Job Name: System Reference: Date: Indoor Unit: PEAD-A36AA7 Outdoor Unit: PUZ-A36NKA7 PUZ-A36NKA7-BS INDOOR UNIT FEATURES Unobtrusive ceiling-concealed design for short-run ductwork. Wide ranging external static pressure Built-in condensate lift mechanism Auto fan speed mode Optional FB Series filter boxes for easy access and service Ideal for residential homes,retail shopping centers, larger classrooms, office complexes, conference ballrooms, fitness centers, and more OUTDOOR UNIT FEATURES Variable speed INVERTER-driven compressor Suction accumulator pre-charged with refrigerant volume for piping length up to 100 ft (70 ft. for A12/18/24/30) 24-hour continuous operation (cooling mode) High pressure protection Fast restart due to bypass valve make it ideal for equipment cooling applications, such as data centers Superior energy and operational efficiency SUBMITTAL DATA: PEAD-A36AA7 & PUZ-A36NKA7(-BS) 36,000 BTU/H HORIZONTAL-DUCTED HEAT PUMP SYSTEM Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc. P-SERIES

Transcript of ISUBMITTAL DATA: PEAD-A36AA7 & PUZ-A36NKA7( … Ducted Fan Coils/PEAD-A36AA7___PUZ... ·...

Page 1: ISUBMITTAL DATA: PEAD-A36AA7 & PUZ-A36NKA7( … Ducted Fan Coils/PEAD-A36AA7___PUZ... · pead-a36aa7 21 outlines & dimensions outlines & dimensions hwe16080 indoor unit pead-a12,

Job Name:

System Reference: Date:

Indoor Unit:

PEAD-A36AA7

Outdoor Unit:

□ PUZ-A36NKA7

□ PUZ-A36NKA7-BS

INDOOR UNIT FEATURES• Unobtrusive ceiling-concealed design for short-run ductwork.• Wide ranging external static pressure• Built-in condensate lift mechanism• Auto fan speed mode• Optional FB Series filter boxes for easy access and service• Ideal for residential homes,retail shopping centers, larger classrooms, office complexes, conference ballrooms,

fitness centers, and more

OUTDOOR UNIT FEATURES• Variable speed INVERTER-driven compressor• Suction accumulator pre-charged with refrigerant volume for piping length up to 100 ft (70 ft. for A12/18/24/30)• 24-hour continuous operation (cooling mode)• High pressure protection• Fast restart due to bypass valve make it ideal for equipment cooling applications, such as data centers• Superior energy and operational efficiency

SUBMITTAL DATA: PEAD-A36AA7 & PUZ-A36NKA7(-BS)36,000 BTU/H HORIZONTAL-DUCTED HEAT PUMP SYSTEM

Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.

P-SERIES

Page 2: ISUBMITTAL DATA: PEAD-A36AA7 & PUZ-A36NKA7( … Ducted Fan Coils/PEAD-A36AA7___PUZ... · pead-a36aa7 21 outlines & dimensions outlines & dimensions hwe16080 indoor unit pead-a12,

