Iso Es Cb Interlocks

78
P. GOPALA KRISHNA ADE/400KV/APTRANSCO

description

pfa

Transcript of Iso Es Cb Interlocks

  • P. GOPALA KRISHNAADE/400KV/APTRANSCO

  • INTERLOCKS

    ISOLATOR AND

    EARTH SWITCH INTERLOCKS

    FOR

    1. SINGLE MAIN BUS WITH TRANSFER BUS SYSTEM

    2. DOUBLE MAIN BUS WITH TRANSFER BUS SYSTEM

    3. ONE AND HALF BREAKER SYSTEM

  • INTERLOCKS

    STANDARD PRACTICE1. FOR BUS ISOLATON: EACH BUS HAVING BUS ISOLATOR FOR

    EACH BAY.

    2. FOR CB ISOLATION: CIRCUIT BREAKER HAVING BOTH SIDES ISOLATORS.

    3. FOR LINE/ICT ISOLATION: LINE / ICT HAVING LINE ISOLATOR.

    4. FOR BUS MAINTANENCE: EACH BUS HAVING BUS EARTH SWITCH.

    5. FOR CB MAINTANENCE: EACH ISOLATOR HAVING EARTH SWITCH TOWARDS CB SIDE.

    6. FOR LINE / ICT MAINTANENCE: EACH LINE / ICT HAVING LINE EARTH SWITCH.

  • INTERLOCKS

    1. ISOLATORS ARE NO LOAD SWITCHES. THEY ARE NOT PERMITTED TO BREAK POWER CURRENT OR TO CONNECT DIFFERENT VOLTAGE SYSTEM.

    2. MAKING OR BREAKING OF PARALLEL CIRCUITS IS PERMITTED.3. AN ISOLATOR CONNECTED IN SERIES WITH A CB MAY BE OPERATED

    WHEN CB IS OPEN AND IF NONE OF ADJACENT EARTH SWITCHES IS CLOSED. EVEN IF ANOTHER ISOLATOR CONNECTED IN SERIES TO THE CB IS OPEN THE ISOLATOR IS NOT ALLOWED TO OPERATED UNLESS THE CB IS OPEN.

    4. AN ISOLATOR CONNECTED TO A DUPLICATE BUSBAR OR AUXILIARY BUS MAY BE OPERATED IFi) NO LOAD IS CONNECTED AND NON OF THE EARTH SWITCH IS CLOSED.ii) A PARALLELING CIRCUIT TO THE ISOLATOR IS PRESENT. (ONLY THROUGH THE BUSCOUPLER FOR THE ISOLATORS THAT ARE CONNECTED TO THE TRANSFER BUS.

    ISOLATORS

    1. OPERATED ONLY IF THE ISOLATORS ON BOTH THE SIDES ARE OPEN.2. EARTH SWITCHES WHICH CAN EARTH AN INCOMING LINE DIRECTLY OR

    THROUGH A CB CAN BE OPERATED IF AND ONLY IF THE LINE IS DEAD.

    EARTH SWITCH

  • INTERLOCKS

  • SINGLE BUS & TRANSFER BUS SYSTEM

    FEEDER1

    BUS

    TRANSFER BUS

    FEEDER2

    T

    R

    A

    N

    S

    F

    E

    R

    B

    U

    S

    C

    O

    U

    P

    L

    E

    R

    T/F-1 T/F-2

    BAY1 BAY2 BAY3 BAY4 BAY5

    INTERLOCKS

  • MAIN BUS(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-A89-C

    89-AE

    89-L

    52-CB

    89-LE1

    89-LE2

    BB389E

    BB189E

    FEEDER ORICT OR

    REACTOR

    FOR 89-A/BAY ISOLATOR OPERATION:1. 52 CB/BAY IN OPEN CONDITION.2. 89AE/BAY EARTH SWITCH OPEN CONDITION.3. 89LE1/BAY EARTH SWITCH OPEN CONDITION.4. BB189E BUSEARTH SWITCH OPEN CONDITION.

    89-A/BAY

    INTERLOCK

    CONTACTOR

    89-LE1

    OPEN

    89-AE

    OPEN

    52 CB

    OPEN

    BB189E

    OPEN

    &

    BB189EOPEN

    OPEN52 CB/BAY

    89-AE/BAYOPEN

    OPEN

    89A/BAYOPERATION

    89-LE1/BAY

    LINE BAY

  • MAIN BUS(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-A89-C

    89-AE

    89-L

    52-CB

    89-LE1

    89-LE2

    BB389E

    BB189E

    FEEDER ORICT OR

    REACTOR

    FOR 89-L ISOLATOR OPERATION:1. 52 CB IN OPEN CONDITION.2. 89AE EARTH SWITCH OPEN CONDITION.3. 89LE1 EARTH SWITCH OPEN CONDITION.4. 89LE2 LINE EARTH SWITCH OPEN CONDITION.

    89-L

    INTERLOCK

    CONTACTOR

    89-LE1

    OPEN

    89-AE

    OPEN

    52 CB

    OPEN

    &

    OPEN

    OPEN52 CB

    89-AEOPEN

    OPEN

    89LOPERATION89-LE1

    89-LE2

    89-LE2

    OPEN

    LINE BAY

  • MAIN BUS(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-A89-C

    89-AE

    89-L

    52-CB

    89-LE1

    89-LE2

    BB389E

    BB189E

    FEEDER ORICT OR

    REACTOR

    FOR 89-AE EARTH SWITCH OPERATION:1. 89-A ISOLATOR OPEN CONDITION.2. 89-L ISOLATOR OPEN CONDITION.

    89-AE

    INTERLOCK

    CONTACTOR

    89-A

    OPEN

    &OPEN

    89-A

    OPEN89-AEOPERATION

    89-L

    89-L

    OPEN

    LINE BAY

  • MAIN BUS(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-A89-C

    89-AE

    89-L

    52-CB

    89-LE1

    89-LE2

    BB389E

    BB189E

    FEEDER ORICT OR

    REACTOR

    FOR 89-LE1 EARTH SWITCH OPERATION:1. 89-A ISOLATOR OPEN CONDITION.2. 89-L ISOLATOR OPEN CONDITION.

    89-LE1

    INTERLOCK

    CONTACTOR

    89-A

    OPEN

    &OPEN

    89-A

    OPEN89-LE1OPERATION

    89-L

    89-L

    OPEN

    LINE BAY

  • MAIN BUS(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-A89-C

    89-AE

    89-L

    52-CB

    89-LE1

    89-LE2

    BB389E

    BB189E

    FEEDER ORICT OR

    REACTOR

    FOR 89-LE2 EARTH SWITCH OPERATION:1. 89C BUS ISOLATOR OPEN CONDITION.2. 89L LINE ISOLATOR OPEN CONDITION.3. LINE DEAD CONDITION i.e U/V RELAY

    OPERATED.

    89-LE2

    INTERLOCK

    CONTACTOR

    89-L

    OPEN

    89-C

    OPEN

    U/V RELAY

    OPTD

    &

    U/V RELAYOPTD

    89-COPEN

    OPEN

    89-LE2OPERATION

    89-L

    LINE BAY

  • MAIN BUS(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-A89-C

    89-AE

    89-L

    52-CB

    89-LE1

    89-LE2

    BB389E

    BB189E

    FEEDER ORICT OR

    REACTOR

    FOR 52 CB CIRCUIT BREAKER FOR REMOTE OPERATION:1. 86-GA HSTR/MTR RESET CONDITION.2. 86-GB HSTR/MTR RESET CONDITION.3. 96-BB TBC HSTR/MTR RESET CONDITION.

