CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 1 of 142
INSTALLATION QUALIFICATION (IQ)
PROTOCOL / REPORT
CLIENT
DRUG INTERNATIONAL LIMITED(CEPHALOSPORIN)
TONGI, GAZIPUR
HVAC SYSTEM
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 2 of 142
PROTOCOL APPROVAL
Prepared By: Organization: Designation: Signature: Date:
Md. Fazlul Hoque Confidence Trade Limited Project Manager
Reviewed By: Organization: Designation: Signature: Date:
Nazmul AhsanDrug International
Ltd. Engineering In Charge
Md. Rafiqul IslamDrug International
Ltd.Factory in Charge,
Production
Approved by: Organization: Designation: Signature: Date:
Md. Amir HossainDrug International
Ltd. QA Manager
Authorized by: Organization: Designation: Signature: Date:
Md. Mahbubul IslamDrug International
Ltd. General Manager
REVISION HISTORY
Revision No: Revision Date Change History01 New
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 3 of 142
INDEX OF CONTENTS
1 INTRODUCTION 4
1.1. DESCRIPTION 41.2. OBJECTIVE 51.3. SCOPE 6
2 QUALIFICATION PARTICIPANTS DATA/SIGNATURES RECORD 6
3 STRATEGY OF THE QUALIFICATION 7
4 INSTALLATION QUALIFICATION TESTS 8
Test 1- Documentation Verification 8Test 2- Installation Verification 10
Mechanical Installation & Drawing check. Electrical Installation & Safety Check. Test 3- Equipments/Major components verification 13Test 4- Utilities verification 92Test 5- Control system PLC software 99Test 6- Oparating & Maintenance (O & M) Manual Check 120
5 Summary of Test Performed 122
6 Final Report 123
7 List of Deviations and/or Further actions 124
8 List of Appendices 125
9 Approvals 126
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 4 of 142
1 Introduction
1.1.DESCRIPTIONThe purpose of this IQ is to provide documented evidence to demonstrate that components of HVAC in the Production Area and Dispensing Area of Cephalosporin general facility are installed according to GMP Grade, the HVAC system consists of 34 sub-systems FCU-G01, FCU-G02, FCU-G03, FCU-G04, FCU-G05, FCU-G06, FCU-G07, FCU-G08, FCU-G09 and FCU-G10 for ground floor, FCU-101, FCU-101.1, FCU-101.2, FCU-102, FCU-103, FCU-108, AHU-102, AHU-103, AHU-104, AHU-105, AHU-106, AHU-107, AHU-109 and FAHU-01 for first floor, FCU-201, FCU-202, FCU-203, AHU-201, AHU-202, AHU-203, AHU-204, AHU-205, AHU-206 and FAHU-02 for second floor.
AHU-102 is connected to room no. 204. The area is Grade C.
AHU-103 is connected to room no. 211, 212 and 217. The area is Grade D.
AHU-104 is connected to room no. 210, 213, 214, 215 and 216. The area is Grade D.
AHU-105 is connected to room no. 218, 219, 220 and 221. The area is Grade E.
AHU-106 is connected to room no. 222 and 223. The area is Grade D.
AHU-107 is connected to room no. 225, 230, 232, 233, 234 and 235. The area is Grade D.
AHU-109 is connected to room no. 228, 236, 237 and 238. The area is Grade D.
AHU-201 is connected to room no. 338, 336, 339 and 337. The area is Grade D.
AHU-202 is connected to room no. 334 and 322. The area is Grade D.
AHU-203 is connected to room no. 329, 328 and 327. The area is Grade B.
AHU-204 is connected to room no. 323, 324, 325, 326, 330, 331, 332, 333 and 340. The area is Grade C.
AHU-205 is connected to room no. 311, 312, 313, 314, 318, 319, 320 and 321. The area is Grade D.
AHU-206 is connected to room no. 315, 316 and 317. The area is Grade E.
FCU-G01 is connected to room no. 111. The area is Grade E.
FCU-G02 is connected to room no.113. The area is Grade E.
FCU-G03 is connected to room no. 104, 105 and 106. The area is Grade E.
FCU-G04 is connected to room no. 114 and 116. The area is Grade E.
FCU-G05 is connected to room no. 115, 117 and 121. The area is Grade E.
FCU-G06 is connected to room no. 122. The area is Grade E.
FCU-G07 is connected to room no. 124, 125, 126 and 127. The area is Grade E.
FCU-G08 is connected to room no. 131, 132 and 133. The area is Grade E.
FCU-G09 is connected to room no. 130. The area is Grade E.
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 5 of 142
FCU-G10 is connected to room no. 102. The area is Grade E.FCU-101 is connected to room no. 207. The area is Grade E.FCU-101.1 is connected to room no. 205. The area is Grade E.FCU-101.2 is connected to room no. 205. The area is Grade E.
FCU-102 is connected to room no. 202. The area is Grade E.
FCU-103 is connected to room no. 202. The area is Grade E.
FCU-108 is connected to room no. 226, 227, 229 and 231. The area is Grade E.
FCU-201 is connected to room no. 307. The area is Grade E.
FCU-202 is connected to room no. 302 and 304. The area is Grade E.
FCU-203 is connected to room no. 302. The area is Grade E.
FAHU-01 and FAHU-02 are for fresh air supply to above mentioned AHUs.
All zones required to maintain temperature 23±1°C. Relative Humidity requirement is 35±5% for production area
except under the area of AHU 101,103, 105, 108, 201-202, 204-206, FCU G01-G10, 101-103, and 201-203 where
Relative Humidity uncontrolled.
1.2.OBJECTIVE
The objectives of the Installation Qualification for these systems are: -
To verify that design qualification work has been performed and documented. To confirm that the HVAC system specifications meet the User Requirements. To determine whether the components of the system conform to the manufacturer’s technical
description and installation requirements. To determine whether the HVAC system complies with relevant requirements of current Good
Manufacturing Practice for Pharmaceuticals. To provide a record of principal features of the HVAC systems and components as currently
installed. To determine whether there is sufficient information available to enable the HVAC systems to be
installed and maintained safely, effectively and consistently.
1.3.SCOPE
This Installation Qualification Protocol applies to:
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 6 of 142
Clean room qualification, including:
Rooms Air handling’s units Fan Coil units Ducts Filters Associated utilities
The scope of this study does not include the qualification of any computerized control system.
2 QUALIFICATION PARTICIPANTS DATA/SIGNATURES RECORD
In the table below enter details of the people involved in the execution of the Installation Qualification:
NAME POSITION / COMPANY
SIGNATURE INITIAL DATE
3 STRATEGY OF THE QUALIFICATION
The designated qualification team will carry out the verification.
To check that installation corresponds with supplier specifications several tests will be carried out, and each
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 7 of 142
one of the tests will consist in the following parts:
a) OBJECTIVE: It defines the purpose of the test.
b) METHODOLOGY: It defines the procedure to follow in test execution.
c) ACCEPTANCE CRITERIA: It details the expected results that are considered correct.
d) VERIFICATION REGISTER: It details the verification to be done, checking the grade of compliance with the acceptance criteria.
The results obtained are registered as follows:
YES NOTThe result of the verification is considered in accordance with the acceptance criteria.
The result of the verification disagrees with the acceptance criteria.
e) CONCLUSIONS: Once the verifications of the test are made, the result of the test will be consigned as well as the appropriate comments
The result of the test could be:
PASS FAIL When all verification carried out have been considered in accordance with the acceptance criteria, or if non-conformities found have been solved in time or considered as non-critical.
When any verification does not fulfil the acceptance criteria because critical deviations are opened and it has not been possible to solve them in time. In this case, once the non-conformity has been solved, the verification must be repeated and the new result registered.
f) OBSERVATIONS: In these part it will be noted any outstanding point to clarify any decision or just events during qualification process. It will be detailed when critical data should be registered.
People that carry out the verification or review final data must put their signature and date where required.Any deviation or non-conformity found during verification process would be registered and technical personnel in charge will carry out a revision and make appropriate comments, in order to classify the deviation according to the following categories:
C (Critical): NC (Non-critical):
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 8 of 142
It can affect to the product quality and, therefore it must be corrected. After correction, it must be done again a verification to demonstrate that it has been solved adequately
It does not affect the product quality and it can remain without corrective action or with partial correction.
Deviations will be registered following the model attached in ANNEX I.This qualification is completed with an Installation Qualification Final Report
4 INSTALLATION QUALIFICATION TESTS
Test 1- Documentation Verification
a) OBJECTIVE
To verify that the related technical and functional specifications, ”as built” drawings and diagrams, materials and certificates of materials, instrumentations list and operating and maintenance manuals of the HVAC Sys-tem is available.
b) METHODOLOGY
The verification matrix will be completed with the name and reference of the documentation (handbooks, certifications, specifications…) provided by the supplier and identifying the archive location. The performance of the test will also ensure that the information contained in the documentation cover all necessary aspects.
c) ACCEPTANCE CRITERIA
Technical information indicated is available and it covers all necessary aspects. Documentation is correct, completed, and correctly filled.
d) VERIFICATION REGISTER:
Documentation Review Verification Matrix. HVAC SYSTEMItem Type of Document Available Reference /
Comments
1. As built schematic diagram of HVAC system Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 9 of 142
2. As built Duct Layout Yes / No
3 As built piping Layout Yes / No
4. Technical and functional specification Yes / No
5. List of components and tags Yes / No
6. Certificates for HEPA filter integrity and efficiency Yes / No
7. Operating and Maintenance manual of all HVAC components Yes / No
OBSERVATIONS:
Test final result PASS FAILPerformed by Signature Date
Checked by Signature Date
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 10 of 142
Test 2- Installation Verification
a) OBJECTIVE:
Provide documentary evidence that HVAC system have been installed and are correctly identified in accordance with existent installation drawings (As built diagrams and schemes).
b) METHODOLOGY
1. Obtain a copy of the last version of “as built” drawings.2. Indicate that it is a “Validation Copy” as well as the reference and version of the present
protocol and the date and signature of the technician responsible.3. “As built” drawings will be registered in test validation matrix.4. Check the installation to verify that the layout corresponds to “as built” drawings.
The following color system will be used during the check process:
Green : Parts that in installation correspond with As Built P&IDs drawing Yellow : Elements installed, but they are not in As Built P&ID drawing. Orange : Elements in As Built P&ID drawing but not installed Blue : Parts of the installation not checked (Explain the reason because they have not been checked)
5. Once the verification has been finished, the technician/s that have perform the test must write in the “as built” drawings “Verified in Installation Qualification”, the date and signature.
6. The “as built” drawings will be attached to this protocol.
c) ACCEPTANCE CRITERIA:
“As built” drawings reflect the real the installation exactly (all disagreement between drawings and installation must be justified).
The components are identified in “as built” P&ID drawings and labeled using identifications codes (Tags) in the installation.
The security mechanisms are installed correctly and in adequate direction The instruments are correctly installed and They are accessible and easily to read The access for operations and maintenance works is easy.
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 11 of 142
d) VERIFICATION REGISTER
Register Verification MatrixAs Built drawings used in installation
verificationDRG. NO. REV. NO. Date Result
HVAC Drawing List & Abbreviations A.C-01 01 19-02-14 Yes / No
HVAC Symbols A.C-02 01 19-02-14 Yes / No
Air conditioning Ducting Layout of Gr. floor A.C-03 01 19-02-14 Yes / No
Air conditioning Ducting Layout of 1st floor A.C-04 01 19-02-14 Yes / No
Air conditioning Ducting Layout of 2nd floor A.C-05 01 19-02-14 Yes / No
Chilled water piping Layout of Gr. floor A.C-06 01 19-02-14 Yes / No
Chilled water piping Layout of 1st floor A.C-07 01 19-02-14 Yes / No
Chilled water piping Layout of 2nd floor A.C-08 01 19-02-14 Yes / No
Chilled water piping Layout of Rooftop A.C-09 01 19-02-14 Yes / No
Drain Water Pipe Layout Ground Floor A.C-11 01 19-02-14 Yes / No
Drain Water Pipe Layout 1st Floor A.C-12 01 19-02-14 Yes / No
Drain Water Pipe Layout 2nd Floor A.C-13 01 19-02-14 Yes / No
Drain Water Pipe Layout 3rd Floor A.C-14 01 19-02-14 Yes / No
HVAC System schematic diagram of Gr. floor A.C-15 01 19-02-14 Yes / No
HVAC System schematic diagram of Gr. floor A.C-16 01 19-02-14 Yes / No
HVAC System schematic diagram of Gr. floor A.C-17 01 19-02-14 Yes / No
HVAC System schematic diagram of Gr. floor A.C-18 01 19-02-14 Yes / No
HVAC System schematic diagram of Gr. floor A.C-19 01 19-02-14 Yes / No
HVAC System schematic diagram of Gr. floor A.C-20 01 19-02-14 Yes / No
HVAC System schematic diagram of Gr. floor A.C-21 01 19-02-14 Yes / No
HVAC System schematic diagram of Gr. floor A.C-22 01 19-02-14 Yes / No
HVAC System schematic diagram of Gr. floor A.C-23 01 19-02-14 Yes / No
HVAC System schematic diagram of Gr. floor A.C-24 01 19-02-14 Yes / No
HVAC System schematic diagram of 1st floor A.C-25 01 19-02-14 Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 12 of 142
Register Verification MatrixAs Built drawings used in installation
verificationDRG. NO. REV. NO. Date Result
HVAC System schematic diagram of 1st floor A.C-26 01 19-02-14 Yes / No
HVAC System schematic diagram of 1st floor A.C-27 01 19-02-14 Yes / No
HVAC System schematic diagram of 1st floor A.C-28 01 19-02-14 Yes / No
HVAC System schematic diagram of 1st floor A.C-29 01 19-02-14 Yes / No
HVAC System schematic diagram of 1st floor A.C-30 01 19-02-14 Yes / No
HVAC System schematic diagram of 1st floor A.C-31 01 19-02-14 Yes / No
HVAC System schematic diagram of 1st floor A.C-32 01 19-02-14 Yes / No
HVAC System schematic diagram of 1st floor A.C-33 01 19-02-14 Yes / No
HVAC System schematic diagram of 1st floor A.C-34 01 19-02-14 Yes / No
HVAC System schematic diagram of 1st floor A.C-35 01 19-02-14 Yes / No
HVAC System schematic diagram of 2nd floor A.C-36 01 19-02-14 Yes / No
HVAC System schematic diagram of 2nd floor A.C-37 01 19-02-14 Yes / No
HVAC System schematic diagram of 2nd floor A.C-38 01 19-02-14 Yes / No
HVAC System schematic diagram of 2nd floor A.C-39 01 19-02-14 Yes / No
HVAC System schematic diagram of 2nd floor A.C-40 01 19-02-14 Yes / No
HVAC System schematic diagram of 2nd floor A.C-41 01 19-02-14 Yes / No
HVAC System schematic diagram of 2nd floor A.C-42 01 19-02-14 Yes / No
HVAC System schematic diagram of 2nd floor A.C-43 01 19-02-14 Yes / No
OBSERVATIONS:
Test final result PASS FAILPerformed by Signature Date
Checked by Signature Date
Test 3- Equipments/Major components verification
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 13 of 142
a) OBJECTIVE Characterize the major components of the installation Air Handling Units, terminal HEPA system, exhaust fans, Air grills and diffusers, verifying that the equipment installed corresponds with existing technical documentation, and recording the following information for each one: designation, brand and model.
b) METHODOLOGY
A visual inspection is carried out of the characteristics plate from each major equipment and auxiliary equipment. The code of equipment, manufacturer, model, and/or other relevant characteristics must be registered.This information obtained from field inspection should be contrasted with technical documentation.Signature of the personnel that performs the check, date, and conformity between equipment installed and technical description should be registered.The result of the verification is detailed on the register sheet as a checklist.
c) ACCEPTANCE CRITERIA
Characteristics of major equipment installed correspond with characteristics described in technical documentation.
d) VERIFICATION MATRIX:
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 14 of 142
Equipments/Major components verificationAir Handling Unit verification
AHU-102EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
AHU-102(CENAHU-01)
Manufacturer ACSON
Yes / No
Model ADM2-0407
Serial number 1204071
Flow 1500 CFM
Dimension (LxWxH) 2550x1150x930 mm
MIXING SECTION
02 Nos. of Manual dampers (Size 410 x 980 mm) for return and FAI are correctly installed. Yes / No
- Mixing system allows keeping dampers at the selected position (open/close). - Position indicator correctly shows open or close position at any time.
Yes / No
Section verification: Check on adequate assembling and not damages. Yes / No
FILTRATION SECTION Pre filter (G-4)
is correctly installed, with no damages and perfectly assembled and fitted.Efficiency: 50%Filter media: SyntheticFilter size: 24”x24” (01 nos.) 12”x24” (01 nos.)
Yes / No
SECONDARY FILTERS
Cartridge Filter (F9)
Is correctly installed, with no damages and perfectly assembled and fitted.Efficiency 95%Filter media: Ultra-fine fiberglass Filter size: 24”x24” (01 nos.) 12”x24” (01 nos.)
Yes / No
COOLING SECTION Cooling Coil Capacity: 15.278 KW Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 15 of 142
Equipments/Major components verificationAir Handling Unit verification
AHU-102EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
Check water circuit is correctly installed and connected to the main water circuit.
Section verification: Check on adequate assembling and not damages
SUPPLY FAN SECTION
Fan Manufacturer: Kruger Engineering Pte. Ltd.
Yes / No
Model & Potency: Supply:BDB225CM (2.2 KW)
Fan Duty: Supply: 1500 CFM
Fan Type: Backward Curved Centrifugal
Belt Type: V belt
Motor Manufacturer: Teco Elec. & Mech. Ptv. Ltd.
Section verification: Check on adequate assembling and not damages. Yes / No
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that
assures a suitable assembling. Yes / No
Equipments/Major components verificationAir Handling Unit verification
AHU-103
EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
AHU-102(BENAHU-02)
Manufacturer ACSON
Yes / No
Model ADM2-0713
Serial number 1204072
Flow 5000 CFM
Dimension (LxWxH) 2850x1750x1230 mm
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 16 of 142
Equipments/Major components verificationAir Handling Unit verification
AHU-103
EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
MIXING SECTION
02 Nos. of Manual dampers (Size 410 x 1580 mm) for return and FAI are correctly installed. Yes / No
- Mixing system allows keeping dampers at the selected position (open/close). - Position indicator correctly shows open or close position at any time.
