io zone 583 - Hydro-Temp...WebCTRL WebCTRL is a web-based building automation system that includes...

15
Automated Logic Corporation 1150 Roberts Blvd. Kennesaw, GA 30144 770/429-3000 770/429-3001 Fax www.automatedlogic.com Copyright 2003 Automated Logic Corporation. All rights reserved. Automated Logic, the Automated Logic logo, WebCTRL, Eikon, and InterOp are registered trademarks of Automated Logic Corporation. WebPRTL is a trademark of Automated Logic Corporation. BACnet ® is a registered trademark of ASHRAE. All other brand and product names are trademarked by their respective companies. Technical Instructions I/O Zone 583 I/O Zone 583 Hardware 2 About this document 2 Introduction 2 Communicating with the I/O Zone 583 3 Hardware 3 BACnet Networking 7 ARC156 7 BACnet MS/TP 7 Third Party Networking 9 Modbus 9 N2 9 Inputs and Outputs 10 Inputs 10 Outputs 10 WebCTRL Configuration 12 Open Protocol Interface 12 Troubleshooting 14 Formatting the Module 14 LEDs 14 Production Date 15

Transcript of io zone 583 - Hydro-Temp...WebCTRL WebCTRL is a web-based building automation system that includes...

  • Automated Logic Corporation • 1150 Roberts Blvd. • Kennesaw, GA 30144 • 770/429-3000 • 770/429-3001 Fax •

    Technical Instructions

    I/O Zone 583

    I/O Zone 583 Hardware 2

    About this document 2

    Introduction 2

    Communicating with the I/O Zone 583 3

    Hardware 3

    BACnet Networking 7

    ARC156 7

    BACnet MS/TP 7

    Third Party Networking 9

    Modbus 9

    N2 9

    Inputs and Outputs 10

    Inputs 10

    Outputs 10

    WebCTRL Configuration 12

    Open Protocol Interface 12

    Troubleshooting 14

    Formatting the Module 14

    LEDs 14

    Production Date 15

    www.automatedlogic.com • Copyright 2003 Automated Logic Corporation. All rights reserved. Automated Logic, the Automated Logic logo, WebCTRL, Eikon, and InterOp are registered trademarks of Automated Logic Corporation. WebPRTL is a trademark of Automated Logic Corporation. BACnet® is a registered trademark of ASHRAE. All other brand and product names are trademarked by their respective companies.

  • I/O Zone 583 Hardware

    About this documentThis document provides information specific to the I/O Zone 583 hardware platform and its module driver, drv_iozone.

    IntroductionThe I/O Zone 583 is designed specifically for zone control and for mounting within the building envelope. The I/O Zone 583 provides the communications circuitry, non-volatile memory, and removable screw terminals for I/O connections. See Table 1 for a description of the I/O Zone 583’s points.

    Table 1. I/O Zone 583 points

    Point Type Specifics

    Digital Output 5 digital outputs, relay contacts rated at 1A maximum at 24VAC. Configured as normally open.

    Input 6 inputs, configurable for dry contact or thermistor input, Resolution is 10 bit A/D. Inputs 1 & 2 may be configured for 0-5 VDC as well.

    Analog Output 3 analog outputs, 0-10VDC. Output resolution is 8 bit.

    Figure 1. I/O Zone 583 Layout and Dimensions

    2.55“6.48 cm

    5.1“12.95 cm

    5.65“14.35 cm

    5.24“13.31 cm

    CMnet Port

    Dual RotaryAddress Switches

    Access Port

    Rnet Port

    Inputs

    FormatJumper

    RS Pro/Rnet PortSelector Jumper

    Gain1Jumper

    24 VoltAC Power

    CommSelectorDIP Switches

    CommunicationsSelection Jumper

    AnalogOutputs

    DigitalOutputs

    I/O ZONE 583

    Revised 9/8/03 • I/O Zone 583 2 © 2003 Automated Logic Corporation

  • Communicating with the I/O Zone 583

    WebCTRLWebCTRL is a web-based building automation system that includes communications with field devices like the I/O Zone 583 through a conventional web browser (such as Internet Explorer). A central WebCTRL server generates web pages containing device-specific information. In this way, the user can access status information and operating parameters for a single device, an entire building, or a network of facilities over the Internet, an intranet, or dial-up connection. For information on using WebCTRL, see the WebCTRL help file.

