ISA Automation Conference Preheat APC-Rev.00
Transcript of ISA Automation Conference Preheat APC-Rev.00
Standards
Certification
Education & Training
Publishing
Conferences & Exhibits
ISA Automation Conference 2013- EMEA
(Dammam, Saudi Arabia) – December 10-12, 2013
Preheat APC Controller
Benefits Study
RAKAN M. BINTOHMAN Process Control Engineer
Saudi Aramco / Yanbu Refinery
ISA Automation Conference 2013- EMEA
(Dammam, Saudi Arabia) – December 10-12, 2013
ISA Automation Conference 2013- EMEA (Dammam, Saudi Arabia) – December 10-12, 2013
Agenda
Preheat Network Overview
Preheat APC Controller
Benefits
ISA Automation Conference 2013- EMEA (Dammam, Saudi Arabia) – December 10-12, 2013
Preheat Network Overview
V25
Surge
Drum
V2
Flash
Drum
H1A
H1B
E11
V8V1
To Flare
Fuel Gas
Crude
LPG
LSRN
HSRN
RCO
HDO
LDO
KERO
V11
V09
V6C & D
Desalters
V6A & B
Desalters
CDU APC
Controller
04CU
Stabilizer /
SplitterController
04SP
Crude Preheat
Optimizer
04PH
CVs
Product Qualities
PA / Feed
DHT Surge Drum
Heaters COT
Balance
MVs
Total Draws
Total PA
Heaters COT
MVs
Reflux
Reboiler
Stabilizer feed
LSR to ISOM
CVs
STAB BTM PCT
SPLT OH RVP, 90%
OH Pressure
Reflux/Feed
Surge Drums
ISA Automation Conference 2013- EMEA (Dammam, Saudi Arabia) – December 10-12, 2013
Preheat Network Overview
2 Identical Crude Preheat Trains (A/B)
V04- E1 Crude/ Naphtha PA
V04- E2 Crude/kerosene Draw
V04- E3 Crude/LDO Draw
V04- E4 Crude/1st LDO PA
V04- E5 Desalted crude/ 2nd LDO PA
V04- E6 Desalted crude/HDO Draw
V04- E7 Desalted crude/ Cold RCO
V04- E8 Desalted crude/ HDO PA
V04- E9 Desalted crude/ Hot RCO
ISA Automation Conference 2013- EMEA (Dammam, Saudi Arabia) – December 10-12, 2013
Preheat Network Overview
ISA Automation Conference 2013- EMEA (Dammam, Saudi Arabia) – December 10-12, 2013
Preheat Network Overview
ISA Automation Conference 2013- EMEA (Dammam, Saudi Arabia) – December 10-12, 2013
Preheat Network Overview
ISA Automation Conference 2013- EMEA (Dammam, Saudi Arabia) – December 10-12, 2013
Preheat Network Overview
ISA Automation Conference 2013- EMEA (Dammam, Saudi Arabia) – December 10-12, 2013
Preheat Network Overview
ISA Automation Conference 2013- EMEA (Dammam, Saudi Arabia) – December 10-12, 2013
Preheat APC Controller
DCS: Honeywell TDC 3000, APC: ProfitSuite R205.1
Controller covers the CDU Preheat Trains A and B for
series of exchangers E1…E9
Optimize (Balance) incremental heat duties between
exchangers in CDU Preheat Train A and B
Manipulating the crude flows and the hot stream flows
(PA and products draws) through the exchangers.
ISA Automation Conference 2013- EMEA (Dammam, Saudi Arabia) – December 10-12, 2013
Preheat APC Controller
Exchanger Toolkits
Custom profit toolkits
Calculate heat exchanger performance parameters
Used to calculate the several of the controlled
variables in the APC controller.
The toolkits calculate the incremental duty for the cold
and hot streams for each exchanger.
The relative incremental duties for a pair of parallel
exchangers are calculated in DCS.
ISA Automation Conference 2013- EMEA (Dammam, Saudi Arabia) – December 10-12, 2013
Preheat APC Controller
Exchanger Toolkits
INPUTS
Flow rate of adjusted stream m3/Hr
Inlet Temperature of Cold Stream Deg C.
