Page 1: Katalog City Multi

VRF SeriesR410A

Page 2: Katalog City Multi

2

For large applications such as office blocks, hotels andlarge retail stores, City Multi VRF-Systems (variable re-frigerant flow) offer significant advantages over cen-tralised plant systems.A certain times of the year, many buildings can requirecooling in some areas and heating in others – even inadjacent rooms.The outstanding City Multi R2 and WR2 systems meetthis requirement by distributing surplus heat fromcooling operations to rooms where it is needed.This can result in energy savings of up to 20% overconventional systems. The water-cooled WR-systemis adaptable specially to high-rise buildings.

City Multi-Series Y and R2

Page 3: Katalog City Multi

3

City Multi advantages:● Wide range of outdoor units

available with capacities of 14.0 – 140.4kW for cooling andfrom 16.0 – 156.5kW for heating.

● Up to 42 indoor units can be con-nected to a single refrigerant cir-cuit (City Multi Super Y system)

● A choice of 71 indoor and 36 out-door units allow configuration ofindividualised systems. MitsubishiElectric has also developed twospecialised IT air conditioners thatmeet the most demanding re-quirements of computer centresand IT equipment rooms.

● The outdoor units (8-50HP) have a coated Blue Fin heat exchangerwith very effective protectionagainst aggressive atmospheres.

● You can use standard T-connec-tors as junctions, special T-con-nectors are not required. This sig-nificant reduces material costs.

● Unique 2-pipe system for simulta-neous cooling and heating opera-tion. R2 with air-cooled and WR2with water-cooled heat exchang-ers. Mitsubishi Electric has suc-ceeded in eliminating the thirdpipe required in conventional sys-tems, significantly reducing instal-lation overheads and costs.

● Up to 50% power savings with theheat recovery system. The heatenergy recovered in cooling opera-tion is used for simultaneous heat-ing operation.

● Connection to local or central con-trollers of building managementsystems possible with floatingcontacts, 12V DC outputs, LONWorks or BACNET.

● The outdoor units up to 45kWhave entirely internal piping, elimi-nating the need for installation ofadditional piping on site. The unitsup to 50HP require a maximum of8 connections. This is unmatchedby any other units on the marketand significantly reduces installa-tion overheads.

● The special design of the heat ex-changers in the outdoor units andthe inverter controlled condenserfans guarantee extremely lownoise levels at the outdoor units(10HP 49dB(A) at 1m during nightoperation).

● Very low startup currents thanks tofull inverter drive technology

● DC compressor technology

● The temperature range in heatingoperation of +15.5 – -20°C out-door temp, makes it possible to in-stall monovalent City Multi sys-tems in very cold regions.

● For applications requiring very lowindoor temperatures the PEFY-Pand PFFY-P indoor units have aspecial function with which roomscan be cooled down to tempera-tures of 14°C.

● All the components of the CityMulti system are designed formaximum efficiency and achieveoutstanding COP (Coefficient OfPerformance) values with R410Arefrigerant.

Page 4: Katalog City Multi

4

City Multi Y Series The City Multi Y series uses 2-pipetechnology for cooling and heatingmode. Users can switch modesmanually and adjust individually forthe most comfortable room cli-mate. The system is very versatileñ you can connect up to 42 differ-ent indoor units to a single refriger-ant circuit, and the capacities of allthe connected systems can rangefrom 50% to 130%.

City Multi R2 SeriesThe City Multi R2 series is speciallydesigned for power-conserving,environment-friendly installations inmodern buildings. Sealed buildingswith minimal natural air exchangeand office equipment like PCs,printers, copiers etc. that give off agreat deal of heat require modernair conditioning systems capable ofsimultaneous cooling and heating.The „fuzzy logic“ used in this seriesallows precise adjustment of up to32 indoor units (City Multi Big R2Series) for individual usersí needs.The outdoor unit is fitted with thelatest inverter drive technology, en-abling the compressor to be run atdown to 16% of its rated capacity.In the WR2 series recovered heat isoutput to a water circuit, allowing itbe stored or used in other locationsin other WR2 systems. The heart ofevery R2 system is the BC Con-troller – a refrigerant distributor thatlinks with the outdoor unit to form asingle refrigerant and control sys-tem, thus enabling efficient heat re-covery. The capacities of all theconnected systems can range from50% to 150%.

Remote Control /Central ControlWall-mounted and hand-held infra-red remote control units are avail-able for the City Multi Y and R2 se-ries for operation of the individualindoor units. Group, system andcentral remote control units withwhich you can control up to 200 in-door units are also available. Forlarger systems a PC-based systemcan be used to control up to 2,000indoor units, and the LON Worksinterface is available for connectingthe air conditioners to buildingmanagement systems.

Combining City Multi withExternal Ventilation Sys-temsSpecial LEV kits are available forconnecting the City Multi outdoorunits to external ventilation sys-tems. This passes on all the bene-fits of the City Multi outdoor unitsto the external systems, ensuring aperfectly fresh climate at all times.Please ask for more information!

Measurement conditions for the MITSUBISHI ELECTRIC air conditioners:Cooling: Indoor 27°C (DB) / 19°C (WB)

Outdoor 35°C (DB) / 24°C (WB)(Outdoor cooling water temperature for WR2: 30°C)

Heating: Indoor 20°C (DB)Outdoor 7° C (DB) / 6° C (WB)(Outdoor cooling water temperature for WR2/WY: 20°C)Refrigerant line length 7.5m (one way), �H = 0m.Sound pressure level measured in free field, outdoor unit measure-ment point at height of 1m and 1m away from the unit. For indoorunits point depends on unit model, see specifications.

GuaranteedOperating Range:● Cooling: Indoor 15° – 24°C

(WB) / Outdoor -15° – 43°C (DB) (Outdoor cooling water tempera-ture for WR2/WY: 10° – 45°C)

● Heating (Y Series):Indoor 15° – 27°C (DB) /Outdoor -20° – 15.5°C (WB)

● Heating (R2 Series):Indoor 15° – 27°C (DB) /Outdoor -20° – 15.5°C (WB)(Outdoor cooling water temperatu-re for WR2: 10° - 45°C)

Page 5: Katalog City Multi

City Multi Systems:Economic, efficient and high-quality

Cooling or HeatingThe City Multi Y-Series stands for maximum possible flexibility. A wide line-up of indoor units in combination with a flexible piping system can conform to any layout. From 1 to 42 various indoor models can be connected to Y-Standard, BIG Y and SUPER Y outdoor units, as well as to the water-cooled version WY. All indoor units connected to only one refrigerant circuit with 14 to 140 kW cooling capacity. This enables easy air conditioning of areas requiring individual control.

5

Y-SeriesOutdoor unit

Indoor unit

Indoor unit

Header BranchWY-Series

Outdoor unit

Waterpiping

Page 6: Katalog City Multi

6

Simultaneous Cooling and Heating The City Multi R2- and WR2-Series allow simultaneous cooling and heating as 2-pipe-system – unique worldwide. Via the BC-Controller (Master + max. 2x Slave) up to 32 indoor units can be connected with one outdoor unit, using only two pipes and energy-saving heat recovery operation. Economy and efficiency are guaranteed. Smooth auto-switching (heating/cooling) based on individual set temperature realises easier operation and more comfortable environment.The WR2-Series with water-cooled outdoor units provides the same well-known advantages of the R2-Series and is specially used for high-rise buildings.

R2-SeriesOutdoor unit

WR2-SeriesOutdoor unit

Waterpiping

Two-Pipe system

Conference room(cooling)

BC Controller

Conferenceroom (heating)

Office (heating)

OA room(cooling)

Indoor unitas ceiling cassette

Office (heating)

Connection

Office(cooling)

World-wide the onlysystem for simultaneouscooling and heatingwith 2 pipes.

Page 7: Katalog City Multi

Direct expansion format for excess refrigerant pipes

7

R2-SerieRefrigerant piping restrictionsTotal length ………………………………………………………maximum 400 m*Greatest length ……………………………………………………………. 150 m(Equivalent greatest length ………………………………………………. 175 m)Between outdoor unit/BC-Controller ……………………………… ……. 110 mBetween BC-Controller/indoor unit ………………………………………… 40 mTop-bottom differentials betweenIndoor/outdoor unit (outdoor higher) ………………………………………... 50 mIndoor/outdoor unit (outdoor lower) ………………………………………… 40 mIndoor unit/BC-Controller …………………………………..………….… 15 m**Indoor units ……………………………………………………………… 15 m**

* based on distance outdoor unit and BC-Controller maximum 70 m.** maximum 10 m for indoor units type P200 and P250.

Y-SerieRefrigerant piping restrictionsTotal length ………………………………… …………………………….. 300 mGreatest length …………………………………………………………… 150 m(Equivalent greatest length ……………………………………………… 175 m)Greatest length after first branch …………………………………… …….. 40 mTop-bottom differentials betweenIndoor/outdoor unit (outdoor higher) ………………………………… …... 50 mIndoor/outdoor unit (outdoor lower) ………………………………… …… 40 mIndoor units ……………………………………………………………….… 15 m

Big R2-Serie Refrigerant piping restrictionsTotal length ……………………………… ……………………….. maximum 400 m*Greatest length ……………………………………………………………..…. 150 m(Equivalent greatest length …………………………………………………… 175 m)Between outdoor unit/Master-Controller ………………………………………. 110 mBetween BC-Controller (Master)/indoor unit …………………………………… 40 mTop-bottom differentials betweenIndoor/outdoor unit (outdoor higher) …………………………………….……… 50 mIndoor/outdoor unit (outdoor lower) ……………………………………………. 40 mIndoor unit/BC-Controller (Master, Slave) ……………………………………. 15 m**Indoor units ………………………………………………………………….… 15 m**Master/Slave-Controller ……………………………………………………… 15 m**

* based on distance outdoor unit and BC-Controller maximum 70 m.** maximum 10 m for indoor units type P200 and P250.

outdoor unit

greatest length 150 m

top-bottom differentials between indoor units 15 mindoor unit

top-bottom differential

50 m

outdoor unit

top-bottom differential

50 mlength between outdoor unit and BC-Controller maximum 110 m

length between BC-Controllerand indoor unit maximum 40 m

top-bottom differentials between indoor units and indoor unit/BC-Controller 15 m

top-bottom differential

50 m

outdoor unit

length between BC-Controller and indoor unit maximum 40 m

top-bottom differentials between indoor units and indoor unit/BC-Controller 15 m

PUMYRefrigerant piping restrictionsTotal length ……………………………………………………………….. 100 mGreatest length …………………………………………………………… 70 mGreatest length after first branch ………………………………… …….. 30 mTop-bottom differentials betweenIndoor/outdoor unit (outdoor higher) ……………………………………... 30 mIndoor/outdoor unit (outdoor lower) ……………………………………… 20 mIndoor units …………………………………………………………….… 12 m

outdoor unit

greatest length 70 m

top-bottom differentials between indoor units 12 m

indoor unit

top-bottom differential 30 m

Page 8: Katalog City Multi

8

Outdoor unit

4-way valve

Highpressuregas Low pressure gas

Highpressure gas

Heatexchanger

Check valve

Compressor

Fan

Low pressure pipe

Gas/liquidseparator

High pressure 2-phase

High pressure pipe

BC controller

Switching valve Indoor unit

Low pressure 2-phase

High pressure liquid

Cooling

Cooling

Cooling

Heating

LEV

Ope

ratio

n pr

imar

ily fo

r coo

ling

BC controller

Indoor Indoor Indoor IndoorIndoor Indoor

BC controller

To outdoor unit

Joint pipe kit (CMY-R160) Branch pipe (CMY-Y102S-F)

Below Models P20-P50 Models P50-P140 Models P200, P250

Reducer(attached)

Max. 3 sets for 1 connectionTotal capacity below 140(But same cooling/heating mode)

BC-Controller Operations

Operation primarily for cooling Total heat recovery operation

BC-Controllerfor R2-Systems

BC-Controller -the R2 and WR2(simultaneous heating/coolingsystem) refrigerantcircuit core

The compact BC-Controller connects several indoor units to oneoutdoor unit and efficiently distributesrefrigerant in accordance with heating(gas refrigerant) and cooling (liquidrefrigerant) modes.

