    IRA A. FULTON SCHOOL OF ENGINEERING

    George G. Karady, Saurabh Saksena, Baozhuang Shi

    Effects of Voltage Sags on

    Household Loads

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    2/69

    2

    IntroductionIntroduction Voltage sags is an important part of the

    power quality problem Significant amount of research concentrated

    on power quality issues

    Detailed literature review was performed tostudy the effect of sags on power systemoperation, induction motors, synchronous

    machines, and adjustable speed drives(ASDs)

    The literature survey incorporated around 40

    IEEE and other technical journal papers

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    3/69

    3

    MotivationMotivation No significant and authentic data is available

    to study the effect of sags on household loads Very few journal papers are published on the

    effect of sags on residential loads, specially

    on sensitive equipment The sensitivity of household equipment is

    increasing because of increasing use of

    electronics Due to the fast changing technology, the test

    results performed few years ago have become

    obsolete

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    4/69

    4

    ObjectivesObjectives To present an experimental study of the effect of

    voltage sags on household loads such as airconditioners, lighting loads, DVD players, televisions

    and other sensitive equipment

    To design Computer Business EquipmentManufacturers Association (CBEMA) curves for loads

    that stalled/ switched off due to sags, and comparewith the standard CBEMA curves

    To create a prediction table for the effect of sags on a

    single apartment unit To discuss financial implications of sags on

    customers and utilities

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    5/69

    5

    Experiments on HouseholdExperiments on Household

    LoadsLoads

    Contactors and Circuit Breakers Motor loads eg. Air conditioners Lighting loads eg. Fluorescent and Helium

    Lamps Sensitive equipment9 Computers9 Microwave Ovens9 Televisions9 DVD and VCR players, digital radio clocks

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    6/69

    6

    What are voltage sags???What are voltage sags???A sag or dip, as defined by IEEE Standard1159, IEEE Recommended Practice forMonitoring Electric Power Quality, is

    a decrease in root mean square (rms) voltageat the power frequency for durations from 0.5cycles to 1 minute, reported as the remaining

    voltage

    Typical values of sags are between 0.1 pu and

    0.9 pu.

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    7/69

    7

    Terminology usedTerminology used

    The terminology used to describevoltage sag is confusing

    Sag of 20% means a voltage drop, V

    of 20% from its initial voltage level

    20% sag depth represents that the

    remaining voltage is 20% of theoriginal line voltage

    Terminology used

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    8/69

    8

    Voltage Sag: A Pictorial ViewVoltage Sag: A Pictorial View

    -200

    -150

    -100

    -50

    0

    50

    100

    150

    200

    0 500 1000 1500 2000 2500

    voltage

    cycles

    Voltage sag showing 50% sag depth, 20 cycle duration

    Sag depth of 50% which

    depicts the remaining

    voltage in%

    Sag period of 20 cycles

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    9/69

    9

    Experimental ConfigurationExperimental Configuration

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    10/69

    10

    Experimental ConfigurationExperimental Configuration The sags are created using the EPRI Process

    RideThrough Evaluation System (PRTES) which isa portable voltage sag generator with built in dataacquisition system

    Salt River Project (SRP) lent the voltage saggenerator

    The sag generator supplied directly the test object.

    The current of the test object and the voltageacross the terminals was measured and recorded

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    11/69

    11

    Data acquisition system

    Voltage sag generator Laptop interface

    Contactor under test

    Experimental ConfigurationExperimental Configuration

    EPRI PRTES system portable sag generator and built-in data

    acquisition system

    Tap setting for

    Changing sag depths

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    12/69

    12

    Test ProcedureTest Procedure The sag depths are varied in steps of 10%

    starting from 90% and going to 50% usingthe tap setting

    At each sag depth the sag duration was

    varied from 5, 10, 20 60 cycles. (10 Cyclesteps)

    The voltage and current wave shapes weremeasured and recorded in an excel file

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    13/69

    13

    Experiments on AirExperiments on Air--

    Conditioner CompressorsConditioner Compressors

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    14/69

    14

    Experiments on AirExperiments on Air--ConditionerConditionerCompressorsCompressors

    Three window unit air conditioners were

    tested:

    Air conditioner A, 2kW, 9A full load Air conditioner B, 1kW, 7.4A full load

    Air conditioner C, 670W, 6.1 A full load

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    15/69

    15

    Experiments on AirExperiments on Air--ConditionerConditionerCompressorsCompressorsSpecifications of air conditioner compressor A