Model number Indoor unit PEAD-A36AA7

Outdoor unit PUZ-A36NKA7

PUZ-A36NKA7-BS

Cooling*1 Maximum Capacity Btu/h 36,000

Rated Capacity Btu/h 36,000

Minimum Capacity Btu/h 16,000

Maximum Power Input W 3,000

Rated Power Input W 3,000

Moisture Removal Pints/h 8.10

Sensible Heat Factor 0.75

Power factor % 93.8

Heating at 47° F*2 Maximum Capacity Btu/h 40,000

Rated Capacity Btu/h 38,000

Minimum Capacity Btu/h 18,200

Maximum Power Input W 3,020

Rated Power Input W 2,410

Power factor % 92.7

Heating at 17° F*3

Maximum Capacity Btu/h 24,200

Rated Capacity Btu/h 20,800

Maximum Power Input W 2,400

Rated Power Input W 2,350

Efficiency SEER 19.1

EER *1 12.0

HSPF (IV) 9.9

COP at 47° F *2 4.62

COP at 17° F *3 2.60

Electrical Voltage, Phase, Frequency 208 / 230V, 1-phase, 60 Hz

Guaranteed Voltage Range V AC 187 - 253

Voltage: Indoor - Outdoor, S1-S2 V AC 208V / 230

Voltage: Indoor - Outdoor, S2-S3 V DC 24

Voltage: Indoor - Remote controller V DC 12

Recommended Fuse/Breaker Size A 30

Recommended Wire Size (Indoor - Outdoor) AWG 14

Indoor unit MCA A 3.30

MOCP A 15

Fan Motor Full Load Amperage A 2.64

SPECIFICATIONS: PEAD-A36AA7 & PUZ-A36NKA7(-BS)

Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.

Page 3: ISUBMITTAL DATA: PEAD-A36AA7 & PUZ-A36NKA7( … Ducted Fan Coils/PEAD-A36AA7___PUZ... · pead-a36aa7 21 outlines & dimensions outlines & dimensions hwe16080 indoor unit pead-a12,

Model number Indoor unit PEAD-A36AA7

Outdoor unit PUZ-A36NKA7

PUZ-A36NKA7-BS

Fan Motor Output W 244

Airflow Rate, Dry CFM 847-1024-1201

Airflow Rate, Wet CFM 807-984-1161

External Static Pressure in.WG 0.14-0.20-0.28-0.40-0.60

Sound Pressure Level dB(A) 33-38-42

Drain Pipe Size In. (mm) 1-1/4 (32)

Condensate Lift Mechanism, Max. Distance Ft. (m) 27-9/16 (700)

Heat Exchanger Type Plate fin coil

External finish color Galvanized

Unit Dimensions // Grille Dimensions W: In. (mm) 55-1/8 (1400)

D: In. (mm) 28-7/8 (732)

H: In. (mm) 9-7/8 (250)

Package Dimensions // Grille Dimensions W: In. 65

D: In. 34-11/16

H: In. 13-7/16

Unit Weight Lbs. (kg) 86 (39)

Package Weight Lbs. 101

Indoor unitoperatingtemperature range

Cooling Intake Air Temp (Maximum /Minimum)

°F 90 DB, 73 WB / 66 DB, 59 WB

Heating Intake Air Temp (Maximum /Minimum)

°F 82 DB / 50 DB

Outdoor unit MCA A 25

MOCP A 31

Fan Motor Full Load Amperage A 0.5 + 0.5

Fan Motor Output W 74

Airflow Rate CFM 3,880

Refrigerant Control Electronic Expansion Valve

Defrost Method Reverse Cycle

Heat Exchanger Type Cross fin

Sound Pressure Level, Cooling*1 dB(A) 52

Sound Pressure Level, Heating*2 dB(A) 53

Compressor Type INVERTER-driven twin rotary

Compressor Model MNB33FBRMC-L

Compressor Rated Load Amps A 8

SPECIFICATIONS: PEAD-A36AA7 & PUZ-A36NKA7(-BS)

Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.

Page 4: ISUBMITTAL DATA: PEAD-A36AA7 & PUZ-A36NKA7( … Ducted Fan Coils/PEAD-A36AA7___PUZ... · pead-a36aa7 21 outlines & dimensions outlines & dimensions hwe16080 indoor unit pead-a12,

Model number Indoor unit PEAD-A36AA7

Outdoor unit PUZ-A36NKA7

PUZ-A36NKA7-BS

Compressor Locked Rotor Amps A 13

Compressor Oil Type // Charge oz. FV50S // 45

External finish color Ivory Munsell 3Y 7.8/1.1

Base pan heater n/a

Unit Dimensions W: In. (mm) 1050 [41-5/16]

D: In. (mm) 330 + 30 [13+1-3/16]

H: In. (mm) 1338 [52-11/16]

Package Dimensions W: In. 42-15/16

D: In. 17-11/16

H: In. 56-4/16

Unit Weight Lbs. 214 (97)

Package Weight Lbs. 243 (110)

Outdoor unitoperatingtemperature range

Cooling *5 Intake Air Temp (Maximum /Minimum)

°F 115 DB / 0* DB

Heating Intake Air Temp (Maximum /Minimum)