Low pressure gas

Low pressure gas

Low pressure gas

Low pressure gas

Highpressure gas

Highpressure gasTo

tal h

eat r

ecov

ery

oper

atio

n

Low pressure 2-phase

High pressure liquid

Cooling

Cooling

Heating

Heating

High pressure gasL

g p gLow pressure gas Low pressure 2-phase

p pHigh pressure liquid High pressure 2-phase

Page 9: Katalog City Multi

9

CITY MULTI SystemsOutdoor Units Cooling or Heating●

Cooling only●

Cooling and Heating●

Type

Cooling (kW)

Heating (kW)

● ● ● ●

● ● ● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ● ● ●

● ●

Y-Series/Big Y-Series

700

78.4

88.0

750

84.0

94.5

800

90.0

100.0

850

96.0

108.0

1000

113.0

127.0

950

108.0

119.5

900

101.0

113.0

1050

118.0

132.0

1100

124.0

140.0

1150

130.0

145.0

1200

136.0

150.0

Super Y-Series PUHY + PUHN

PUHY

PQRY

PURY

PUMY

PUY

PUHY

R2-Series/Big R2-Series

WR2-Series

●●

PQHYWY-Series

● ●

1250

140.0

156.5

Capacity Type

Cooling (kW)

Series Heating (kW)

125

14.0

16.0

200

22.4

25.0

250

28.0

31.5

300

33.5

37.5

450

50.0

56.0

400

45.0

50.0

350

40.0

45.0

500

56.0

63.0

550

63.0

67.0

600

67.4

75.0

650

73.0

81.5

Capacity Type

Cooling (kW)

Type Heating (kW)

125

14.0

16.0

200

22.4

25.0

250

28.0

31.5

300

33,5

37.5

450

50.0

56.0

400

45.0

50.0

350

40,0

45.0

500

56.0

63.0

550

63.0

67.0

600

67.4

75.0

650

73.0

81.5

Capacity

Type

Page 10: Katalog City Multi

10

* The noise levels are measured at a position 1 m in front of and 1 m above the unit in anechoic chamber.** one-way

1-20 / 20-2501-19 / 20-2501-16 / 20-2501-13 / 20-250Connectable indoor units (Number/Type)19.216.113.010.3(A)RUNNING CURRENT

88810(A)STARTING CURRENT11.399.577.726.14(kW)MAX. INPUT POWER

380-415V, 50Hz, 3380-415V, 50Hz, 3380-415V, 50Hz, 3380-415V, 50Hz, 3(V, Freq.,Phase)

ELECTRICAL SUPPLY28222218s.12101010fl.Ø (mm)PIPE SIZE9.59.59.57.0(kg)REFRIGERANT CHARGE

50505050(m)MAX. HEIGHTDIFFERENCE

300300300300(m)MAX. PIPE LENGTH**1840184018401840Height840840840840Depth990990990990Width(mm)DIMENSIONS233233233218(kg)WEIGHT60595756dB(A)NOISE*

12000120001200012000(m³/h)AIRFLOW40.033.528.022.4(kW)COOLING CAPACITY

PUY-P350 YGM-APUY-P300 YGM-APUY-P250 YGM-APUY-P200 YGM-AMODEL REFERENCESTANDARD Y OUTDOOR UNITS, COOLING ONLY

City Multi Y-Series: PUY-P200-350YGM-A, Cooling only

Outdoor units - Technical dataCity Multi Y-Series, Cooling or Heating

* The noise levels are measured at a position 1 m in front of and 1 m above the unit in anechoic chamber.** one-way*** R407C factory charged to 50 m pipe length (one-way)

1-8 / 20-125Connectable indoor units (Number/Type)9.1(A)RUNNING CURRENT8(A)STARTING CURRENT

5.58(Heating)5.95(Cooling)(kW)MAX. INPUT POWER

380-415V, 50Hz, 3(V, Freq.,Phase)

ELECTRICAL SUPPLY18s.10fl.Ø (mm)PIPE SIZE

8.5(kg)REFRIGERANT

CHARGE***

30(m)MAX. HEIGHTDIFFERENCE

100(m)MAX. PIPE LENGTH**1280Height350Depth1020Width(mm)DIMENSIONS127(kg)WEIGHT54dB(A)NOISE*

5400(m³/h)AIRFLOW16.0(kW)HEATING CAPACITY14.0(kW)COOLING CAPACITY

PUMY-P125YMAMODEL REFERENCEOUTDOOR UNIT PUMY-P125YMA WITH R407C

Cooling or Heating: PUMY-P125YMA forR407C (from September 2005 availablein R410A)

Page 11: Katalog City Multi

11

City Multi Big Y: PUHY-P450-650YGM-A

1-32 / 20-2501-32 / 20-2501-24 / 20-2501-24 / 20-2501-24 / 20-250Connectable indoor units (Number/Type)31.528.227.325.021.8(A)RUNNING CURRENT19.8217.7316.3715.8913.86(Heating)19.6517.5917.0815.5913.61(Cooling)(kW)MAX. INPUT POWER

380-415V,50Hz, 3

380-415V,50Hz, 3

380-415V,50Hz, 3

380-415V,50Hz, 3

380-415V,50Hz, 3

(V, Freq.,Phase)

ELECTRICAL SUPPLY2828282828s.1616161616fl.Ø (mm)PIPE SIZE

22.022.022.022.022.0(kg)REFRIGERANT CHARGE

5050505050(m)MAX. HEIGHTDIFFERENCE

300300300300300(m)MAX. PIPE LENGTH**18401840184018401840Height840840840840840Depth19901990199019901990Width(mm)DIMENSIONS455455455455455(kg)WEIGHT6261616060dB(A)NOISE*

2400024000240002400024000(m³/h)AIRFLOW81.575.067.063.056.0(kW)HEATING CAPACITY73.067.463.056.050.0(kW)COOLING CAPACITY

PUHY-P650YGM-A

PUHY-P600YGM-A

PUHY-P550YGM-A

PUHY-P500YGM-A

PUHY-P450YGM-AMODEL REFERENCE

BIG Y OUTDOOR UNITS

City Multi Y-Series: PUHY-P400YGM-A

1-22 / 20-250Connectable indoor units (Number/Type)22.6(A)RUNNING CURRENT

8(A)STARTING CURRENT12.43(Heating)13.42(Cooling)(kW)MAX. INPUT POWER

380-415V, 50Hz, 3(V, Freq.,Phase)

ELECTRICAL SUPPLY28s.12fl.Ø (mm)PIPE SIZE

13.0(kg)REFRIGERANT CHARGE

50(m)MAX. HEIGHTDIFFERENCE

300(m)MAX. PIPE LENGTH**1840Height840Depth1290Width(mm)DIMENSIONS275(kg)WEIGHT61dB(A)NOISE*

14400(m³/h)AIRFLOW50.0(kW)HEATING CAPACITY45.0(kW)COOLING CAPACITY

PUHY-P400YGM-AMODEL REFERENCEBIG Y OUTDOOR UNITS

Outdoor units - Technical dataCity Multi Y-Series and Big Y

City Multi Y-Series: PUHY-P200-350YGM-A

1-20 / 20-2501-19 / 20-2501-16 / 20-2501-13 / 20-250Connectable indoor units (Number/Type)19.216.113.010.3(A)RUNNING CURRENT

88810(A)STARTING CURRENT11.029.107.625.98(Heating)11.399.577.726.14(Cooling)(kW)MAX. INPUT POWER

380-415V, 50Hz,3

380-415V, 50Hz,3

380-415V, 50Hz,3

380-415V, 50Hz,3

(V, Freq.,Phase)

ELECTRICAL SUPPLY28222218s.12101010fl.Ø (mm)PIPE SIZE9.59.59.57.0(kg)REFRIGERANT CHARGE

50505050(m)MAX. HEIGHTDIFFERENCE

300300300300(m)MAX. PIPE LENGTH**1840184018401840Height840840840840Depth990990990990Width(mm)DIMENSIONS233233233218(kg)WEIGHT60595756dB(A)NOISE*

12000120001200012000(m³/h)AIRFLOW45.037.531.525.0(kW)HEATING CAPACITY40.033.528.022.4(kW)COOLING CAPACITY

PUHY-P350YGM-A

PUHY-P300YGM-A

PUHY-P250YGM-A

PUHY-P200YGM-AMODEL REFERENCE

STANDARD Y OUTDOOR UNITS, COOLING OR HEATING

* The noise levels are measured at a position 1 m in front of and 1 m above the unit in anechoic chamber.** one-way

Page 12: Katalog City Multi

12

Outdoor units - Technical dataCity Multi WY-Series

* The noise levels are measured at a position 1 m in front of and 1 m above the unit in anechoic chamber.** one-way*** water temperature 10°C-45°C

1-16/20-2501-13/20-250Connectable indoor units (Number/Type)

15°C-27°C (DB)15°C-27°C (DB)(Heatingindoor)

15°C-24°C (WB)15°C-24°C (WB)(Coolingindoor)

OPERATING TEMP.RANGE***

14.411.5(A)RUNNING CURRENT1212(A)STARTING CURRENT

9.237.24(Heating)9.027.22(Cooling)(kW)MAX. INPUT POWER

380-415V, 50Hz,3380-415V, 50Hz,3(V,Freq.,Phase)

ELECTRICAL SUPPLY2822s.1212fl.(mm)PIPE SIZE8.07.0(kg)REFRIGERANT CHARGE

5050(m)MAX. HEIGHTDIFFERENCE

220220(m)MAX. PIPE LENGTH**16701670Height500500Depth11501150Width(mm)DIMENSIONS280270(kg)WEIGHT5251db(A)NOISE*108(k Pa)PRESSURE DROP

5,794,27(m³/h)COOLING WATER FLOW RATE31.525.0(kW)HEATING CAPACITY28.022.4(kW)COOLING CAPACITY

PQHY-P250 YEM-APQHY-P200 YEM-AMODEL REFERENCEWY-SERIES (WATER COOLED) WITH R407C

PQHY-P200/250-YEM-A with R407C. Important:The unit must be placed indoor.