    120 V ac single phase thermally protected

    Full load amperes: 7.4 A

    Locked rotor amperes: 35.7 A

    Measured operating current: 6.7 A

    Peak value of starting current of thecompressor before subjected to sags: 48 A

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    16/69

    16

    -2 0 0

    -1 5 0

    -1 0 0

    -5 0

    0

    5 0

    10 0

    15 0

    20 0

    0 500 1000 1500 2000 2500

    voltage

    cycles

    Voltage sag (60% depth, 20 cycles)

    -4 0

    -3 0

    -2 0

    -1 0

    0

    1 0

    2 0

    3 0

    0 500 1000 1500 2000 2500

    Current

    Responding motor current

    cycles

    Non stalling condition for compressor A

    Experiments on air-conditioner

    compressors

    IEEE PES Meeting, San Francisco, Jun 12- Jun 17, 2005

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    17/69

    17

    Experiments on air-conditionercompressors

    -200

    -150

    -100

    -5 0

    0

    5 0

    10 0

    15 0

    20 0

    0 500 1000 1500 2000 2500

    volta

    ge

    Voltage sag (50% depth, 20 cycles)

    cycles

    Stalling condition for compressor A

    - 5 0

    - 4 0

    - 3 0

    - 2 0

    - 1 0

    0

    1 0

    2 0

    3 0

    4 0

    5 0

    0 500 1000 1500 2000 2500

    curre

    nt

    cycles

    Responding motor current

    IEEE PES Meeting, San Francisco, Jun 12- Jun 17, 2005

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    18/69

    18

    Experiments on Air-Conditioners

    - 5 0

    - 4 0

    - 3 0

    - 2 0

    - 1 0

    0

    1 0

    2 0

    3 0

    4 0

    5 0

    0 5 0 0 1 00 0 1 5 0 0 2 0 00 2 5 0 0

    cur

    rent

    cycles

    Responding motor current for stalling condition for

    compressor A

    Momentary

    transient

    period

    Point of sag initiation

    1.5 times normal current

    after transient period

    Gradual increase in

    current

    Sag period

    Post sag period

    High current

    greater than

    locked rotor

    current signifyingstalling condition

    (A)

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    19/69

    19

    Experiments on air-conditioner

    compressors

    N: Non- stalling condition Y: Stalling condition

    Results of stalling conditions for

    different sag depths and durations for compressor A

    For a sag of50% depth

    and

    duration 60

    cycles,

    compressor

    A stalls

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    20/69

    20

    Experiments on AirExperiments on Air--ConditionersConditionersThree window unit air conditioners were tested

    Results of stalling conditions for air-conditioners

    N no effect on speed of compressor

    SR speed reduction due to sag

    S air-conditioner stalls

    Sag Depth (%)

    5 10 20 30 40 60

    90 N N N N N N

    80 SR SR SR SR SR SR

    70 SR SR SR SR SR SR

    60 SR SR SR SR S S

    50 SR SR S S S S

    Sag Duration (cycles)

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    21/69

    21

    Conclusions

    Air conditioners stall for sags of 60% depthand 40 - cycle and 60 - cycle duration, andsags of 50% depth and duration greater than

    10 cycles; thermal protection causes thecompressor to stall

    The motor current can rise to as high as 4.7

    pu during sag

    Initiation phase of the sag has no obviouseffect on the performance of the motor

    Experiments on Air-Conditioners

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    22/69

    22

    Experiments on AirExperiments on Air--ConditionerConditioner

    CompressorsCompressorsImpact of sag initiation phase on motor recovery current

    0

    1

    2

    3

    4

    5

    6

    0 90 180 270 360

    Phase (Degree)

    Motorrecoverycurr

    ent(p.u.)

    50%10Cycle

    50%20Cycle

    40%10Cycle

    40%45Cycle

    Motor recovery

    current in per unit

    Sags represent voltage

    drop in this case

    Stalling cases; no effectof sag initiation phase

    on recovery current

    Non-stalling cases;

    recovery current forsags initiated at 0

    and 180 deg. Is

    greater than that for

    90 and 270 deg.

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    23/69

    23

    Experiments on Air-

    Conditioner Compressors

    Conclusions

    Compressor A stalls for sags of depths60% and more and duration greater than

    40 cycles

    Compressor B stalls for sags of depths60% and more and duration greater than20 cycles

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    24/69

    24

    Experiments on Air-

    Conditioner CompressorsConclusions (Generalized)

    Test results of 2 motors show that motor stallsfor sags deeper than 60% and longer than 20cycles

    The motor current can rise to as high as 4.7 puduring sag

    Initiation phase of the sag has no obviouseffect on the performance of the motor.