    RS ProThe I/O Zone 583 supports the Rnet Sensor Pro (RS Pro) on the RS Pro port. The RS Pro is a thermistor-based temperature sensor designed for use with zone control modules. See Figure 2 for a diagram on how to connect the RS Pro to the I/O Zone 583.

    Figure 2. Connecting RS Pro

    Gnd

    Rnet +

    Rnet -

    +12V

    Ground

    Rnet-

    Rnet+

    +12V

    1 2 3 4

    RS Pro

    1

    23

    4

    LogiStat or LogiStat PlusThe I/O Zone 583 supports the LogiStat or LogiStat Plus on inputs 5 and 6. The LogiStat and LogiStat Plus are thermistor based temperature sensors designed for use with zone control modules. See Figure 3 for a diagram on how to connect the LogiStat or LogiStat Plus to the I/O Zone 583.

    NOTE The I/O Zone 583 does not support the LogiStat Pro.

    Figure 3. Connecting LogiStat or LogiStat Plus

    Gnd

    IN-5

    IN-6

    LED

    Gnd

    Tx RxPwr

    1 2 3 4

    LogiStat orLogiStat Plus

    1

    234

    HardwareFigure 1 on page 2 details the I/O Zone 583 hardware.

    PortsThe I/O Zone 583 has the following ports.

    CMnet Port 3-pin port for ARC156 or BACnet MS/TP communications.

    Rnet port 4-pin port for interface with the RS Pro.

    Access port This 5-pin port is not currently available for use. In the future, it will be used for communication with a laptop computer.

    JumpersThe I/O Zone 583 has the following jumper settings:

    NOTE To avoid damaging the jumpers, grip them on the sides parallel to the jumper leads. The jumper leads must remain parallel to the row of jumper pins. See Figure 4.

    Figure 4. Proper Grip of Jumpers

    GripHere

    Revised 9/8/03 • I/O Zone 583 3 © 2003 Automated Logic Corporation

  • Format Jumper Allows you to manually reformat the module. See “Formatting the Module” on page 14 for more information.

    NOTE If the Format jumper is covering both pins, the module will be formatted when powered up. If you do not want to format the module, make sure that the Format jumper is covering only one or neither of the pins.

    LStat/Rnet Port Selector Jumper Select “LStat” if you are using inputs 5 and 6, either as regular inputs or to connect to a LogiStat or LogiStat Plus. Select “Rnet” if you are using the Rnet port to connect to an RS Pro. Inputs 5 and 6 are available as additional inputs if you are using the RS Pro.

    Gain 1 Jumper Cover both pins with the jumper if you are using inputs 5 and 6 as regular inputs. Remove the jumper from both pins if you are using inputs 5 and 6 to connect to a LogiStat or LogiStat Plus.

    Input 1 and Input 2 Jumpers Select “Thermistor/dry contact” or “0-5Vdc”, depending on what type of signal the input should expect. See Table 5 on page 10 for more information on input signal types.

    Communications Selection Jumper Select RS-485 or BACnet-over-ARC156, depending on the type of network you are connecting to. Figure 5 shows the Communications Selection Jumper (set to RS-485).

    Figure 5. Communications Selection Jumper

    BACnetover ARC156

    RS-485

    Communications Selection

    Rotary Address SwitchesThe I/O Zone 583’s pair of rotary switches determines the I/O Zone 583’s MAC address when it is placed on a BACnet/ARC156 network. The rotary switches define the MAC address portion of the device’s BACnet address which is composed of the network address and the MAC address.