°F 70 DB, 59 WB / -4 DB, -4 WB

Thermal Lock-out / Re-start Temperatures** °F -8 / -4 DB

Refrigerant Type R410A

Charge Lbs, oz 10 lbs, 6 oz

Piping Gas Pipe Size O.D. (Flared) In.(mm) 5/8 (15.88)

Liquid Pipe Size O.D. (Flared) In.(mm) 3/8 (9.52)

Maximum Piping Length Ft. (m) 165 (50)

Maximum Height Difference Ft. (m) 100 (30)

Maximum Number of Bends 15

AHRI RatedConditions

*1 Cooling (Indoor // Outdoor) °F 80°F DB, 67°F WB // 95°F DB, 75°F WB

*2 Heating at 47°F (Indoor // Outdoor) °F 70°F DB, 60°F WB // 47°F DB, 43°F WB

*3 Heating at 17°F (Indoor // Outdoor) °F 70°F DB, 60°F WB // 17°F DB, 15°F WB

Conditions *4 Heating at 5°F (Indoor // Outdoor) °F 70°F DB, 60°F WB // -4°F DB, -5°F WB

Notes

*Wind baffles required to operate below 23°F DB in cooling mode. PUZ with wind baffle: 0°F - 115°F.

**System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures

SPECIFICATIONS: PEAD-A36AA7 & PUZ-A36NKA7(-BS)

Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.

Page 5: ISUBMITTAL DATA: PEAD-A36AA7 & PUZ-A36NKA7( … Ducted Fan Coils/PEAD-A36AA7___PUZ... · pead-a36aa7 21 outlines & dimensions outlines & dimensions hwe16080 indoor unit pead-a12,

SEACOAST PROTECTION

External Outer Panel: Phosphate coating + Acrylic-Enamel coating

Fan Motor Support: Epoxy resin coating (at edge face)

Separator Assembly; Valve Bed: Epoxy resin coating (at edge face)

“Blue Fin” treatment is an anti-corrosion treatment that is applied to the condenser coil to protect it against airbornecontaminants.

Notes:

SPECIFICATIONS: PEAD-A36AA7 & PUZ-A36NKA7(-BS)

Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.

Page 6: ISUBMITTAL DATA: PEAD-A36AA7 & PUZ-A36NKA7( … Ducted Fan Coils/PEAD-A36AA7___PUZ... · pead-a36aa7 21 outlines & dimensions outlines & dimensions hwe16080 indoor unit pead-a12,

PEAD-A36AA7

Filter Box with Filters (MERV 13) □ FBM2-4

3-Pole Disconnect Switch (30A/600V/UL) [fits 2" X 4" utility box] □ TAZ-MS303

Drain Pan Level Sensor (Control for indoor unit shut off to prevent drain pan overflow) □ DPLS2

Advanced Blue Diamond Mini-Condensation pump w/ Resevoir & Sensor (110V) □ X87-711 - 110

Advanced Blue Diamond Mini-Condensation pump w/ Resevoir & Sensor (208/230V) □ X87-721 - 208/230

Extension Cord for Blue Diamond Pump □ C13-103

MegaBlue Blue Diamond Condensate Pump (110-230V) □ X87-835

Remote Sensor (extensible) □ PAC-SE41TS-E

Connector Cable for Remote Display □ PAC-SA88HA-EP

□ PAC-725AD-E (10pcs)

Connector for CN32 (remote ON/OFF) □ PAC-SE55RA-E

Connector for CN24 (Back up heating) □ PAC-SE56RA-E

Connector for CN30 (LLC) □ PAC-SE57RA-E

Remote Operation Adapter (with wire terminals for remote ON/OFF and operation status/error)

□ PAC-SF40RM-E*1

External Fan / Heater Control Relay Adapter □ CN24RELAY-KIT-CM3

Backlit, Wall-mounted, Wireless □ MHK1

Wireless Adapter □ PAC-USWHS002-WF-1

BACnet® and Modbus Interface □ PAC-UKPRC001-CN-1

Wall-mounted, Wired □ PAC-YT53CRAU-J

T-STAT Interface □ PAC-US444CN-1

Wired Remote Controller □ PAR-32MAA

Signal Receiver □ PAR-SA9CA-E

Wireless Remote Controller □ PAR-FL32MA-E

Wireless Signal Receiver □ PAR-FA32MA-E

Wire for Remote ON/OFF with CN32 connector □ PAC-715AD

Lockdown Bracket for Wireless, Hand-held, Remote Controllers □ RCMKP1CB*1 Unable to use with wireless remote controller