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    25/69

    25

    Experiments on AirExperiments on Air--

    Conditioner CompressorsConditioner Compressors

    The gradual increase of sag and sagduration leads to the stalling of the motor

    The motor stops and current increases to

    the starting current

    The large current activates the thermal

    protection in the winding

    The motor is re-started manually

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    26/69

    26

    Experiments on LightingLoads

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    27/69

    27

    Experiments on Lighting Loads Experiments were conducted on

    fluorescent lamps and

    helium lamps

    Lamps were subjected to sags ofdifferent depths, durations and

    initiation phases

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    28/69

    28

    Experiments on Lighting LoadsFluorescent lamps

    Specifications of Fluorescent Lamp Tested

    GE/Philips SP35 32W Canada

    110VAC/32Watt Regular size (4 feet) fluorescent lamp

    120V, RMS value of operation current is 0.33 A.

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    29/69

    29

    Experiments on Lighting Loads The sag produces a sudden reduction of light

    intensity

    The current becomes zero at the beginning ofsag for two cycles

    Subsequently, current increases to a value,which is proportional to the sag voltage

    When sag ends, a current spike occurs and

    then current returns to its normal

    During the current spike the light intensityincreases sharply

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    30/69

    30

    Experiments on Lighting Loads

    - 4

    - 3 . 5

    - 3

    - 2 . 5

    - 2

    - 1 . 5

    - 1

    - 0 . 5

    0

    0 . 5

    1

    1 . 5

    0 5 0 0 1 0 0 0 1 5 0 0 2 0 0 0 2 5 0 0

    c

    u

    rr

    e

    cycles

    Typical responding current signal for florescent lamp (40% depth, 10 cycles)

    Point of sag initiation

    Zero current indicating

    beginning of sag

    Sag period where current

    becomes proportional to applied voltage

    Current spike indicating

    end of sag

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    31/69

    31

    Experiments on Lighting LoadsHelium Lamps

    Specifications of Helium Lamp Tested

    GE Helium Lamp 120V AC/ 750 Watts

    Measured operating current: 6.19 A

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    32/69

    32

    Experiments on Lighting Loads

    Conclusions Light dims during sags in helium lamps

    Lamp current is proportional to sag depth

    Dimness of light is dependent on sag depth and isindependent of sag duration

    At the end of the sag, a current surge occursresulting in a sharp increase in the intensity of light.

    This may reduce the life of the lamps

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    33/69

    33

    Experiments on Computers

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    34/69

    34

    Experiments on ComputersSpecifications of the tested computers

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    35/69

    35

    Experiments on Computers

    -20

    -15

    -10

    -5

    0

    5

    10

    15

    20

    0 500 1000 1500 2000 2500 3000 3500 4000

    Cur

    rent(A)

    IEEE PES Meeting, San Francisco, Jun 12- Jun 17, 2005

    -25

    -20

    -15

    -10

    -5

    0

    5

    10

    15

    20

    25

    0 500 1000 1500 2000 2500 3000 3500

    Cur

    rent(A)

    Current for 60%/ 20 ~ No loading/ Restart Current for 50%/ 30 ~ loading/ Restart

    Loading refers to the case when the hard disk is loading data

    High current surges of the order of 7-10 times the normal current

    indicating end of sag

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    36/69

    36

    Experiments on ComputersEffect of voltage sag on computer As restarting and data loading

    Experiments were conducted considering two cases: when the hard disk is loading

    data and one when it is functioning normally without loading data

    For a sag of depth 40%,

    duration of 15 cycles or

    less and when hard disk is

    not loading data, there is

    no effect on computer A

    For a sag of depth 50%,

    duration of 8 cycles or

    more and when hard disk

    is loading data, computerA restarts

    C

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    37/69

    37

    Experiments on Computers

    If the sag duration is shorter than 7 cycles,sags do not cause the restart of a computer

    and the loss of data

    If the depth of voltage sag is larger than 30%

    and duration is longer than 8 cycles, voltagesag may cause a computer to start

    Voltage sags have more severe effect on

    computers restarting if the computer powersupply is driving more devices such as harddisk, CD R, etc

    E i C

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    38/69

    38

    Experiments on Computers

    Voltage sag is normally not a hugeproblem to single computers unlessthey are used as servers or mainframecomputers.