Page 13: Katalog City Multi

13

PUHN-P01 YGM-A Heat Exchanger Unit* The noise levels are measured at a position 1 m in front of and 1 m above the unit in anechoic chamber.** one-way

0.7(Heating)0.7(Cooling)(kW)MAX. INPUT POWER

380-415V, 50Hz, 3(V, Freq.,Phase)

ELECTRICAL SUPPLY28s.12fl.Ø (mm)PIPE SIZE

1840Height840Depth990Width(mm)DIMENSIONS155(kg)WEIGHT

14400(m³/h)AIRFLOWPUHN-P01YGM-AMODEL REFERENCE

PUHN UNITS

Outdoor units - Technical dataCity Multi Super Y-Series

City Multi Super Y series PUHY-P700-800YGM-A can only operate with PUHN-P01!

* The noise levels are measured at a position 1 m in front of and 1 m above the unit in anechoic chamber.** one-way*** Look at outdoor unit combination

1-34 / 20-2501-34 / 20-2501-34 / 20-250Connectable indoor units (Number/Type)42.939.934.8(A)RUNNING CURRENT151515(A)STARTING CURRENT

26.9025.3721.83(Heating)26.7524.9021.70(Cooling)(kW)MAX. INPUT POWER

380-415V, 50Hz, 3380-415V, 50Hz, 3380-415V, 50Hz, 3(V, Freq.,Phase)

ELECTRICAL SUPPLY353535s.181818fl.Ø (mm)PIPE SIZE

27.027.027.0(kg)REFRIGERANT CHARGE

505050(m)MAX. HEIGHTDIFFERENCE

300300300(m)MAX. PIPE LENGTH**184018401840Height840840840Depth169016901690Width(mm)DIMENSIONS430430430(kg)WEIGHT646362dB(A)NOISE*

144001440014400(m³/h)AIRFLOW100.094.588.0(kW)HEATING CAPACITY90.084.078.4(kW)COOLING CAPACITY

PUHY-P800YGM-APUHY-P750YGM-APUHY-P700YGM-AMODEL REFERENCESUPER Y OUTDOOR UNITS***

The outdoor unit of theSuper Y series is a combi-nation of PUHY-YGM-A and

PUHN-P01.SUPER Y UNIT COMBINATIONModel Reference Necessary combination Dimension Cooling Heating max.

capacity capacity connectableindoor units /types

PUHY-P700YSGM-A PUHY-P700YGM-A + PUHN-P01YGM-A width 2680 mm 78,4 kW 88,0 kW 1-34 / 20-250(compressor unit) (heat exchanger unit) depth 840 mm

hight 1840 mm

PUHY-P750YSGM-A PUHY-P750YGM-A + PUHN-P01YGM-A width 2680 mm 84,0 kW 94,5 kW 1-34 / 20-250(compressor unit) (heat exchanger unit) depth 840 mm

hight 1840 mm

PUHY-P800YSGM-A PUHY-P800YGM-A + PUHN-P01YGM-A width 2680 mm 90,0 kW 100,0 kW 1-34 / 20-250(compressor unit) (heat exchanger unit) depth 840 mm

hight 1840 mm

Page 14: Katalog City Multi

14

* The noise levels are measured at a position 1 m in front of and 1 m above the unit in anechoic chamber.** one-way*** Look at outdoor unit combination

1-42 / 20-2501-42 / 20-2501-42 / 20-2501-42 / 20-250Connectable indoor units (Number/Type)76.271.264.058.3(A)RUNNING CURRENT42.6339.7338.4636.93(Heating)47.5644.4039.9636.39(Cooling)(kW)MAX. INPUT POWER

380-415V, 50Hz, 3380-415V, 50Hz, 3380-415V, 50Hz, 3380-415V, 50Hz, 3(V, Freq.,Phase)

ELECTRICAL SUPPLY28282828s.16161616fl.Ø (mm)PIPE SIZE

44.044.044.044.0(kg)REFRIGERANT CHARGE

50505050(m)MAX. HEIGHTDIFFERENCE

300300300300(m)MAX. PIPE LENGTH**1840184018401840Height840840840840Depth3980398039803980Width(mm)DIMENSIONS918918918918(kg)WEIGHT65646464dB(A)NOISE*

48000480004800048000(m²/h)AIRFLOW156.5150.0145.0140.0(kW)HEATING CAPACITY140.0136.0130.0124.0(kW)COOLING CAPACITY

PUHY-P1250YSGM-APUHY-P1200YSGM-APUHY-P1150YSGM-APUHY-P1100YSGM-AMODEL REFERENCESUPER Y OUTDOOR UNITS***

Outdoor units - Technical dataCity Multi Super Y-Series

1-42 / 20-2501-42 / 20-2501-42 / 20-2501-42 / 20-2501-42 / 20-250Connectable indoor units (Number/Type)53.649.846.842.840.5(A)RUNNING CURRENT34.2432.6830.4229.1027.47(Heating)33.4831.1129.2326.7125.28(Cooling)(kW)MAX. INPUT POWER

380-415V, 50Hz, 3380-415V, 50Hz, 3380-415V, 50Hz, 3380-415V, 50Hz, 3380-415V, 50Hz, 3(V, Freq.,Phase)

ELECTRICAL SUPPLY2828282828s.1616161616fl.Ø (mm)PIPE SIZE

44.044.044.044.044.0(kg)REFRIGERANT CHARGE

5050505050(m)MAX. HEIGHTDIFFERENCE

300300300300300(m)MAX. PIPE LENGTH**18401840184018401840Height840840840840840Depth39803980398039803980Width(mm)DIMENSIONS918918918918918(kg)WEIGHT63,563636363dB(A)NOISE*

4800048000480004800048000(m²/h)AIRFLOW132.0127.0119.5113.0108.0(kW)HEATING CAPACITY118.0113.0108.0101.096.0(kW)COOLING CAPACITY

PUHY-P1050YSGM-APUHY-P1000YSGM-APUHY-P950YSGM-APUHY-P900YSGM-APUHY-P850YSGM-AMODEL REFERENCESUPER Y OUTDOOR UNITS***

SUPER Y UNIT COMBINATIONModel Reference Necassary Combination Dimension Cooling Heating max.

(Main unit + Sub unit) depth 840 mm capacity capacity connectablehight 1840 mm indoor units / types

PUHY-P850YSGM-A PUHY-P450YMM-A + PUHY-P400YSM-A width 3980 mm 96,0 kW 108,0 kW 1-42 / 20-250

PUHY-P900YSGM-A PUHY-P500YMM-A + PUHY-P400YSM-A width 3980 mm 101,0 kW 113,0 kW 1-42 / 20-250

PUHY-P950YSGM-A PUHY-P550YMM-A + PUHY-P400YSM-A width 3980 mm 108,0 kW 119,5 kW 1-42 / 20-250

PUHY-P1000YSGM-A PUHY-P600YMM-A + PUHY-P400YSM-A width 3980 mm 113,0 kW 127,0 kW 1-42 / 20-250

PUHY-P1050YSGM-A PUHY-P650YMM-A + PUHY-P400YSM-A width 3980 mm 118,0 kW 132,0 kW 1-42 / 20-250

PUHY-P1100YSGM-A PUHY-P450YMM-A + PUHY-P650YSM-A width 3980 mm 124,0 kW 140,0 kW 1-42 / 20-250

PUHY-P1150YSGM-A PUHY-P500YMM-A + PUHY-P650YSM-A width 3980 mm 130,0 kW 145,0 kW 1-42 / 20-250

PUHY-P1200YSGM-A PUHY-P550YMM-A + PUHY-P650YSM-A width 3980 mm 136,0 kW 150,0 kW 1-42 / 20-250

PUHY-P1250YSGM-A PUHY-P600YMM-A + PUHY-P650YSM-A width 3980 mm 140,0 kW 156,5 kW 1-42 / 20-250

The outdoor unit of theSuper Y series is a combi-nation of PUHY-PYMM-A

and PUHY-PYSM-A.

Page 15: Katalog City Multi

15

City Multi R2-Series: PURY-P450-650YGM-A

1-32 / 20-2501-32 / 20-2501-24 / 20-2501-24 / 20-2501-24 / 20-250Connectable indoor units (Number/Type)31.528.227.325.021.8(A)RUNNING CURRENT19.8217.7316.3715.8913.86(Heating)19.6517.5917.0815.5913.61(Cooling)(kW)MAX. INPUT POWER

380-415V,50Hz, 3

380-415V,50Hz, 3

380-415V,50Hz, 3

380-415V,50Hz, 3

380-415V,50Hz, 3

(V, Freq.,Phase)

ELECTRICAL SUPPLY2828282828s.2828282222fl.Ø (mm)PIPE SIZE

16.516.516.516.516.5(kg)REFRIGERANT CHARGE

5050505050(m)MAX. HEIGHTDIFFERENCE

400400400400400(m)MAX. PIPE LENGTH**18401840184018401840Height840840840840840Depth19901990199019901990Width(mm)DIMENSIONS481481481481481(kg)WEIGHT6261616060dB(A)NOISE*

2400024000240002400024000(m³/h)AIRFLOW81.575.067.063.056.0(kW)HEATING CAPACITY73.067.463.056.050.0(kW)COOLING CAPACITY

PURY-P650YGM-A

PURY-P600YGM-A

PURY-P550YGM-A

PURY-P500YGM-A

PURY-P450YGM-AMODEL REFERENCE

BIG R2 OUTDOOR UNITS

City Multi R2-Series: PURY-P400YGM-A

1-24 / 20-250Connectable indoor units (Number/Type)21.5(A)RUNNING CURRENT

8(A)STARTING CURRENT12.43(Heating)13.42(Cooling)(kW)MAX. INPUT POWER

380-415V, 50Hz, 3(V, Freq.,Phase)