PUZ-A36NKA7(-BS)

Twinning Distribution Pipe (50:50) □ MSDD-50TR-E

Air Outlet Guide □ PAC-SH96SG-E

Front Wind Baffle □ WB-PA

Drain socket □ PAC-SG61DS-E

Centralized Drain Pan □ PAC-SH97DP-E

M-NET Converter □ PAC-SF83MA-E

ACCESSORIES: PEAD-A36AA7 & PUZ-A36NKA7(-BS)

Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.

Page 7: ISUBMITTAL DATA: PEAD-A36AA7 & PUZ-A36NKA7( … Ducted Fan Coils/PEAD-A36AA7___PUZ... · pead-a36aa7 21 outlines & dimensions outlines & dimensions hwe16080 indoor unit pead-a12,

PUZ-A36NKA7(-BS)

Control/Service Tool □ PAC-SK52ST

Wall mounting bracket (powder-coated steel) □ QCWB2000M-1

Wall mounting bracket (316 Series Stainless Steel) □ QCWBSS

M-NET control adapter for Building Management System □ PAC-SF83MA-E

Outdoor Unit Mounting Pad 24" x 42" x 3" □ ULTRILITE2

Outdoor Unit 3-1/4 inch Mounting Base - Pair (Plastic) □ DSD-400N

MiniSplit Mounting Stand-Dual Fan models - 12" □ QSMS1202M

MiniSplit Mounting Stand-Dual Fan models - 18" □ QSMS1802M

MiniSplit Mounting Stand-Dual Fan models - 24" □ QSMS2402M

3/8 x 5/8 x 10' / 1/2" Lineset (Twin-Tube Insulation) □ MPLS385812T-10

3/8 x 5/8 x 15' / 1/2" Lineset (Twin-Tube Insulation) □ MPLS385812T-15

3/8 x 5/8 x 30' / 1/2" Lineset (Twin-Tube Insulation) □ MPLS385812T-30

3/8 x 5/8 x 50' / 1/2" Lineset (Twin-Tube Insulation) □ MPLS385812T-50

3/8 x 5/8 x 65' / 1/2" Lineset (Twin-Tube Insulation) □ MPLS385812T-65

3/8 x 5/8 x 100' / 1/2" Lineset (Twin-Tube Insulation) □ MPLS385812T-100

ACCESSORIES: PEAD-A36AA7 & PUZ-A36NKA7(-BS)

Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.

Page 8: ISUBMITTAL DATA: PEAD-A36AA7 & PUZ-A36NKA7( … Ducted Fan Coils/PEAD-A36AA7___PUZ... · pead-a36aa7 21 outlines & dimensions outlines & dimensions hwe16080 indoor unit pead-a12,

PEAD-A36AA7

21H

WE

16080

OU

TLINE

S &

DIM

EN

SIO

NS

6.OU

TLINES &

DIM

ENSIO

NS

IND

OO

R U

NIT

PEAD

-A12, 18, 24, 30, 36, 42A

A7

200(

7-7/

8)

120°

120°ø125

135

378(14-15/16) 153(6-1/16)

B(S

uspe

nsio

n bo

lt pi

tch)

23(1

5/16

)

CA

40(1

-5/8

)

15(5/8)

40(1

-5/8

)

58(2

-5/1

6)

20(1

3/16

)D

(Duc

t)

30(1

-3/1

6)10

0(3-

15/1

6)X

(E-1

)=F

100(

3-15

/16)

10(7/16)

57(2-1/4) 643(25-3/8)

18(3/4) 210(8-5/16)

21(7

/8)

G

732(28-7/8)32(1-5/16) 700(27-9/16)

238(9-3/8)10(7/16)

33(1

-5/1

6)

40(1

-5/8

)10

0(3-

15/1

6)