    These rotary switches can be set to anything between 1 and 99. One switch corresponds to the tens digit and the other corresponds to the ones digit. For example, if the module’s address is one, set the tens switch to zero and the ones switch to one, as shown in Figure 6.

    Figure 6. Rotary Address Switches

    10‘s

    1‘s

    Comm Selector DIP SwitchesThe I/O Zone 583’s DIP switches determine the baud rate it is communicating at and the protocol it is communicating with. As indicated on the module, set the DIP switch to the left for On and to the right for Off.

    Baud Rate DIP Switches (SW1 and SW2)Switches 1 and 2 are used to determine what baud rate the I/O Zone 583 is communicating at. Table 2 shows the appropriate DIP switch settings for each baud rate.

    Table 2. Baud Rate (SW1 and SW2)

    Baud Rate SW1 SW2

    9600 Off Off

    19.2K Off On

    38.4K On Off

    76.8K On On

    Revised 9/8/03 • I/O Zone 583 4 © 2003 Automated Logic Corporation

  • Protocol DIP Switches (SW3 and SW4)Switches 3 and 4 are used to determine what protocol the I/O Zone 583 is communicating with. Table 3 shows the appropriate DIP switch settings for each protocol.

    Table 3. Protocol (SW3 and SW4)

    Protocol SW3 SW4

    BACnet MS/TP Off Off

    N2 On Off

    Modbus Off On

    LEDsThe I/O Zone 583 has ten LEDs: Power, Run, Error, Rx, Tx, and one for each of the five digital outputs. The LEDs provide visual indication of power, device status, or communications.

    SpecificationsPower 24VAC ± 10%, 50-60Hz, 20VA power

    consumption (single Class 2 source only, 100VA or less).

    Inputs Eight inputs. 2 inputs, jumper configurable for 0-5VDC, 10K ohm thermistor, or dry contact and 4 inputs that support thermistor or dry contact only.

    Input Resolution 10 bit A/D.

    Digital Outputs Five digital outputs, relay contacts rated at 1A resistive @ 24VAC. Configured as dry contact, normally open.

    Analog Outputs Three analog outputs rated as 0-10VDC, 5mA (max).

    Output Resolution 8 bit D/A.

    Communication One CMnet port configurable for BACnet-over-ARC156 or RS-485 BACnet MS/TP, (9600 bps, 19.2k bps, 38.4k bps, or 76.8k bps), Modbus (9600 bps, 19.2k bps, or 38.4k bps), or N2 (9600 bps); one Access port (115.2k bps via Rnet passthrough); one Rnet port (RS485).

    Environmental Operating Range 0° to 130°F (-17.8° to 54.4°C); 10 to 90% relative humidity, non-condensing.

    Status Indication Visual (LED) status of CMnet communication, running, errors, power, and all digital outputs.

    Memory 1 MB Flash memory and 512 KB non-volatile battery-backed RAM (stores data even during a power failure).

    Protection Built-in surge and transient protection circuitry. The module is protected by internal solid state Polyswitches on the incoming power and network connections. These Polyswitches are not replaceable and will reset themselves if the condition that caused the fault returns to normal.

    Battery Lithium 3V coin cell battery, CR2032, provides a minimum of 10,000 hours of data retention during power outages.

    Listed By FCC Part 15 - Subpart B - Class A. Pending listings at the time of publishing this document: UL 916 (PAZX), cUL C22.2 No. 205-M1983 (PAZX7), CE (1997).

    MountingScrew the I/O Zone 583 into an enclosed panel using the mounting holes provided on the cover plate. Be sure to leave about 2 inches (5 centimeters) on each side for wiring.

    Power WiringCAUTION The I/O Zone 583 is a Class 2 device (less than 30VAC, 100VA maximum). Take appropriate isolation measures when mounting the I/O Zone 583 in a control panel where non-Class 2 devices (for example, 120VAC) or wiring are present.

    You can power several devices from the same transformer if you maintain the same polarity.

