional CO2 must beapplied.

If there is a short run down time but the quantity of air removed is significant, additional CO2 must beapplied. The additional CO2 must be discharged within the time specified in BS5306 Part 4.

For calculation purposes the volume of air removed in one minute will be replaced with CO2 at thedesign concentration being used.

Example:Assume the room has 30 m3 of air removed by the ventilation system in one minute:30 m3 x 2 kg/m3 = 60 kg + 216 kg (original) = 276 kg

Services such as heating, fuel supplies, paint spraying, conveyors etc. must also be shutdown beforeor simultaneously, with the CO2 discharge.

3.4 Interconnected VolumesIn two or more interconnected volumes where free flow of CO2 can occur, the CO2 quantity shall bethe sum of the quantities calculated for each volume, using its respective volume factor. If one volumerequires greater than normal concentration, the higher concentration shall be used for allinterconnected volumes.

Page 76: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-4019

CO2 REQUIREMENTS FOR DEEP SEATED FIRES

Table 3 Hazard Factors

Based on an expansion ratio of 0.52 m3/kg at a temperature of 10°C.

Hazard Design FloodingConcentration Factors

(%) (kg/m3)

Electrical equipment.Enclosed rotating equipmentDry electrical wiringElectrical insulating materials 50 1.35

Computer installations *Central processing areas and equipment 53 1.50

Data processingTape controlled machineryand tape storage 68 2.25

StoresRecord stores and archives forpaper documents Ducts and covered trenches 65 2.00

Fur storage vaultsDust collectors 75 2.70

GeneralCocoaLeatherSilkWool 63 1.78

CoalCoffeeCorkCottonPeanutsRubberSoybeanSugar 75 2.70

* See also BS 6266.

» NOTE 1 Flooding factors for other deep seated fires should be agreed with Kidde Fire Protection.

» NOTE 2 Table 1 Volume Factors, is not applicable for deep seated fires and must not be used.

Page 77: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-40110

CO2 REQUIREMENTS FOR DEEP SEATED FIRES

3.5 Extended Discharge

In some instances it may be necessary to have an extended discharge for leakage compensation witha rate of flow that is considerably slower than that required for initial fire extinguishing. A typicalexample is the protection of rotating electrical machinery, i.e. alternators and generators, where aninitial concentration has to be achieved in a short time and a minimum concentration of 30% during aspecified deceleration period, which should be held for 20 minutes.

Two separate banks of CO2 containers and distribution piping are used in this case, the ‘initial’ bankdischarging at a fast rate and the ‘extended’ bank discharging at a slow rate.

Table 4 is used to determine the quantity of CO2 to maintain minimum concentration.

The quantities are based on the nett internal volume of the machine and the deceleration timeassuming average leakage.

For non re-circulating machines with relief vents, add 35% to the quantities shown in Table 4.

3.5.1 Venting for Deep Seated Fire SystemsLeakage around doors and windows often provides sufficient pressure relief without specialarrangements being required. It is possible to calculate the area of free venting needed for very tightenclosures but it is recommended you provide the customer with the formula and CO2 flow rate so thathis architect can take the responsibility.

PQ

where:X is the free venting area (in mm2).Q is the calculated carbon dioxide flow rate (in kg/min).P is the permissible strength (internal pressure) of enclosure (in bar).

X=23.9

Page 78: Kidde co2 product manual 050128

Carbon DioxideRequired

5 mm 10 mm 15 mm 20 mm 30 mm 40 mm 50 mm 60 mm

kg lb m3 ft3 m3 ft3 m3 ft3 m3 ft3 m3 ft3 m3 ft3 m3 ft3 ft3

45 100 34 1 200 28 1 000 23 800 17 600 14 500 11 400 9 300 6 20068 150 51 1 800 43 1 500 34 1 200 28 1 000 21 750 17 600 14 500 11 40091 200 68 2 400 55 1 950 45 1 600 37 1 300 28 1 000 24 850 18 650 14 500

113 250 93 3 300 69 2 450 57 2 000 47 1 650 37 1 300 30 1 050 23 800 17 600136 300 130 4 600 88 3 100 68 2 400 57 2 000 47 1 650 37 1 300 28 1 000 20 700159 350 173 6 100 116 4 100 85 3 000 71 2 500 57 2 000 47 1 650 34 1 200 26 900181 400 218 7 700 153 5 400 108 3 800 89 3 150 71 2 500 57 2 000 45 1 600 34 1 200204 450 262 9 250 193 6 800 139 4 900 113 4 000 88 3 100 74 2 600 60 2 100 45 1 600227 500 306 10 800 229 8 100 173 6 100 142 5 000 110 3 900 93 3 300 79 2 800 62 2 200250 550 348 12 300 269 9 500 210 7 400 173 6 100 139 4 900 119 4 200 102 3 600 88 3 100272 600 394 13 900 309 10 900 244 8 600 204 7 200 170 6 000 147 5 200 127 4 500 110 3 900295 650 436 15 400 348 12 300 279 9 850 235 8 300 200 7 050 176 6 200 156 5 500 136 4 800319 700 479 16 900 385 13 600 314 11 100 266 9 400 230 8 100 204 7 200 181 6 400 159 5 600340 750 524 18 500 425 15 000 350 12 350 297 10 500 259 9 150 232 8 200 207 7 300 184 6 500363 800 566 20 000 464 16 400 385 13 600 329 11 600 289 10 200 261 9 200 232 8 200 207 7 300386 850 609 21 500 503 17 750 421 14 850 360 12 700 320 11 300 289 10 200 258 9 100 229 8 100408 900 651 23 000 541 19 100 456 16 100 391 13 800 350 12 350 317 11 200 285 10 050 255 9 000431 950 697 24 600 581 20 500 491 17 350 422 14 900 379 13 400 346 12 200 312 11 000 278 9 800454 1 000 739 26 100 620 21 900 527 18 600 453 16 000 411 14 500 374 13 200 337 11 900 303 10 700476 1 050 782 27 600 666 23 300 564 19 900 484 17 100 442 15 600 402 14 200 364 12 850 326 11 500499 1 100 824 29 100 697 24 600 596 21 050 515 18 200 470 16 600 430 15 200 389 13 750 351 12 400522 1 150 867 30 600 736 26 000 632 22 300 547 19 300 501 17 700 459 16 200 416 14 700 374 13 200544 1 200 912 32 200 773 27 300 667 23 550 578 20 400 532 18 800 487 17 200 442 15 600 399 14 100567 1 250 954 33 700 813 28 700 702 24 800 609 21 500 562 19 850 515 18 200 467 16 500 422 14 900590 1 300 1 000 35 300 852 30 100 738 26 050 641 22 650 592 20 900 544 19 200 494 17 450 447 15 800612 1 350 1 042 36 800 889 31 400 773 27 300 673 23 750 623 22 000 572 20 200 521 18 400 472 16 650635 1 400 1 087 38 400 929 32 800 809 28 550 705 24 900 654 23 100 600 21 200 548 19 350 496 17 500658 1 450 1 130 39 900 968 34 200 844 29 800 736 26 000 685 24 200 629 22 200 575 20 300 520 18 350680 1 500 1 172 41 400 1 008 35 600 879 31 050 767 27 100 715 25 250 657 23 200 600 21 200 544 19 200

CO

2 RE

QU

IRE

MEN

TS FO

R D

EE

P S

EA

TED

FIRE

S

Table 4 Extended Discharge G

as Quantities for Enclosed C

irculation:

Rotating Electrical M

achines

Issue 5 Decem

ber 2004 11 M

anual No 59812-401

Page 79: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-40112

DISCHARGE RATES FOR TOTAL FLOODING SYSTEMS

4 DISCHARGE RATES FOR TOTAL FLOODING SYSTEMS

The importance of the following calculations is that pipe and nozzle sizes are based on the desiredflow rate, refer to Chapter 9.

0.52 m3/kg @ 10°C

0.54 m3/kg @ 20°C

0.56 m3/kg @ 30°C

4.1 Surface Fires

For surface fires the design concentration will be achieved in one minute.

Example:Room requiring 1,000 kg of CO2.This would be the basic quantity calculated, plus all additions but not includingany special addition for cooling purposes, refer to Section 2.4.1,000 kg of CO2 ÷ by one minuteFlow rate = 1000 kg/min

4.2 Deep Seated FiresFor deep seated fires the design concentration will be achieved within seven minutes but the rate willnot be less than that required to develop a concentration of 30% in two minutes.

This would be the basic quantity calculated, plus all additions but not including an extended discharge.

Example:Paper documents storage room:6 m x 6 m x 3 m high = 108 m3

108 m3 x 2 kg/m3 of CO2 = 216 kg30% Vol = 32.4 m3

32.4 in3 ÷ 0.56 m3/kg (expansion 30°C) = 57.85 kg ÷ 2Flow rate = 29 kg/minFlow time = 216 ÷ 29 = 7.45 minutesTo ensure a flow time of 7 minutesUse 216 ÷ 7 = 31 kg per minute

Most calculations produce a flow time of between four and seven minutes, the last step shows what todo if seven minutes is exceeded.

Page 80: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-40113

NOZZLE DISTRIBUTION

5 NOZZLE DISTRIBUTION

For flooding rooms use discharge horn nozzles Part No K61793 or K61792, refer to Data Sheet811-9148, depending upon flow rate required.

Nozzles should spaced approximately 6 m apart.

For rooms up to 5 m high, install nozzles at a height of 2.5 m and angle of 45°. Average throwapproximately 4 m.

For rooms between 5 and 10 m high, install at 2/3 height up from floor.

For rooms with high stacking or rooms over 10 m high, it may be necessary to install at 1/3 and 2/3levels.

Obstructions: If obstructions interfere with efficient distribution it may be necessary to use morenozzles than specified above, or even locate nozzles at ceiling level.

To protect the nozzle in dirty conditions use Part No. K5814, refer to Data Sheet 811-9139.

To inject CO2 into ducts use nozzle Part No. K13045, refer to Data Sheet 811-9151.

Page 81: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-40114

LOCAL APPLICATION SYSTEMS

6 LOCAL APPLICATION SYSTEMS

Local application systems are used for extinguishing surface fires in flammable liquids, vapours andshallow solids, where the hazard is not enclosed or where the degree of enclosure does not conformto the requirements for total flooding.

In carbon dioxide local application systems, CO2 is discharged directly into the fire. The efficiency ofthe system depends on the CO2 contacting the burning surface at the required rate of flow. Correctdischarge horn nozzle positioning is critical.

Quantities of CO2 must not be determined by using Table 1.

6.1 Examples of Hazards

Dip tanks, quench tanks, printing presses, textile machinery, coating machinery, spray booths, kitchenranges and hoods etc.

6.2 General

The important point is that the hazard shall be isolated from other hazards and the entire hazardprotected simultaneously, so that fire is prevented from spreading to unprotected areas and a re-flashfrom unprotected areas is not possible.

For example, in a six stand printing press simultaneous protection would be given to all printingstands, the drying boxes, the ink supply containers, and the flammable vapour extract duct. Similarly inan industrial food processing environment, simultaneous protection is given to the cooking oilsurfaces, the burner compartment, the fume hood and extraction duct.

Any service likely to affect the efficiency of the CO2 discharge must be interlocked with the system soas to automatically shut down. This would include ventilating fans, conveyors, flammable liquid pumps,mixers, heaters, dryers, sprayers etc.

6.3 CO2 Quantities

The quantity of CO2 to be used in a local application system can be determined by either of twomethods depending upon the hazard construction, but there are various factors that are common toboth.

The amount of CO2 required is computed by multiplying the total nozzle discharge rate by the time thedischarge is required to be maintained.

For high pressure systems, the computed quantity of CO2 is increased by 40% to compensate for thefact that only 70% of the cylinder content is discharged as a liquid and considered effective.

If a combination of total flooding and local application protection is being given, this increase is notneeded for the total flooding portion. The discharge rate for the total flooding portion can be calculatedby dividing the quantity required for total flooding by the factor 1.4 and by the time of the localapplication discharge in minutes.

Page 82: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-40115

LOCAL APPLICATION SYSTEMS

6.3.1 Duration of Discharge

The minimum, effective liquid discharge time is 30 seconds.

This is increased if inherently hot surfaces or materials require a longer time to assist in cooling and toprevent re-ignition.

The standard does not specify the prolonged discharge time so this must be decided by the designertaking into account the temperature involved and local site considerations, but somewhere betweenone and three minutes is usually adequate.

The minimum discharge time for Carbon Dioxide being applied to liquids that have an auto-ignitiontemperature that is lower than their boiling temperature shall be 3 min.For example when protecting a kitchen range a prolonged discharge is given to the cooking oil surface(3 minutes) but only 30 seconds to other associated areas.

6.3.2 Material Conversion Factor

A MCF is applied when appropriate, as specified in Section 2.3. The increased quantity of CO2 has tobe discharged during the 30 second minimum period.

Example:Local application portion:Flow rate (kg/min) x discharge time (mins) x 1.4 x MCF = kg of CO2 requirede.g. 100 kg/min x 0.5 x 1.4 x 1.5 (Ethyl Ether)=100 x 0.7x 1.5= 105kgpIus 150 kg for a 90 second discharge for cooling = 315 kg in total and discharged at arate of 150 kg/min

Total flooding portion:Quantity of CO2 required is determined by the total flooding methodFlow rate = Quantity of CO2

1.4 x discharge timee.g. 14 kg of CO2 is for a Total Flooding portion of a combined Local Application minusTotal Flooding system (discharge time 0.5min)Flow rate = 14 kg = 14 = 20 kg/min

1.4 x 0.5 0.7

The foregoing information relates to high pressure storage containers of which the majority of systemscomprise.

If a low pressure bulk storage tank is employed, the 1.4 liquid flow factor is omitted.

Also the pre-liquid flow time, which is a feature of low pressure systems must not be included as partof the 30 second liquid discharge time.

» NOTE Only liquid discharge is effective in a local application system.

Page 83: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-40116

RATE BY AREA METHOD

7 RATE BY AREA METHOD

The area method of system design is used where the fire hazard consists of flat surfaces or low-levelobjects associated with flat horizontal surfaces.

When flammable liquid fires are to be extinguished, a minimum freeboard of 150 mm is necessary.

7.1 CO2 Quantity

The maximum area protected by each discharge horn and the amount of CO2 required varies with thedistance of the horn from the surface being protected. The greater the distance, the larger the areacovered and quantity of CO2 required.

The portion of a hazard surface protected by each horn is based on its ‘side of square’ coverage.Nozzle sizes are selected for their area coverage and flow rate so as to minimise the amount of CO2required.

See Table 5 for details of horn height, area coverage and CO2 quantity combinations.

Page 84: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-40117

RATE BY AREA METHOD

Table 5 Horn Selection and CO2 Quantity

Part Nos. K5814 up to N8, refer to Data Sheet 811-9139.

Part Nos. K61793 up to N12 and K61792 up to N18, refer to Data Sheet 811-9148.

Coated Surface (m) Discharge Horn Liquid Surface (m)Area(m2)

Side ofSquare

Height(m)

Rate(kg/min)

Area(m2)

Side ofSquare

1.17 1.08 0.60 14.0 0.84 0.91

1.23 1.11 0.68 15.7 0.88 0.94

1.30 1.14 0.76 17.3 0.93 0.96

1.36 1.17 0.84 19.3 0.98 0.99

1.43 1.19 0.91 20.5 1.02. 1.01

1.50 1.22 0.99 21.6 1.07 1.03

1.56 1.25 1.07 23.6 1.11 1.05

1.62 1.27 1.14 25.2 1.16 1.08

1.69 1.30 1.22 26.8 1.20 1.09

1.76 1.33 1.30 28.4 1.25 1.12

1.82 1.35 1.37 30.0 1.30 1.14

1.86 1.37 1.45 31.6 1.35 1.16

1.95 1.40 1.52 33.2 1.39 1.18

2.01 1.42 1.60 34.8 1.44 1.20

2.08 1.44 1.67 36.4 1.49 1.22

2.15 1.46 1.75 38.0 1.53 1.23

2.21 1.48 1.83 39.5 1.58 1.26

2.28 1.50 1.90 41.1 1.62 1.27

2.34 1.53 1.98 42.7 1.67 1.29

2.41 1.55 2.06 44.3 1.72 1.31

2.47 1.57 2.13 46.0 1.76 1.33

2.54 1.59 2.21 47.5 1.81 1.34

2.60 1.81 2.29 49.1 1.86 1.36

2.60 1.61 2.36 50.7 1.86 1.36

2.60 1.61 2.44 52.3 1.86 1.36

2.60 1.61 2.51 53.9 1.86 1.36

2.60 1.61 2.59 55.5 1.86 1.36

2.60 1.61 2.67 57.0 1.86 1.36

2.60 1.61 2.74 58.6 1.86 1.36

» NOTE Interpolations are not permitted.

Page 85: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-40118

RATE BY AREA METHOD

7.2 Horn Dispositions

Hazard conditions often restrict the positioning of discharge horns but to use Table 5 accurately, hornsmust be installed perpendicular to the hazard and centred over the area to be protected. They mayalso be installed at angles between 45 and 90° to the plane of the hazard. The ‘height’ used indetermining the necessary flow rate and area coverage is the distance from the aiming point on theprotected surface to the face of the horn measured along the axis of the horn.

See Figure 1 for a typical example.

Figure 1 Aiming Position for Angled Discharge Horns

Page 86: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-40119

RATE BY AREA METHOD

The aiming point is measured from the near side of the area protected and is located by multiplyingthe fractional aiming factor in Table 6 by the width of the area protected by the horn.

Table 6 Aiming Factors for Nozzles Installed at an Angle(based on 150 mm Freeboard)

Discharge Angle (See Note 1) Aiming Factor (See Note 2)

45 to 60°60 to 75°75 to 90°90° (perpendicular)

1741/4 to 3/83/8 to 1/21/2 (centre)

» NOTE 1 Degrees from plane of hazard surface.» NOTE 2 Fractional amount of nozzle coverage area.

It is important that horns are located so that the discharge is not obstructed and their alignment is noteasily disturbed.

Discharge horns must be located so as to develop an extinguishing concentration over coated stockthat may be extending over a protected surface, e.g. freshly dipped items hanging on a conveyor line.In these circumstances additional horns may be required for this specific purpose, particularly if stockextends more than 600 mm above a protected surface.

Note the increase in area coverage that is given in Table 5 for coated surfaces compared with liquidsurfaces.

The effects of severe air currents and draughts shall be compensated for by adjusting horn locationsor by providing additional horns to suit the expected conditions.

Example:Hazard: Quench TankMaterial: Quench Lube OilMCF: 1Surface dimensions: 0.92 m x 2.13 m

Horn Location. The site survey has shown that discharge horns can be positioned anywhere from 0.92m to 1.83 m above the liquid surface without interfering with plant operations.

Design Aim. To select a combination of horn height, area coverage and flow rate to adequately coverthe area with the minimum CO2 quantity.

Procedure. Consider the size to be protected. What is the minimum number of horns that could beused to cover a length of 2.13 m of liquid surface?

Answer. Two horns with a side of square each of 1.08 m. This selection also satisfies a width of 0.92m since it is less than 1.08 m, and also an area of 1.95 m² since it is less than can be protected by thetwo horns selected.

Horns required. Two located centrally above the liquid surface pointing down from a height of 1.14m.

Flow rate. 2 x 25.2 kg per minute = 50.4 kg/min

CO2 required. 50.4 x 1 (MCF) 1 4 (liquid flow for 0.5 min) = 50.4 x 0.7 = 35.3 kg2

This provides the basic CO2 quantity for the minimum permitted length of time but the discharge timeat the calculated flow rate could be increased for cooling to prevent reignition.

Page 87: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-40120

RATE BY VOLUME METHOD

8 RATE BY VOLUME METHOD

The assumed volume method of system design is used where the fire hazard consists of threedimensional irregular objects that cannot easily be reduced to equivalent surface areas, or where thedegree of enclosure does not conform to the requirements for total flooding.

8.1 Assumed EnclosureThe total discharge rate of the system is based on the volume of hypothetical enclosure surroundingthe hazard.

The assumed enclosure must have a closed floor.

The assumed walls and ceiling of the ‘enclosure’ shall be at least 0.6 m from the main hazard unlessactual walls are involved, and they must enclose all areas of possible leakage, splashing or spillage.

No deduction from the assumed volume shall be made for solid objects within this volume. A minimumdimension of 1.2 m shall be used in calculating the assumed volume.

8.2 CO2 QuantityThe total discharge rate for the basic system shall be 16 kg/min per m3 of assumed volume.

If the assumed enclosure is partly defined by permanent continuous walls extending at least 0.6 mabove the hazard, the discharge rate may be proportionately reduced to not less than 4 kg/min per m3

for the actual walls completely surrounding the hazard. See Figure 2 for quickly deciding theappropriate discharge rate.

Figure 2 Discharge Rate, per kg per min per m3

Page 88: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-40121

RATE BY VOLUME METHOD

8.3 Horn DispositionsA sufficient number of horns must be used to adequately cover the entire hazard volume and theymust be located and directed so as to retain the CO2 in the hazard volume by suitable co-operationbetween horns and objects making up the hazard volume.

If forced draughts or air currents are anticipated they must be compensated for by a suitabledisposition of the discharge horns.

To ensure that discharge horns are not located so remote from the risk as to be ineffective, and not soclose to liquids as to cause splashing, a check can be made by using Table 6.

Example:If horn, Part No. K61792, with a flow rate of 52.3 kg/min, was selected it should be locatedapproximately 2.44 m from the surface it is protecting.

Example 1Hazard: Paint Spray Booth (ignoring extract duct for this calculation)Actual dimensions: 2.44 m wide (open front) x 2.13 m high x 1.83 m deepAssumed volume: 2.44 m x 2.13 m x 2.43 m (1.83 m deep + 0.6 m) = 12.63 m3

Percent Perimeter enclosed =244 + 1.83 + 183 = 6.1 = 71%2.44 + 2.44 + 1.83 + 1.83 8.54Discharge rate for 71% enclosure: from Figure 2 = 7.5 kg/min m3

Discharge rate: 12.63 m3 x 7.5 kg/min m3 = 94.73 kg/minCO2 required: 94.73 kg/min x 0.7 = 66.3 kg x MCF (1.0)

Example 2Hazard: Printer with 4 sides and top open (no continuous solid walls and ignoringextract duct for this calculation).Actual dimensions: 1.22 m wide x 1.52 m long x 1.22 m high (this is the maximumhazard outline).Assumed volume: 2.42 m (1.22 + 0.6 + 0.6) x 2.72 m (1.52 + 0.6 + 0.6)x 1.82 m (1.22 + 0.6) = 11.98 m3

Percent perimeter enclosed: ZeroDischarge rate for 0% enclosure: 16 kg/min m3

Discharge rate: 11.98 m3 x 16 kg/min m3 = 191.7 kg/minCO2 required: 191.7 kg/min x 0.7 = 134.2 kg x MCF (1.0)

» NOTE The assumed volume method of system design always needs more gas than the rateby area method, so to be competitive it is always worth considering if the risk can beprotected by the area method. Example 2 can, but Example 1 cannot.

Page 89: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-40122

PIPE SELECTION

9 PIPE SELECTION

The selection of the various grades of pipe and fittings in order to meet the duties imposed byoperating pressures arid temperatures is made by complying with BS 5306 part 4 or NFP A 12 asappropriate.

9.1 Rate of ApplicationAlso see to Chapter 4.

Where advancement of flame is potentially rapid, as in surface fires, the CO2 discharge must becomparably fast to minimise damage.

Where the spread of fire is potentially slow, such as deep seated fires in solid materials, moreemphasis is placed on maintaining a fire suppression concentration for a lengthy period of time toallow time for cooling.

Where the spread of fire may be faster than normal for the type of fire expected, or where high values,or vital machinery or equipment are involved, rates higher than the stated minimums may be used.

Where a hazard contains materials that will produce both surface and deep seated fires, the rate ofapplication should be at least the minimum required for surface fires.

9.2 Pipe Size EstimatesHydraulic pipe size calculations are accurately determined by using the Kidde Fire Protection CO2Computer Calculation Program. However, for estimating for a quotation, only a reasonably accurateresult is needed and this can be achieved by using Table 7.

Table 7 Pipe Size Estimates

Metric

Flow Rate(kg/min)

Estimated Pipe SizeNominal bore (mm)

Up to 123 20124 to 177 25178 to 363 32364 to 545 40546 to 1045 501045 to 1363 65

Imperial

Flow Rate(lbs/min)

Estimated Pipe SizeNominal bore (inches)

Up to 270 ¾271 to 390 1391 to 800 1¼801 to 1200 1½1201 to 2300 22300 to 3000 2½

Page 90: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-40123

PIPE SELECTION

Examples

(a) A surface fire where the design concentration has to be achieved in one minute. If a spacerequires 300 kg of CO2, the flow rate from the main manifold would be 300 kg/min and the sizeof the feed pipe would be 32 mm bore.

If the system used 4 discharge horns in a balanced distribution system, the feed pipe wouldbranch into two pipes each flowing at 150 kg/min and would be sized 25 mm bore.

» NOTE The design concentration would include any extra CO2 for losses through openingsand that demanded by the MCF but would not include any extra CO2 allowed forcooling. This would be allowed to discharge at the same rate and would extend thedischarge time beyond one minute.

The same philosophy applies in a local application system except that the minimum dischargetime is 30 seconds, which may be extended beyond this time to discharge any extra CO2 addedfor cooling.

(b) A deep seated fire where the design concentration has to be achieved within seven minutes, buta concentration of 30% (must be achieved within) two minutes.

When an order has been received, a Contract Engineer would calculate the flow rate accurately,as shown in Section 4.2.

For estimating purposes it is sufficient to adopt a short cut method.

To determine the flow rate divide the volume protected by:3 if in cubic metres and answer in kg/min.51 if in cubic feet and answer in lbs/min.

(c) In an extended discharge system where the CO2 quantity is derived from Table 4, it is simplynecessary to divide the quantity of CO2 required by the length of time of the extended dischargeto determine the flow rate.

9.3 Nozzle SizesThese are determined by use of the Calculation Program, and nozzle orifice sizes are drilled accordingto Data Sheet 811-9148.

A point to bear in mind is that the maximum number of discharge horns that can be fed by onecontainer is 11 – N3.

The larger the nozzle orifice the smaller the number of horns that can be used, i.e. only one N11

Page 91: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-40124

STORAGE CONTAINER LOCATION

10 STORAGE CONTAINER LOCATION

It is important to get a commitment from a prospective client about the location of storage containersbecause this will affect the installation of pipe, detection lines and cabling, and remote pull controls.

The containers shall be located in a secure area and arranged so that they are readily accessible forinspection, testing, recharging and other maintenance.

Containers shall be located as near as possible to the space they protect. They may be located withinthe protected space, but must not be exposed to a fire in a manner that is likely to impair systemperformance. If located within the protected space the manual/pneumatic actuator can be used toprovide a means of mechanically operating the system from outside the protected space. The chosenlocation should provide protection from mechanical, chemical, electrical and other types of damage.Suitable guards or enclosures should be provided when necessary, as required by an appropriate riskanalysis. The floor at the container location must be suitable for withstanding the loading exerted bythe containers.

The containers must not be exposed to the direct rays of the sun. When excessive temperaturevariations are expected, suitable enclosures shall be provided.

The general ambient storage temperatures should not exceed the following:

(a) For total flooding systems:not greater than 55ºC or less than -18ºC.

(b) For local application systems:not greater than 46ºC or less than 0ºC.

» NOTE The minimum storage temperature for local application is higher than that allowed fortotal flooding systems because the discharge area limit tests were carried out at aminimum temperature of 0ºC and to operate at lower temperatures would cause thefigures in Table 5 to be incorrectly applied.

Page 92: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-40125

DISTRIBUTION VALVES

11 DISTRIBUTION VALVES

When the multiple hazards are located reasonably close together they can be protected with a singlebank of containers with the CO2 being directed to the hazard on fire by opening the appropriatedistribution valve on a distribution valve manifold.

When using this method it is important to consider the list below:

(a) The amount of CO2 is sufficient for the largest hazard.

(b) There is only one supply of agent so it must not be possible for fire to spread from one zone toanother.

(c) Any number of zones can be protected by a single bank of containers but Insurers’ rulesgenerally limit the number to 5.

(d) A reserve supply of CO2 should be considered.

Page 93: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-40126

AUTOMATIC OPERATION

12 AUTOMATIC OPERATION

Systems should preferably be operated automatically by a detection system which is appropriate tothe risk.

Where applicable, e.g. slow burning hazards, the requirements of BS5839 should be observed.

Page 94: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-40127

MANUAL CONTROL

13 MANUAL CONTROL

All systems must be fitted with a manual release facility.

Refer to Data Sheet 841-5027.

13.1 Manual ReleaseWhen mechanically operated pull-handles are used the following limitations apply:

Maximum length of cable =45 m

Maximum number of corner pulleys = 10

Maximum number of sets = 1

All mechanical functions must be tested upon completion of the installation to ensure properperformance.

Page 95: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-40128

ALARMS

14 ALARMS

System condition indicators should be provided as appropriate to the surroundings.

(a) A total flooding systems should have indicators located outside the entrance doors to show:

CO2 Discharged - red lampManual Control only - green lampAutomatic and Manual Control - amber lamp

These indications may not always be necessary for a local application system.

(b) Additional alarms may be needed to be transmitted to remote locations including a CentralStation, and other system conditions may be required such as:

System Totally Disabled - amber lampFire - red flashing lampSystem Operated - red steady lampSupply Healthy - green lamp

Warning labels are required to be located alongside manual release points, refer to Data Sheet811-9225, and located on all entrance doors, refer to Data Sheet 811-9237.

Depending upon the size and complexity of the site or system, instructional wall charts may beneeded.

Operating and Maintenance manuals should always be provided.

Audible alarms should be provided as appropriate to the type of system and protected area, but atleast to the requirements of B5306 Part 4.

Where BS5839 is not a requirement, local alarms may be mains operated provided the supply can beguaranteed.

Page 96: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-40129

ELECTROSTATIC DISCHARGE

15 ELECTROSTATIC DISCHARGE

WARNING

CO2 FIRE EXTINGUISHING SYSTEMS MUST NOT BE USEDFOR INERTING EXPLOSIVE ATMOSPHERES.

Page 97: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-40130

DETECTION

16 DETECTION

Automatic detection systems used with CO2 extinguishing systems should comply with appropriateCodes of Practice, these include:

1. BS5839 - Fire Detection and Alarm Systems in Buildings.

2. BS6266 - Data Processing Installations.

3. FOC Rules.

4. This Manual.

» NOTE Attention is drawn to the considerably higher concentration of detectors required byBS6266 when protecting computer suites.

This philosophy should not be extended into other areas of protection without prior consultation withKidde Fire Protection.

The following guidance is given for use when designing systems using pneumatic detection systems.

16.1 Pneumatic Detection - Heat Actuated Devices

16.1.1 GeneralHeat Actuated Devices (HADs) are heat detectors and the following general points must beconsidered before using the devices.

(a) It is always necessary to determine that the minimum expected quantity of fuel is sufficient toproduce a significant rise in the ambient temperature.

(b) Heat detection should never be used where the fire can be of a smouldering, or primarily smokeproducing type.

(c) Height reduces the efficiency of heat detectors: it takes a larger floor level fire to actuate adetector in a tall room, than a room with a height of only 3 m.

(d) Where the passage of smoke or hot gas from a position to a detector is disturbed by a ceilingobstruction (such as a beam) having depth greater than 450mm, then the obstruction should betreated as a wall for the purposes of detector location.

(e) Rate-of-rise systems are recommended only for Class B flammable liquid, or exceptionally fastburning Class A types of hazards.

(f) Fixed temperature systems should be used where rapid changes in temperature are the norm,such as forced hot air ovens, kitchens, boiler houses, lantern lights, etc. The operatingtemperature of the detector should be about 30ºC above the maximum working temperature. Beaware that capillary tubing can act as a rate-of-rise detector so routes outside the rapid changearea must be found.

(g) Detectors fitted in lantern lights should be protected from direct sunlight and fitted at least50 mm below the glass.

Page 98: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-40131

DETECTION

16.1.2 Location of HADs on Smooth Flat Ceilings

(a) Distance between detectors and walls.(i) HADs shall be spaced no more than 10 m apart.(ii) Where ceilings are level, the distance between the wall and the nearest detector should not

exceed one half the distance allowed between detectors.(iii) With sloped ceilings, (slope more than 1 in 10) and apexed ceilings, consult Kidde Fire

Protection.

(b) Height of detector above the hazard.

Where detectors are place more than 7 m above the hazard, consult Kidde Fire Protection forguidance on the spacing of detectors.

(c) Number of detectors on one circuit:

(i) There shall be no more than six HADs on any one detection circuit or control head.

(ii) The maximum length of 1/8” (3mm) O.D. tube per detection circuit is 210 m.

Each HAD is equivalent to 30 m of 1/8” (3mm) O.D. tube:

1 HAD + 180 m tube

2 HAD + 150 m tube

3 HAD+ 120 m tube

4 HAD + 90 m tube

5 HAD + 60 m tube

6 HAD + 30 m tube

(d) Reducing the risk of accidental discharge:

(i) Care should be taken to prevent unwanted discharges as a result of normal ambient oroperating conditions. This includes most forced air sources such as exhaust systems, unitheaters and air conditioning systems; as well as the opening of oven or furnace doors,opening doors from the protected area or a heating system able to rapidly raise thetemperature of the hazard. Similarly consider the effect of locating detectors adjacent tofresh air inlets that will dilute heat build up.

(ii) Where portions of a single hazard have different temperature characteristics, the HAD’sin each section shall be installed on a separate cell of a check valve unit.

Page 99: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-40132

DETECTION

16.1.3 Fixed Temperature HAD

(a) Fixed temperature HAD’s employ a meltable alloy slug are available for a limited range, contactKidde Fire Protection.

Select an operating temperature that is at least 30ºC above the maximum expectedtemperature.

Page 100: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-40133

SAFETY REQUIREMENTS

17 SAFETY REQUIREMENTS

Suitable safeguards are necessary to protect people in areas where the atmosphere may be madehazardous by a carbon dioxide fire extinguishing system.

The principal risk is from suffocation. The effects of toxicity are usually not considered a life hazard.

17.1 Total Flooding Systems

Entry into a protected space may only be made when the system is on manual control and automaticrelease has been prevented.

If a CO2 protected room is normally occupied by people a normally closed valve should be fitted intothe feed pipe so that a malicious or accidental release at the container bank is stopped fromdischarging into the room. The valve should only open when demanded by the detectors or by amanual release unit.

The condition of the valve should be automatically monitored and indicated. CO2 trapped in the feedpipe should be indicated by means of a pressure switch and a locked closed valve fitted so that theCO2 can be safely vented to atmosphere.

A time delay may be used, but only in addition to an isolation device, refer to Chapter 14 for alarmsignals.

17.2 Local Application Systems

An isolating device to prevent automatic release is not necessary, if it can be shown that following arisk analysis a hazardous concentration cannot be created within the total volume of the roomcontaining the local application system. A time delay and pre-discharge alarm is acceptable to theHealth and Safety Executive in this circumstance.

A concentration in excess of 10% on the nett volume could be considered hazardous to some people.

Concentrations below 5% are harmless to the majority of people.

The facility provided on system actuators and control heads for totally disabling a system are not to beused as a normal ‘entry to space isolating device’.

Page 101: Kidde co2 product manual 050128

Issue 5 December 2004 Manual No 59812-40134

FACTORY MUTUAL RULES

18 FACTORY MUTUAL RULES

Kidde Fire Protection has official approval of its CO2 equipment by Factory Mutual (FM) Insurance.These are generally similar to NFPA 12 rules, with some variations.

Page 102: Kidde co2 product manual 050128

Issue B December 2004 Manual No 59812-400

High PressureCarbon DioxideFire Protection Equipment

INSTALLATION,COMMISSIONING &MAINTENANCE MANUAL

Page 103: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

ii

PROPRIETARY RIGHTS NOTICE

This document and the information that it contains are the property of Kidde Fire Protection. Rights toduplicate or otherwise copy this document and rights to disclose the document and the informationthat it contains to others and the right to use the information contained therein may be acquired onlyby written permission signed by a duly authorised officer of Kidde Fire Protection.

© Copyright Kidde Fire Protection Services Ltd.

Page 104: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

iii

TABLE OF CONTENTS

Chapter Page

FOREWORD.........................................................................................................11 GENERAL....................................................................................................2

1.1 SAFETY PRECAUTIONS ....................................................................21.2 PRELIMINARY CHECKS.....................................................................3

PART 1 INSTALLATION......................................................................................42 CO2 CYLINDERS AND RACKING...............................................................4

2.1 CO2 CYLINDERS .................................................................................42.1.1 Klem Cylinder Valves K23521 and K24509.............................5

2.2 INSTALLATION....................................................................................62.2.1 Single Cylinder ........................................................................62.2.2 Single Row Cylinders ..............................................................72.2.3 Double Row Cylinders .............................................................8

3. CO2 MANIFOLD PIPE ................................................................................103.1 MANIFOLD BRACKETS, SINGLE ROW ...........................................113.2 MANIFOLD BRACKETS, DOUBLE ROW..........................................11

4. DISTRIBUTION PIPING.............................................................................124.1. PIPING...............................................................................................124.2 ELECTRICAL CLEARANCES............................................................154.3 INSTALLATION..................................................................................16

5. PRESSURE OPERATED DIRECTION VALVES .......................................175.1 ¾ TO 2 INCH POD VALVES..............................................................18

5.1.1 Pressure Operation ...............................................................195.1.2 Manual Operation ..................................................................195.1.3 Valve Open Indication ...........................................................19

5.2 3 AND 4 INCH POD VALVES ............................................................205.2.1 Pressure Operation ...............................................................215.2.2 Manual operation...................................................................215.2.3 Valve Open Indication ...........................................................21

5.3 3 AND 4 INCH COMPANION FLANGE, BOLTS AND GASKET........225.4 SAFETY OUTLETS K 921 AND K22968 ..........................................235.5 INSTALLATION..................................................................................26

Page 105: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

iv

6. DISCHARGE LOOPS K21578 AND K97112.............................................276.2. RIGID DISCHARGE LOOP K21578...................................................276.2 FLEXIBLE DISCHARGE LOOP K97112............................................286.3 INSTALLATION..................................................................................29

7. SYSTEM ACTUATOR ASSEMBLY...........................................................307.1 NITROGEN PILOT GAS CYLINDER AND VALVE ............................317.2 OPTIONAL PRESSURE MONITORING SWITCH.............................327.3 CONTROL HEAD K62303 .................................................................337.4 CONTROL HEAD WITH SWITCHES K62304 ...................................347.5 CONTROL HEAD MOUNTING BRACKET K62487 ...........................357.6 SAFETY AND RESET PIN K62401 ...................................................36

Retain reset pin in safe location for future use. ..................................367.7 INSTALLATION..................................................................................37

8. CONTROL HEAD ACTUATING DEVICES................................................398.1 MANUAL PUSH-TO-FIRE BUTTON K62412.....................................408.2 SOLENOID ACTUATORS K62422B AND K93206/AX ......................418.3 FLAMEPROOF 24V D.C SOLENOID K93206/AX .............................428.4 INSTALLATION..................................................................................43

8.4.1 Standard Solenoid .................................................................438.4.2 Flameproof Solenoid .............................................................448.4.3 Control Head and Solenoid Wiring ........................................458.4.4 Special Instructions to comply with 94/9/EC (ATEX) .............46

8.5 PNEUMATIC DIAPHRAGM ACTUATOR K62459 .............................478.6 PNEUMATIC BREATHER VENTS K62895 .......................................488.7 INSTALLATION..................................................................................498.8 CABLE RELEASE ASSEMBLY K62478 ............................................49

8.8.1 Installation .................................................................................508.9 PULL BOX K 1114 .............................................................................52

8.9.1 Corner Pulley K 1122 ................................................................538.9.2 Installation .............................................................................53

9. CYLINDER VALVE PRESSURE/LEVER ACTUATOR K62341 ................559.1 INSTALLATION..................................................................................56

10. PILOT GAS FLEXIBLE LOOPS K93433 and K93434 ..............................5710.1 PILOT GAS VENT K24051 ................................................................5710.2 PILOT GAS RIGID TUBING AND FITTINGS.....................................5910.3 INSTALLATION..................................................................................61

11. TIME DELAY UNIT K23650 .......................................................................62

Page 106: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

v

11.1 INSTALLATION..................................................................................6311.2 TESTING............................................................................................6311.3 TIME DELAY BY-PASS VALVE K60736 ...........................................67

12. CO2 OPERATED PRESSURE SWITCH K60218 .......................................6912.1 INSTALLATION..................................................................................71

13. CO2 OPERATED PRESSURE TRIP K17554 .............................................7213.1 INSTALLATION..................................................................................73

14. CO2 DISCHARGE NOZZLES.....................................................................7414.1 MULTIJET NOZZLE K61792 AND K61793........................................7414.2 FLANGED MULTIJET NOZZLE K5814..............................................7514.3 FLANGED NOZZLE DUCT ADAPTORS K61420A-D ........................7614.4 DUCT NOZZLE K13045.....................................................................7714.5 FAN TYPE NOZZLE K6490 ...............................................................78

15. PNEUMATIC DETECTION - HEAT ACTUATED DEVICES ......................7915.1 PNEUMATIC RATE OF RISE DETECTOR K18724 ..........................7915.2 PNEUMATIC FIXED TEMPERATURE DETECTOR K18689.............8015.3 PNEUMATIC CHECK UNIT K24412..................................................8115.4 PNEUMATIC LOCK-OFF UNIT K24300 ............................................8215.5 BELLOWS AND MICROSWITCH ASSY K20057 ..............................8315.6 PNEUMATIC CAPILLARY TUBE, CONDUIT AND FITTINGS...........8415.7 CO2 OPERATED SIREN K18307.......................................................85

16. ODORISER ASSEMBLY K62586 ..............................................................8617. CO2 WARNING LABELS ...........................................................................87PART 2 COMMISSIONING ................................................................................8918. COMMISSIONING......................................................................................89

18.1 VISUAL CHECKS ..............................................................................8918.2 MECHANICAL FUNCTION ................................................................90

18.2.1 General..................................................................................9018.2.2 Manual Push-to Fire ..............................................................9018.2.3 Pull Box .................................................................................9018.2.4 Pneumatic System.................................................................9118.2.5 Pressure/Lever Actuator and POD Valves ............................9618.2.6 Pressure Trip .........................................................................9618.2.7 Pressure Switch.....................................................................97

PART 3 MAINTENANCE....................................................................................9819. MAINTENANCE .........................................................................................98

19.1 PRELIMINARY CHECKS...................................................................98

Page 107: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

vi

19.2 COMPONENT FUNCTION TESTS....................................................9919.2.1 General..................................................................................9919.2.2 Control Head .........................................................................9919.2.3 Pressure/Manual Release Heads and POD Valves.............10019.2.4 Pressure Trip .......................................................................10119.2.5 Pressure Switch...................................................................102

19.3 INSTRUCTIONS FOR COMMISSIONING THE SYSTEM AFTER ITSOPERATION....................................................................................102

PART 4 TERMS AND CONDITIONS................................................................10320. TERMS AND CONDITIONS.....................................................................103

Page 108: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

vii

LIST OF ILLUSTRATIONSFigure PageFigure 1 CO2 Cylinder ................................................................................................4Figure 2 Klem Cylinder Valves ...................................................................................5Figure 3 Single Cylinder Racking ...............................................................................6Figure 4 Single Row Cylinders ...................................................................................7Figure 5 Additional Centre Racks for Two Rows of Cylinders ....................................9Figure 6 CO2 Manifold Pipes ....................................................................................10Figure 7 Manifold Brackets, Single Row...................................................................11Figure 8 Manifold Brackets, Double Row .................................................................11Figure 9 POD Valve System.....................................................................................17Figure 10 ¾ to 2 inch POD Valves ...........................................................................18Figure 11 Indicator Switch........................................................................................19Figure 12 3 & 4 inch POD Valves.............................................................................20Figure 13. 3 and 4 inch Companion Flange, Bolts and Gasket ................................22Figure 14 Safety Outlets ..........................................................................................23Figure 15 All CO2 Cylinders discharging to either space ..........................................24Figure 16 Two Spaces Requiring differing CO2 cylinders .........................................25Figure 17 Rigid Discharge Loop ...............................................................................27Figure 18 Flexible Discharge Loops .........................................................................28Figure 19 System Actuator Assembly ......................................................................30Figure 20 Nitrogen Pilot Gas Cylinder and Valves ...................................................31Figure 21 Pressure Monitoring Switch......................................................................32Figure 22 Control Head ............................................................................................33Figure 23 Control Head with Switches .....................................................................34Figure 24 Standard Mounting Bracket......................................................................35Figure 25 Safety and Reset Pin................................................................................36Figure 26 Control Head Mounting Bracket ...............................................................38Figure 27 Control Head Actuating Devices...............................................................39Figure 28 Manual Push-to-Fire Button .....................................................................40Figure 29 Standard 24V d.c Solenoid.......................................................................41Figure 30 Flameproof ATEX approved 24V d.c. Solenoid........................................42Figure 31 Control Head and Solenoid Wiring ...........................................................45Figure 32 Pneumatic Diaphragm Actuator ...............................................................47Figure 33 Pneumatic Breather Vents .......................................................................48Figure 34 Cable Release Assy .................................................................................49

Page 109: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

viii

Figure 35 Cable Pull Ring Connection .....................................................................50Figure 36 Curvature of Cable ...................................................................................51Figure 37 Cable Release Assembly, Cover Removed .............................................51Figure 38 Pull Box ....................................................................................................52Figure 39 Corner Pulley ...........................................................................................53Figure 40 Cylinder Valve Pressure/Lever Actuator...................................................55Figure 41 Pilot Gas Flexible Loops...........................................................................57Figure 42 Pilot Gas Vent ..........................................................................................58Figure 43 Pilot Gas Rigid Tubing and Fittings ..........................................................59Figure 44 Single Cylinder Row Pilot Gas Operation.................................................61Figure 45 Double Cylinder Row Pilot Gas Operation ...............................................61Figure 46 Time Delay Unit........................................................................................62Figure 47 Single Protected Space System...............................................................64Figure 48 Two Protected Spaces System ................................................................65Figure 49 Two Protected Spaces Requiring Different CO2 Quantities ......................66Figure 50 Time Delay By-Pass Valve.......................................................................67Figure 51 Installation ................................................................................................68Figure 52 CO2 Operated Pressure Switch ................................................................69Figure 53 Pressure Trip............................................................................................72Figure 54 Installation ................................................................................................73Figure 55 Multijet Nozzle..........................................................................................74Figure 56 Flanged Multijet Nozzle ............................................................................75Figure 57 Flanged Nozzle Duct Adaptor ..................................................................76Figure 58 Duct Nozzle..............................................................................................77Figure 59 Fan Type Nozzle ......................................................................................78Figure 60 Pneumatic Rate of Rise Detector .............................................................79Figure 61 Pneumatic Fixed Temperature Detector...................................................80Figure 62 Pneumatic Check Unit..............................................................................81Figure 63 Pneumatic Lock-Off Unit ..........................................................................82Figure 64 Bellows and Microswitch Assembly..........................................................83Figure 65 Pneumatic Capillary Tube, Conduit and Fittings ......................................84Figure 66 CO2 Operated Siren..................................................................................85Figure 67 Odoriser Assembly ...................................................................................86Figure 68 Odoriser Check Valve ..............................................................................86Figure 69 Entrance Door Warning Label ..................................................................87Figure 70 Manual Control Point Label ......................................................................88Figure 71 Manometer Test System ..........................................................................91

Page 110: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

ix

LIST OF TABLES

Table PageTable 1 CO2 Cylinder Specification............................................................................4Table 2 Closed and open ended pipework section – High pressure systems..........12Table 3a Open Ended Pipework................................................................................13Table 3b Closed Section Pipework……………………………………………………… 13Table 4 Pipe Support Spacing.................................................................................14Table 5 Safety Clearances for Pipework .................................................................15

Page 111: Kidde co2 product manual 050128

© K.F.P.S. Ltd November 2004 Manual No 59812-400

1

FOREWORDKidde Fire Protection recognises its responsibility to ensure that the products it manufactures are, as faras is reasonably practical, without risk to the health and safety of the users. The following informationshould be disseminated to all persons using such products.

The information is furnished in good faith based upon technical data and tests, which are believed to bereliable. Products undergo rigorous quality control checks during manufacture to ensure that theypresent no hazards in the use and application for which they are intended.

Technical data and literature which may assist customers in the discharge of their general duties areavailable on request. Should you require further information on this context please contact our salesoffice.

Nothing contained in this publication shall form part of any contract made between a customer andKidde Fire Protection.

It is of vital importance that the CO2 equipment should be correctly installed. The Installation Engineershould become fully conversant with the contract files and all installation drawings before going to site.

Page 112: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

2

1 GENERAL

1.1 Safety Precautions

Characteristics of Carbon DioxideCarbon Dioxide (CO2) at atmospheric pressure is a colourless, odourless and electrically non-conductinginert gas which is almost 1.5 times as dense as air.

CO2 extinguishes fire by reducing the oxygen content of the atmosphere to a point where it will not supportcombustion. Reducing the oxygen content from the normal 21% in air to 15% will extinguish most surfacefires, though for some materials a greater reduction is necessary. In some applications the cooling effect ofCO2 may assist extinction.

Hazards to personnelExposure to atmospheres containing about 5% CO2 leads to shortness of breath and slight headache. Atthe 10% level, headache, visual disturbance, ringing in the ears (tinnitus) and tremor are followed by loss ofconsciousness.

Fire extinguishing concentrations of CO2, which are normally in excess of 30%, especially near to the pointof discharge from total flooding or local application systems, carry a risk of almost immediate asphyxiation.The gas is also more dense than air and will drift and accumulate in low spaces, such as cellars, pits andfloor voids, which may be difficult to ventilate effectively.

The rapid expansion of large quantities of CO2 results in a substantial localised cooling of the installationand of the air surrounding the point of discharge. This can present a frostburn hazard.

Handling and storage of CO2 cylindersObserve the following precautions to prevent accidental discharge of CO2:

On despatch, all cylinder and valve assemblies are fitted with transport caps which must not be removeduntil after the cylinders have been securely restrained, store the transport caps for future use.

Never use the cylinder valve to turn or move the cylinder, this could cause damage or leakage: use atransport trolley.

Never store cylinders in direct sunlight or in location where the cylinder temperature is likely to exceed55°C.

Page 113: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

3

Never depress the cylinder valve actuating pin as this action will open the valve and discharge its contentscausing the cylinder, unless securely restrained, to act as a projectile.

Never fit any release device to a cylinder valve until it has been secured in the cylinder rack and connectedto the discharge pipework.

Re-entry into a flooded areaNever enter an area after a CO2 discharge until it has been thoroughly ventilated to external atmosphere.

If it is necessary to enter an area containing CO2 always use self-contained Breathing Apparatus, never usea filter or canister type mask. As an added precaution the person entering should be tethered by a mannedlifeline.

Dismantling and modificationsIt is recommended that Kidde Fire Protection be notified of any intention to alter or extend the system orareas protected in order that advice be given of any effect that this may have on the original design.

1.2 Preliminary checks

Check that all equipment has been delivered, any damaged equipment must be replace.

Check that the area(s) to be protected agree with the installation drawings.

Check the CO2 cylinder location for ease of access during maintenance; also safety. Check that theambient temperature of the cylinder location complies with the following limitations: -

Total flooding systems: -18 to 55°C.

Local Application flooding Systems: Minimum 0°C Maximum 46°C.

Page 114: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

4

PART 1 INSTALLATION2 CO2 CYLINDERS AND RACKING

2.1 CO2 Cylinders

CO2 is stored in solid drawn steel cylinders containing gas in liquid form equal to two thirds of its watercapacity. The pressure within the cylinder varies with changes in ambient temperature, increasing withrising temperature. At 21°C the pressure is 58.6 bar.

The cylinder assembly comprises a cylinder, cylinder valve and rigid syphon tube which must ALWAYS beinstalled in an upright position.

Figure 1 CO2 Cylinder

Table 1 CO2 Cylinder Specification

Part No WaterCapacity(Litres)

Fill Weight(kg)

Total Weight(kg)

Dimension (mm)‘A’ ‘B’

E7194-001 67.5 45 120 Approx 267 1515K24069/FM 67.5 45 120 Approx 267 1531K24338 34.0 22.6 81 Approx 229 1102

NOTE: All dimensions ‘B’ are ±10mm

Cylinder Specification: 1999/36/EC (TPED)Material: SteelTest Pressure: 250 barFill Ratio: 0.661kg/litreStandard Point Finish: Red

Page 115: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

5

2.1.1 Klem Cylinder Valves K23521 and K24509

The “Klem” cylinder valve is a compact, horizontal servo-assisted valve which can be operated by eitherpressure or use of its integral manual lever.

The valve is opened by depressing the actuator rod by applying a force of between 23 and 27kg.

WARNINGThe valve will close immediately the force is removed from the actuator rod.

Each cylinder valve incorporates a safety disc designed to rupture and discharge the CO2 cylinder contentswhen the ambient temperature reaches approximately 60°C (140°F).

MaterialsBody: BrassSeals: Silicone Rubber Shore 70° - 90°Actuator Rod: St. SteelSafety Burst Disc: Ruptures at 179 to 196 bar

Figure 2 Klem Cylinder Valves

Page 116: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

6

2.2 INSTALLATION

2.2.1 Single Cylinder

Storage containers should be located as near as possible to the hazard they protect, but should not beexposed to the fire in a manner that is likely to impair performance. They should not be exposed toweather conditions or put in a location where they can be subjected to chemical or other damage. Suitableguards or enclosures should be provided when necessary.

1. Offer strap up to a suitable structure or wall and mark the hole centres for drilling at an elevation fromground level, see in Figure 3.

2. Drill appropriate fixing holes.3. Place and clamp the container in position.

Part No Cyl Size Dim A FixingHoles

Materials Weight(kg)

K16896 6.8 175 9.5mmØ

1.0

K4881 22.6 292 10.5mmØ

Mild Steel 25mm x 3mm1.2

K62943 45.0 320 12.7mmØ

Nylon Dipped Black 1.5

Figure 3 Single Cylinder Racking

Page 117: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

7

2.2.2 Single Row Cylinders

Storage containers should be located as near as possible to the hazard they protect, but should not beexposed to the fire in a manner that is likely to impair performance. They should not be exposed toweather conditions or put in a location where they can be subjected to chemical or other damage. Suitableguards or enclosures should be provided when necessary.

1. Offer the cylinder back rack up to a suitable structure or wall and mark the hole centres for drilling atan elevation from the ground as shown in Figure 3. Check that the back rack is correctly offset inrelation to the manifold inlet. See Figure 4.

2. Drill appropriate fixing holes.

3. Fix the back rack to the suitable structure or wall using the bolts.

4. Place the cylinders in position against the cut-outs in the back rack.

5. Hook the rack bolts through the 17.5mm diameter hole(s) in the back rack.

6. Locate the straight end of the rack bolts through the 17.5mm diameter holes in the front strap andclamp the containers firmly in place using the nuts and washers supplied with the rack bolts.

Part No Material Finish Weight(kg)

2 Cylinder K17238 MS Angle Paint Black 1.8Steel BackRacks 3 Cylinder K17235 MS Angle Paint Black 2.7

2 Cylinder K13744 MS Strap 2.7Steel FrontStraps 3 Cylinder K13745 MS Strap

Nylon DippedBlack 4.5

Single Row Rack BoltAssembly

K62752 MS Rod Paint Black 0.4

Figure 4 Single Row Cylinders

Page 118: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

8

2.2.3 Double Row Cylinders

Storage containers should be located as near as possible to the hazard they protect, but should not beexposed to the fire in a manner that is likely to impair performance. They should not be exposed toweather conditions or put in a location where they can be subjected to chemical or other damage. Suitableguards or enclosures should be provided when necessary.

1. Offer the cylinder back rack up to the wall and mark the hole centres for drilling at an elevation fromthe ground as shown in Figure 5. Check that the back rack is correctly offset in relation to themanifold inlet. See Figure 5.

2. Drill appropriate fixing holes.

3. Fix the back rack a suitable structure or wall using the bolts.

4. Place the cylinders in position against the cut-outs in the back rack.

5. Slide the rack bolt through the wood centre rack and hook onto the back rack.

6. Place the front row of cylinders into position.

7. Place the front straps in position and clamp the cylinders firmly in position using the nuts andwashers supplied.

Page 119: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

9

45kg CylindersPart No Weight (kg)

2 Cylinder K24334 1.4Cylinder CentreRacks 3 Cylinder K24335 2.0Two Row Rack Bolt K62753 1.1Two Rack Special Rack Bolt K17327 0.7

22.6kg CylindersPart No Weight (kg)

2 Cylinder K22654 1.1Cylinder CentreRacks 3 Cylinder K22655 1.8Two Row Rack Bolt K17245 1.0Two Rack Special Rack Bolt K17327 0.7

Figure 5 Additional Centre Racks for Two Rows of Cylinders

Page 120: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

10

3. CO2 MANIFOLD PIPE

On multiple cylinder systems manifold pipes are supplied as a complete assembly including factoryinstalled check valves.

1” (25mm) NB Manifold 1¼” (32mm) NB Manifold

AssemblyPart No.

Number ofCylinders

Weight(kg)

AssemblyPart No.

Number ofCylinders

Weight(kg)

K21207 2 2.7 K21215 2 3K21209 3 3.9 K21217 3 4.5K21211 4 5.0 K21219 4 5.9K21213 5 6.3 K21221 5 7.3

Figure 6 CO2 Manifold Pipes

Page 121: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

11

3.1 MANIFOLD BRACKETS, SINGLE ROW

Dimension (mm)Part No Pipe SizeA B

Material - Finish Weight (kg)

K24267D 1” Mild SteelK24267E 1¼”

101.6 174.5Painted Black

2.0

Figure 7 Manifold Brackets, Single Row

3.2 MANIFOLD BRACKETS, DOUBLE ROW

Dimension (mm)Part No Pipe SizeA B

Material - Finish Weight (kg)

K24268D 1” Mild SteelK24268E 1¼”

101.6 479.4Painted Black

2.5

NOTE: Pipe Clips and Pipe Clip Bolts are supplied with the Brackets.

Figure 8 Manifold Brackets, Double Row

Page 122: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

12

4. DISTRIBUTION PIPING

All the pipework sizes shown in the schematic of the installation have been determined using a computerprogramme. It is IMPORTANT that these sizes are used to ensure the correct flow of CO2 within the stateddischarge time.

4.1. PIPING

1. The pipe and fittings materials must conform with the-requirements of BS 5306 Part 4 as shown inthe following tables.

Table 2 Closed and open ended pipework section – High pressure systems

Closed section of pipeworkNominal pipe size Type of fitting Grade or Material Conforms to

WPA or WPB BS 3799:1974Forged steel, screwed,3000 lb ASTM A105N ANSI B16.11:1996

Up to and including 40mm

Wrought steel, buttwelded

WPA or WPB BS 1640-3:1968

WPA or WPB BS 3799:1974Above 40mm up to 50mm Forged steel, socketwelded, 3,000 lb ASTM A105N ANSI B16.11:1996

Open section of pipeworkNominal pipe size Type of fitting Grade or Material Conforms toUp to and including 20mm Screwed fittings Malleable iron BS EN

10242:1995a

Screwed fittings Wrought steel BS EN 10241:2000Up to and including 40mm

Wrought steel, buttwelded

WPA or WPB BS 1640-3:1968

WPA or WPB BS 3799:1974Forged steel, screwed,3000 lb ASTM A105N ANSI B16.11:1996

WPA or WPB BS 3799:1974

All sizes up to 150mm

Forged steel, socketwelded, 3,000 lb ASTM A105N ANSI B16.11:1996

a Fittings conforming to BS EN 10242 may be used on open section pipework greater than 20 mm provided that they aresuitable certified by the manufacturer for the anticipated pressure

Page 123: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

13

Table 3a Open Ended Pipework

BS1387 BW - HeavyBS 3601 S 430BS 3601 ERW 430BS 3601 BW 320 or 430BS 3602-1 HFS or CFS 360 or 430API 5L S or ERW B

Up to & incl 40mm

ASTM A106-77 HF or CD A or B

Schedule 40

BS 3601 S 430BS 3601 ERW 430BS 3602-1 HFS or CFS 360 or 430ASTM A106-77 HF or CD A or B

Over 40mm up to & incl50mm

API 5L S or ERW B

Schedule 80

* AbbreviationsHF Hot Finished CFS Cold Finished SeamlessCD Cold Drawn HFS Hot Finished SeamlessS SeamlessERW Electric Resistance Welded & Induction Welded

Flange bolts, studs, nuts and washers

Bolts and studs shall conform to BS EN 1515-1. Nuts shall conform to BS EN 1515-1. Washers shallconform to BS 3410 or BS 4320NOTE: Plain washers should be fitted under bolt head and nut. A minimum of two threads should project above the nut when fullytightened

Gasket for flanged joints

Flanges joints shall be fitted with a gasketCOMMENTARY AND RECOMMENDATIONS ON 19.4: The recommendation of the gasket manufacturer should be followed inselecting the grade, specification and thickness to be used.

Table 3b Closed Section Pipework

High pressure carbon dioxide systems

Nominal pipe size Conforms to Type of Pipe a Grade of steel Minimum wall thickness b

BS 3601 S 430

BS 3602-1 HFS or CFS 430

ASTM A106-77 HF or CD B

Up to and including40mm

API 5L S or ERW B

Schedule 40 (schedule80 for joints)

BS 3602-1 HFS or CFS 430

ASTM A106-77 HF or CD B

50mm and above

API 5L S or ERW B

Schedule 80

a For abbreviations see footnote to Table 3 on previous pageb Schedule numbers determine the minimum wall thickness in accordance with BS 1600. Where the specified pipe is notobtainable in these dimensions, the next largest thickness should be used.

Page 124: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

14

NOTE: Crosses must not be used.

2. All pipe and fittings shall be galvanised inside and out.

3. Screwed threads shall comply with the dimensions specified in BS21.

4. Use PTFE pipe tape on all pipe screw threads (or other approved thread sealant).

5. The pipework MUST BE FIRMLY SUPPORTED because, in the event of a fire, the discharge willimpose a force on the pipework. If the piping became dislodged, considerable damage could becaused and the extinguishing system may not function correctly. Allowance must be made forexpansion and contraction of the pipework. See Table 4 for the minimum recommended pipe supportspacing.

Table 4 Pipe Support Spacing

Pipe Size (mm) 15 20 25 32 40 50 80 100 150Max Spacing (m) 1.5 1.8 2.1 2.4 2.7 3.4 3.7 4.3 5.2

Page 125: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

15

4.2 ELECTRICAL CLEARANCES

Where exposed electrical conductors are present, clearance no smaller than those given in Table 5 shallbe provided where practicable, between the electrical conductors and all parts of the CO2 system that maybe approached during maintenance, where these clearance distances cannot be achieved, warning noticesshall be provided and a safe system of maintenance work shall be adopted.

Minimum clearance from any point on or about the permanent equipment where a man may be required tostand (measured from position of the feet)

Table 5 Safety Clearances for PipeworkTo the nearestunscreened liveconductor in air(‘section clearance’)

Metres 2.59 2.59 2.74 2.74 2.89 3.05 3.20 3.35 3.50 3.81 4.27 4.57To the nearest partnot at earth potentialof an insulatorsupporting a liveconductor ('groundclearance')

Metres 2.44Max rated Voltage(XY) 11 15 22 33 44 66 88 110 132 165 220 275

The term insulator includes all forms of insulating supports, such as pedestal and suspension insulators,bushings, cable sealing ends and the insulating supports of certain types of circuit breaker etc.

IMPORTANT: See qualifying notes of clause 34 and definitions 30 and 31 of BS 7354: 1990 fromwhich this table is taken.

Page 126: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

16

4.3 INSTALLATION

Piping is normally supplied to site in random lengths. Installation of this pipework must be carried out inaccordance with the site fabrication drawings.

Table 5 shows recommended clearances to enable operation, maintenance and repair work to be carriedout safely.

NOTE: All dirt, swarf and cutting oil must be removed from each section of pipe beforeinstallation. CO2 pressure will remove any debris and may deposit it on valuableequipment.

Before installation of any pipework check the following:

(a) That all screw threads are clean and free of any damage.

(b) That all flange faces are clean and free of any damage.

(c) That pipe bores are clean and unobstructed.

(d) The route of the piping. Make sure that it is possible to fix the piping securely on the wall and in theceiling and floor voids.

(e) That none of the pipe fittings have been used before because of the risk of distortion.

NOTE: Use PTFE pipe tape on all pipe screw threads. (Or other approved thread sealant).

To install the pipework, carry out the following procedure:

(a) Mark the positions of the supports and hangers.

(b) Drill the wall or ceiling and install the required quantity of rawbolts or anchor bolts to suit the type ofsupport being used.

(C) Install a pipe hangar or clip adjacent to each nozzle in order to prevent movement of the nozzlesduring discharge.

(d) All CO2 pipework should be painted signal red to BS 381C ref 537 (equivalent to BS 4800 Ref04E53)

(e) All exposed metalwork in CO2 systems shall be efficiently earthed to prevent the metal workbecoming electrically charged.

Page 127: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

17

5. PRESSURE OPERATED DIRECTION VALVES

When two or more areas are to be protected using a central bank of CO2 cylinders, a Pressure OperatedDirection (POD) valve is installed in each of the CO2 main feed pipes leading to the designated areas, seeFigure 9.

Figure 9 POD Valve System

Page 128: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

18

5.1 ¾ to 2 INCH POD VALVES

PartNumber

Size(inch)

WithSwitch

Dimension mmA

Dimension mmB

Weight(kg)

K24004 ¾ NO 171 117 3.4K24628 ¾ YES 216 117 3.5K24005 1 NO 171 100 3.2K24629 1 YES 216 100 3.3K24175 1¼ NO 210 156 5.7K24630 1¼ YES 255 156 5.8K24176 1½ NO 210 137 5.4K24631 1½ YES 255 137 5.5K24177 2 NO 295 191 17.0K24632 2 YES 340 191 17.1

Figure 10 ¾ to 2 inch POD Valves

Page 129: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

19

5.1.1 Pressure Operation

Application of Nitrogen pilot gas to the pilot gas inlet port depresses the valve piston. When the valve pistonis at the bottom of its stroke a pilot gas outlet port is uncovered thus allowing the pilot gas to be conveyed,by the pilot gas line, to the CO2 cylinder pressure release heads.

NOTE: The valve remains open until the pilot gas pressure is vented from the pilot gas line.

5.1.2 Manual Operation

Remove the safety pin and operate lever fully.

NOTE: The valve can be opened while subjected to CO2 pressure.

5.1.3 Valve Open Indication

The indicator switch provides means for operating audible/visual alarms to give warning of a partial or fullyopen valve.

Figure 11 Indicator Switch

Page 130: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

20

5.2 3 and 4 INCH POD VALVES

Dimension (mm)PartNumber

Sizeinch

WithSwitch A B C

FlangeFixing Holes

Weight(kg)

K24775 3” YES 330 292 2038-EQUI spaced21mm Dia On165mm PCD

43.3

K24777 4” YES 406 340 2418-EQUI spaced25 mm Dia On197mm PCD

69.5

Figure 12 3 & 4 inch POD Valves

Page 131: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

21

5.2.1 Pressure Operation

Application of Nitrogen pilot gas to the pilot gas inlet port lifts the valve piston. When the valve piston is atthe top of its inlet stroke an outlet port is uncovered thus allowing the pilot gas to be conveyed, by the pilotgas line, to the CO2 cylinder pressure release heads.

NOTE: The valve remains open until the pilot line is depressurised.

5.2.2 Manual operation

Turn the hand wheel fully anti-clockwise to open the valve.

NOTE: The valve can be opened while subjected to CO2 pressure.

5.2.3 Valve Open Indication

The indicator switch provides means for operating audible/visual alarms to give warning of a partial of fullyopen valve, see Figure 11.

Page 132: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

22

5.3 3 and 4 INCH COMPANION FLANGE, BOLTS AND GASKET

Dimension (mm)PartNumber

Sizeinch A B C

Bolt PartNumber

Weight

K60103 3 203 165 32 K60101 7 kgK60104 4 241 197 35 K60102 8.5 kg

NOTE: Use Gasket K60105 (3”) or K60106 (4”)

Figure 13. 3 and 4 inch Companion Flange, Bolts and Gasket

Page 133: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

23

5.4 SAFETY OUTLETS K 921 and K22968

On systems employing normally closed directional/stop valves there is a possibility of CO2 entrapment inpipework between the CO2 cylinders and the valves therefore a safety outlet must always be fitted. Theindicator sleeve is “blown-off” when the disc ruptures giving a visual indication of operation.

WARNINGTHESE DEVICES SHOULD BE FITTED SO THAT THE DISCHARGE IN THE EVENT OF OPERATIONWILL NOT INJURE OR ENDANGER PERSONNEL, IF NECESSARY THE DISCHARGE SHOULD BEPIPED TO AN AREA WHERE IT WILL NOT BECOME A HAZARD TO PERSONNEL (AS PER THEREQUIREMENTS OF BS 5306 part 4).

K 921 K22968

Figure 14 Safety Outlets

K 921 Specification: K22968 Specification:

Burst/Opening Pressure: 150 bar ± 5% 126 barMaterial: Brass BrassFinish: Natural NaturalWeight: 0.35 kg 0.8 kg

Figures 15 and 16 show the Nitrogen pilot gas installation requirements for opening the pressure operateddirection valve prior to operation of the CO2 cylinders.

Page 134: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

24

Figure 15 All CO2 Cylinders discharging to either space

Page 135: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

25

Figure 16 Two Spaces Requiring differing CO2 cylinders

Page 136: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

26

5.5 INSTALLATION

Before installation of POD valves check the following:

1. All screw threads are clean and free of any damage.

2. If using a flanged valve check that all flanges are clean and free of damage.

3. That all flange bolt holes on the valve align with the flange bolt holes on feed pipe.

4. With the Safety Lock pin removed check that the indicator switch clicks into operation.

After the checks have been carried out satisfactorily install the POD valve as follows:-

1. Install the POD valve in the main feed line at a position where access for manual operation ofmaintenance/service is unhindered by other obstacles. Where possible install the POD valve at aheight of approximately (1.5 meters) 5’- 0” (maximum). Make sure that the arrow shown on the valvebody to indicate the direction of flow faces away from the CO2 manifold.

2. Connect a nipple and socket union to the outlet side of the POD valve for ease of installation to themain CO2 feed line.

3. Use PTFE pipe tape on all screwed pipe fittings.

4. To prevent accidental discharge of fire fighting systems during installation work check the followingbefore connecting the pilot gas lines:

(i) That the Safety and Reset pin is screwed fully home in the control head.

(ii) That all safety pins are fully inserted in the cylinder release heads, and POD valves.

5. Using 3/16” bundy tubing and fittings, see Figure 44, connect the Nitrogen pilot cylinder valve to thepilot gas inlet port of the POD valves and from the POD valve gas outlet port to the CO2 cylinderpressure release head as shown in Figure 15 and 16.

NOTES

1. Clip the bundy tube to the wall at approx 457mm centres.

2. ¾ to 2 inch POD valves require adaptors K90220 and K90219 fitted in the pilot gas inlet port andadaptor K90219 fitted to the pilot gas outlet port. See Datasheet 841-5036

3. 3 and 4 inch POD valves require adaptor K90219 fitted to both inlet and outlet pilot gas ports.

6. A POD valve indicator switch, if fitted, must be wired as shown in Figure 11.

Page 137: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

27

6. DISCHARGE LOOPS K21578 AND K97112

6.2. RIGID DISCHARGE LOOP K21578

The discharge loop is used to convey CO2 from the gas outlet of the cylinder valve to the check valvemanifold above the cylinders.

Figure 17 Rigid Discharge Loop

Materials:Tube: 12.7mm x 18 SWG Annealed.Material: CopperCoupling Nuts: BrassThread: W21.8 x 1/14 DIN 477. 30.5mm A/FTest Pressure: 152 Bar ApproxWeight: 0.3kg

Page 138: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

28

6.2 FLEXIBLE DISCHARGE LOOP K97112

This loop is used when “in-situ” weighing of the cylinders are required. It is also recommended for use onsingle cylinder systems for ease of connection to rigid discharge piping. When used for this purpose a loopto pipe adaptor K62755 is required.

Figure 18 Flexible Discharge Loops

Materials - K97112Hose: Reinforced RubberConnectors: Mild Steel Zinc Plate and Chromate PassivatedCoupling Nuts: Mild Steel Zinc Plate and Chromate PassivatedTest Pressure: 210 barWeight: 0.5kg

Adaptor K62755: Brass

Page 139: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

29

6.3 INSTALLATION

Manifold Heights

Height To Underside Of ManifoldCyl Size (kg) Cyl Part No Copper Loop K21578 Flexible Loop K97112

22.6 K24338 1267 157745.0 K24069/FM45.0 E7194-001

1700 1800 ± 100

NOTE: All dimensions in mm

WARNINGALWAYS CONNECT THE LOOP TO THE MANIFOLD INLET OR PIPEWORK IF SINGLE CYLINDER,BEFORE CONNECTING TO THE CYLINDER VALVE OUTLET.

Page 140: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

30

7. SYSTEM ACTUATOR ASSEMBLY

The system actuator assembly incorporates the source of pilot Nitrogen gas supply and the mechanism torelease it either automatically and/manually.

Figure 19 System Actuator Assembly

Page 141: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

31

7.1 NITROGEN PILOT GAS CYLINDER AND VALVE

Figure 20 Nitrogen Pilot Gas Cylinder and Valves

Specification:

Cylinder: CF-CD01 Issue 2Water Capacity: 0.4 LitresMaterial: Steel Test Pressure: 250 barValve: BrassCharge: Dry Nitrogen to 65 bar at 20 (Recharge required at 55 bar)Weight: 1.7kgFinish: Grey PaintK62462 Standard AssyK62462A Complete with switch (Factory fitted)

Page 142: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

32

7.2 OPTIONAL PRESSURE MONITORING SWITCH

This switch provides means of signaling low-pressure within the Nitrogen pilot cylinder.

WARNINGPRESSURE HEAD - DO NOT ATTEMPT TO REMOVE FROM CYLINDER.

Figure 21 Pressure Monitoring Switch

Sensor Capacity: Max System Pressure 207 barProof Pressure 621 bar

Electrical Rating: 28 V d.c 5 Amp resistive3 Amp inductive

Connections: Common - EarthOpen under pressure - 1Closed under pressure - 2

Temperature Range: -54 to +107°CConstruction: ST.ST Housing, Black Nylon CapOperating Pressure: Factory set at 50 bar - decreasing

Page 143: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

33

7.3 CONTROL HEAD K62303

The control head is mounted directly onto the Nitrogen pilot gas cylinder valve and is secured by a couplingnut. When the control head is operated the firing pin shoots out (extends) by approximately 3mm.

Figure 22 Control Head

Materials:Body: BrassWeight: 2.35kg

IP55 Rating

Page 144: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

34

7.4 CONTROL HEAD WITH SWITCHES K62304

As K62303 plus switches to provide remote indication that the safety and reset pin has been inserted and asecond switch to indicate the condition of the control head.

Figure 23 Control Head with Switches

Safety/Reset Pin Switch

Orange - CommonRed - N.O.Black - N.C.

Control Head Condition SwitchGrey - CommonWhite - N.O.Yellow - N.C.

Electrical Rating

250 V a.c - 7A Resistive 7A Inductive30 V d.c - 4A Resistive 3A Inductive50 V d.c - 1A Resistive 0.25A Inductive125 V d.c - 0.4A Resistive 0.3A Inductive

Page 145: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

35

7.5 CONTROL HEAD MOUNTING BRACKET K62487

Figure 24 Standard Mounting Bracket

Material: Mild SteelFinish: Painted Black

Page 146: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

36

7.6 SAFETY AND RESET PIN K62401

This device, supplied with the control head, when screwed fully home will reset the control head causingthe firing pin to retract to its normal position.

WARNINGDO NOT ATTEMPT TO RESET WHILST STILL ELECTRICALLY OR PNEUMATICALLY ENERGISED.

When carrying out servicing or maintenance, screw the safety/reset pin fully home to inhibit (isolate) thesystem.

Retain reset pin in safe location for future use.

Figure 25 Safety and Reset Pin

Body Material: SteelWeight: 0.1kg

Page 147: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

37

7.7 INSTALLATION

The installation procedure is as follows:-

1. Install the control head mounting bracket.

NOTE: Check the distance to the 1st cylinder valve release head to ensure that the long pilot gasflexible hose K93434 can be easily coupled to the Nitrogen pilot gas cylinder valve outlet,see Figures 44 and 45.

2. Lower the control head so that its swivel nut projects through the hole in the mounting bracket andbolt onto the bracket.

WARNINGDO NOT FIT THE NITROGEN PILOT GAS CYLINDER AT THIS TIME.

3. Check the operation of the control head safety and reset.

(i) Remove the red plastic dust cap from the control head threads.

(ii) Ensure that the Safety and Reset pin is screwed fully in.

(iii) Verify that the actuating pin, see Figures 22 and 23, does not project by more than 3mm.

(iv) Check that when the Safety and Reset pin is screwed FULLY OUT and the Push-to-Firebutton of the control head is operated the actuating pin extends so that it now projects by aminimum of 6mm. If a Push-to-Fire button is not supplied, remove the port plug, Section 8.1,and push the pin in. Ensure that no dirt or foreign matter falls into the control head while theport is open. reconnect the port plug.

(v) Verify that as the Safety and Reset pin is screwed in, the actuating pin retracts, reverting to itsoriginal position when the Safety and Reset pin is FULLY IN.

Page 148: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

38

Figure 26 Control Head Mounting Bracket

TORQUE TO 5/5.5 NO

Page 149: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

39

8. CONTROL HEAD ACTUATING DEVICES

There are various options available for automatically or manually operating the control head as illustratedbelow:-

Figure 27 Control Head Actuating Devices

1. Manual Push-to-Fire Button K624122. Pneumatic Diaphragm K624593. 24V d.c Solenoid K62422B4. 24V d.c Flameproof Solenoid K93206/AX5. Remote Cable Release Assy K62489

Page 150: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

40

8.1 MANUAL PUSH-TO-FIRE BUTTON K62412

To manually operate the control head, pull safety pin and operate ‘push to fire’ button

Figure 28 Manual Push-to-Fire Button

Unscrew the port plug on the control head and screw the button fully home, as shown below.

Port Plug

Page 151: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

41

8.2 SOLENOID ACTUATORS K62422B and K93206/AX

Figure 29 Standard 24V d.c Solenoid

K62422B

Designed to meet with BS5490 IP55. The unit is prewired and supplied complete with flexible conduit.

Case Material: Aluminium Alloy.Finish: Grey Anodise.Weight: 0.77kg.

Electrical SpecificationCable:. PVCCoil resistance at 20°C: 64.5 Ohms ± 5% 24V d.c (Nominal) 8.5 Watts.

Page 152: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

42

8.3 FLAMEPROOF 24V d.c SOLENOID K93206/AX

Figure 30 Flameproof ATEX approved 24V d.c. Solenoid

K93206/AX

Designed in accordance with ATEX directive: ATEX 94/9/EC classification: for potentially explosiveatmospheres flameproof enclosure EX II 2 G Eex d II C T6 to T4

II 2 D IP65 T 85 to T135ºC

Case material: Aluminium Alloy.Finish: Epoxy Gloss Grey/GreenWeight: 1.4kg.

Suitable for offshore and marine conditions.

Electrical Specification

Coil resistance at 20°C: 16 Ohms ± 10% 24V d.c (Nominal), 16.8 Watts.

Page 153: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

43

8.4 INSTALLATION

Before installation of the standard or flameproof solenoid check the following:

1. All screw threads are clean and free of damage.

2. The tip of the plunger does not project by more than 3mm.

8.4.1 Standard Solenoid

1. Make sure that the Safety and Reset pin is screwed fully home into the control head before attachingthe solenoid.

2. Attach the solenoid to the 24mm diameter screwed port on the control head by hand, taking care notto cross thread the unit. When fully home the solenoid can be finally tightened using an open-endedspanner (27mm A/F thin section).

3. Insert the 20mm screwed thread of the cable gland, which is attached to the loose end of the flexiblecable of the solenoid, through the 20mm diameter hole located in the junction box and, using a20mm back nut tighten the gland from inside the junction box.

4. Connect the two crimp terminals to their relevant connections inside the junction box.

WARNINGENSURE THAT THE NITROGEN PILOT GAS CYLINDER HAS NOT BEEN FITTED.

5. Remove the Safety and Reset pin and energise the solenoid causing the firing pin, see Figures 22and 23, to operate.

6. To reset de-energise the solenoid and re-insert the Safety and Reset pin.

Page 154: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

44

8.4.2 Flameproof Solenoid

1. Make sure that the Safety and Reset pin is screwed fully home into the control head before attachingthe solenoid.

2. Check the solenoid nameplate for correct voltage, wattage and service. The solenoid must beinstalled only in locations covered by group II category 2 G/D enclosures and where the flammablegases present in the atmosphere have ignition temperatures higher than the temperatureclassification stamped on the nameplate. Ambient temperatures must not exceed the value stampedon the nameplate.

3. Attach the solenoid to the 24mm diameter screwed port on the control head by hand, taking care notto cross thread the unit. Once fully home the solenoid can be finally tightened using an A/F open-ended spanner.

4. Connect the solenoid to the control circuit via a ATEX approved junction box or MICC cable gland.

5. Access to the cable terminal connector is achieved by removing the four cap screws and springwashers and withdrawing the housing cover. It may be necessary to rotate the cover slightly to easewithdrawal.

6. After the cover has been removed connect the MICC cable into the terminal connector and tightenthe screws.

Operation Check

WARNINGENSURE THAT THE NITROGEN PILOT GAS CYLINDER HAS NOT BEEN FITTED.

7. Remove the Safety and Reset pin and energise the solenoid causing the firing pin, see Figures 22and 23, to operate.

8. To Reset de-energise the solenoid and re-insert the Safety and Reset pin.

Page 155: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

45

8.4.3 Control Head and Solenoid Wiring

The internal switches of the control head can be used to indicate whether the ‘Safety and Reset’ pin hasbeen inserted or the control head has been operated or reset. A suitable junction box should be used forthe connections, see Figure 31. Normally the ‘operate’ switch is not used to signal to the control panel thatthe extinguishing system has operated; the manifold mounted pressure switch is utilised instead.

Figure 31 Control Head and Solenoid Wiring

Colour State TerminalReset and Safetypin switch

RedBlackOrange

NCNOCommon

123

Operate Switch YellowWhiteGrey

NONCCommon

456

FROMCONTROLHEAD

From Solenoid 78

Recommended terminal connections to be made in a junction box.

NOTE: If a solenoid is used, connect the control panel between terminals 5 and 8, and link 6 and7.

After the control head, K62304, has been operated, the actuation signal is removed if the solenoid is wiredas shown in Figure 31.

Page 156: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

46

8.4.4 Special Instructions to comply with 94/9/EC (ATEX)

1. Area classification

Control Head Basic and Control Head c/w Switches part numbers, K62303 and K62304 respectively.

Control heads are one part of a pneumatic activation system for extinguishers. These Control heads havebeen designed and certified as a non-electric equipment for compliance to the following hazardous areaclassification:

Group II category 3 GD c T6 X

The user of this equipment should make themselves aware of the following information;

2. Placing the device into service

These Control Heads may be installed in an area classified as Zone 2 or Zone 22 or unclassified.

3. Safe use of Control Heads

Control Heads are for use only as a component of a pneumatic activation system for extinguisherscompatible with the activation pressure (65 bar at 20° C.). The Control Head solenoid activation option islimited to certified version K93206/AX.

The switched version is to be used with an intrinsically safe supply suitable for the hazard area.

Control Heads are supplied with a resetting tool that also acts as a disable device to allow maintenance onthe extinguishing system.

4. Assembling and dismantling

Control Heads are supplied complete and ready to install in accordance with KFP High Pressure CarbonDioxide Fire Protection Equipment Installation, Commissioning and Maintenance Manual 59812-400.

5. Installation

Control Head installation shall be in accordance with KFP High Pressure Carbon Dioxide Fire ProtectionEquipment Installation, Commissioning and Maintenance Manual 59812-400, except that for zone 2 orzone 22 compliance solenoid K62422B SHALL NOT be used.

6. Maintenance (service and emergency repair)

The Safety and Reset Pin must be used to disable the control head before any system maintenance isperformed refer to manual 59812-400. For maintenance of control head refer to this manual.

7. Adjustment

Control Heads have no adjustable components

8. Training

Consult KFP High Pressure Carbon Dioxide Fire Protection Equipment Installation, Commissioning andMaintenance Manual 59812-400 before use.

9. Limitations of use

Control Heads must only be used within areas specified by the hazardous area certification as indicated onthe equipment label

10. Special Parameters

The ambient temperature for this equipment is –18°C to 55°C.

Page 157: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

47

8.5 PNEUMATIC DIAPHRAGM ACTUATOR K62459

The pneumatic diaphragm actuator is used to operate the control head. The two 1/8” screwed connectorson the cover plate of the actuator allow connection to a detector line and a breather assembly.

Air pressure from the detectors deflects the diaphragm which moves the firing pin approximately 3mm intothe control head. After operation the firing pin returns to its normal position, assisted by a spring assemblywhich is located under the diaphragm.

Figure 32 Pneumatic Diaphragm Actuator

Diaphragm Housing Material: Aluminium BronzeFinish: AnodisedConnector Material: BrassFinish: Dull Nickel PlateWeight: 0.93kg

Page 158: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

48

8.6 PNEUMATIC BREATHER VENTS K62895

The pneumatic breather is a calibrated leak used in pneumatic fire detecting systems.

The purpose of the breather is to relieve slight increases or decreases of air pressure within the detectorcircuit caused by normal atmospheric temperature changes or heating of the premises. etc.

Part Number Breather Setting

K62895/5 5 SecondsK62895/10 10 SecondsK62895/15 15 SecondsK62895/20 20 SecondsK62895/25 25 SecondsK62895/30 30 SecondsK62895/100 100 Seconds

Figure 33 Pneumatic Breather Vents

Vent settings to be used (seconds)

Temperature Variation: For 1 & 2Detectors

For 3 & 4Detectors

For 5 & 6Detectors

NORMAL 15 20 25CONSTANT(Thermostatically controlled)

25 30 30

RAPID (Ovens, etc) 5 10 10

NOTES:1. A 100 second breather is used only if a pneumatic check unit is employed.2. The breather in a lock-off unit must be rated the same as the breather fitted to the

Pneumatic Diaphragm Actuator see Figure 32.

Page 159: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

49

8.7 INSTALLATION

Before installation of the pneumatic diaphragm actuator check the following:

1. That all screw threads are clean and free of damage,

2. The tip of the plunger does not project by more than 3mm,

3. That the Safety and Reset pin is screwed fully home into the control head before attaching theactuator.

After the above checks have been carried out satisfactorily install the pneumatic actuator as follows:

1. Attach the pneumatic diaphragm actuator to the 24mm diameter screwed port on the control head byhand, taking care not to cross thread the unit. Once fully home the actuator can be finally tightenedusing an open-ended spanner.

2. Attach the breather vent assembly, see Figure 32, to one of the connections on the actuator.

3. Attach the compression coupling on the copper detection tubing to the second connection.

8.8 CABLE RELEASE ASSEMBLY K62478

This device is used in conjunction with a remote pull box and cable system to manually operate the controlhead.

Figure 34 Cable Release Assy

Material: Mild steel box painted black

Page 160: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

50

8.8.1 Installation

To install the single release assembly, see Figure 35 and proceed as follows:

1. Unscrew and remove the box lid and gasket. Slacken the cable clamp locking screws and slideclamp off the inner bowden cable (use a 2.5mm A/F hex wrench).

2. Pull out the inner cable from the release assembly.

NOTE: Do not remove top cover from control head.

3. Unscrew both blanking plugs from the control head body (use a ¼” A/F hex wrench).

NOTE: A manual Push-to-Fire button, if fitted, should be unscrewed.

Figure 35 Cable Pull Ring Connection

Cable Connection Port, see Figure 35.

4. Feed in the inner cable through the blanking plug port on the “Safety and Reset” pin side of thecontrol head, through the top hole of the cable pull-ring inside the control head and out through theblanking plug port on the other side of the control head.

5. Slide the outer Bowden cable, complete with box, onto the free end of the inner cable and screwcable into the blanking port and tighten.

6. Attach the cable box to the wall at a point convenient to the remote pull cable conduit.

Page 161: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

51

Figure 36 Curvature of Cable

Curvature of Cable, see Figure 36

7. Make sure that the control head cable is not forced to bend through a radius of less than 45mm(approximately 1 ¾”) along its length.

Figure 37 Cable Release Assembly, Cover Removed

8. Slide the cable clamp into the inner cable, loop the inner cable end and feed back through the clampas illustrated above.

NOTE: With “Safety and Reset” pin screwed fully home make sure that there is approximately3mm of slack cable between the cable clamp and the cable attachment nut inside the box.Adjust if necessary.

9. Feed remote pull cable into the cable clamp and secure with the two locking screws.

10. Test for satisfactory operation with the pilot valve and cylinder assembly removed and adjust tensionof remote cable if necessary. Refit the box lid and gasket.

11. Leave the system in an operable condition.

Page 162: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

52

8.9 PULL BOX K 1114

The pull box is used where remote emergency manual operation of a system is required. The handle isconnected to the gas release device by flexible phosphor bronze cable run in mild steel conduit forprotection. Abrupt changes in direction to the routing of the manual pull line are affected by means ofenclosed brass pulleys. Part No. K 1122.

Pulley can be mounted in 90º increments.

Figure 38 Pull Box

Specification: BS5490 IP40Materials: Box-Steel painted signal red BS 381C/537

Front Cover - PlasticWeight: 1.65kg

Page 163: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

53

8.9.1 Corner Pulley K 1122

Figure 39 Corner Pulley

Materials: Brass - NaturalWeight: 0.5kg

8.9.2 Installation

To install the pull box proceed as follows:

WARNINGTO PREVENT ACCIDENTAL DISCHARGE OF THE FIRE FIGHTING SYSTEM DURING INSTALLATIONWORK, MAKE SURE THAT THE SAFETY AND RESET PIN IS SCREWED FULLY HOME INTO THECONTROL HEAD OR THE COMPLETE PILOT VALVE AND GAS CYLINDER ASSEMBLY ISUNSCREWED FROM THE CONTROL HEAD.

1. Attach the pull box using the single 7/16 (11.1mm) diameter fixing hole.

2. With front plate and glass removed, use a slotted screwdriver to remove the 7/16” Whitworthgrubscrew from the centre of the pull handle.

3. Feed the 1/8” diameter bronze cable through the pull handle, steel conduit and pulley assemblies, upto the cable clamp located inside the cable release box.

4. With the cable protruding inside the cable release box slacken the two cable-clamp locking-screwsand attach the bronze cable as shown for single release mechanism.

5. With approximately 76mm of cable protruding out through the pull handle, tie a single knot in cable.Solder the knot completely.

6. Slide the cable into the handle recess, tighten and then cut-off excess cable.

7. Re-fit the 7/16” Whitworth grubscrew to the pull handle.

Page 164: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

54

8. With the pilot gas cylinder detached from the control head, remove the Safety and Reset pin, pull thehandle in the pull box and test the system for each operation.

9. Check that the control head operates.

10. Insert the Safety and Reset pin.

11. Refit the pilot cylinder.

12. When satisfied with the operation re-locate glass and front plate and tighten using the four long 2½”long x 2BA round head screws.

13. Remove the Safety and Reset pin and hand it to a responsible person.

NOTE: All cable runs must be straight. Changes in direction must only be accomplished by theuse of pulleys; bends and dog legs must not be used.

Page 165: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

55

9. CYLINDER VALVE PRESSURE/LEVER ACTUATOR K62341

The release head is a piston device which is fitted to the cylinder valve by means of a “U” pin and can beoperated by means of independent Nitrogen gas pressure and/or by use of the manual lever. Two gaspressure ports provide the means of interconnecting a series of release heads by using flexible pilot gashoses. (K93433 & K93434)

All pilot lines must include a pilot vent (K24051) as part of the assembly.

WARNINGTHIS DEVICE IS NOT SELF-RESETTING. AFTER OPERATION THE PISTON MUST BE MANUALLYRESET BY PUSHING THE PISTON BACK ONTO ITS SEATING.

NOTE: If manually operated the lever must be returned to its original position and secured beforere-setting.

Figure 40 Cylinder Valve Pressure/Lever Actuator

MaterialsBody: BrassSeals: NitrileLever: Plated SteelSecuring Pin: Stainless SteelSafety Pin: Stainless SteelWeight: 0.4kg

Page 166: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

56

9.1 INSTALLATION

Before installation check the following:-

1. Remove Safety pin and rotate manual lever for ease of movement of both the lever and piston.

2. Return lever original position and insert Safety pin.

3. Manually reset the piston.

After these checks have been carried out satisfactorily install as follows:

(a) Remove the securing pin.

(b) Slide the release head onto the cylinder valve and refit the securing pin, lightly tap fully home.

Leave safety pin in place until commissioning system. Refer to section 19 – Maintenance.

Page 167: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

57

10. PILOT GAS FLEXIBLE LOOPS K93433 and K93434

The short pilot loop K93433 is used to interconnect the pressure / lever actuator K62341 pressure inletports on multiple cylinder systems.

The long pilot loop K93434 is used to interconnect the release head where the cylinders are installed in adouble row. It is also used to convey the pilot nitrogen gas from a system actuator to the inlet port of thefirst release head.

Figure 41 Pilot Gas Flexible Loops

Materials

Hose: Polyamide inner tube, synthetic branding/polyamide coverEnd Fittings: Brass - Natural FinishMinimum Bend Radius: 50mmTest Pressure: 207 barWeight: 50 grammes

10.1 PILOT GAS VENT K24051

This device is fitted in the last unused pressure inlet port of the release head K62341 allowing the pilot gaspressure to slowly vent (bleed) to atmosphere. The rate at which the pilot gas is vented is slow enough tomaintain adequate operation pressure in the pilot gas line far in excess of the duration of the main CO2discharge for normal flooding systems. See Datasheet 811-9040A

The bleed valve is factory calibrated to vent at 0.8 litres/min at 750psi.

Page 168: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

58

Figure 42 Pilot Gas Vent

Materials

Body: BrassWeight: 0.02kg

Page 169: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

59

10.2 PILOT GAS RIGID TUBING AND FITTINGS

On systems where either the system actuator is remote from the CO2 cylinders or when the systemincorporates directional valves the pilot gas line consists of steel (bundy) tubing and compression fittings.

Figure 43 Pilot Gas Rigid Tubing and Fittings

K

K

K K

K K K

K K

K

K

Page 170: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

60

ASSEMBLY

1. Tubing must be cut off square and all burrs and swarf removed as loose particles could damage anyseals used elsewhere in the pipeline.

2. Place tubing nut and sleeve on tube.

3. Offer the tubing to the coupling, pushing it right home so that the tubing bottoms on the tubing stopinside the fitting.* This is important as it ensures that the correct amount of tubing projects beyond the sleeve to

give a sound joint.

4. Hold the tubing square to the coupling and screw the tubing nut up finger tight so that the sleeve istrapped between the tubing nut and the seating radius of the counterbore.

5. While holding the tube firmly in contact with the tubing stop, screw the tubing nut down to areasonable spanner tightness. This varies between 3/4 and one full turn. On fittings for tubing sizesof 12mm outside diameter and over, a smear of lubricant applied to the sleeve and the threads of thetubing nut will effect a sound joint with the minimum of effort.

6. Slacken off the assembly about a ¼ turn then pinch down once again.

Where an inaccessible fitting would make the assembly of a sound joint difficult, it is recommendedthat the sleeve is pre-assembled onto the tubing. This can be done by following the above procedurebut using a fitting of the correct size clamped in a vice. The tubing assembly can then be done andreleased and transferred to the final union with the sleeve already correctly positioned.

WARNINGDo not use loctite, adhesive or tape on any part of this assembly.

Page 171: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

61

10.3 INSTALLATION

Install the correct length pilot gas flexible loops as shown in Figure 44 for single row cylinders or Figure 45for double row cylinders.

Install a pilot gas vent, see Figure 42, in the last open port of the pressure/lever actuator, Figure 40.

NOTES:

1. Do not use PTFE or other pipe sealant.

2. Do not overtighten fittings.

Figure 44 Single Cylinder Row Pilot Gas Operation

Figure 45 Double Cylinder Row Pilot Gas Operation

Page 172: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

62

11. TIME DELAY UNIT K23650

This hydraulic device can be installed in a system to ensure that personnel are given time to evacuate aprotected space following a warning of imminent CO2 discharge. It is fitted in the Nitrogen pilot gas line fromthe System Actuator thus delaying the flow of pilot gas to the CO2 cylinder pressure release heads and/orP.O.D valve for a pre-determined time of 15 or 30 seconds.

This unit is factory pre-set do not adjust. Tampering with this unit could cause failure.

Figure 46 Time Delay Unit

Page 173: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

63

Spec Factory set at 15 or 30 sec.

Material: Brass - Painted RedPart No: K23650/15 = 15 secs

K23650/30 = 30 secsWeight: 1.9 kg

11.1 INSTALLATION

1. Install vertically with the pilot gas inlet at the top.

2. Fit adaptor K90219 to both inlet and outlet pilot gas points.

11.2 TESTING

Wait approximately 1 hour before testing.

Page 174: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

64

Figure 47 Single Protected Space System

Page 175: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

65

Figure 48 Two Protected Spaces System

Page 176: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

66

Figure 49 Two Protected Spaces Requiring Different CO2 Quantities

Page 177: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

67

11.3 TIME DELAY BY-PASS VALVE K60736

This device may be used to by-pass the time delay units.

Figure 50 Time Delay By-Pass Valve

Materials: Box Mild SteelFinish: Hammer Grey

Page 178: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

68

Figure 51 Installation

Page 179: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

69

12. CO2 OPERATED PRESSURE SWITCH K60218

The universal pressure switch is a gas pressure operated device which is connected to the distributionpiping or manifold. A gas pressure of 4 bar - 110 bar is required to operate the piston which makes orbreaks electrical contacts.

When the system is activated, gas pressure forces the piston against the operating rod which movesacross the housing, operating the switch. The switch completes an electrical circuit and illuminates thesystem discharged lamp on the indicating lamp panel or operates the alarm etc. The rod extends into thetransparent cover to indicate the switch has operated.

To reset, unscrew re-setting cap (transport cover) from box, - reverse, and screw onto the operating rod.Press until switch clicks home. Remove resetting cap from rod - reverse and screw back into box.

Refer to Datasheet 811-9119

Figure 52 CO2 Operated Pressure Switch

MaterialsHousing: Aluminium CastingFinish: Red EnamelTesting: 2KV tested

¾ ” BSPT

Page 180: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

70

Inductive Rating

Power Factor 250 Volts 440 Volts 600 Volts1 30 Amps 25 Amps 20 Amps

0.74 25 Amps 20 Amps 16 Amps0.50 17.5 Amps 14 Amps 11.5 Amps

D.C. Rating

Resistance 220 Volts 500 VoltsLoadings 30 Amps 15 Amps

Page 181: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

71

12.1 INSTALLATION

Before installation of the pressure switch (see Figures 52), check the following:

1. The ¾” BSP inlet thread is clean and free of any damage.

2. When manually operated, using the visual indicator and re-setting cap, the switch roller is in thecoupler channel and the operation is smooth with no binding.

After the above checks have been satisfactorily carried out, install the pressure switch as follows:-

1. A ¾” BSP screwed connection is required on the end of the manifold, attach a ¾” BSP galvanisedhexagon nipple.

2. Attach the pressure switch or, wall mount the switch, make up all pipework to suit the site location ofyour pressure switch making sure that there is a ¾” BSP galvanised union in this line for each ofinstallation and/or removal of equipment.

3. To the ¾” BSP outlet connection on the pressure switch attach a ¾ BSP galvanised hexagon nippleand one half of the union as mentioned in (2) above.

4. Connect the pressure switch to the pipework via the union and hand tighten.

5. Mark the two pressure switch fixing holes on the wall or framework.

6. Loosen the union nut and remove the pressure switch.

7. Drill the two holes.

8. Reconnect the pressure switch to the pipework and tighten the union nut.

9. Fix the pressure switch to the wall or framework.

Alternatively, the switch may be wall mounted by adapting the ¾ threads to 3/16” ENOT and using bundytube to connect.

Page 182: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

72

13. CO2 OPERATED PRESSURE TRIP K17554

The pressure trip is fitted into the CO2 distribution piping and is used to automatically release ventilationshutters, fire curtains, ducting dampers, fuel valves, etc. CO2 pressure of approximately 2 bar is sufficient tooperate the piston and unlatch -the catch mechanism.

Figure 53 Pressure Trip

Materials: Body - GunmetalFinish: Nickel Plate

Page 183: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

73

13.1 INSTALLATION

Figure 54 Installation

NOTES:

• Always install the pressure trip in a vertical position as shown.

• Dimension from top of doorframe is typical & should be adhered to where possible.

• Use PTFE tape on all screw threads.

• The maximum load that can be suspended from a pressure trip is 100lb (45kg).

Install the pressure trip as follows:-

1. To the ¾” BSP male screwed connection on the pressure trip attach a ¾” BSP elbow a suitablelength of ¾” BSP galvanised pipe and one half of a ¾” BSP union.

2. Offer the pressure trip assembly up to the CO2 distribution piping and hand tighten the union nut.

3. Making sure that the pressure trip is located in the centre of the doorway and at a suitable verticaldimension above the door frame so as not to hinder the operation of the equipment mark the one offfixing hole on the wall.

4. Loosen and disconnect the pressure trip assembly.

5. Drill the pressure trip fixing hole on the wall.

6. Reconnect the pressure trip assembly to the CO2 pipework.

7. Using a adequate wall fixing to attach the pressure trip to the wall.

8. Once attached to the wall finally tighten the union nut.

9. Attached the cable & cable ring to the pressure trip.

Page 184: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

74

14. CO2 DISCHARGE NOZZLES

There are various nozzles suitable for either “total flooding” and/or local application systems. In all cases itis essential that they are installed in their correct locations as defined by the code number stamped on thenozzle body.

14.1 MULTIJET NOZZLE K61792 AND K61793

These nozzles are the standard carbon dioxide discharge nozzles. The horn has been developed toprevent the scattering of burning material that can take place with a high velocity discharge.

Datasheet 811-9148

Figure 55 Multijet Nozzle

Environment: Industrial/Offshore/MarineMaterial: Horn - mild steel

Nozzle - brassFinish: Horn - black paint.

Nozzle - NaturalWeight: K61792 N13 - N18 :- 0.8 kg approx.

K61793 N3 - N12 :- 0.6 kg approx.

Page 185: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

75

14.2 FLANGED MULTIJET NOZZLE K5814

The flanged carbon dioxide horn is designed for use in those areas where the nozzle may become blockedby dirt or the process being protected. The force of the discharge automatically blows the disc clear. Threediscs are available:-

Refer to Datasheet 811-9139

Figure 56 Flanged Multijet Nozzle

1. Bakelite - temperatures up to 200°C and ambient pressures below 50 psig.2. Tin Foil - temperatures up to 400°C and ambient pressures below 25 psig. (used where

fragmented pieces cannot be tolerated)3. Mica - temperatures above 400°C and ambient pressures below 50 psi.

The flanged horn may be fitted to ductwork by the addition of the appropriate adaptor.

Material: Body: Aluminium Nozzle: BrassFinish: Body: Natural Nozzle: NaturalWeight: 0.9 kg approx.

Page 186: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

76

14.3 FLANGED NOZZLE DUCT ADAPTORS K61420A-D

The range of duct adaptors is designed for those situations where it is required to fit the flanged CO2 nozzle(K5814 N3 - N8) to circular or square section ductwork.

Figure 57 Flanged Nozzle Duct Adaptor

Material: Cast aluminium.Finish: Black paint

NOTE: 4 - 5/16" Whit. Hex. Hd. Screws C/W nuts and washers together with joint sealing tapesupplied with each adaptor.

Adaptor Assembly Weight (approx) Ducting SizeK61420A 1.3kg 610mm DiaK61420B 1.3kg 457mm DiaK61420C 1.3kg 305mm DiaK61420D 1.1kg Flat

Page 187: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

77

14.4 DUCT NOZZLE K13045

The CO2 nozzle and duct adaptor is used to protect ductwork in areas where space is limited.

Datasheet 811-9151

Figure 58 Duct Nozzle

Material: Mounting plate : mild steelNozzle : brass

Finish: Mounting plate : zinc plated and passivated.Nozzle : natural

Weight: 0.4kg approx.

Page 188: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

78

14.5 FAN TYPE NOZZLE K6490

Fan type nozzles are designed to be mounted at the sides of the protected equipment and to direct carbondioxide across the hazard.

Figure 59 Fan Type Nozzle

Material: Body: Grey cast iron. Nozzle: Brass

Finish: Body: Black paint. Nozzle: Natural

Weight: 2.6kg approx.

Page 189: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

79

15. PNEUMATIC DETECTION - HEAT ACTUATED DEVICES

The “Rate of Rise” system is a thermo-pneumatic system consisting of one or more detectors connected toa release actuator in which there is a diaphragm and a compensating vent.

15.1 PNEUMATIC RATE OF RISE DETECTOR K18724

The pneumatic detector is a hollow copper chamber of 12cc capacity containing air at normal atmosphericpressure. It is fixed to the ceiling or in any other positions best suited to site conditions. The function of thedetector is to absorb heat thereby increasing the air pressure within it which is then transmitted throughsmall bore copper capillary tube running in protective steel conduit to a release actuator. Operation of thediaphragm in the release actuator will discharge the extinguishing agent or initiate an alarm.

Figure 60 Pneumatic Rate of Rise Detector

Page 190: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

80

15.2 PNEUMATIC FIXED TEMPERATURE DETECTOR K18689

This detector works on the same principle as the Rate of Rise detector but is fitted with a slug assemblycontaining a fusible alloy disc which will melt at a predetermined temperature. These are used to protectareas which are subjected to rapid increases in ambient temperatures such as ovens, kitchens, boilerhouses, lantern lights, etc.

Be aware that capillary tubing can act as a rate-of rise detector so routes outside the rapid change areamust be found.

K18689 = Pneumatic Fire Detector less slug assembly, washers and identification disc.

Order appropriate slug assembly kit for fitting on site and for spares. (see table)

Slug assembly kit comprises - slug assembly, 2 washers, identification disc with fitting screwand fitting instructions.

Note: Slug assembly kits are available in a limited range of temperatures. Please contact Kidde FireProtection for further details.

Figure 61 Pneumatic Fixed Temperature Detector

Page 191: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

81

15.3 PNEUMATIC CHECK UNIT K24412

The pneumatic check is used on pneumatic type fire detection systems incorporating Rate of Risedetectors.

The checks are used to divide the detectors into groups of no more than six. Each group is, in this way,isolated, so that air pressure rise caused by a detector sensing fire can pass through the check to thesystem actuator etc, without being dissipated into other detector groups.

The pneumatic check is formed by making use of silicone fluid. The unit being filled with fluid at the factory.No adjustment should be necessary, but check fluid level.

Installation

This unit must be installed in a vertical position as shown above. Fit pneumatic breathers in the two inletports, see Figure 62 for correct setting.

Figure 62 Pneumatic Check Unit

K 6 2 8 9 5

Page 192: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

82

15.4 PNEUMATIC LOCK-OFF UNIT K24300

An extinguishing system utilising non-electrical heat detectors can be fitted with a pneumatic lock-off unit inorder to prevent automatic actuation when the area protected by the system is occupied. With the unitswitched to AUTOMATIC & MANUAL the pneumatic signal from the heat detectors is allowed to passthrough the unit to the extinguishing system.

However, when the unit is switched to MANUAL ONLY the signal is directed to a pneumatic switch fittedwithin the Lock-off unit which can thus provide remote indication, and is prevented from actuating theextinguishing system. A second Pneumatic breather of the same vent setting as the one fitted to theextinguishing system actuator must be fitted to the pneumatic switch in the Lock-off unit.

Figure 63 Pneumatic Lock-Off Unit

Page 193: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

83

15.5 BELLOWS AND MICROSWITCH ASSY K20057

The bellows and microswitch assembly is used to convert an air pressure signal received from a non-electrical heat detection device into an electric signal for indication or the operation of a releasemechanism.

The assembly consists of a pair of aluminium castings enclosing a diaphragm and connected to amicroswitch. On receipt of an air pressure signal a spindle housed in the upper casting actuates themicroswitch.

The unit is self-resetting when the air pressure signal is removed. No maintenance is required. Orderappropriate Pneumatic Breather for fitting on site, see Figure 64.

Figure 64 Bellows and Microswitch Assembly

Page 194: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

84

15.6 PNEUMATIC CAPILLARY TUBE, CONDUIT AND FITTINGS

Figure 65 Pneumatic Capillary Tube, Conduit and Fittings

Page 195: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

85

15.7 CO2 OPERATED SIREN K18307

This device can be fitted into the main CO2 feed pipe to provide an audible alarm for the duration of the CO2discharge.

Figure 66 CO2 Operated Siren

Material: Body - Aluminium CastingFinish: Painted Red

Page 196: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

86

16. ODORISER ASSEMBLY K62586

At normal atmospheric pressures and temperatures, the extinguishing gas is colourless and odourless. Toenable CO2 to be detected during and following a discharge an odoriser shall be fitted. The unit must befitted in the main pipe run so that the pressure of the gas passing through the pipe bursts a seal in the unitand releases a liquid odorant into the gas system. Burst pressure range 20 to 40 psi.

Each unit contains 30cc of odorant which is sufficient to produce a positive and identifiable lemon smell in aprotected space of up to 1,400 cubic metres volume.

Figure 67 Odoriser Assembly

Material: Aluminium AlloyFinish: Black anodise

NOTES:

1. This unit must be installed in the vertical position with the cylinder uppermost.

2. Adaptor K22152 can be supplied as an optional fitting, see Figure 68. This incorporates acheck valve so that in the event of the gas being released while the odoriser is removedthere is no loss of gas from the pipe.

Figure 68 Odoriser Check Valve

Material: Brass

Page 197: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

87

17. CO2 WARNING LABELS

MATERIAL:- 22 SWG ALUMINIUM

Figure 69 Entrance Door Warning Label

Part Number K93681

Page 198: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

88

Figure 70 Manual Control Point Label

Part Number K93680

Page 199: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

89

PART 2 COMMISSIONING

18. COMMISSIONING

This chapter described the commissioning procedure under the following headings:

1. Visual Checks

2. Mechanical Function

18.1 VISUAL CHECKS

Before commencement of commissioning tests visually check the following:-

1. Check that the installation conforms to the engineering drawings. Any deviations from drawings mustbe reported.

2. All work, e.g. electrical wiring, carried out by other contractors has been completed satisfactorily.

3. Check the protected area for confinement of the extinguishing agent, i.e. that no passage is allowedto other spaces through floor or ceiling voids, ductwork, holes in partitions or vents, unless allowancehas been made.

4. Check that all manual controls are accessible and correctly identified.

5. Check that the discharge nozzles are unobstructed and are adequately secured. Check that thenozzles comply with sizes shown on the drawings.

6. Check that the container and valve manifolds are correctly sized, and that check valves and PODvalves are installed for correct directional flow.

7. Check the manifold-to-container installation for undue strain on connecting loops because incorrectinstallation can cause service problems.

8. Check the containers are installed in an accessible location, that the area is clean, dry and ventilatedand meets the safe temperature requirements.

9. Check that all system controls, such as valves, lock off, pull boxes, manually or electrically operateddevices, are accessible to operating personnel. If located outdoors ensure that they conform to therequired standards and that adequate shelter has been provided.

10. Check that pipes and fittings are sized in accordance with the drawings and are adequately secured.All piping must be rigidly secured to the nozzle to prevent damage from recoil.

11. Check that all warning labels and notices give correct information for system operation and that theyare suitably located.

12. Check weigh containers to ensure nett content is in accordance with the requirements.

Page 200: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

90

18.2 MECHANICAL FUNCTION

WARNINGDO NOT PROCEED WITH ANY FUNCTIONAL TESTS UNTIL EVERY PRECAUTION HAS BEENTAKEN TO PREVENT ACCIDENTAL DISCHARGE.

18.2.1 General

If the control head is connected to the pilot gas cylinder check as follows:-

1. Make sure that the “Safety and Reset” pin is screwed fully home.

2. Unscrew the pilot gas cylinder from the control head.

3. Remove the “Safety and Reset” pin.

4. Check the distance moved by the firing pin.

5. Energise the solenoid, if fitted, from the control panel. The solenoid operates the control headthereby causing the control head firing pin to be moved downwards by a minimum distance of 3mmthus giving a total projection of 6mm. This insures that the solenoid and control head are bothoperable and have functioned correctly.

6. After the test has been carried out satisfactorily reset the control head by screwing the “Safety andReset” pin fully home and checking that the firing pin does not project more than 3mm.

18.2.2 Manual Push-to Fire

1. Remove the “Safety and Reset” pin.

2. Remove pin from “Push-to Fire” button

3. Manually fire the control head by operating the “Push-to-Fire” button as shown in Section 8.1

4. When the manual operation of the “Push-to-Fire” button has been proved, reset the control head byscrewing the “Safety and Reset” pin fully home.

5. Replace pin into “Push-to fire” button.

18.2.3 Pull Box

WARNINGDO NOT PROCEED WITH ANY FUNCTIONAL TESTS UNTIL EVERY PRECAUTION HAS BEENTAKEN TO PREVENT ACCIDENTAL DISCHARGE.

1. Remove the “Safety and Reset” pin from the control head.

2. Remove the front cover and glass from the pull box unit.

3. Pull the handle in the pull box unit and manually fire the control head.

4. When satisfied, reset the control head by screwing the “Safety and Reset” pin fully home.

5. Reset the cable arrangement as described in Section 8.8.

6. Relocate the glass and front cover plate to pull box unit.

Page 201: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

91

18.2.4 Pneumatic System

If the control head is to be operated using a pneumatic diaphragm actuator and HAD detection system, amanometer test, see Figure 71, shall be carried out.

Figure 71 Manometer Test System

Specification: Designed for pressure or vacuum up to 8” water gauge.Material: Base and Cover Al. AlloyPaint: Red EnamelPart No: K17523

Page 202: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

92

Before testing the pneumatic actuator and HAD system, ensure that the manometer water level is zeroedand check for leaks as follows:-

1. Compress the rubber bulb slightly and plug both the simplifix coupling and the open end of the glasstee piece near the bulb - a wetted thumb is usually adequate for this purpose. Release the pressureon the rubber bulb, thus causing the water to rise up the right hand side of the simplifix coupling tubeuntil a reading of 6” water gauge is shown and holds level until the pressure is relieved by removingthe thumbs from the open ends.

Test the HADs, if necessary, as follows:-

1. Remove the HAD from the system and immerse it in water the temperature of which is some 10°Cabove ambient. but does not exceed 50°C. There must be no air leaking from the HAD.

2. If satisfactory replace the HAD in the system making sure all water has been removed andconnections are tight.

Page 203: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

93

Test that the system is airtight, as follows:-

1. Remove the pneumatic breather from the breather connection on the diaphragm actuator.

2. Connect the manometer to the breather connection on the diaphragm actuator as shown, and createa vacuum as described above.

Page 204: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

94

3. After an initial pressure drop there should be no further drop for one minute.

4. With the manometer still connected, test that the system is free from blockage, by slightly heatingeach HAD in turn and observing that a slight pressure is built up in the system each time; adisplacement of ½” water gauge is sufficient.

After this test has been carried out satisfactorily proceed to check the rating of the pneumatic breather asfollows:-

1. Remove the breather from the pneumatic actuator and connect it to a manometer. Set the waterlevel in line with the top edge of the metal indicator of the manometer.

NOTE: Before testing ensure that the breather is situated above the level of the manometer toprevent any possibility of water being blown into the breather.

2. Create a small vacuum (approximately 3” difference in water level in the two limbs of themanometer). As the water returns slowly to its normal position, note the time taken for the water topass through the “visor space” of one inch of the indicator. This is the time taken for the pressure todrop by 2” of water pressure. The time should be between 5 and 100 seconds depending on thebreather used; the specified time stamped on the breather.

After this test has been carried out satisfactorily re-connect the breather to the pneumatic actuators.

Page 205: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

95

The operation of the system is checked as follows:-

1. Disconnect the pneumatic detector line from the actuator.

2. Connect the manometer to the pneumatic connection on the actuator as shown below:

3. Remove the “Safety and Reset” pin.

4. Using the rubber hand bulb gently pump until the pneumatic actuator operates the control head.

NOTE: The pneumatic actuator should operate the control head only between 1" and 3" of watergauge, as shown in the manometer operating range above.

Page 206: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

96

5. Re-place the “Safety and Reset” pin, ensuring that it is screwed fully home.

6. Re-connect the pneumatic detection line to the pneumatic actuator.

WARNINGDO NOT ATTEMPT TO RESET THE SYSTEM UNTIL THE PRESSURE IN THE HAD LINE HAS BEENRELEASED.

18.2.5 Pressure/Lever Actuator and POD Valves

Details of the pressure/lever actuator are given in Part 1, Chapter 9.

To check the pressure /lever actuator and POD valves as follows:

1. Remove the pressure/lever actuator complete with pilot loops and vents from the container valvesand secure them, making sure that they are clear of the container valves. The entire pilot gas systemmust remain intact.

2. Remove the safety lock pin from each actuator and check the manual operation.

3. When satisfied with the manual operation of the release heads check the POD valves, if installed, byconnecting a pilot gas (Nitrogen) test cylinder to the head.

Remove Safety Lock Pin from each POD valve and check for manual operation (Valves up to 2”).

NOTE: If the POD valves are fitted with switches check that the indication has been given at thecontrol panel that the POD valve is open.

4. When satisfied with the manual operation of the POD valves reset and re-insert the Safety Lock pins.

5. With the pressure/manual release heads still removed, depress the Push-to-Fire button on thecontrol head thereby releasing the pilot gas (Nitrogen) into the pilot line causing the pressure/manualrelease heads to operate.

NOTE: If POD valves are installed in the system check that these have been opened beforechecking the pressure/lever actuator

5. After the POD valves and/or pressure/lever actuator have functioned correctly re-set each controlhead by screwing the “Safety and Reset” pin fully home.

7. Push piston inside pressure/lever actuator back to set position.

8. Remove the pilot gas (Nitrogen) test cylinder from the control head.

9. Visually check that the plunger assembly has returned to its normal position. When satisfied, re-connect the pilot cylinder and the pressure/lever actuator to the container valves. Tighten the runningnut at the control head/pilot cylinder interface.

18.2.6 Pressure Trip

Check the pressure trip mechanism, if incorporated in the CO2 system, as follows:-

1. Physically lift the pivoted lever allowing relevant equipment, e.g. fire curtains or dampers, to beoperated.

2. After manual operation of the pressure trip has been carried out successfully, re-set all fire curtains,dampers etc.

Page 207: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

97

3 To demonstrate operation of the pressure trip assembly, release one container from the main bank.Disconnect all pressure levers actuators and CO2 outlet hoses from the cylinders not required for thetest.

WARNINGDO NOT DISCHARGE CO2 WHILE THERE ARE PERSONNEL PRESENT IN THE AREA. THEENGINEER CARRYING OUT THE TEST MUST OBSERVE THE SAFETY REGULATIONS GOVERNINGTHE USE OF CO2.

4. If POD valves are installed in the main distribution line, remove the Safety Lock pins and manuallyopen.

5. Discharge the CO2 cylinder and check that the trip assemblies have all functioned correctly.

6. Re-insert the Safety Lock pin to the CO2 container.

7. Re-set the pressure trip assemblies.

8. Reconnect cylinders and replace discharged cylinder.

18.2.7 Pressure Switch

If a pressure switch assembly is installed in the main CO2 line check that it has operated as follows:-

1. Check that an alarm signal has been given on the main control.

2. Check that the pressure switch operating rod has extended into the transparent cover.

3. When satisfied re-set the pressure switch.

4. Manually close the POD valves and re-insert the Safety Lock pins.

5. Disconnect the empty CO2 container and reconnect the remaining cylinder and replacement.

Page 208: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

98

PART 3 MAINTENANCE

19. MAINTENANCE

This part of the manual describes procedures which enable a proficient Service Engineer to undertake theregular inspection and testing of a Kidde Fire Protection CO2 System safely in accordance with therecommendation of BS 5306 Part 4.

Before going to site the Service Engineer should obtain the relevant details and drawings of the systems tobe serviced and refer to report of previous service visits and of fault call-outs since the last service.

The Engineer’s signature on the Service Report and on the record card after carrying out the work, isconfirmation that the system, on that day, is in complete operational order. It is an advantage to have awitness to this fact, and he should therefore encourage the Customer’s representative to accompany himwhile he does the work.

The first action to take, when arriving at site, is to report to the customer’s representative and to ask if thereare any specific instructions with which to comply.

Ask if any particular problems have arisen since the last service visit.

Ask if any fires have occurred and how the system performed.

Similarly, record any false or accidental operation and get reasons.

If it is necessary to take some action which may cause inconvenience to the Customer, ask his permissionfirst.

Notify all concerned that the fire protection system is being maintained and may be inoperative.

Work systematically and in a clean, tidy and professional manner.

Consider the possibility of genuine fire alarm occurring while you are working on the system and makeappropriate arrangements.

Prepare a service report. Submit a copy to the Client, one to the Service Manager and retain a copy.

Service visits should be on a six-monthly (minimum) basis.

19.1 PRELIMINARY CHECKS

Before commencement of maintenance work check the following:-

1. Check the installation for any structural alternation that could affect the efficiency of the system.

2. Check the protected area for confinement of the extinguishant. If the system has been altered in anyway, and/or if the customer’s building or plant has been modified since the last inspection visit, thismust be noted on the Service Report. The Client must be informed of any factor jeopardizing the fireprotection system.

Check if doors and windows are being propped open and would not be shut in the event of a systemoperation. Report this to the Customer and note it on the report sheet.

Page 209: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

99

3. Check that all manual controls are accessible, correctly identified and have not become obscured.

4. Check that the discharge nozzles are unobstructed and are adequately secured.

5. Check that all warning and instruction labels are clearly visible and legible. Check that all necessarysafety precautions and operational instructions are clearly stated.

6. Check that the paintwork is in good condition.

7. Check that containers are accessible and that the area is clean, dry and ventilated.

8. Check that pipes and fittings are adequately secured. All piping must be rigidly secured at the nozzleto prevent damage from recoil.

9. Check that all system controls, such as valves, lock-off units, pull boxes, manually or electricallyoperated devices, are accessible to operating personnel. Any damage must be noted and rectifiedafter obtaining the customer’s official order number for the additional work. Rectification work shouldbe recorded on a report sheet separate from the service report sheet.

19.2 COMPONENT FUNCTION TESTS

WARNINGDO NOT PROCEED WITH ANY FUNCTIONAL TESTS UNTIL EVERY PRECAUTION HAS BEENTAKEN TO PREVENT ACCIDENTAL DISCHARGE. ENSURE THAT ALL PERSONNEL IN PROTECTEDAREAS KNOW THAT YOU ARE THERE AND OF THE WORK YOU ARE DOING.

19.2.1 General

1. Check that the manifold bracket fixings are secure.

2. Check that the manifold-to-container discharge valve couplings are tight.

19.2.2 Control Head

Check the control head as follows:-

1. Make sure that the “Safety and Reset” pin is screwed fully home.

2. Unscrew the pilot gas cylinder from the second head.

3. Remove the “Safety and Reset” pin.

4. Energise the solenoid from the control panel or operate the HAD detection system. The solenoidplunger operates the control head causing the firing pin to be moved downwards by a minimumdistance of 3mm, (6mm projection) proving that the solenoid and control head are both operable andhave functioned correctly.

5. Check the distance moved by the firing pin. Reset the control panel and/or HAD system.

NOTE: The HAD or the solenoid would be damaged if the control head is reset whilst either ofthem is in the activated mode.

6. After the test has been carried out satisfactorily, reset the control head by screwing the “Safety andReset” pin fully home and checking that the firing pin does not project by more than 3mm.

Page 210: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

100

Push-to-Fire Button

7. Remove the “Safety and Reset” pin.

8. Manually fire the control head by operating the “Push-to- Fire” button.

9. When the manual operation of the “Push-to-Fire” Button has been proved reset the control head byscrewing the “Safety and Reset” pin fully home.

Pull Box

Check the operation of the pull box.

10. Remove the “Safety and Reset” pin.

11. Remove the front cover and glass from the pull box unit.

12. Pull the handle in the pull box firmly and manually fire the control head.

13. Rest the pull cable arrangement.

14. When satisfied reset the control head by screwing the “Safety and Reset” pin fully home.

15. Relocate glass and front cover panel to pull box unit.

Pilot Gas Cylinder

16. Screw the “Safety and Reset” pin fully home.

17. Check the pressure is approx 65 bar. If it is below 55 bar the container should be refilled.

Reinstatement

18. Refit the pilot gas cylinder to the control head.

19.2.3 Pressure/Manual Release Heads and POD Valves

To check the pressure/manual release heads and POD valves proceed as follows:

1. Remove the pressure/manual release heads complete with pilot loops and vents from the CO2container discharge valves. The entire pilot gas system must remain intact.

2. Remove the Safety Lock pin from each release head and check the manual operation. Manuallyreset the release head piston and refit the Safety Lock pins when satisfied.

3. Remove the Safety Lock pin from each POD valve and check for manual operation.

Page 211: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

101

NOTE: If the POD valves are fitted with indicator switched check that the indication has beengiven at the control panel that the POD valve is open.

4. When satisfied with the manual operation of the POD valves reset and re-insert the Safety Lock pins.

5. Connect a Nitrogen pilot gas test cylinder to the control head and connect the pilot loop. With thepressure/manual. release heads still removed from the CO2 cylinder, operate the control headthereby releasing the pilot gas (Nitrogen) into the pilot causing the pressure/manual release heads tooperate.

NOTE: If POD valves are installed in the system check that these have opened before checkingthe pressure/manual release heads.

6. Check that there are no leaks in the pilot gas system and that the pilot vent bleed, K24051, operatescorrectly. Sufficient pressure to operate the pressure/manual release heads (and POD valves iffitted) should be maintained in the system for a MINIMUM OF TEN MINUTES.

7. After the POD valves and/or pressure/manual release heads have functioned correctly re-set thecontrol head by screwing the “Safety and Reset” pin fully home.

8. Disconnect the pilot line from the pilot gas cylinder and remove the pilot gas cylinder from the controlhead. The pilot gas line will now be vented.

9. Manually reset the piston and visually check the plunger in each pressure/manual release head.

10. Reset the control head and replace the test pilot gas cylinder with the full pilot gas cylinder. Tightenthe running nut at the control head/pilot cylinder interface.

11. When satisfied, re-connect the pressure/manual release heads to the CO2 container dischargevalves.

19.2.4 Pressure Trip

The trip may be operated from the pilot line or from the discharge pipework. Check the pressure tripmechanism if incorporated in the system as follows:-

1. Physically lift the pivoted lever as shown in Figure 53 etc, allowing relevant equipment, e.g. firecurtains or dampers, to be operated.

2. After manual operation of the pressure trip has been carried out successfully, re-set all fire curtains,dampers etc.

3. To demonstrate operation of a pressure trip assembly, which is operated from the dischargepipework, release one CO2 cylinder or connect a portable CO2 extinguisher to the manifold.Disconnect all other cylinders.

WARNINGDO NOT DISCHARGE CO2 WHILE THERE ARE PERSONNEL IN THE AREA. THE ENGINEERCARRYING OUT THE TEST MUST OBSERVE THE SAFETY REGULATIONS GOVERNING THE USEOF CO2.

4. If POD valves are installed in the main distribution line, remove the Safety Lock pins and manuallyopen.

5. Discharge a CO2 cylinder or portable CO2 extinguisher, and check that the trip assemblies have allfunctioned correctly.

Page 212: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

102

6. Re-set the POD valve and re-insert the Safety Lock pin to the CO2 container.

7. Re-set the pressure trip assemblies.

19.2.5 Pressure Switch

If a pressure switch assembly is installed in the main CO2 line, check the correct operation as follows:

1. Remove the clear plastic spindle cover, reverse and screw it onto the spindle.

2. Check that an alarm is given when the spindle is pulled out.

3. When satisfied re-set the pressure switch. Chapter 12.

NOTE: The switch may be pressure tested by connecting a CO2 container onto the distributionpipework.

19.3 INSTRUCTIONS FOR COMMISSIONING THE SYSTEM AFTER ITS OPERATION

1. Refit the cylinder transport caps. Remove the empty CO2 cylinders.

2. Refill the CO2 cylinders or replace with fully charged cylinder and secure.

3. If distribution valves are fitted check that they are shut.

4. Check nozzles’ orifices for debris; clean if necessary.

5. Re-set all system ancillaries, including pressure switches, pressure trips, dampers, curtains, door orwindow shutters, ventilators, remote lock-off services and pull boxes.

6. Reset each control head by screwing the “Safety and Reset” pin fully home. Remove the “Safety andReset” pins and leave them in the possession of an authorised person.

7. Replace the empty pilot gas cylinder with a new or refilled assembly.

Page 213: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

103

PART 4 TERMS AND CONDITIONS

20. TERMS AND CONDITIONS

Kidde Fire Protection Services LTD1.0 In these Conditions, the Seller means KIDDE FIRE PROTECTION SERVICES LTD, the Particulars of Contract

are the details of the Contract set out overleaf, the Buyer and the Goods are respectively the person and theproducts specified in the Particulars of Contract as such. Appointed Person means a director or appointedmanager of the Seller, and the Contract means the Contract for the sale of the Goods by the Seller to the Buyercomprising the Particulars of Contract and these Conditions. These Conditions shall apply to all contracts of salewith the Seller in relation to the goods and services supplied by the Seller.

Formation and Parties2.0 No express terms other than those contained in these Conditions and the Particulars of Contract shall be part of

the Contract, and the Contract may only be varied in writing by an Appointed Person. No representations orwarranties relating to the Goods or advice or recommendation on the use of the Goods are binding on the Sellerunless confirmed by the Seller in writing in response to a written request of the Buyer specifically referring to thisCondition.

2.1 The Contract may be cancelled by the Buyer only with the Seller's written consent which, if given, shall be on theexpress condition that the Buyer shall pay to the Seller a cancellation charge commensurate with the Seller'scosts incurred up to the date of cancellation plus the Seller's loss of profit or, at the Seller's option, a sum equal toten per cent of the Contract Price.

2.2 Unless otherwise specified, quotations made by the Seller shall automatically lapse if no order is received by theSeller within 30 days of the date of quotation. None of the Seller's distributors, agents or employees areauthorised to conclude contracts orally or over the telephone, and quotations, statements in price lists, or salesliterature and advertisements do not constitute offers. No contract for the sale of Goods shall be concluded untilthe Seller has accepted an order of the Buyer by sending to the Buyer an Acknowledgement of Order signed byan Appointed Person.

2.3 The Buyer warrants that all information which it has given to the Seller prior to entering into the Contract is trueand correct and the Seller reserves all its rights where it subsequently discovers such information is incorrect.

Delivery3.0 If any delivery time is specified in the Particulars of Contract, this period shall commence on the later of the date

of the Seller's written Acknowledgement of Order and the date the Seller receives all the information necessary toallow it to proceed without interruption, or if the Buyer requests any variation to the Contract, the date of theSeller's written confirmation of its agreement to such variation.

3.1 Although the Seller will endeavour to complete the Contract within any specified delivery time or by any specifieddelivery date, that time or date is an estimate only and the Seller shall not be liable for any reasonable delay indelivery.

3.2 Any delivery time specified shall (in any event) be extended by any period or periods of Force Majeure duringwhich the manufacture or delivery of the goods by the Seller under the Contract is delayed owing to fire,explosion, flood, storm, sabotage, strikes (official and unofficial), riot, acts of war (whether war be declared or not)shortage of labour, power, or materials, delay by the Seller's suppliers, civil commotion, accidents, plantbreakdowns, technical difficulties connected with the manufacture or adaptation of the Goods to the Buyer'sdesign or specification, seizure or other action by or compliance with an order of an apparently competentauthority and any other event or circumstance beyond the control of the Seller.

3.3 The Seller shall be entitled to withhold delivery of any Goods if at the time delivery is to be made payment is dueby the Buyer to the Seller on any account whatsoever.

3.4 The delivery of a greater or lesser quantity of the Goods than the quantity ordered, of other Goods not ordered, orof Goods only some of which are defective, shall not entitle the Buyer to reject Goods that were ordered and arenot defective.

3.5 Unless otherwise stated, delivery shall be deemed to take place when the Goods are delivered to the deliveryaddress specified in the Particulars of Contract or if not so specified, at the principal place of business of theBuyer known to the Seller.

3.6 If the Buyer fails to accept delivery of the Goods in accordance with the Contract the Seller may (without prejudiceto its other rights against the Buyer) store the Goods at the sole risk and cost of the Buyer.

3.7 The Buyer shall inspect the Goods immediately on delivery thereof and shall within five days from such deliverygive notice to the Seller of any matter or thing by reason thereof the Buyer may allege that the goods are not inaccordance with the Contract or are defective in material or workmanship. If the Buyer shall fail to give suchnotice the Goods shall be conclusively presumed to be in all respects in accordance with the Contract and free

Page 214: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

104

from any defect which would be apparent on reasonable examination of the Goods and the Buyer shall, asbetween the Buyer and the Seller, be deemed to have accepted the Goods accordingly.

3.8 The Seller reserves the right to make delivery by instalments and invoice and be paid for each installmentseparately. Each installment shall be deemed to constitute a separate agreement subject to the terms of theContract and no failure of or delay in delivery of any installment nor any defect in the contents thereof shall entitlethe Buyer to treat the Contract as repudiated with regard to any remaining instalments.

Retention of Title4.0 Notwithstanding delivery, title to the Goods shall not pass to the Buyer until all sums due on any account

whatever by the Buyer to the Seller have been paid in full. Until such time the Buyer will hold the Goods as baileeof and in a fiduciary capacity for the Seller and will:(i) keep the Goods marked or stored separately from other goods, so as to be identifiable as the property of theSeller;(ii) deliver the Goods up to the Seller on demand; and(iii) permit the Seller or its agents to enter upon the Buyer's premises in order to retake possession of theGoods.

4.1 Notwithstanding that the property in all Goods to be delivered to the Buyer by the Seller will remain vested asaforesaid until the Seller has received payment in full therefor, the risk of damage to or loss of all or any suchGoods will pass to the Buyer upon delivery in accordance with the Contract unless the Buyer shall fail to acceptdelivery whereupon the risk shall pass to the Buyer on the earliest date on which the delivery could have beenmade but for such failure on the part of the Buyer.

Price5.0 Unless otherwise stated in the Particulars of Contract, the Contract prices for the Goods shall be:

(i) exclusive of VAT, taxes or duties levied on the Seller in the Buyer's country for which the Seller shall beentitled to make additional charges, and shall be exclusive of the costs of delivery and associated packagingand insurance costs which shall be charged separately.

(ii) subject to increase by the Seller to reflect any variation in the delivery schedule for or design, quantities orspecifications of the Goods made at the request of the Buyer or any delay caused by the failure of the Buyerto provide adequate information or instructions to the Seller.

Payment6.0 Unless otherwise specified in the Particulars of Contract payment for the Goods shall be made in full within 30

days of the date of invoice. Time of payment shall be of the essence. If the Buyer fails to make any payment onthe due date then, without prejudice to any other right or remedy available to the Seller, the Seller shall be entitledto suspend any further deliveries to the Buyer, appropriate any payment made by the Buyer to such of the Goods(or the Goods supplied under any other contract between the Buyer and the Seller) as the Seller may think fit(notwithstanding any purported appropriation by the Buyer) charge the Buyer interest (both before and after anyjudgement) on the amount unpaid at the rate of 4 per cent per annum above Barclays Bank plc base rate fromtime to time and exercise a lien over any property of the Buyer then in its possession, until payment in full ismade.

6.1 Save as aforesaid payments shall be applied to invoices in the order in which they were issued and to Goods inthe order in which they are listed in invoices.

6.2 The Buyer shall not be entitled to make any deduction or withhold any sum from the payment from time to timedue from it whether by way of set-off, counter claim or otherwise.