122(

4-13

/16)

178(

7-1/

16)

136 67

356(14-1/16)

217(

8-9/

16)

41(1

-5/8

)

250(

9-7/

8)

23(1

5/16

)

H±3

(H±1

/8)

J±3(

J±1/

8)

(4-15/16)

(5-3

/8)

3-ø2.9(1/8) mount hole

Drain pipe(O.D ø32(1-1/4))Fresh air intake ø100(3-15/16)knock out hole

2XE-ø2.9(1/8)

(Suspension bolt pitch)

Air filter

Drain pipe(Integral lift pump outlet)

Drain pump

(DU

CT)

1Refrigerant piping (gas) (5-3/8) (2-11/16)

(Emergency drain)

2Refrigerant piping(liquid)

Drain pipe(O.Dø32(1-1/4))(Gravity drain)

Terminal block(Power source)

Terminal block(Transmission)

Note 4

Control box

(O.Dø32(1-1/4))

Top

Top

Bottom

view

Top

Bottom

Inlet airside view

Outlet airside view

Opposite pipingside view

Pipingside view

2X2-ø2.9(1/8)

(43-5/16)

(55-1/8)

(45-7/16)

(57-1/4) (59-1/16) (53-9/16)

(47-1/4) (41-3/4) (39-3/8)

(51-3/16)

(41-11/16)

(53-1/2)

2Liquid pipe1Gas pipe

1058

13581300

Model

1200 1110601100 1154

1400

ø15.88 (5/8)

1454 1500

ø9.52 (3/8)

1360 14

1000PEAD-A24,30AA7

PEAD-A36,42AA7

Unit:mm(in.)

Airinlet

Airoutlet

Note 1.Use an M10 screw for the suspension bolt (field supply).

2.Keep the service space for maintenanceat the bottom.

3.This drawing is for PEAD-A24·30·36·42AA7 models,which have 2 fans. PEAD-A12·18AA7 models have 1 fan.

4.If the inlet duct is used,remove the airfilter (supplied with the unit), theninstall the filter (field supply) at thesuction side.

5.Heat air to 0˚C (32˚F) or higher whentaking fresh air with a fresh air intake.

PEAD-A24,30AA7

PEAD-A36,42AA7

PEAD-A12,18AA7

Model A EDCB F G

Unit:mm(in.)

(35-7/16) (37-9/16) (39-3/8) (33-7/8) (31-1/2) (33-13/16) 8581000 9 860 900 954 800PEAD-A12,18AA7

ø12.7 (1/2)

ø6.35 (1/4)

(3-1/8)78

H

(2-7/8)72

J

(2-5/8)66

(2-1/2)62

Unit:mm(in.)

DIMENSIONS: PEAD-A36AA7 & PUZ-A36NKA7 (-BS)

Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.

Page 9: ISUBMITTAL DATA: PEAD-A36AA7 & PUZ-A36NKA7( … Ducted Fan Coils/PEAD-A36AA7___PUZ... · pead-a36aa7 21 outlines & dimensions outlines & dimensions hwe16080 indoor unit pead-a12,

PUZ-A36NKA7(-BS)

16

PUZ-A

36NK

A7

PUZ-A

42NK

A7

PUY-A

36NK

A7

PUY-A

42NK

A7

PUZ-A

36NK

A7-B

S PU

Z-A42N

KA

7-BS

PUY-A

36NK

A7-B

S PU

Y-A42N

KA

7-BS

Bottom piping hole(Knockout)

Drain hole(5-ø33<1-5/16>)

154

<6-1

/16>

136

<5-1

1/32

>

81 <3-3/16>

45 <1-25/32>

110 <14-11/32>160

<6-5/16>160

<6-5/16>160

<6-5/16>

86<3

-3/8

>

Rear Air Intake

Handle for moving

Handle for moving

Side Air Intake

12

Handle for moving

Handle for moving

Service panel

Earth terminal Terminal connectionLeft ... Power supply wiringRight ... Indoor/Outdoor wiring

