I.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” John Comey B.Eng. M.Eng. M.Sc. MIEI Comsec Protection Systems Ltd. Michael P. Lyons, B.E., CEng, MIEI Chartered Engineer Michael P. Lyons & Associates

Transcript of John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification...

Page 1: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

John ComeyB.Eng. M.Eng. M.Sc. MIEIComsec Protection Systems Ltd.

Michael P. Lyons, B.E., CEng, MIEI Chartered  EngineerMichael P. Lyons & Associates

Page 2: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Current certification system: a brief overview.Why crisis, example of why systems are not working.Look at voluntary 3rd Party Certification SchemeLessons from other industries.Suggestions

Page 3: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Page 4: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

4 Certificates Signed By:1. Designer 2. Installer 3. Commissioner4. Client (Handover)

Design

Install

Commission HandoverOptional 5th Certificate for Verification.Required for New Systems and Modifications to existing, since 1989.Not controlled documents but should be issued on headed paper of company.

Page 5: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Designer certifies:System designed to comply with IS3218Certifies his competence to do thisModifications to existing system will not adversely impact on the original system.

Certificate includes a list of design drawings for the compliant systemCertificate records any variations from the standards for example:

Use reduced sound levels in hospitals (HTM05‐03).Engineered solutions for environmental reasons etc. 

install

HandoverCommission

DesignDesign

I.S.3218:2009 Annex C1

Page 6: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Design certificate should be issued before installation and commissioning process.  (Clause 4.4.3)

“Ideally, a single party should maintain overall responsibility for the system design, development and implementation process”. (Clause 5.2.9) 

Where it is not possible verification process (as set out in clause 7.5.11.2) should be considered.

install

HandoverCommission

DesignDesign

Page 7: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Installer Certifies:system had been installed in accordance with design cert, specification and drawings,installation complies with Clauses 5 and 7 of I.S. 3218:2009,their competence to do this work ,and any modifications to existing system will have no adverse effect on that existing system . 

Certificate includes a list of as installed drawings for the compliant system

install

HandoverCommission

DesignDesign

I.S.3218:2009 Annex C2

Page 8: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

As well as certificate of Installation, the installer is also required to issue a separate certificate of compliance with Electro‐Technical Council of Ireland Limited (ETCI) ET101 guidelines, for the wiring following testing of cabling. (Clause 7.5.3 )

ETCI cert. are controlled certificates purchased from RECI and ECSSA and may be subject to periodic inspections by them.

install

HandoverCommission

DesignDesign

Page 9: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

3 Types of commissioning Certificate:

New system (Annex C3)Modification (Annex C4)Early Handover (Annex C5)

Commissioner Certifies:They have inspected, tested and commissioned the system in accordance with IS3218.

Certificate should include a list of variations from both the standard and the Designer’s specification (or a declaration that there is none)

install

HandoverCommission

DesignDesign

Page 10: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Commissioning Process includes 100% test of full system. 

(Clause 7.5.8.4.2)

Measure sound levels to confirm they are adequate 

(Clause 7.5.8.4.2)

install

HandoverCommission

DesignDesign

Page 11: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Issued to the User/PurchaserSigned by the “Responsible Person” for the acceptance of the fire alarm system.

install

Commission

DesignDesign

Page 12: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Includes a checklist to say that they have:

Witnessed the system in operation, (including links to Alarm receiving centres if applicable)Received Design, Installation and Commissioning Certificates.Received all drawings Received all Manuals Sufficient people have been trained on the system.

install

Commission

DesignDesign

Page 13: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Optional verification CertificateTest done by competent independent person“The prime objective of the verification process is to independently assess, as far as is reasonably practicable, that the system as installed meets the standard set out in the Design, Installation, Commissioning and Handover certification”. (Clause 7.5.11.2)

install

HandoverCommission

DesignDesign

Page 14: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Certificate of servicing/testing of fire alarm should be issued to users following: 

Quarterly inspection and tests:Annual inspection and tests;Special servicing following a fire or false alarms.

Display Certificate:Displayed next to the control panel showing date of last service/next service. 

Page 15: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Page 16: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Zone Chart:“On or adjoining to the CIE shall be a diagrammatic representation of the building (zone chart), showing at least the building entrances, the circulation areas, stairwells and escape routes and the division into zones”. (Clause  5.12.8.2 )

Page 17: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Required since 1989 standard.How important are they?How often do you see zone charts?

Also required in UK under their BS5839 standard. The following findings from a Scottish sheriff’s report into Rosepark Care Home fire illustrate their importance*.