Outlet Temperature of Cold Stream Deg C.
Inlet Temperature of Hot Stream Deg C.
Outlet Temperature of Hot Stream Deg C.
Heat Exchanger Area m2.
Adjusted stream average specific heat (CP) kCal/Kg.C
Adjusted stream average Specific Gravity SG.
OUTPUTS
Heat Exchanger Duty (Q) kCal/hr
Log Mean Temperature Difference (LMTD) Deg C.
Over all heat transfer coefficient (U) kCal/hr/m2/C
Incremental duty (dQ/dF) kCal/m3
ISA Automation Conference 2013- EMEA (Dammam, Saudi Arabia) – December 10-12, 2013
Preheat APC Controller
No. MV Tag name Description
1 04FDC231.SP Cold Crude Delta Flow before V2
2 04FDC036.SP Hot Crude Delta Flow after V2
3 04FDC222.SP Naphtha PA Delta Flow – E1
4 04FDC184.SP LDO Draw Delta Flow – E3
5 04FDC171.SP LDO PA Delta Flow – E4
6 04FDC165.SP LDO PA Delta Flow – E5
7 04FDC146.SP HDO Draw Delta Flow – E6
8 04FDC005.SP RCO Draw Delta Flow – E7/9
9 04FDC109.SP HDO PA Delta Flow – E8
ISA Automation Conference 2013- EMEA (Dammam, Saudi Arabia) – December 10-12, 2013
Preheat APC Controller
Total Pump around flow / Total Product Draw flow
Controlled by CDU APC controller (as MVs)
Individual stream in each train is cascaded to to the
stream master (Total) flow controller
FDC controllers are AM tags with no output
connection.
ISA Automation Conference 2013- EMEA (Dammam, Saudi Arabia) – December 10-12, 2013
Preheat APC Controller
04FLWBAL, Flow Balance Controller
AM CL program
Reads an operator-entered flow split %
Calculates & Writes bias values for 2 flow controllers
(04FLWBAL) adjusts the PID controller bias parameters
in DCS for parallel flow streams
ISA Automation Conference 2013- EMEA (Dammam, Saudi Arabia) – December 10-12, 2013
Preheat APC Controller
04FLWBAL, 04PH Controller
AM CL Program 04PRHTDF
Transfers the output signal of the MV (FDC) to the
appropriate flow split percentage
Target parameter of the existing custom flow balance
controller, 04FLWBAL
ISA Automation Conference 2013- EMEA (Dammam, Saudi Arabia) – December 10-12, 2013
Preheat Network Overview
ISA Automation Conference 2013- EMEA (Dammam, Saudi Arabia) – December 10-12, 2013
Preheat APC Controller
ISA Automation Conference 2013- EMEA (Dammam, Saudi Arabia) – December 10-12, 2013
Preheat APC Controller
No. CV Tag name Description
1 04QD001C.PV Delta dQ/dF Crude before V2
2 04QDE1H.PV Delta dQ/dF E1 - Naphtha
3 04QDE3H.PV Delta dQ/dF E3 - LDO
4 04QDE4H.PV Delta dQ/dF E4 – LDO PA
5 04TI173.PV Crude to Desalter Temperature – Train A
6 04TI168.PV Crude to Desalter Temperature – Train B
7 04QDE5H.PV Delta dQ/dF E5 – LDO PA
8 04QDE6H.PV Delta dQ/dF E6 – HDO Draw
9 04QDE79H.PV Delta dQ/dF E7/9 – RCO Draw
10 04QD002C.PV Delta dQ/dF Crude after V2
11 04QDE8H.PV Delta dQ/dF E8 – HDO PA
12 04TI008.PV Crude Heater A Inlet Temperature
13 04TX004.PV Crude Heater B Inlet Temperature
ISA Automation Conference 2013- EMEA (Dammam, Saudi Arabia) – December 10-12, 2013
Preheat APC Controller
No. CV Tag name Description
14 04FC222.OP Naphtha Circulation to E1 - A/B OP
15 04FC223.OP Naphtha Circulation to E1 - C/D OP
16 04FC163.OP LDO #2 Circulation to E5 - B OP
17 04FC165.OP LDO #2 Circulation to E5 - A OP
18 04FC169.OP LDO #1 Circulation to E4 - B OP
19 04FC171.OP LDO #1 Circulation to E4 - A OP
20 04FC109.OP HDO Circulation to E8 - A OP
21 04FC111.OP HDO Circulation to E8 - B OP
22 04TXH1OP.OP Sum of 04TC044G.OP and 04TC048G.OP
23 04TXH2OP.OP Sum of 04TC078G.OP and 04TC082G.OP
ISA Automation Conference 2013- EMEA (Dammam, Saudi Arabia) – December 10-12, 2013
Preheat APC Controller
ISA Automation Conference 2013- EMEA (Dammam, Saudi Arabia) – December 10-12, 2013
Preheat APC Controller
ISA Automation Conference 2013- EMEA (Dammam, Saudi Arabia) – December 10-12, 2013
Benefits Study
Preheat Controller was down for long time due to flow
& temperature measurements issues.
Preheat Controller was successfully re-commissioned
Prior commissioning, complete checks of
instrumentation, toolkits & interface points.
Conservative tuning of ramp rates & maximum
moves to avoid high fluctuations in heat exchangers
operations.
ISA Automation Conference 2013- EMEA (Dammam, Saudi Arabia) – December 10-12, 2013
Benefits Study
670
680
690
700
710
720
730
271
272
273
274
275
276
277
278
279
280
E9A5_OUT Deg C
E9B5_OUT Deg C
H1A TOTL M3/Hr
H1B TOTL M3/Hr
Preheat APC
OFF
Preheat APC
ON
Operations reduced
crude feed due to high
ambient temperature
and crude column
pressure
ISA Automation Conference 2013- EMEA (Dammam, Saudi Arabia) – December 10-12, 2013
Benefits Study
There are 2 elements of calculations to determine the
true value of APC optimizer:
1- Pre-heat energy recovery loss/gain
2- Overall fuel gas consumption
Following basis are used in estimating the benefit:
Fuel Gas Heating Value = 26,000 Btu/M3
Crude Heater Efficiency = 77% (based on actual
operation)
ISA Automation Conference 2013- EMEA (Dammam, Saudi Arabia) – December 10-12, 2013
Benefits Study
Table 1: Crude Preheat Recovery
Controller Status OFF ON
Train A Train B Train A Train B
Crude Feed, m3/hr 709 709 699 719
Temperature, oC 272.9 276.6 274.3 275.7
Heat MMBtu/Hr 428 434 425 438
Net Gain, MMBtu/Hr 1.0
ISA Automation Conference 2013- EMEA (Dammam, Saudi Arabia) – December 10-12, 2013
Benefits Study
670
675
680
685
690
695
700
705
710
715
1
1.2
1.4
1.6
1.8
2
2.2
04PI513
04PT001
H1A M3/HrPreheat APC
OFF
Preheat APC
ON
Operations
reduced crude
feed due to high
ambient
temperature
and crude
column
pressure
ISA Automation Conference 2013- EMEA (Dammam, Saudi Arabia) – December 10-12, 2013
Benefits Study
670
680
690
700
710
720
730
15000
16000
17000
18000
19000
20000
21000
TOT_FG
04HC036
04HC070
Preheat APC
OFF Preheat APC
ON
Operations reduced crude
feed due to high ambient
temperature and crude
column pressure
ISA Automation Conference 2013- EMEA (Dammam, Saudi Arabia) – December 10-12, 2013
Benefits Study
Collected data showed insignificant changes in fuel gas
composition and heaters flue gas oxygen contents
441 NM3/Hr = 11.5 MMBtu/hr = 581,773 U.S.$/Year.
ISA Automation Conference 2013- EMEA (Dammam, Saudi Arabia) – December 10-12, 2013
Conclusion
Preheat APC controller benefits can be described as
follow:
Operational benefits of reducing Heater A fuel gas
pressure.
Preheat recovery gain of 1MMBtu/Hr.
Overall Fuel gas consumption reduced by 441
NM3/Hr which is equivalent to savings of 11.5
MMBtu/Hr or > 0.5 MM $ / year