ELECTRICAL SUPPLY28s.22fl.Ø (mm)PIPE SIZE

13.0(kg)REFRIGERANT CHARGE

50(m)MAX. HEIGHTDIFFERENCE

400(m)MAX. PIPE LENGTH**1840Height840Depth1290Width(mm)DIMENSIONS291(kg)WEIGHT61dB(A)NOISE*

14400(m³/h)AIRFLOW50.0(kW)HEATING CAPACITY45.0(kW)COOLING CAPACITY

PURY-P400YGM-AMODEL REFERENCEBIG R2 OUTDOOR UNITS

Outdoor units - Technical dataCity Multi R2-Series and Big R2

City Multi R2-Series: PURY-P200-350YGM-A

1-20 / 20-2501-16 / 20-2501-16 / 20-2501-15 / 20-250Connectable indoor units (Number/Type)18.215.312.39.8(A)RUNNING CURRENT

88810(A)STARTING CURRENT11.029.107.625.98(Heating)11.399.577.726.14(Cooling)(kW)MAX. INPUT POWER

380-415V, 50Hz,3

380-415V, 50Hz,3

380-415V, 50Hz,3

380-415V, 50Hz,3

(V, Freq.,Phase)

ELECTRICAL SUPPLY28222218s.18181816fl.Ø (mm)PIPE SIZE

13.013.013.010.5(kg)REFRIGERANT CHARGE

50505050(m)MAX. HEIGHTDIFFERENCE

400400400400max. (m)MAX. PIPE LENGTH**1840184018401840Height840840840840Depth990990990990Width(mm)DIMENSIONS251251251236(kg)WEIGHT60595756dB(A)NOISE*

12000120001200012000(m³/h)AIRFLOW45.037.531.525.0(kW)HEATING CAPACITY40.033.528.022.4(kW)COOLING CAPACITY

PURY-P350YGM-A

PURY-P300YGM-A

PURY-P250YGM-A

PURY-P200YGM-AMODEL REFERENCE

R2 OUTDOOR UNITS

* Noise level measuredat a position in 1m in front of the unit** one way

Page 16: Katalog City Multi

16

* The Slave BC-Controller can only use in combination with the Master Controller** for max. 3 indoor units with a capacity up to 140 will be needed only one branch

max. 8/20-250**max. 4/20-250**Connectable indoor units (Number/Type)0.590.3(A)RUNNING CURRENT

220-240V, 50Hz, 1220-240V, 50Hz, 1(V, Freq.,Phase)

ELECTRICAL SUPPLY284284Height432432Depth648648Width(mm)DIMENSIONS3222(kg)WEIGHT

(Indoor unit at Slave-Controller)

1616s.Ø (mm)EXT.1010fl.PIPE SIZE

2222s.(Master-Controller atSlave-Controller)

1818s.Ø (mm)EXT.1010fl.PIPE SIZE

CMB-P108V-GBCMB-P104V-GBMODEL REFERENCEBIG R2 SLAVE-CONTROLLER*

Slave-Controller for Big R2

* Only for R410A** for max. 3 indoor units with a capacity up to 140 will be needed only one branch

max. 16/20-250**max. 13/20-250**max. 10/20-250**max. 8/20-250**Connectable indoor units (Number/Type)1.221.000.770.63(A)RUNNING CURRENT0.2790.2280.1770.144(kW)MAX. INPUT POWER

220-240V, 50Hz,1

220-240V, 50Hz,1

220-240V, 50Hz,1

220-240V, 50Hz,1

(V, Freq.,Phase)

ELECTRICAL SUPPLY289289289289Height520520520520Depth1110111011101110Width(mm)DIMENSIONS64574944(kg)WEIGHT

18181818s.(Master-Controller atSlave-Controller)

16161616s.Ø (mm)EXT.10101010fl.PIPE SIZE

(BC-Controller atoutdoor unit)

28282828s.Ø (mm)EXT.22222222fl.PIPE SIZE

CMB-P1016V-GA

CMB-P1013V-GA

CMB-P1010V-GA

CMB-P108V-GAMODEL REFERENCE

BIG R2 MASTER-CONTROLLER*

Master-Controller for Big R2

Outdoor units - Technical dataBC-Controller

* Only for R410A Systems** for max. 3 indoor units with a capacity up to 140 will be needed only one branch

max.16/20-250**

max.13/20-250**

max.10/20-250**

max.8/20-250**

max.6/20-250**

max.5/20-250**

max.4/20-250**

Connectable indoor units (Number/Type)1.221.000.770.630.480.410.34(A)RUNNING CURRENT0.2790.2280.1770.1440.1100.0930.076(kW)MAX. INPUT POWER

220-240V,

50Hz, 1

220-240V,

50Hz, 1

220-240V,

50Hz, 1

220-240V,

50Hz, 1

220-240V,

50Hz, 1

220-240V,

50Hz, 1

220-240V,

50Hz, 1

(V, Freq.,Phase)

ELECTRICAL SUPPLY284284284284284284284Height432432432432432432432Depth10981098648648648648648Width(mm)DIMENSIONS54473934292724(kg)WEIGHT

(BC-Controller atoutdoor unit)

22222222222222s.Ø (mm)EXT.18181818181818fl.PIPE SIZE

CMB-P1016V-G

CMB-P1013V-G

CMB-P1010V-G

CMB-P108V-G

CMB-P106V-G

CMB-P105V-G

CMB-P104V-G

MODEL REFERENCE

R2 BC-CONTROLLER*

BC-Controller:Required for R2 System

Page 17: Katalog City Multi

17

* Only for 407C units** for max. 3 indoor units with a capacity up to 80 will be needed only one

max. 16/20-250max. 13/20-250max. 10/20-250max. 8/20-250max. 6/20-250max. 5/20-250max. 4/20-250Connectable indoor units (Number/Type)1.080.890.690.560.430.360.30(A)RUNNING CURRENT0.250.200.160.130.090.080.07(kW)MAX. INPUT POWER

220-240V, 50Hz,1

220-240V, 50Hz,1

220-240V, 50Hz,1

220-240V, 50Hz,1

220-240V, 50Hz,1

220-240V, 50Hz,1

220-240V, 50Hz,1

(V, Freq.,Phase)

ELECTRICAL SUPPLY284284284284284284284Height432432432432432432432Depth10981098648648648648648Width(mm)DIMENSIONS54473934292724(kg)WEIGHT

(BC-Controller atoutdoor unit)

28282828282828s.Ø (mm)EXT.18181818181818fl.PIPE SIZE

CMB-P1016V-FCMB-P1013V-FCMB-P1010V-FCMB-P108V-FCMB-P106V-FCMB-P105V-FCMB-P104V-FMODEL REFERENCEWR2 R407C BC-CONTROLLER*

BC-Controller:required for R2 Systems

Outdoor units - Technical dataCity Multi WR2-Series

WR2-Serie (water cooled): PQRY-P200/250YEM-A with R407C. Important:

The unit must be placed indoor.

* Noise level measuredat a position in 1m in front of the unit** one way

1-16 / 20-2501-15 / 20-250Connectable indoor units (Number/Type)15.512.1(A)RUNNING CURRENT12.012.0(A)STARTING CURRENT9.237.24(Heating)9.027.22(Cooling)(kW)MAX. INPUT POWER

380-415V, 50Hz, 3380-415V, 50Hz, 3(V, Freq.,Phase)

ELECTRICAL SUPPLY2828s.1818fl.Ø (mm)PIPE SIZE8.57.5(kg)REFRIGERANT CHARGE

5050(m)MAX. HEIGHTDIFFERENCE

220220(m)MAX. PIPE LENGTH**16701670Height500500Depth11501150Width(mm)DIMENSIONS280270(kg)WEIGHT5251dB(A)NOISE*108(k Pa)PRESSURE DROP

5,794,27(m³/h)COOLING WATER FLOW RATE31.525.0(kW)HEATING CAPACITY28.022.4(kW)COOLING CAPACITY

PQRY-P250YEM-APQRY-P200YEM-AMODEL REFERENCEWR2-SERIES (WATER COOLED) WITH R407C

Page 18: Katalog City Multi

18

All City Multi indoor units are compatible to Y-Series,R2- and WR2-Series.

* L-model: low stat. pressure, H-model: high stat. pressure

Indoor units- Overview

Capacity Capacity code

Cooling capacity (kW)

Type Heating capacity (kW)

P 20

2.2

2.5

P 25

2.8

3.2

P 32

3.6

4.0

P 40

4.5

5.0

P 50

5.6

6.3

P 63

7.1

8.0

P 71

8.0

9.0

P 80

9.0

10.0

P 100

11.2

12.5

P 125

14.0

16.0

P 140

16.0

18.0

P 200

22.4

25.0

P 250

28.0

31.5

Ceiling CassetteType(1-way airflow)

PMFY-VBM-E

Ceiling Cassette Type(2-way airflow)

PLFY-VLMD-E

Ceiling Cassette Type(4-way airflow)

PLFY-VCM-E

Ceiling Cassette Type(4-way airflow)

PLFY-VAM-E

Ceiling Concealed(horizontal airflow)

PEFY-VML-E/VMH-E

Ceiling Concealed(variable airflow)

PEFY-VMM-E

Ceiling SuspendedType

PCFY-VGM-E

Wall Mounted Type

PKFY-VAM-E

Wall Mounted Type

PKFY-VGM-E

Floor StandingExposed Type

PFFY-VLEM-E

● ● ● ●

● ● ● ● ● ● ● ● ●

● ● ● ●

● ● ● ● ● ● ●

● ● ● ● ● ● ● ● ● ● ● ● ●

● ● ● ● ● ● ● ● ● ●

● ● ● ●

● ●

● ● ●

● ● ● ● ● ●

● ● ● ● ● ●

L-model H-model

Floor StandingConcealed Type

PFFY-VLRM-E

Ceiling Concealed for 100% fresh air

PEFY-VMH-E-F● ●

Page 19: Katalog City Multi

19

Compact size for smooth installation andmaintenanceUnit body size has been standardised for all models (H = 230 mm, W = 812 mm, D = 395 mm).

Body weight is also only 14 kg for the main unit and3 kg for the panel, making this unit one of the lightestin the industry.

Quiet operationNewly developed airflow control system reduces noiselevel to only 27 dB(A) at the smallest unit.

Drain water lift-up mechanismThe drain pan can be positioned anywhere up to600 mm from the ceiling´s surface.

Fresh air intakeThe construction allows an intake of fresh air, twobranch connections are prepared.