*Reference:SHERIFFDOM OF SOUTH STRATHCLYDE DUMFRIES AND GALLOWAY Fatal Accident Inquiry http://www.scotcourts.gov.uk/opinions/2011FAI18.pdf

Page 18: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Rosepark Care Home Fire10 People killed, January 2004.Several factors found to have contributed to the deaths.One being the delay in locating source of fire:

Building split across two levels.Main Entrance on upper level.Fire Panel Labelled “Ground Floor and Lower Ground Floor.Staff used “ground” and “First”Staff Searching Lower Level while fire was on upper level

Photo from BBC news website.http://news.bbc.co.uk/2/hi/uk_news/scotland/4213535.stm

Page 19: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

One of the findings of the report “RP4.1: It would have been a reasonable precaution to have provided clear information at the fire alarm panel (and, in particular, a diagrammatic representation) such as would enable staff to identify quickly and accurately the location of the detector which had been activated.”**(SHERIFFDOM OF SOUTH STRATHCLYDE DUMFRIES AND GALLOWAY  Fatal Accident Inquiry  Report   http://www.scotcourts.gov.uk/opinions/2011FAI18.pdf)

Photo from BBC news website.http://news.bbc.co.uk/2/hi/uk_news/scotland/4213535.stm

Page 20: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Fire Resistive Cables : to maintain their integrity they should be supported in a way that has equal fire resistance to the cable.Best done by fixing directly to the building structure using manufacturers recommended supports. (e.g. copper P clips)Steel conduit or Tray also permitted provided steel cable ties are used.

(I.S.3218 clause 5.14.4.5)

Plastic ties will melt quickly

Page 21: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Plastic Connectors

Inner cores exposed

Page 22: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

When exposed to fire outer insulation becomes charred and brittle. If not supported can break exposing inner cores. 

Loose cables pose additional hazard for fire fighters.

Cable pulled out of Panel by weight of unsupported cable.

Fire Alarm Cable Following Fire

Page 23: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Irish standard 3218 is specific about the sound level requirement:

65 dB(A) or 5 dB(A) above background noise (whichever is higher).To wake a sleeping person 75 dB(A) at the bed head.In all accessible areas of the building.Tone ideally between 500 and 1000 Hz

Exceptions:HTM05‐03 Part B areas where patients require assistance to evacuate 45 –55 dB(A),  Draft IS3218:2013 (may be reduced to 60dB(A) in some limited circumstances.

Page 24: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

The installation of the fire alarm system to IS3218 L3X, escape routes and rooms leading onto escape routes.Detectors in Stairwells, corridors and Apartment lobbies.Internal layout, may contain numerous partitions  and doors. Sounders in lobbies alone often not sufficient to reach required sound level in bedroom.Note: Different requirement for individual apartments’ (or houses’) stand alone “Domestic Systems” Lower limit  of 85dB(A) in open bedroom door applies

sounder

Page 25: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Same issues seen over and over again.....Why?

Commercial Pressure?Poor knowledge of  the standard?Certificates not being issued?Certificates not being requested?

Is self certification working?Is third party certification the answer?

Customer

EngineerBuilder

Electrical Contractor

Fire Alarm Company

Page 26: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Page 27: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Recommended by IS3218:2009“... Within two years of the publication of this Standard, Commissioning providers shall be able to formally demonstrate competence in commissioning procedures. Commissioning providers who are third party certified and registered should be preferred (see 5.2.9 g)).” (Clause 7.5.8.1)“... Commissioning providers should be certified by a Certification Body that is accredited by a member of the European Cooperation of Accreditation (EA), (clause 5.2.9 g)

Currently optionalAccreditation currently operated by two companies:

National Standards Authority of Ireland (NSAI)Management Systems Certification Limited (MSC)

Launched by NSAI in 2006 for “Commissioners” –initial launch stated Design and Install to follow but this hasn’t happened.

Page 28: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Industry Slow to Adopt SchemeFirst company registered in 2006 was Comsec Protection Systems Ltd.Only two companies registered in 2009 when new standard launched.Currently 7 companies listed on NSAI site as accredited. MSC (the only other company currently providing a scheme) have only 1 company registered for past 3 years.FESA (A trade body for the industry) currently has 80 members listed on their Website. This is only a portion of those installing/commissioning fire systems. 

Page 29: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Why has the industry not embraced the scheme?Not compulsory?Not specified by designers?Not required by large user groups e.g. government bodies such as HSE?Not insisted on by Fire officers?Expensive?

Page 30: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Page 31: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Intruder Alarm Systems.An Garda Síochána launched in the mid 90’s a policy  on Monitored intruder alarms to reduce number of nuisance  calls.Will only respond to calls from companies/homes with URN.Must be installed by certified alarm installer.PSA act in 2004 made 3rdparty certification compulsory.

Page 32: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Registered Gas Installers:Since 2006, the Commission for Energy Regulation (CER) has worked with the gas industry to put in place a new regulatory system to supervise the work of gas installers with respect to safety. This new statutory‐based regulatory system has replaced the previous voluntary register operated by Bord Gaìs*.

Electrical Installations:On 21st October 2008, the Commission for Energy 

Regulation (CER) appointed the Electrical Contractors Safety & Standards Association (Ireland) Ltd (ECSSAI) and the Register of Electrical Contractors of Ireland Ltd (RECI) as the new electrical safety supervisory bodies (SSBs). These SSBs are now responsible for regulating the activities of Registered Electrical Contractors (RECs).#

• Reference: • *http://www.rgii.ie/about‐us/the‐rgii‐register.2713.html• #http://www.safeelectric.ie/about.php

Page 33: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Page 34: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Crisis = Challenges

My focus is going to be on what is currently missing and some suggestions

I would ask you to ask yourself and your colleagues ‐What is this "it" and why is "it" missing ?