    The I/O Zone 583 has an operating range of 21.6VAC to 26.4VAC. If voltage measured at the I/O Zone 583’s power input terminals is

    Revised 9/8/03 • I/O Zone 583 5 © 2003 Automated Logic Corporation

  • outside this range, the I/O Zone 583 may not work properly.

    1. Turn the I/O Zone 583’s power off. This prevents the I/O Zone 583 from being powered up before the proper voltage is verified.

    2. Make sure the 24VAC power source is off.

    3. Connect the power wires to the I/O Zone 583’s power terminals labeled Ground and Hot (24VAC) (see Figure 1 on page 2 for location).

    4. Apply power to the transformer.

    5. Make sure that 24VAC is present at the I/O Zone 583’s power input terminals.

    6. Set the I/O Zone 583’s address. Refer to “Rotary Address Switches” on page 4 for details about setting the address.

    7. Turn the I/O Zone 583’s power switch on.

    When the I/O Zone 583 turns on, the Power, Run and Error LEDs turn on and the Run and Error LEDs begin blinking. The Error LED then turns off. (See “LEDs” on page 14 for more information about LED signals.)

    Revised 9/8/03 • I/O Zone 583 6 © 2003 Automated Logic Corporation

  • BACnet Networking

    ARC156An ARCNET coprocessor allows the I/O Zone 583 to communicate on an ARC156 network through the CMnet port. ARC156 is a unique implementation of the industry standard, ARCNET. It differs from ARCNET as shown in Table 4.

    The I/O Zone 583 uses the BACnet protocol to communicate with up to 99 other devices on the ARC156 network at 156 kbps. A special communications cable is recommended for maximum signal integrity. This cable can be ordered from:

    Magnum Cable CorporationCleveland, OH 44110-0500(800) 421-0820

    Table 4. ARC156 vs. ARCNET

    ARC156 ARCNET

    Speed 156K bits/second 2.5M bits/second

    Coupling Opto coupled, d.c. Transformer coupled

    Mode Backplane Dipulse Hybrid

    Connector type

    3 pos screw terminal

    BNC

    Wire type twisted pair RG-59/U coax

    Topology daisy chain star, with active hub

    Termination 120 Ohm 75 Ohm

    Refer to the ARC156 CMnet Wiring Technical Instructions for more information about termination, repeaters, wiring, and ARCNET token passing.

    Configuring the I/O Zone 583 for ARC1561. Turn the I/O Zone 583’s power off.

    2. Set the I/O Zone 583’s Communications Selection jumper to BACnet over ARC156. See Figure 7.

    Figure 7. Communications Selection Jumper, Set to BACnet over ARC156

    BACnetover ARC156

    RS-485

    Communications Selection

    3. Use the I/O Zone 583’s rotary address switches to set the device’s ARC156 MAC address. See Figure 6 on page 4 for a diagram of the rotary switches.

    4. Refer to the ARC156 CMnet Wiring Technical Instructions for information about connecting the ARC156 cable to the I/O Zone 583’s screw terminals.

    5. Turn the I/O Zone 583’s power on.

    NOTE You can verify that the I/O Zone 583 is communicating on the ARC156 network segment by checking the module’s transmit and receive LEDs the CMnet port. Both LEDs should be active.

    BACnet MS/TPThe I/O Zone 583 can be configured to communicate on a BACnet MS/TP network as an MS/TP master or slave device through the CMnet port.

    Configuring the I/O Zone 583 for BACnet MS/TP1. Turn the I/O Zone 583’s power off.

    2. Configure the CMnet port for BACnet MS/TP.

    Revised 9/8/03 • I/O Zone 583 7 © 2003 Automated Logic Corporation

  • • Set the Communications Selection jumper to RS-485. See Figure 5 on page 4.

    • Set the Comm Selector DIP Switches’ SW1 and SW2 for the appropriate communications speed (9600, 19.2k, 38.4k, or 76.8k bps).