    The sag typically restarts the computer,which results in loss of data

    This may cause financial losses totrading and telecommunication offices

    E i t C t

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    39/69

    39

    Experiments on Computers

    The obtained numbers (which representsag depths and sag duration) were put

    in the CBEMA curve and were seen tocomply with the experimental values.

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    40/69

    40

    Experiments onExperiments onMicrowave OvensMicrowave Ovens

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    41/69

    41

    Experiments on Microwave OvensExperiments on Microwave Ovens

    -30

    -20

    -10

    0

    10

    20

    30

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.7

    Time (sec)

    Current(A)

    Load current for 50% sag depth and 30-cycle sag duration

    Current decreasing to almost

    zero signifying switching off

    condition

    Decrease in current signifying

    flickering inside the oven

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    42/69

    42

    Experiments on Microwave OvensExperiments on Microwave Ovens

    Sag Depth (%)

    5 10 20 30 40 60

    90 V V V V V D

    80 V V V V V D

    70 V V V V V D

    60 V V V S S S

    50 V S S S S S

    Sag Duration (cycles)

    Two microwave ovens were tested

    V: oven does not switch off, only visible effects such as flickering

    D: oven does not switch off, visible effects such as flickering andmomentary stopping of digital clock

    S: oven switches off without getting damaged

    Summary of performance of microwave oven A due to sags

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    43/69

    43

    Conclusions

    No microwave oven was damaged dueto sags of varying depths and duration

    Microwave oven A switched off for 60%depth/ 30 cycle duration and 50%

    depth/ 10 cycle duration

    Microwave oven B showed only visible

    effects of sags such as flickering

    Experiments on Microwave OvensExperiments on Microwave Ovens

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    44/69

    44

    Experiments on TelevisionsExperiments on Televisions

    Current waveform for 50%, 60-cycle sag (television turns off)

    Point of sag initiation

    Period marked by

    blinking and shrinkingof image

    Television switches

    off automatically

    End of sag marked by

    sharp surge; television

    turns on automatically

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    45/69

    45

    Experiments on TelevisionsExperiments on TelevisionsTwo televisions were tested

    N: television has no effect of sag

    V: television does not switch off; only visible effect such as

    blinking and shrinking of image S: television switches off without getting damaged

    Summary of performance of televisions due to sags

    Sag Depth (%)

    5 10 20 30 40 60

    90 N N N N V V80 N N V V V V

    70 V V V V V V

    60 V V V V V V

    50 V V V S S S

    Sag Duration (cycles)

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    46/69

    46

    Conclusions

    No television was damaged due to sags ofvarying depths and duration because ofinternal protection circuitry

    The televisions switched off for 50% depthand duration greater than 20 cycles

    The end of sag was marked by a surge; at

    this instant the television switches onautomatically

    The cause of the surge is Switch Mode

    Power Supply (SMPS) inside the television

    Experiments on TelevisionsExperiments on Televisions

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    47/69

    47

    Experiments on DVD/VHS PlayersExperiments on DVD/VHS PlayersThree VHS/DVD players were tested

    N: VHS/DVD has no effect of sag

    V: VHS/DVD does not switch off; only visible effect such asblinking of electronic timer

    D: VHS/DVD does not switch off; electronic timer stopsmomentarily

    Summary of performance of DVD/ VHS players due to sags

    Sag Depth (%)

    5 10 20 30 40 60

    90 N N N N N N80 N N N N N N

    70 N N N V V V

    60 N N N V V V

    50 V V D D D D

    Sag Duration (cycles)

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    48/69

    48

    Experiments on DVD/VHS PlayersExperiments on DVD/VHS Players

    Point of sag initiation

    Current waveform for 70%, 50-cycle sag (flickering in timer)

    Momentary current zero

    signifying flickering of the

    timer

    Surge marking the end

    of sag; surge due to

    SMPS

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    49/69

    49

    Conclusions

    No VHS/DVD player was damaged due tosags of varying depths and duration

    The only effect of sags is the visible effecttermed as flickering of the electronic timer

    The end of sag was marked by a surge

    The cause of the surge is Switch ModePower Supply (SMPS) inside the players

    Experiments on VHS/DVD PlayersExperiments on VHS/DVD Players

    E i Di i l Cl k R diE i t Di it l Cl k R di

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    50/69

    50

    Experiments on Digital Clock RadiosExperiments on Digital Clock RadiosTwo FM/AM digital clock radios were tested