    52-CB

    INTERLOCK

    CONTACTOR

    96-BB

    RESET

    86-GB

    RESET

    86-GA

    RESET

    &

    86-GARESET

    86-GBRESET

    RESET

    52-CBREMOTEOPERATION

    96-BB

    LINE BAY

  • MAIN BUS(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-A89-C

    89-AE

    89-L

    52-CB

    89-LE1

    89-LE2

    BB389E

    BB189E

    FEEDER ORICT OR

    REACTOR

    FOR 52 CB CIRCUIT BREAKER FOR LOCAL OPERATION:1. 89-A ISOLATOR OPEN CONDITION.2. 89-L ISOLATOR OPEN CONDITION.3. 89-AE TBC EARTH SWITCH CLOSED CONDITION.4. 89-LE1 EARTH SWITCH CLOSED CONDITION.

    52CB

    INTERLOCK

    CONTACTOR

    89-LE1

    CLOSE

    89-AE

    CLOSE

    89L

    OPEN

    89A

    OPEN

    &

    89-A OPEN

    OPEN89-L

    89-AE CLOSE

    CLOSE

    52-CBLOCALOPERATION

    89-LE1

    LINE BAY

  • MAIN BUS(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-A89-C

    89-AE

    89-L

    52-CB

    89-LE1

    89-LE2

    BB389E

    BB189E

    FEEDER ORICT OR

    REACTOR

    FOR 89-C ISOLATOR OPERATION:1. NO OTHER ISOLATOR IS CLOSED TO TRANSFER BUS C2. BB389E EARTH SWITCH OPEN CONDITION.3. 89LE2 EARTH SWITCH OPEN CONDITION.4. 52 TBC CB IN OPEN CONDITION.

    OR1. 52 CB IN CLOSED POSITION.2. 89-A ISOLATOR CLOSED CONDITION.3. 89-L ISOLATOR CLOSED POSITION.4. 89-A/TBC BAY BUS-A ISOLATOR CLOSED POSITION.5. 89-C/TBC BAY BUS-C ISOLATOR CLOSED POSITION.6. NO OTHER ISOLATOR IS CLOSED TO TRANSFER BUS C7. ADDITIONAL INTERLOCK PROTECTION TRANSFERRED

    MAY ALSO PUT THROUGH PROTECTION TRANSFER SWITCH.

    89-A

    89-C

    89-AE

    52-CB

    89-CE

    TRANSFER BUS COUPLER

    LINE BAY

  • INTERLOCKS

    FOR LINE-1

    89-C/ LINE-1

    FOR LINE-2

    89-C/ LINE-2

    FOR ICT-1

    89-C/ ICT-1

    FOR ICT-2

    89-C/ ICT-2

    F

    U

    T

    U

    R

    E

    B

    A

    Y

    S

    + VE

    + VE

    TO OBTAIN A CONTACT FOR NO OTHER ISOLATOR CLOSED TO BUSBARC

    1. TO OBTAIN CONTACTS OF TRANSFER BUS COUPLER CIRCUIT CLOSSED IT IS PREFERED TO USE CONTACTS OF AUXILIARY RELAY ENERGISED UNDER THESE CONDITIONS.

    2. TO MAKE SURE THE PROTECTION IS TRANSFERRED TO TBC CIRCUIT BREAKER BEFORE THE ISOLATOR IS CLOSSED, CONTACT OF TRIP TRANSFER SWITCH MAY BE UTILISED.

    LINE BAY

  • INTERLOCKS

    89-C/BAY

    INTERLOCK

    CONTACTOR

    NO OTHER ISOLATOR CLOSED TOBUSBAR-C

    CLOSE

    BB389E

    OPEN

    89LE2

    OPEN

    52CB/TBC

    OPEN

    NO OTHER ISOLATOR CLOSED TOBUSBAR-C

    CLOSE

    52CB/BAY

    CLOSE CLOSE

    89L/BAY

    CLOSE

    89A/BAY89-A/TBC

    CLOSE CLOSE

    89C/TBC

    &

    52CB/TBC OPEN

    OPEN89-LE2

    BB389E OPEN

    CLOSENO OTHER ISOLATOR CLOSED TOBUSBAR-C

    &52CB/BAY CLOSECLOSE89-A

    89L CLOSE

    CLOSENO OTHER ISOLATOR CLOSED TOBUSBAR-C

    89-A/TBC

    89-C/TBC CLOSE

    CLOSETTS TRANSFER OR

    OPERATION 89-C/BAY

    LINE BAY

    .N TTTS

  • MAIN BUS(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-A89-C

    89-AE52-CB89-CE

    BB389E

    BB189E

    TRANSFER BUS COUPLER

    FOR 89-A / TBC ISOLATOR OPERATION:1. 52 CB / TBC IN OPEN CONDITION.2. 89AE / TBC EARTH SWITCH OPEN CONDITION.3. 89CE / TBC EARTH SWITCH OPEN CONDITION.4. BB189E BUSEARTH SWITCH OPEN CONDITION.

    89-A/TBC

    INTERLOCK

    CONTACTOR

    89-CE/TBC

    OPEN

    89-AE/TBC

    OPEN

    52 CB/TBC

    OPEN

    BB189E

    OPEN

    &

    BB189EOPEN

    OPEN52 CB / TBC

    89-AE / TBCOPEN

    OPEN

    89A / TBCOPERATION

    89-CE / TBC

    TBC BAY

  • MAIN BUS(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-A89-C

    89-AE52-CB89-CE

    BB389E

    BB189E

    TRANSFER BUS COUPLER

    FOR 89-C / TBC ISOLATOR OPERATION:1. 52 CB / TBC IN OPEN CONDITION.2. 89AE / TBC EARTH SWITCH OPEN CONDITION.3. 89CE / TBC EARTH SWITCH OPEN CONDITION.4. BB389E BUSEARTH SWITCH OPEN CONDITION.

    89-C/TBC

    INTERLOCK

    CONTACTOR

    89-CE/TBC

    OPEN

    89-AE/TBC

    OPEN

    52 CB/TBC

    OPEN

    BB389E

    OPEN

    &

    BB389EOPEN

    OPEN52 CB / TBC

    89-AE / TBCOPEN

    OPEN

    89C / TBCOPERATION

    89-CE / TBC

    TBC BAY

  • MAIN BUS(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-A89-C

    89-AE52-CB89-CE

    BB389E

    BB189E

    TRANSFER BUS COUPLER

    FOR 89-AE / TBC EARTH SWITCH OPERATION:1. 89-A / TBC ISOLATOR OPEN CONDITION.2. 89-C / TBC ISOLATOR OPEN CONDITION.

    89-AE/TBC

    INTERLOCK

    CONTACTOR

    89-A/TBC

    OPEN

    &OPEN

    89-A / TBC

    OPEN89-AE / TBCOPERATION

    89-C/TBC

    89-C/TBC

    OPEN

    TBC BAY

  • MAIN BUS(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-A89-C

    89-AE52-CB89-CE

    BB389E

    BB189E

    TRANSFER BUS COUPLER

    FOR 89-CE / TBC EARTH SWITCH OPERATION:1. 89-A / TBC ISOLATOR OPEN CONDITION.2. 89-C / TBC ISOLATOR OPEN CONDITION.

    89-CE/TBC

    INTERLOCK

    CONTACTOR

    89-A/TBC

    OPEN

    &OPEN

    89-A / TBC

    OPEN89-CE / TBCOPERATION

    89-C/TBC

    89-C/TBC

    OPEN

    TBC BAY

  • MAIN BUS(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-A89-C

    89-AE52-CB89-CE

    BB389E

    BB189E

    TRANSFER BUS COUPLER

    FOR 52 CB / TBC CIRCUIT BREAKER FOR REMOTE OPERATION:1. 86-GA / TBC HSTR/MTR RESET CONDITION.2. 86-GB / TBC HSTR/MTR RESET CONDITION.3. 96-BB / TBC HSTR/MTR RESET CONDITION.

    52-CB/TBC

    INTERLOCK

    CONTACTOR

    96-BB/TBC

    RESET

    86-GB/TBC

    RESET

    86-GA/TBC

    RESET

    &

    86-GA/TBCRESET

    86-GB/TBCRESET

    RESET

    52-CB/TBCREMOTEOPERATION

    96-BB/TBC

    TBC BAY

  • MAIN BUS(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-A89-C

    89-AE52-CB89-CE

    BB389E

    BB189E

    TRANSFER BUS COUPLER

    FOR 52 CB / TBC CIRCUIT BREAKER FOR LOCAL OPERATION:1. 89-A / TBC ISOLATOR OPEN CONDITION.2. 89-C / TBC ISOLATOR OPEN CONDITION.3. 89-AE / TBC EARTH SWITCH CLOSED CONDITION.4. 89-CE / TBC EARTH SWITCH CLOSED CONDITION.

    52CB/TBC

    INTERLOCK

    CONTACTOR

    89-CE/TBC

    CLOSE

    89-AE/TBC

    CLOSE

    89C/TBC

    OPEN

    89A/TBC

    OPEN

    &

    89-A/TBC OPEN

    OPEN89-C/ TBC

    89-AE / TBC CLOSE

    CLOSE

    52-CB / TBCLOCALOPERATION

    89-CE / TBC

    TBC BAY

  • MAIN BUS(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-A89-C

    89-AE

    89-L

    52-CB

    89-LE1

    89-LE2

    BB389E

    BB189E

    FEEDER ORICT OR

    REACTOR

    FOR BB189E EARTH SWITCH OPERATION:1. ALL BAYS BUS-A ISOLATORS OPEN CONDITION

    89-A

    89-C

    89-AE

    52-CB

    89-CE

    TRANSFER BUS COUPLER

    &

    89-A/BAY1 OPEN

    OPEN

    OPEN

    BB189EOPERATION89-A/BAY2

    89-A/BAYn

    UP TO NO OF BAYS

    BB189E

    INTERLOCK

    CONTACTOR

    89-A / BAY n

    OPEN

    89-A/BAY2

    OPEN

    89-A /BAY1

    OPENUP TO NO OF BAYS

    BUS BAY

  • MAIN BUS(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-A89-C

    89-AE

    89-L

    52-CB

    89-LE1

    89-LE2

    BB389E

    BB189E

    FEEDER ORICT OR

    REACTOR

    FOR BB389E EARTH SWITCH OPERATION:1. ALL BAYS BUS-C ISOLATORS OPEN CONDITION

    89-A

    89-C

    89-AE

    52-CB

    89-CE

    TRANSFER BUS COUPLER

    &

    89-C/BAY1 OPEN

    OPEN

    OPEN

    BB389EOPERATION89-C/BAY2

    89-C/BAYn

    UP TO NO OF BAYS

    BB389E

    INTERLOCK

    CONTACTOR

    89-C / BAY n

    OPEN

    89-C/BAY2

    OPEN

    89-C /BAY1

    OPENUP TO NO OF BAYS

    BUS BAY

  • INTERLOCKS

  • DOUBLE MAIN BUS & TRANSFER BUS SYSTEM

    FEEDER1

    BUS-2

    BUS-1

    FEEDER2

    T

    R

    A

    N

    S

    F

    E

    R

    B

    U

    S

    C

    O

    U

    P

    L

    E

    R

    T/F-1 T/F-2

    B

    U

    S

    C

    O

    U

    P

    L

    E

    R

    TRANSFER BUS

    FEEDER3 FEEDER4

    BAY1 BAY2BAY3 BAY4 BAY5

    BAY6 BAY7 BAY8

    INTERLOCKS

  • MAIN BUS-1(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-B 89-C89-AE

    89-L

    52-CB

    89-LE1

    89-LE2

    BB289E

    BB189E

    FEEDER ORICT OR

    REACTOROF BAY

    BB389E

    MAIN BUS-2(B)

    89-A

    FEEDER BAY

    89-A/BAY

    INTERLOCK

    CONTACTOR

    BB189E

    OPEN

    89-AE/BAY

    OPEN

    89LE1/BAY

    OPEN

    52CB/BAY

    OPEN

    89-A/BC

    CLOSE

    52 CB/BC

    CLOSE

    89-B/BC

    CLOSE

    89-B/BAY

    OPEN

    52CB/BAY

    CLOSE

    89-B/BAY

    CLOSE

    &

    52CB/BAY OPEN

    OPEN89-LE1/BAY

    89-AE/BAY OPEN

    OPEN

    &52CB/BAY CLOSE

    CLOSE89-A/BC

    89-B/BC CLOSE

    CLOSE

    89-B/BAY CLOSE

    OR &

    52CB/TBC

    89-B/BAY

    BB189EOPEN

    89-A/BAYOPERATION

    FOR 89-A/BAY ISOLATOR OPERATION:

  • MAIN BUS-1(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-B 89-C89-AE

    89-L

    52-CB

    89-LE1

    89-LE2

    BB289E

    BB189E

    FEEDER ORICT OR

    REACTOROF BAY

    BB389E

    MAIN BUS-2(B)

    89-A

    FEEDER BAY

    89-B/BAY

    INTERLOCK

    CONTACTOR

    BB289E

    OPEN

    89-AE/BAY

    OPEN

    89LE1/BAY

    OPEN

    52CB/BAY

    OPEN

    89-A/BAY

    CLOSE

    52 CB/BC

    CLOSE

    89-B/BC

    CLOSE

    89-A/BAY

    OPEN

    52CB/BAY

    CLOSE

    89-A/BC

    CLOSE

    &

    52CB/BAY OPEN

    OPEN89-LE1/BAY

    89-AE/BAY OPEN

    OPEN

    &52CB/BAY CLOSE

    CLOSE89-A/BC

    89-B/BC CLOSE

    CLOSE

    89-A/BAY CLOSE

    OR &

    52CB/TBC

    89-A/BAY

    BB289EOPEN

    89-B/BAYOPERATION

    FOR 89-B/BAY ISOLATOR OPERATION:

  • INTERLOCKS

    89-C/BAY

    INTERLOCK

    CONTACTOR

    NO OTHER ISOLATOR CLOSED TOBUSBAR-C

    CLOSE

    BB389E

    OPEN

    89LE2

    OPEN

    52CB/TBC

    OPEN

    NO OTHER ISOLATOR CLOSED TOBUSBAR-C

    CLOSE

    52CB/BAY

    CLOSE CLOSE

    89L/BAY

    CLOSE

    89A/BAY89-A/TBC

    CLOSE CLOSE

    89C/TBC

    &

    52CB/TBC OPEN

    OPEN89-LE2/BAY

    BB389E OPEN

    CLOSENO OTHER ISOLATOR CLOSED TOBUSBAR-C

    &52CB/BAY CLOSE

    89L/BAY CLOSE

    CLOSENO OTHER ISOLATOR CLOSED TOBUSBAR-C

    89-C/TBC CLOSETTS TRANSFER OR

    OPERATION 89-C/BAY

    FEEDER BAY

    &

    CLOSE

    89B/BAY

    CLOSE

    89B/TBC

    CLOSE89-B/TBC

    89-B/BAY CLOSE

    &CLOSE89-A/TBC

    89-A/BAY CLOSE

    OR

    FOR 89-C/BAY ISOLATOR OPERATION:

    .N TTTS

    FOR 89-C/BAY ISOLATOR OPERATION:

  • MAIN BUS-1(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-B 89-C89-AE

    89-L

    52-CB

    89-LE1

    89-LE2

    BB289E

    BB189E

    FEEDER ORICT OR

    REACTOROF BAY

    BB389E

    MAIN BUS-2(B)

    89-A

    FEEDER BAY

    FOR 89-L/BAY ISOLATOR OPERATION:

    &

    OPEN

    OPEN52 CB/BAY

    OPEN

    OPEN

    89L/BAYOPERATION89-LE1/BAY

    89-LE2/BAY

    89-L

    INTERLOCK

    CONTACTOR

    89-LE1/BAY

    OPEN

    89-AE/BAY

    OPEN

    ICT HV TE

    OPEN

    89-LE2/BAY

    OPEN

    89-AE/BAYOPENICT HV TE

    (FOR ICT ONLY)

    52 CB/BAY

    OPEN(FOR ICT ONLY)