Indoor units - Technical data1-Way In-Ceiling Cassettes

* The values given in the table reflect the measured noise level at a position 1.5 m below the unit in anechoic chamber** Needed installation hight, in brackets: Visible grille hight

0.260.210.210.20(A)RUNNING CURRENT0.0540.0440.0440.042(kW)MAX. INPUT POWER

220-240V, 50Hz, 1220-240V, 50Hz, 1220-240V, 50Hz, 1220-240V, 50Hz, 1(V, Freq.,Phase)

ELECTRICAL SUPPLY12121212s.6666fl.Ø (mm)PIPE SIZE

395 (470)395 (470)395 (470)395 (470)Depth(GRILLE)812 (1000)812 (1000)812 (1000)812 (1000)Width(mm)DIMENSIONS

14 (17)14 (17)14 (17)14 (17)(kg)WEIGHT INCL. GRILLELow/High

33/3932/3732/3727/35dB(A)NOISE*642558558522High582516516480Middle 2522480480432Middle 1462438438390Low(m³/h)AIRFLOW5.04.03.22.5(kW)HEATING CAPACITY4.53.62.82.2(kW)COOLING CAPACITY

PMP-40BMPMP-40BMPMP-40BMPMP-40BMGRILLEPMFY-P40VBM-EPMFY-P32VBM-EPMFY-P25VBM-EPMFY-P20VBM-EMODEL REFERENCE

PMFY 1-WAY IN-CEILING CASSETTES

230 (30)230 (30)230 (30)230 (30)Height**

Page 20: Katalog City Multi

20

Compact dimensionsOptimised low installation height of only 335 mm (VLMD)for easy installation in small ceilings

Drain lift up mechanismAll units are serial equipped with drain lift up mechanism for600 mm lifting height

Lighter unit - easy installationThe light weight of only 23 kg (PLFY-P50 VLMD-E) simplifiesthe installation extremly

Coanda-Effect - draft-free air-flowThe draft-free air-flow is adjustable by two air outlets

Quiet operationOptimised air-outlet-flow allows low noise pressure level ofonly 27 dB(A) (PLFY-P20 - 32 VLMD-E)

Fresh air intakeThe construction of the 2-way Cassette allows an intake offresh air, one branch connection is prepared. (Optional partsrequired)

Indoor units - Technical data2-Way In-Ceiling Cassettes

* The values given in the table reflect the measured noise level at a position 1.5 m below the unit in anechoic chamber** Needed installation hight, in brackets: Visible grille height

1.350.880.740.510.430.420.370.370.37(A)RUNNING CURRENT0.2800.1860.1560.1050.0860.0850.0750.0750.075(kW)MAX. INPUT POWER

220-240V,50Hz, 1

220-240V,50Hz, 1

220-240V,50Hz, 1

220-240V,50Hz, 1

220-240V,50Hz, 1

220-240V,50Hz, 1

220-240V,50Hz, 1

220-240V,50Hz, 1

220-240V,50Hz, 1

(V, Freq.,Phase)

ELECTRICAL SUPPLY161616161212121212s.1010101066666fl.Ø (mm)PIPE SIZE

1708 (2010)1446 (1750)1446 (1750)946 (1250)946 (1250)776 (1080)776 (1080)776 (1080)776 (1080)Width(mm)DIMENSIONS56 (69)47 (59,5)44 (56,5)28 (35,5)27 (34,5)24 (30,5)24 (30,5)23 (29,5)23 (29,5)(kg)WEIGHT INCL. GRILLE

Low/High40/4636/4233/3932/3931/3729/3627/3327/3327/33dB(A)NOISE*198015001320930750630570570570High1800--------Middle 2162012601110780660510480480480Middle 114401050930600540420390390390Low(m³/h)AIRFLOW16.012.510.08.06.35.04.03.22.5(kW)HEATING CAPACITY14.011.29.07.15.64.53.62.82.2(kW)COOLING CAPACITY

CMP-125VLW-B

CMP-100VLW-B

CMP-100VLW-B

CMP-63VLW-B

CMP-63VLW-B

CMP-40VLW-B

CMP-40VLW-B

CMP-40VLW-B

CMP-40VLW-B

GRILLE

PLFY-P125VLMD-E

PLFY-P100VLMD-E

PLFY-P80VLMD-E

PLFY-P63VLMD-E

PLFY-P50VLMD-E

PLFY-P40VLMD-E

PLFY-P32VLMD-E

PLFY-P25VLMD-E

PLFY-P20VLMD-E

MODEL REFERENCEPLFY 2-WAY IN-CEILING CASSETTES

606 (710)634 (710)634 (710)634 (710)634 (710)634 (710)634 (710)634 (710)634 (710)Depth(GRILLE)335 (20)335 (20)335 (20)335 (20)335 (20)335 (20)335 (20)335 (20)335 (20)Height**

Page 21: Katalog City Multi

21

Euro-RasterCompact dimensions (650x650 mm Euro-raster) allowseasy installation in raster-ceilings

Minimised installation heightOptimised low installation height of only 235 mm foreasy installation in small ceiling

Lighter unit - easy installationState-of-the-art materials allows lighter weights as of15,5 - 17 kg and simplified installation

4 servo-motors for 4 air-outletsEach air-outlet-flow is individual controlled by servo-motors. A 4-way-cassette can easily modified to a 3-wayor 2-way cassette.

Serial equipped with fresh-air intakeThe construction of the Euro-raster 4-way-cassetteallows an intake of fresh air, one branch connection isprepared.

Drain Pump for 500 mm hight difference

Indoor units - Technical data2-by-2 In-Ceiling Cassettes standar-dised Euro-spacing

* The values given in the table for the noise level reflect the measurde at a position 1.5m below the unit in anechoic chamber** Needed installation hight, in brackets: Visible grille hight

0.280.280.230.23(A)RUNNING CURRENT0.060.060.050.05(Heating)0.060.060.050.05(Cooling)(kW)MAX. INPUT POWER

220-240, 50Hz, 1220-240, 50Hz, 1220-240, 50Hz, 1220-240, 50Hz, 1(V, Freq.,Phase)

ELECTRICAL SUPPLY12121212s.6666fl.Ø (mm)PIPE SIZE

570 (650)570 (650)570 (650)570 (650)Width(mm)DIMENSIONS17 (20)17 (20)15,5 (18,5)15,5 (18,5)(kg)WEIGHT INCL. GRILLE

Low/High30/3929/3829/3728/35dB(A)NOISE*660660600600High600600540540Middle540540480480Low(m³/h)AIRFLOW5.04.03.22.5(kW)HEATING CAPACITY4.53.62.82.2(kW)COOLING CAPACITY

SLP-2AASLP-2AASLP-2AASLP-2AAGRILLEPLFY-P40VCM-EPLFY-P32VCM-EPLFY-P25VCM-EPLFY-P20VCM-EMODEL REFERENCE

PLFY 2-BY-2 IN-CEILING CASSETTES STANDARDISED EURO-SPACING

570 (650)570 (650)570 (650)570 (650)Depth(GRILLE)235 (20)235 (20)235 (20)235 (20)Height**

Page 22: Katalog City Multi

22

Compact dimensionsOptimised low installation height and lighter weight for easy installation insmall ceilings.

Drain lift up mechanismAll units are serial equipped with drain lift up mechanism for 850 mm liftingheight.

Extreme quiet operationOptimised air-outlet-flow by inverter controlled turbo-fan with large diame-ter allows low noise pressure level of only 27 dB(A)(PLFY-P32 - P50VAM-E).

Draft-free air-flowUp and down mechanism of the air-outlets provides fresh and natural airdrafts.

Flexible air flow rate4 speed microprocessor controlled fan mode provides many airflow varia-tions. Adjustable air flow rate by dip switch on controller board for differentceiling heights.The construction of the 4-way Cassette allows an intake offresh air, a branch connection is prepared.

Indoor units - Technical data4-Way In-Ceiling Cassettes

840 (950)840 (950)840 (950)840 (950)840 (950)840 (950)840 (950)Width(mm)DIMENSIONS32 (37)32 (37)24 (29)24 (29)22 (27)22 (27)22 (27)(kg)WEIGHT INCL. GRILLE

Low/High35/4333/4130/3728/3327/3227/3227/31dB(A)NOISE*1740162013201080960960840High162015001200960840840780Middle 2144013201080900780780720Middle 112601140960840720720660Low(m³/h)AIRFLOW16.012.510.08.06.35.04.0(kW)HEATING CAPACITY14.011.29.07.15.64.53.6(kW)COOLING CAPACITY

PLP-6AAPLP-6AAPLP-6AAPLP-6AAPLP-6AAPLP-6AAPLP-6AAGRILLE

PLFY-P125VAM-E

PLFY-P100VAM-E

PLFY-P80VAM-E

PLFY-P63VAM-E

PLFY-P50VAM-E

PLFY-P40VAM-E

PLFY-P32VAM-E

MODEL REFERENCEPLFY 4-WAY IN-CEILING CASSETTES

840 (950)840 (950)840 (950)840 (950)840 (950)840 (950)840 (950)Depth(GRILLE)298 (30)298 (30)258 (30)258 (30)258 (30)258 (30)258 (30)Height**

* The values given in the table reflect the measured noise level at a position 1.5 m below the unit in anechoic chamber** Needed installation height, in brackets: Visible grille height

1.641.430.860.780.680.680.59(A)RUNNING CURRENT0.340.300.180.160.140.140.12(kW)MAX. INPUT POWER

220-240V, 50Hz,1

220-240V, 50Hz,1

220-240V, 50Hz,1

220-240V, 50Hz,1

220-240V, 50Hz,1

220-240V, 50Hz,1

220-240V, 50Hz,1

(V, Freq.,Phase)

ELECTRICAL SUPPLY16161616121212s.10101010666fl.Ø (mm)PIPE SIZE

Page 23: Katalog City Multi

23

PKFY-P20/25 VAM-E

Compact dimensionsWall mounted units are the ideal conception for lessinstallation scope. Small outline dimensions of 295 mmand only 8,5 kg weight (Type VAM-E) provides easyinstallation above windows or doors.

Quiet operationOptimised 4 speed fan allows low noise air-outlet-flowpressure

Shapely designThe pleasing design makes it easy to blend in rooms oroffices. An integrated fin closes the air outlet if thesystem is switched off.

Easy to install - Easy to maintainEasy electrical connection after installation because offront cover installation box and reachable srews fromfront side. Very flexible installation. All piping is con-nectable from right, left, bottom or back cover of theunit.

