iPRO Series - Sterowniki Dixell - DXL Sp. z o.o. (Dixell Can Protocol, not open) RS232 Config...

36
iPRO Series Pieve d’Alpago June 2015

Transcript of iPRO Series - Sterowniki Dixell - DXL Sp. z o.o. (Dixell Can Protocol, not open) RS232 Config...

iPRO Series

Pieve d’Alpago – June 2015

It is an hardware and software system, dedicated to regulate and

control a large number of applications

The main characteristic is that it can be programmed by people with

experienced in final application but not a specific experience in

programming

For Dixell, the Programmable Controller project has been designed

and developed as a new concept of configurable hardware, looking

at the same time to find the best environment to develop

applications

Introduction

iPro FAMILY

• Powerful Modular Platform

• High Flexibility/Expandibility

• High Connectivity

• Easy and Useful HMI

• Easy and Fast Programming Tools

Programmable Digital Controllers Applicable to:

REFRIGERATION – RETAIL – BMS – HVAC Markets

High Flexibility & Expandability

EEV Driver Connettivity Module Expansion Module

iPro FAMILY

High Connectivity

High Connectivity

iPro FAMILY - Easy and Useful HMI

iPro FAMILY

Touch Screen Visograph

• CPU: ARM9 200Mhz – LINUX 2.6 Operating System

• 80 MB of free memory flash – 10 DIN format & IPL

4 MB of free memory flash – 4 DIN format

• 24 Vac-dc power-supply

• Up to 10 ANALOG INPUTs

• Up to 6 ANALOG OUTPUTs

• Up to 20 DIGITAL INPUTs

• Up to 15 DIGITAL OUTPUTs

The Analog Input and the Analog Output can be configured as Digital Input and

Digital Output.

Main Features

ISaGRAF® VISOPROG

iPro Hardware that control

the application

Visograph &

Visotouch User interace for the

applications

Visoprog Software to develop

the Visograph

& Visotouch

application

Web Server The integrated web

server lets the

development of a

custom website

Function Blocks

and Templates Dixell provide a lot of FB

usable for applications

ISaGRAF® Environment to develop

the iPro application

About Programmable Controller Structure

ARCHITECTURE AND DEVELOPMENT TOOLS

• IPG series

• IPC series

• IPR series

• IPL series

• IPX series

Programmable

version 10 or 4 DIN

rail

No application

inside

Chiller – Heat Pump

application Dixell application

Rack Controller

application Dixell application

Expansion Modules

10 or 4 DIN rail

Programmable

connectivity module

No application

inside

iPro RANGE

iPro RANGE

iPRO Programmable Controllers

iPro

GENIUS

IPG115D IPG215D

TF20D

DWB-30KIT

TF20D

IP-FC215CP

IP-FC215CT

IPC115D IPC315D IPC108D

IPC108E

TF20D

DWB-30KIT

TF20D

DWB-315KIT

IP-FC315

TF40D

DWS-30KIT

IP-FC108

USB-ETH-CONV

iPro

CHILL

Without

application

Black White

Bayonet

Screw

Black

With

chiller application

IPG315D

TF20D

DWB-315KIT

IP-FC315

IPG108D

IPG108E

TF40D

DWS-30KIT

IP-FC108

USB-ETH-CONV

IPG208D

IPG208E

TF40D

IP-FC208

USB-ETH-CONV

White

Disconnectable

Screw

Disconnectable

Screw

White Black Black Black

Bayonet

Screw

Disconnectable

Molex

Disconnectable

Screw

Disconnectable

Molex

Disconnectable

Molex

Black

Screw

IPL500D

TF20D

IP-FC500

iPro

LINK

Black

IPR215D

TF20D

IP-FC215CP

IP-FC215CT

iPro

RACK

Bayonet

Screw

Without

application

With rack

application

Black

Bayonet

Screw

TF40D

IP-FC208

USB-ETH-CONV

IPR208D

IPG100 & IPC100 (10 DIN)

IPG115D – IPC115D

Power supply 24Vac\dc from TF20D

Analogue inputs 10 x config (0÷1V - 0÷5V - 0÷10V - 0÷20mA - 4÷20mA - NTC - PTC - DI)

Digital inputs 20 x config (Potential free contacts - Opto-insulated)

Relay outputs 12 x5A + 3 x 8A

Analogue outputs 4 x config (0÷10V - ON\OFF - Not opto-insulated)

2 x config (0÷10V – 4÷20mA - ON\OFF - Non opto-insulated)

2 x PWM (for fan speed modules - Non opto-insulated)

Other outputs Remote keyboard (2 VGIPG/C)

RS485 MASTER

RS485 SLAVE

USB

ETHERNET

CANBus (Dixell Can Protocol, not open)

RS232 Config (optional)

Other functions Internal RTC

Logging memory (80M)

BACNet protocol (optional)

LON protocol with external device (optional)

IPG200 (10 DIN)

IPG215D

Power supply 24Vac\dc from TF20D

Analogue inputs 10 x config (0÷1V - 0÷5V - 0÷10V - 0÷20mA - 4÷20mA - NTC - PTC - DI)

Digital inputs 20 x config (Potential free contacts - Opto-insulated)

Relay outputs 15 x 5A

Analogue outputs 4 x config (0÷10V - ON\OFF - Not opto-insulated)

2 x config (0÷10V – 4÷20mA - ON\OFF - Non opto-insulated)

Other outputs Remote keyboard (2 VGIPG)

RS485 MASTER

RS485 SLAVE

USB

ETHERNET

CANBus (Dixell Can Protocol, not open)

RS232 Config (optional)

Other functions Internal RTC

Logging memory (80M)

BACNet protocol (optional)

LON protocol with external device (optional)

IPG300 & IPC300 (10 DIN)

IPG315D – IPC315D

Power supply 24Vac\dc from TF20D

Analogue inputs 10 x config (0÷1V - 0÷5V - 0÷10V - 0÷20mA - 4÷20mA - NTC - PTC - DI)

Digital inputs 20 x config (Potential free contacts - Opto-insulated)

Relay outputs 15 x 5A + 5 SSR

Analogue outputs 4 x config (0÷10V - ON\OFF - Not opto-insulated)

2 x config (0÷10V – 4÷20mA - ON\OFF - Non opto-insulated)

2 x PWM (for fan speed modules - Non opto-insulated)

Other outputs Remote keyboard (2 VGIPG/C)

RS485 MASTER

RS485 SLAVE

USB

ETHERNET

CANBus (Dixell Can Protocol, not open)

RS232 Config (optional)

Other functions Internal RTC

Logging memory (80M)

BACNet protocol (optional)

LON protocol with external device (optional)

IPG108D – IPG108E – IPG208D

IPG208E – IPC108D – IPC108E

Display Dual with icons on IPG108E, IPG208E, IPC108E

Power supply 24Vac\dc from TF40D

Analogue inputs 6 x config (0÷1V - 0÷5V - 0÷10V - 0÷20mA - 4÷20mA - NTC - PTC - DI)

Digital inputs 11 x config (Potential free contacts - Opto-insulated)

Relay outputs 8 x 5A

Analogue outputs 4 x config (0÷10V - ON\OFF - Not opto-insulated)

Other outputs Remote keyboard (VGIPG/C)

RS485 MASTER or LAN

RS485 SLAVE

USB

ETHERNET via USB-ETH-CONV

Other functions Internal RTC

Logging memory (80M)

BACNet protocol (optional)

LON protocol with external device (optional)

IPG100, IPG200 & IPC100 (4 DIN)

IPL500

IPL500D

Power supply 24Vac\dc from TF20D

Other outputs Remote keyboard (VGIPG/C)

RS485 MASTER or LAN

RS485 SLAVE

USB

CANBus (Dixell Can Protocol, not open)

ETHERNET

Other functions Internal RTC

Logging memory (80M)

BACNet protocol (optional)

LON protocol with external device (optional)

Internal GPRS modem (optional)

ETHERNET 10/100

• To connect PC and iPro

through ISaGRAF workbench you can download and debug the

application in your target (iPro)

• To connect more iPro

different applications on differents iPro exchanges variables

(Multimaster connection – no polling)

• To send mail and sms

you can program your iPro so it can sends mail/sms on time

or on demand

• Ethernet ModBUS Slave on TCP/IP

to download the map parameters through Wizmate

• To visit your own website

iPro Main Features

SERIAL BUS

• CAN-Bus (NOT CAN OPEN)

iPro is MASTER for a network of CAN devices made by Dixell

I/O expansion modules – electronic expansion valve drivers

• RS485 MASTER

iPro is the MASTER for a network of ModBUS RTU devices

(Dixell controllers and/or third party devices ModBUS RTU 485).