  • MAIN BUS-1(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-B 89-C89-AE

    89-L

    52-CB

    89-LE1

    89-LE2

    BB289E

    BB189E

    FEEDER ORICT OR

    REACTOROF BAY

    BB389E

    MAIN BUS-2(B)

    89-A

    FEEDER BAY

    FOR 89-AE/BAY ISOLATOR OPERATION:

    &

    OPEN89-L/BAY

    89-A/BAY OPEN

    OPEN

    89-AE/BAYOPERATION

    89-B/BAY

    89-AE/BAY

    INTERLOCK

    CONTACTOR

    89A/BAY

    OPEN

    89-L/BAY

    OPEN

    89-B/BAY

    OPEN

  • MAIN BUS-1(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-B 89-C89-AE

    89-L

    52-CB

    89-LE1

    89-LE2

    BB289E

    BB189E

    FEEDER ORICT OR

    REACTOROF BAY

    BB389E

    MAIN BUS-2(B)

    89-A

    FEEDER BAY

    FOR 89-LE1/BAY ISOLATOR OPERATION:

    &

    OPEN89-L/BAY

    89-A/BAY OPEN

    OPEN

    89-LE1/BAYOPERATION

    89-B/BAY

    89-LE1/BAY

    INTERLOCK

    CONTACTOR

    89A/BAY

    OPEN

    89-L/BAY

    OPEN

    89-B/BAY

    OPEN

  • MAIN BUS-1(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-B 89-C89-AE

    89-L

    52-CB

    89-LE1

    89-LE2

    BB289E

    BB189E

    FEEDER ORICT OR

    REACTOROF BAY

    BB389E

    MAIN BUS-2(B)

    89-A

    FEEDER BAY

    FOR 89-LE2/BAY ISOLATOR OPERATION:

    &89-L/BAY OPEN

    OPEN89-C/BAY

    LINE U/V OPTD

    OPEN

    1-89LE2OPERATION

    LV-89T

    89-LE2

    INTERLOCK

    CONTACTOR

    LINE U/V

    OPTD

    LV-89T

    OPEN

    89-L/BAY

    OPEN

    89-C/BAY

    OPEN

    (FOR ICT)

    (FOR LINE)

    (FOR ICT) (FOR LINE)

  • MAIN BUS-1(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-B 89-C89-AE

    89-L

    52-CB

    89-LE1

    89-LE2

    BB289E

    BB189E

    FEEDER ORICT OR

    REACTOROF BAY

    BB389E

    MAIN BUS-2(B)

    89-A

    FEEDER BAY

    FOR 52 CB/BAY CIRCUIT BREAKER FOR REMOTE OPERATION:1. 86-GA HSTR/MTR RESET CONDITION.2. 86-GB HSTR/MTR RESET CONDITION.3. 96-BB TBC HSTR/MTR RESET CONDITION.

    52-CB/BAY

    INTERLOCK

    CONTACTOR

    96-BB

    RESET

    86-GB

    RESET

    86-GA

    RESET

    &

    86-GARESET

    86-GBRESET

    RESET

    52-CB/BAYREMOTEOPERATION

    96-BB

  • MAIN BUS-1(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-B 89-C89-AE

    89-L

    52-CB

    89-LE1

    89-LE2

    BB289E

    BB189E

    FEEDER ORICT OR

    REACTOROF BAY

    BB389E

    MAIN BUS-2(B)

    89-A

    FEEDER BAY

    FOR 52 CB /BAYCIRCUIT BREAKER FOR LOCAL OPERATION:1. 89-A ISOLATOR OPEN CONDITION.2. 89-L ISOLATOR OPEN CONDITION.3. 89-AE TBC EARTH SWITCH CLOSED CONDITION.4. 89-LE1 EARTH SWITCH CLOSED CONDITION.

    52-CB/BAY

    INTERLOCK

    CONTACTOR

    89-LE1

    CLOSE

    89-AE

    CLOSE

    89L

    OPEN

    89A

    OPEN

    &

    89-A OPEN

    OPEN89-L

    89-AE CLOSE

    CLOSE

    52-CB/BAYLOCALOPERATION

    89-LE1

  • MAIN BUS-1(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-B 89-C89-AE

    52-CB

    89-CE

    BB289E

    BB189E

    TRANSFER BUS

    COUPLER

    BB389E

    MAIN BUS-2(B)

    89-A

    TBC BAY

    FOR 89-A / TBC ISOLATOR OPERATION:1. 52 CB / TBC IN OPEN CONDITION.2. 89AE / TBC EARTH SWITCH OPEN CONDITION.3. 89CE / TBC EARTH SWITCH OPEN CONDITION.4. BB189E BUSEARTH SWITCH OPEN CONDITION.5. 89-B/TBC ISOLATOR OPEN CONDITION

    89-A/TBC

    INTERLOCK

    CONTACTOR

    89-CE/TBC

    OPEN

    89-AE/TBC

    OPEN

    52 CB/TBC

    OPEN

    BB189E

    OPEN

    &

    BB189EOPEN

    OPEN52 CB / TBC

    89-AE / TBCOPEN

    OPEN89A / TBCOPERATION

    89-CE / TBCOPEN89-B / TBC

    89-B/TBC

    OPEN

  • MAIN BUS-1(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-B 89-C89-AE

    52-CB

    89-CE

    BB289E

    BB189E

    TRANSFER BUS

    COUPLER

    BB389E

    MAIN BUS-2(B)

    89-A

    TBC BAY

    FOR 89-B / TBC ISOLATOR OPERATION:1. 52 CB / TBC IN OPEN CONDITION.2. 89AE / TBC EARTH SWITCH OPEN CONDITION.3. 89CE / TBC EARTH SWITCH OPEN CONDITION.4. BB289E BUSEARTH SWITCH OPEN CONDITION.5. 89-A/TBC ISOLATOR OPEN CONDITION

    89-B/TBC

    INTERLOCK

    CONTACTOR

    89-CE/TBC

    OPEN

    89-AE/TBC

    OPEN

    52 CB/TBC

    OPEN

    BB289E

    OPEN

    &

    BB289EOPEN

    OPEN52 CB / TBC

    89-AE / TBCOPEN

    OPEN89B / TBCOPERATION

    89-CE / TBCOPEN89-A / TBC

    89-A/TBC

    OPEN

  • MAIN BUS-1(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-B 89-C89-AE

    52-CB

    89-CE

    BB289E

    BB189E

    TRANSFER BUS

    COUPLER

    BB389E

    MAIN BUS-2(B)

    89-A

    TBC BAY

    FOR 89-C / TBC ISOLATOR OPERATION:1. 52 CB / TBC IN OPEN CONDITION.2. 89AE / TBC EARTH SWITCH OPEN CONDITION.3. 89CE / TBC EARTH SWITCH OPEN CONDITION.4. BB389E BUSEARTH SWITCH OPEN CONDITION.

    89-C/TBC

    INTERLOCK

    CONTACTOR

    89-CE/TBC

    OPEN

    89-AE/TBC

    OPEN

    52 CB/TBC

    OPEN

    BB389E

    OPEN

    &

    BB389EOPEN

    OPEN52 CB / TBC

    89-AE / TBCOPEN

    OPEN

    89C / TBCOPERATION

    89-CE / TBC

  • MAIN BUS-1(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-B 89-C89-AE

    52-CB

    89-CE

    BB289E

    BB189E

    TRANSFER BUS

    COUPLER

    BB389E

    MAIN BUS-2(B)

    89-A

    TBC BAY

    FOR 89-AE / TBC EARTH SWITCH OPERATION:1. 89-A / TBC ISOLATOR OPEN CONDITION.2. 89-B / TBC ISOLATOR OPEN CONDITION.3. 89-C / TBC ISOLATOR OPEN CONDITION.