Indoor units - Technical dataWall Mounted Systems

* The values given in the table reflect the measured noise level at a position 1 m in front of and 1 m below the unit in anechoic chamber

0.320.320.320.200.20(A)RUNNING CURRENT0.070.070.070.040.04(kW)MAX. INPUT POWER

220-240V, 50Hz, 1220-240V, 50Hz, 1220-240V, 50Hz, 1220-240V, 50Hz, 1220-240V, 50Hz, 1(V, Freq.,Phase)

ELECTRICAL SUPPLY1212121212s.66666fl.Ø (mm)PIPE SIZE

340340340295295Height235235235158158Depth990990990815815Width(mm)DIMENSIONS1616168,58,5(kg)WEIGHT

Low/High34/4333/4133/4132/3632/36dB(A)NOISE*720690690354354High660630630336336Middle 2600570570312312Middle 1540480480294294Low(m³/h)AIRFLOW6.35.04.03.22.5(kW)HEATING CAPACITY5.64.53.62.82.2(kW)COOLING CAPACITY

PKFY-P50VGM-EPKFY-P40VGM-EPKFY-P32VGM-EPKFY-P25VAM-EPKFY-P20VAM-EMODEL REFERENCEPKFY WALL MOUNTED SYSTEMS

Page 24: Katalog City Multi

24

Extremly quiet - highest convenienceOptimised air-outlet-flow and high quality materials provides lownoise pressure level of only 29 dB(A) (PCFY-P40VGM-E)

Optimised air outlet pressure for variable ceilingheightsAll units are serial equipped with 4 speed microprocessor controlledfan mode to provide many airflow variations. Adjustable air flow rateby dip switch on controller board for different ceiling heights(max 3,5 m).

Optional drain pumpThe drain pump (optional part) can be connected from the left orthe right

Easy to installEdgewise mounting provides easy and quick installation.Sidecovers can be removed.

Up and down moving fin for optimised air outlet flowUp and down mechanism of the air-outlet fin provides fresh andnatural air drafts. An integrated fin closes the air outlet if the systemis switched off.

Pleasing and slimThe pleasing and slim ceiling conceiled units make it easy to blend inrooms or offices.

Indoor units - Technical dataFloor or Ceiling MountedSystems

* The values given in the table reflect the measured noise level at a position 1 m in front of and 1 m below the unit in anechoic chamber

1.100.730.600.46(A)RUNNING CURRENT0.240.160.130.10(kW)MAX. INPUT POWER

220-240V, 50Hz, 1220-240V, 50Hz, 1220-240V, 50Hz, 1220-240V, 50Hz, 1(V, Freq.,Phase)

ELECTRICAL SUPPLY16161612s.1010106fl.Ø (mm)PIPE SIZE270270210210Height680680680680Depth1620131013101000Width(mm)DIMENSIONS43373427(kg)WEIGHT

Low/High37/4436/4332/3929/38dB(A)NOISE*210015001080720High19201380960660Middle 216801200840600Middle 115601080720480Low(m³/h)AIRFLOW16.012.58.05.0(kW)HEATING CAPACITY14.011.27.14.5(kW)COOLING CAPACITY

PCFY-P125VGM-EPCFY-P100VGM-EPCFY-P63VGM-EPCFY-P40VGM-EMODEL REFERENCEPCFY FLOOR OR CEILING MOUNTED SYSTEMS

Page 25: Katalog City Multi

25

Compact dimensions, optimised roomutilisationThe approved technology of the (conceiled type) floorstanding type is easy to integrate (depth only 220 mm)in offices and rooms and its architecture

Humidification modeTo keep humidity constant it is possible to switch ondehumidification mode for fresh air.

Indoor units - Technical dataFloor Standing Units(Concealed type)

* The values given in the table reflect the measured noise level at a position 1 m in front of and 1 m above the unit in anechoic chamber

0.460.400.320.290.190.19(A)RUNNING CURRENT0.100.0850.0650.060.040.04(kW)MAX. INPUT POWER

220-240V, 50Hz, 1220-240V, 50Hz, 1220-240V, 50Hz, 1220-240V, 50Hz, 1220-240V, 50Hz, 1220-240V, 50Hz, 1(V, Freq.,Phase)

ELECTRICAL SUPPLY161212121212s.1066666fl.Ø (mm)PIPE SIZE639639639639639639Height220220220220220220Depth1246124610061006886886Width(mm)DIMENSIONS2725212018,518,5(kg)WEIGHT

Low/High40/4638/4338/4335/4034/4034/40dB(A)NOISE*

Low/High720 / 930720 / 840540 / 660420 / 540330 / 390330 / 390(m³/h)AIRFLOW

8.06.35.04.03.22.5(kW)HEATING CAPACITY7.15.64.53.62.82.2(kW)COOLING CAPACITY

PFFY-P63VLRM-EPFFY-P50VLRM-EPFFY-P40VLRM-EPFFY-P32VLRM-EPFFY-P25VLRM-EPFFY-P20VLRM-EMODEL REFERENCEPFFY FLOOR STANDING UNITS (CONCEALED TYPE)

Page 26: Katalog City Multi

26

Compact dimensions, optimised roomutilisationThe approved technology of the (cabinet type) floorstanding type is easy to integrate (depth only 220 mm)in offices and rooms and its architecture.

Humidification modeTo keep humidity constant it is possible to switch ondehumidification mode for fresh air.

Control systemRemote controllers can be integrated with the casing ofthe floor standing units. Wall mounted installation forremote controllers is not necessary.

Serial equipped fresh air intakeThe construction allows an intake of fresh air, a branchconnection is prepared, serial equipped air filter can beused.

Indoor units - Technical dataFloor Standing Units(Cabinet type)

* The values given in the table reflect the measured noise level at a position 1 m in front of and 1 m above the unit in anechoic chamber

0.460.400.320.290.190.19(A)RUNNING CURRENT0.100.0850.0650.060.040.04(kW)MAX. INPUT POWER

220-240V, 50Hz, 1220-240V, 50Hz, 1220-240V, 50Hz, 1220-240V, 50Hz, 1220-240V, 50Hz, 1220-240V, 50Hz, 1(V, Freq.,Phase)

ELECTRICAL SUPPLY161212121212s.1066666fl.Ø (mm)PIPE SIZE630630630630630630Height220220220220220220Depth141014101170117010501050Width(mm)DIMENSIONS323026252323(kg)WEIGHT

Low/High40/4638/4338/4335/4034/4034/40dB(A)NOISE*

Low/High720 / 930720 / 840540 / 660420 / 540330 / 390330 / 390(m³/h)AIRFLOW

8.06.35.04.03.22.5(kW)HEATING CAPACITY7.15.64.53.62.82.2(kW)COOLING CAPACITY

PFFY-P63VLEM-EPFFY-P50VLEM-EPFFY-P40VLEM-EPFFY-P32VLEM-EPFFY-P25VLEM-EPFFY-P20VLEM-EMODEL REFERENCEPFFY FLOOR STANDING UNITS (CABINET TYPE)

Page 27: Katalog City Multi

27

Top flexibility13 types with 2,2 kW up to 28,0 kW for flexibleapplication.

Compact dimensions - only 225 mm casingheight (Type PEFY-PVML-A)Low casing height of only 225 mm (PEFY-VML) for easyinstallation in low air ducts.

Maximum high static pressure up to 260 PaPEFY-VMH with high static pressure (50 - 260 Pa) areoptimised for long distance air ducts.

Extremely quietlow noise level of PEFY-VML only 25 dB(A)

Easy maintenanceeasy maintenance by the use of service port

Filter as Standard for all PEFY-P VML-E

Indoor units - Technical dataCeiling Concealed Ducted Units

* The values given in the table for the noise level reflect the measurde at a position 1.5m below the unit in anechoic chamber** static pressure depends of the power supply

1.201.120.880.880.320.240.24(A)RUNNING CURRENT0.260.240.190.190.070.050.05(kW)MAX. INPUT POWER

220-240V, 50Hz,1

220-240V, 50Hz,1

220-240V, 50Hz,1

220-240V, 50Hz,1

220-240V, 50Hz,1

220-240V, 50Hz,1

220-240V, 50Hz,1

(V, Freq.,Phase)

ELECTRICAL SUPPLY16161212121212s.101066666fl.Ø (mm)PIPE SIZE380380380380225225225Height900900900900550550550Depth1000750750750720720720Width(mm)DIMENSIONS50454544181818(kg)WEIGHT

Low/High32/3932/3827/3427/3425/4025/3625/36dB(A)NOISE*

50/100/150/20050/100/150/20050/100/150/20050/100/150/200555(Pa)EXT. STATIC

PRESSURE**

13201140840840570474474High348348348Middle

930810600600288288288Low(m³/h)AIRFLOW9.08.06.35.04.03.22.5(kW)HEATING CAPACITY8.07.15.64.53.62.82.2(kW)COOLING CAPACITY

PEFY-P71VMH-E

PEFY-P63VMH-E

PEFY-P50VMH-E

PEFY-P40VMH-E

PEFY-P32VML-E

PEFY-P25VML-E

PEFY-P20VML-E

MODEL REFERENCEPEFY CEILING CONCEALED DUCTED UNITS (REAR OR BOTTOM SUCTION FOR VML-E UNITS)

Page 28: Katalog City Multi

28

Top flexibility13 types with 2,2 kW up to 28,0 kW for flexibleapplication

Maximum high static pressure up to 260 PaPEFY-VMH with high static pressure (50 - 260 Pa) areoptimised for long distance air ducts.

Easy maintenanceeasy maintenance by the use of service port

Indoor units - Technical dataCeiling Concealed Ducted Units

* The values given in the table reflect the measured noise level at a position 1.5 m below the unit in anechoic chamber** static pressure depends of the power supply

2.001.622.352.342.341.47(A)RUNNING CURRENT1.230.990.480.480.480.32(kW)MAX. INPUT POWER

380-415V, 50Hz, 3380-415V, 50Hz, 3220-240V, 50Hz, 1220-240V, 50Hz, 1220-240V, 50Hz, 1220-240V, 50Hz, 1(V, Freq.,Phase)

ELECTRICAL SUPPLY221816181616s.101010101010fl.Ø (mm)PIPE SIZE470470380380380380Height11201120900900900900Depth125012501200120012001000Width(mm)DIMENSIONS10010070707050(kg)WEIGHT

Low/High524534/4234/4234/4235/41dB(A)NOISE*

110/130/220/260110/130/220/26050/100/150/20050/100/150/20050/100/150/20050/100/150/200(Pa)EXT. STATIC

PRESSURE**

Low/High432034801680 / 24001590 / 22801590 / 22801080 / 1500(m³/h)AIRFLOW31.525.018.016.012.510.0(kW)HEATING CAPACITY28.022.416.014.011.29.0(kW)COOLING CAPACITY

PEFY-P250VMH-EPEFY-P200VMH-EPEFY-P140VMH-EPEFY-P125VMH-EPEFY-P100VMH-EPEFY-P80VMH-EMODEL REFERENCEPEFY CEILING CONCEALED DUCTED UNITS (REAR SUCTION)

Page 29: Katalog City Multi

29

Optimised flexibility by variable air intakeVariable air intake flow from bottom or backside provi-des optimised installation solutions

Compact dimensions - only 295 - 325 mmcasing heightLow casing height for easy installation in low air ductswith high quality ventilation requirements

Extreme quiet operation and high staticpressureOptimised air-outlet-flow allows low noise pressure levelof only 33 dB(A) (type-P20 - P25) with high static pres-sure up to 130 Pa.