Yes / No
Section verification: Check on adequate assembling and not damages. Yes / No
FILTRATION SECTION Pre filter (G-4)
is correctly installed, with no damages and perfectly assembled and fitted.Efficiency 50%Filter media: Synthetic Filter size: 24”x24” (02 nos.)12”x24” (03 nos.)
Yes / No
SECONDARY FILTERS
Cartridge Filter (F9)
Is correctly installed, with no damages and perfectly assembled and fitted.Efficiency 95%Filter media: Ultra-fine fibreglass Filter size: 24”x24” (02 nos.) 12”x24” (03 nos.)
Yes / No
COOLING SECTION
Cooling Coil Capacity: 46.171 KW
Yes / NoCheck water circuit is correctly installed and connected to the main water circuit.Section verification: Check on adequate assembling and not damages
SUPPLY FAN SECTION
Fan Manufacturer: Kruger Engineering Pte. Ltd. Yes / No
Model & Potency: Supply: BDB400CM (5.5KW)
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 17 of 142
Equipments/Major components verificationAir Handling Unit verification
AHU-103
EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
Fan Duty: Supply: 5000 CFM
Fan Type: Backward Curved Centrifugal
Belt Type: V belt
Motor Manufacturer: Teco Elec. & Mech. Ptv. Ltd.
Section verification: Check on adequate assembling and not damages. Yes / No
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling.
Yes / No
Equipments/Major components verificationAir Handling Unit verification
AHU-104EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
AHU-103(BENAHU-03)
Manufacturer ACSON Yes / No
Model ADM2-0713
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 18 of 142
Equipments/Major components verificationAir Handling Unit verification
AHU-104EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
Serial number 1204073
Flow 4000 CFM
Dimension (LxWxH) 2850x1750x1230 mm
MIXING SECTION
02 Nos. of Manual dampers (Size 410 x 1580 mm) for return and FAI are correctly installed. Yes / No
- Mixing system allows keeping dampers at the selected position (open/close). - Position indicator correctly shows open or close position at any time.
Yes / No
Section verification: Check on adequate assembling and not damages. Yes / No
FILTRATION SECTION Pre filter (G-4)
is correctly installed, with no damages and perfectly assembled and fitted.Efficiency 50%Filter media: SyntheticFilter size: 24”x24” (02 nos.) 12”x24” (03 nos.)
Yes / No
SECONDARY FILTERS
Cartridge Filter (F9)
Is correctly installed, with no damages and perfectly assembled and fitted.Efficiency 95%Filter media: Ultra-fine fiberglassFiltersize: 24”x24” (02 nos.) 12”x24” (03 nos.)
Yes / No
COOLING SECTION
Cooling Coil Capacity: 49.875 KW Yes / NoCheck water circuit is correctly installed and
connected to the main water circuit.Section verification: Check on adequate assembling and not damages
Fan Manufacturer: Kruger Engineering Pte. Ltd. Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 19 of 142
Equipments/Major components verificationAir Handling Unit verification
AHU-104EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
SUPPLY FAN SECTION
Model & Potency: Supply:BDB400CM (5.5 KW)
Fan Duty: Supply: 4000 CFM
Fan Type: Backward Curved Centrifugal
Belt Type: V belt
Motor Manufacturer: Teco Elec. & Mech. Ptv. Ltd.
Section verification: Check on adequate assembling and not damages. Yes / No
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling.
Yes / No
Equipments/Major components verificationAir Handling Unit verification
AHU-105
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 20 of 142
EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
AHU-104(BENAHU-04)
Manufacturer ACSON
Yes / No
Model ADM2-0713
Serial number 1204074
Flow 4000 CFM
Dimension (LxWxH) 2450x1750x1230 mm
MIXING SECTION
02 Nos. of Manual dampers (Size 410x 1580 mm) for return and FAI are correctly installed. Yes / No
- Mixing system allows keeping dampers at the selected position (open/close). - Position indicator correctly shows open or close position at any time.
Yes / No
Section verification: Check on adequate assembling and not damages. Yes / No
FILTRATION SECTION Pre filter (G-4)
is correctly installed, with no damages and perfectly assembled and fitted.Efficiency 50%Filter media: SyntheticFilter size: 24”x24” (02 nos.) 12”x24” (03 nos.)
Yes / No
COOLING SECTION
Cooling Coil Capacity: 61.223 KW Yes / NoCheck water circuit is correctly installed and
connected to the main water circuit.Section verification: Check on adequate assembling and not damages
SUPPLY FAN SECTION
Fan Manufacturer: Kruger Engineering Pte. Ltd.
Yes / No
Model & Potency: Supply: BDB400CM (2.2KW)
Fan Duty: Supply: 4000 CFM
Fan Type: Backward Curved Centrifugal
Belt Type: V belt
Motor Manufacturer: Teco Elec. & Mech. Ptv. Ltd
Section verification: Check on adequate assembling and not damages. Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 21 of 142
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling. Yes / No
Equipments/Major components verificationAir Handling Unit verification
AHU-106EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
AHU-105(BENAHU-05)
Manufacturer ACSON
Yes / NoModel ADM2-0410
Serial number 1204075
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 22 of 142
Equipments/Major components verificationAir Handling Unit verification
AHU-106EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
Flow 2200 CFM
Dimension (LxWxH) 2650x1450x930 mm
MIXING SECTION
02 Nos. of Manual dampers (Size 410 x 1280 mm) for return and FAI are correctly installed. Yes / No
- Mixing system allows keeping dampers at the selected position (open/close). - Position indicator correctly shows open or close position at any time.
Yes / No
Section verification: Check on adequate assembling and not damages. Yes / No
FILTRATION SECTION Pre filter (G-4)
correctly installed, with no damages and perfectly assembled and fitted.Efficiency 50%Filter media: SyntheticFilter size: 24”x24” (02 nos.)
Yes / No
SECONDARY FILTERS
Cartridge Filter (F9)
Is correctly installed, with no damages and perfectly assembled and fitted.Efficiency 95%Filter media: Ultra-fine fiberglass Filter size: 24”x24” (02 nos.)
Yes / No
COOLING SECTION
Cooling Coil Capacity: 26.364 KW Yes / NoCheck water circuit is correctly installed and
connected to the main water circuit.Section verification: Check on adequate assembling and not damages
Fan Manufacturer: Kruger Engineering Pte. Ltd. Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 23 of 142
Equipments/Major components verificationAir Handling Unit verification
AHU-106EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
SUPPLY FAN SECTION
Model & Potency: Supply: BDB280CM (3.0KW)
Fan Duty: Supply: 2200 CFM
Fan Type: Backward Curved Centrifugal
Belt Type: V belt
Motor Manufacturer: Teco Elec. & Mech. Ptv. Ltd
Section verification: Check on adequate assembling and not damages. Yes / No
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling. Yes / No
Equipments/Major components verificationAir Handling Unit verification
AHU-107EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
AHU-106(BENAHU-06)
Manufacturer ACSON Yes / No
Model ADM2-0413
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 24 of 142
Equipments/Major components verificationAir Handling Unit verification
AHU-107EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
Serial number 1204076
Flow 3000 CFM
Dimension (LxWxH) 2650x1750x930 mm
MIXING SECTION
02 Nos. of Manual dampers (Size 410 x 1580 mm) for return and FAI are correctly installed. Yes / No
- Mixing system allows keeping dampers at the selected position (open/close). - Position indicator correctly shows open or close position at any time.
Yes / No
Section verification: Check on adequate assembling and not damages. Yes / No
FILTRATION SECTION Pre filter (G-4)
is correctly installed, with no damages and perfectly assembled and fitted.Efficiency 50%Filter media: SyntheticFilter size: 24”x24” (02 nos.) 12”x24” (01 no.)
Yes / No
COOLING SECTION
Cooling Coil Capacity: 37.761 KW
Yes / NoCheck water circuit is correctly installed and connected to the main water circuit.Section verification: Check on adequate assembling and not damages
Section verification: Check on adequate assembling and not damages
SUPPLY FAN SECTION
Fan Manufacturer: Kruger Engineering Pte. Ltd.
Yes / NoModel & Potency: Supply:BDB315CM(4.0 KW)
Fan Duty: Supply: 3000 CFM
Fan Type: Backward Curved Centrifugal
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 25 of 142
Equipments/Major components verificationAir Handling Unit verification
AHU-107EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
Belt Type: V belt
Motor Manufacturer: Teco Elec. & Mech. Ptv. Ltd.
Section verification: Check on adequate assembling and not damages. Yes / No
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling. Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 26 of 142
Equipments/Major components verificationAir Handling Unit verification
AHU-109EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
AHU-107(BENAHU-07)
Manufacturer ACSON
Yes / No
Model ADM2-0413
Serial number 1204077
Flow 3000 CFM
Dimension (LxWxH) 2650x1750x930 mm
MIXING SECTION
02 Nos. of Manual dampers (Size 410 x 1580 mm) for return and FAI are correctly installed. Yes / No
- Mixing system allows keeping dampers at the selected position (open/close). - Position indicator correctly shows open or close position at any time.
Yes / No
Section verification: Check on adequate assembling and not damages. Yes / No
FILTRATION SECTION Pre filter (G-4)
is correctly installed, with no damages and perfectly assembled and fitted.Efficiency 50%Filter media: SyntheticFilter size: 24”x24” (02 nos.) 12”x24” (01 no.)
Yes / No
SECONDARY FILTERS
Cartridge Filter (F9)
Is correctly installed, with no damages and perfectly assembled and fitted.Efficiency 95%Filter media: Ultra-fine fiberglassFilter size: 24”x24” (02 nos.) 12”x24” (01 no.)
Yes / No
COOLING SECTION
Cooling Coil Capacity: 37.195 KW
Yes / NoCheck water circuit is correctly installed and connected to the main water circuit.
Section verification: Check on adequate assembling and not damages
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 27 of 142
Equipments/Major components verificationAir Handling Unit verification
AHU-109EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
SUPPLY FAN SECTION
Fan Manufacturer: Kruger Engineering Pte. Ltd.
Yes / No
Model & Potency: Supply: BDB315CM (4.0KW)
Fan Duty: Supply: 3000 CFM
Fan Type: Backward Curved Centrifugal
Belt Type: V belt
Motor Manufacturer: Teco Elec. & Mech. Ptv. Ltd.
Section verification: Check on adequate assembling and not damages. Yes / No
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling. Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 28 of 142
Equipments/Major components verificationAir Handling Unit verification
AHU-201EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
AHU-201(CENAHU-08)
Manufacturer ACSON
Yes / No
Model ADM2-0713
Serial number 1204078
Flow 5500 CFM
Dimension (LxWxH) 3500x1750x1230 mm
MIXING SECTION
02 Nos. of Manual dampers (Size 410 x 1580 mm) for return and FAI are correctly installed. Yes / No
- Mixing system allows keeping dampers at the selected position (open/close). - Position indicator correctly shows open or close position at any time.
Yes / No
Section verification: Check on adequate assembling and not damages. Yes / No
FILTRATION SECTION Pre filter (G-4)
is correctly installed, with no damages and perfectly assembled and fitted.Efficiency 50%Filter media: SyntheticFilter size: 24”x24” (02 nos.) 12”x24” (03 nos.)
Yes / No
COOLING SECTION
Cooling Coil Capacity: 60.612 KW
Yes / NoCheck water circuit is correctly installed and connected to the main water circuit.
Section verification: Check on adequate assembling and not damages
Section verification: Check on adequate assembling and not damages
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 29 of 142
Equipments/Major components verificationAir Handling Unit verification
AHU-201EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
FILTRATION SECTION Pre filter (G-4)
is correctly installed, with no damages and perfectly assembled and fitted.Efficiency 50%Filter media: SyntheticFilter size: 24”x24” (02 nos.) 12”x24” (03 nos.)
Yes / No
SECONDARY FILTERS
Cartridge Filter (F9)
Is correctly installed, with no damages and perfectly assembled and fitted.Efficiency 95%Filter media: Ultra-fine fiberglassFilter size: 24”x24” (02 nos.) 12”x24” (03 nos.)
Yes / No
SUPPLY FAN SECTION
Fan Manufacturer: Kruger Engineering Pte. Ltd.
Yes / No
Model & Potency: Supply:BDB400CM (7.5 KW)
Fan Duty: Supply: 5500 CFM
Fan Type: Backward Curved Centrifugal
Belt Type: V belt
Motor Manufacturer: Teco Elec. & Mech. Ptv. Ltd.
Section verification: Check on adequate assembling and not damages. Yes / No
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling. Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 30 of 142
Equipments/Major components verificationAir Handling Unit verification
AHU-202EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
AHU-202(BENAHU-09)
Manufacturer ACSON
Yes / No
Model ADM2-0410
Serial number 1204079
Flow 2500 CFM
Dimension (LxWxH) 3300x1450x930 mm
MIXING SECTION
02 Nos. of Manual dampers (Size 410 x 1280 mm) for return and FAI are correctly installed. Yes / No
- Mixing system allows keeping dampers at the selected position (open/close). - Position indicator correctly shows open or close position at any time.
Yes / No
Section verification: Check on adequate assembling and not damages. Yes / No
FILTRATION SECTION Pre filter (G-4)
is correctly installed, with no damages and perfectly assembled and fitted.Efficiency 50%Filter media: SyntheticFilter size: 24”x24” (08 nos.)
Yes / No
COOLING SECTION
Cooling Coil Capacity: 45.370 KW
Yes / NoCheck water circuit is correctly installed and connected to the main water circuit.Section verification: Check on adequate assembling and not damages
FILTRATION SECTION Pre filter (G-4)
is correctly installed, with no damages and perfectly assembled and fitted.Efficiency 50%Filter media: SyntheticFilter size: 24”x24” (02 nos.)
Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 31 of 142
Equipments/Major components verificationAir Handling Unit verification
AHU-202EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
SECONDARY FILTERS
Cartridge Filter (F9)
Is correctly installed, with no damages and perfectly assembled and fitted.Efficiency 95%Filter media: Ultra-fine fiberglassFilter size: 24”x24” (02 nos.)
Yes / No
SUPPLY FAN SECTION
Fan Manufacturer: Kruger Engineering Pte. Ltd.
Yes / No
Model & Potency: Supply: BDB280CM(4.0 KW)
Fan Duty: Supply: 2500 CFM
Fan Type: Backward Curved Centrifugal
Belt Type: V belt
Motor Manufacturer: Teco Elec. & Mech. Ptv. Ltd.
Section verification: Check on adequate assembling and not damages. Yes / No
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling. Yes / No
Equipments/Major components verificationAir Handling Unit verification
AHU-203EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
AHU-203(CENAHU-10)
Manufacturer ACSON Yes / No
Model ADM2-1315
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 32 of 142
Equipments/Major components verificationAir Handling Unit verification
AHU-203EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
Serial number 1204080
Flow 10000 CFM
Dimension (LxWxH) 4300x1950x1830 mm
MIXING SECTION
02 Nos. of Manual dampers (Size 410 x 1780 mm) for return and FAI are correctly installed. Yes / No
- Mixing system allows keeping dampers at the selected position (open/close). - Position indicator correctly shows open or close position at any time.
Yes / No
Section verification: Check on adequate assembling and not damages. Yes / No
FILTRATION SECTION Pre filter (G-4)
is correctly installed, with no damages and perfectly assembled and fitted.Efficiency 50%Filter media: SyntheticFilter size: 24”x24” (06 nos.) 12”x24” (03 nos.)
Yes / No
COOLING SECTION
Cooling Coil Capacity: 89.807 KW
Yes / NoCheck water circuit is correctly installed and connected to the main water circuit.Section verification: Check on adequate assembling and not damages
FILTRATION SECTION Pre filter (G-4)
is correctly installed, with no damages and perfectly assembled and fitted.Efficiency 50%Filter media: SyntheticFilter size: 24”x24” (06 nos.) 12”x24” (03 nos.)
Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 33 of 142
Equipments/Major components verificationAir Handling Unit verification
AHU-203EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
SECONDARY FILTERS
Cartridge Filter (F9)
Is correctly installed, with no damages and perfectly assembled and fitted.Efficiency 95%Filter media: Ultra-fine fiberglassFilter size:24”x24” (06 nos.) 12”x24” (03 nos.)
Yes / No
SUPPLY AND RETURN FAN
SECTION
Fan Manufacturer: Kruger Engineering Pte. Ltd.
Yes / No
Model & Potency: Supply: BDB560CM (15 KW)
Fan Duty: Supply: 10000 CFM
Fan Type: Backward Curved Centrifugal
Belt Type: V belt
Motor Manufacturer: Teco Elec. & Mech. Ptv. Ltd.
Section verification: Check on adequate assembling and not damages. Yes / No
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling. Yes / No
Equipments/Major components verificationAir Handling Unit verification
AHU-204EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
AHU-204(CENAHU-11)
Manufacturer ACSON Yes / No
Model ADM2-0713
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 34 of 142
Equipments/Major components verificationAir Handling Unit verification
AHU-204EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
Serial number 1204081
Flow 6000 CFM
Dimension (LxWxH) 3500x1750x1230 mm
MIXING SECTION
02 Nos. of Manual dampers (Size 410 x 1580 mm) for return and FAI are correctly installed. Yes / No
- Mixing system allows keeping dampers at the selected position (open/close). - Position indicator correctly shows open or close position at any time.
Yes / No
Section verification: Check on adequate assembling and not damages. Yes / No
FILTRATION SECTION Pre filter (G-4)
is correctly installed, with no damages and perfectly assembled and fitted.Efficiency 50%Filter media: SyntheticFilter size: 24”x24” (02 nos.) 12”x24” (03 nos.)
Yes / No
COOLING SECTION
Cooling Coil Capacity: 70.179 KW
Yes / NoCheck water circuit is correctly installed and connected to the main water circuit.
Section verification: Check on adequate assembling and not damages
FILTRATION SECTION Pre filter (G-4)
is correctly installed, with no damages and perfectly assembled and fitted.Efficiency 50%Filter media: SyntheticFilter size:24”x24” (02 nos.)12”x24” (03 nos.)
Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 35 of 142
Equipments/Major components verificationAir Handling Unit verification
AHU-204EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
SECONDARY FILTERS Cartridge Filter (F9)
Is correctly installed, with no damages and perfectly assembled and fitted.Efficiency 95%Filter media: Ultra-fine fiberglassFilter size: 24”x24” (02 nos.)12”x24” (03 nos.)
Yes / No
SUPPLY FAN SECTION
Fan Manufacturer: Kruger Engineering Pte. Ltd.
Yes / No
Model & Potency: Supply:BDB450CM (7.5KW)
Fan Duty: Supply: 6000 CFM
Fan Type: Backward Curved Centrifugal
Belt Type: V beltMotor Manufacturer: Teco Elec. & Mech. Ptv. Ltd.