Warranty7.0 The Seller warrants for a period of 12 months from invoice date that, in so far as the Goods are of its own

manufacture, they shall be free from defects in workmanship or materials at the time of delivery. If any Goods donot conform to that warranty the Seller will at its option:(a) replace the Goods found not to conform to the warranty and such replacements shall be supplied subject to

these Conditions; or(b) take such steps as the Seller deems necessary to bring the Goods into a state where they are free from

such defects; or(c) take back the Goods found not to conform to the warranty and refund the appropriate part of the purchase

price.PROVIDED THAT:(i) the liability of the Seller shall not arise unless the Buyer demonstrates to the Seller's reasonable satisfaction

that the Goods have, prior to use, been properly stored and handled and subsequently have not been usedin any unusual or abnormal way or in a manner contrary to any instructions or recommendations for useprovided by the Seller;

(ii) the liability of the Seller shall in no event exceed the purchase price of the Goods;(iii) performance of any one of the above options (as limited by (ii) above) shall constitute an entire discharge of

the Seller's liability under this warranty.

Page 215: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

105

7.1 The foregoing warranty is conditional upon:(a) the Buyer giving written notice to the Seller of the alleged defect in the Goods, such notice to be received by

the Seller within 7 days of the time when the Buyer discovers or ought to have discovered the defect and inany event within one year of delivery of the Goods;

(b) the Buyer affording the Seller a reasonable opportunity to inspect the Goods and, if so requested by theSeller, returning the allegedly defective Goods to the Seller's works, carriage pre-paid, for inspection to takeplace there;

(c) the Buyer making no further use of the Goods that are alleged to be defective after the time at which theBuyer discovers or ought to have discovered that they are defective.

7.2 The Seller further undertakes that, in so far as the Goods are not of its own manufacture, it will pass on to theBuyer the benefit of any guarantees or indemnities given to it in respect of such Goods by its own suppliers.

7.3 Save as provided in paragraphs 1 and 3 of this clause, in clause 2 and in section 12 of the Sale of Goods Act1979:(i) all conditions and warranties, express or implied, as to the quality or fitness for any purpose of the Goods

are hereby expressly excluded; and(ii) except in respect of death or personal injury caused by the Seller's negligence, or in respect of liability under

the Consumer Protection Act 1987, the Seller shall not be liable for any loss or damage (whether direct,indirect or consequential) howsoever arising which may be suffered by the Buyer.

It is hereby expressly declared that any statements as to quality made by the Seller do not form part of thedescription of the Goods.

Limits of Liability8.0 The Buyer must satisfy itself of the suitability of the Goods for the purposes for which they are purchased, and

must comply with any directions, instructions or warnings as to the use storage or handling of the Goods given bythe Seller. The Buyer must also ensure that the Goods comply with all local approvals and standards relating tothe use to which they are to be put, and without prejudice to the generality of paragraph 3 above, allrecommendations and advice given by or on behalf of the Seller to the Buyer as to the methods of storing,applying or using the Goods the purposes to which the Goods may be applied and the suitability of using theGoods in any manufacturing process or in conjunction with any other materials are (except when given pursuantto a request of the Buyer under clause 2) given without liability on the part of the Seller, its servants or agents.

8.1 In the event that, notwithstanding the provisions of paragraphs 7.3 and 8.0 above, the Seller is found liable for anyloss or damage suffered by the Buyer, that liability shall in no event exceed the purchase price of the Goods.

8.2 Nothing in these Conditions or in the Particulars of Contract shall affect or limit the validity or application of anycustomer warranty with the benefit of which any of the Goods are sold and if the Buyer, being an end-user, is ableto benefit from such a warranty the terms thereof shall prevail over the terms of these Conditions and theParticulars of Contract.

Bankruptcy and Liquidation9.0 This clause applies if the Buyer becomes (or appears to the Seller to be about to become) bankrupt, or goes (or

appears to the Seller to be about to go) into liquidation, has a petition presented or threatened for its winding-up,suspends payment of debts or makes any arrangement with creditor, fails to pay in accordance with the terms ofthe Contract, has an administration order made or a petition for such an order presented or threatened, has areceiver appointed over all or any part of its assets or is answerable under the law of the country havingjurisdiction over the Buyer or its assets for any of the foregoing, or is in breach of any other term of the Contract.

9.1 If this clause applies, then without prejudice to any other right or remedy available to the Seller, the Seller shall beentitled to cancel the Contract or suspend any further deliveries under the Contract without liability to the Buyer,and if the Goods have been delivered but not paid for the price shall become immediately due and payablenotwithstanding any previous agreement or arrangement to the contrary.

Indemnities10.0 The Buyer shall indemnify the Seller in respect of all damage injury or loss occurring to any person or property

and against all actions, suits, claims, demands, charges or expenses in connection therewith arising from thecondition or use of the Goods in the event that the damage injury or loss shall have been occasioned partly orwholly by the carelessness of the Buyer and his servants, contractors or agents or by any breach by the Buyer ofeither its obligations to the Seller hereunder or of any patent, design or other intellectual property right of a thirdparty.

10.1 The Buyer undertakes that it shall not solicit purchasers for the Goods outside countries which for the time beingare Member States of the European Economic Area ("EEA State") or sell the Goods to any person who it knowsis intending to use or resell the same outside the EEA States PROVIDED THAT nothing in this clause orelsewhere in these Conditions shall be construed so as to prevent the Buyer from selling or distributing the Goodsin or to any EEA State to any person intending to use or resell the same in any EEA State.

Notices11.0 Any notice required or authorised to be given hereunder shall be in writing and shall be served by registered mail

sent to the address given above or any other address notified for the purpose and shall be deemed to be served

Page 216: Kidde co2 product manual 050128

© K.F.P.S. Ltd December 2004 Manual No 59812-400

106

seven days after proven despatch, provided that any other mode of service shall be valid if the said notice orother communication is actually received by the addressee.

Force Majeure12.0 The Seller shall not be liable to the Buyer if unable to carry out any provision of the Contract for any reason

beyond its control including (but without limitation) Act of God, legislation, war, civil commotion, fire, flood,drought, failure of power supply, lock out, strike, stoppage or other action by employees or third parties incontemplation or furtherance of any dispute or owing to any inability to procure parts or materials required for theperformance of the Contract.

Waiver13.0 Any failure by the Seller to enforce any or all of these conditions shall not be construed as a waiver of the Seller's

rights.

Construction and Jurisdiction14.0 The proper law of the Contract shall be English law and the English courts shall have jurisdiction over any

disputes arising thereunder. This edition of the Conditions of Sale dated October 2002 supercedes all previouseditions.

Page 217: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-402 Issue B December 2004 Page ii

High PressureCarbon DioxideFire Protection Equipment

Flow Calculation ProgramKFP CO2 Version 2.0.3

User’s Manual

Manual No. 59812-402Issue B December 2004

Page 218: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-402 Issue B December 2004 Page ii

ContentsCOVER..................................................................................................................................................... iCONTENTS .............................................................................................................................................. iiFOREWORD ............................................................................................................................................ iii

1 OVERVIEW 1

1.1 Total Flooding.............................................................................................................................. 11.2 Local Application .......................................................................................................................... 2

2 HYDRAULIC FLOW CALCULATION PROGRAM (KFP CO2) 3

2.1 Commands Available ................................................................................................................... 42.1.1 System Information ...................................................................................................................... 42.1.2 Hazard Information....................................................................................................................... 62.1.3 Piping Model Data...................................................................................................................... 112.1.4 Calculate and Display Results ................................................................................................... 182.2 Output / Print Data and Results.................................................................................................. 21

APPENDIX 23

A-1 Equivalent Length Reference Tables ......................................................................................... 23A-2 KFP CO2 Calculation Example #1.............................................................................................. 24A-3 KFP CO2 Software Hot Keys Reference List.............................................................................. 31

Page 219: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-402 Issue B December 2004 Page iii

Foreword

Kidde Fire Protection Services Ltd reserves the right to revise and improve its products as it deems necessarywithout notification. This publication is intended to describe the state of this product at the time of its publication,and may not reflect the product at all times in the future. The software screen prints depicted in this manual arepresented for reference purposes only and may not reflect the most current version of the High Pressure CO2Flow Calculation Software (KFP CO2 Version 2.0.3).

This technical manual provides the necessary information for designing and performing flow calculations for aKidde Fire Protection CO2 Engineered System.

This publication, or parts thereof, may not be reproduced in any form, by any method, for any purpose, withoutthe express written consent of Kidde Fire Protection Services Ltd.

Any questions concerning the information presented in this manual should be sent to the address below.

Copyright ©2004 Kidde Fire Protection Services Ltd. All Rights Reserved.

Thame Park Road,Thame,Oxfordshire,OX9 3RT,UK

Page 220: Kidde co2 product manual 050128
Page 221: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-402 Issue B December 2004 Page 1

1 OVERVIEW

Carbon dioxide (CO2) is a universally accepted extinguishing agent for fires involving flammable liquids,electrical equipment and other special hazards such as record and fur storage vaults, where ordinaryfire protection with water could cause as much or more damage than the fire itself.

Carbon dioxide is an odourless, colourless gas at ordinary temperatures. When used for fire protection,it is stored under pressure in high pressure cylinders. Under normal conditions, the gas is compressedinto a liquid. The colder the storage temperature, the denser the liquid.

When a carbon dioxide system is released, the gas pressure in the storage container propels the liquidthrough pipe lines to discharge nozzles. Carbon dioxide vapour will continue to be expelled from thestorage container after all the liquid is gone. This “gas point” occurs when about 70 percent by weightof a high pressure cylinder’s contents have been discharged. This is an important feature to keep inmind when designing a system.

Carbon dioxide extinguishes fires mainly by smothering; that is, by displacing air and its oxygen, whichis needed to sustain burning, or rapid oxidation. An average concentration of 34 percent by volumewill handle fires involving most common materials. Other materials may require an inert atmosphereof up to 100 percent. Some burning materials, such as stacked paper, furs, non-plastic electricalinsulation and baled cotton, oxidize at very low oxygen levels and there is so much oxygen containedin pores or other internal spaces that they must be “soaked” in a smothering atmosphere for periodsof from five (5) minutes to hours to allow CO2 to reduce the oxidation level to a point where new heatgenerated is less than the heat loss to surrounding material or atmosphere.

There are two basic methods of applying carbon dioxide:

1) Total Flooding

2) Local Application.

1.1 Total FloodingTotal flooding is used when the hazard is enclosed in a room, compartment or other type of housing.BS5306 Pt 4 / NFPA 12 (2000 edition, Section 2-1.2) states that total flooding shall be used “wherethere is permanent enclosure around the hazard that adequately enables the required concentrationof carbon dioxide to be built up and to be maintained for the required period of time.” If the space isacceptably tight; if openings that can leak carbon dioxide, such as doors, windows and ducts can beclosed; and if forced draft devices, such as fans, can be shut off, the amount of carbon dioxide requiredand the duration of discharge are readily calculated on a volume basis for the types of materialinvolved. The entire contents of the storage container, liquid and vapor, are usable.

There are circumstances, however, wherein some opening, small but critical, cannot be closed. Or,as with rotating electrical or other motorised equipment, it takes a considerable period of time for theequipment to come to a stop, during which essential ventilation continues. Total flooding often is usedin these situations, but additional carbon dioxide is applied to “screen” the openings and/or to replaceleakage. With large generators, which may have deceleration times of twenty (20) minutes or more andhazards with low flash point fuel or lube oil and exposed hot metal surfaces that require a cool downperiod, a supplementary extended discharge of carbon dioxide is applied during the period.

Page 222: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-402 Issue B December 2004 Page 2

1.2 Local ApplicationLocal application is used when the hazard is open or is not enclosed sufficiently for flooding. Rate andduration of application, positioning of nozzles, arrangement of discharge piping and the usable capacityof storage containers are critical factors as the discharged carbon dioxide is soon dissipated and hasno continuing effect.

System design for local application is considerably more complex than for flooding an enclosure. Thetypes of nozzle to be used and their locations must first be determined within accurate limits.

Page 223: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-402 Issue B December 2004 Page 3

2 HYDRAULIC FLOW CALCULATION PROGRAM (KFP CO2)

The high pressure CO2 calculation program (KFP CO2) has been written within the WindowsTM

environment. Installation procedures will be provided with the CD. (It is our assumption that the userhas a basic knowledge of this operating system and its operation will not be addressed within thismanual.) The computer program will establish pipe sizes as well as calculate terminal pressures,discharge time, and nozzle drill sizes. The primary requirement for a proper calculation is to insure thatthe system is modelled into the computer program correctly. Therefore, the input parameters may beprinted out as well as the calculation results. This makes it possible to verify the input data against theintended design parameters and/or the actual installation. It is possible to input either kilogramsrequired for each nozzle fixed flow rate or the existing nozzle drill size (fixed code).

The Kidde Fire Protection Carbon Dioxide Flow calculation program has been divided into three mainareas:

1) Commands Available2) Output3) File Utilities.

NOTE

THE CALCULATION INFORMATION CAN BE ENTERED AND DISPLAYED IN METRIC OR IMPERIAL UNITS. IT CAN BE

CONVERTED AT ANY TIME UPON COMMAND BY SIMPLY USING THE METRIC CHECK BOX.

Figure 2.1 – Commands Available

Page 224: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-402 Issue B December 2004 Page 4

2.1 Commands AvailableThis area has been subdivided into the following categories:

System InformationHazard InformationPiping Model dataCalculate and Display ResultsClear All Current Data

2.1.1 System InformationWithin the Systems Information screen there are four submenus:

Project DataRevisionCylinder DataConfiguration Variables

Figure 2.1.1 – System Information

Page 225: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-402 Issue B December 2004 Page 5

2.1.1.1 Project DataThe Project Data section consists of the following data:

1. Project Number: Reference number

2. Project Name: Name of project or end user

3. Site Location: Installation location

4. Hazard Name: Name of protected hazard

2.1.1.2 RevisionThis data field is used to track versions/changes on a specific data file and/or submittal.

2.1.1.3 Cylinder Data

The Cylinder Data section consists of the following data:

1. Number of Cylinders: The number of cylinders required to contain the amount of CO2 required fora discharge. This value may be entered by one of two means: the value may be directly enteredinto this field or a value may be selected from the pop-down window, which may be accessed byclicking onto the arrow at the right of the data field.

2. Cylinder Capacity: The CO2 cylinders are available in only 6.8, 22.6, 36.2, and 45 kg capacities.

3. Storage Pressure (BAR): This is a fixed selection. All highpressure CO2 calculations are based upon an average storagepressure of 58.6 bar @ 21 deg C (850 psi).

4. Pipe Length Factor: The length of the main piping run affects thevapour time associated with a CO2 discharge. The longer the run,the greater the amount of CO2 vaporised within the piping. Thedischarge rate of each nozzle must be increased to draw more liquidCO2 into the piping network to compensate for the vapour. Table2.1.1.3-D is a guideline for the pipe length factor.

5. Exclude Pipe Size: Occasionally, it is desirable to exclude or inhibitspecific pipe sizes from being selected and used by the calculationprogram. To exclude a pipe size from being selected, simplychoose the specific size or “None”. Only a maximum of 2 sizes maybe excluded from the calculation. The sizes in this list represent allthe pipe sizes possible for both steel pipe and tubing.

NOTE

THE USER SHOULD BE AWARE AS TO WHICH PIPE SIZES ARE APPLICABLE TO THE PIPE TYPE THAT WILL BE

UTILIZED IN THE PIPING NETWORK.

6. Pipe Temperature: The initial pipe temperature should be entered here to accurately calculate thevapor portion of the discharge.

Table 2.1.1.3-DPipe Length Factor

Distance Factor

0 - 15 Meters(0-50 Feet) 1.10

15 - 30 Meters(50-100 Feet) 1.20

30 - 90 Meters(101-300 Feet) 1.30

90 - 120 Meters(301-400 Feet) 1.40

120 - 150 Meters(401-500 Feet) 1.50

Page 226: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-402 Issue B December 2004 Page 6

Figure 2.1.1.3 – Exclude pipe sizes

7. Loss Factor (%): To compensate for enclosure tightness or lack thereof, the loss factor (expressedin percentages) will proportionally increase the amount of CO2 storage required to assure aminimum concentration. The default value is 10%.

8. Minimum Temperature: For High Pressure CO2 systems where the cylinders may be exposed totemperatures below 0°C (32°F) for local application systems or -18°C (0°F) for total floodingsystems.

9. Main/Reserve: Adjusts the quantity of equipment for the Bill of Material printout.

2.1.1.4 Configuration Variables

1. Report Title: The data entered here will appear in the general heading area on all printouts. Theintended use is to allow Kidde Fire Protection distributors to incorporate their company name intothe printouts.

2.1.2 Hazard InformationWithin the Hazard Information screen there are three subcategories:

Hazard DataAreaArea Nozzle List

Page 227: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-402 Issue B December 2004 Page 7

2.1.2.1 Hazard DataThe first section is used to input the hazard area name(s) for reference, type of CO2 protection,concentration and temperature. More than one area name may be included; however, each area namemust be entered separately.

Figure 2.1.2.1 – Hazard Data

A. Area Name: Enter the name of the specific area - commas are not allowed.

B. Type: Select the appropriate hazard type and the calculation module will perform the necessary crosschecks needed to determine if the calculated system’s discharge performance is satisfactory. See thechart on the following page for some examples of the cross checks performed.

The latest edition of BS5306 pt 4 / NFPA 12 should be consulted prior to determining the fire typefor each hazard.

Page 228: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-402 Issue B December 2004 Page 8

Figure 2.1.2.1 – System Type

Extended Discharge

A fifth fire type of “Ext’d Discharge” is for those hazards that require an extended discharge. Theprogram accommodates this by requesting a few bits of information and then compares thecalculated results to what the calculated requirements are based on the information suppliedto the program.

Fire Type Required Duration Comparison

TF Surface <=60 seconds Did the calculated requirement of gas discharge in time?

TF Deep Seated <=420 seconds Did the hazard achieve 30% concentration in 2 minutes, andthe remainder of gas required in less than 7 minutes?

LA Rate by Area >=30 seconds Was there at least 30 seconds of LIQUID discharge fromeach nozzle?

LA Rate by Volume >=30 seconds Was there at least 30 seconds of LIQUID discharge fromeach nozzle?

Ext’d Discharge See below

Page 229: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-402 Issue B December 2004 Page 9

When “Ext’d Discharge” is chosen, the ExtendedDischarge Input form is shown.

There are three choices available based on thehazard:

Dry Electrical HazardHydroElectric GeneratorJob Specification

1. Dry Electrical Hazard: A typical hazard ofthis kind is anything that requires a 30% concentration held for some period of time, i.e., a transformer room or acompartmentalised gas turbine. If this optionis chosen, simply fill in the volume, choose a loss factor per minute (usually between 1% &3% is sufficient for enclosures that have average leakage), and type in the cool-down (orhold) time in minutes. After supplying these three pieces of information, press the Compute button.

Next an Extended Discharge Wizard Dialogbox will be shown - fill in the design criteria forthe INITIAL discharge. Based on theinformation you supply, the program will beable to compute the extended discharge CO2quantity and the rate of discharge per minute.If the initial discharge design criteria needs tobe modified, simply depress the “Edit InitialDischarge Information” and the program willre-compute the requirements for the extendeddischarge. When finished, simply press theClose button and the information from thisform will automatically transfer to the HazardData Screen. Next add the required amount ofdischarge nozzles.

2. HydroElectric Generator: If this option ischosen, simply type in the volume and selectthe cool-down time from the drop-down list. After completing this, press the Compute button.The software will use Table 4 from Design Manual 59812-401 to calculate the amount of gasrequired and then calculate the appropriate rate of discharge per minute. After this iscomplete, press the Close button and the information from this form will automaticallytransfer to the Hazard Data Screen. Then just add the required amount of dischargenozzles.

3. Job Specification: Sometimes manufacturers supply a specification for how the extendeddischarge shall perform. In this case, select this option. You then fill in all the fields, i.e.,volume, CO2 quantity, rate, and the cool-down time. Next, press Compute so the programcan compute/set the necessary values needed for the calculation module. When this iscomplete, press the Close button and the information from this form will automaticallytransfer to the Hazard Data Screen. Next, just add the required number of dischargenozzles.

Figure 2.1.2.1.2

Figure 2.1.2.1.1

Page 230: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-402 Issue B December 2004 Page 10

C. % (% Concentration): For Total Flooding Systems only, this is the minimum percentage ofCO2 concentration required for this specific area. Refer to BS5306 pt 4 / NFPA12 for furtherinformation.

D. Temperature: For Total Flooding Systems Only, enter the normal ambient temperature forthe area. If the area has a temperature in excess of 100°C (212°F) or below -18°C (0°F), theprogram will automatically compensate an additional 2% CO2 Gas for every 5°C above 100°Cand 2% CO2 gas for every 1°C below -20°C.

2.1.2.2 AreaEnter the appropriate values in the Length, Width and Height field and the program will compute thecorrect room volume and amount of agent required automatically. As you will note, the Width andHeight fields are both set to a default of 1. If the volume is known, enter it into the Length data field andleave the Width and Height fields as 1. Once the data has been entered, clicking on the Add button willassign this data to the current hazard.

2.1.2.3 Area Nozzle ListEach area must have one or more nozzles associated with it. Each nozzle will have a unique IDnumber. These numbers are automatically assigned and are incremental, starting with 301. The propertype of nozzle must be chosen for the type of hazard area being protected. Once a nozzle has beenadded, a blank line will appear at the bottom of the nozzle grid. If no blank line appears at the bottomof the grid, the nozzle has not been added. To change the nozzle type, simply click on the row(s) andchoose the correct nozzle type from the list. To change an existing nozzle number, select the nozzleto be changed and type in the new nozzle number.

Figure 2.1.2.3 – Area Nozzle List

Page 231: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-402 Issue B December 2004 Page 11

2.1.3 Piping Model DataThe piping information is the heart of the system model. This area is where the pipe and kgs / nozzlesdata is recorded. Several pieces of data are required and Section 2.1.3.2 provides a brief descriptionof each of the columns.

Figure 2.1.3 – Piping Model Data

2.1.3.1 System Design Considerations for Sectioning of PipeThe first step is to make an isometric sketch of the system. All rises and drops should be noted, as wellas other known pertinent data such as manifold size and pipe schedule.

A separate pipe section is required for any one of the following conditions:

Change in Pipe Diameter.Change in Pipe Schedule.Divisions of Flow (as at a tee).Rise or drop in elevation greater than 1.52 meters (5 feet).

1. Terminal Points

1. All terminal points should progress in logical numeric succession. The starting point (point 1)is located at the bottom of the first cylinder’s dip tube. From here the subsequent points areplotted moving toward the discharge nozzles.

Page 232: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-402 Issue B December 2004 Page 12

2. A terminal point is placed upstream of (before) a tee where a division of flow occurs. Whereflow is routed through only one branch of a tee, a terminal number can be omitted if none of thefour conditions mentioned above occurs.

3. A Pressure Operated Directional Valve (POD) should be kept as close to the beginning of asection as possible. A POD valve can begin a section by placing the terminal point at thevalve’s inlet.

4. A terminal point should be located at the start of a rise or drop of greater than five feet.

5. Number the terminal points consecutively to the end of each distribution section. Do notduplicate numbers on the same calculation.

6. Multi-hazard systems (utilising POD valves) demand close attention. The hazard requiring thegreatest flow rate (not necessarily the greatest quantity of CO2) should be calculated first, sinceit will establish the size of the manifold and main discharge header. These sizes must be usedin calculations for the other hazards.

2.1.3.2 Column Headings and Descriptions

1. Nodes: These points identify the section of pipe, nozzle or a cylinder that is being modelled.

2. Start: This indicates the beginning of a pipe, manifold, orcylinder section.

3. End: This indicates the end of the same section. If thisline is a nozzle, clicking the button that appears in this cellwill cause a Hazard Nozzle Reference Box to be visible.Here the user can scroll through the hazards and selectthe desired nozzle, or simply type in the nozzle numberinto the “end” cell.

4. Cylinder Qty: The quantity of cylinders flowing through this specific section of manifold piping.Enter a quantity of zero (0) to indicate distribution piping.

5. Pipe Len: Length of pipe in feet or meters, as applicable, including all elevation changes.

6. Elev: Change of elevation within the pipe section, expressed in feet or meters.

1. A positive number indicates a rise in elevation.

2. A negative number indicates a drop in elevation.

3. A zero indicates no change in elevation.

Figure 2.1.3.2.C – Hazard nozzle reference box

Page 233: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-402 Issue B December 2004 Page 13

7. Type: Type of pipe to be installed. There are several types available, accessible through the pop-down, for use:

1. 40T: Schedule 40 pipe with threaded fittings. Select for BS5306 systems using BS1387 pipe,up to and including 40mm.

2. 40W/V Schedule 40 pipe with welded or grooved / Victaulic fittings. Select for BS5306 systemsusing BS1387 pipe, up to and including 40mm.

3. 80T: Schedule 80 pipe with threaded fittings. Select for BS5306 systems using BS3601 orAPI5L pipe.

4. 80W/V: Schedule 80 pipe with welded or grooved / Victaulic fittings. Select for BS5306 systemsusing BS3601 or API5L pipe.

5. Tubing: Stainless steel tubing with compression fittings. Not to be used in BS5306 systems

Table 2.1.3.2.G5 - Tubing Chart

Tubing OD

inches mm

WallThickness(inches)

1/4 8 0.065

5/16 9 0.065

3/8 10 0.065

1/2 15 0.065

5/8 18 0.065

3/4 20 0.095

7/8 22 0.095

1 25 0.095

1-1/4 32 0.188

1-1/2 40 0.188

2 50 0.188

All tubing to be either: Grade 304 seamless (ASTM A-213, A-269) Grade 304 welded (ASTM A-129, A-269) Grade 316 seamless (ASTM A-213, A-269) Grade 316 welded (ASTM A-249, A-269)

Grade 304L and 316L Tubing is NOT allowed.

Page 234: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-402 Issue B December 2004 Page 14

Figure 2.1.3.2.7 – Type of Pipe

8. Size: The size of pipe in the section. When a pipe size of “0" is chosen, the program willautomatically calculate the pipe size required. Depending on the type of pipe chosen under the pipetype column, the appropriate pipe sizes will be displayed in the pipe size drop down list; i.e., if 40Tis chosen, a size of 22 cm (7/8") will not be available.

Figure 2.1.3.2.8 – Pipe Size

Page 235: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-402 Issue B December 2004 Page 15

9. Fittings 90's: Indicates the number of 90°elbows in the pipe section. When 45° elbows are used,they are treated as an equivalent number of 90° elbows. In this case, 0.5 would be inserted foreach 45° elbow and included in the 90's field.

Figure 2.1.3.2.10.1 – Tees and Valves

10. Tees/Valves: The default for this section is “None.” For sections where tees or selector valves areused, the following choices are available:

1. Thru: The beginning of the pipe section begins with a thru tee. If the side branch of a tee isused to provide pressure for tripping a pressure switch or pressure release, it is treated as anequivalent number of elbows. In this case, 0.6 would be included in the 90's field.

2. Side: The beginning of the pipe sectionbegins with side tee. If one of the thrubranches of a tee is used to providepressure for tripping a pressure switch orpressure release, it is treated as anequivalent number of elbows. In thiscase, 2.0 would be included in the 90'sfield.

3. Dirt Trap (Blow Out): The equivalentlength of the dirt trap fittings willautomatically be included in thecalculation program. Figure 2.1.3.2.10.2depicts a typical dirt trap arrangement.

Figure 2.1.3.2.10.2

Page 236: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-402 Issue B December 2004 Page 16

4. Pressure Operated Directional Valve (POD): The beginning of the pipe section begins witha POD valve. The equivalent length of the valve will automatically be included in the calculationprogram. If a pipe type of “Tubing” was chosen, it will be automatically changed to 40T.

5. Thru & POD: To save time by avoiding additional lines of piping data input, if the pipe sectionbegins with a thru tee and is followed by a POD selector valve, the pipe modelling can beconfigured as one line of input. All fitting equivalent lengths will automatically be included withthe input. If a pipe type of “Tubing” was chosen, it will be automatically changed to 40T.

6. Side & POD: Same as above but using a side tee instead of a thru tee.

7. Ball Valve: When the section of piping contains a ball valve for purposes such as lockout orisolation, the equivalent length of the valve will automatically be included in the calculationprogram. If a pipe type of “Tubing” was chosen, it will be automatically changed to 40T.

8. Check Valve: When the section of piping contains a check valve, i.e., a main with reservesystem, the equivalent length of the check valve will automatically be included in the calculation.If a pipe type of “Tubing” was chosen, it will be automatically changed to 40T.

11. Fix Code: This default button should be on when the values in the “Kgs Required” column indicatethe actual nozzle code or drill diameter in inches for a particular nozzle.

Flow Rate: This default button should be on when the values in the last column indicate thedischarge rate in kgs (pounds) per minute to be discharged from a nozzle. To set the rate for aparticular nozzle, select the far right cell, click the Flow Rate default button, and then either typethe flow rate in or use the drop down list and select the “Get Rate” option. The computer willautomatically calculate and display the required flow rate needed for that particular nozzle.Alternatively, you can set all the flow rates simultaneously after finishing the piping model byfollowing the above steps, but instead of selecting “Get Rate,” select “Set All.”

Figure 2.1.3.2.11 – Flow Rate

Page 237: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-402 Issue B December 2004 Page 17

NOTE

THE “GET RATE” AND “SET ALL” FUNCTIONS ONLY WORK FOR TOTAL FLOODING HAZARDS AND FOR HAZARDSTHAT UTILIZED THE EXT’D DISCHARGE, THE RATE MUST BE DETERMINED BY THE LOCAL APPLICATION NOZZLESELECTOR SLIDE RULE AND INPUTTED MANUALLY.

UNLESS A LOW RATE ORIFICE NOZZLE IS SELECTED FOR A HAZARD, ALL FLOW RATES WILL DEFAULT TO AMINIMUM OF) 4.54 KG/MIN (10 LBS/MIN). THIS IS TO INSURE THAT THE NOZZLE WILL NOT FREEZE UP AND CLOGTHE DISCHARGE PIPE.

2.1.3.3 Add, Copy & Paste, Insert, and Delete

1. Add: The Add button works similarly to the Add buttons on the previous screens. Clicking the Addbutton will add a blank line to the bottom of the data grid. Other ways to “Add”: Function key F5, theRight Arrow key (if you are in the last column of the last row), or depressing the Shift and Insertkeys simultaneously.

2. Copy & Paste: Click the Copy button. Alternatively, you can depress the F9 key. Select any cellin the row or rows desired to be copied. To copy multiple rows at one time, simply click on any cellin the first row to be copied and while continuing to depress the left mouse button, highlight theremaining rows. Select a cell in the row where you want to paste the copied rows. Press the Pastebutton. Alternatively, you can depress the F10 key.

NOTE

ONLY CONSECUTIVE ROWS CAN BE COPIED AT ONCE. THE LINES WILL BE INSERTED STARTING AT THE ROW OFTHE CELL THAT IS HIGHLIGHTED. YOU CAN PASTE THIS INFORMATION AT ANY TIME AND AS MANY TIMES ASNECESSARY WITHOUT RESELECTING THE ROWS TO BE COPIED.3. Insert: The Insert button is used to insert a line of data into the data grid in a specific location other

than at the next available position at the bottom of the grid. In order to insert a line, click onto thehighest line in the data grid that must be moved down and depress the Insert button. This can alsobe accomplished using function key F7 or by depressing the Insert key.

4. Delete: The Delete button is used to delete a line of data in the data grid. Highlight the data linewithin the data grid by clicking on it with the mouse. Click on the delete button. A verificationmessage will appear to validate the request. Should you confirm the request, the data line will bedeleted and any data lines below it will be moved up to compensate for the deleted line of data.This can also be accomplished using function key F8 or by depressing the Shift and Delete keyssimultaneously.

2.1.3.4 Fix PipeAfter running a calculation, it is always recommended to Fix Results (see paragraph 2.1.4.1.3). Afterthis is done, the input data can be fixed to represent the pipe sizes, pipe schedules, and actual nozzlecodes that were determined by the calculation program. This is useful for “as-built” modifications, etc.

NOTE

THIS OPTION IS ONLY AVAILABLE AFTER A “FIX RESULTS” CALCULATION HAS BEEN PERFORMED.

Page 238: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-402 Issue B December 2004 Page 18

2.1.4 Calculate and Display ResultsBy clicking on the “Calculate and Display Results” button, the piping data file will be passed on to thecalculation program for processing. Once the processing is completed, the results will be displayedon four different screens:

Calc ResultsNozzle BOMNozzle InfoDischarge Info

2.1.4.1 Calc Results

1. System Information: This section of the Results screen indicates the cylinder quantity, size,pressure and temperature as entered in the System Information Screen. Inhibited/Excluded pipesizes are also noted.

Figure 2.1.4.1 – Calculation Results – System Information

2. Piping:

1. Section Nodes: The starting and ending nodes for a particular section of the pipe model.

2. Nominal Pipe Size: The computed or inputted pipe size and schedule.

Page 239: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-402 Issue B December 2004 Page 19

NOTE

IF TUBING WAS CHOSEN RATHER THAN PIPE, THE CALCULATION RESULTS PRINTOUT WILL GIVE INFORMATIONON THE MINIMUM WALL THICKNESS (IN INCHES) THAT IS REQUIRED FOR EACH SIZE OF TUBING.

3. Length: Length of pipe within the section, including elevation changes.

4. Elev: The length of an elevation change within the section of pipe.

5. EQL: Total equivalent length of the section of pipe, including pipe, elbows, tees, couplingsunions, valves, and additional information inputted into the equivalent length column of the datafile.

6. Section Flow: The flow rate through the pipe section.

7. BAR: The pressure at the termination of the section.

8. Nozzle Flow: The flow rate through the pipe section and nozzle.

9. Nozzle Code: The calculated/ideal nozzle code.

3. Fix Results: This will run one additional calculation using the pipe sizes and actual nozzle sizesavailable. It is recommended to always use this feature to ensure that the system will be acceptableand meet code utilising actual available nozzle codes.

Figure 2.1.4.1.C – Fix Results – Nozzle Summary

Page 240: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-402 Issue B December 2004 Page 20

2.1.4.2 Nozzle BOMThe nozzle bill of materials will provide the ordering Bill of Materials. This will include quantity, nozzletype(s), code(s) required and the Kidde Fire Protection stock number.

Figure 2.1.4.2 – Nozzle BOM

2.1.4.3 Nozzle Info (Nozzle Summary)Similar to the Bill of Materials, the nozzle information individually lists each nozzle along with comparingits calculated code vs. its actual code. The actual code is the closest manufactured code available.

Figure 2.1.4.3 – Nozzle Summary

Page 241: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-402 Issue B December 2004 Page 21

2.1.4.4 Discharge InformationThe discharge information screen provides evaluation data in the form of average vapour and liquidCO2 discharge times, and weights of CO2 discharged. Also included is the maximum vapour timeachieved by a nozzle within the CO2 system, along with each nozzle’s residual vapour discharge. Herea comparison is made as to how much gas is required in a given amount of time and how much gasis discharged at the end of the discharge period for each hazard.

Figure 2.1.4.4 – Discharge Information

2.2 Output/Print Data and ResultsThis screen will allow the user to send both the results of the calculation and/or the input data used forthe calculation to a selected printer. A Bill of Materials option is also available to provide a basic BOMbased on the flow calculation.

2.2.1 Items to Print

1. Input Data Listing: When this option is selected, the program will output the data file.

2. Calculation Results: The selection of this option will output the results of the calculation.

3. BOM: The mechanical High Pressure CO2 System Bill of Material, including pipe and pipefittings. Once the BOM has been printed, the system must be recalculated before printingthe BOM again.

Page 242: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-402 Issue B December 2004 Page 22

Figure 2.2 –Output/Print Data and Results

4. Print CO2 Requirements: Selecting this option will print the CO2 requirements for each individualhazard (not applicable to LA Rate by Area and LA Rate by Volume hazard types). A step bystep walk-through of how the requirement was calculated will be printed. This information can besent directly to a printer to obtain a hard copy (useful for submitting to authorities having jurisdiction,etc.) or it can be printed to a text file, which can then be entered into AutoCAD or a word processingprogram.

NOTE

IF YOU DO NOT HAVE ANY TOTAL FLOODING HAZARDS DEFINED, THIS OPTION WILL NOT BE AVAILABLE.

2.2.2 Output Units

1. Metric: This selection will produce a metric unit output.

2. Imperial: This option will output the required information with standard English units.

2.2.3 Configure PrinterThere are numerous types of printers on the market and the program is designed to incorporate a widerange of printers. It is advisable to click on Configure Printer to verify the current Windows selectedprinter.

There are virtually hundreds of fonts available in the industry today. Even though the program willaccept and use a number of them, the suggested font is ARIAL, which is commonly found within theWindows list of available fonts. However, there are a number of acceptable fonts and by selecting andtrying these fonts, based on the numerous styles and types of printers, Kidde Fire Protection cannotassure you of satisfactory results. The printout uses various configurations and sizes to produce itshard copy printout.

2.2.4 PrintClicking on this command will start the printing or writing of the selected data.

Page 243: Kidde co2 product manual 050128

© K.F.P.S. Ltd 98812-402 Issue B November 2004 Page 23

FLOW CALCULATION SOFTWAREUSER`S MANUAL - APPENDIX

A-1 EQUIVALENT LENGTH

The equivalent length for all components is automatically calculated within Kidde Fire Protectionsoftware.

Page 244: Kidde co2 product manual 050128

© K.F.P.S. Ltd 98812-402 Issue B November 2004 Page 24

FLOW CALCULATION SOFTWAREUSER`S MANUAL - APPENDIX

A-2 CO2 Calculation Example #1

The following pages depict an example of a calculation performed using the KFP CO2 softwareprogram.

Example A-2.1 – Isometric Drawing

Page 245: Kidde co2 product manual 050128

© K.F.P.S. Ltd 98812-402 Issue B November 2004 Page 25

FLOW CALCULATION SOFTWAREUSER`S MANUAL - APPENDIX

Figure A-2.2 – System Information

Page 246: Kidde co2 product manual 050128

© K.F.P.S. Ltd 98812-402 Issue B November 2004 Page 26

FLOW CALCULATION SOFTWAREUSER`S MANUAL - APPENDIX

Figure A-2.3 – Hazard Information

Page 247: Kidde co2 product manual 050128

© K.F.P.S. Ltd 98812-402 Issue B November 2004 Page 27

FLOW CALCULATION SOFTWAREUSER`S MANUAL - APPENDIX

Figure A-2.4 – Piping Model Data

Page 248: Kidde co2 product manual 050128

© K.F.P.S. Ltd 98812-402 Issue B November 2004 Page 28

FLOW CALCULATION SOFTWAREUSER`S MANUAL - APPENDIX

Figure A-2.5 – Calculate and Display Results

Page 249: Kidde co2 product manual 050128

© K.F.P.S. Ltd 98812-402 Issue B November 2004 Page 29

FLOW CALCULATION SOFTWAREUSER`S MANUAL - APPENDIX

Figure A-2.6 – Nozzle Summary

Page 250: Kidde co2 product manual 050128

© K.F.P.S. Ltd 98812-402 Issue B November 2004 Page 30

FLOW CALCULATION SOFTWAREUSER`S MANUAL - APPENDIX

Figure A-2.7 – Discharge Information

Page 251: Kidde co2 product manual 050128

© K.F.P.S. Ltd 98812-402 Issue B November 2004 Page 31

FLOW CALCULATION SOFTWAREUSER`S MANUAL - APPENDIX

A-3 Software Hot Keys Reference List

Hot Keys Reference List

HOT KEYS

FUNCTION PRIMARY ALTERNATE

PIPING MODEL FUNCTION

Add F5 Key Shift + Insert

Insert Pipe F7 Key Insert Key

Delete F8 Key Shift + Delete

Copy F9 Key

Paste F10 Key

HAZARD DATA FUNCTION

Area Name & Area (Volume) Sections

Add F5 Key Shift + Insert

Delete F8 Key Shift + Delete

Area Nozzle List Section

Add F5 Key Plus Sign (+) Key

Delete F8 Key Shift + Delete

GENERAL FUNCTIONS

Move one cell to the left Left Arrow Key Shift + Tab

Move one cell to the right Right Arrow Key Enter or Tab

Move one cell up Up Arrow

Move one cell down Down Arrow

Drop down a list box Shift + Down Arrow

Go to System Information Screen F1 Key

Go to Hazard Data Screen F2 Key

Go to Piping Model Screen F3 Key

Calculate and Display Results F4 Key

Page 252: Kidde co2 product manual 050128

December 2004 issue B Manual No 59812-250i

Weight IndicatorMechanism(Part No. E8731-402)

USER'S MANUAL

December 2004 issue B Manual No 59812-250

Page 253: Kidde co2 product manual 050128

December 2004 issue B Manual No 59812-250ii

PROPRIETARY RIGHTS NOTICE

This document and the information that it contains are the property of Kidde Fire Protection. Rightsto duplicate or otherwise copy this document and rights to disclose the document and theinformation that it contains to others and the right to use the information contained therein may beacquired only by written permission signed by a duly authorised officer of Kidde Fire Protection.

© Copyright Kidde Fire Protection Services Ltd

Page 254: Kidde co2 product manual 050128

December 2004 issue B Manual No 59812-250iii

Amendment Incorporation Record

AmendmentNumber

Brief Descriptionof Content

Name of personIncorporatingAmendment

1

2

3

4

5

6

7

8

9

10

Page 255: Kidde co2 product manual 050128

December 2004 issue B Manual No 59812-250iv

TABLE OF CONTENTS

Chapter Page

1. INTRODUCTION ..........................................................................................11.1 GENERAL............................................................................................11.2 OPERATION........................................................................................1

2. SPECIFICATION..........................................................................................23. INSTALLATION ...........................................................................................3

4.1 EVERY SIX MONTHS........................................................................104.2 EVERY TWELVE MONTHS...............................................................10

APPENDIX A TESTING......................................................................................11APPENDIX B ATEX COMPLIANCE...................................................................13

SPECIAL INSTRUCTIONS FOR COMPLIANCE WITH 94/9/EC ...............13

Page 256: Kidde co2 product manual 050128

December 2004 issue B Manual No 59812-250v

LIST OF ILLUSTRATIONS

Figure PageFigure 1-1 Weight Indicator Mechanism.....................................................................1Figure 2-1 Dimensions ...............................................................................................2Figure 3-1 Flexible Conduit Installation ......................................................................4Figure 3-2 Electrical Installation - SERIES Two Wires ...............................................5Figure 3-3 Electrical Installation - SERIES One Wire .................................................5Figure 3-4 Electrical Installation - PARALLEL ............................................................6Figure 3-5 Mechanical Installation..............................................................................8Figure 3-6 Typical Support Frame..............................................................................9Figure A-1 Test Kit ...................................................................................................12

Page 257: Kidde co2 product manual 050128

December 2004 issue B Manual No 59812-2501

1. INTRODUCTION

1.1 General

The Weight Indicator Mechanism (Part No. E8731-402) is a device used to automaticallymonitor the contents of a fixed fire CO2 cylinder. When the contents of the cylinder fall bya pre-determined amount, typically 10%, the weight drops causing a microswitch to tripand send a signal to a signal panel.

The components of the weight indicator mechanism are shown in Figure 1-1. The deviceis supplied in a kit form, for assembly onto the mounting frame, and comprises: the body,two hanger rods, neck collar, weight, four off M10 nuts and washers, and one off M12 nutand washer.

The mounting frame will be supplied by others.

Figure 1-1 Weight Indicator Mechanism

1.2 Operation

When the weight indicator mechanism is set up, the downward force of the cylinder isgreater than the leverage provided by the weight on the weight rod.

As the contents of the cylinder drops through a pre-determined amount, the downwardforce of the cylinder becomes less than the leverage of the weight, therefore the weightrod drops and trips the microswitch sending a signal to a control panel.

Page 258: Kidde co2 product manual 050128

December 2004 issue B Manual No 59812-2502

2. SPECIFICATION

Figure 2-1 shows the dimensions (in mm) of the weight indicator mechanism.

Figure 2-1 Dimensions

All screws and steel fittings are zinc plated.

Microswitch details:

Type: Single-pole, volt-free, change-over.Rating: Maximum current 3 A at 125 or 250 V a.c.Sealing: Rated at IP 67 to BS5490.Connections: RED - common.

BLUE - normally open (N/O).YELLOW - normally closed (N/C).

The customer is to provide protective flexible conduit (rated at IP 65 minimum), wire andinsulated crimp pin or blade terminal connectors.

Page 259: Kidde co2 product manual 050128

December 2004 issue B Manual No 59812-2503

3. INSTALLATION

WARNING

THE CO2 CYLINDER IS AT HIGH PRESSURE.

THE ANTI-RECOIL CAP MUST BE FITTED TO THE VALVE OUTLET AND THEPROTECTION CAP MUST BE FITTED BEFORE MOVING THE CO2 CYLINDER.

NORMAL PRESSURE VESSEL HANDLING PRECAUTIONS MUST BE OBSERVED.

THE WEIGHT INDICATOR MECHANISM, FRAME AND CO2 CYLINDER ARE HEAVY.

SAFETY CLOTHING (FOOTWEAR, GLASSES AND HARD HATS) MUST BE WORNWHEN CARRYING OUT INSTALLATION AND MAINTENANCE.

CAUTIONThe frame must be fixed and all floors and walls must capable of supportingoverall weight loadings.

The weight of the weight indicator mechanism is heavy and may operate at anytime. It is therefore recommended that the weight indicator mechanisms and theCO2 cylinders are installed in unoccupied areas.

To install the weight indicator mechanism carry out the following procedure and seeFigures 3-1 through 3-6.

(a) Assemble the mounting frame, supplied by others, to comply with Figure 3-6.

(b) If the weight indicator mechanism is outside or in a damp environment, it isrecommended that the threads are sprayed with oil to keep them free of rust.

(c) Using the mounting rod, fit the body to the mounting frame using the M12 nut andwasher, see Figure 3-5.

Page 260: Kidde co2 product manual 050128

December 2004 issue B Manual No 59812-2504

(d) Remove the terminal box cover, by undoing the four M4x16 mm screws.

Connect the flexible conduit to each terminal box as shown in Figure 3-1.

Make sure that the flexible conduit, rated at IP 65 minimum, passes underneath theweight when it is in the down (operated) position and that it does obstruct themovement of the weight.

Figure 3-1 Flexible Conduit Installation

(e) It is recommended to connect the microswitch in SERIES, this enables the wires tomonitored continuously.

CAUTIONDo not touch the microswitch.

If the microswitch contacts are to be wired in the NORMALLY CLOSED (N/C) position,i.e. in SERIES, carry out the procedure in steps (i) through (iv) and see Figure 3-2.

(i) Remove the BLUE wire from the terminal block, cut 10 mm from it and electricallyinsulate the end with an insulating cap or tape.

(ii) Thread the two core cable through the flexible conduit and connect to the terminalbox as shown in Figure 3-2. Use an insulated crimp pin connector for each wire.

(iii) Replace the terminal box cover.

(iv) On the end/last terminal box, the spare exit hole from the terminal box must besealed or blanked off to maintain IP 65.

NOTE A simpler SERIES installation using a single wire is shown in Figure 3-3.However, the wire will not be monitored continuously.

Page 261: Kidde co2 product manual 050128

December 2004 issue B Manual No 59812-2505

Figure 3-2 Electrical Installation - SERIES Two Wires

Figure 3-3 Electrical Installation - SERIES One Wire

Page 262: Kidde co2 product manual 050128

December 2004 issue B Manual No 59812-2506

If the microswitch contacts are to be wired in the NORMALLY OPEN (N/O) position, i.e.in PARALLEL, carry out the procedure in steps (v) through (viii) and see Figure 3-4.

(v) Remove the YELLOW wire from the terminal block, cut 10 mm from it andelectrically insulate the end with an insulating cap or tape.

(vi) Thread the two core cable through the flexible conduit and connect to the terminalbox as shown in Figure 3-4. Where two wires are to be connected into sameterminal outlet, use an insulated blade terminal connector.

(vii) Replace the terminal box cover.

(viii) On the end/last terminal box, the spare exit hole from the terminal box must besealed or blanked off to maintain IP 65.

Figure 3-4 Electrical Installation - PARALLEL

Page 263: Kidde co2 product manual 050128

December 2004 issue B Manual No 59812-2507

(f) Make sure that the protection cap is fitted and inspect the cylinder for externaldamage.

(g) Weigh the cylinder for correct contents using a scale weighing device and recordthe weight.

WARNINGIF CYLINDERS ARE TO BE MOVED IN A SKID ASSEMBLY, THEY MUST BESECURELY WEDGED IN POSITION TO PREVENT MOVEMENT.

(h) Transport the cylinder to its position at the mounting frame using a suitable trolley.Remove the securing wedge from the cylinder.

(i) Remove the protection cap from the cylinder and store in a safe place.

(j) Screw the neck collar fully onto the cylinder ensuring that all threads are engaged.Make sure that the cylinder valve outlet is in the correct position.

(k) Connect the flexible discharge hose to the manifold and torque to between 30 and40 Nm.

(l) Remove the anti-recoil cap from discharge outlet of the cylinder valve and store in asafe place.

Connect the other end of the flexible discharge hose to the discharge outlet of thecylinder valve and torque to between 30 and 40 Nm.

(m) Fit the two hanger rods through the holes in the body and the neck collar. Securewith an M10 nut and washer on each hanger rod, see Figure 3-5.

Make sure that the M10 nuts are screwed evenly onto the hanger rods by the sameamount.

(n) Tighten the M12 nut, on the mounting rod, until the cylinder is 20 mm from the flooror mounting frame base.

NOTE Make sure that the cylinder is hanging vertically. If not, carefully adjust thenuts on the hanger rods until the cylinder is hanging vertically

(o) Fit an M10 nut to the weight rod and wind halfway down the rod. Fit an M10 washerto the weight rod, followed by the weight, another M10 washer and finally an M10nut. DO NOT TIGHTEN.

(p) With the weight rod in the “full” (uppermost) position, slowly wind the nuts andweight up the rod away from the body, until a position is reached where the weightrod will just begin to drop from its stop.

(q) From this set point, wind the inner nut towards the body by five turns. Hold thisposition and lock the other nut against the weight. With the weight in the “full”position, the indicator is now set.

(r) If required, carry out the testing procedure, refer to Appendix A.

(s) Repeat steps (a) through (r) for each weight indicator mechanism and cylinder.

Page 264: Kidde co2 product manual 050128

December 2004 issue B Manual No 59812-2508

Figure 3-5 Mechanical Installation

Page 265: Kidde co2 product manual 050128

December 2004 issue B Manual No 59812-2509

Figure 3-6 Typical Support Frame

Page 266: Kidde co2 product manual 050128

December 2004 issue B Manual No 59812-25010

4. MAINTENANCE

WARNING

THE CO2 CYLINDER IS AT HIGH PRESSURE.

THE ANTI-RECOIL CAP MUST BE FITTED TO THE VALVE OUTLET AND THEPROTECTION CAP MUST BE FITTED BEFORE MOVING THE CO2 CYLINDER.

NORMAL PRESSURE VESSEL HANDLING PRECAUTIONS MUST BE OBSERVED.

THE WEIGHT INDICATOR MECHANISM, FRAME AND CO2 CYLINDER ARE HEAVY.

SAFETY CLOTHING (FOOTWEAR, GLASSES AND HARD HATS) MUST BE WORNWHEN CARRYING OUT INSTALLATION AND MAINTENANCE.

IT IS RECOMMENDED TO MOVE THE WEIGHT ROD TO THE OPERATED (LOWER)POSITION BEFORE ANY WORK IS CARRIED OUT ON THE CYLINDER AND/ORVALVE.

4.1 Every Six Months

(a) Check tightness of nuts and bolts.

(b) If required, carry out the testing procedure, refer to Appendix A.

4.2 Every Twelve Months

(a) Check the threads for rust, clean and apply an oil spray if necessary

(b) Carry out the six monthly check.

Page 267: Kidde co2 product manual 050128

December 2004 issue B Manual No 59812-25011

APPENDIX A TESTING

WARNING

THE CO2 CYLINDER IS AT HIGH PRESSURE.

THE ANTI-RECOIL CAP MUST BE FITTED TO THE VALVE OUTLET AND THEPROTECTION CAP MUST BE FITTED BEFORE MOVING THE CO2 CYLINDER.

NORMAL PRESSURE VESSEL HANDLING PRECAUTIONS MUST BE OBSERVED.

THE WEIGHT INDICATOR MECHANISM, FRAME AND CO2 CYLINDER ARE HEAVY.

SAFETY CLOTHING (FOOTWEAR, GLASSES AND HARD HATS) MUST BE WORNWHEN CARRYING OUT INSTALLATION AND MAINTENANCE.

If the user wishes to confirm that the weight indicator mechanism is functioning correctly,a test kit can be built, see Figure A-1.

The procedure for testing is given below.

(a) Assemble the test kit as shown in Figure A-1.

(b) With the weight rod in the “FULL” position, carefully lower the test weight, between3.2 and 4.5 kg, onto the test kit.

NOTE The test weight, between 3.2 and 4.5 kg, represents a weight loss of CO2corresponding to between 7 and 10%.

(c) When the weight indicator mechanism is set correctly, the mechanism will trip.

Page 268: Kidde co2 product manual 050128

December 2004 issue B Manual No 59812-25012

Figure A-1 Test Kit

Page 269: Kidde co2 product manual 050128

December 2004 issue B Manual No 59812-25013

APPENDIX B ATEX COMPLIANCE

SPECIAL INSTRUCTIONS FOR COMPLIANCE WITH 94/9/EC

1. Area classification

Weight Indicator Mechanism and Weight Indicator Mechanism Unswitched part numbers,E8731-402 and E8731-403 respectively.

Weight Indicator Mechanisms are used to monitor the contents of CO2 45kg extinguisherassemblies. Weight Indicator Mechanisms have been designed and certified as a non-electric equipment for compliance to the following hazardous area classification:

Group II category 3 GD c T6 X

The user of this equipment should make themselves aware of the following information;

2. Placing the device into service

These Weight Indicator Mechanisms may be installed in an area classified as Zone 2 orZone 22 or unclassified.

3. Safe use of Weight Indicator Mechanisms

Weight Indicator Mechanisms are for use only as a contents indicator system for CO2 45kg extinguishers.

The switched version is to be used with an intrinsically safe supply suitable for the hazardarea.

4. Assembling and dismantling

Weight Indicator Mechanisms are supplied complete and ready to install in accordancewith KFP Weight Indicator Mechanism Users Manual 59812-250.