Filter as Standard

Indoor units - Technical dataCeiling Concealed Ducted Units

* The values given in the table reflect the measured noise level at a position 1.5 m below the unit in anechoic chamber** static pressure depends of the power supply

1.951.901.341.151.151.070.980.920.810.730.73(A)RUNNING CURRENT0.420.400.290.250.250.220.200.190.170.150.15(kW)MAX. INPUT POWER

220-240V,50Hz, 1

220-240V,50Hz, 1

220-240V,50Hz, 1

220-240V,50Hz, 1

220-240V,50Hz, 1

220-240V,50Hz, 1

220-240V,50Hz, 1

220-240V,50Hz, 1

220-240V,50Hz, 1

220-240V,50Hz, 1

220-240V,50Hz, 1

(V, Freq.,Phase)

ELECTRICAL SUPPLY1616161616161212121212s.10101010101066666fl.Ø (mm)PIPE SIZE325325325295295295295295295295295Height740740740700700700700700700700700Depth171514151415117511751175935935815815815Width(mm)DIMENSIONS7065624242423333272727(kg)WEIGHT

Low/High42/4542/4540/4432/3932/3931/3831/3831/3728/3527/3227/32dB(A)NOISE*

50/13050/13050/13030/50/10030/50/10030/50/10030/50/10030/50/10030/50/10030/50/10030/50/100(Pa)EXT. STATIC

PRESSURE**

2520240019801260126011401020840630510510High---10801080972870720540432432Middle

177016801380870870810720600450360360Low(m³/h)AIRFLOW18.016.012.510.09.08.06.35.04.03.22.5(kW)HEATING CAPACITY16.014.011.29.08.07.15.64.53.62.82.2(kW)COOLING CAPACITY

PEFY-P140VMM-E

PEFY-P125VMM-E

PEFY-P100VMM-E

PEFY-P80VMM-E

PEFY-P71VMM-E

PEFY-P63VMM-E

PEFY-P50VMM-E

PEFY-P40VMM-E

PEFY-P32VMM-E

PEFY-P25VMM-E

PEFY-P20VMM-E

MODEL REFERENCEPEFY CEILING CONCEALED DUCTED UNITS (REAR OR BOTTOM SUCTION)

Page 30: Katalog City Multi

30

Highest comfort with 100% fresh airThese ducted type are designed for 100% fresh air intake.Additional air handling units are not needed

Maximum high static pressure up to 220 PaPEFY-VMH-E-F with high static pressure from 50 up to220 Pa (at 230V) are optimised for long distance airducts.

Easy maintenanceEasy maintenance by the use of service port

Quiet operation with high static pressureOptimised air-outlet-flow allows low noise pressure levelof only 33 dB(A) (type P80) with high static pressure upto 220 Pa.

Indoor units - Technical data100% Fresh Air Intake

* The values given in the table for the noise reflect the levels measured at a position 1.5m below the unit in anechoic chamber by 50/220Pa** the static pressure depends of the power supply

1.240.67(A)RUNNING CURRENT0.290.16(kW)MAX. INPUT POWER

220-240V, 50Hz, 1220-240V, 50Hz, 1(V, Freq.,Phase)

ELECTRICAL SUPPLY1616s.1010fl.Ø (mm)PIPE SIZE380380Height900900Depth12001000Width(mm)DIMENSIONS7050(kg)WEIGHT

Low/High34/4533/45dB(A)NOISE*

50/130/220/24050/130/170/220(Pa)EXT. STATIC

PRESSURE**

1080540AIRFLOW15.18.5(kW)HEATING CAPACITY16.09.0(kW)COOLING CAPACITY

PEFY-P140VMH-E-FPEFY-P80VMH-E-FMODEL REFERENCE

Page 31: Katalog City Multi

31

The Perfect Combination Air Conditioning and Ventilation

The powerful City Multi air-conditioning systems canbe combined with the MITSUBISHI ELECTRIC Loss-nay LGH series. No additional adapters are needed forconnection to the data bus.

Maximum heat recovery and 100% fresh air

The advanced Lossnay range of ventilation units ex-tract stale air and replace it with fresh air, saving ener-gy in the process with their very effective heat energyrecovery system. This system utilises almost all theavailable cooling and heating energy, cutting powerconsumption by between 40% and 70%. This is madepossible by the special plate-fin paper diaphragm heatexchanger, which enables maximum recovery of thelatent heat in the exhausted air.

Low installation costs and simple maintenance

● The superbly efficient heat recovery system enablesyou to minimise the power consumption of your airconditioning equipment, thus significantly reducingoverall installation costs.

● In addition to this the system also humidifies or dehu-midifies the fresh air fed into the room, as required

● Lossnay systems can be installed in all modern build-ings, creating an ideally healthy living and workingenvironment.

● The ceiling suspended series includes 9 models withairflows from 150 – 2,000 m3/h. For further detailsplease see the main catalogue or contact MitsubishiElectric or your dealer.

The Lossnay-principle

LossnayLGH-seriesceiling suspendedunits

Stale internalair recovery

Renewedinternal air

outside air isdrawn in

Stale air expelled outside

Page 32: Katalog City Multi

32

Close Control Air Conditioning PFD Series

PFD Close Controll - Air Conditioning UnitThis unit is designed for computer- and technical equipmentrooms with high sensible heat load. The direction from the air-flow is from the top of the unit to the ground. 100% redundancein case of emergency (standard for PFD-P500VM-A).

High SHF Factorthe big heat exchanger of the PFD unit makes it possible toreach an SHF factor from 0,93. The result is a very high effi-ciency close control unit.

Close Control +-1K

Small installation place

Full inverter controlled outdoor unitThe PUD outdoor unit for the close control unit PFD-P VM-Ahas one full inverter compressor. Advantages are very low star-ting current (8A), long piping length between indoor- and out-door unit and the max. hight difference from max. 50 m.

9.05.3(A)RUNNING CURRENT5.02.5(kW)MAX. INPUT POWER

380-415V, 50Hz, 3380-415V, 50Hz, 3(V, Freq.,Phase)

ELECTRICAL SUPPLY2822s.1212fl.Ø (mm)PIPE SIZE

18951895Height800800Depth18001200Width(mm)DIMENSIONS480350(kg)WEIGHT6459dB(A)NOISE

196009600(m²/h)AIRFLOW5628.0(kW)COOLING CAPACITY

PFD-P500VM-APFD-P250VM-AMODEL REFERENCEPFD INDOOR UNIT

* 2X Outdoor units PUD-P250YMF-C are necessary for PFD-Gerät P500VM-A** Noise level measured at a position of 1m in front of the unit*** one way

13.3(A)RUNNING CURRENT8(A)STARTING CURRENT

(Heating)7.5(Cooling)(kW)MAX. INPUT POWER

380-415V, 50Hz, 3(V, Freq.,Phase)

ELECTRICAL SUPPLY28s.12fl.Ø (mm)PIPE SIZE7(kg)REFRIGERANT CHARGE

50(m)MAX. HEIGHTDIFFERENCE

300(m)MAX. PIPE LENGTH***1715Height840Depth990Width(mm)DIMENSIONS231(kg)WEIGHT56dB(A)NOISE**

11100m³/hAIRFLOW28.0(kW)COOLING CAPACITY

PUD-P250 YMF-CMODEL REFERENCEPUD OUTDOOR UNIT WITH R407C*

Page 33: Katalog City Multi

33

Replace Multi SeriesTo change an old VRF system which is operating with therefrigerant R22 makes is nessecary to change also the refri-gerant pipes because this pipes are contaminated withmineral oil.

The City Multi Outdoor Units PUHY-P200/250 YREM-Acan re-use this old pipes. A special Oil Trap Kit which isdeveloped for re-using old refrigerant pipes, clean thepipes and seperate the mineral oil from the system in anoil accumulator which is placed inside of the Oil Trap Kit.After this procedure - new indoor- and outdoor units canwork without any problems.

The Replace Multi units have all advantages of our suc-cessful City Multi Systems.

Replace Multi = High and fast Clima Comfort

The cleaning of the pipe system without our Oil Trap Kitis is not possible.

In case you need more information please contact us.

Outdoor Unit- Technical DatasReplace Multi Series R407C

1-16 / 20-2501-13 / 20-250Connectable indoor units (Number/Type)14.310.9(A)RUNNING CURRENT

88(A)STARTING CURRENT8.956.80(Heating)8.546.32(Cooling)(kW)MAX. INPUT POWER

380-415V, 50Hz, 3380-415V, 50Hz, 3(V, Freq.,Phase)

ELECTRICAL SUPPLY2822s.1212fl.Ø (mm)PIPE SIZE

13.013.0(kg)REFRIGERANT CHARGE

5050(m)MAX. HEIGHTDIFFERENCE

220220(m)MAX. PIPE LENGTH**17551755Height840840Depth990990Width(mm)DIMENSIONS239239(kg)WEIGHT5756dB(A)NOISE*

1200012000(m³/h)AIRFLOW31.525.0(kW)HEATING CAPACITY28.022.4(kW)COOLING CAPACITY

PUHY-P250 YRME-APUHY-P200 YREM-AMODEL REFERENCEREPLACE MULTI OUTDOOR UNIT, COOLING OR HEATING WITH R407C

* Noise level measured at a position of 1m in front of the unit** one way

Page 34: Katalog City Multi

34

● PAR-20 MAA to connect at the indoor unit, building of groups of seperate Databus System possible

● 1 Indoor unit individual, 1 Group with 16 indoor units possible by two-wire signal lines

● Easy to read, easy to operate display● On/Off Timer● Temperature selection in 1°C units● Auto-diagnosis display

A microcomputer constantly monitors operation to keep the units running smoothly. Should problems occure, the temperature setting display changes to an auto-diagnosis display that shows the inspection mode and the unit address alternately.

● Room thermometer is built into the remote controller. Switching possible to indoor unit room thermometer.