Section verification: Check on adequate assembling and not damages. Yes / No
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling.
Yes / No
Equipments/Major components verificationAir Handling Unit verification
AHU-205EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
AHU-205(CENAHU-12)
Manufacturer ACSON
Yes / NoModel ADM2-0410
Serial number 1204082
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 36 of 142
Equipments/Major components verificationAir Handling Unit verification
AHU-205EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
Flow 2000 CFM
Dimension (LxWxH) 3300x1450x930 mm
MIXING SECTION
02 Nos. of Manual dampers (Size 410 x 1280 mm) for return and FAI are correctly installed. Yes / No
- Mixing system allows keeping dampers at the selected position (open/close). - Position indicator correctly shows open or close position at any time.
Yes / No
Section verification: Check on adequate assembling and not damages. Yes / No
FILTRATION SECTION Pre filter (G-4)
is correctly installed, with no damages and perfectly assembled and fitted.Efficiency 50%Filter media: SyntheticFilter size: 24”x24” (02 nos.)
Yes / No
COOLING SECTION
Cooling Coil Capacity: 44.489 KW
Yes / No
Check water circuit is correctly installed and connected to the main water circuit.
Section verification: Check on adequate assembling and not damagesSection verification: Check on adequate assembling and not damages
SUPPLY FAN SECTION
Fan Manufacturer: Kruger Engineering Pte. Ltd.
Yes / No
Model & Potency: Supply:BDB250CM (3.0 KW)
Fan Duty: Supply: 2000 CFM
Fan Type: Backward Curved Centrifugal
Belt Type: V belt
Motor Manufacturer: Teco Elec. & Mech. Ptv. Ltd.
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 37 of 142
Equipments/Major components verificationAir Handling Unit verification
AHU-205EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
Section verification: Check on adequate assembling and not damages. Yes / No
FILTRATION SECTION Pre filter (G-4)
is correctly installed, with no damages and perfectly assembled and fitted.Efficiency 50%Filter media: SyntheticFilter size: 24”x24” (02 nos.)
Yes / No
SECONDARY FILTERS
Cartridge Filter (F9)
Is correctly installed, with no damages and perfectly assembled and fitted.Efficiency 95%Filter media: Ultra-fine fiberglassFilter size: 24”x24” (02 nos.)
Yes / No
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling. Yes / No
Equipments/Major components verificationAir Handling Unit verification
AHU-206EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
AHU-206 Manufacturer ACSON Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 38 of 142
Equipments/Major components verificationAir Handling Unit verification
AHU-206EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
(CENAHU-13)
Model ADM2-1010
Serial number 1204083
Flow 6500 CFM
Dimension (LxWxH) 2850x1450x1530mm
MIXING SECTION
02 Nos. of Manual dampers (Size 410 x 1280 mm) for return and FAI are correctly installed. Yes / No
- Mixing system allows keeping dampers at the selected position (open/close). - Position indicator correctly shows open or close position at any time.
Yes / No
Section verification: Check on adequate assembling and not damages. Yes / No
FILTRATION SECTION Pre filter (G-4)
is correctly installed, with no damages and perfectly assembled and fitted.Efficiency 50%Filter media: SyntheticFilter size: 24”x24” (04 nos.)
Yes / No
SECONDARY FILTERS
Cartridge Filter (F9)
Is correctly installed, with no damages and perfectly assembled and fitted.Efficiency 95%Filter media: Ultra-fine fiberglassFilter size: 24”x24” (04 nos.)
Yes / No
COOLING SECTION
Cooling Coil Capacity: 64.684 KW
Yes / NoCheck water circuit is correctly installed and connected to the main water circuit.Section verification: Check on adequate assembling and not damages
Fan Manufacturer: Kruger Engineering Pte. Ltd.
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 39 of 142
Equipments/Major components verificationAir Handling Unit verification
AHU-206EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
SUPPLY FAN SECTION
Yes / No
Model & Potency: Supply:BDB400CM(5.5KW)
Fan Duty: Supply: 6500 CFM
Fan Type: Backward Curved Centrifugal
Belt Type: V belt
Motor Manufacturer: Teco Elec. & Mech. Ptv. Ltd.
Section verification: Check on adequate assembling and not damages. Yes / No
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling.
Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 40 of 142
Equipments/Major components verificationAir Handling Unit verification
FAHU-101EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
FAHU-101(CENAHU-14)
Manufacturer ACSON
Yes / No
Model ADM2-0407
Serial number 1204084
Flow 2000 CFM
Dimension (LxWxH) 2750x1150x930mm
MIXING SECTION
02 Nos. of Manual dampers (Size 410 x 980 mm) for FAI are correctly installed. Yes / No
- Mixing system allows keeping dampers at the selected position (open/close). - Position indicator correctly shows open or close position at any time.
Yes / No
Section verification: Check on adequate assembling and not damages. Yes / No
FILTRATION SECTION
Pre filter (G-4)
is correctly installed, with no damages and perfectly assembled and fitted.Efficiency 50%Filter media: SyntheticFilter size: 24”x24” (01 nos.)12”x24” (01 nos.)
Yes / No
Bag filter (F8)
is correctly installed, with no damages and perfectly assembled and fitted.Efficiency 90-95%Filter media: Synthetic Filter size: 24 “ × 24” (01 Nos)12” × 24” (01 Nos)
Yes / No
COOLING SECTION
Cooling Coil Capacity: 58.907 KW
Yes / NoCheck water circuit is correctly installed and connected to the main water circuit.Section verification: Check on adequate assembling and not damages
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 41 of 142
Equipments/Major components verificationAir Handling Unit verification
FAHU-101EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
SUPPLY FAN SECTION
Fan Manufacturer: Kruger Engineering Pte. Ltd.
Yes / No
Model & Potency: Supply:BDB250CM(1.5KW)
Fan Duty: Supply: 2000 CFM
Fan Type: Backward Curved Centrifugal
Belt Type: V belt
Motor Manufacturer: Teco Elec. & Mech. Ptv. Ltd.
Section verification: Check on adequate assembling and not damages. Yes / No
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling.
Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 42 of 142
Equipments/Major components verificationAir Handling Unit verification
FAHU-201EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
FAHU-201(CENAHU-14)
Manufacturer ACSON
Yes / No
Model ADM2-0407
Serial number 1204085
Flow 2000 CFM
Dimension (LxWxH) 2750x1150x930mm
MIXING SECTION
02 Nos. of Manual dampers (Size 410 x 980 mm) for FAI are correctly installed. Yes / No
- Mixing system allows keeping dampers at the selected position (open/close). - Position indicator correctly shows open or close position at any time.
Yes / No
Section verification: Check on adequate assembling and not damages. Yes / No
FILTRATION SECTION
Pre filter (G-4)
is correctly installed, with no damages and perfectly assembled and fitted.Efficiency 50%Filter media: SyntheticFilter size: 24”x24” (01 nos.)12”x24” (01 nos.)
Yes / No
Bag filter (F8)
is correctly installed, with no damages and perfectly assembled and fitted.Efficiency 90-95%Filter media: Synthetic Filter size: 24 “ × 24” (01 Nos)12” × 24” (01 Nos)
Yes / No
COOLING SECTION
Cooling Coil Capacity: 58.907 KW
Yes / NoCheck water circuit is correctly installed and connected to the main water circuit.Section verification: Check on adequate assembling and not damages
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 43 of 142
Equipments/Major components verificationAir Handling Unit verification
FAHU-201EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
SUPPLY FAN SECTION
Fan Manufacturer: Kruger Engineering Pte. Ltd.
Yes / No
Model & Potency: Supply:BDB250CM(1.5KW)
Fan Duty: Supply: 2000 CFM
Fan Type: Backward Curved Centrifugal
Belt Type: V belt
Motor Manufacturer: Teco Elec. & Mech. Ptv. Ltd.
Section verification: Check on adequate assembling and not damages. Yes / No
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling.
Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 44 of 142
Equipments/Major components verificationFan Coil Unit verification
FCU-G01EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
FCU-G01(CENFCU-1)
Manufacturer: ACSON
Yes / No
Model: ACC30CW-AXAA-R
Serial number: 20552706-00116
Flow: 830 CFM
Dimension (HxWxD): 384x917x462mm
COOLING SECTION
Cooling Coil Capacity: 7.27 KW
Yes / NoCheck water circuit is correctly installed and connected to the main water circuit.Section verification: Check on adequate assembling and not damages.
FAN SECTION
Type: Blower
Yes / NoDrive: Direct
Fan Speed: 1180 RPM
Fan Efficiency: 37.20%
Motor Type: Induction
Yes / No
Motor Rated Input Power: 345 W
Motor Efficiency: 60.80%
Poles: 4
Section verification: Check on adequate assembling and not damages. Yes / No
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling. Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 45 of 142
Equipments/Major components verificationFan Coil Unit verification
FCU-G02EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
FCU-G02(CENFCU-2)
Manufacturer: ACSON
Yes / No
Model: ACC20CW-AXAC-R
Serial number: 20552706-00124
Flow: 675 CFM
Dimension (HxWxD): 267x1002x351mm
COOLING SECTION
Cooling Coil Capacity: 5.28 KW
Yes / NoCheck water circuit is correctly installed and connected to the main water circuit.Section verification: Check on adequate assembling and not damages.
FAN SECTION
Type: Blower
Yes / NoDrive: Direct
Fan Speed: 1328 RPM
Fan Efficiency: 47.50%
Motor Type: Induction
Yes / No
Motor Rated Input Power:
165 W
Motor Efficiency: 50.90%
Poles: 4
Section verification: Check on adequate assembling and not damages. Yes / No
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling. Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 46 of 142
Equipments/Major components verificationFan Coil Unit verification
FCU-G03EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
FCU-G03(CENFCU-3)
Manufacturer: ACSON
Yes / No
Model: ACC50CW-AXAA-R
Serial number: 20553004-00139
Flow: 1220 CFM
Dimension (HxWxD): 384x1287x462mm
COOLING SECTION
Cooling Coil Capacity: 13.10 KW
Yes / NoCheck water circuit is correctly installed and connected to the main water circuit.Section verification: Check on adequate assembling and not damages.
FAN SECTION
Type: Blower
Yes / NoDrive: Direct
Fan Speed: 1204 RPM
Fan Efficiency: 47.30%
Motor Type: Induction
Yes / No
Motor Rated Input Power:
388 W
Motor Efficiency: 58.60%
Poles: 4
Section verification: Check on adequate assembling and not damages. Yes / No
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling. Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 47 of 142
Equipments/Major components verificationFan Coil Unit verification
FCU-G04EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
FCU-G04(CENFCU-4)
Manufacturer: ACSON
Yes / No
Model: ACC30CW-AXAA-R
Serial number: 20552706-00115
Flow: 760 CFM
Dimension (HxWxD): 384x917x462mm
COOLING SECTION
Cooling Coil Capacity: 7.27 KW
Yes / NoCheck water circuit is correctly installed and connected to the main water circuit.Section verification: Check on adequate assembling and not damages.
FAN SECTION
Type: Blower
Yes / NoDrive: Direct
Fan Speed: 1053 RPM
Fan Efficiency: 39.50%
Motor Type: Induction
Yes / No
Motor Rated Input Power:
304 W
Motor Efficiency: 47.40%
Poles: 4
Section verification: Check on adequate assembling and not damages. Yes / No
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling. Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 48 of 142
Equipments/Major components verificationFan Coil Unit verification
FCU-G05EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
FCU-G05(CENFCU-5)
Manufacturer: ACSON
Yes / No
Model: ACC20CW-AXAC-R
Serial number: 20552706-00125
Flow: 675 CFM
Dimension (HxWxD): 267x1002x351mm
COOLING SECTION
Cooling Coil Capacity: 5.28 KW
Yes / NoCheck water circuit is correctly installed and connected to the main water circuit.Section verification: Check on adequate assembling and not damages.
FAN SECTION
Type: Blower
Yes / NoDrive: Direct
Fan Speed: 1328 RPM
Fan Efficiency: 47.50%
Motor Type: Induction
Yes / No
Motor Rated Input Power:
165 W
Motor Efficiency: 50.90%
Poles: 4
Section verification: Check on adequate assembling and not damages. Yes / No
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling. Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 49 of 142
Equipments/Major components verificationFan Coil Unit verification
FCU-G06EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
FCU-G06(CENFCU-6)
Manufacturer: ACSON
Yes / No
Model: ACC10CW-AXAC-R
Serial number: 20552706-00007
Flow: 285 CFM
Dimension (HxWxD): 266x702x351mm
COOLING SECTION
Cooling Coil Capacity: 2.9 KW
Yes / NoCheck water circuit is correctly installed and connected to the main water circuit.Section verification: Check on adequate assembling and not damages.
FAN SECTION
Type: Blower
Yes / NoDrive: Direct
Fan Speed: 1172 RPM
Fan Efficiency: 40.70%
Motor Type: Induction
Yes / No
Motor Rated Input Power:
86 W
Motor Efficiency: 42.40%
Poles: 4
Section verification: Check on adequate assembling and not damages. Yes / No
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling. Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 50 of 142
Equipments/Major components verificationFan Coil Unit verification
FCU-G07EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
FCU-G07(CENFCU-7)
Manufacturer: ACSON
Yes / No
Model: ACC25CW-AXAC-R
Serial number: 20552706-00081
Flow: 730 CFM
Dimension (HxWxD): 267x1137x351mm
COOLING SECTION
Cooling Coil Capacity: 6.59 KW
Yes / NoCheck water circuit is correctly installed and connected to the main water circuit.Section verification: Check on adequate assembling and not damages.
FAN SECTION
Type: Blower
Yes / NoDrive: Direct
Fan Speed: 1355 RPM
Fan Efficiency: 36.20%
Motor Type: Induction
Yes / No
Motor Rated Input Power: 182W
Motor Efficiency: 57.50%
Poles: 4
Section verification: Check on adequate assembling and not damages. Yes / No
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling. Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 51 of 142
Equipments/Major components verificationFan Coil Unit verification
FCU-G08EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
FCU-G08(CENFCU-8)
Manufacturer: ACSON
Yes / No
Model: ACC20CW-AXAC-R
Serial number: 20552706-00126
Flow: 675 CFM
Dimension (HxWxD): 267x1002x351mm
COOLING SECTION
Cooling Coil Capacity: 5.28 KW
Yes / NoCheck water circuit is correctly installed and connected to the main water circuit.Section verification: Check on adequate assembling and not damages.
FAN SECTION
Type: Blower
Yes / NoDrive: Direct
Fan Speed: 1328 RPM
Fan Efficiency: 47.50%
Motor Type: Induction
Yes / No
Motor Rated Input Power:
165 W
Motor Efficiency: 50.90%
Poles: 4
Section verification: Check on adequate assembling and not damages. Yes / No
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling. Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 52 of 142
Equipments/Major components verificationFan Coil Unit verification
FCU-G09EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
FCU-G09(CENFCU-9)
Manufacturer ACSON
Yes / No
Model ACC40CW-AXAA-R
Serial number 20552806-00460
Flow 1020 CFM
Dimension (HxWxD) 384x1003x462mm
COOLING SECTION
Cooling Coil Capacity: 10.84 KW
Yes / NoCheck water circuit is correctly installed and connected to the main water circuit.Section verification: Check on adequate assembling and not damages.
FAN SECTION
Type: Blower
Yes / NoDrive: Direct
Fan Speed: 1181 RPM
Fan Efficiency: 42.90%
Motor Type: Induction
Yes / No
Motor Rated Input Power:
384 W
Motor Efficiency: 47.50%
Poles: 4
Section verification: Check on adequate assembling and not damages.
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling. Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 53 of 142
Equipments/Major components verificationFan Coil Unit verification
FCU-G10EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
FCU-G10(CENFCU-10)
Manufacturer ACSON
Yes / No
Model ADB100BW-AXAA-R
Serial number 20552904-00247
Flow 3000 CFM
Dimension (HxWxD) 572x1502x761mm
COOLING SECTION
Cooling Coil Capacity: 27.84 KW
Yes / NoCheck water circuit is correctly installed and connected to the main water circuit.Section verification: Check on adequate assembling and not damages.
FAN SECTION
Type: Blower
Yes / NoDrive: Direct
Fan Speed: 885 RPM
Fan Efficiency: 35.00%
Motor Type: Induction
Yes / No
Motor Rated Input Power:
1620 W
Motor Efficiency: 36.60%
Poles: 4
Section verification: Check on adequate assembling and not damages.
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling. Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 54 of 142
Equipments/Major components verificationFan Coil Unit verification
FCU-101EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
FCU-101(CENFCU-11)
Manufacturer ACSON
Yes / No
Model ACC40CW-AXAA-R
Serial number 20552806-00461
Flow 1020 CFM
Dimension (HxWxD) 384x1003x462mm
COOLING SECTION
Cooling Coil Capacity: 10.84 KW
Yes / NoCheck water circuit is correctly installed and connected to the main water circuit.Section verification: Check on adequate assembling and not damages.
FAN SECTION
Type: Blower
Yes / NoDrive: Direct
Fan Speed: 1181 RPM
Fan Efficiency: 42.90%
Motor Type: Induction
Yes / No
Motor Rated Input Power:
384 W
Motor Efficiency: 47.50%
Poles: 4
Section verification: Check on adequate assembling and not damages.
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling. Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 55 of 142
Equipments/Major components verificationFan Coil Unit verification
FCU-101.1EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
FCU-101.1(CENFCU-12)
Manufacturer ACSON
Yes / No
Model ADB75BW-AXAA-R
Serial number 20552104-00250
Flow 2100 CFM
Dimension (HxWxD) 572x1502x761mm
COOLING SECTION
Cooling Coil Capacity: 22.16 KW
Yes / NoCheck water circuit is correctly installed and connected to the main water circuit.Section verification: Check on adequate assembling and not damages.
FAN SECTION
Type: Blower
Yes / NoDrive: Direct
Fan Speed: 720 RPM
Fan Efficiency: 43.20%
Motor Type: Induction
Yes / No
Motor Rated Input Power:
611 W
Motor Efficiency: 42.50%
Poles: 4
Section verification: Check on adequate assembling and not damages.
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling. Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 56 of 142
Equipments/Major components verificationFan Coil Unit verification
FCU-101.2EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
FCU-101.2(CENFCU-13)
Manufacturer ACSON
Yes / No
Model ADB75BW-AXAA-R
Serial number 20552704-00257
Flow 2100 CFM
Dimension (HxWxD) 572x1502x761mm
COOLING SECTION
Cooling Coil Capacity: 22.16 KW
Yes / NoCheck water circuit is correctly installed and connected to the main water circuit.Section verification: Check on adequate assembling and not damages.