    89-AE/TBC

    INTERLOCK

    CONTACTOR

    89-B/TBC

    OPEN

    &OPEN

    89-A / TBC

    OPEN89-AE / TBCOPERATION

    89-C/TBC

    89-C/TBC

    OPEN

    OPEN89-B / TBC

    OPEN

    89-A/TBC

  • MAIN BUS-1(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-B 89-C89-AE

    52-CB

    89-CE

    BB289E

    BB189E

    TRANSFER BUS

    COUPLER

    BB389E

    MAIN BUS-2(B)

    89-A

    TBC BAY

    FOR 89-CE / TBC EARTH SWITCH OPERATION:1. 89-A / TBC ISOLATOR OPEN CONDITION.2. 89-B / TBC ISOLATOR OPEN CONDITION.3. 89-C / TBC ISOLATOR OPEN CONDITION.

    89-CE/TBC

    INTERLOCK

    CONTACTOR

    89-B/TBC

    OPEN

    &OPEN

    89-A / TBC

    OPEN89-CE / TBCOPERATION

    89-C/TBC

    89-C/TBC

    OPEN

    OPEN89-B / TBC

    OPEN

    89-A/TBC

  • MAIN BUS-1(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-B 89-C89-AE

    52-CB

    89-CE

    BB289E

    BB189E

    TRANSFER BUS

    COUPLER

    BB389E

    MAIN BUS-2(B)

    89-A

    TBC BAY

    FOR 52 CB / TBC CIRCUIT BREAKER FOR REMOTE OPERATION:1. 86-GA / TBC HSTR/MTR RESET CONDITION.2. 86-GB / TBC HSTR/MTR RESET CONDITION.3. 96-BB / TBC HSTR/MTR RESET CONDITION.

    52-CB/TBC

    INTERLOCK

    CONTACTOR

    96-BB/TBC

    RESET

    86-GB/TBC

    RESET

    86-GA/TBC

    RESET

    &

    86-GA/TBCRESET

    86-GB/TBCRESET

    RESET

    52-CB/TBCREMOTEOPERATION

    96-BB/TBC

  • MAIN BUS-1(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-B 89-C89-AE

    52-CB

    89-CE

    BB289E

    BB189E

    TRANSFER BUS

    COUPLER

    BB389E

    MAIN BUS-2(B)

    89-A

    TBC BAY

    FOR 52 CB / TBC CIRCUIT BREAKER FOR LOCAL OPERATION:1. 89-A / TBC ISOLATOR OPEN CONDITION.2. 89-B / TBC ISOLATOR OPEN CONDITION.3. 89-C / TBC ISOLATOR OPEN CONDITION.4. 89-AE / TBC EARTH SWITCH CLOSED CONDITION.5. 89-CE / TBC EARTH SWITCH CLOSED CONDITION.

    52CB/TBC

    INTERLOCK

    CONTACTOR

    89-CE/TBC

    CLOSE

    89-AE/TBC

    CLOSE

    89C/TBC

    OPEN

    89B/TBC

    OPEN

    &

    89-A/TBC OPEN

    OPEN89-C/ TBC

    89-AE / TBC CLOSE

    CLOSE

    52-CB / TBCLOCALOPERATION

    89-CE / TBC

    89-B/TBCOPEN

    89A/TBC

    OPEN

  • MAIN BUS-1(A)

    INTERLOCKS

    89-A 89-B

    89-AE 52-CB 89-BE

    BB289E

    BB189E

    BUS COUPLER

    BC BAY

    MAIN BUS-2(B)

    FOR 89-A / BC ISOLATOR OPERATION:1. 52 CB / BC IN OPEN CONDITION.2. 89AE / BC EARTH SWITCH OPEN CONDITION.3. 89BE / BC EARTH SWITCH OPEN CONDITION.4. BB189E BUSEARTH SWITCH OPEN CONDITION.

    89-A/BC

    INTERLOCK

    CONTACTOR

    89-BE/BC

    OPEN

    89-AE/BC

    OPEN

    52 CB/BC

    OPEN

    BB189E

    OPEN

    &

    BB189EOPEN

    OPEN52 CB / BC

    89-AE / BCOPEN

    OPEN

    89A / BCOPERATION

    89-BE / BC

  • MAIN BUS-1(A)

    INTERLOCKS

    89-A 89-B

    89-AE 52-CB 89-BE

    BB289E

    BB189E

    BUS COUPLER

    BC BAY

    MAIN BUS-2(B)

    FOR 89-B / BC ISOLATOR OPERATION:1. 52 CB / BC IN OPEN CONDITION.2. 89AE / BC EARTH SWITCH OPEN CONDITION.3. 89BE / BC EARTH SWITCH OPEN CONDITION.4. BB289E BUSEARTH SWITCH OPEN CONDITION.

    89-B/BC

    INTERLOCK

    CONTACTOR

    89-BE/BC

    OPEN

    89-AE/BC

    OPEN

    52 CB/BC

    OPEN

    BB289E

    OPEN

    &

    BB289EOPEN

    OPEN52 CB / BC

    89-AE / BCOPEN

    OPEN

    89B / BCOPERATION

    89-BE / BC

  • MAIN BUS-1(A)

    INTERLOCKS

    89-A 89-B

    89-AE 52-CB 89-BE

    BB289E

    BB189E

    BUS COUPLER

    BC BAY

    MAIN BUS-2(B)

    FOR 89-AE / BC EARTH SWITCH OPERATION:1. 89-A / BC ISOLATOR OPEN CONDITION.2. 89-B / BC ISOLATOR OPEN CONDITION.

    89-AE/BC

    INTERLOCK

    CONTACTOR

    89-A/BC

    OPEN

    &OPEN

    89-A / TBC

    OPEN89-AE / BCOPERATION

    89-B/TBC

    89-B/BC

    OPEN

  • MAIN BUS-1(A)

    INTERLOCKS

    89-A 89-B

    89-AE 52-CB 89-BE

    BB289E

    BB189E

    BUS COUPLER

    BC BAY

    MAIN BUS-2(B)

    FOR 89-BE / BC EARTH SWITCH OPERATION:1. 89-A / BC ISOLATOR OPEN CONDITION.2. 89-B / BC ISOLATOR OPEN CONDITION.

    89-BE/BC

    INTERLOCK

    CONTACTOR

    89-A/BC

    OPEN

    &OPEN

    89-A / BC

    OPEN89-BE / BCOPERATION

    89-B/BC

    89-B/BC

    OPEN

  • MAIN BUS-1(A)

    INTERLOCKS

    89-A 89-B

    89-AE 52-CB 89-BE

    BB289E

    BB189E

    BUS COUPLER

    BC BAY

    MAIN BUS-2(B)

    FOR 52 CB / BC CIRCUIT BREAKER FOR REMOTE OPERATION:1. 86-GA / BC HSTR/MTR RESET CONDITION.2. 86-GB / BC HSTR/MTR RESET CONDITION.3. 96-BB / BC HSTR/MTR RESET CONDITION.

    52-CB/BC

    INTERLOCK

    CONTACTOR

    96-BB/BC

    RESET

    86-GB/BC

    RESET

    86-GA/BC

    RESET

    &

    86-GA/BCRESET

    86-GB/BCRESET

    RESET

    52-CB/BCREMOTEOPERATION

    96-BB/BC

  • MAIN BUS-1(A)

    INTERLOCKS

    89-A 89-B

    89-AE 52-CB 89-BE

    BB289E

    BB189E

    BUS COUPLER

    BC BAY

    MAIN BUS-2(B)

    FOR 52 CB / BC CIRCUIT BREAKER FOR LOCAL OPERATION:1. 89-A / BC ISOLATOR OPEN CONDITION.2. 89-B / BC ISOLATOR OPEN CONDITION.3. 89-AE / BC EARTH SWITCH CLOSED CONDITION.4. 89-BE / BC EARTH SWITCH CLOSED CONDITION.