• RS485 SLAVE

To connect iPro to XWEB or standard ModBUS Scada

iPro reads/writes variables from/to these network

iPro Main Features

BUS RS485

(IPG-IPS-IPL series)

ETHERNET

(IPG-IPL series)

CAN BUS

(IPG-IPL series)

LAN

(IPS-IPL series)

Protocol

ModBUS RTU

(Master-Slave)

BacNet

ModBUS RTU TCP/IP

(Multi master)

BacNet

Dixell (no CAN open)

(Multi master)

Dixell

(Master-Slave)

External HW NO SWITCH NO NO

Devices

iPro

Dixell controllers

ModBUS devices

iPro

ModBUS TCP/IP

Devices

iPro

Expansion Module

Driver(XEV20D)

iPro

Expansion Module

Driver(XEV20D)

Number UP TO 100 NODES SWITCH INPUTS UP TO 4 NODES UP TO 4 NODES

Speed 9600-19200 bit/sec 100 Mbit 100 Kbit 19200 bit/sec

Max distance 1KM 50mt 400mt 100mt

Terminals MASTER for master

SLAVE for slave ETH CAN LAN

iPro Main Features

RS485 SLAVE

CANBUS

ETHERNET

RS485 MASTER

iPro Connections

iPro Expansion/Driver

IPX106D Discon./Molex

TF10D

DWEX60-30KIT

(CANBUS + LAN)

IPX115/125D Discon./Molex

TF20D

DWX115-30KIT

DWEX70-30KIT

(CANBUS + LAN)

XEV20D TF20D ( 1 valve)

TF40D (2 valves)

DWXEV30

(CANBUS + LAN)

Expansion Module Driver for valve/s

4 DIN 10 DIN

Black White

IPX206D Bayonet/Screw

TF10D

IP-FCEX60

(CANBUS + LAN)

IPX306D Discon./Screw

TF10D

DWEX306-30KIT

(CANBUS + LAN)

IPX215/225D Bayonet/Screw

TF20D

IP-FCX215

IP-FCEX70

(CANBUS + LAN)

IPX315/325D Discon./Screw

TF20D

DWX315-30KIT/IP-FCX315

DWX325-30KIT/IP-FCX325

(CANBUS + LAN)

Black Black White Black Black

4 DIN

iPro Expansions & Driver

EXPANSION MODULE

IPX (4 DIN)

IPX106D IPX206D – IPX306D

Power supply 24Vac\dc from TF10D 24Vac\dc from TF10D

Analogue inputs 7 x config (0÷1V - 0÷5V - 0÷10V - 0÷20mA

- 4÷20mA - NTC - PTC - DI)

7 x config (0÷1V - 0÷5V - 0÷10V - 0÷20mA

- 4÷20mA - NTC - PTC - DI)

Digital inputs 3 x config (Potential free contacts - Opto-

insulated)

3 x config (Potential free contacts - Opto-

insulated)

Relay outputs 6 x 5A 5 x 5A + 1 x 8A

or

4 x 5A + 1 x 8A + 1 x SSR

Analogue outputs 3 x config (0÷10V - Not opto-insulated) 3 x config (0÷10V - Not opto-insulated)

Other outputs CANBus

LAN

CANBus

LAN

Other functions Dip switch for address set Dip switch for address set

EXPANSION MODULE

IPX100 (10 DIN)

IPX115D IPX125D

Power supply 24Vac\dc from TF20D 24Vac\dc from TF20D

Analogue inputs 10 x config (0÷1V - 0÷5V - 0÷10V -

0÷20mA - 4÷20mA - NTC - PTC - DI)

10 x config (0÷1V - 0÷5V - 0÷10V -

0÷20mA - 4÷20mA - NTC - PTC - DI)

Digital inputs 20 x config (Potential free contacts -

Opto-insulated)

20 x config (Potential free contacts -

Opto-insulated)

Relay outputs 12 x 5A + 3 x 8A 18 x 5A + 3 x 8A + 4 x SSR

Analogue outputs 4 x config (0÷10V - Not opto-insulated)

2 x config (0÷10V - 4÷20mA - ON\OFF

- Non opto-insulated)

4 x config (0÷10V - Not opto-insulated)

2 x config (0÷10V - 4÷20mA - ON\OFF

- Non opto-insulated)

Other outputs CANBus

LAN

CANBus

LAN

Other functions Dip switch for address set Dip switch for address set

EXPANSION MODULE

IPX200 (10 DIN)

IPX215D IPX225D

Power supply 24Vac\dc from TF20D 24Vac\dc from TF20D

Analogue inputs 10 x config (0÷1V - 0÷5V - 0÷10V -

0÷20mA - 4÷20mA - NTC - PTC - DI)

10 x config (0÷1V - 0÷5V - 0÷10V -

0÷20mA - 4÷20mA - NTC - PTC - DI)

Digital inputs 20 x config (Potential free contacts -

Opto-insulated)

20 x config (Potential free contacts -

Opto-insulated)

Relay outputs 15 x 5A 21 x 5A + 4 x SSR

Analogue outputs 4 x config (0÷10V - Not opto-insulated)

2 x config (0÷10V - 4÷20mA - ON\OFF

- Non opto-insulated)

4 x config (0÷10V - Not opto-insulated)