FAN SECTION
Type: Blower
Yes / NoDrive: Direct
Fan Speed: 720 RPM
Fan Efficiency: 43.20%
Motor Type: Induction
Yes / NoMotor Rated Input Power:
611 W
Motor Efficiency: 42.50%
Poles: 4Section verification: Check on adequate assembling and not damages.
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling. Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 57 of 142
Equipments/Major components verificationFan Coil Unit verification
FCU-102EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
FCU-102(CENFCU-14)
Manufacturer ACSON
Yes / No
Model ACC60CW-AXAA-R
Serial number 20552706-00638
Flow 1400 CFM
Dimension (HxWxD) 384x1487x462mm
COOLING SECTION
Cooling Coil Capacity: 15.18 KW
Yes / NoCheck water circuit is correctly installed and connected to the main water circuit.Section verification: Check on adequate assembling and not damages.
FAN SECTION
Type: Blower
Yes / NoDrive: Direct
Fan Speed: 12.80 RPM
Fan Efficiency: 43.30%
Motor Type: Induction
Yes / No
Motor Rated Input Power:
457 W
Motor Efficiency: 59.6%
Poles: 4
Section verification: Check on adequate assembling and not damages.
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling. Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 58 of 142
Equipments/Major components verificationFan Coil Unit verification
FCU-103EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
FCU-103(CENFCU-15)
Manufacturer ACSON
Yes / No
Model ACC60CW-AXAA-R
Serial number 20552706-00637
Flow 1400 CFM
Dimension (HxWxD) 384x1487x462mm
COOLING SECTION
Cooling Coil Capacity: 15.18 KW
Yes / NoCheck water circuit is correctly installed and connected to the main water circuit.Section verification: Check on adequate assembling and not damages.
FAN SECTION
Type: Blower
Yes / NoDrive: Direct
Fan Speed: 12.80 RPM
Fan Efficiency: 43.30%
Motor Type: Induction
Yes / No
Motor Rated Input Power:
457 W
Motor Efficiency: 59.6%
Poles: 4
Section verification: Check on adequate assembling and not damages.
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling. Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 59 of 142
Equipments/Major components verificationFan Coil Unit verification
FCU-108EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
FCU-108(CENFCU-16)
Manufacturer: ACSON
Yes / No
Model: ACC25CW-AXAC-R
Serial number: 20552706-00082
Flow: 660 CFM
Dimension (HxWxD): 267x1137x351mm
COOLING SECTION
Cooling Coil Capacity: 6.59 KW
Yes / NoCheck water circuit is correctly installed and connected to the main water circuit.Section verification: Check on adequate assembling and not damages.
FAN SECTION
Type: Blower
Yes / NoDrive: Direct
Fan Speed: 1215 RPM
Fan Efficiency: 38.10%
Motor Type: Induction
Yes / No
Motor Rated Input Power:
175 W
Motor Efficiency: 48.40%
Poles: 4
Section verification: Check on adequate assembling and not damages. Yes / No
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling. Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 60 of 142
Equipments/Major components verificationFan Coil Unit verification
FCU-201EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
FCU-201(CENFCU-17)
Manufacturer ACSON
Yes / No
Model ACC60CW-AXAA-R
Serial number 20552706-00636
Flow 1550 CFM
Dimension (HxWxD) 384x1487x462mm
COOLING SECTION
Cooling Coil Capacity: 15.18 KW
Yes / NoCheck water circuit is correctly installed and connected to the main water circuit.Section verification: Check on adequate assembling and not damages.
FAN SECTION
Type: Blower
Yes / NoDrive: Direct
Fan Speed: 1351 RPM
Fan Efficiency: 41.70%
Motor Type: Induction
Yes / No
Motor Rated Input Power: 530 W
Motor Efficiency: 68.00%
Poles: 4
Section verification: Check on adequate assembling and not damages.
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling. Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 61 of 142
Equipments/Major components verificationFan Coil Unit verification
FCU-202EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
FCU-202(CENFCU-18)
Manufacturer ACSON
Yes / No
Model ACC60CW-AXAA-R
Serial number 20552706-00640
Flow 1550 CFM
Dimension (HxWxD) 384x1487x462mm
COOLING SECTION
Cooling Coil Capacity: 15.18 KW
Yes / NoCheck water circuit is correctly installed and connected to the main water circuit.Section verification: Check on adequate assembling and not damages.
FAN SECTION
Type: Blower
Yes / NoDrive: Direct
Fan Speed: 1351 RPM
Fan Efficiency: 41.70%
Motor Type: Induction
Yes / No
Motor Rated Input Power:
530 W
Motor Efficiency: 68.00%
Poles: 4
Section verification: Check on adequate assembling and not damages.
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling. Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 62 of 142
Equipments/Major components verificationFan Coil Unit verification
FCU-203EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
FCU-203(CENFCU-19)
Manufacturer ACSON
Yes / No
Model ACC60CW-AXAA-R
Serial number 20552706-00639
Flow 1550 CFM
Dimension (HxWxD) 384x1487x462mm
COOLING SECTION
Cooling Coil Capacity: 15.18 KW
Yes / NoCheck water circuit is correctly installed and connected to the main water circuit.Section verification: Check on adequate assembling and not damages.
FAN SECTION
Type: Blower
Yes / NoDrive: Direct
Fan Speed: 1550 RPM
Fan Efficiency: 41.70%
Motor Type: Induction
Yes / No
Motor Rated Input Power:
530 W
Motor Efficiency: 68.00%
Poles: 4
Section verification: Check on adequate assembling and not damages.
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assures a suitable assembling. Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 63 of 142
Equipments/Major components verificationAir Handling Unit verification
DEHUMIDIFIER-102EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
DEHUMIDIFIER-102
ID : BENDE 01
Manufacturer Dehutech
Yes / No
Model DT- 800Tag/Identification no. ENDE 01
Flow 470 CFMDimension (LxWxH)
600x1050x690 mm
MIXING SECTION
__0__ No / Nos of Manual dampers for return and FAI are correctly installed.
Yes / No
Section verification: Check on adequate assembling and not damages.
Yes / No
HEATINGSECTION
Heater is correctly installed.
Yes / NoHeater capacity- 6.5 KWSection verification: Check on adequate assembling and not damages
PROCESS AND REACTIVATION FAN SECTION
Process Fan
Yes / No
Manufacturer: ZIEHL-ABEGG
Fan Speed: 2700 rpm
Fan Type:
Backward Curved Centrifugal DIDW
Drive Type Direct (Coupling)Motor Power rating: 0.225 KWReactivation Fan
Yes / No
Manufacturer: ZIEHL-ABEGG
Fan Speed: 2600 rpm
Fan Type:
Backward Curved Centrifugal DIDW
Drive Type Direct (Coupling)Motor Power rating: 0.085 KWSection verification: Check on adequate assembling and not damages.
Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 64 of 142
Equipments/Major components verificationAir Handling Unit verification
DEHUMIDIFIER-102EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assure a suitable assembling
Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 65 of 142
Equipments/Major components verificationAir Handling Unit verification
DEHUMIDIFIER-103EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
DEHUMIDIFIER-103
ID : BENDE 02
Manufacturer Dehutech
Yes / No
Model DT-3000Tag/Identification no. ENDE 02
Flow 1764 CFMDimension (LxWxH) 1122x805x1020 mm
MIXING SECTION
__0__ No / Nos. of Manual dampers for return and FAI are correctly installed. Yes / No
Section verification: Check on adequate assembling and not damages. Yes / No
HEATINGSECTION
Heater is correctly installed.
Yes / NoHeater capacity- 18 KWSection verification: Check on adequate assembling and not damages
PROCESS AND REACTIVATION FAN
SECTION
Process Fan
Yes / No
Manufacturer: ZIEHL-ABEGG
Fan Speed: 3550 rpm
Fan Type: Backward Curved Centrifugal DIDW
Drive Type Direct (Coupling)Motor Power rating: 2.2 KW
Reactivation Fan
Yes / No
Manufacturer: ZIEHL-ABEGG
Fan Speed: 2750 rpm
Fan Type: Backward Curved Centrifugal DIDW
Drive Type Direct (Coupling)Motor Power rating: 0.250 KW
Section verification: Check on adequate assembling and not damages. Yes / No
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assure a suitable assembling
Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 66 of 142
Equipments/Major components verificationAir Handling Unit verification
DEHUMIDIFIER-106EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
DEHUMIDIFIER-106
ID : BENDE 03
Manufacturer Dehutech
Yes / No
Model DT-2000Tag/Identification no. ENDE 03
Flow 1176 CFMDimension (LxWxH) 1122x805x1020 mm
MIXING SECTION
__0__ No / Nos. of Manual dampers for return and FAI are correctly installed. Yes / No
Section verification: Check on adequate assembling and not damages. Yes / No
HEATINGSECTION
Heater is correctly installed.
Yes / NoHeater capacity- 18 KWSection verification: Check on adequate assembling and not damages
PROCESS AND REACTIVATION FAN
SECTION
Process Fan
Yes / No
Manufacturer: ZIEHL-ebm
Fan Speed: 2770 rpmFan Type: RH35M-2DK.6F.2RDrive Type Direct (Coupling)Motor Power rating: 1.35 KW
Reactivation Fan
Yes / No
Manufacturer: ZIEHL-ebm
Fan Speed: 2950 rpmFan Type: R2D280-AF08-14Drive Type Direct (Coupling)Motor Power rating: 0.330 KW
Section verification: Check on adequate assembling and not damages. Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 67 of 142
Equipments/Major components verificationAir Handling Unit verification
DEHUMIDIFIER-106EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assure a suitable assembling
Yes / No
Equipments/Major components verificationAir Handling Unit verification
DEHUMIDIFIER-107EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
DEHUMIDIFIER-107
ID : BENDE 04
Manufacturer Dehutech
Yes / No
Model DT-2000Tag/Identification no. ENDE 04
Flow 1176 CFMDimension (LxWxH) 1122x805x1020 mm
MIXING SECTION
__0__ No / Nos of Manual dampers for return and FAI are correctly installed. Yes / No
Section verification: Check on adequate assembling and not damages. Yes / No
HEATINGSECTION
Heater is correctly installed.
Yes / NoHeater capacity- 18 KWSection verification: Check on adequate assembling and not damages.
PROCESS AND REACTIVATION FAN
SECTION
Process Fan
Yes / No
Manufacturer: ZIEHL-ebm
Fan Speed: 2770 rpmFan Type: RH35M-2DK.6F.2RDrive Type Direct (Coupling)Motor Power rating: 1.35 KW
Reactivation Fan
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 68 of 142
Equipments/Major components verificationAir Handling Unit verification
DEHUMIDIFIER-107EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
Yes / No
Manufacturer: ZIEHL-ebm
Fan Speed: 2950 rpmFan Type: R2D280-AF08-14Drive Type Direct (Coupling)Motor Power rating: 0.330 KW
Section verification: Check on adequate assembling and not damages. Yes / No
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assure a suitable assembling
Yes / No
Equipments/Major components verificationAir Handling Unit verification
DEHUMIDIFIER-109EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
DEHUMIDIFIER-109
ID : BENDE 05
Manufacturer Dehutech
Yes / No
Model DT-2000Tag/Identification no. ENDE 05
Flow 1176 CFMDimension (LxWxH) 1122x805x1020 mm
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 69 of 142
Equipments/Major components verificationAir Handling Unit verification
DEHUMIDIFIER-109EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
MIXING SECTION
__0__ No / Nos of Manual dampers for return and FAI are correctly installed. Yes / No
Section verification: Check on adequate assembling and not damages. Yes / No
HEATINGSECTION
Heater is correctly installed.
Yes / NoHeater capacity- 18 KWSection verification: Check on adequate assembling and not damages
PROCESS AND REACTIVATION FAN
SECTION
Process Fan
Yes / No
Manufacturer: ZIEHL-ebm
Fan Speed: 2770 rpmFan Type: RH35M-2DK.6F.2RDrive Type Direct (Coupling)Motor Power rating: 1.35 KWReactivation Fan
Yes / No
Manufacturer: ZIEHL-ebm
Fan Speed: 2950 rpmFan Type: R2D280-AF08-14Drive Type Direct (Coupling)Motor Power rating: 0.330 KWSection verification: Check on adequate assembling and not damages. Yes / No
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assure a suitable assembling
Yes / No
Equipments/Major components verificationAir Handling Unit verification
DEHUMIDIFIER-203EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
DEHUMIDIFIER-203 Manufacturer Dehutech Yes / NoModel DT-2000
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 70 of 142
Equipments/Major components verificationAir Handling Unit verification
DEHUMIDIFIER-203EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
ID : BENDE 06
Tag/Identification no. ENDE 15Flow 1176 CFMDimension (LxWxH) 1122x805x1020 mm
MIXING SECTION
__0__ No / Nos of Manual dampers for return and FAI are correctly installed. Yes / No
Section verification: Check on adequate assembling and not damages. Yes / No
HEATINGSECTION
Heater is correctly installed.
Yes / NoHeater capacity- 18 KWSection verification: Check on adequate assembling and not damages
PROCESS AND REACTIVATION FAN
SECTION
Process Fan
Yes / No
Manufacturer: ZIEHL-ebm
Fan Speed: 2770 rpmFan Type: RH35M-2DK.6F.2RDrive Type Direct (Coupling)Motor Power rating: 1.35 KW
Reactivation Fan
Yes / No
Manufacturer: ZIEHL-ebm
Fan Speed: 2950 rpmFan Type: R2D280-AF08-14Drive Type Direct (Coupling)Motor Power rating: 0.330 KW
Section verification: Check on adequate assembling and not damages. Yes / No
IMPULSIONDUCT
Verify ducts are not damaged & leaked, and are properly isolated, clean and correctly installed that assure a suitable assembling.
Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 71 of 142
Equipments/Major components verificationAir Handling Unit verification
DEHUMIDIFIER-203EQUIPMENT SPECIFICATIONS CONFORMITY COMMENTS
OBSERVATIONS:
Performed by Signature Date
Checked by Signature Date
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 72 of 142
Equipments/major components verificationTerminal HEPA filters verification: identification and certificates
ROOM NO SUPPLY FILTER SIZE (mm) SERIAL NO CONFORMITY REMARKS
204204-S1 610 x 610 x 149 000206
Yes / No204-S2 610 x 610 x 149 000711
210210-S1 610 x 610 x 149 000205
Yes / No210-S1 610 x 610 x 149 000700
211
211-S1 610 x 610 x 149 000714
Yes / No211-S2 610 x 610 x 149 000696
211-S3 610 x 610 x 149 000095
211-S4 610 x 610 x 149 000096
212 212-S1 610 x 610 x 149 000091 Yes / No
213 213-S1 610 x 610 x 149 000092 Yes / No
214 214-S1 610 x 610 x 149 000080 Yes / No
215215-S1 610 x 610 x 149 000081
Yes / No215-S1 610 x 610 x 149 000706
216 216-S1 610 x 310 x 149 000079 Yes / No
217 217-S1 610 x 310 149 000090 Yes / No
222222-S1 610 x 610 x 149 000709
Yes / No222-S2 610 x 610 x149 000710
223223-S1 610 x 610 x 149 000078 Yes / No
223-S2 610 x 610 x 149 000718 Yes / No
225 225-S1 610 x 310 x 149 000089 Yes / No
228228-S1 610 x 310 x 149 000001
Yes / No228-S2 610 x 310 x 149 000002
232 232-S1 610 x 310 x 149 000703 Yes / No
233 233-S1 610 x 610 x 149 000077 Yes / No
234 234-S1 610 x 310 x 149 000090 Yes / No
235 235-S1 610 x 310 x 149 000089 Yes / No
236236-S1 610 x 610 x 149 000086
Yes / No236-S2 610 x 610 x 149 000084
237 237-S1 610 x 610 x 149 000009 Yes / No
238 238-S1 610 x 610 x 149 000083 Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 73 of 142
Equipments/major components verificationTerminal HEPA filters verification: identification and certificates
ROOM NO SUPPLY FILTER SIZE (mm) SERIAL NO CONFORMITY REMARKS319 319-S1 610 x 310 x 149 000083 Yes / No
320 320-S1 610 x 310 x 149 000088 Yes / No
321 321-S1 610 x 310 x 149 000090 Yes / No
322322-S1 610 x 610 x 149 000684
Yes / No322-S1 610 x 610 x 149 000687
323 323-S1 610 x 310 x 149 000088 Yes / No
324 324-S1 610 x 310 x 149 000087 Yes / No
325325-S1 610 x 610 x 149 000677
Yes / No325-S2 610 x 610 x 149 000086
326326-S1 610 x 610 x 149 000683
Yes / No326-S2 610 x 610 x 149 000688
327
327-S1 610 x 610 x 149 000088
Yes / No327-S1 610 x 610 x 149 000089
327-S3 610 x 610 x 149 000085
328
328-S1 610 x 610 x 149 000704
Yes / No328-S2 610 x 610 x 149 000708
328-S3 610 x 610 x 149 000084
329329-S1 610 x 610 x 149 000709
Yes / No329-S2 610 x 610 x 149 000706
330 330-S1 610 x 310 x 149 000082 Yes / No
331 331-S1 610 x 310 x 149 000086 Yes / No
332 332-S1 610 x 310 x 149 000084 Yes / No
333 333-S1 610 x 310 x 149 00003 Yes / No
334 334-S1 610 x 310 x 149 000703 Yes / No
336
336-S1 610 x 610 x 149 000082
Yes / No
336-S2 610 x 610 x 149 000087
336-S3 610 x 610 x 149 000679
336-S4 610 x 610 x 149 000680
336-S5 610 x 610 x 149 000678
336-S6 610 x 610 x 149 000698
339 339-S1 610 x 610 x 149 000699
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 74 of 142
Equipments/major components verificationTerminal HEPA filters verification: identification and certificates
ROOM NO SUPPLY FILTER SIZE (mm) SERIAL NO CONFORMITY REMARKS Yes / No339-S2 610 x 610 x 149 000697
340 340-S1 610 x 610 x 149 000702 Yes / No
338 338-S1 610 x 610 x 149 000091 Yes / NoOBSERVATIONS:
Performed by Signature Date
Checked by Signature Date
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 75 of 142
Equipments/major components verificationTerminal (Diffuser, Grille & Hepa) verification
ROOM NO SUPPLY/RETURN GRILL SIZE CONFORMITY REMARKS
102
102-S1 C.D-12”X12”
Yes / No
102-S2 C.D-12”X12”
102-S3 C.D-12”X12”
102-S4 C.D-12”X12”
102-R1 C.R-30”X18”
104104-S1 C.D-12”X12”
Yes / No104-R1 C.R-14”X14”
105105-S1 C.D- 14”x14”
Yes / No105-R1 C.R- 16”x16”
106106-S1 C.D- 12”x12”
Yes / No106-R1 C.R- 12”x12”
111
111-S1 C.D- 10”x10”
Yes / No
111-S2 C.D- 10”x10”
111-S3 C.D- 10”x10”
111-S4 C.D- 14”x14”
111-R1 C.R- 12”x12”
111-R2 C.R- 12”x12”
113
113-S1 C.D- 10”x10”
Yes / No
113-S2 C.D- 10”x10”113-S3 C.D- 12”x12”113-S4 C.D- 12”x12”
113-R1 C.R-12”X12”
113-R2 C.R-12”X12”
114114-S1 C.D- 12”x12”
Yes / No114-R1 C.R-12”X12”
115115-S1 C.D-6”X6”
Yes / No115-R1 C.R-6”X6”
116
116-S1 C.D-10”X10”
Yes / No116-R1 C.R-12”X12”
116-R2 C.R-16”X10”
117 117-S1 C.D-10”X10”
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 76 of 142
Equipments/major components verificationTerminal (Diffuser, Grille & Hepa) verification
ROOM NO SUPPLY/RETURN GRILL SIZE CONFORMITY REMARKS Yes / No117-R1 C.R-10”X10”
121
121-S1 C.D-8”X8”
Yes / No121-R1 C.R-8”X8”
121-R2 C.R-16”X10”
122122-S1 C.D-10”X10”
Yes / No122-R1 C.R-18”X10”
124124-S1 C.D-10”X10”
Yes / No124-R1 C.R-8”X8”
125 125-S1 C.D-10”X10” Yes / No
126126-S1 C.D-6”X6”
Yes / No126-R1 C.R-10”X10”
127127-S1 C.D-10”X10”
Yes / No127-R1 C.R-8”X8”
130
130-S1 C.D-14”X14”
Yes / No130-S2 C.D-14”X14”
130-R1 C.R-12”X12”
130-R2 C.R-12”X12”
131131-S1 C.D-12”X12”
Yes / No131-R1 C.R-12”X12”
132132-S1 C.D-12”X12”
Yes / No132-R1 C.R-12”X12”
133133-S1 C.D-10”X10”
Yes / No133-R1 C.R-8”X8”
202
202-S1 C.D-16”X16”
Yes / No202-S2 C.D-16”X16”
202-S3 C.D-16”X16”
202-S4 C.D-16”X16”
202-R1 C.R-24”X12”
202-R2 C.R-24”X12”
202-R3 C.R-14”X10”
204 204-S1 H-24”X24”
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 77 of 142
Equipments/major components verificationTerminal (Diffuser, Grille & Hepa) verification
ROOM NO SUPPLY/RETURN GRILL SIZE CONFORMITY REMARKS
Yes / No
204-S2 H-24”X24”
204-R1 L.R-14”X14”
204-E1 L.D-8”X6”
205
205-S1 C.D-14”X14”
Yes / No
205-S2 C.D-14”X14”
205-S3 C.D-14”X14”
205-S4 C.D-14”X14”
205-S5 C.D-12”X12”
205-R1 C.R-24”X12”
205-R2 C.R-24”X12”
205-R3 C.R-14”X10”
207
207-S1 C.D-12”X12”
Yes / No207-S2 C.D-12”X12”
207-R1 C.R-12”X12”
207-R2 C.R-12”X12”
210
210-S1 H-24”X24”
Yes / No210-S2 H-24”X24”
210-R1 C.R-8”X6”
211
211-S1 H-24”X24”
Yes / No
211-S2 H-24”X24”
211-S3 H-24”X24”
211-S4 H-24”X24”
211-R1 L.R-24”X12”
211-R2 L.R-24”X12”
211-R3 L.R-24”X12”
211-E1 L.D-8”X6”
212212-S1 H-24”X24”
Yes / No212-R1 C.R-12”X12”
213
213-S1 H-24”X24”
Yes / No213-R1 L.R-16”X10”
213-E1 L.D-8”X6”
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 78 of 142
Equipments/major components verificationTerminal (Diffuser, Grille & Hepa) verification
ROOM NO SUPPLY/RETURN GRILL SIZE CONFORMITY REMARKS
214
214-S1 H-24”X24”
Yes / No214-R1 L.R-16”X10”
214-R2 L.R-8”X6”
215
215-S1 H-24”X24”
Yes / No
215-S2 H-24”X24”
215-R1 L.R-16”X10”
215-R2 L.R-16”X10”
215-E1 L.D-8”X6”
216
216-S1 H-24”X24”
Yes / No216-R1 L.R-12”X8”
216-E1 L.D-8”X6”
217217-S1 H-24”X12”
Yes / No217-R1 C.R-12”X12”
218
218-S1 C.D-12”X12”
Yes / No
218-S2 C.D-12”X12”
218-S3 C.D-12”X12”
218-R1 C.R-12”X12”
218-R2 C.R-12”X12”
218-R3 C.R-12”X12”
219
219-S1 C.D-12”x12”
Yes / No219-S2 C.D-12”x12”
219-R1 L.R-14”X10”
220
220-S1 C.D-12”x12”
Yes / No220-S2 C.D-12”x12”
220-R1 L.R-14”X10”
220-S1 C.D-12”X12”
221
221-S2 C.D-12”X12”
Yes / No221-R1 C.R-12”X12”
221-E1 C.E-12”X12”
222222-S1 H-24”X24”
Yes / No222-S2 H-24”X24”
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 79 of 142
Equipments/major components verificationTerminal (Diffuser, Grille & Hepa) verification
ROOM NO SUPPLY/RETURN GRILL SIZE CONFORMITY REMARKS222-R1 L.R-10”X8”
222-R2 L.R-10”X8”
223
223-S1 H-24”X24”
Yes / No223-S2 H-24”X24”
223-R1 L.R-10”X8”
223-R2 L.R-10”X8”
225225-S1 H-24”X12”
Yes / No225-R1 C.R-10”X8”
226226-S1 C.D-10”X10”
Yes / No226-R1 C.R-10”X8”
227227-S1 C.D-14”X14”
Yes / No227-R1 C.R-6”X6”
228
228-S1 H-24”X12”
Yes / No228-S2 H-24”X12”
228-R1 C.R-8”X6”
229229-S1 C.D-10”X10”
Yes / No229-R1 C.R-10”X8”
230230-S1 H-24”X24”
Yes / No230R1 C.R-10”X10”
231231-S1 C.D-8”X8”
Yes / No231-R1 C.R-6”X6”
232
232-S1 H-24”X24”
Yes / No232-R1 L.R-12”X8”
232-E1 L.D-8”X6”
233
233-S1 H-24”X24”
Yes / No233-R1 L.R-12”X10”
233-E1 L.D-8”X6”
234
234-S1 H-24”X24”
Yes / No234-R1 L.R-12”X8”
234-E1 L.D-8”X6”
235 235-S1 H-24”X24”
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 80 of 142
Equipments/major components verificationTerminal (Diffuser, Grille & Hepa) verification
ROOM NO SUPPLY/RETURN GRILL SIZE CONFORMITY REMARKS
Yes / No235-R1 L.R-12”X8”
235-E1 L.D-8”X6”
236
236-S1 H-24”X24”
Yes / No
236-S2 H-24”X24”
236-R1 L.R-10”X8”
236-R2 L.R-8”X6”
236-E1 L.D-8”X6”
237
237-S1 H-24”X24”
Yes / No237-R1 L.R-10”X8”
237-E1 L.D-8”X6”
238
238-S1 H-24”X24”
Yes / No238-R1 L.R-10”X8”
238-E1 L.D-8”X6”
302
302-S1 C.D-16”X16”
Yes / No
302-S2 C.D-16”X16”
302-S3 C.D-16”X16”
302-R1 C.R-24”X12”
302-R2 C.R-24”X12”
304 304-S1 C.D-10”X10” Yes / No
307
307-S1 C.D-16”X16”
Yes / No307-S2 C.D-16”X16”
307-R1 C.R-14”X14”
307-R2 C.R-14”X14”
311311-S1 C.D-10”X10”
Yes / No311-R1 C.R-10”X10”
312
312-S1 C.D-14”X14”
Yes / No312-R1 C.R-14”X14”
312-R2 C.R-8”X8”
312-E1 C.E-8”X8”
313313-S1 C.D-8”X8”
Yes / No313-R1 C.R-8”X8”
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 81 of 142
Equipments/major components verificationTerminal (Diffuser, Grille & Hepa) verification
ROOM NO SUPPLY/RETURN GRILL SIZE CONFORMITY REMARKS314 314-R1 C.R-6”X6” Yes / No
315
315-S1 C.D-18”X18”
Yes / No
315-S2 C.D-18”X18”
315-S3 C.D-18”X18”
315-S4 C.D-18”X18”
315-S5 C.D-18”X18”
315-S6 C.D-18”X18”
315-R1 L.R-26”X16”
315-R2 L.R-26”X16”
315-R3 L.R-18”X18”
315-R4 L.R-14”X14”
316316-S1 C.D-12”X12”
Yes / No316-R1 C.R-6”X6”
317
317-S1 C.D-16”X16”
Yes / No317-S2 C.D-12”X12”
317-R1 L.R-12”X12”
317-E1 L.D-12”X12”
318318-S1 H-24”X12”
Yes / No318-R1 C.R-10”X10”
319319-S1 H-24”X12”
Yes / No319-R1 C.R-8”X6”
320320-S1 H-24”X12”
Yes / No320-R1 C.R-8”X6”
321321-S1 H-24”X12”
Yes / No321-R1 C.R-10”X8”
322
322-S1 H-24”X24”
Yes / No322-S2 H-24”X24”
322-R1 C.R-14”X14”
322-R2 C.R-12”X8”
323323-S1 H-24”X12”
Yes / No323-R1 C.R-10”X8”
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 82 of 142
Equipments/major components verificationTerminal (Diffuser, Grille & Hepa) verification
ROOM NO SUPPLY/RETURN GRILL SIZE CONFORMITY REMARKS
324324-S1 H-24”X12”
Yes / No324-R1 L.R-10”X8”
325
325-S1 H-24”X24”
Yes / No325-S2 H-24”X24”
325-R1 C.R-24”X12”
325-E1 C.E-14”X10”
326
326-S1 H-24”X24”
Yes / No326-S1 H-24”X24”
326-R1 L.R-16”X10”
327
315-S1 H-24”X24”
Yes / No
327-S2 H-24”X24”
327-S3 H-24”X24”
327-R1 L.R-24”X12”
327-R2 L.R-24”X12”
328
328-S1 H-24”X24”
Yes / No
328-S2 H-24”X24”
328-S3 H-24”X24”
328-R1 L.R-24”X12”
328-R2 L.R-24”X12”
329
329-S1 H-24”X24”
Yes / No329-S2 H-24”X24”
329-R1 C.R-16”X10”
329-R2 C.R-16”X10”
330330-S1 H-24”X12”
Yes / No330-R1 C.R-10”X8”
331331-S1 H-24”X12”
Yes / No331-R1 C.R-10”X8”
332332-S1 H-24”X12”
Yes / No332-R1 C.R-10”X8”
333333-S1 H-24”X12”
Yes / No333-R1 C.R-10”X8”
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 83 of 142
Equipments/major components verificationTerminal (Diffuser, Grille & Hepa) verification
ROOM NO SUPPLY/RETURN GRILL SIZE CONFORMITY REMARKS
334334-S1 H-24”X24”
Yes / No334-R1 C.R-12”X8”
336
336-S1 H-24”X24”
Yes / No
336-S2 H-24”X24”
336-S3 H-24”X24”
336-S4 H-24”X24”
336-S5 H-24”X24”
336-S6 H-24”X24”
336-R1 L.R-18”X10”
336-R2 L.R-18”X10”
336-R3 L.R-14”X10”
336-R4 L.R-14”X10”
337
337-S1 H-24”X24”
Yes / No
337-S2 H-24”X24”
337-R1 C.R-10”X8”
337-R2 C.R-10”X8”
337-R3 C.R-10”X8”
337-E1 C.E-10”X8”
338 338-S1 H-24”X24” Yes / No
339
339-S1 H-24”X24”
Yes / No339-S2 H-24”X24”
339-R1 C.R-24”X12”
339-R2 C.R-24”X12”
340340-S1 H-24”X24”
Yes / No340-R1 L.R-16”X10”
OBSERVATIONS:
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 84 of 142
Equipments/major components verificationTerminal (Diffuser, Grille & Hepa) verification
ROOM NO SUPPLY/RETURN GRILL SIZE CONFORMITY REMARKS
Performed by Signature Date
Checked by Signature Date
Auxiliary Equipment Identification MatrixTag/Identification
No. Items Specification Result Comments
CHILLERChiller-1 Model: SR-U120GBI; Capacity: 120TR,
Brand: Century; Origin: USA. Compressor-2 no’s; fan: 8 no’s, Refrigerant: 134a.
Yes / NoChiller-2
CHILLED WATER PUMP
CHWP-1Brand: Monoflo, Model: DMT 65-320,
Head-100 ft, Hp-15, Kw-11, IP 11, HZ-50,RPM-1450 V- 400, Pole-4.
Yes / No
CHWP-2
CHWP-3
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 85 of 142
DUST COLLECTOR DC-1 Brand: Donaldson, Model: DFO 2-8, Origin:
India, Capacity: 4000 CFM.
Yes / No
OBSERVATIONS :
Test final result PASS FAILPerformed by Signature Date
Checked by Signature Date
Instrument Verification Matrix
Tag/Identificati
onItems Specification Result Comments
AHU-102
102/DTS-01
Duct Temperature & RH Transmitter
Model No: KFTF-U, Brand: Trane; Origin: USA. Pt 1k ohm, (375), 18” probe.
Yes / No
102/MV-01 3 Way Modulating Valve
Model No: H525+NVD24-SR-T, Brand: Belimo, Origin-Switzerland. Medium temperature: 5 - 120°C, Permissible pressure ps: 1600 kPa,
Yes / No
102/BV-01 Balancing Valve Brand: Danfoss, Model: MSV-BD, Size: DN25, 1 inch, KVS: 9.5m³/h, Max. static working pressure: 20 bar, Max. Flow temperature: 120
Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 86 of 142
Instrument Verification MatrixTag/
Identification
Items Specification Result Comments
°C, Min. temperature -20 °C,
102/DPS-01
DP Switches for Motor
Model: DS-205_B, Brand: Trane, Origin: USA, Adjustable set point range-change constants
on increasing pressure from .05±.02 to 2 in wg.
Yes / No
102/DPT-01
Static Pressure Transmitter
Model: 1301-1142-0010-200, Brand: Trane, Origin: USA,
Yes / No
AHU-103
103/DTS-01
Duct Temperature & RH Transmitter
Model No: KFTF-U, Brand: Trane; Origin: USA. Pt 1k ohm, (375), 18” probe.
Yes / No
103/MV-01 3 Way Modulating Valve
Model No: H550B+NVD24-MFT2, Brand:Belimo, Origin-Switzerland Medium temp: 5 - 120°C, Permissible pressure ps: 1600 kPa,
Yes / No
103/BV-01 Balancing Valve
Brand: Danfoss, Model: MSV-BD, size: DN50, 2 inch, KVS: 40m³/h, Max. Static working pressure: 20 bar, Max. Flow temperature: 130 °C Min. temperature: -20 °C,
Yes / No
103/DPS-01
DP Switches for Motor
Model: DS-205_B, Brand: Trane, Origin: USA, Adjustable set point range-change constants
on increasing pressure from .05±.02 to 2 in wg.
Yes / No
103/DPT-01
Static Pressure Transmitter
Model: 1301-1142-0010-200, Brand: Trane, Origin: USA,
Yes / No
AHU-104
104/DTS-01
Duct Temperature & RH Transmitter
Model No: KFTF-U, Brand: Trane; Origin: USA. Pt 1k ohm, (375), 18” probe.
Yes / No
104/MV-01 3 Way Modulating Valve
Model No: H550B+NVD24-MFT2, Brand: Belimo, Origin-Switzerland Medium temp: 5 - 120°C, Permissible pressure ps: 1600 kPa,
Yes / No
104/BV-01 Balancing Valve
Brand: Danfoss, Model: MSV-BD, size: DN50, 2 inch, KVS: 40m³/h, Max. Static working pressure: 20 bar, Max. Flow temperature: 130 °C Min. temperature: -20 °C
Yes / No
104/DPS-01
DP Switches for Motor
Model: DS-205_B, Brand: Trane, Origin: USA, Adjustable set point range-change constants
on increasing pressure from .05±.02 to 2 in wg.
Yes / No
104/DPT-01
Static Pressure Transmitter
Model: 1301-1142-0010-200, Brand: Trane, Origin: USA,
Yes / No
AHU-105
105/DTS-01
Duct Temperature & RH Transmitter
Model No: KFTF-U, Brand: Trane; Origin: USA. Pt 1k ohm, (375), 18” probe.
Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 87 of 142
Instrument Verification MatrixTag/
Identification
Items Specification Result Comments
105/MV-01 3 Way Modulating Valve
Model No: H550B+NVD24-MFT2, Brand: Belimo, Origin-Switzerland. Medium temp:
5 - 120°C, Permissible pressure ps: 1600 kPa,
Yes / No
105/BV-01 Balancing Valve
Brand: Danfoss, Model: MSV-BD, size: DN50, 2 inch, KVS: 40m³/h, Max. Static working pressure: 20 bar, Max. Flow temperature: 130 °C Min. temperature: -20 °C,
Yes / No
105/DPS-01
DP Switches for Motor
Model: DS-205_B, Brand: Trane, Origin: USA, Adjustable set point range-change constants
on increasing pressure from .05±.02 to 2 in wg.
Yes / No
105/DPT-01 Static Pressure
TransmitterModel: 1301-1142-0010-200, Brand: Trane,
Origin: USA, Yes / No
AHU-106
106/DTS-01
Duct Temperature & RH Transmitter
Model No: KFTF-U, Brand: Trane; Origin: USA. Pt 1k ohm, (375), 18” probe.