    52CB/BC

    INTERLOCK

    CONTACTOR

    89-BE/BC

    CLOSE

    89-AE/BC

    CLOSE

    89B/BC

    OPEN

    &

    89-A/BC OPEN

    89-AE/BC CLOSE

    CLOSE

    52-CB / BCLOCALOPERATION

    89-BE/BC

    89-B/BCOPEN

    89A/BC

    OPEN

  • MAIN BUS-1(A)

    TRANSFER BUS( C )

    INTERLOCKS

    89-B 89-C89-AE

    89-L

    52-CB

    89-LE1

    89-LE2

    BB289E

    BB189E

    FEEDER ORICT OR

    REACTOROF BAY

    BB389E

    MAIN BUS-2(B)

    89-A

    BUS ES

    89-B

    89-AE 52-CB 89-BE

    BUS COUPLER

    89-A89-B 89-C

    52-CB

    89-CE

    TRANSFER BUS

    COUPLER

    89-A89-AE

  • INTERLOCKS BUS EARTH SWITCH

    &

    89-A/BAY1 OPEN

    OPEN

    OPEN

    BB189EOPERATION

    89-A/BAY2

    89-A/BAYn

    UP TO NO OF BAYS &

    89-B/BAY1 OPEN

    OPEN

    OPEN

    BB289EOPERATION

    89-B/BAY2

    89-B/BAYn

    UP TO NO OF BAYS &

    89-C/BAY1 OPEN

    OPEN

    OPEN

    BB389EOPERATION

    89-C/BAY2

    89-C/BAYn

    UP TO NO OF BAYS

    BB189E BB289E BB389E

    BB189E

    INTERLOCK

    CONTACTOR

    89-A / BAY n

    OPEN

    89-A/BAY2

    OPEN

    89-A /BAY1

    OPENUP TO NO OF BAYS

    BB289E

    INTERLOCK

    CONTACTOR

    89-B / BAY n

    OPEN

    89-B/BAY2

    OPEN

    89-B /BAY1

    OPENUP TO NO OF BAYS

    BB389E

    INTERLOCK

    CONTACTOR

    89-C / BAY n

    OPEN

    89-C/BAY2

    OPEN

    89-C /BAY1

    OPENUP TO NO OF BAYS

    FOR BUS EARTH SWITCH OPERATION, ALL ISOLATORS CONNECTED TO CONCERNED BUS ARE TO BE OPENED.

  • INTERLOCKS

  • I-CONFIGUARATION

    FEEDER2 FEEDER4 FEEDER6 FEEDER8 FEEDER10 FEEDER12

    FEEDER1 FEEDER3 FEEDER5 FEEDER7 FEEDER9 FEEDER11

    BUS-2

    BUS-1

    B

    A

    Y

    1

    B

    A

    Y

    2

    B

    A

    Y

    3

    B

    A

    Y

    4

    B

    A

    Y

    5

    B

    A

    Y

    6

    B

    A

    Y

    7

    B

    A

    Y

    8

    B

    A

    Y

    9

    B

    A

    Y

    1

    0

    B

    A

    Y

    1

    1

    B

    A

    Y

    1

    2

    B

    A

    Y

    1

    3

    B

    A

    Y

    1

    4

    B

    A

    Y

    1

    5

    B

    A

    Y

    1

    6

    B

    A

    Y

    1

    7

    B

    A

    Y

    1

    8

    DIA1 DIA2 DIA3 DIA4 DIA5 DIA6

    INTERLOCKS

  • D-CONFIGUARATION

    BUS-2

    BUS-1

    FEEDER3 FEEDER4 FEEDER7 FEEDER8 FEEDER11 FEEDER12

    FEEDER1 FEEDER2 FEEDER5 FEEDER6 FEEDER9 FEEDER10

    B

    A

    Y

    1

    BAY2

    B

    A

    Y

    3

    B

    A

    Y

    4

    BAY5

    B

    A

    Y

    6

    B

    A

    Y

    7

    BAY8

    B

    A

    Y

    9

    B

    A

    Y

    1

    0

    BAY11B

    A

    Y

    1

    2

    B

    A

    Y

    1

    3

    BAY14

    B

    A

    Y

    1

    5

    B

    A

    Y

    1

    6

    BAY17

    B

    A

    Y

    1

    8

    DIA1

    DIA2

    DIA3

    DIA4

    DIA5

    DIA6

    INTERLOCKS

  • ONE & HALF BREAKER SYSTEM

    LINE 1

    1-89

    1-89A

    1-52CB

    3-89

    3-89A

    3-52CB

    2-52CB

    2-89A 2-89B

    1-89L 3-89T

    BUS-1 BUS-2

    T/F-1

    U

    U

    U

    U

    U

    U

    LINESHUNT

    REACTOR .1-PH NEUTRAL GROUNDING

    REACTOR

    INTERLOCKS

    BB1-89E BB2-89E

    1-89E

    1-89AE 3-89AE

    2-89AE 2-89BE

    3-89E

    1-89LE 3-89TE

    1-89R1-89RE

  • LINE 1

    1-89

    1-89A

    1-52CB

    1-89L

    BUS-1U

    U

    U

    U

    U

    U

    L

    I

    N

    E

    S

    H

    U

    N

    T

    R

    E

    A

    C

    T

    O

    R

    .

    INTERLOCKS

    BB1-89E

    1-89E

    1-89AE

    1-89LE

    1-89R1-89RE

    BAY 1

    &BB189E OPEN

    OPEN1-89AE

    1-89E OPENOPEN

    1-89OPERATION

    1-52CB

    1-89

    INTERLOCK

    CONTACTOR

    1-89AE

    OPEN

    BB189E

    OPEN

    1-52 CB

    OPEN

    1-89E

    OPEN

    FOR 1-89 ISOLATOR OPERATION:

  • LINE 1

    1-89

    1-89A

    1-52CB

    1-89L

    BUS-1U

    U

    U

    U

    U

    U

    L

    I

    N

    E

    S

    H

    U

    N

    T

    R

    E

    A

    C

    T

    O

    R

    .

    INTERLOCKS

    BB1-89E

    1-89E

    1-89AE

    1-89LE

    1-89R1-89RE

    BAY 1

    &OPEN

    1-89A

    1-89 OPEN1-89E

    OPERATION

    1-89E

    INTERLOCK

    CONTACTOR

    1-89A

    OPEN

    1-89

    OPEN

    FOR 1-89E ISOLATOR OPERATION:

  • LINE 1

    1-89

    1-89A

    1-52CB

    1-89L

    BUS-1U

    U

    U

    U

    U

    U

    L

    I

    N

    E

    S

    H

    U

    N

    T

    R

    E

    A

    C

    T

    O

    R

    .

    INTERLOCKS

    BB1-89E

    1-89E

    1-89AE

    1-89LE

    1-89R1-89RE

    BAY 1

    &

    OPEN1-89AE

    1-89E OPEN

    OPEN

    1-89AOPERATION

    1-52CB

    1-89A

    INTERLOCK

    CONTACTOR

    1-89AE

    OPEN

    1-52 CB

    OPEN

    1-89E

    OPEN

    FOR 1-89A ISOLATOR OPERATION:

  • LINE 1

    1-89

    1-89A

    1-52CB

    1-89L

    BUS-1U

    U

    U

    U

    U

    U

    L

    I

    N

    E

    S

    H

    U

    N

    T

    R

    E

    A

    C

    T

    O

    R

    .

    INTERLOCKS

    BB1-89E

    1-89E

    1-89AE

    1-89LE

    1-89R1-89RE

    BAY 1

    FOR 1-89AE EARTH SWITCH OPERATION:

    &OPEN

    1-89A

    1-89 OPEN1-89AE

    OPERATION

    1-89AE

    INTERLOCK

    CONTACTOR

    1-89A

    OPEN

    1-89

    OPEN

  • LINE 1

    1-89

    1-89A

    1-52CB

    1-89L

    BUS-1U

    U

    U

    U

    U

    U

    L

    I

    N

    E

    S

    H

    U

    N

    T

    R

    E

    A

    C

    T

    O

    R

    .