5. Installation

Weight Indicator Mechanism installation shall be in accordance with KFP WeightIndicator Mechanism Users Manual 59812-250, except that where fitted the switch circuitshall be intrinsically safe and appropriate to the hazard.

6. Maintenance (service and emergency repair)

For maintenance of Weight Indicator Mechanisms refer to manual 59812-250.

7. Adjustment

After Installation adjustment of the Weight Indicator Mechanism is not required. Forinitial set up follow instructions provided in KFP Weight Indicator Mechanism UsersManual 59812-250

8. Training

Consult KFP Weight Indicator Mechanism Users Manual 59812-250 before use.

Page 270: Kidde co2 product manual 050128

December 2004 issue B Manual No 59812-25014

9. Limitations of use

Weight Indicator Mechanisms must only be used within areas specified by the hazardousarea certification as indicated on the equipment label

10. Special Parameters

The ambient temperature for this equipment is –18°C to 55°C.

Page 271: Kidde co2 product manual 050128

Issue A December 2004 59812-4031 of 17

High PressureCarbon DioxideFire Protection Equipment

DIRECT ACTING SOLENOID

Issue A December 2004 Manual No 59812-403

Page 272: Kidde co2 product manual 050128

Issue A December 2004 59812-4032 of 17

PROPRIETARY RIGHTS NOTICE

This document and the information that it contains are the property of KiddeFire Protection Services Ltd. The information contained in this manual isbelieved to be correct in light of the latest data available.Rights to duplicate or otherwise copy this document and rights to disclose thedocument and the information that it contains to others and the right to usethe information contained therein may be acquired only by written permissionsigned by a duly authorised officer of Kidde Fire Protection Services Ltd.

© Copyright 2004 Kidde Fire Protection Services Ltd

Page 273: Kidde co2 product manual 050128

Issue A December 2004 59812-4033 of 17

ASSEMBLY, TEST AND DISASSEMBLYINSTRUCTIONS FOR DIRECT ACTING

SOLENOID ASSEMBLY

IMPORTANT:-

1. BEFORE PROCEEDING, THE FOLLOWING SHOULD ONLY BEATTEMPTED BY TRAINED PERSONNEL WHO ARE FAMILIAR WITHALL THE RELEVANT HAZARDS ASSOCIATED WITH CO2 SYSTEMS.

2. ENSURE THAT THE RECOIL CAP IS FITTED TO THE VALVE OUTLETDURING THE ASSEMBLY OF THE DIRECT ACTING SOLENOIDASSEMBLY.

3. POSITION CYLINDERS IN DESIGNATED LOCATION AND SECUREWITH CYLINDER STRAPS AND ATTACHING HARDWARE.

Page 274: Kidde co2 product manual 050128

Issue A December 2004 59812-4034 of 17

ASSEMBLY INSTRUCTIONSSINGLE CYLINDER INSTALLATION

SPECIFICATION POWER SUPPLY REQUIREMENTS

ENVIRONMENTAL PROTECTION TO BE BS EN 60529 1991 IP65 VOLTAGE RANGE :- 18V DC TO 28V DCNOMINAL COIL RESISTANCE :- 53.2 OHMS CURRENT AT 18V DC :- -338mAMINIMUM FIRING PULSE :- 60ms CURRENT AT 28V DC :- -526MaMAXIMUM FIRING PULSE :- UNLIMITEDELECTRICAL CONNECTION :- DIN PLUG TYPE DIN 43650STORAGE TEMPERATURE RANGE :- -30°C TO +55°COPERATING TEMPERATURE RANGE :- -20°C TO +55°CMAXIMUM WORKING PRESSURE :- 152.5 BAR G

NOTE

ITEMS SHOWN THUS * ARE NOT PART OF THE SOLENOID ACTUATED VALVE AND CYLINDER ASSEMBLIES– THESE ITEMS ARE PURCHASED SEPARATELY.

Page 275: Kidde co2 product manual 050128

Issue A December 2004 59812-4035 of 17

ASSEMBLY INSTRUCTIONSMULTI-CYLINDER INSTALLATION

SPECIFICATION POWER SUPPLY REQUIREMENTS

ENVIRONMENTAL PROTECTION TO BE BS EN 60529 1991 IP65 VOLTAGE RANGE :- 18V DC TO 28V DCNOMINAL COIL RESISTANCE :- 53.2 OHMS CURRENT AT 18V DC :- -338mAMINIMUM FIRING PULSE :- 60ms CURRENT AT 28V DC :- -526MaMAXIMUM FIRING PULSE :- UNLIMITEDELECTRICAL CONNECTION :- DIN PLUG TYPE DIN 43650ASTORAGE TEMPERATURE RANGE :- -30°C TO +55°COPERATING TEMPERATURE RANGE :- -20°C TO +55°CMAXIMUM WORKING PRESSURE :- 152.5 BAR G

NOTE

THE MASTER CYLINDER PLUS 5 SLAVE CYLINDERS ARE THE MAXIMUM NUMBER OF CYLINDERSALLOWED ON ANY ONE SYSTEM.ITEMS SHOWN THUS * ARE NOT PART OF THE SOLENOID ACTUATED VALVE AND CYLINDER ASSEMBLIES– THESE ITEMS ARE PURCHASED SEPARATELY.ITEM SHOWN THUS φ IS SUPPLIED AS 1-OFF WITH THE SOLENOID ACTUATED VALVE. ADDITIONALQUANTITIES SHOULD BE PURCHASED SEPARATELY.

Page 276: Kidde co2 product manual 050128

Issue A December 2004 59812-4036 of 17

ASSEMBLY INSTRUCTIONSVALVE AND CYLINDER ASSEMBLY

REMOVE THE CYLINDER CAP FROM THE VALVE AND CYLINDER ASSEMBLY

Page 277: Kidde co2 product manual 050128

Issue A December 2004 59812-4037 of 17

ASSEMBLY INSTRUCTIONSCYLINDER VALVE ASSEMBLY

REMOVE THE VALVE PROTECTION CAP FROM THE VALVE AND CYLINDER ASSEMBLY.

CHECK THAT THE SEALING FACE IS UNDAMAGED.

Page 278: Kidde co2 product manual 050128

Issue A December 2004 59812-4038 of 17

ASSEMBLY INSTRUCTIONSSOLENOID ASSEMBLY

REMOVE THE SOLENOID COIL FROM THE SOLENOID ASSEMBLY.

ENSURE THE SWIVEL NUT ROTATES FREELY.

Page 279: Kidde co2 product manual 050128

Issue A December 2004 59812-4039 of 17

ENSURE THE `O’ RING SEAL IS CORRECTLY POSITIONED.

ASSEMBLY INSTRUCTIONSCYLINDER VALVE ANDSOLENOID ASSEMBLY

ENSURE RECOIL CAP IS IN POSITION.

ASSEMBLE THE SOLENOID ONTO THE CYLINDER VALVE.

TIGHTEN SWIVEL NUT TO TORQUE 8/10 Nm.

(NOTE – A SHORT BURST OF GAS MAY BE HEARD)

Page 280: Kidde co2 product manual 050128

Issue A December 2004 59812-40310 of 17

ASSEMBLY INSTRUCTIONSCYLINDER VALVE ANDSOLENOID ASSEMBLY

ASSEMBLE THE FLEXIBLE PILOT LOOP TO THE OUTLET PORT ON THE SOLENOIDASSEMBLY, TORQUE TO 2/2.5 Nm.

REASSEMBLE THE SOLENOID COIL TO THE SOLENOID AND FIT THE SOLENOID COILRETAINING NUT.

Page 281: Kidde co2 product manual 050128

Issue A December 2004 59812-40311 of 17

ASSEMBLY INSTRUCTIONSPRESSURE ACTUATOR ASSEMBLY

REMOVE THE SAFETY PIN AND MOVE LEVER TO THE ACTUATE POSITION, ENSUREPISTON MOVES FREELY.

RETURN LEVER TO PARKED POSITION AND REPLACE THE SAFETY PIN.

ASSEMBLE BLEED ASSEMBLY TO PRESSURE ACTUATOR AND TIGHTEN TO TORQUE2/2.5 Nm.

SUPPORT THE PRESSURE ACTUATOR AND CONNECT THE FREE END OF THEFLEXIBLE PIPE LOOP (ITEM 3) AND TIGHTEN TO TORQUE 2/2.5 Nm.

DEPRESS THE PISTON OF THE PRESSURE ACTUATOR AND CHECK PISTONREMAINS IN THE DEPRESSED STATE.

MOVEMENT OF THE PISTON WILL INDICATE A LEAK AT THE SOLENOID – IFMOVEMENT OCCURS REPLACE THE SOLENOID.

Page 282: Kidde co2 product manual 050128

Issue A December 2004 59812-40312 of 17

ASSEMBLY INSTRUCTIONSCYLINDER VALVE AND

PRESSURE ACTUATOR ASSEMBLY

ASSEMBLE THE PRESSURE ACTUATOR TO THE CYLINDER VALVE, ENSURING THATTHE RETENTION PIN IS IN PLACE AND THE FLEXIBLE PILOT LOOP IS FREE OF KINKS.

Page 283: Kidde co2 product manual 050128

Issue A December 2004 59812-40313 of 17

ASSEMBLY INSTRUCTIONSDIN CONNECTOR PLUG ASSEMBLY

Page 284: Kidde co2 product manual 050128

Issue A December 2004 59812-40314 of 17

DISASSEMBLY INSTRUCTIONSSOLENOID REMOVAL

REMOVAL OF SOLENOID ASSEMBLY FROM CYLINDER VALVE

DISCONNECT THE DIN PLUG FROM SOLENOID.

DISCONNECT THE PILOT LOOP FROM SOLENOID.

SLOWLY UNSCREW THE SOLENOID SWIVEL NUT (AFTER ONE/TWO REVOLUTIONS ASHORT DISCHARGE OF GAS WILL BE AUDIBLE) AND FULLY REMOVE THE SOLENOIDAND RETAIN THE `O’ RING SEAL.

CAREFULLY CHECK THE `O’ RING SEAL FOR DAMAGE BEFORE REASSEMBLY.IF DAMAGED THE SEAL MUST BE REPLACED.

CHECK THAT THE CYLINDER VALVE POPPET HAS RESEALED BY APPLYING LEAKSEEKING FLUID TO THE POPPET ORIFICE.

IF ANY LEAKAGE OCCURS RESEAT THE POPPET SEAL BY REASSEMBLING THESOLENOID (EXCLUDING THE `O’ RING SEAL) UNTIL ESCAPING GAS IS AUDIBLE.IMMEDIATELY UNSCREW AND REMOVE THE SOLENOID ASSEMBLY.

TO PROTECT THE CYLINDER VALVE SEALING FACE IMMEDIATELY ASSEMBLE THEPROTECTION CAP TO THE VALVE.

IMPORTANT:- IF THE VALVE CONTINUES TO LEAK, CONTACT THE EQUIPMENTMANUFACTURER FOR FURTHER INFORMATION.

Page 285: Kidde co2 product manual 050128

Issue A December 2004 59812-40315 of 17

DISASSEMBLY INSTRUCTIONSPRESSURE ACTUATOR REMOVAL

REMOVAL OF PRESSURE ACTUATOR FROM CYLINDER VALVE

DISCONNECT THE PILOT LOOP/PILOT LOOPS FROM THE PRESSURE ACTUATOR.

REMOVE THE RETENTION PIN.

SLIDE THE PRESSURE ACTUATOR OFF THE CYLINDER VALVE.

IMPORTANTIF THE PRESSURE ACTUATOR TO BE REMOVED IS MOUNTED ON A SLAVE CYLINDERIN A MULTI-CYLINDER ASSEMBLY, DISCONNECT THE DIN PLUG AND THE PILOTLOOP FROM THE SOLENOID ASSEMBLY MOUNTED ON THE MASTER CYLINDERBEFORE PROCEEDING WITH THE REMOVAL OF THE PRESSURE ACTUATOR.

Page 286: Kidde co2 product manual 050128

Issue A December 2004 59812-40316 of 17

TEST INSTRUCTIONSSINGLE CYLINDER INSTALLATION

KEEPING THE FLEXIBLE PILOT LOOP ATTACHED TO THE PRESSURE ACTUATOR ANDSOLENOID ASSEMBLY, REMOVE THE PRESSURE ACTUATOR FROM THE CYLINDERVALVE BY REMOVING THE RETENTION PIN.

APPLY THE CORRECT ELECTRICAL POWER TO THE SOLENOID AND CHECK THATTHE PISTON IS FULLY EXTENDED FORWARD, CHECK THAT ALL JOINTS (EXCEPT THEBLEED ASSEMBLY OUTLET) ARE LEAK TIGHT.

TO RESET THE SOLENOID, EITHER REVERSE THE POLARITY OF THE COIL (FORAPPROXIMATELY ONE SECOND) OR REMOVE THE COIL FROM THE SOLENOID ANDREASSEMBLE IT `IMPORTANT’. THIS SHALL BE CARRIED OUT WITH THE POWERSUPPLY ISOLATED TO THE COIL. THEN DEPRESS THE BLEED BUTTON UNTIL ALLGAS HAS VENTED.

FULLY DEPRESS THE PRESSURE ACTUATOR PISTON (BY HAND) AND CHECK THATTHE PISTON REMAINS IN THE DEPRESSED STATE. MOVEMENT OF THE PISTON WILLINDICATE A LEAK AT THE SOLENOID.

REASSEMBLE THE PRESSURE ACTUATOR TO THE CYLINDER VALVE USING THERETENTION PIN.

Page 287: Kidde co2 product manual 050128

Issue A December 2004 59812-40317 of 17

TEST INSTRUCTIONSMULTI-CYLINDER INSTALLATION

KEEPING THE FLEXIBLE LOOPS ATTACHED TO ALL THE PRESSURE ACTUATORSAND THE SOLENOID ASSEMBLY, REMOVE THE PRESSURE ACTUATORS FROM ALLTHE CYLINDER VALVES BY REMOVING THE RETENTION PINS. ADEQUATELYSUPPORT TO ENSURE PILOT LOOPS ARE KINK FREE.

APPLY THE CORRECT ELECTRICAL POWER TO THE SOLENOID AND CHECK THATALL THE PISTONS ARE FULLY EXTENDED FORWARD, CHECK THAT ALL JOINTS(EXCEPT THE BLEED ASSEMBLY OUTLET) ARE LEAK TIGHT.

TO REST THE SOLENOID, EITHER REVERSE THE POLARITY OF THE COIL (FORAPPROXIMATELY ONE SECOND) OR REMOVE THE COIL FROM THE SOLENOID ANDREASSEMBLE IT `IMPORTANT’. THIS SHALL BE CARRIED OUT WITH THE POWERSUPPLY ISOLATED FROM THE COIL. THEN DEPRESS THE BLEED BUTTON UNTIL ALLGAS HAS BEEN VENTED.

FULLY DEPRESS ALL THE PRESSURE ACTUATOR PISTONS (BY HAND) AND CHECKTHAT THE PISTONS REMAINED DEPRESSED. MOVEMENT OF THE PISTON WILLINDICATE A LEAK AT THE SOLENOID.

REASSEMBLE THE PRESSURE ACTUATORS TO THE CYLINDERS VALVES USING THERETENTION PINS.

Page 288: Kidde co2 product manual 050128

High PressureCarbon DioxideFire Protection Equipment

Owners Manual

Manual No. 59812-405

Issue A December 2004

Page 289: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-405 Issue A December 2004

Page 2 of 10

PROPRIETARY RIGHTS NOTICE

This document and the information that it contains are the property ofKidde Fire Protection Services Ltd. The information contained in thismanual is believed to be correct in light of the latest data available.Rights to duplicate or otherwise copy this document and rights todisclose the document and the information that it contains to others andthe right to use the information contained therein may be acquired onlyby written permission signed by a duly authorised officer of Kidde FireProtection Services Ltd.

© Copyright 2004 Kidde Fire Protection Services Ltd

Page 290: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-405 Issue A December 2004

Page 3 of 10

KIDDE FIRE PROTECTIONHigh Pressure CO2 Fire Protection Equipment

OWNERS MANUAL

This manual is to familiarise you and your personnel with your Kidde Fire ProtectionHigh Pressure CO2 Fire Suppression Equipment.

IMPORTANT

It is your responsibility as the system owner to read this manual to ensureproper system operation and personnel safety. Follow the instructions in thismanual and on the container nameplates. Review these instructions with youremployees every 6 months or more frequently. Place this manual in anaccessible place near the system for ready reference.

IMPORTANT

This system is made up of units tested within limitations contained in thedesign, installation, operation and maintenance manual. The system designermust be consulted whenever changes are planned for the system or area ofprotection. A Kidde distributor must be consulted after the system hasdischarged.

IMPORTANT

The technical data contained herein is limited strictly for informationalpurposes only. Kidde believes this data to be accurate, but it is published andpresented without any guarantee or warranty whatsoever. Kidde disclaimsany liability for any use that may be made by the data and informationcontained herein by any and all other parties.

YOUR KIDDE DISTRIBUTOR IS:

ENTER EMERGENCY NUMBER FOR FIRE BRIGADE HERE:

Page 291: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-405 Issue A December 2004

Page 4 of 10

ATTENTION INSTALLER

This form must be signed by the system owner indicating that he/she has received acopy of this Owner’s Manual Part Number 59812-405. Retain a copy of this form foryour records.

1. System Installed:

2. Listing of Major System Components:

3. Description of Hazard Protected by System:

Owner or Authorised Representative Date

Page 292: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-405 Issue A December 2004

Page 5 of 10

WARNING

PRESSURISED (CHARGED) CONTAINERS ARE EXTREMELYHAZARDOUS AND IF NOT HANDLED PROPERLY ARECAPABLE OF VIOLENT DISCHARGE. THIS MAY RESULT INSERIOUS BODILY INJURY, DEATH AND PROPERTY DAMAGE

Before handling Kidde products, all personnel must be thoroughly trained in the safehandling of pressurised containers as well as in the proper procedures forinstallation, removal, filling and connection of other critical devices, such assolenoids, cable assemblies, pressure switches and safety caps. READ andUNDERSTAND and ALWAYS FOLLOW: the Kidde Fire Protection High PressureCO2 Fire Protection Equipment Installation, Operation, Commissioning andMaintenance Manual (Part Number 59812-400), that is provided with the individualsystems, or can be obtained from Kidde Fire Protection.

Hazards to personnel

Exposure to atmospheres containing about 5% CO2 leads to shortness of breath andslight headache. At the 10% level, headache, visual disturbance, ringing in the ears(tinnitus) and tremor are followed by loss of consciousness.

Fire extinguishing concentrations of CO2, which are normally in excess of 30%,especially near to the point of discharge from total flooding or local applicationsystems, carry a risk of almost immediate asphyxiation. The gas is also more densethan air and will drift and accumulate in low spaces, such as cellars, pits and floorvoids, which may be difficult to ventilate effectively.

The rapid expansion of large quantities of CO2 results in a substantial localisedcooling of the installation and of the air surrounding the point of discharge. This canpresent a frostburn hazard.

Moving of Containers

The following safety procedures must be observed at all times:

Handling of cylinders should be conducted by TRAINED AND COMPETENTpersonnel only.

Transportation: Containers must be shipped compactly and properly secured inplace. Containers must not be rolled, dragged, or slid nor allowed to be slid from tail-gates of vehicles. A suitable hand truck, fork truck, roll platform or similar devicemust be used.

Rough Handling: Containers must not be dropped or permitted to strike violentlyagainst each other or other surfaces.

Storage: Containers must be stored standing upright where they are not likely to beknocked over, or the containers must be secured.

Page 293: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-405 Issue A December 2004

Page 6 of 10

Safety Caps:

THESE INSTRUCTIONS MUST BE FOLLOWED TO PREVENT SERIOUS INJURY,DEATH OR PROPERTY DAMAGE.

(a) Each CO2 container is factory equipped with a valve protection safety cap.This device is a safety feature, and is a legislative requirement fortransportation.

(b) Each valve is equipped with a safety cap installed on the container outlet.This device is a safety feature, and will provide controlled, safe dischargewhen installed if the container is actuated accidentally.

(c) These caps must be installed on the container AT ALL TIMES except whenthe containers are connected into the system piping. Do not remove safetycaps until the cylinder has been securely fixed / bracketed to a load bearingstructure.

(d) All valve protection caps shall be retained for future transportationrequirements. e.g. when cylinders are returned for refill or service.

For additional information on safe handling of compressed gas containers in theUnited Kingdom, the Health and Safety Executive Guidance Notes are applicable.These are available from: Health and Safety Executive regional offices or HMSOoutlets or online at www.hse.gov.uk/cdg/pdf/safusgc.pdf

All appropriate European Standards that are in force must be satisfied.

Thank you for purchasing a Kidde Fire Protection High Pressure CO2 FireSuppression System. This owner’s manual is provided to instruct you and youremployees.

IMPORTANT

This owner’s manual does not cover every detail of step-by-step installationprocedures for the Kidde CO2 system. This information is available in theInstallation, Operation and Maintenance Manual (Part No. 59812-400), whichmay be obtained from Kidde Fire Protection.

ABOUT YOUR SYSTEM

Your Kidde CO2 system is designed for either total flooding or local applicationsuppression. Examples of typical CO2 system applications include:

* Electrical Equipment.

* Dust collectors.

* Computer Installations.

* Flammable Liquid Stores.

* Archives.

Page 294: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-405 Issue A December 2004

Page 7 of 10

HOW YOUR CO2 SYSTEM OPERATES

Your system is designed to discharge a specific amount of CO2 through nozzleslocated within the hazard area. The amount of CO2 necessary for your system hasbeen carefully calculated to meet strict requirements set by FM Approvals, NFPA 12and BS 5306 part 4. Additional code requirements may apply depending upon theapplication, design specifications, and the authority having jurisdiction.

Basically, your CO2 system consists of:

* High Pressure CO2 container(s), discharge piping and nozzles.

* Actuation devices – electric and mechanical.

* Detection, alarm devices and control panel.

Your system must be provided with means for manual operation using one or both ofthe following approved devices:

* Electric actuation station.

* Automatic detector (control panel required).

Automatic system operation (if provided) can be electric using heat detectors,photoelectric or ionization smoke detectors or optical flame detectors.

An electromechanical actuator is used to operate the first cylinder. Pressure is usedto open the valves on additional cylinders as applicable.

Additional Safety devices (such as lock-off valves) are required for manned areas.

If your system has a control panel, refer to the appropriate Kidde control panelmanual as applicable.

HOW CO2 WORKS

CO2 extinguishes fire by reducing the oxygen content of the atmosphere to a pointwhere it will not support combustion. Reducing the oxygen content from the normal21% in air to 15% will extinguish most surface fires, though for some materials agreater reduction is necessary. In some applications the cooling effect of CO2 mayassist extinction.

INSTALLATION OF YOUR SYSTEM

Your Kidde CO2 fire suppression system must be installed by a Kidde distributor.Your system must be installed in a professional manner with genuine Kiddecomponents and installation materials as specified in the CO2 Installation, Operationand Maintenance Manual (Part No. 59812-400).

DO NOT ACCEPT POOR WORKMANSHIP, MISSING SYSTEMPARTS, OR SUBSTITUTE SYSTEM COMPONENTS!

Page 295: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-405 Issue A December 2004

Page 8 of 10

The following items must be checked after the system is installed:

1. All areas requiring protection are protected.

2. A means of manually discharging the CO2 system is provided in a readilyaccessible location outside the risk area where it can be operated whileleaving the vicinity of the hazard area. The manual control must be clearlylabelled. The installer of your CO2 system should answer any questions youhave regarding the components and coverage of the system.

The installer must also demonstrate that the installed system conforms to therequirements of the CO2 Installation, Operation and Maintenance Manual (Part No.59812-400), the requirements of your insurance carrier and any authorities havingjurisdiction in your area.

INSTRUCTIONS IN CASE OF FIRE

1. Suspend all operations in the fire area. Direct all occupants to leave the firearea immediately. DO NOT WAIT FOR THE SYSTEM TO OPERATEAUTOMATICALLY – OPERATE SYSTEM MANUALLY, WHENEVACUATION OF ALL OCCUPANTS IS COMPLETE, USING THEMANUAL RELEASE.

2. Have someone contact the fire brigade immediately, no matter how small thefire appears to be. Post the fire brigade number and YOUR ADDRESSbeside each telephone. Advise the fire brigade that a CO2 discharge hasoccurred.

3. Do not return until the area has been made safe and completelyventilated to remove all CO2.

POST-FIRE INSTRUCTIONS

After the system has discharged, DO NOT ATTEMPT TO RESUME OPERATIONSIN THE FIRE AREA. Contact your Kidde distributor to reset and recharge yoursystem. Insist that the system be recharged immediately and only with the propertype and quantity of agent.

Page 296: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-405 Issue A December 2004

Page 9 of 10

INSPECTION AND MAINTENANCE OF YOUR SYSTEM

IMPORTANT

The owner of the Kidde CO2 fire suppression system has the responsibility andduty to comply with these instructions. Failure to do so may result ininadequate system performance, property damage and personal injury.

Refer to the Kidde CO2 Installation, Operation and Maintenance Manual (Part No.59812-400) for additional inspection information.

Weekly

1. Visually inspect the hazard and the integrity of the enclosure for changeswhich may effect the performance of the system.

2. Visually inspect the pipework for damage and that all operating controls andcomponents are properly set and undamaged.

3. Check Nitrogen Pilot cylinder(s) pressure gauge.

4. Check Detectors for signs of damage.

5. Manual Release Points are accessible & clearly labeled

6. Check weight monitoring devices if applicable.

Monthly

1. Make a general inspection of all equipment for damaged or missing parts. Ifequipment requires replacement, contact your Kidde distributor.

2. Ensure access to hazard areas, manual pull stations, discharge nozzles, andcylinders are unobstructed.

CAUTION

Nozzles must never be painted. A part number is located oneach. Nozzles must be replaced by nozzles of the same partnumber. They must never be interchanged since randominterchanging of nozzles could adversely affect proper CO2distribution and concentration level within a hazard area.

3. Check that all personnel who may have to operate the system are properlytrained and authorised to do so. All new employees must be instructed in itsuse.

Six (6) Monthly

1 Inspection of all cylinders and equipment by Kidde Distributor per theprocedures detailed in the appropriate Installation, Operation andMaintenance Manual (Part Number 59812-400).

For more information regarding inspection and maintenance, contact your Kiddedistributor or Kidde Fire Protection.

Page 297: Kidde co2 product manual 050128

© K.F.P.S. Ltd 59812-405 Issue A December 2004

Page 10 of 10

YOUR RESPONSIBILITIES AND RELATED EQUIPMENT REQUIREMENTS

1. Ensure an appropriate risk assessment has been conducted to establish therequirement for additional protection in all areas. Supplementary Portable fireextinguishers may be required.

2. Read, understand, and follow the instructions in this manual and on thecontainer nameplates. Review these instructions with your employees every6 months or more frequently. Place this manual in an accessible area nearthe CO2 system for ready reference. Post the name, phone number andaddress of your Kidde distributor near your telephone. Also, post theemergency telephone number of the fire brigade and your address near yourtelephones.

3. If any condition exists which would render your CO2 system inoperative orineffective, SUSPEND ALL OPERATIONS IN THE PROTECTED AREAIMMEDIATELY. Have the condition corrected by your Kidde distributorbefore resuming operations.

Page 298: Kidde co2 product manual 050128

High PressureCarbon DioxideFire Protection Equipment

APPROVALS

Page 299: Kidde co2 product manual 050128

High PressureCarbon DioxideFire Protection Equipment

BULLETINSPlease insert future bulletins in this section