Yes / No
106/MV-01 3 Way Modulating Valve
Model No: H540B+NVD24-SR-T, Brand: Belimo, Origin-Switzerland. Medium temp: 5 - 120°C, Permissible pressure ps: 1600 kPa,
Yes / No
106/BV-01 Balancing Valve
Brand: Danfoss, Model: MSV-BD, size: DN40,1.5 inch, KVS: 26 m³/h, Max. Static working pressure: 20 bar, Max. Flow temperature: 130 °C Min. temperature: -20 °C
Yes / No
106/DPS-01
DP Switches for Motor
Model: DS-205_B, Brand: Trane, Origin: USA, Adjustable set point range-change constants
on increasing pressure from .05±.02 to 2 in wg.
Yes / No
106/DPT-01 Static Pressure
TransmitterModel: 1301-1142-0010-200, Brand: Trane,
Origin: USA, Yes / No
AHU-107
107/DTS-01
Duct Temperature & RH Transmitter
Model No: KFTF-U, Brand: Trane; Origin: USA. Pt 1k ohm, (375), 18” probe.
Yes / No
107/MV-01 3 Way Modulating Valve
Model No: H540B+NVD24-SR-T, Brand: Belimo, Origin-Switzerland. Medium temp: 5 - 120°C, Permissible pressure ps: 1600 kPa,
Yes / No
107/BV-01 Balancing Valve
Brand: Danfoss, Model: MSV-BD, size: DN40, 1.5 inch, KVS: 26 m³/h, Max. Static working pressure: 20 bar, Max. Flow temperature: 130 °C, Min. temperature: -20 °C,
Yes / No
107/DPS-01
DP Switches for Motor
Model: DS-205_B, Brand: Trane, Origin: USA, Adjustable set point range-change constants
on increasing pressure from .05±.02 to 2 in wg.
Yes / No
107/DPT-01
Static Pressure Transmitter
Model: 1301-1142-0010-200, Brand: Trane, Origin: USA,
Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 88 of 142
Instrument Verification MatrixTag/
Identification
Items Specification Result Comments
AHU-109
109/DTS-01
Duct Temperature & RH Transmitter
Model No: KFTF-U, Brand: Trane; Origin: USA. Pt 1k ohm, (375), 18” probe.
Yes / No
109/MV-01 3 Way Modulating Valve
Model No: H540B+NVD24-SR-T, Brand: Belimo, Origin- Switzerland. Medium temp: 5 - 120°C, Permissible pressure ps: 1600 kPa,
Yes / No
109/BV-01 Balancing Valve
Brand: Danfoss, Model: MSV-BD, size: DN40, 1.5 inch, KVS: 26 m³/h, Max. Static working pressure: 20 bar, Max. Flow temperature: 130 °C, Min. temperature: -20 °C.
Yes / No
109/DPS-01
DP Switches for Motor
Model: DS-205_B, Brand: Trane, Origin: USA, Adjustable set point range-change constants
on increasing pressure from .05±.02 to 2 in wg.
Yes / No
109/DPT-01
Static Pressure Transmitter
Model: 1301-1142-0010-200, Brand: Trane, Origin: USA,
Yes / No
AHU-201
201/DTS-01
Duct Temperature & RH Transmitter
Model No: KFTF-U, Brand: Trane; Origin: USA. Pt 1k ohm, (375), 18” probe.
Yes / No
201/MV-01 3 Way Modulating Valve
Model No: H550B+NVD24-MFT2, Brand: Belimo, Origin-Switzerland. Medium temp: 5 - 120°C, Permissible pressure PS: 1600 kPa.
Yes / No
201/BV-01 Balancing Valve
Brand: Danfoss, Model: MSV-BD, size: DN50, 2 inch, KVS: 40m³/h, Max. Static working pressure: 20 bar, Max. Flow temperature: 130 °C Min. temperature: -20 °C.
Yes / No
201DPS-01
DP Switches for Motor
Model: DS-205_B, Brand: Trane, Origin: USA, Adjustable set point range-change constants
on increasing pressure from .05±.02 to 2 in wg.
Yes / No
201/DPT-01
Static Pressure Transmitter
Model: 1301-1142-0010-200, Brand: Trane, Origin: USA,
Yes / No
AHU-202
202/DTS-01
Duct Temperature & RH Transmitter
Model No: KFTF-U, Brand: Trane; Origin: USA. Pt 1k ohm, (375), 18” probe.
Yes / No
202/MV-01 3 Way Modulating Valve
Model No: H550B+NVD24-MFT2, Brand: Belimo, Origin-Switzerland. Medium temp: 5 - 120°C, Permissible pressure ps: 1600 kPa,
Yes / No
202/BV-01 Balancing Valve Brand: Danfoss, Model: MSV-BD, size: DN40, 1.5 inch, KVS: 26 m³/h, Max. Static working
Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 89 of 142
Instrument Verification MatrixTag/
Identification
Items Specification Result Comments
pressure: 20 bar, Max. Flow temperature: 130 °C, Min. temperature: -20 °C.
202/DPS-01
DP Switches for Motor
Model: DS-205_B, Brand: Trane, Origin: USA, Adjustable set point range-change constants
on increasing pressure from .05±.02 to 2 in wg.
Yes / No
202/DPT-01
Static Pressure Transmitter
Model: 1301-1142-0010-200, Brand: Trane, Origin: USA,
Yes / No
AHU-203
203/DTS-01
Duct Temperature & RH Transmitter
Model No: KFTF-U, Brand: Trane; Origin: USA. Pt 1k ohm, (375), 18” probe.
Yes / No
203/MV-01 3 Way Modulating Valve
Model No: H550B+NVD24-MFT2, Brand: Belimo, Origin-Switzerland. Medium temp: 5 - 120°C, Permissible pressure ps: 1600 kPa,
Yes / No
203/BV-01 Balancing Valve
Brand: Danfoss, Model: MSV-BD, size: DN50, 2 inch, KVS: 40m³/h, Max. Static working pressure: 20 bar, Max. Flow temperature: 130 °C Min. temperature: -20 °C,
Yes / No
203/DPS-01
DP Switches for Motor
Model: DS-205_B, Brand: Trane, Origin: USA, Adjustable set point range-change constants
on increasing pressure from .05±.02 to 2 in wg.
Yes / No
203/DPT-01 Static Pressure
TransmitterModel: 1301-1142-0010-200, Brand: Trane,
Origin: USA, Yes / No
AHU-204
204/DTS-01
Duct Temperature & RH Transmitter
Model No: KFTF-U, Brand: Trane; Origin: USA. Pt 1k ohm, (375), 18” probe.
Yes / No
204/MV-01 3 Way Modulating Valve
Model No: H550B+NVD24-MFT2, Brand: Belimo, Origin-Switzerland. Medium temp:
5 - 120°C, Permissible pressure ps: 1600 kPa,
Yes / No
204/BV-01 Balancing Valve
Brand: Danfoss, Model: MSV-BD, size: DN50, 2 inch, KVS: 40m³/h, Max. Static working pressure: 20 bar, Max. Flow temperature: 130 °C Min. temperature: -20 °C
Yes / No
204/DPS-01
DP Switches for Motor
Model: DS-205_B, Brand: Trane, Origin: USA, Adjustable set point range-change constants
on increasing pressure from .05±.02 to 2 in wg.
Yes / No
204/DPT-01
Static Pressure Transmitter
Model: 1301-1142-0010-200, Brand: Trane, Origin: USA,
Yes / No
AHU-205205/DTS-
01Duct Temperature & RH Transmitter
Model No: KFTF-U, Brand: Trane; Origin: USA. Pt 1k ohm, (375), 18” probe.
Yes / No
205/MV-01 3 Way Modulating Valve
Model No: H540B+NVD24-SR-T, Brand: Belimo, Origin-Switzerland. Medium temp:
Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 90 of 142
Instrument Verification MatrixTag/
Identification
Items Specification Result Comments
5 - 120°C, Permissible pressure ps: 1600 kPa,
205/BV-01 Balancing Valve
Brand: Danfoss, Model: MSV-BD, size: DN40, 1.5 inch, KVS: 26 m³/h, Max. Static working pressure: 20 bar, Max. Flow temperature: 130 °C, Min. temperature: -20 °C,
Yes / No
205/DPS-01
DP Switches for Motor
Model: DS-205_B, Brand: Trane, Origin: USA, Adjustable set point range-change constants
on increasing pressure from .05±.02 to 2 in wg.
Yes / No
205/DPT-01
Static Pressure Transmitter
Model: 1301-1142-0010-200, Brand: Trane, Origin: USA,
Yes / No
AHU-206206/DTS-
01Duct Temperature & RH Transmitter
Model No: KFTF-U, Brand: Trane; Origin: USA. Pt 1k ohm, (375), 18” probe.
Yes / No
206/MV-01 3 Way Modulating Valve
Model No: H550B+NVD24-MFT2, Brand: Belimo, Origin-Switzerland. Medium temp:
5 - 120°C, Permissible pressure ps: 1600 kPa,
Yes / No
206/BV-01 Balancing Valve
Brand: Danfoss, Model: MSV-BD, size: DN50, 2 inch, KVS: 40m³/h, Max. Static working pressure: 20 bar, Max. Flow temperature: 130 °C Min. temperature: -20 °C,
Yes / No
206/DPS-01
DP Switches for Motor
Model: DS-205_B, Brand: Trane, Origin: USA, Adjustable set point range-change constants
on increasing pressure from .05±.02 to 2 in wg.
Yes / No
206/DPT-01
Static Pressure Transmitter
Model: 1301-1142-0010-200, Brand: Trane, Origin: USA,
Yes / No
FAHU-101OA-01/DTS-01
Duct Temperature & RH Transmitter
Model No: KFTF-U, Brand: Trane; Origin: USA. Pt 1k ohm, (375), 18” probe.
Yes / No
OA-01/MV-01
3 Way Modulating Valve
Model No: H550B+NVD24-MFT2, Brand: Belimo, Origin-Switzerland. Medium temp:
5 - 120°C, Permissible pressure ps: 1600 kPa,
Yes / No
OA-01/BV-01 Balancing Valve
Brand: Danfoss, Model: MSV-BD, size: DN50, 2 inch, KVS: 40m³/h, Max. Static working pressure: 20 bar, Max. Flow temperature: 130 °C Min. temperature: -20 °C,
Yes / No
OA-01/DPS-01
DP Switches for Motor
Model: DS-205_B, Brand: Trane, Origin: USA, Adjustable set point range-change constants
on increasing pressure from .05±.02 to 2 in wg.
Yes / No
OA-01/DPT-01
Static Pressure Transmitter
Model: 1301-1142-0010-200, Brand: Trane, Origin: USA,
Yes / No
FAHU-201
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 91 of 142
Instrument Verification MatrixTag/
Identification
Items Specification Result Comments
OA-02/DTS-01
Duct Temperature & RH Transmitter
Model No: KFTF-U, Brand: Trane; Origin: USA. Pt 1k ohm, (375), 18” probe.
Yes / No
OA-02/MV-01
3 Way Modulating Valve
Model No: H550B+NVD24-MFT2, Brand: Belimo, Origin-Switzerland. Medium temp: 5 - 120°C, Permissible pressure ps: 1600 kPa,
Yes / No
OA-02/BV-01 Balancing Valve
Brand: Danfoss, Model: MSV-BD, size: DN50, 2 inch, KVS: 40m³/h, Max. Static working pressure: 20 bar, Max. Flow temperature: 130 °C Min. temperature: -20 °C,
Yes / No
OA-02/DPS-01
DP Switches for Motor
Model: DS-205_B, Brand: Trane, Origin: USA, Adjustable set point range-change constants
on increasing pressure from .05±.02 to 2 in wg.
Yes / No
OA-02/DPT-01 Static Pressure
TransmitterModel: 1301-1142-0010-200, Brand: Trane,
Origin: USA, Yes / No
OBSERVATIONS:
Test final result PASS FAILPerformed by Signature Date
Checked by Signature Date
Test 4- Utilities verification
a) OBJETIVE
Verify that the following utilities conform to manufacturer specifications when applicable: power supply, water pressure (chilled water), and check that the operative range of each service is appropriate to the correct operation of the equipment and its installation is suitable for required use.
b) METHODOLOGY
Verify that the services listed in the verification matrix are connected to the system.
Verify that service supplied is in accordance with the operative range required by the system.
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 92 of 142
c) ACCEPTANCE CRITERIA
All utilities are correctly installed and they have got all necessary ancillary elements for their correct use.
Operative ranges of utilities are appropriate for the equipment.
d) VERIFICATION REGISTER
Utilities Verification Matrix
User Equipment Service List Verification Result
AHU-102
Power supplyConnected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
Chilled water
Connected as per standard details of the AHU piping drawing (DRG. No. A.C-27). Yes / No
Operative range suitable for the system Yes / No
DEHUMIDIFIER-102 Power supply
Connected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
AHU-103
Power supplyConnected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
Chilled waterConnected as per standard details of the AHU piping drawing (DRG. No. A.C-28). Yes / No
Operative range suitable for the system Yes / No
DEHUMIDIFIER-103 Power supply
Connected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
AHU-104
Power supplyConnected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
Chilled water
Connected as per standard details of the AHU piping drawing (DRG. No. A.C-29). Yes / No
Operative range suitable for the system Yes / No
Operative range suitable for the system Yes / NoOperative range suitable for the system Yes / No
AHU-105 Power supplyConnected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 93 of 142
Utilities Verification Matrix
User Equipment Service List Verification Result
Chilled waterConnected as per standard details of the AHU piping drawing (DRG. No. A.C-30). Yes / No
Operative range suitable for the system Yes / No
AHU-106
Power supplyConnected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
Chilled waterConnected as per standard details of the AHU piping drawing (DRG. No. A.C-31). Yes / No
Operative range suitable for the system Yes / No
DEHUMIDIFIER-106 Power supply
Connected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
AHU-107
Power supplyConnected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
Chilled waterConnected as per standard details of the AHU piping drawing (DRG. No. A.C-32). Yes / No
Operative range suitable for the system Yes / No
DEHUMIDIFIER-107 Power supply
Connected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
AHU-108
Power supplyConnected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
Chilled waterConnected as per standard details of the AHU piping drawing (DRG. No. A.C-33). Yes / No
Operative range suitable for the system Yes / No
AHU-109
Power supplyConnected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
Chilled waterConnected as per standard details of the AHU piping drawing (DRG. No. A.C-34). Yes / No
Operative range suitable for the system Yes / No
DEHUMIDIFIER-109 Power supply
Connected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
AHU-201
Power supplyConnected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
Chilled waterConnected as per standard details of the AHU piping drawing (DRG. No. A.C-37). Yes / No
Operative range suitable for the system Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 94 of 142
Utilities Verification Matrix
User Equipment Service List Verification Result
AHU-202
Power supplyConnected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
Chilled waterConnected as per standard details of the AHU piping drawing (DRG. No. A.C-38). Yes / No
Operative range suitable for the system Yes / No
AHU-203
Power supplyConnected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
Chilled waterConnected as per standard details of the AHU piping drawing (DRG. No. A.C-39). Yes / No
Operative range suitable for the system Yes / No
DEHUMIDIFIER-203 Power supply
Connected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
AHU-204
Power supplyConnected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
Chilled waterConnected as per standard details of the AHU piping drawing (DRG. No. A.C-40). Yes / No
Operative range suitable for the system Yes / No
AHU-205
Power supplyConnected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
Chilled waterConnected as per standard details of the AHU piping drawing (DRG. No. A.C-41). Yes / No
Operative range suitable for the system Yes / No
AHU-206
Power supplyConnected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
Chilled waterConnected as per standard details of the AHU piping drawing (DRG. No. A.C-42). Yes / No
Operative range suitable for the system Yes / No
FCU-G01
Power supplyConnected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
Chilled water
Connected as per standard details of the AHU piping drawing (DRG. No. A.C-15). Yes / No
Operative range suitable for the system Yes / No
FCU-G02Power supply
Connected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
Chilled water Connected as per standard details of the AHU piping drawing (DRG. No. A.C-16). Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 95 of 142
Utilities Verification Matrix
User Equipment Service List Verification Result
Operative range suitable for the system Yes / No
FCU-G03
Power supplyConnected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
Chilled waterConnected as per standard details of the AHU piping drawing (DRG. No. A.C-17). Yes / No
Operative range suitable for the system Yes / No
FCU-G04
Power supplyConnected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
Chilled water
Connected as per standard details of the AHU piping drawing (DRG. No. A.C-18). Yes / No
Operative range suitable for the system Yes / No
FCU-G05
Power supplyConnected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
Chilled water
Connected as per standard details of the AHU piping drawing (DRG. No. A.C-19). Yes / No
Operative range suitable for the system Yes / No
FCU-G06
Power supplyConnected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
Chilled water
Connected as per standard details of the AHU piping drawing (DRG. No. A.C-20). Yes / No
Operative range suitable for the system Yes / No
FCU-G07
Power supply
Connected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
Chilled water
Connected as per standard details of the AHU piping drawing (DRG. No. A.C-21). Yes / No
Operative range suitable for the system Yes / No
FCU-G08
Power supply
Connected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
Chilled water
Connected as per standard details of the AHU piping drawing (DRG. No. A.C-22). Yes / No
Operative range suitable for the system Yes / No
FCU-G09Power supply Connected to the system with necessary
accessories Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 96 of 142
Utilities Verification Matrix
User Equipment Service List Verification Result
Operative range suitable for the system Yes / No
Chilled water
Connected as per standard details of the AHU piping drawing (DRG. No. A.C-23). Yes / No
Operative range suitable for the system Yes / No
FCU-G10
Power supply
Connected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
Chilled water
Connected as per standard details of the AHU piping drawing (DRG. No. A.C-24). Yes / No
Operative range suitable for the system Yes / No
FCU-101
Power supply
Connected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
Chilled water
Connected as per standard details of the AHU piping drawing (DRG. No. A.C-25). Yes / No
Operative range suitable for the system Yes / No
FCU-101.1
Power supply
Connected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
Chilled water
Connected as per standard details of the AHU piping drawing (DRG. No. A.C-26). Yes / No
Operative range suitable for the system Yes / No
FCU-101.2
Power supply
Connected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
Chilled water
Connected as per standard details of the AHU piping drawing (DRG. No. A.C-05). Yes / No
Operative range suitable for the system Yes / No
FCU-102
Power supply
Connected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
Chilled water
Connected as per standard details of the AHU piping drawing (DRG. No. A.C-35). Yes / No
Operative range suitable for the system Yes / No
FCU-103 Power supply
Connected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 97 of 142
Utilities Verification Matrix
User Equipment Service List Verification Result
Chilled water
Connected as per standard details of the AHU piping drawing (DRG. No. A.C-35). Yes / No
Operative range suitable for the system Yes / No
FCU-108
Power supply
Connected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
Chilled water
Connected as per standard details of the AHU piping drawing (DRG. No. A.C-33). Yes / No
Operative range suitable for the system Yes / No
FCU-201
Power supply
Connected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
Chilled water
Connected as per standard details of the AHU piping drawing (DRG. No. A.C-36). Yes / No
Operative range suitable for the system Yes / No
FCU-202
Power supply
Connected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
Chilled water
Connected as per standard details of the AHU piping drawing (DRG. No. A.C-43). Yes / No
Operative range suitable for the system Yes / No
FCU-203
Power supply
Connected to the system with necessary accessories Yes / No
Operative range suitable for the system Yes / No
Chilled water
Connected as per standard details of the AHU piping drawing (DRG. No. A.C-43). Yes / No
Operative range suitable for the system Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 98 of 142
Utilities Verification Matrix
User Equipment Service List Verification Result
OBSERVATIONS
Test final result PASS FAILPerformed by Signature Date
Checked by Signature Date
Test 5- Control system PLC software
a) OBJECTIVE
Characterized the hardware and software components of the control system installation, verifying that the components installed corresponds with existing technical documentation, and recording the following information for each one: designation, brand, and model.
b) METHODOLOGY
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 99 of 142
1. Complete the verification matrix for all hardware and software components with their location, tag, brand, and model.
2. Verified that all components have been installed and that their coding matches their characteristics.
c) ACCEPTANCE CRITERIA
Hardware and software components installed are properly identified.
Hard copy is available
d) VERIFICATION REGISTER
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
SERVERBrand HP Yes / NoModel HP Pro Micro Tower, Intel core-i3 Yes / No
Product No. QT035AV Yes / NoSerial No. SGH4VQ35AV Yes / NoLocation BMS ROOM Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 100 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
DDC PANEL - 01Brand: Trane Yes / NoModel: UC 400 & XM30 Yes / No
Field Device DDC Panel No.
Connecting with switch IP Address
Link between
DDC Panel and
Switch
Link Address
Actualresult
AHU102 DDC-11
Tracer SC 192.168.1.10
Link-1
12 Yes / No
AHU103 DDC-03 3 Yes / No
AHU104 DDC-10 11 Yes / No
AHU105 DDC-05 5 Yes / No
AHU106 DDC-12 25 Yes / No
AHU107 DDC-09 10 Yes / No
AHU109 DDC-08 9 Yes / No
FAHU (101 & 201) DDC-14
Link-2
25 Yes / No
CHILLER (01 &02) DDC-16 16 Yes / No
CHWP (01,02 &03) DDC-15 15 Yes / No
AHU201 DDC-01 1 Yes / No
AHU202 DDC-02 2 Yes / No
AHU203 DDC-13 6 Yes / No
AHU204 DDC-04 7 Yes / No
AHU205 DDC-06 21 Yes / No
AHU206 DDC-07 23 Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 101 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
Serial Number: BMUC400AAA0100011 & X13651537030 Yes / No
Location: AHU-201 Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 102 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
Field Device Description Point Detail UC-400
XM-30
Signal & port
no.Actual result
Differential pressure switch (Air)
Supply fan Run Status CEP.A201.SF.STS 1 BI-1 Yes /
No
Variable speed drive
Supply fan Start/ Stop Command to VSD CEP.A201.SF.SS 1 BO-1 Yes /
NoSupply fan Frequency
Indication from VSDCEP.A201.SF.IND 1 UI-2 Yes /
No
Supply Fan Trip Status to VSD CEP.A201.SF.TRP 1 BI-2 Yes /
NoFrequency
Command to VSDCEP.A201.SF.FRQ
CMD 1 AO-1 Yes / No
Static Pressure Transmitter
Supply Air Static Pressure CEP.A201.SA.STP 1 UI-1 Yes /
No
3-way Modulating Valve Chilled Water Valve Control
CEP.A201.CHW.CMD 1 AO-2 Yes /
No
Duct Temp. & RH Transmitter
Return Air Temperature
IndicationCEP.A201.RAT 1 UI-1 Yes /
No
Duct Temp. & RH Transmitter
Return Air RH Indication CEP.A201.RRH 1 UI-2 Yes /
No
Dust Collector-01
Relay Output(
VSD)
Start/ Stop Command CEP.A201.DC.SS 1 BO-2 Yes /
No
Potential Free
Contact(VSD)
Run Status CEP.A201.DC.RS 1 BI-3 Yes / No
VSD Trip Status CEP.A201.DC.TRP 1 UI-4 Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 103 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
DDC PANEL - 02Brand: Trane Yes / NoModel: UC 400 & XM30 Yes / No
Serial Number: BMUC400AAA0100011 & X13651537031 Yes / No
Location: AHU-202 Yes / No
Field Device Description Point Detail UC-400
XM-30
Signal & port
no.Actual result
Differential pressure switch (Air)
Supply fan Run Status CEP.A202.SF.STS 2 BI-1 Yes /
No
Variable speed drive
Supply fan Start/ Stop Command to VSD CEP.A202.SF.SS 2 BO-1 Yes /
NoSupply fan Frequency
Indication from VSDCEP.A202.SF.IND 1 UI-2 Yes /
No
Supply Fan Trip Status to VSD CEP.A202.SF.TRP 2 BI-2 Yes /
NoFrequency
Command to VSDCEP.A202.SF.FRQ
CMD 2 AO-1 Yes / No
Static Pressure Transmitter
Supply Air Static Pressure CEP.A202.SA.STP 1 UI-1 Yes /
No
3-way Modulating Valve Chilled Water Valve Control
CEP.A202.CHW.CMD 2 AO-2 Yes /
No
Duct Temp. & RH Transmitter
Return Air Temperature
IndicationCEP.A202.RAT 2 UI-1 Yes /
No
Duct Temp. & RH Transmitter
Return Air RH Indication CEP.A202.RRH 2 UI-2 Yes /
No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 104 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
DDC PANEL – 03
Brand: Trane Yes / No
Model: UC 400 & XM30 Yes / No
Serial Number: BMUC400AAA0100011 & X13651537033
Yes / No
Location: AHU-103 Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 105 of 142
Field Device Description Point Detail UC-400
XM-30
Signal & port
no.Actual result
Differential pressure switch (Air)
Supply fan Run Status CEP.A103.SF.STS 3 BI-1 Yes /
No
Variable speed drive
Supply fan Start/ Stop Command to VSD CEP.A103.SF.SS 3 BO-1 Yes /
NoSupply fan Frequency
Indication from VSDCEP.A103.SF.IND 1 UI-2 Yes /
No
Supply Fan Trip Status to VSD CEP.A103.SF.TRP 3 BI-2 Yes /
NoFrequency
Command to VSDCEP.A103.SF.FRQ
CMD 3 AO-1 Yes / No
Static Pressure Transmitter
Supply Air Static Pressure CEP.A103.SA.STP 1 UI-1 Yes /
No
3-way Modulating Valve Chilled Water Valve Control
CEP.A103.CHW.CMD 3 AO-2 Yes /
No
Duct Temp. & RH Transmitter
Return Air Temperature
IndicationCEP.A103.RAT 3 UI-1 Yes /
No
Duct Temp. & RH Transmitter
Return Air RH Indication CEP.A103.RRH 3 UI-2 Yes /
No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 106 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
DDC PANEL - 04Brand: Trane Yes / NoModel: UC 400 & XM30 Yes / No
Serial Number: BMUC400AAA0100011 & X13651537034 Yes / No
Location: AHU-204 Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 107 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
Field Device Description Point Detail UC-400
XM-30
Signal & port
no.Actual result
Differential pressure switch (Air)
Supply fan Run Status CEP.A204.SF.STS 4 BI-1 Yes /
No
Variable speed drive
Supply fan Start/ Stop Command to VSD CEP.A204.SF.SS 4 BO-1 Yes /
NoSupply fan Frequency
Indication from VSDCEP.A204.SF.IND 1 UI-2 Yes /
No
Supply Fan Trip Status to VSD CEP.A204.SF.TRP 4 BI-2 Yes /
NoFrequency
Command to VSDCEP.A204.SF.FRQ
CMD 4 AO-1 Yes / No
Static Pressure Transmitter
Supply Air Static Pressure CEP.A204.SA.STP 1 UI-1 Yes /
No
3-way Modulating Valve Chilled Water Valve Control
CEP.A204.CHW.CMD 4 AO-2 Yes /
No
Duct Temp. & RH Transmitter
Return Air Temperature
IndicationCEP.A204.RAT 4 UI-1 Yes /
No
Duct Temp. & RH Transmitter
Return Air RH Indication CEP.A204.RRH 4 UI-2 Yes /
No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 108 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
DDC PANEL - 05Brand: Trane Yes / NoModel: UC 400 & XM30 Yes / No
Serial Number: BMUC400AAA0100011 & X13651537035 Yes / No
Location: AHU-105 Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 109 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
Field Device Description Point Detail UC-400
XM-30
Signal & port
no.Actual result
Differential pressure switch (Air)
Supply fan Run Status CEP.A105.SF.STS 5 BI-1 Yes /
No
Variable speed drive
Supply fan Start/ Stop Command to VSD CEP.A105.SF.SS 5 BO-1 Yes /
NoSupply fan Frequency
Indication from VSDCEP.A105.SF.IND 1 UI-2 Yes /
No
Supply Fan Trip Status to VSD CEP.A105.SF.TRP 5 BI-2 Yes /
NoFrequency
Command to VSDCEP.A105.SF.FRQ
CMD 5 AO-1 Yes / No
Static Pressure Transmitter
Supply Air Static Pressure CEP.A105.SA.STP 1 UI-1 Yes /
No
3-way Modulating Valve Chilled Water Valve Control
CEP.A105.CHW.CMD 5 AO-2 Yes /
No
Duct Temp. & RH Transmitter
Return Air Temperature
IndicationCEP.A105.RAT 5 UI-1 Yes /
No
Duct Temp. & RH Transmitter
Return Air RH Indication CEP.A105.RRH 5 UI-2 Yes /
No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 110 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
DDC PANEL - 06Brand: Trane Yes / NoModel: UC 400 & XM30 Yes / No
Serial Number: BMUC400AAA0100011 & X13651537036 Yes / NoLocation: AHU-205 Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 111 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
Field Device Description Point Detail UC-400
XM-30
Signal & port
no.Actual result
Differential pressure switch (Air)
Supply fan Run Status CEP.A205.SF.STS 6 BI-1 Yes /
No
Variable speed drive
Supply fan Start/ Stop Command to VSD CEP.A205.SF.SS 6 BO-1 Yes /
NoSupply fan Frequency
Indication from VSDCEP.A205.SF.IND 1 UI-2 Yes /
No
Supply Fan Trip Status to VSD CEP.A205.SF.TRP 6 BI-2 Yes /
NoFrequency
Command to VSDCEP.A205.SF.FRQ
CMD 6 AO-1 Yes / No
Static Pressure Transmitter
Supply Air Static Pressure CEP.A205.SA.STP 1 UI-1 Yes /
No
3-way Modulating Valve Chilled Water Valve Control
CEP.A205.CHW.CMD 6 AO-2 Yes /
No
Duct Temp. & RH Transmitter
Return Air Temperature
IndicationCEP.A205.RAT 6 UI-1 Yes /
No
Duct Temp. & RH Transmitter
Return Air RH Indication CEP.A205.RRH 6 UI-2 Yes /
No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 112 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
DDC PANEL - 07Brand: Trane Yes / NoModel: UC 400 & XM30 Yes / No
Serial Number: BMUC400AAA0100011 & X13651537037 Yes / NoLocation: AHU-206 Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 113 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
Field Device Description Point Detail UC-400
XM-30
Signal & port
no.Actual result
Differential pressure switch (Air)
Supply fan Run Status CEP.A206.SF.STS 7 BI-1 Yes /
No
Variable speed drive
Supply fan Start/ Stop Command to
VSDCEP.A206.SF.SS 7 BO-1 Yes /
No
Supply fan Frequency
Indication from VSD
CEP.A206.SF.IND 1 UI-2 Yes / No
Supply Fan Trip Status to VSD CEP.A206.SF.TRP 7 BI-2 Yes /
NoFrequency
Command to VSD CEP.A206.SF.FRQCMD 7 AO-1 Yes / No
Static Pressure Transmitter
Supply Air Static Pressure CEP.A206.SA.STP 1 UI-1 Yes /
No3-way Modulating
ValveChilled Water Valve
Control CEP.A206.CHW.CMD 7 AO-2 Yes / No
Duct Temp. & RH Transmitter
Return Air Temperature
IndicationCEP.A206.RAT 7 UI-1 Yes /
No
Duct Temp. & RH Transmitter
Return Air RH Indication CEP.A206.RRH 7 UI-2 Yes /
No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 114 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
DDC PANEL - 08Brand: Trane Yes / NoModel: UC 400 & XM30 Yes / No
Serial Number: BMUC400AAA0100011 & X13651537038 Yes / NoLocation: AHU-109 Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 115 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
Field Device Description Point Detail UC-400
XM-30
Signal & port
no.Actual result
Differential pressure switch (Air)
Supply fan Run Status CEP.A109.SF.STS 8 BI-1 Yes /
No
Variable speed drive
Supply fan Start/ Stop Command to VSD CEP.A109.SF.SS 8 BO-1 Yes /
NoSupply fan Frequency
Indication from VSDCEP.A109.SF.IND 1 UI-2 Yes /
No
Supply Fan Trip Status to VSD CEP.A109.SF.TRP 8 BI-2 Yes /
NoFrequency
Command to VSDCEP.A109.SF.FRQ
CMD 8 AO-1 Yes / No
Static Pressure Transmitter
Supply Air Static Pressure CEP.A109.SA.STP 1 UI-1 Yes /
No
3-way Modulating Valve Chilled Water Valve Control
CEP.A109.CHW.CMD 8 AO-2 Yes /
No
Duct Temp. & RH Transmitter
Return Air Temperature
IndicationCEP.A109.RAT 8 UI-1 Yes /
No
Duct Temp. & RH Transmitter
Return Air RH Indication CEP.A109.RRH 8 UI-2 Yes /
No
Dehumidifier
Start/Stop Relay Output CEP.A108.DHM.SS 8 BO-2 Yes / No
Run indignatio
n
Differential Pressure Switch (Air)
CEP.A108.DHM.STS 8 BI-3 Yes /
No
Return Air Temp.
Indication
Duct Temp. & RH Transmitter
CEP.A109.DHM.RAT 1 UI-3 Yes /
No
Return Air RH
Indication
Duct Temp. & RH Transmitter CEP.A109.DHM.R
RH 1 UI-4 Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 116 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
DDC PANEL - 09Brand: Trane Yes / NoModel: UC 400 & XM30 Yes / No
Serial Number: BMUC400AAA0100011 & X13651537039 Yes / NoLocation: AHU-107 Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 117 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
Field Device Description Point Detail UC-400
XM-30
Signal & port
no.Actual result
Differential pressure switch (Air)
Supply fan Run Status CEP.A107.SF.STS 9 BI-1 Yes /
No
Variable speed drive
Supply fan Start/ Stop Command to VSD CEP.A107.SF.SS 9 BO-1 Yes /
NoSupply fan Frequency
Indication from VSDCEP.A107.SF.IND 1 UI-2 Yes /
No
Supply Fan Trip Status to VSD CEP.A107.SF.TRP 9 BI-2 Yes /
NoFrequency
Command to VSDCEP.A107.SF.FRQ
CMD 9 AO-1 Yes / No
Static Pressure Transmitter
Supply Air Static Pressure CEP.A107.SA.STP 1 UI-1 Yes /
No
3-way Modulating Valve Chilled Water Valve Control
CEP.A107.CHW.CMD 9 AO-2 Yes /
No
Duct Temp. & RH Transmitter
Return Air Temperature
IndicationCEP.A107.RAT 9 UI-1 Yes /
No
Duct Temp. & RH Transmitter
Return Air RH Indication CEP.A107.RRH 9 UI-2 Yes /
No
Dehumidifier
Start/Stop Relay Output CEP.A107.DHM.SS 9 BO-2 Yes / No
Run indignatio
n
Differential Pressure Switch (Air)
CEP.A107.DHM.STS 9 BI-3 Yes /
No
Return Air Temp.
Indication
Duct Temp. & RH Transmitter
CEP.A107.DHM.RAT 1 UI-3 Yes /
No
Return Air RH
Indication
Duct Temp. & RH Transmitter CEP.A107.DHM.R
RH 1 UI-4 Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 118 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
DDC PANEL - 10Brand: Trane Yes / NoModel: UC 400 & XM30 Yes / No
Serial Number: BMUC400AAA0100011 & X13651537040 Yes / NoLocation: AHU-104 Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 119 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
Field Device Description Point Detail UC-400
XM-30
Signal & port
no.Actual result
Differential pressure switch (Air)
Supply fan Run Status CEP.A104.SF.STS 10 BI-1 Yes /
No
Variable speed drive
Supply fan Start/ Stop Command to VSD CEP.A104.SF.SS 10 BO-1 Yes /
NoSupply fan Frequency
Indication from VSDCEP.A104.SF.IND 1 UI-2 Yes /
No
Supply Fan Trip Status to VSD CEP.A104.SF.TRP 10 BI-2 Yes /
NoFrequency
Command to VSDCEP.A104.SF.FRQ
CMD 10 AO-1 Yes / No
Static Pressure Transmitter
Supply Air Static Pressure CEP.A104.SA.STP 1 UI-1 Yes /
No
3-way Modulating Valve Chilled Water Valve Control
CEP.A104.CHW.CMD 10 AO-2 Yes /
No
Duct Temp. & RH Transmitter
Return Air Temperature
IndicationCEP.A104.RAT 10 UI-1 Yes /
No
Duct Temp. & RH Transmitter
Return Air RH Indication CEP.A104.RRH 10 UI-2 Yes /
No
Dehumidifier
Start/Stop Relay Output CEP.A104.DHM.SS 10 BO-2 Yes / No
Run indignatio
n
Differential Pressure Switch (Air)
CEP.A104.DHM.STS 10 BI-3 Yes /
No
Return Air Temp.
Indication
Duct Temp. & RH Transmitter
CEP.A104.DHM.RAT 1 UI-3 Yes /
No
Return Air RH
Indication
Duct Temp. & RH Transmitter CEP.A104.DHM.R
RH 1 UI-4 Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 120 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
DDC PANEL - 11Brand: Trane Yes / NoModel: UC 400 & XM30 Yes / No
Serial Number: BMUC400AAA0100011 & X13651537041 Yes / NoLocation: AHU-102 Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 121 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
Field Device Description Point Detail UC-400
XM-30
Signal & port no.
Actual result
Differential pressure switch (Air)
Supply fan Run Status CEP.A102.SF.STS 11 BI-1 Yes /
No
Variable speed drive
Supply fan Start/ Stop Command to
VSDCEP.A102.SF.SS 11 BO-1 Yes /
No
Supply fan Frequency
Indication from VSD
CEP.A102.SF.IND 1 UI-2 Yes / No
Supply Fan Trip Status to VSD CEP.A102.SF.TRP 11 BI-2 Yes /
NoFrequency
Command to VSD
CEP.A102.SF.FRQCMD 11 AO-1 Yes /
No
Static Pressure Transmitter
Supply Air Static Pressure CEP.A102.SA.STP 1 UI-1 Yes /
No
3-way Modulating Valve Chilled Water Valve Control
CEP.A102.CHW.CMD 11 AO-2 Yes /
No
Duct Temp. & RH Transmitter
Return Air Temperature
IndicationCEP.A102.RAT 11 UI-1 Yes /
No
Duct Temp. & RH Transmitter
Return Air RH Indication CEP.A102.RRH 11 UI-2 Yes /
No
Dehumidifier
Start/Stop Relay Output CEP.A102.DHM.SS 11 BO-2 Yes / No
Run indignation
Differential Pressure Switch
(Air)CEP.A102.DHM.STS 11 BI-3 Yes /
No
Return Air Temp.
Indication
Duct Temp. & RH Transmitter CEP.A102.DHM.RAT 1 UI-3 Yes /
No
Return Air RH
Indication
Duct Temp. & RH Transmitter CEP.A102.DHM.RRH 1 UI-4 Yes /
No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 122 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
DDC PANEL - 12Brand: Trane Yes / NoModel: UC 400 & XM30 Yes / No
Serial Number: BMUC400AAA0100011 & X13651537042 Yes / NoLocation: AHU-106 Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 123 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
Field Device Description Point Detail UC-400
XM-30
Signal & port no.
Actual result
Differential pressure switch (Air) Supply fan Run Status CEP.A106.SF.ST
S 12 BI-1
Yes / No
Variable speed drive
Supply fan Start/ Stop Command to VSD CEP.A106.SF.SS 12 BO-1
Yes / No
Supply fan Frequency Indication from VSD CEP.A106.SF.IND 1 UI-2
Yes / No
Supply Fan Trip Status to VSD
CEP.A106.SF.TRP 12 BI-2
Yes / No
Frequency Command to VSD
CEP.A106.SF.FRQCMD 12 AO-1
Yes / No
Static Pressure Transmitter
Supply Air Static Pressure
CEP.A106.SA.STP 1 UI-1
Yes / No
3-way Modulating Valve Chilled Water Valve Control
CEP.A106.CHW.CMD 12 AO-2
Yes / No
Duct Temp. & RH Transmitter
Return Air Temperature
IndicationCEP.A106.RAT 12 UI-1
Yes / No
Duct Temp. & RH Transmitter
Return Air RH Indication CEP.A106.RRH 12 UI-2
Yes / No
Dehumidifier
Start/Stop Relay Output CEP.A106.DHM.SS 12 BO-2
Yes / No
Run indignatio
n
Differential Pressure Switch (Air)
CEP.A106.DHM.STS 12 BI-3
Yes / No
Return Air Temp.
Indication
Duct Temp. & RH Transmitter
CEP.A106.DHM.RAT 1 UI-3
Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 124 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
DDC PANEL - 13Brand: Trane Yes / NoModel: UC 400 & XM30 Yes / No
Serial Number: BMUC400AAA0100011 & X13651537043 Yes / NoLocation: AHU-203 Yes / No
Field Device Description Point Detail UC-400
XM-30
Signal & port no.
Actual result
Differential pressure switch (Air) Supply fan Run Status CEP.A106.SF.ST
S 12 BI-1
Yes / No
Variable speed drive
Supply fan Start/ Stop Command to VSD CEP.A106.SF.SS 12 BO-1
Yes / No
Supply fan Frequency Indication from VSD CEP.A106.SF.IND 1 UI-2
Yes / No
Supply Fan Trip Status to VSD
CEP.A106.SF.TRP 12 BI-2
Yes / No
Frequency Command to VSD
CEP.A106.SF.FRQCMD 12 AO-1
Yes / No
Static Pressure Transmitter
Supply Air Static Pressure
CEP.A106.SA.STP 1 UI-1
Yes / No
3-way Modulating Valve Chilled Water Valve Control
CEP.A106.CHW.CMD 12 AO-2
Yes / No
Duct Temp. & RH Transmitter
Return Air Temperature
IndicationCEP.A106.RAT 12 UI-1
Yes / No
Duct Temp. & RH Transmitter
Return Air RH Indication CEP.A106.RRH 12 UI-2
Yes / No
Dehumidifier
Start/Stop Relay Output CEP.A106.DHM.SS 12 BO-2
Yes / No
Run indignatio
n
Differential Pressure Switch (Air)
CEP.A106.DHM.STS 12 BI-3
Yes / No
Return Air Temp.
Indication
Duct Temp. & RH Transmitter
CEP.A106.DHM.RAT 1 UI-3
Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 125 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
Field Device Description Point Detail UC-400
XM-30
Signal & port
no.Actual result
Differential pressure switch (Air) Supply fan Run Status CEP.A203.SF.STS 13 BI-1 Yes /
No
Variable speed drive
Supply fan Start/ Stop Command to VSD CEP.A203.SF.SS 13 BO-1 Yes /
NoSupply fan Frequency Indication from VSD CEP.A203.SF.IND 1 UI-2 Yes /
NoSupply Fan Trip Status to VSD CEP.A203.SF.TRP 13 BI-2 Yes /
NoFrequency Command
to VSDCEP.A203.SF.FRQ
CMD 13 AO-1 Yes / No
Static Pressure Transmitter
Supply Air Static Pressure CEP.A203.SA.STP 1 UI-1 Yes /
No
3-way Modulating Valve Chilled Water Valve Control
CEP.A203.CHW.CMD 13 AO-2 Yes /
No
Duct Temp. & RH Transmitter
Return Air Temperature
IndicationCEP.A203.RAT 13 UI-1 Yes /
No
Duct Temp. & RH Transmitter
Return Air RH Indication CEP.A203.RRH 13 UI-2 Yes /
No
Dehumidifier
Start/Stop Relay Output CEP.A203.DHM.SS 13 BO-2 Yes / No
Run indignatio
n
Differential Pressure Switch (Air)
CEP.A203.DHM.STS 13 BI-3 Yes /
No
Return Air Temp.
Indication
Duct Temp. & RH Transmitter
CEP.A203.DHM.RAT 1 UI-3 Yes /
No
Return Air RH
Indication
Duct Temp. & RH Transmitter CEP.A203.DHM.R
RH 1 UI-4 Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 126 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
DDC PANEL - 14Brand: Trane Yes / NoModel: UC 400 & XM30 Yes / No
Serial Number: BMUC400AAA0100011 & X13651537010 Yes / NoLocation: FAHU-01 Yes / No
Field Device Description Point Detail UC-400
XM-30
Signal & port
no.Actual result
Differential pressure switch (Air)
Supply fan Run Status CEP.FA01.SF.STS 14 BI-3 Yes /
No
Relay OutputSupply fan Start/
Stop Command to VSD
CEP.FA01.SF.SS 14 BO-1 Yes / No
Variable speed drive
Supply fan Frequency
Indication from VSDCEP.FA01.SF.IND 14 UI-1 Yes /
No
Supply Fan Trip Status to VSD CEP.FA01.SF.TRP 14 BI-2 Yes /
NoFrequency
Command to VSD CEP.FA01.SF.FRQCMD 14 AO-1 Yes / No
Duct Temp sensor Supply Air Temperature
IndicationCEP.FA01.RAT 14 AI-2 Yes /
No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 127 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
DDC PANEL - 14Brand: Trane Yes / NoModel: UC 400 & XM30 Yes / No
Serial Number: BMUC400AAA0100011 & X13651537044 Yes / NoLocation: FAHU-02 Yes / No
Field Device Description Point Detail UC-400
XM-30
Signal & port
no.Actual result
Differential pressure switch (Air)
Supply fan Run Status CEP.FA01.SF.STS 14 BI-1 Yes /
No
Relay OutputSupply fan Start/
Stop Command to VSD
CEP.FA01.SF.SS 14 BO-2 Yes / No
Variable speed drive
Frequency Indication from
VSDCEP.FA01.SF.IND (16) 2 UI-1 Yes /
No
Supply Fan Trip Status to VSD CEP.FA01.SF.TRP 14 UI-2 Yes /
NoFrequency
Command to VSD CEP.FA01.SF.FRQCMD 14 AO-2 Yes / No
Duct Temp sensor Supply Air Temperature
IndicationCEP.FA01.RAT 14 AI-1 Yes /
No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 128 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
DDC PANEL - 15Brand: Trane Yes / NoModel: UC 400 & XM30 Yes / No
Serial Number: BMUC400AAA0100011 & X13651537045 Yes / NoLocation: Chilled Water Pump 1, 2 & 3 Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 129 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
Field Device Description Point Detail UC-400
XM-30
Signal & port
no.Actual result
Chilled Water
Pump-01
Relay Output Chilled Water Pump
Start/Stop Command
CEP. CWP1.CHWP.SS 15 BO-1 Yes / No
Differential Press. Switch (Water)
Chilled Water Pump Run
StatusCEP. CWP1.CHWP.RS 15 BI-1 Yes
/ No
Potential Free Contact
Chilled Water Pump Trip
statusCEP. CWP1.CHWP.TRP 15 BI-2 Yes
/ No
Chilled Water
Pump-02
Potential Free Contact
Chilled Water Pump
Start/Stop Command
CEP. CWP2.CHWP.SS 15 BO-2 Yes / No
Differential Press. Switch (Water)
Chilled Water Pump Run
StatusCEP. CWP2.CHWP.RS 1 UI-2 Yes
/ No
Potential Free Contact
Chilled Water Pump Trip
statusCEP. CWP2.CHWP.TRP 1 UI-1 Yes
/ No
Chilled Water Pump-03
Potential Free Contact
Chilled Water Pump
Start/Stop Command
CEP. CWP3.CHWP.SS 15 BO-3 Yes / No
Differential Press. Switch (Water)
Chilled Water Pump Run
StatusCEP. CWP3.CHWP.RS 15 BI-3 Yes
/ No
Potential Free Chilled Water Yes
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 130 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
DDC PANEL - 16Brand: Trane Yes / NoModel: UC 400 & XM30 Yes / No
Serial Number: BMUC400AAA0100011 & X13651537046 Yes / NoLocation: Chiller-01 Yes / No
Field Device Description Point Detail UC-400
XM-30
Signal & port
no.Actual result
Chilled Water
Pump-01
Relay Output Chilled Water Pump
Start/Stop Command
CEP. CWP1.CHWP.SS 15 BO-1 Yes / No
Differential Press. Switch (Water)
Chilled Water Pump Run
StatusCEP. CWP1.CHWP.RS 15 BI-1 Yes
/ No
Potential Free Contact
Chilled Water Pump Trip
statusCEP. CWP1.CHWP.TRP 15 BI-2 Yes
/ No
Chilled Water
Pump-02
Potential Free Contact
Chilled Water Pump
Start/Stop Command
CEP. CWP2.CHWP.SS 15 BO-2 Yes / No
Differential Press. Switch (Water)
Chilled Water Pump Run
StatusCEP. CWP2.CHWP.RS 1 UI-2 Yes
/ No
Potential Free Contact
Chilled Water Pump Trip
statusCEP. CWP2.CHWP.TRP 1 UI-1 Yes
/ No
Chilled Water Pump-03
Potential Free Contact
Chilled Water Pump
Start/Stop Command
CEP. CWP3.CHWP.SS 15 BO-3 Yes / No
Differential Press. Switch (Water)
Chilled Water Pump Run
StatusCEP. CWP3.CHWP.RS 15 BI-3 Yes
/ No
Potential Free Chilled Water Yes
Field Device Description Point Detail UC-400
XM-30
Signal & port
no.Actual result
Water Flow Switch Chilled Water Flow Confirmation
CEP. CHLR01.CHWF.CNFRMTN 2 UI-2 Yes /
No
Chiller Panel
Chiller On/Off Control CEP.CHLR01.CP.CNTRL 16 BO-1 Yes /
NoChiller Compressor 1
Run Status CEP.CHLR01.CMPRSR1.RS 16 BI-1 Yes / No
Chiller Compressor 2 Run Status CEP.CHLR01.CMPRSR2.RS 16 BI-2 Yes /
No
Chiller Fault Status CEP.CHLR01.CP.FLT 16 BI-3 Yes / No
2 Way On-Off Butterfly Valve
Chilled Water Supply Valve Command CEP.CHLR01.CHW.CMD 16 BO-2 Yes /
No
Position Feedback from the above
Chilled Water Supply Valve Status CEP.CHLR01.CHWSV.STS 1 UI-3 Yes /
No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 131 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
DDC PANEL - 16Brand: Trane Yes / NoModel: UC 400 & XM30 Yes / No
Serial Number: BMUC400AAA0100011 & X13651537046 Yes / NoLocation: Chiller-02 Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 132 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
Field Device Description Point Detail UC-400
XM-30
Signal & port
no.Actual result
Water Flow Switch Chilled Water Flow Confirmation
CEP. CHLR02.CHWF.CNFRM
TN1 UI-1 Yes /
No
Chiller Panel
Chiller On/Off Control
CEP.CHLR02.CP.CNTRL 16 BO-3 Yes /
NoChiller Compressor
1 Run StatusCEP.CHLR02.CMPRSR
1.RS 16 UI-1 Yes / No
Chiller Compressor 2 Run Status
CEP.CHLR02.CMPRSR2.RS 16 UI-2 Yes /
No
Chiller Fault Status CEP.CHLR02.CP.FLT 16 UI-3 Yes / No
2 Way On-Off Butterfly Valve
Chilled Water Supply Valve
CommandCEP.CHLR02.CHW.CM
D 14 BO-3 Yes / No
Position Feedback from the above
Chilled Water Supply Valve Status CEP.CHLR02.CHWSV.
STS 1 UI-2 Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 133 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
DDC PANEL - 16Brand: Trane Yes / NoModel: UC 400 & XM30 Yes / No
Serial Number: BMUC400AAA0100011 & X13651537046 Yes / NoLocation: Chilled Water Common Point Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 134 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
Field Device Description Point Detail UC-400
XM-30
Signal & port
no.Actual result
Immersion Temperature Sensor
Chiller Supply Header
Temperature CEP. CWCP.CHSH.TEMP 16 AI-1 Yes / No
Immersion Temperature Sensor
Chiller Return Header
Temperature CEP. CWCP.CHRH.TEMP 16 AI-2 Yes / No
Space Temp. & Humidity Sensor
Ambient Air Temperature CEP. CWCP.STHS.AATEMP (15) 1 UI-3 Yes /
No
Space Temp. & Humidity Sensor
Ambient Air Relative Humidity CEP. CWCP.STHS.AARH (15) 1 UI-4 Yes /
No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 135 of 142
Control System PLC HARDWARE/SOFTWAREComponent Verification Comments Result
OBSERVATIONS:
Test final result PASS FAILPerformed by Signature Date
Checked by Signature Date
Test 6- Operating & Maintenance (O & M) Manual Check.
e) OBJECTIVE:
Provide documentary evidence that HVAC system have been installed and are correctly identified in accordance with existent installation drawings (As built diagrams and schemes).
f) METHODOLOGY
1. Obtain a copy of the latest version of operation & maintenance manual.
2. Once the verification has been finished, the technician/s that have perform the test must write in the “operation & maintenance manual” “Verified in Installation Qualification”, the date and signature. 3. The “manuals” will be attached to this protocol.
g) ACCEPTANCE CRITERIA:
“Manual” reflects the real the installation exactly (all disagreement between drawings and installation must be justified).
The instruction of operation & maintenance can be done exactly what written.
The access for operations and maintenance works is easy.
h) VERIFICATION REGISTER
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 136 of 142
Register Verification MatrixOperation & Maintenance Manual Result Comments
AHU Yes / No
Chiller Yes / No
Pump Yes / No
Verification Result Comments
Manual exactly reflect the installation Yes / No
Operation can be done as manual instructed Yes / No
Maintenance can be done as manual instruct Yes / No
The access of operation & maintenance is easy Yes / No
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 137 of 142
OBSERVATIONS:
Test final result PASS FAILPerformed by Signature Date
Checked by Signature Date
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 138 of 142
5 SUMMARY OF TEST PERFORMED
Summary of verificationTest Name Comments Result
P/ F P/ F P/ F P/ F P/ F P/ F P/ F P/ F P/ F P/ F P/ F P/ F P/ F
OBSERVATIONS:
Performed by Signature Date
Checked by Signature Date
Reviewed by Signature Date
6 FINAL REPORT
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 139 of 142
INSTALLATION QUALIFICATION HVAC REPORT
Non-conformities register:
Test number Description Resolution(Date and signature)
Critical Non Critical Critical Non Critical Critical Non Critical Critical Non Critical
Conclusions:
Additional information attached:
The signature of the present document implies the complete revision of the protocol and the revision of all the data that support the tests.
Result: PASS FAIL
Prepared by: Department: Date: Signature:
Reviewed by: Department: Date: Signature:
Approved by: Department: Date: Signature:
7 ANNEX I: LIST OF DEVIATIONS AND/OR FURTHER ACTIONS
Ref. No.: Test:
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 140 of 142
Description:
Registered By: Signature: Date:
Investigation:
Evaluation: Critical (It stops Validation) No critical (Validation goes on)
Registered By: Signature: Date:
Corrective Action Proposal:
Action responsible: Expected Date:
Registered By: Signature: Date:
Approved by Signature: Date:
Solved satisfactorily? (Yes / No / N.A.): ClosedComments:
Executed by: Signature: Date:
Approved by Signature: Date:
List & Deviations AND/OR Further action
No Deviation/Further Action Test Responsible for closure Deviation
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 141 of 142
Complete
8.0 List & Appendix
No Details Protocol Ref.
9.0 Approvals
9.1 Interim Approval
CONFIDENCE TRADE LIMITED
DRUG INTERNATIONAL LTD. (UNIT-2)
INSTALLATION QUALIFICATION OF HVAC SYSTEM FOR PRODUCTION FLOOR (Gr., 1st and 2nd Floor) OF CEPHALOSPORIN
Doc. No: Rev No: Rev. Date: Page:IQP/CON/01 01 08.04.2015 Page 142 of 142
Name Position Signature Date
Comments:
9.2 Final Approval
Name Position Signature Date