    INTERLOCKS

    BB1-89E

    1-89E

    1-89AE

    1-89LE

    1-89R1-89RE

    BAY 1

    &OPEN2-52CB

    1-89LE OPENOPEN

    1-89LOPERATION

    1-52CB

    1-89L

    INTERLOCK

    CONTACTOR

    2-52 CB

    OPEN

    1-89R

    CLOSE

    1-52 CB

    OPEN

    1-89LE

    OPEN

    FOR 1-89L ISOLATOR OPERATION:

    1-89R CLOSEPUSHDC

    INTERLOCK BYPASS

    PB

    OR

    IL

    INTER LOCK FACILITY:WHEN 1-89R CLOSES ONLY

    PERMIT TO CLOSE 1-89L AND1-89L OPENS ONLY

    PERMIT TO OPEN 1-89R.

    DC INTERLOCK BYPASS PB

    PUSH

    IL

  • LINE 1

    1-89

    1-89A

    1-52CB

    1-89L

    BUS-1U

    U

    U

    U

    U

    U

    L

    I

    N

    E

    S

    H

    U

    N

    T

    R

    E

    A

    C

    T

    O

    R

    .

    INTERLOCKS

    BB1-89E

    1-89E

    1-89AE

    1-89LE

    1-89R1-89RE

    BAY 1

    &OPEN

    1-89L

    LINE U/V RELAY OPTD1-89LE

    OPERATION

    1-89LE

    INTERLOCK

    CONTACTOR

    LINE U/V RELAY

    OPTD

    1-89L

    OPEN

    FOR 1-89LE EARTH SWITCH OPERATION:

  • LINE 1

    1-89

    1-89A

    1-52CB

    1-89L

    BUS-1U

    U

    U

    U

    U

    U

    L

    I

    N

    E

    S

    H

    U

    N

    T

    R

    E

    A

    C

    T

    O

    R

    .

    INTERLOCKS

    BB1-89E

    1-89E

    1-89AE

    1-89LE

    1-89R1-89RE

    BAY 1

    &OPEN2-52CB

    1-89L OPENOPEN

    1-89LOPERATION

    1-52CB

    1-89L

    INTERLOCK

    CONTACTOR

    2-52 CB

    OPEN

    1-52 CB

    OPEN

    1-89LE

    OPEN

    FOR 1-89R ISOLATOR OPERATION:

    1-89RE OPEN

    IL

    1-89RE

    OPEN

  • LINE 1

    1-89

    1-89A

    1-52CB

    1-89L

    BUS-1U

    U

    U

    U

    U

    U

    L

    I

    N

    E

    S

    H

    U

    N

    T

    R

    E

    A

    C

    T

    O

    R

    .

    INTERLOCKS

    BB1-89E

    1-89E

    1-89AE

    1-89LE

    1-89R1-89RE

    BAY 1

    OPEN1-89R 1-89RE

    OPERATION

    1-89RE

    INTERLOCK

    CONTACTOR

    1-89R

    OPEN

    FOR 1-89RE EARTH SWITCH OPERATION:

  • INTERLOCKS BAY1

    REMOTE

    1-52 CB

    LOCAL

    1-52 CB

    INTERLOCK

    CONTACTOR

    1-89 E

    CLOSE

    1-89 AE

    CLOSE

    &1-89E

    CLOSE

    CLOSE

    1-52 CBLOCALOPERATION

    1-89AE

    LINE 1

    1-89

    1-89A

    1-52CB

    1-89L

    BUS-1U

    U

    U

    U

    U

    U

    L

    I

    N

    E

    S

    H

    U

    N

    T

    R

    E

    A

    C

    T

    O

    R

    .

    BB1-89E

    1-89E

    1-89AE

    1-89LE

    1-89R1-89RE

    1-52 CB

    INTERLOCK

    CONTACTOR

    96-BB/BAY1

    RESET

    86-GB/BAY1

    RESET

    86-GA/BAY1

    RESET

    &

    86-GA/BAY1RESET

    86-GB/BAY1RESET

    RESET

    1-52 CBREMOTEOPERATION

    96-BB/BAY1

  • 2-52CB

    2-89A 2-89B

    INTERLOCKS

    2-89AE 2-89BE

    BAY 2

    2-89A

    INTERLOCK

    CONTACTOR

    289-BE

    OPEN

    289-AE

    OPEN

    2-52 CB

    OPEN

    &

    OPEN2-52 CB

    289-AEOPEN

    OPEN

    2-89AOPERATION

    289-BE

    FOR 2-89A ISOLATOR OPERATION:

  • 2-52CB

    2-89A 2-89B

    INTERLOCKS

    2-89AE 2-89BE

    BAY 2

    2-89B

    INTERLOCK

    CONTACTOR

    289-BE

    OPEN

    289-AE

    OPEN

    2-52 CB

    OPEN

    &

    OPEN2-52 CB

    289-AEOPEN

    OPEN

    2-89BOPERATION

    289-BE

    FOR 2-89B ISOLATOR OPERATION:

  • 2-52CB

    2-89A 2-89B

    INTERLOCKS

    2-89AE 2-89BE

    BAY 2

    2-89AE

    INTERLOCK

    CONTACTOR

    289-B

    OPEN

    289-A

    OPEN

    &289-A

    OPEN

    OPEN2-89AEOPERATION

    289-B

    FOR 2-89AE EARTH SWITCH OPERATION:

  • 2-52CB

    2-89A 2-89B

    INTERLOCKS

    2-89AE 2-89BE

    BAY 2

    2-89BE

    INTERLOCK

    CONTACTOR

    289-B

    OPEN

    289-A

    OPEN

    &289-A

    OPEN

    OPEN2-89BEOPERATION

    289-B

    FOR 2-89BE EARTH SWITCH OPERATION:

  • INTERLOCKS BAY2

    REMOTE

    2-52 CB

    LOCAL

    2-52 CB

    INTERLOCK

    CONTACTOR

    2-89 BE

    CLOSE

    2-89 AE

    CLOSE

    &2-89BE

    CLOSE

    CLOSE

    2-52 CBLOCALOPERATION

    2-89AE

    2-52 CB

    INTERLOCK

    CONTACTOR

    96-BB/BAY2

    RESET

    86-GB/BAY2

    RESET

    86-GA/BAY2

    RESET

    &

    86-GA/BAY2RESET

    86-GB/BAY2RESET

    RESET

    2-52 CBREMOTEOPERATION

    96-BB/BAY2

    2-52CB

    2-89A 2-89B

    2-89AE 2-89BE

    FOR HALF DIA ONLY

    FOR HALF DIA ONLY

  • 3-89

    3-89A

    3-52CB

    3-89T

    BUS-2

    INTERLOCKSBB2-89E

    3-89E

    3-89AE

    3-89TE

    &BB289E OPEN

    OPEN3-89AE

    3-89E OPENOPEN

    3-89OPERATION

    3-52CB

    3-89

    INTERLOCK

    CONTACTOR

    3-89AE

    OPEN

    BB289E

    OPEN

    3-52 CB

    OPEN

    3-89E

    OPEN

    FOR 3-89 ISOLATOR OPERATION:

    BAY 3

    ICT

  • INTERLOCKS BAY 3

    &OPEN

    3-89A

    3-89 OPEN3-89E

    OPERATION

    3-89E

    INTERLOCK

    CONTACTOR

    3-89A

    OPEN

    3-89

    OPEN

    FOR 3-89E EARTH SWITCH OPERATION:

    3-89

    3-89A

    3-52CB

    3-89T

    BUS-2BB2-89E

    3-89E

    3-89AE

    3-89TE

    ICT

  • 3-89

    3-89A

    3-52CB

    3-89T

    BUS-2

    INTERLOCKSBB2-89E

    3-89E

    3-89AE

    3-89TE

    &OPEN

    3-89AE

    3-89E OPENOPEN

    3-89AOPERATION

    3-52CB

    3-89A

    INTERLOCK

    CONTACTOR

    3-89AE

    OPEN

    3-52 CB

    OPEN

    3-89E

    OPEN

    FOR 3-89A ISOLATOR OPERATION:

    BAY 3

    ICT

  • INTERLOCKS BAY 3

    &OPEN

    3-89A

    3-89 OPEN3-89AE

    OPERATION

    3-89AE

    INTERLOCK

    CONTACTOR

    3-89A

    OPEN

    3-89

    OPEN

    FOR 3-89AE EARTH SWITCH OPERATION:

    3-89

    3-89A

    3-52CB

    3-89T

    BUS-2BB2-89E

    3-89E

    3-89AE

    3-89TE

    ICT

  • 3-89

    3-89A

    3-52CB

    3-89T

    BUS-2

    INTERLOCKSBB2-89E

    3-89E

    3-89AE

    3-89TE

    &LV89TE2 OPEN

    OPEN2-52 CB

    3-89TE OPENOPEN

    3-89TOPERATION

    3-52CB

    3-89T

    INTERLOCK

    CONTACTOR

    2-52CB

    OPEN

    LV89TE2

    OPEN

    3-52 CB

    OPEN

    3-89TE

    OPEN

    FOR 3-89T ISOLATOR OPERATION:

    BAY 3

    ICT

  • INTERLOCKS BAY 3

    &OPEN

    3-89T

    LV89T OPEN3-89TE

    OPERATION

    3-89TE

    INTERLOCK

    CONTACTOR

    3-89T

    OPEN

    LV89T

    OPEN

    FOR 3-89TE EARTH SWITCH OPERATION:

    3-89

    3-89A

    3-52CB

    3-89T

    BUS-2BB2-89E

    3-89E

    3-89AE

    3-89TE

    ICT

  • INTERLOCKS BAY3

    REMOTE

    3-52 CB

    LOCAL

    3-52 CB

    INTERLOCK

    CONTACTOR

    3-89 E

    CLOSE

    3-89 AE

    CLOSE

    &3-89E

    CLOSE

    CLOSE

    3-52 CBLOCALOPERATION

    3-89AE

    3-52 CB

    INTERLOCK

    CONTACTOR

    96-BB/BAY3

    RESET

    86-GB/BAY3

    RESET

    86-GA/BAY3

    RESET

    &

    86-GA/BAY3RESET

    86-GB/BAY3RESET

    RESET

    3-52 CBREMOTEOPERATION

    96-BB/BAY3

    3-89

    3-89A

    3-52CB

    3-89T

    BUS-2BB2-89E

    3-89E

    3-89AE

    3-89TE

    ICT

  • INTERLOCKS BUS EARTH SWITCH

    FOR BUS EARTH SWITCH OPERATION, ALL ISOLATORS

    CONNECTED TO CONCERNED BUS ARE TO BE OPENED.

    &

    3-89/ DIA1 OPEN

    BB289EOPERATION

    UP TO NO OF DIAS

    BB289E

    6-89/ DIA2 OPEN

    9-89/ DIA3 OPEN

    DIA N OPEN

    &

    1-89/ DIA1 OPEN

    BB189EOPERATION

    UP TO NO OF DIAS

    BB189E

    4-89/ DIA2 OPEN

    7-89/ DIA3 OPEN

    DIA N OPEN

    BB189E

    INTERLOCK

    CONTACTOR

    DIA N

    OPEN

    7-89/DIA3

    OPEN

    4-89/DIA2

    OPENUP TO NO OF DIAS

    BB289E

    INTERLOCK

    CONTACTOR

    DIA N

    OPEN

    9-89/DIA3

    OPEN

    6-89/DIA2

    OPENUP TO NO OF BAYS

    1-89/DIA1

    OPEN

    3-89/DIA1

    OPEN

  • ISOLATOR INTERLOCKS INTERLOCKS REQUIRED FOR CONCERNED ISOLATOR / EARTH SWITCH OPEN OR CLOSE

    BAY - 2

    BAY - 3

    O152 CBO189 EO189 AEOBB189 EISO1 - 891BAY - 1

    EQUIPMENT-4EQUIPMENT-3EQUIPMENT-2EQUIPMENT-1ISOLATOROPEN/CLOSES.NO

    ------O189O189 AES1 89 AE4---O152 CBO189 EO189 AEISO1 89 A3------O189O189 AES1 89 E2

    ------AUV RELAYO189 LES1 89 LE6---O252 CBO152 CBO189 LEISO1 89 L5

    ------O289 AO289 BES2 89 AE8---O252 CBO289 AEO289 BEISO2 89 A7

    ------O289 AO289 BES2 89 BE10---O252 CBO289 AEO289 BEISO2 89 B9

    O352 CBO389 EO389 AEOBB289 EISO3 89 11------O389O389 AES3 89 E12---O352 CBO389 EO389 AEISO3 89 A13------O389O389 AES3 89 AE14

    ------OLV89 TO389 TES3 89 TE16O352 CBO252 CBO389 TEOLV89 E2ISO3 89 T15

    NOTE: All Earth Switches in the Bay are towards Circuit Breaker side only. The Line and Transformer Earth Switches are towards Line & Transformer.

    O: OPENC: CLOSEA: ACTED

    BB189E : BUSBAR-1 EARTH SWITCH .BB289E : BUSBAR-2EARTH SWITCH . UV RELAY: UNDER VOLTAGE RELAY.

  • ISOLATOR & CB INTERLOCKS

    1-52CB&

    OPENOPEN

    OPEN

    OPERATION1-89LE

    2-52CB

    1-89L

    1-52CB

    &OPENOPEN

    OPENOPERATION1-89AE

    1-89E

    1-89A

    &BB189E OPEN

    OPEN1-89AE

    1-89E OPENOPEN

    1-89OPERATION

    1-52CB

    &1-89OPENOPEN

    1-89A1-89EOPERATION

    2-52CB&

    OPENOPEN

    OPENOPERATION2-89AE

    2-89BE2-89A

    OPEN

    &1-89 OPEN1-89A 1-89AEOPERATION

    &1-89LOPEN

    ACTEDU/V RLY

    1-89LEOPERATION

    &OPERATIONOPENOPEN

    OPENOPEN

    BB289E

    3-89AE

    3-89E3-52CB

    3-89

    3-52CB

    3-89AE&

    OPENOPEN

    OPEN3-89E

    OPERATION3-89A

    2-52CB&

    OPENOPEN

    OPEN

    3-52CB

    3-89TEOPERATION3-89T

    OPEN LV89E2

    OPENOPEN& 3-893-89A

    OPERATION3-89E

    OPENOPEN& 3-893-89A

    OPERATION3-89AE

    OPENOPEN&OPERATION3-89TE

    3-89T

    LV89T

    OPEN &OPEN2-89A

    2-89BOPERATION

    2-89AEOPENOPEN &2-89A2-89B

    OPERATION

    2-89BE

    2-52CB&

    OPENOPEN

    OPENOPERATION2-89AE

    2-89BE2-89B

    CLOSE &CLOSE1-89E

    1-89AE

    LOCAL CLOSE

    1-52CB

    CLOSE &CLOSE2-89AE

    2-89BE

    LOCAL CLOSE

    2-52CB

    CLOSE &CLOSE3-89E

    3-89AE

    LOCAL CLOSE

    3-52CB

    RESET &RESET86GR-A

    86GR-BREMOTE CLOSE

    1-52CBRESET96BB

    RESET &RESET

    86GR-A86GR-B

    REMOTE CLOSE

    2-52CB

    RESET &RESET86GR-A

    86GR-BREMOTE CLOSE

    3-52CBRESET96BB

    /ColorImageDict > /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /DownsampleGrayImages true /GrayImageDownsampleType /Bicubic /GrayImageResolution 300 /GrayImageDepth -1 /GrayImageDownsampleThreshold 1.50000 /EncodeGrayImages true /GrayImageFilter /DCTEncode /AutoFilterGrayImages true /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /DownsampleMonoImages true /MonoImageDownsampleType /Bicubic /MonoImageResolution 1200 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects false /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile () /PDFXOutputCondition () /PDFXRegistryName (http://www.color.org) /PDFXTrapped /Unknown