    • Set the Comm Selector DIP Switches’ SW3 and SW4 both to Off for BACnet MS/TP.

    Figure 8 shows the DIP switches set for 38.4k bps and BACnet MS/TP. (See “Comm Selector DIP Switches” on page 4 for information on DIP switch settings.)

    Figure 8. Comm Selector DIP Switches, set to 38.4k bps and BACnet MS/TP

    4

    3

    2

    1

    On

    3. Refer to the WebCTRL help file for information on MS/TP wiring.

    4. Turn the I/O Zone 583’s power on.

    Revised 9/8/03 • I/O Zone 583 8 © 2003 Automated Logic Corporation

  • Third Party Networking

    ModbusThe I/O Zone 583 can be configured as a Modbus slave device and connected directly to a Modbus network at the CMnet port.

    Configuring the I/O Zone 583 for Modbus1. Turn the I/O Zone 583’s power off.

    2. Configure the CMnet port for communications with the Modbus network.

    • Set the Communications Selection jumper to RS-485. See Figure 5 on page 4.

    • Set the Comm Selector DIP Switches’ SW1 and SW2 for the appropriate communications speed (9600, 19.2k, or 38.4k bps).

    • Set the Comm Selector DIP Switches’ SW3 to Off and SW4 to On for Modbus.

    Figure 9 shows the DIP switches set for 38.4k bps and Modbus. (See “Comm Selector DIP Switches” on page 4 for information on DIP switch settings.)

    Figure 9. Comm Selector DIP Switches, Set to 38.4k bps and Modbus

    4

    3

    2

    1

    On

    3. Refer to Wiring Tips for EIA-232 and EIA-485 Communications in ALC’s OEM Knowledge Base for information on wiring.

    4. Turn the I/O Zone 583’s power on.

    N2The I/O Zone 583 can be configured as an N2 slave device and connected directly to an N2 network at the CMnet port. Up to 255 slaves are allowed on an N2 network.

    Configuring the I/O Zone 583 for N21. Turn the I/O Zone 583’s power off.

    2. Configure the CMnet port for communications with the N2 network.

    • Set the Communications Selection jumper to RS-485. See Figure 5 on page 4.

    • Set the Comm Selector DIP Switches’ SW1 and SW2 both to Off for 9600 bps.

    • Set the Comm Selector DIP Switches’ SW3 to On and SW4 to Off for N2.

    Figure 10 shows the DIP switches set for 9600 bps and N2. (See “Comm Selector DIP Switches” on page 4 for information on DIP switch settings.)

    Figure 10. Comm Selector DIP Switches, Set to 9600 bps and N2

    4

    3

    2

    1

    On

    3. Refer to Wiring Tips for EIA-232 and EIA-485 Communications in ALC’s OEM Knowledge Base for information on wiring.

    4. Turn the I/O Zone 583’s power on.

    Revised 9/8/03 • I/O Zone 583 9 © 2003 Automated Logic Corporation

  • Inputs and Outputs

    InputsThe I/O Zone 583 is equipped with universal inputs that can accept both analog and digital input signals. Inputs 1 and 2 support thermistors, dry contacts, and 0-5VDC sensors. Inputs 3 through 6 support thermistors and dry contacts only.

    The I/O Zone 583 uses voltage dividers and current sensing resistors to convert electric input signals to volts, which are then measured and converted to the appropriate units.

    Input Signal TypesTable 5 describes the input signal types available on the I/O Zone 583.

    Table 5. Input Signal Types

    Signal Type Description

    Thermistor Precon type 2 (10kohm at 77 deg F). Thermistor input voltages should range between 0.489V and 3.825V.

    Dry Contact A 5VDC wetting voltage is used to detect contact position. This results in a 0.5mA maximum sense current when the contacts are closed. Any switch, which has more than 412 Ohms effective resistance (0.2V) when closed, must have an interposing mechanical relay when used with ALC modules.