Challenges = Solutions

Page 35: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Step 1 We need an Irish standard for Domestic Smoke Alarm systems I.S. 5839‐6:2013,  or

I.S.3218 Part 1 for commercial buildings

I.S.3218 Part 2 for dwellings and buildings containing dwellings

Page 36: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Step 2:We need to agree that for all dwellings ‐ flats, maisonettes, apartments, housesWe should specify an LD1 system 

Smoke detection in bedrooms for all dwellings.

The argument that there is an acceptable trade‐off between protective fire barriers (walls, doors)/alternative route(s) and the non‐existent (in practical terms) "additional protection" afforded by an LD1 over an LD3/LD2 is frequently a nonsense, is specious sophistry because : LD1 only gives additional detection away from the escape route but offers no hard protection to the occupant(s). 

In 90% of simple commercial buildings the same goes for L1 over L2/L3

Page 37: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Step 3:Change B1 to mention detection and alarm

There currently is no “legal” mention of detection

Building Regulation B1: “ A building shall be so designed and constructed that there are adequate means of escape in case of fire from the building to a place of safety outside the building, capable of being safely and effectively used.”TGD‐B: “Means of escape” means ‐ Physical means whereby a safe route or routes is or are provided for persons to travel from any point in a building to a place of safety.i.e. No mention of means of warning

Page 38: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

The courts give pride of place to evidence given by agents of the Fire Authority

It behoves Fire Authorities to have a common practice arrangement or document for installers

Is it really the place for the NSAI to try and establish a national common framework from within an Irish Standard ? 

Why is there a vacuum that they are trying to fill ?

Will it not all fall foul of competition law ?

Page 39: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

I.S.3218:2008 (2013) is not a manual

but neither is there any authoritative supporting manual published by anybody else

NSAIDepartment of EnvironmentCFOA ‐ LAFOARECIECSSAAECI

Step 4: Implementation manual is neededHochiki Europe have a guide to BS5839‐1:2002BSI’s  “BIP 2109:2008” – Guide to BS5839‐1 [Colin S. Todd]BSI’s   “BIP 2044:2004” – Guide to BS5839‐6 [Colin S. Todd]

Anecdotal evidence of huge variation in practice

Page 40: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Intended staged approach of < Design ‐ Installation ‐ Commissioning ‐ Handover / Verification > 

Step 5: Needs to be supported by Fire Authorities

Intelligent directed actionDissemination of pro‐active policy, and Common consistent procedure(s) 

by agents of Fire Authorities

Page 41: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Biggest qualitative problem within the industry installers are being foisted with doing an installation without an agreed design, since 1989.......

Solution: Create a level playing field for contractorsOne design to be priced ‐make it illegal to install a fire detection and alarm system without a written design to IS3218Condition it on every fire safety certificate issued

e.g."A copy of the fully completed fire detection and alarm system's design certificate to Annex C1 to be forwarded to the Building Control Authority with any Commencement Notice".e.g."A copy of the fully completed fire detection and alarm system's design certificate to Annex C1, and the associated performance summary description} to be forwarded to the Building Control Authority with any Commencement Notice".

Page 42: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Step 6 : ConveyancingSOFT PAINLESS ENFORCEMENT

Conditions attached to FSCs trigger obligations fromsolicitors etc and create an atmosphere of compliance

MPLAA:The mindset of a "clean" FSC is nonsense and indicative ofisolated thinkingA BC Authority is entitled, indeed expected, under thelegislation to issue conditions indicating its direction.

Page 43: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

The first and immediate interaction with the public in Ireland is not a fire : it is the fire alarm system and many systems are not meeting the public's expectations in 

quality, performance or delivery of reliability. 

The public look to the state's agent in each little republic 

back to the Fire Authority.

Page 44: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Where is the Crisis ?

What is missing ?

What is needed is Systemic Clarity

Page 45: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

I.S. 3218 ;  Certification of fire detection and alarm systems, “ a system in crisis ”

Page 46: John Comey and Michael Lyons - Certification of fire ... · PDF fileI.S. 3218 ; Certification of fire detection and alarm systems, “ a system in crisis ” Current certification

Comsec Protection Systems Ltd.Fire Protection and Security Engineers.

Unit 26 Stadium Business Park.Ballycoolin Rd.

Dublin 11Tel: (01) 8853008Fax: (01) 8853007

Email: [email protected] http://www.comsec.ie/

John ComeyB.Eng M.Eng.(Elec.) M.Sc.(Fire) MIEI

12 RECTORY SLOPES, HERBERT ROAD,

BRAY, CO. WICKLOW

TEL: 01 2829688 FAX: 01 2116925

MOB: 086 6093847Email: [email protected]

Michael P. Lyons, B.E., CEng, MIEI Chartered EngineerMichael P. Lyons & Associates