    N: digital clock radio has no effect of sag

    V: only visible effect such as flickering of the electronic timer

    A: loss of audio for few cycles

    Summary of performance of digital clock radios due to sags

    Sag Depth (%)

    5 10 20 30 40 60

    90N N N N N N

    80 N N N N V V

    70 V V V V V V

    60 V V V V A A

    50 V V V A A A

    Sag Duration (cycles)

    E i t T tE i t T t

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    51/69

    51

    Experiments on ToastersExperiments on ToastersTwo toasters were tested

    N: toaster has no effect of sag

    V: only visible effect such as blinking of the coils

    S: toaster switches off; to be restarted manually

    Summary of performance of toasters due to sags

    Sag Depth (%)

    5 10 20 30 40 60

    90N N N N N N

    80 N N N N N N

    70 N N N N N N

    60 V V V V V S/V

    50 V V V V S/V S/V

    Sag Duration (cycles)

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    52/69

    52

    Conclusions

    No toaster was damaged due to sags ofvarying depths and duration

    For the case when toaster has just begun

    operation, toaster switches off automaticallyfor 60% depth/60 cycle and 50% depth/40cycle,60 cycle duration; it is restarted

    manually For the case when toaster is already

    operational, there is no effect of sag except

    blinking of red hot coils

    Experiments on ToastersExperiments on Toasters

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    53/69

    53

    CBEMA Curve AnalysisCBEMA Curve Analysis

    CBEMA Curve AnalysisCBEMA Curve Analysis

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    54/69

    54

    CBEMA curve defines the envelope withinwhich the equipment should continue tofunction without interruption

    It plots the depth of voltage sags inpercentage on the vertical axis against theduration of voltage sags on the horizontalaxis

    Curves have been created for all theappliances that were switched off or stalleddue to voltage sags air conditioners,computers, microwave ovens, andtelevisions

    CBEMA Curve AnalysisCBEMA Curve Analysis

    CBEMA Curve AnalysisCBEMA Curve Analysis - MethodologyMethodology

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    55/69

    55

    The CBEMA curves are plotted using theresults of the experiments performed on the

    various appliances The CBEMA curve for the appliance is

    created by looking at the voltage sag depth

    and duration for which the appliance isaffected by the sag

    For a particular sag depth, if the appliance is

    affected by several sag durations, then theminimum sag duration for which theequipment stalled is taken as the boundary

    point

    CBEMA Curve AnalysisCBEMA Curve Analysis -- MethodologyMethodology

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    56/69

    56

    CBEMA Curve AnalysisCBEMA Curve Analysis--MethodologyMethodology

    A percentage level of 40% is used to provide

    zero level for the CBEMA curve

    The corresponding sag duration for 40% sagdepth is chosen as duration which is less than

    the x coordinate of the boundary point

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    57/69

    57

    CBEMA Curve AnalysisCBEMA Curve Analysis--MethodologyMethodologySag Depth (%)

    5 10 20 30 40 60

    90 N N N N N N

    80 N N N N N N

    70 N N N N N N

    60 N N N Y Y Y50 N Y Y Y Y Y

    Sag Duration (cycles)

    1 10 100Duration in (60 Hz) cycles

    40

    50

    60

    70

    80

    90

    Magnitude

    inPercent

    Standard CBEMA curve

    Microwave oven switches off

    No effect of voltage sags

    Ove

    nsw

    itch

    esoff

    ITIC

    CBEMA Curve AnalysisCBEMA Curve Analysis

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    58/69

    58

    CBEMA Curve AnalysisCBEMA Curve Analysis

    1 10 100Duration in (60 Hz) cycles

    40

    60

    80

    100

    Mag

    nitudeinPercent

    Standard CBEMA curve

    ITIC

    Air-conditioner compressorsLighting LoadsMicrowave OvensTelevisionsComputers

    The obtainedCBEMA curves areconservative in

    comparison tostandard CBEMA/ITIC curves

    These curvesprovide the utilitiesand themanufacturers with

    the informationabout thesensitivity of theequipment to

    voltage sags

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    59/69

    59

    Survey of ResidentialSurvey of Residential

    ComplexesComplexes

    Survey of Residential Complexes

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    60/69

    60

    The survey of electric loads is performed

    for an apartment complex to identify themost common electric loads present ineach unit

    Two apartment complexes were surveyed Tempe Terrace and University Crossroads

    The common loads are the air-conditioningmotors, fan motors, refrigerators,

    microwave ovens, bulbs, crushers, andtelevisions

    Survey of Residential ComplexesSurvey of Residential Complexes

    Creation of Prediction Table for aCreation of Prediction Table for a

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    61/69

    61

    The identification of the common loads throughsurveys resulted in the creation of predictiontable for a single apartment

    It predicts the effect of voltage sags on a single

    apartment as a function of sag depth andduration

    The maximum effects of voltage sags to the

    residential customers occur during a sag depthof 50% and duration greater than 10 cycles. Mostof the single phase electric motors stall, themicrowave switches off, lamps get blown off and

    the television switches off

    Single Apartment UnitSingle Apartment Unit

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    62/69

    62

    Sample Prediction TableSample Prediction Table

    50%

    Non-Stalling

    AC

    motor

    stalls,

    Microw

    ave

    ovens

    switches

    off

    automati

    cally

    AC

    motor

    stalls,

    Microw

    ave

    ovens

    switches

    off

    automati

    cally

    AC motor

    stalls,Microwave

    ovens

    switches off

    automaticall

    y, television

    switches off

    automaticall

    y and turns

    on

    automaticall

    y after thesag

    AC motor

    stalls,Microwave

    ovens

    switches off

    automatically,

    television

    switches off

    automatically

    and turns on

    automatically

    after the sag,

    toasterswitches off

    In the case of DVD/VHS

    players, for 30-cycle duration

    and greater, the timer stops for2-3 seconds and resets itself

    once the sag is over, in the

    case of digital clock radios

    audio is lost for duration of 50

    and 60 cycles and takes few

    cycles after the sag is over to

    recover, in the case of stereo

    players song being played is

    stopped accompanied by a

    scratching noise, song restarts

    few cycles after the sag is over,Toaster switches off for

    duration of 40 cycles or more

    5~ 10~ 20~ 30~ 40~ 60~

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    63/69

    63

    Financial Implication ofFinancial Implication of

    Voltage SagsVoltage Sags

    Financial Implication of Voltage SagsFinancial Implication of Voltage Sags

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    64/69

    64

    Voltage sags do not damage any householdequipment. Hence, residential customers have

    minimal or no cost of voltage sags incurred onthem

    Electric utilities might incur financial losses ifvoltage sags cause feeders to go out ofoperation.

    This scenario is possible if all the air-conditionercompressors in an apartment complex are stalledfor sag of 50% depth and duration greater than 30

    cycles and restarted simultaneously

    Financial Implication of Voltage SagsFinancial Implication of Voltage Sags

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    65/69

    65

    Overall ConclusionsOverall Conclusions

    Overall ConclusionsOverall Conclusions

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    66/69

    66

    Overall ConclusionsOverall Conclusions

    The most severely effected is the computer assag can cause loss of data

    No damage occurred on any of the loads

    The sag may stop the air conditioners in the

    residential areas due to sags The restart can produce over load if all air-

    conditioners are started simultaneously and

    further sags can occur.

    In residential areas, the sag has minimal financial

    consequences to the owners

    Contribution of the ProjectContribution of the Project

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    67/69

    67

    Has provided the utilities and the customers withthe information that voltage sags are not a

    serious cause of concern in residential areas Has provided the utilities and the manufacturers

    of sensitive equipment with CBEMA curves which

    will inform them about the sensitivity of theequipment

    Has provided the utilities with a prediction table

    of a single apartment which will help in predictingthe performance of loads on being subjected tovoltage sags

    Contribution of the ProjectContribution of the Project

    PublicationsPublications

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    68/69

    68

    S. Saksena, B. Shi, G. Karady, Effects of voltagesags on household loads, IEEE Power

    Engineering Society, San Francisco, June 2005

    S. Saksena, G. Karady, Effects of voltage sags

    on sensitive equipment in residentialcomplexes, IEEE Transaction on Power Delivery,to be submitted

    S. Saksena, G. Karady, Designing CBEMAcurves for household appliances affected byvoltage sags, IEEE Transaction Letter, to be

    submitted

    PublicationsPublications

    AcknowledgementsAcknowledgements

  • 7/29/2019 Karady Voltage Sag Pserc Tele-seminar Feb2006

    69/69

    69

    AcknowledgementsAcknowledgements

    Sincere acknowledgement to PowerSystem Engineering Research Center(PSERC) for sponsoring the research

    Special thanks to Dr. Baj Agrawal,Arizona Public Service for key inputs

    Special thanks to Salt River Project for

    lending us the Voltage Sag Generator