*1 4

42<1

7-2/

5>

1063

<41-

7/8>

632

<24-

7/8>

*1 4

50<1

7-23

/32>

26<1

-1/3

2>36

9<1

4-17

/32>

1338

<52-

11/1

6>

362 <14-1/4>1050 <41-11/32>

Air intake

Front piping cover

Rear piping cover

2-12×36 Oval holes(Foundation Bolt M10<W3/8>)

Installation Feet

2-U Shaped notched holes(Foundation Bolt M10<W3/8>)

225 <8-27/32>

42 <1-21/32>60 <2-3/8>

25<3

1/32

>33

0<1

3>

225 <8-27/32>600 <23-5/8>

70 <2-3/4>

417

<16-

13/3

2>

28<1

-3/3

2>37

0<1

4-9/

16>

19<3

/4>

40 <1-9/16> 53 <2-3/32>

56 <2-7/32>

0

Conduit hole(ø 24<15/16>knockout)

Conduit hole(ø 37<1-15/32>knockout)

Rear trunking hole(Knockout)

Rear piping hole(Knockout)

75 <2-15/16>

92 <3-5/8>

73<2

-7/8

>60

<2-3

/8>

5<3/

16>

26<1

-1/3

2>

27<1

-1/1

6>55

<2-3

/16>

55 <2-3/16> 60 <2-3/8>

ø 92<3-5/8>

Conduit hole(ø 24<15/16>knockout)

Front piping hole(Knockout)

Front trunking hole(Knockout)

Conduit hole(ø 37<1-15/32>knockout)

26<1

-1/3

2>

92 <3-5/8> 27<1

-1/1

6>55

<2-3

/16>

73<2

-7/8

>

75 <2-15/16>

55 <2-3/16>60 <2-3/8>

ø 92<3-5/8>

Right trunking hole(Knockout)

Conduit hole(ø 37<1-15/32>knockout)

Conduit hole(ø 24<15/16>knockout)

Right piping hole(Knockout)

73<2

-7/8

>61

<2-3

/8>

5<3/

16>

29 <1-5/32>

27<1

-1/1

6>26

<1-1

/32>

92<3

-5/8

>

53 <2-3/32> 60 <2-3/8>

55 <2-3/16>

92 <3-5/8>

ø 92<3-5/8>

Min.

Min.

Min.

Min.

Service space Min.

150

<5-2

9/32

>50

0<1

9-11

/16>

500<19-11/16>

15 <3/5>

50<2> Ma

x.30

<1-3

/16>

( )

21 ... Refrigerant GAS pipe connection (FLARE) ø15.88(5/8F)

... Refrigerant LIQUID pipe connection (FLARE) ø9.52(3/8F)

*1 ... Indication of STOP VALVE connection location.

Piping Knockout Hole Details

Example of Notes

FREE

Min. 15mm<3/5>

Min. 15mm<3/5>

Min. 1000mm<39-3/8>

Min. 150mm<5-29/32>

Piping and wiring connectionscan be made from 4 directions:FRONT, Right, Rear and Below.

4 PIPING-WIRING DIRECTIONS3 FOUNDATION BOLTS2 SERVICE SPACE1 FREE SPACE (Around the unit)Please secure the unit firmlywith 4 foundation (M10<W3/8>) bolts.(Bolts and washers must be purchased locally.)

Dimensions of space neededfor service access areshown in the below diagram.

The diagram below shows a basic example.Explantion of particular details aregiven in the installation manuals etc.

<Foundation bolt height>

Air Discharge

Rear Air Intake

Side Air Intake

1/2 Conduitattachment

ø 22.2<7/8>ø 27.8<1-3/32>

When installing the conduit.Set the attachment to the inner side of each panel.

3/4 Conduitattachment

Scale 1:5

60 <2-3/8> 22.5 <7/8>

5<3/

16>

24.7

<31/

32>

100<3-15/16>

FOUNDATION

OC

H636

Unit: mm<in>

FORM# PEAD-A36AA7 / PUZ-A30NKA7(-BS) -201702Ver2

1340 Satellite Boulevard. Suwanee, GA 30024Toll Free: 800-433-4822 www.mehvac.com

DIMENSIONS: PEAD-A36AA7 & PUZ-A36NKA7 (-BS)

Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.