2 x config (0÷10V - 4÷20mA - ON\OFF

- Non opto-insulated)

Other outputs CANBus

LAN

CANBus

LAN

Other functions Dip switch for address set Dip switch for address set

EXPANSION MODULE

IPX300 (10 DIN)

IPX315D IPX325D

Power supply 24Vac\dc from TF20D 24Vac\dc from TF20D

Analogue inputs 10 x config (0÷1V - 0÷5V - 0÷10V -

0÷20mA - 4÷20mA - NTC - PTC - DI)

10 x config (0÷1V - 0÷5V - 0÷10V -

0÷20mA - 4÷20mA - NTC - PTC - DI)

Digital inputs 20 x config (Potential free contacts -

Opto-insulated)

20 x config (Potential free contacts -

Opto-insulated)

Relay outputs 15 x 5A

or

10 x 5A + 5 x SSR

21 x 5A + 4 x SSR

or

16 x 5A + 9 x SSR

Analogue outputs 4 x config (0÷10V - Not opto-insulated)

2 x config (0÷10V - 4÷20mA - ON\OFF

- Non opto-insulated)

4 x config (0÷10V - Not opto-insulated)

2 x config (0÷10V - 4÷20mA - ON\OFF

- Non opto-insulated)

Other outputs CANBus

LAN

CANBus

LAN

Other functions Dip switch for address set Dip switch for address set

ELECTRONIC EXPANSION VALVE MODULE

XEV20D

XEV20D

Power supply 24Vac\dc from TF20D for 1 valve or from TF40D for 2 valves

Probe inputs Pb1 - Pb2 (Pt1000 - NTC - PTC - DI)

Pb3 - Pb4 (0÷1V - 0÷5V - 0÷10V - 0÷20mA - 4÷20mA - Pt1000 - NTC - PTC - DI)

Valve number Up to 2

Relay outputs 8 x 5A

Other outputs CANBus

LAN

Other functions Dip switch for address set

iPro – Expansion Module Connection

Example of connection between iPro 10 DIN and

expansion modules

iPro Connectivity

Example of iPro 10 DIN connectivity

iPro Connectivity

Example of iPro 4 DIN connectivity

iPro Connectivity

Example of iProLINK connectivity

VISOGRAPH

• GRAPICH LCD 240x96 pixel

• Processor: 32bit

• Multi-language

• Panel and wall mounting

• Industrial and commercial frame

• 8 full programmable keys

• 3 wires bus

• ASCII or UNICODE characters (different part number)

• Software updating from USB (through ISaGRAF® application)

VISOGRAPH

VISOGRAPH User Interface

VGIPC Wall/Panel mounting

Only for ASCII fonts

VGIPR Wall/Panel mounting

Only for ASCII fonts

Without application

For models

IPG108D, IPG108E, IPG208D,

IPG208E, IPG115D, IPG215D,

IPG315D, IPL500D

For models

IPC108D, IPC108E

IPC115D, IPC315D

VGIPG Wall/Panel mounting.

Different part number:

- for ASCII fonts

- for UNICODE fonts

With chiller application

For models

IPR208D, IPR215D

With rack application

• Display: 4,3’’ TFT color

• Resolution: 480x272 pixel

• Portrait and Landscape orientation

• Technology: resistive touch

• Panel and Wall mounting

• Alarm and Power front leds

• Temperature and Humidity sensors on board

• Processor: 32bit

• 100% compatible with Visograph connections

• Main project upload through USB stick

• Minor modifies on code can be uploaded through the iPro

VISOTOUCH

VTIPG

For all iPro models

Dimension Frontal (Panel Mounting) 134x93x4.5 mm

Dimension PCB 119x78x1.6 mm

Frontal IP (with UR/NTC sensor) IP20

Frontal IP (without UR/NTC sensor Panel mounting) IP54

Rear IP (Panel mounting) IP20

Power Supply 12Vdc (like visopraph 2.0)

24Vac

NTC (103AT 10kΩ@25°C) 1 on-board

1 remote

Measuring and Regulation Range NTC -10 to 50 C (on-board)

-50 to 110 C (remote)

Umidity probe (UR) 1 on-board

Measuring range Umidity 20 to 85%

Accuracy Umidity Sensor (SH71) +/-3% (20 to 80%)

+/-5% elsewhere

USB connector Rear (standard A type)

Buzzer yes

Operating Temperature -20 to 60 C

Storage Temperature -25 to 70 C

Relative Humidity 20 to 85%

VISOTOUCH

Thank you!

Dixell reserves the right to alter its products without notice. All rights reserved.

Because environmental conditions are outside of Dixell’s control, we cannot assume

liability for results obtained or any damages which may occur due to improper application.