● PAR-F27 MEA to connect at the City Multi Databus System, easy to form groups

● 1 Indoor unit individual / 1 Group with16 indoor units● Easy to read, easy to operate display● Extensive time function● Temperature selection in 1°C units● Auto-diagnosis display

A microcomputer constantly monitors operation to keep the units running smoothly. Should problems occure, the temperature setting display changes to an auto-diagnosis display that shows the inspection mode and the unit address alternately.

● Room thermometer is built into the remote controller. Switching possible to indoor unit room thermometer.

● Limit temperature setting

● To simplify operation of the system, the range of controls has been limited to START/STOP, room temperature and fan speed

● The only wiring required is cross-over wiring based on two-wire signal lines

● Room temperature sensors are built-in The indoor unit can be replaced with body thermostats

● Easy-to-read, easy-to-operate icon display● Temperature selection● Can operate all types of indoor units● Standardized remote controllers for all indoor units● 1 indoor unit individual/1 group with 16 indoor units● PAC-SE51 CRA – Grouping addressing by data bus● PAC-YT51 CRA – Main grouping by two-wire signal lines

*Since this system has no operation mode switching, test operation, self-diagnosis or linked setting functions, it should always be used in conjunction with the PAR-F27MEA or other centralized controller.

PAR-20MAA

PAC-YT51CRAPAC-SE51CRA

PAR-F27 MEA

City MultiSystem Control – Standard Remote Control

Page 35: Katalog City Multi

35

City Multi Control Accessories – Infrared- On/Off- and Group Remote Control– Timer

Infrared-Remote Control PAR-FL31 MA and PAR-FA31 MA (Signal receiver)

● It can operate in a group system without requiring address settings

● When operating, it displays LED lamps. When errors occure,the error can be shown by the LED flash count

● 1 Indoor unit individual/1 group with 16 indoor units by two-wire signal lines

On/Off Remote Controller PAC-YT40 ANRA

● Up to 50 groups● Price competitive solution,

up to 50 indoor units

Group Remote Control PAC-SC30 GRA

● Easy to read, easy to operate display● Temperature selection in 1°C units● Auto-diagnosis-display

A microcomputer constantly monitors operation to keep the units running smoothly. Should problems occure, the temperature setting display changes to an auto-diagnos is display that shows the inspection mode and the unit address alternately.

● 8 Indoor units individual / Max. 16 Indoor units in 8 groups

Programme Timer PAC-YT32 PTA

● One-week scheduling by remote controller● Set-back function● Control for PAR-F27 MEA

(1 Indoor unit individual / 1 group with 16 indoor units)

PAC-SC30 GRA

PAC-YT40 ANRA

PAR-FL31MA

PAR-FA31MA

PAC-YT32 PTA

Page 36: Katalog City Multi

36

City Multi Control Accessories – System Remote Control– SystemTimer

System Remote Controller PAC-SF44 SRA

● Control range as Standard Controller (Air Outlet Angle/Air Filter)● Limited room air temperature selection● Auto diagnosis system● 50 indoor units individual/max. 50 indoor units with 50 groups● Lock-out function for PAR-F27 MEA● External Input/Output

System Timer PAC-YT34 STA

● Directly connected to the M-Net databus● 50 groups/max. 50 indoor units● Timer-controlled mode● Timer-controlled temperature● 9 Timer functions● Lock-off selection (On/Off/Mode/Temperatue)

PAC-SF44SRA

PAC-YT34STA

Page 37: Katalog City Multi

37

City Multi Control Accessories – Central Remote Control with WEB-Function

● Simple and flexibleThe central controller G-50 A is equally suitable for small and large systems.

● Web browserUse a standard web browser on your PC, e.g. Microsoft Internet ExplorerTM, to operate and monitor the air-conditioning unit, which is connected to your local Intranet, in comfort.

● Integrated software The easy to understand operating software is already integrated in the G-50 A. This represents Mitsubishi Electric’s own innovation and is not Windows-based. It is therefore impossible for hackers to spy in your system data.

● Three password levels You can safeguard against unauthorised access to the air-conditioning system on three operating levels which are individually protected by passwords of your choice. – Access to an air-conditioning unit (or group) e.g. for each office/floor but

without the possibility to change the system settings – Access to group and maintenance functions, e.g. for in-house technicians– Access to the entire system, e.g. for the system administrator

● Remote accessYou can also operate your air-conditioning system with your PC by remote con-trol via your local intranet or phone connection. The access is protected by a password of your choice.

● Automatic alarm If an error occurs, the G-50 A sends a message with the most important information to a mobile phone (SMS) or an email to an address of your choice.

● Always up-to-date Upgrades with continuously updated special functions are available for the G-50 A.Examples: – Energy consumption data for individual cost statements

– Special economy programmes– Annual schedules

The new Remote Controller G-50A + G-50M –the next Controller Generation

G-50A

HARDWARE FOR G-50A Type Description G-50A Standard Standard central controller for 50 air conditionersG-50A Pro As above G-50 incl. Web function & annual schedule,

programmed for clients demandPAC-SC50KUA Power supply unit for G-50BTX-1000 Router according to ME specification & installation is required

depending to clients demandsPC* with software TG 2000 PC according Me specification & installation with OS,

Internet Explorer and software TG 2000Watt Hour Meter Amount of WHM is depend of the project

SOFTWARE FOR G-50Web Function Set free Homepage

Personal Web RC Remote Controlvia PC

Power consumption Ratio Calculate individual cost***

Demand Control I Limit tempera-ture range, optimize indoor-outdoor unit**

Demand Control II Peak Cut*** only connection with PLC + PLCSoftware

Annual Schedule Weekly and Yearly Timer**

Data Export Trend Graph***

Error scanning function MonitoringError History

Auto Alarming Auto Alarm function– Error Code mailing

Service Maintenance Tool function

BACnet BACnet Connection

PLC PLC connection direct with G-50 via RJ45

TG 2000 Installation TG 2000 software according customer requirement

* Computer periphery like Monitor, Keyboard, Mouse, Printer from client** Operation with G-50 or Pos. 5*** Additional pos. 5 nessassary, for Power consumption ration additional Pos. 6 nessassary

NEW: G-50M (without display, no powersupply needed)

Page 38: Katalog City Multi

38

City Multi Control Accessories– LonWorks®-Interface– Maintenance Tool

Lon Works® -Interface● Easy connection of City Multi Systems through LMAP02-E, the Lon

Works®-M-Net protocol converter, the total system requirements of engineers and end-users can be met more effectively and simply.

● 1 Lon Works®-Interface manages 50 indoor units.L-MAP02-E

Maintenance Tool - CMS-MNF-B● Using Maintenance Tool is the easiest way for

controlling, servicing and operating the City Multisystem. All system information will be displayed onpersonal computer* screen based on Windows Software and settings can be changed.

● In addition, error code numbers are output onto thedisplay.

● Easy maintenance is assured through the trouble history printer output and call functions. Besides ths connection with modem and data transfer ispossible. CMS-MNF-B consists of converter boxand software, RS-232 cable (cross) is needed.

* Windows 3.1 or Windows 95, Pentium 75 MHz or more,16 MB RAM, free space 10 MB on HDD.

Page 39: Katalog City Multi

39

CONTROLSMODEL REFERENCE DESCRIPTIONPAC-SE40TS-E Temperature sensorPAC-725AD Remote indicator (pack of 10)PAC-SA88HA-E Remote indicator (pack of 1)PAC-SE55RA-E Remote indicator ON/OFFPAC-SF46EPA Transmission booster

INDOOR/OUTDOOR UNITSMODEL REFERENCE DESCRIPTIONPLFY-P-VAM-EPAC-SG06SP-E Air outlet shutter platePAC-SG01KF-E High efficiency filter for PAC SG03TM-E PAC-SG03TM-E Multifunction casement

PLFY-P-VLMD-EPAC-KH110F Fresh air access

PCFY-P-VGM-EPAC-SE80KF-E High efficiency filter for PCFY-P40 VGM-EPAC-SE81KF-E High efficiency filter for PCFY-P63/100 VGM-EPAC-SE82KF-E High efficiency filter for PCFY-P125 VGM-EPAC-SE84DMA-E Drain pump for PCFY-P40 VGM-E PAC-SE85DMA-E Drain pump for PCFY-P63 VGM-E PAC-SH17DM-E Drain pump for PCFY-P100/125 VGM-E

PEFY-P-VML/VMH/VMH-E-FPAC-KE04DM-F Drain pump for PEFY-P-VMH-EPAC-KE32LAF-F Replacement filter for PEFY-P20/25/32 VML-EPAC-KE86LAF Optional filter for PEFY-P40/50/63 VMH-EPAC-KE88LAF Optional filter for PEFY-P71/80 VMH-EPAC-KE89LAF Optional filter for PEFY-P100/125/140 VMH-EPAC-KE85LAF Optional filter for PEFY-P200/250 VMH-EPAC-KE63TB-F Filter box for PEFY-P40/50/63 VMH-EPAC-KE80TB-F Filter box for PEFY-P71/80 VMH-EPAC-KE140TB-F Filter box for PEFY-P100/125/140 VMH-EPAC-KE250TB-F Filter box for PEFY-P200/250 VMH-E

PEFY-P-VMM-EPAC-KE03DM-F Drain pump for PEFY-P-VMM-EPAC-KE32EDF-F Round duct flange for PEFY-P20/25/32 VMM-EPAC-KE50EDF-F Round duct flange for PEFY-P40/50 VMM-EPAC-KE80EDF-F Round duct flange for PEFY-P63/71/80 VMM-EPAC-KE125EDF-F Round duct flange for PEFY-P100/125 VMM-EPAC-KE140EDF-F Round duct flange for PEFY-P140 VMM-E

PU(H)Y-P/PURY-P-YGM-EPAC-KBU04MT-F High static pressure motor 30/60 Pa

REFRIGERANT PIPESMODEL REFERENCE DESCRIPTIONCMY-R160-J Junction pipe kit for BC-ControllerCMY-Y102S-G* T-Branch 18/10**CMY-Y102L-G* T-Branch 22/12**CMY-Y202-G* T-Branch 22/16**CMY-Y302-G* T-Branch 35/18**CMY-Y104-G* Header (4 branch)CMY-Y108-G* Header (8 branch)CMY-Y1010-G* Header (10 branch)

City Multi Accessories

* Standard T-Branch can be used** Various restricted fittings included

Page 40: Katalog City Multi

Mitsubishi and Mitsubishi Electric are trademarks of Mitsubishi Electric Europe B. V.The Company reserves the right to make any variation in specification to the equipment described or to withdraw orreplace products without prior notification or public announcement. Mitsubishi Electric is constantly developing andimproving its products. All descriptions, illustrations, drawings and specifications in this publication present only generalparticulars and shall not form part of any contract. All goods are supplied subject to the Companyís General Conditionsof Sale, a copy of which is available on request.