    0 to 5 VDC The output impedance of a 0 to 5VDC source must not exceed 10kohmx. The input impedance of the module is approximately 1Mohm.

    Input Wiring RestrictionsWiring restrictions for the I/O Zone 583’s inputs are as follows:

    • Maximum length: 50 feet (15 meters)

    • Minimum gauge: 24 AWG

    • Shielding: shielded and grounded to module’s Gnd terminal

    Input Connection Sequence1. Turn the I/O Zone 583’s power off.

    2. Connect the input wiring to the screw terminals on the module.

    3. Ground shielded wire to the module's ground terminal.

    4. Set the configuration jumper for inputs 1 and 2 to indicate signal type. Make sure the jumper is positioned correctly, and be sure to grip the jumper by the sides only. See Figure 4 on page 3.

    5. Turn the module’s power on.

    OutputsDigital outputs can be connected to a maximum of 24 Volts AC/DC. Each output is a dry contact (rated at 1A, 24VAC maximum).

    Analog outputs can support voltage devices in the range of 0 to 10VDC. The device that is being controlled must have a minimum of 500 Ohms resistance measured from its input to ground and must share the same ground as the I/O Zone 583.

    Digital Output Connection Sequence1. Turn the I/O Zone 583’s power off.

    2. Connect the output wiring to the screw terminals on the module as shown in Figure 11 on page 11.

    NOTE Do not power pilot relays from the same transformer that powers the module.

    3. Verify each output's operation.

    Lock the output to a known condition using the Equipment Definition's Properties page, then make sure the equipment operates as specified.

    Revised 9/8/03 • I/O Zone 583 10 © 2003 Automated Logic Corporation

  • Figure 11. Wiring for Digital Outputs

    DO-2

    DO-1

    BUS

    Gnd

    +24VAC

    DO

    DO

    Analog Output Connection SequenceNOTE The device that is being controlled by the I/O Zone 583 must have a minimum of 2000 Ohms resistance at 10VDC out measured from its input to ground and must share the same ground as the I/O Zone 583.Turn the I/O Zone 583’s power off.

    4. Connect the output wiring to the screw terminals on the module as shown in Figure 12.

    5. Verify each output's operation.

    Lock the output to a known condition using the Equipment Definition's Properties page, then make sure the equipment operates as specified.

    Figure 12. Wiring for Analog Outputs

    Gnd

    AO-3

    Gnd

    AO-2

    Gnd

    AO-10 - 10VDC

    -

    +

    Revised 9/8/03 • I/O Zone 583 11 © 2003 Automated Logic Corporation

  • WebCTRL Configuration

    You must configure protocol information on the Open Protocol Interface Properties page in WebCTRL (see Figure 13).

    Open Protocol Interface

    Base AddressUse the BACnet Device ID drop-down list to determine whether the I/O Zone 583’s BACnet Device ID will be autogenerated.

    Not autogenerated The I/O Zone 583 uses the BACnet Device ID that was programmed in SiteBuilder.

    Autogenerated The I/O Zone 583 uses the Base BACnet Device ID and the rotary address switches’ settings to determine

    the BACnet Device ID. For example, if 240000 is entered in the Base BACnet Device ID field and the rotary address switches are set to one, then the BACnet Device ID is 240001.

    You could change the BACnet Device ID by turning the I/O Zone 583’s power off, changing the rotary address switches, and turning the module back on.

    Protocol Cross ReferenceThe Protocol Cross Reference tables allow you to define Modbus and N2 data addresses and cross reference them to BACnet objects in the GFBs. The parameters are defined on

    the Open Protocol Interface Properties page.

    Figure 13. Open Protocol Interface Properties Page

    Revised 9/8/03 • I/O Zone 583 12 © 2003 Automated Logic Corporation

  • For example, BACnet analog input 1 (see Figure 14) references Modbus float value 30001 and N2 analog input 1 (see Figure 13 on page 12).

    Figure 14. Sample GFB

    Revised 9/8/03 • I/O Zone 583 13 © 2003 Automated Logic Corporation

  • Troubleshooting

    Formatting the ModuleIf you are unable to communicate with the I/O Zone 583 after transferring memory, you can, as a last resort, manually format the module to try to restore communication. Formatting the module erases all memory, so you need to transfer memory back to the module once it is formatted.over the network segment.

    NOTE Since the I/O Zone 583 is automatically formatted when you transfer memory, you should only manually format the module if communication was not established after the memory transfer.

    1. Turn the I/O Zone 583’s power off. Make sure the module’s address switches are addressed correctly and are not set to ‘0 0’.

    2. Set the Format jumper to cover both pins.

    3. Turn the module’s power on.

    4. The Error LED flashes three times in sync with the Run LED.

    5. Remove the Format jumper.

    6. Transfer memory to the module.

    LEDsThe I/O Zone 583 has several LED indicators to show the status of certain functions.

    Power - lights when power is being supplied to the module.

    NOTE The I/O Zone 583 is protected by internal solid state Polyswitches on the incoming power and network connections. These Polyswitches are not replaceable and will reset themselves if the condition that caused the fault returns to normal.

    Digital Output Status - lights when the digital output is activated.

    Rx - lights when the module receives data from the network segment.

    Tx - lights when the module transmits data over the network segment.

    Run - lights based on module health. See Table 6 for explanation.

    Error - lights based on module health. See

    Table 6 for explanation.

    Table 6. LED Signals

    Run LED Error LED Condition

    2 flashes per second

    Off Normal

    2 flashes per second

    2 flashes alternating

    Five minute auto-restart delay after system error

    2 flashes per second

    2 flashes in sync, then pause

    Module is configured for a different baud rate than the rest of the network segment

    2 flashes per second

    3 flashes, then off

    Module has just been formatted

    2 flashes per second

    4 flashes, then pause

    Two or more devices on this network have the same ARC156 network segment address

    2 flashes per second

    On Exec halted after frequent system errors or GFBs halted

    5 flashes per second

    On Exec start-up aborted, Boot is running

    5 flashes per second

    Off Firmware transfer in progress, Boot is running

    7 flashes per second

    7 flashes per second, alternating

    Ten second recovery period after brownout

    14 flashes per second

    14 flashes per second, alternating

    Brownout

    Revised 9/8/03 • I/O Zone 583 14 © 2003 Automated Logic Corporation

  • Production DateTo determine when a module was manufactured, check the module status report for the module in WebCTRL. Refer to the appropriate user's guide for more information about the module status report.

    A sticker on the back of the module also shows the date the module was manufactured. The first three characters on the sticker indicate the type of module. The next two characters show the year and month of manufacture. (The month digit is in hexadecimal.)

    CAUTION Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user’s authority to operate equipment.

    NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

    Revised 9/8/03 • I/O Zone 583 15 © 2003 Automated Logic Corporation

    I/O Zone 583 HardwareAbout this documentIntroductionCommunicating with the I/O Zone 583WebCTRLRS ProLogiStat or LogiStat Plus

    HardwarePortsJumpersRotary Address SwitchesComm Selector DIP SwitchesBaud Rate DIP Switches (SW1 and SW2)Protocol DIP Switches (SW3 and SW4)

    LEDsSpecificationsMountingPower Wiring

    BACnet NetworkingARC156Configuring the I/O Zone 583 for ARC156

    BACnet MS/TPConfiguring the I/O Zone 583 for BACnet MS/TP

    Third Party NetworkingModbusConfiguring the I/O Zone 583 for Modbus

    N2Configuring the I/O Zone 583 for N2

    Inputs and OutputsInputsInput Signal TypesInput Wiring RestrictionsInput Connection Sequence

    OutputsDigital Output Connection SequenceAnalog Output Connection Sequence

    WebCTRL ConfigurationOpen Protocol InterfaceBase AddressProtocol Cross Reference

    TroubleshootingFormatting the ModuleLEDsProduction Date