Información de cable para inversores Mitsubishi There is a cable available from Mits, SC-FRPC. This cables allows you to plug the cable from PC to VFD directly. It has a 9 pin female connector with built-in RS232/RS485 converter and a RJ45 connector. If someone has more info about this cable, then it would be useful to post it here. All info I have now is the following pinouts on the RJ45 plug. 1 -> SG 2 -> P5S 3 -> RDA 4 -> SDB 5 -> SDA 6 -> RDB 7 -> SG 8 -> P5S P5S is the supply to the PU unit. Also, it appears that the default comms parameters are: Adress: 0 Baud: 19200 Data: 8 bits Stop: 2 bits Parity: Even To easily verify the integrity of your cable, use the Mits drive setup software: FR-SW1-SETUP-WE.
Transcript of ion de Cable Para Inversores Mitsubishi
Información de cable para inversores Mitsubishi
There is a cable available from Mits, SC-FRPC. This cables allows you to plug the cable
from PC to VFD directly. It has a 9 pin female connector with built-in RS232/RS485
converter and a RJ45 connector.
If someone has more info about this cable, then it would be useful to post it here. All
info I have now is the following pinouts on the RJ45 plug.
1 -> SG
2 -> P5S
3 -> RDA
4 -> SDB
5 -> SDA
6 -> RDB
7 -> SG
8 -> P5S
P5S is the supply to the PU unit.
Also, it appears that the default
comms parameters are:
Adress: 0
Baud: 19200
Data: 8 bits
Stop: 2 bits
Parity: Even
To easily verify the integrity of your cable, use the Mits drive setup software: