Inverter Power Source ISQ20 Series · Inverter Power Source ISQ20 Series OPERATING INSTRUCTIONS ....
Transcript of Inverter Power Source ISQ20 Series · Inverter Power Source ISQ20 Series OPERATING INSTRUCTIONS ....
Original Instructions: German Translation of Original Instructions
76609605EN-ISQ20-V1.2
Inverter Power Source
ISQ20 Series
OPERATING INSTRUCTIONS
ISQ20
76609605EN-ISQ20-V1.2.docx 2/63 2016-04-21
Annex:
- Safety Regulations - General References on Resistance welding - Contact addresses
Valid for following models:
ISQ20-3-DC ISQ20-10-DC
ISQ20-6-DC ISQ20-20-DC
ISQ20-8-AC
Version Date Basis of Revision
1.0 2014-07 new
1.0a 2014-11 Adaption to new company name
1.1 2015-02 New installation notes (chap. 1.2)
1.1a 2015-09 New cover
1.2 2016-04 New declaration of conformity (CE)
Copyright 2016: AMADA MIYACHI EUROPE GmbH
Lindberghstr. 1, 82178 Puchheim, Germany
Right to make amendments reserved. Deviations may occur. All rights reserved. The products named in this manual are only used for identification purposes and may be trademarks
or registered trademarks of the respective companies.
ISQ20 Content
76609605EN-ISQ20-V1.2.docx 3/63
Content
1 General Information ............................................................................................. 5
1.1 Safety Notes ....................................................................................................................... 5
1.2 Installation Notes ............................................................................................................... 6
1.3 Declaration of Conformity ................................................................................................. 7
2 Technical Description .......................................................................................... 8
2.1 Device Types ...................................................................................................................... 9 2.1.1 Technical Data ISQ20-3-DC ............................................................................................................. 10 2.1.2 Technical Data ISQ20-6-DC ............................................................................................................. 11 2.1.3 Technical Data ISQ20-10-DC ........................................................................................................... 12 2.1.4 Technical Data ISQ20-20-DC ........................................................................................................... 13 2.1.5 Technical Data ISQ20-8-AC ............................................................................................................. 14
2.2 Operation .......................................................................................................................... 15
2.3 Displacement Sensor (optional, only usable with OP-AWS3/TP-AWS3) .................... 15
2.4 Pressure/Force Measuring (optional, only usable with OP-AWS3/TP-AWS3) ........... 15
2.5 Sound Pressure Level ..................................................................................................... 15
2.6 Maximum Duty Ratio ....................................................................................................... 16
3 Design and Mode of Action ............................................................................... 17
3.1 Front Panel ISQ20 ............................................................................................................ 17
3.2 Rear Panel ISQ20-3 / ISQ20-6 .......................................................................................... 18
3.3 Rear Panel ISQ20-8 / ISQ20-10 ........................................................................................ 19
3.4 Rear Panel ISQ20-20 ........................................................................................................ 20
4 Connections ....................................................................................................... 21
4.1 Overview ........................................................................................................................... 21
4.2 RS232 Serial Interface ..................................................................................................... 21 4.2.1 Data Transfer ................................................................................................................................... 21 4.2.2 Data Output Format, AWS3 Mode .................................................................................................... 22 4.2.3 Data Output Format, Classic Mode .................................................................................................. 23 4.2.4 Baud Rate ........................................................................................................................................ 23 4.2.5 Software Update .............................................................................................................................. 23
4.3 Plug Assignments ............................................................................................................ 24 4.3.1 X1: Binary Inputs, potential free ....................................................................................................... 24 4.3.2 X2: Binary Outputs, potential free .................................................................................................... 27 4.3.3 X3: Initiators ..................................................................................................................................... 30 4.3.4 X4: Valves ........................................................................................................................................ 32 4.3.5 X5: Start ........................................................................................................................................... 32 4.3.6 X6: Proportional Valve Head 1 ......................................................................................................... 33 4.3.7 X7: Pressure Sensor Head 1 ........................................................................................................... 33 4.3.8 X8: Proportional Valve Head 2 ......................................................................................................... 33 4.3.9 X9: Pressure Sensor Head 2 ........................................................................................................... 34 4.3.10 X10: Voltage Measurement 1 ........................................................................................................... 34 4.3.11 X11: Voltage Measurement 2 ........................................................................................................... 34 4.3.12 X12: Binary I/O ................................................................................................................................. 34 4.3.13 X30: Welding Transformer ............................................................................................................... 35 4.3.14 X31: Temperature Sensor Transformer ............................................................................................ 35 4.3.15 X32: Current Measuring Coil ............................................................................................................ 35
ISQ20 Content
76609605EN-ISQ20-V1.2.docx 4/63
5 Commissioning .................................................................................................. 36
5.1 Preconditions for Commissioning ................................................................................. 36
5.2 Electrical Connections .................................................................................................... 36 5.2.1 Mains Supply ................................................................................................................................... 37 5.2.2 Connecting Secondary Cables ......................................................................................................... 38 5.2.3 Connecting Current Measurement ................................................................................................... 39
5.3 Mechanical Connections ................................................................................................. 40 5.3.1 Connection Possibilities Heads / Valves etc. .................................................................................... 40 5.3.2 Connection with One Head and Start 1 ............................................................................................ 41 5.3.3 Connection with Two Heads and Start 1, 2 or 3 ............................................................................... 42
5.4 Insulation Test .................................................................................................................. 43
5.5 Switching-on ..................................................................................................................... 43
6 Sequence ............................................................................................................ 44
6.1 Standard Diagram with One Head .................................................................................. 44
6.2 Diagram for One Head with Stroke Cylinder ................................................................. 45
6.3 Diagram for Pincers resp. Locking Cylinder ................................................................. 46
7 Error Messages .................................................................................................. 47
7.1 Unit Errors (#10 – #59) ..................................................................................................... 47
7.2 Sequence Errors (#60 – #95) ........................................................................................... 49
8 Connection Variants (Examples) ...................................................................... 50
8.1 ISQ20 - pneumatic 1-Head w/o Distance Measurement ............................................... 50
8.2 ISQ20 - pneumatic 1-Head w/o Distance Measurement ............................................... 51
8.3 AWS3 - pneumatic 1-Head ............................................................................................... 52
8.4 AWS3 - pneumatic 2-Head ............................................................................................... 53
8.5 AWS3 – pneumatic with Profibus ................................................................................... 54
8.6 AWS3 – pneumatic with Ethernet IP .............................................................................. 55
8.7 AWS3 - motorized 1-Head ............................................................................................... 56
8.8 AWS3 - motorized 2-Head ............................................................................................... 57
8.9 AWS3 - motorized 1-Head with Profibus ....................................................................... 58
8.10 AWS3 - motorized 1-Head with Ethernet IP ................................................................... 59
8.11 AWS3 – motorized 1-Head with Router (Remote Service) ........................................... 60
9 Connection Schemes ........................................................................................ 61
9.1 Binary Connections 1 ...................................................................................................... 61
9.2 Binary Connections 2 ...................................................................................................... 62
10 Index ................................................................................................................... 63
10.1 Illustration Index .............................................................................................................. 63
10.2 Headword Index ............................................................................................................... 63
ISQ20 General Information
76609605EN-ISQ20-V1.2.docx 5/63
1 General Information
1.1 Safety Notes
Information about safety regulations, symbols, copyrights, protection rights, usage location conditions and notes on resistance welding can be found in the back section of these operating instructions.
Please read this information carefully before using these operating instructions.
These operating instructions should help you familiarize yourself with the system and take advantage of its application possibilities when used as directed.
It contains important notes to help operate the unit safely, properly, and economically.
Observing the notes will help avoid risks, decrease repair costs and down times, and enhance reliability and the service life of the unit.
It is a rule: Safety first!
Warning
Incorrect or inappropriate configuration, installation, settings, handling or use can cause mechanical, electrical or thermal hazards, which may result in serious damage or injury.
Ensure the correct execution of these points and follow the respective notes in the operating instructions. Danger
Do not put the system into operation before you have read the operating instructions!
Danger Persons with cardiac pacemakers and metallic implants are prohibited from
approaching to within a radius of at least 5 m of welding equipment!
Crushing Hazard There is a risk of crushing during the adjustment movement due to closing electrodes, stops for limiting adjustment or stroke movement and the stop on the basic pincers unit for limiting floating movement. Warning
This Class A welding equipment is not supposed to be used in living quarters, where the power supply is carried out by a public low voltage supply.
There it can be difficult to ensure electromagnetic compatibility because of conducted or radiated disturbances. Warning
ISQ20 General Information
76609605EN-ISQ20-V1.2.docx 6/63
1.2 Installation Notes
Please observe the following additionally to the points in chap. 5.1:
Ventilation:
To ensure adequate ventilation of the weld control and motor control units, the distance on the side must be at least 40 mm and behind at least 100 mm.
19“ units (installation in a control cabinet): ISQ20 - 1 U distance upwards MNC (motor control) – at least 40 mm distance on the lateral ventilation slots
If the distances are too small, it can lead to increased temperatures in the inside of the unit. This can affect the functionality.
Cable routing:
For the cable routing ensure an appropriate separation of control and field bus cables to power cables, motor cables and cables with welding current.
EMC guidelines – and thus also the distances to arising magnetic fields – have to be observed.
An appropriate shielding has to be scheduled if necessary.
ISQ20 General Information
76609605EN-ISQ20-V1.2.docx 7/63
1.3 Declaration of Conformity
ISQ20 Technical Description
76609605EN-ISQ20-V1.2.docx 8/63
2 Technical Description
The inverter power supply ISQ20 (hereinafter also referred to as inverter or weld control) can be used as a stand-alone unit with the operating terminal MFT1 or as part of the AWS3 (Active Welding System 3) with the operating terminals OP-AWS3 or TP-AWS3.
Fig. 1: Standard device
A few important functions:
APC (Active Part Conditioner)
Setting of pre-warning and limit values
Error control and process monitoring
Displacement / Force measuring (optional, only possible with AWS3 operating terminal and appropriate measurement technology))
The control mode for each welding pulse can be pre-selected in each of the 99 programs of the ISQ20.
ISQ20 Technical Description
76609605EN-ISQ20-V1.2.docx 9/63
2.1 Device Types
The ISQ20 is available in the following DC- and AC types:
DC device with internal transformer:
ISQ20-3-DC ISQ20-6-DC
3 kA 6 kA
DC device with external transformer:
ISQ20-10-DC 10 kA consisting of basic device ISQ20-EXT-AC/DC-250 and transformer IT-60X *
DC device with external transformer and external line filter:
ISQ20-20-DC 20 kA consisting of basic device ISQ20-EXT-AC/DC-500, transformer IT-113X * and external line filter
AC device with external transformer:
ISQ20-8-AC 8 kA consisting of basic device ISQ20-EXT-AC/DC-250 and transformer TRM3/14 – 9V *
* Other transformers on request.
Special voltages for different mains supplies on request.
ISQ20 Technical Description
76609605EN-ISQ20-V1.2.docx 10/63
2.1.1 Technical Data ISQ20-3-DC
Supply voltage 3x 400 VAC, ±10%, PE
Mains frequency 50...60 Hz
Connecting cable 4 x 2.5 mm²
Connected load 11 kVA
Fuse recommended 3 x 16 A, slow
Rated output current 2 kA at 11 % d.r. measured for Tu = 20 °C
Max. output current 3 kA at 5 % d.r.
Min. terminal voltage 4 V at 3 kA with 400 V rated mains voltage at the unit input
Max. open circuit voltage 10 V
Max. output power 12 kVA
Switching frequency 20 kHz
Output frequency 40 kHz
Protection class IP 30
Permissible humidity 40 – 70 %, non-condensing
Ambient temperature 10..40 °C
Cooling forced ventilation, temperature controlled
Secondary connections Cu busbar, 2 x M8 thread Minus connected with PE
Current measurement integrated measuring coil (toroidal coil)
Dimensions (W x H x D)
216 x 420 x 480 mm 216 x 420 x 550 mm (incl. excess lengths)
Weight ca. 33 kg
ISQ20 Technical Description
76609605EN-ISQ20-V1.2.docx 11/63
2.1.2 Technical Data ISQ20-6-DC
Supply voltage 3x 400 VAC, ±10%, PE
Mains frequency 50...60 Hz
Connecting cable 4 x 2.5 mm²
Connected load 11 kVA
Fuse recommended 3 x 16 A, slow
Rated output current 3 kA at 20 % d.r. measured for Tu = 20 °C
Max. output current 6 kA at 5 % d.r.
Min. terminal voltage 4 V at 6 kA with 400 V rated mains voltage at the unit input
Max. open circuit voltage 10 V
Max. output power 24 kVA
Switching frequency 14 kHz
Output frequency 28 kHz
Protection class IP 30
Permissible humidity 40 – 70 %, non-condensing
Ambient temperature 10..40 °C
Cooling forced ventilation, temperature controlled
Secondary connections Cu busbar, 2 x M8 thread Minus connected with PE
Current measurement integrated measuring coil (toroidal coil)
Dimensions (W x H x D)
216 x 420 x 480 mm 216 x 420 x 550 mm (incl. excess lengths)
Weight ca. 43 kg
ISQ20 Technical Description
76609605EN-ISQ20-V1.2.docx 12/63
2.1.3 Technical Data ISQ20-10-DC
with IT-60X transformer:
Supply voltage 3 x 400 VAC, ±10 %, PE
Mains frequency 50...60 Hz
Connecting cable 4 x 6 mm²
Connected load 22 kVA
Fuse recommended 3 x 32 A, slow
Rated output current dep. on transformer measured for Tu = 20 °C
Max. output current 10 kA at 8 % d.r.
Min. terminal voltage 4 V at 10 kA with 400 V rated mains voltage at the unit input
Max. open circuit voltage 10 V
Max. output power 40 kVA
Switching frequency 1-5 kHz (dependent on primary current)
Output frequency 2-10 kHz
Protection class IP 30
Permissible humidity 40 – 70 %, non-condensing
Ambient temperature 10..40 °C
Cooling forced ventilation, temperature controlled; transformer water cooled
Secondary connections dep. on transformer
Current measurement external measuring coil
Dimensions inverter (W x H x D)
216 x 420 x 480 mm 216 x 420 x 560 mm (incl. excess lengths)
Dimensions transformer(W x H x D)
284 x 110 x 170
Weight inverter ca. 21 kg, transformer ca. 60 kg
ISQ20 Technical Description
76609605EN-ISQ20-V1.2.docx 13/63
2.1.4 Technical Data ISQ20-20-DC
with IT-113X transformer:
Supply voltage 3 x 400 VAC, ±10 %, PE
Mains frequency 50...60 Hz
Connecting cable 4 x 35 mm²
Connected load 85 kVA
Fuse recommended 3 x 100 A, slow
Rated output current dep. on transformer measured for Tu = 20 °C
Max. output current 20 kA at 15 % d.r.
Min. terminal voltage 3 V at 25 kA with 400 V rated mains voltage at the unit input
Max. open circuit voltage 11 V
Max. output power 75 kVA
Switching frequency 1-5 kHz
Output frequency 2-10 kHz
Protection class IP 30
Permissible humidity 40 – 70 %, non-condensing
Ambient temperature 10..40 °C
Cooling inverter and transformer: water cooled
Secondary connections dep. on transformer
Current measurement external measuring coil
Dimensions inverter (W x H x D)
216 x 420 x 480 mm 216 x 420 x 570 mm (incl. excess lengths)
Dimensions transformer(W x H x D)
420 x 125 x 230 mm
Dimensions line filter (W x H x D)
250 x 230 x 600 mm 250 x 230 x 680 mm (incl. excess lengths)
Weight inverter ca. 32 kg, transformer ca. 25.5 kg line filter ca. 19 kg
ISQ20 Technical Description
76609605EN-ISQ20-V1.2.docx 14/63
2.1.5 Technical Data ISQ20-8-AC
with TRM3/14 transformer:
Supply voltage 3 x 400 VAC, ±10 %, PE
Mains frequency 50...60 Hz
Connecting cable 4 x 6 mm²
Connected load dependent on main stage
Fuse recommended dependent on main stage
Rated output current dep. on transformer
Max. output current dep. on transformer
Min. terminal voltage dep. on transformer with 400 V rated mains voltage at the unit input
Max. open circuit voltage dep. on transformer
Max. output power 25 kVA
Switching frequency 1-10 kHz
Output frequency 1-10 kHz
Protection class IP 30
Permissible humidity 40 – 70 %, non-condensing
Ambient temperature 10..40 °C
Cooling forced ventilated, temperature controlled; transformer water cooled
Secondary connections dep. on transformer
Current measurement external measuring coil
Dimensions inverter (W x H x D)
216 x 420 x 480 mm 216 x 420 x 560 mm (incl. excess lengths)
Dimensions transformer(W x H x D)
360 x 150 x 185 mm
Weight inverter ca. 21 kg, transformer ca. 45 kg
ISQ20 Technical Description
76609605EN-ISQ20-V1.2.docx 15/63
2.2 Operation
The operation of the ISQ20 is made with one of the following operating terminals:
OP-AWS3: TP-AWS3: MFT1:
AWS3 operating terminal with toggle wheel AWS3 operating terminal with touch panel Operating terminal with buttons
Find more information regarding the operating terminals in the respective operating instruction.
2.3 Displacement Sensor (optional, only usable with OP-AWS3/TP-AWS3)
Dependent on used weld head.
Article no. Name
770.66 186 Displacement sensor ST1278
770.66 318 Displacement sensor ST3078
770.66 263 Displacement sensor MT1271
770.66 317 Displacement sensor MT2571
Digital (5V/TTL)
Resolution: 0.1 μm / 1 μm / 2 μm
Digital double sampling
2.4 Pressure/Force Measuring (optional, only usable with OP-AWS3/TP-AWS3)
Dependent on used weld head.
0 – 10 V calibration
Voltage detection set values: potential free, connection external X7 / X9
Information regarding necessary measuring parts on request.
2.5 Sound Pressure Level
The equivalent continuous sound pressure level evaluated as A is below 70 dB.
ISQ20 Technical Description
76609605EN-ISQ20-V1.2.docx 16/63
2.6 Maximum Duty Ratio
Duty ratio (d.r.) relative to the set welding current:
Fig. 2: Maximum duty ratio
For ISQ20 with external transformer (ISQ20-8, ISQ20-10 and ISQ20-20) the duty ratio is dependent on the used transformer.
See transformer data sheet for the respective characteristic line.
0
10
20
30
40
50
60
0 0,5 1 1,5 2 2,5 3 3,5
ED
in
%
I in kA
ISQ20-3
ED…
0
10
20
30
40
50
60
0 2 4 6 8
ED
in
%
I in kA
ISQ20-6
ED…
ISQ20 Design and Mode of Action
76609605EN-ISQ20-V1.2.docx 17/63
3 Design and Mode of Action
3.1 Front Panel ISQ20
Main switch
Status display and error messages
RS232
Fig. 3 Front panel
On the front panel you find:
the main switch
the RS232 interface
the display for status and error messages
Status display:
1 2 3
STATUS
4 5 6
Abb. 4 Display
7
1 LED green
Ready 4 LED red Quick-Stop
2 LED green
Pressure contact (DK)
5 LED red Out of Limits
3 LED green
Stepping contact (FK)
6 LED red Sequence error
7 Status messages
00 Ready Operating voltage is present, system is OK, intermediate circuit is not charged
01 Converter ON Intermediate circuit successfully charged. Unit is ready for operation.
02 Controller free
03 Welding program running
04 Reference run active
ISQ20 Design and Mode of Action
76609605EN-ISQ20-V1.2.docx 18/63
3.2 Rear Panel ISQ20-3 / ISQ20-6
X13 S3 X14
X1 X2
X3 X4 X12
S1 S2
X6 X7 X8 X9
X10 X11
X5
XN
Abb. 5: Rear panel ISQ20-3 / ISQ20-6
+
-
ISQ20 Design and Mode of Action
76609605EN-ISQ20-V1.2.docx 19/63
3.3 Rear Panel ISQ20-8 / ISQ20-10
X13 S3 X14
X1 X2
X3 X4 X12
S1 S2
X6 X7 X8 X9
X10 X11
X5
X32
X31 3 4 5 6
1 2 PE
X30
XN
Abb. 6: Rear panel ISQ20-8 / ISQ20-10
ISQ20 Design and Mode of Action
76609605EN-ISQ20-V1.2.docx 20/63
3.4 Rear Panel ISQ20-20
X13 S3 X14
X1 X2
X3 X4 X12
S1 S2
X6 X7 X8 X9
X31 X32 X10 X11
X5
U L1
V L2
X30 L3
PE
IN OUT
Abb. 7: Rear panel ISQ20-20
XN
ISQ20 Connections
76609605EN-ISQ20-V1.2.docx 21/63
4 Connections
4.1 Overview
No. Name Description Mode
XN Power connection
X1 Binary inputs BIN IN DSUB 37 pin
X2 Binary outputs BIN OUT DSUB 37 socket
X3 Initiators DIST DSUB 25 socket
X4 Valves RESOLVER DSUB 15 socket
X5 Start START Binder 6+PE socket
X6 Proportional valve head 1 V1 Binder 7-pol. socket
X7 Pressure sensor head 1 PS1 Binder 4-pol. socket
X8 Proportional valve head 2 V2 Binder 7-pol. socket
X9 Pressure sensor head 2 PS2 Binder 4-pol. socket
X10 Voltage measurement 1 U1 Binder 5-pol. socket
X11 Voltage measurement 2 U2 Binder 5-pol. socket
X12 I/O Binary BIN I/O DSUB 15 socket
X13 Displacement sensor DIST DSUB 15 socket
X14 CAN CAN DSUB 9 pin
X20 MFT1-connection (on the front panel behind the cover plate)
MFT1 RJ45 socket
X21 RS232 (on the front panel) RS232 DSUB 9 socket
Additionally for ISQ20-8-AC, ISQ20-10-DC, ISQ20-20-DC:
X30 Welding transformer
X31 Thermo sensor
X32 Current measuring coil
Toggle switches S1, S2, S3:
S1 Changeover GND/proportional valve (connectors X6, X7) ext. (prop): switch to the left
int. (ISQ): switch to the right
S2 Changeover GND/proportional valve (connectors X8, X9)
S3 internal: supply voltage 24 V DC is supplied internally (max. 1.5 A)
external: supply voltage 24 V DC is supplied externally (input: X2 pin 33/34 to GND 35/36).
4.2 RS232 Serial Interface
The RS232 (X21) interface is situated on the front panel. It is used for transmitting data between the ISQ20 and a computer. The necessary cable you can order with order no. 77066028.
The format of the data output can be changed via the operating panel (default format for data output with OP-AWS3/TP-AWS3: AWS3 mode, with MFT1: classic mode).
4.2.1 Data Transfer
After each welding cycle the measuring results are transmitted via the RS232.
ISQ20 Connections
76609605EN-ISQ20-V1.2.docx 22/63
4.2.2 Data Output Format, AWS3 Mode
Default with OP-AWS3/TP-AWS3
Character string Description Digits
Prg Program number 3
Space 1
AX Axis 1 or axis 2 2
Space 1
Is1_kA Peak current pulse 1 [kA] 6
Space 1
Ie1_kA RMS current pulse 1 [kA] 6
Space 1
Us1_V Peak voltage pulse 1 [V] 6
Space 1
Ue1_V RMS voltage pulse 1 [V] 6
Space 1
P1_kW Peak power pulse 1 [kW] 6
Space 1
W1_Ws Energy pulse 1 [Ws] 7
Space 1
R1_uOhm Resistance 1 [μOhm] 7
Space 1
tw1_ms Welding time pulse 1 [ms] 6
Space 1
Is2_kA Peak current pulse 2 [kA] 6
Space 1
Ie2_kA RMS current pulse 2 [kA] 6
Space 1
Us2_V Peak voltage pulse 2 [V] 6
Space 1
Ue2_V RMS voltage pulse 2 [V] 6
Space 1
P2_kW Peak power pulse 2 [kW] 6
Space 1
W2_Ws Energy pulse 2 [Ws] 7
Space 1
R2_uOhm Resistance 2 [μOhm] 7
Space 1
tw2_ms Welding time pulse 2 [ms] 6
Space 1
Count Global welding counter 5
Space 1
G+ Upper limit exceeding max. (ISQ-AWS3) 1 asterisk (*)
Space 1
G- Lower limit exceeding min. (ISQ-AWS3) 1 asterisk (*)
ISQ20 Connections
76609605EN-ISQ20-V1.2.docx 23/63
4.2.3 Data Output Format, Classic Mode
Default with MFT1.
Classic mode in combination with AWS3 is only recommended, if compatibility with older previous units has to be enabled.
Character string Description Digits
Prg Program number 3
Space 1
Is1_kA Peak current pulse 1 [kA] 6
Space 1
Us1_V Peak voltage pulse 1 [V] 6
Space 1
Ps1_kW Peak power pulse 1 [kW] 6
Space 1
Sz1_ms Welding time pulse 1 [ms] 6
Space 1
Is2_kA Peak current pulse 2 [kA] 6
Space 1
Us2_V Peak voltage pulse 2 [V] 6
Space 1
Ps2_kW Peak power pulse 2 [kW] 6
Space 1
Sz2_ms Welding time pulse 2 [ms] 6
Space 1
Count Global welding counter 5
Space 2
G+ Upper limit exceeding max. (Out of Limits +) 1 asterisk (*)
G- Lower limit exceeding min. (Out of Limits -) 1 asterisk (*)
Space 2
+ No Out Of Limits (ISQ-AWS3) 1 asterisk (*)
- Out Of Limits (ISQ-AWS3) 1 asterisk (*)
4.2.4 Baud Rate
Pay attention to the baud rate during transmission!
Attention
Adjustable baud rates (bps) 2400, 9600, 38400, 115200
Data bits 8
Start bits 1
Stop bits 1
Parity none
4.2.5 Software Update
A software update can be uploaded via the RS232 interface on the ISQ20 or via the USB interface on the OP-AWS3/TP-AWS3.
ISQ20 Connections
76609605EN-ISQ20-V1.2.docx 24/63
4.3 Plug Assignments
4.3.1 X1: Binary Inputs, potential free
DSUB 37 - pin
Pin I/O Function Note
X1.1 I01 without current 2.5 mA at 24 V Setup, run without current
X1.2 I02 Reset counter 2.5 mA at 24 V All counters (w/o action counter)
X1.3 I03 Reset Out Of Limits
2.5 mA at 24 V If set, error „Out of Limits“ is deleted.
X1.4 I04 External current break
2.5 mA at 24 V If set, current program is interrupted and jumps to hold time resp. to the end of the current program. (Suitable for realizing variable pulse duration – e.g. dependent on displacement)
X1.5 I05 Reset unit error 2.5 mA at 24 V Reset occurs at open start until unit is ready after about 30 sec.
X1.6 I06 Not defined 2.5 mA at 24 V ---
Enter the number of the desired welding program with pins 7 to 14. This includes BCD 1 (pin 7) of LSB and BCD 80 (pin 14) of MSB.
External program selection BCD coded Binary coded
X1.7 I07 Bit 0 2.5 mA at 24 V Single digit 1 1
X1.8 I08 Bit 1 2.5 mA at 24 V Single digit 2 2
X1.9 I09 Bit 2 2.5 mA at 24 V Single digit 4 4
X1.10 I10 Bit 3 2.5 mA at 24 V Single digit 8 8
X1.11 I11 Bit 4 2.5 mA at 24 V Tens digit 1 16
X1.12 I12 Bit 5 2.5 mA at 24 V Tens digit 2 32
X1.13 I13 Bit 6 2.5 mA at 24 V Tens digit 4 64
X1.14 I14 Bit 7 2.5 mA at 24 V Tens digit 8 128
X1.15 I15 Start head 1+2 min. 35 mA at 24 V
Unit has to be “ready” before start is set (i.e. Quick Stop is set and unit is in a welding menu).
A program has to be selected in case of external program selection (not program “0”).
For a sequential program (e. g. lower stroke cylinder), the cylinder initiators have to be in basic position.
This input is used for automatic sequential run in twin-head mode (parallel with current changeover or consecutive sequence): head 1 –head 2 - FK – end.
Setting this input starts welding.
See also connector X5.
X1.16 I16 Start head 1 min. 35 mA at 24 V
Start signal for head 1 in twin head mode. See also connector X5.
X1.17 I17 Start head 2 min. 35 mA at 24 V
Start signal for head 2 in twin head mode. See also connector X5
X1.18 I18 Ini 1 head 1 back/top
2.5 mA at 24 V Necessary with one stroke cylinder or pincers.
Display shows error if welding head is not back. See also connector X3.1.
ISQ20 Connections
76609605EN-ISQ20-V1.2.docx 25/63
Pin I/O Function Note
X1.19 I19 Ini 2 head 2 back/top
2.5 mA at 24 V Necessary with two stroke cylinders or two pincers.
Display shows error, if welding head is not back. See also connector X3.4.
X1.20 I20 Ini 3 stroke 1 ahead/top
2.5 mA at 24 V Necessary with one stroke cylinder.
Display shows error, if welding head is not ahead. See also connector X3.7.
X1.21 I21 Ini 4 stroke 2 ahead/top
2.5 mA at 24 V Necessary with two stroke cylinders.
Display shows error, if welding head is not ahead. See also connector X3.10.
X1.22 I22 Ini 5 stroke 1 back/bottom
2.5 mA at 24 V Necessary with one stroke cylinder or pincers.
Display shows error, if welding head is not back. See also connector X3.13.
X1.23 I23 Ini 6 stroke 2 back/bottom or pincers locked
2.5 mA at 24 V Necessary with two stroke cylinders or two pincers.
Display shows error, if welding head is not back. See also connector X3.16.
X1.24 I24 Pressure switch head 1 or initiator
2.5 mA at 24 V A connected pressure switch signalizes that welding pressure in head 1 has been achieved. The input is queried before the on-time starts. If it is not set at this time, it waits until it is set.
This function can be deactivated in basic settings menu if no pressure switch is provided or if this function is not required.
The unit indicates “error” if the input changes during the welding time to “low” (error 61).
See also connector X3.19.
X1.25 I25 Pressure switch head 2 or initiator
2.5 mA at 24 V A second connected pressure switch signalizes that welding pressure in head 2 has been achieved.
The input is queried before the on-time starts. If it is not set at this time, it waits until it is set.
This function can be deactivated in basic settings menu if no pressure switch is provided or if this function is not required.
The unit indicates “error” if the input changes during the welding time to “low” (error 61).
See also connector X3.22.
X1.26 I26 External part detection ok head 1
2.5 mA at 24 V Limits for displacement ok, displacement measuring device has to be connected.
Special case for pneumatic head and activated (internal) displacement measuring: Activation option reference run head 1
ISQ20 Connections
76609605EN-ISQ20-V1.2.docx 26/63
Pin I/O Function Note
X1.27 I27 External part detection ok head 2
2.5 mA at 24 V Limits for displacement ok, displacement measuring device has to be connected.
Special case for pneumatic head and activated (internal) displacement measuring: Activation option reference run head 2
X1.28 I28 Thermo switch 2.5 mA at 24 V Error 73: Switches in case of over temperature
X1.29 I29 Mains compressed air
2.5 mA at 24 V Error 74: The mains pressure monitor must output 24 V if there is a pressure drop (“Low“ active)).
X1.30 ENB Enable Input Quick stop safety relay: Operation locked with open input.
A welding program can only run if this input is set.
The welding program is interrupted immediately at 0 V (“Low“ active Stop input, no STOP category 0, i.e. only the valves are currentless).
The input is active in all operating modes.
X1.31 I31 Reset action counter
2.5 mA at 24 V The action counter is reset to the initial program of this sequence.
X1.32 I32 Not defined 2.5 mA at 24 V ---
X1.33 EXT_+24V (output) External supply voltage
X1.34
X1.35 EXT_GND
0V ext. (ref. to 24V) X1.36
X1.37 PE Protective earth
ISQ20 Connections
76609605EN-ISQ20-V1.2.docx 27/63
4.3.2 X2: Binary Outputs, potential free
DSUB 37 - socket
Pin I/O Function Note
X2.1 O01 Ready 100 mA at 24 V The ready LED (green) shows whether a welding can be started.
Unit has to be “ready” before start is set (i.e. Quick Stop is not released and unit is in a welding menu).
A program has to be selected in case of external program selection (not program “0”).
The cylinder proximity switch has to be in initial position for sequential programs (e. g. lower stroke cylinder, etc.).
X2.2 O02 Locking active 100 mA at 24 V Active during on-time and hold time.
Set during a welding program. It is reset after current program and hold time ended.
X2.3 O03 Stepping contact (FK)
100 mA at 24 V Active after end of hold time.
In case of lower stroke cylinder or pincers not until head and lower stroke cylinder or pincers are in initial position.
The FK remains 10 ms active if the Start is broken (open) before the stepping contact (FK) actuates.
If input Start is still set, this output is only reset in case of falling edge at input Start.
If stepping contact (FK) is set to “forwards” during actual evaluation, the FK remains set until the deviation (out of limits) is evaluated.
X2.4 O04 Welding counter elapsed
100 mA at 24 V Set after a welding when the set number of weldings is reached with this welding.
Reset with the start of the next welding, the internal counter starts to count up again.
X2.5 O05 Out of limits head 1 100 mA at 24 V The actual welding value (depending on the control mode current /voltage / power) is checked for deviations from rated value. If deviation is greater than specified by maximum and minimum value (limits and curves), this output is set.
X2.6 O06 Error message active
100 mA at 24 V For all unit errors #10 - #59
Outputs for controlling the selected program or selection of another unit (e.g. motor head, weld sentry, changeover stage, etc.). BCD1 (pin 7) is LSB and BCD80 (pin 14) is MSB.
Program number BCD coded Binary coded
X2.7 O07 Bit 0 100 mA at 24 V Single digit 1 1
X2.8 O08 Bit 1 100 mA at 24 V Single digit 2 2
X2.9 O09 Bit 2 100 mA at 24 V Single digit 4 4
X2.10 O10 Bit 3 100 mA at 24 V Single digit 8 8
X2.11 O11 Bit 4 100 mA at 24 V Ten digits 1 16
X2.12 O12 Bit 5 100 mA at 24 V Ten digits 2 32
X2.13 O13 Bit 6 100 mA at 24 V Ten digits 4 64
X2.14 O14 Bit 7 100 mA at 24 V Ten digits 8 128
ISQ20 Connections
76609605EN-ISQ20-V1.2.docx 28/63
Pin I/O Function Note
X2.15 O15 Valve 1 See also chap. 5.3
+24 V DC switched; 100 mA at 24 V
See also connector X4.1. function depends on control mode
X2.16 O16 Valve 2
X2.17 O17 Valve 3
X2.18 O18 Valve 4
X2.19 O19 Valve 5
X2.20 O20 Out of limits tw, I, U, P Kopf 1
100 mA at 24 V
X2.21 O21 Out of limits tw, I, U, P Kopf 2
100 mA at 24 V
X2.22 O22 Part detection evaluation head 1
100 mA at 24 V Output from start squeeze time to end of hold time. For control mode with adjustment cylinder 50 ms before current 1st head.
Special case for pneumatic head and activated (internal) displacement measuring:
Error part detection head 1
X2.23 O23 Part detection evaluation head 2
100 mA at 24 V Output from start squeeze time to end of hold time. For control mode with adjustment cylinder 50 ms before current 2nd head.
Special case for pneumatic head and activated (internal) displacement measuring:
Error part detection head 2
X2.24 O24 Start displacement head 1
100 mA at 24 V Signal during on-time head 1.
Special case for pneumatic head and activated (internal) displacement measuring: Error displacement head 1
X2.25 O25 Start displacement head 2
100 mA at 24 V Signal during on-time head 2.
Special case for pneumatic head and activated (internal) displacement measuring: Error displacement head 2
X2.26 O26 Counter pre-warning active
100 mA at 24 V A signal occurs if the set value is reached.
X2.27 O27 Action counter complete
100 mA at 24 V Reset to initial program (sequence abort).
ISQ20 Connections
76609605EN-ISQ20-V1.2.docx 29/63
Pin I/O Function Note
X2.28 O28 Out of limits head 2 100 mA at 24 V The actual welding value (depending on the control mode current /voltage / power) is checked for deviations from rated value. If deviation is greater than specified by maximum and minimum value (limits and curves), this output is set.
Opposite to X2.5 this output is only available if stepping contact (FK) is active.
It hast to be read out prior to breaking (opening) the Start.
X2.29 O29 Out of limits pulse 1
100 mA at 24 V The actual value of first welding pulse (depending on the control mode current /voltage / power) is checked for deviations from rated value. If deviation is greater than specified by maximum and minimum value, this output is set.
Special case for pneumatic head and activated (internal) pressure/force measuring: Error pressure/force head 1
X2.30 O30 Out of limits pulse 2
100 mA at 24 V The actual value of second welding pulse (depending on the control mode current /voltage / power) is checked for deviations from rated value. If deviation is greater than specified by maximum and minimum value, this output is set.
Special case for pneumatic head and activated (internal) pressure/force measuring: Error pressure/force head 2
X2.31 S3
Open: 24 V external Closed: 24 V internal (max. 1.5 A)
Output power supply; depending on switch position of S3 (see chap. 4.1). X2.32
X2.33 S3
Input power supply; depending on switch position of S3 (see chap. 4.1). X2.34
X2.35 GND
0 V external (refer to 24 V)
Reference ground X2.36
X2.37 PE Protective earth
ISQ20 Connections
76609605EN-ISQ20-V1.2.docx 30/63
4.3.3 X3: Initiators
DSUB 25 - socket
Pin I/O Function Note
X3.1 I18 INI1: head 1 back/top
24 V at head back
Necessary with one stroke cylinder or pincers.
Display shows error if welding head is not back
X3.2 INI1_+24V Supply voltage +24 V
X3.3 INI1_GND 0 V ext. (ref. to 24 V)
X3.4 I19 INI2: head 2 back/top
24 V at head back
Necessary with two stroke cylinders or two pincers.
Display shows error if welding head is not back.
X3.5 INI2_+24V Supply voltage +24 V
X3.6 INI2_GND 0 V ext. (ref. to 24 V)
X3.7 I20 INI3: stroke 1 ahead/top
Necessary with one stroke cylinder.
Display shows error if welding head is not ahead.
X3.8 INI3_+24V Supply voltage +24 V
X3.9 INI3_GND 0 V ext. (ref. to 24 V)
X3.10 I21 INI4: stroke 2 ahead/top
Necessary with two stroke cylinders.
Display shows error if welding head is not ahead.
X3.11 INI4_+24V Supply voltage +24 V
X3.12 INI4_GND 0 V ext. (ref. to 24 V)
X3.13 I22 INI5: stroke 1 back/bottom
24 V at head back or pincers locked
Necessary with one stroke cylinder or pincers.
Display shows error if welding head is not back
X3.14 INI5_+24V Supply voltage +24 V
X3.15 INI5_GND 0 V ext. (ref. to 24 V)
X3.16 I23 INI6: stroke 2 back/bottom
24 V at head back or pincers locked
Necessary with two stroke cylinders or two pincers.
Display shows error if welding head is not back..
X3.17 INI6_+24V Supply voltage +24 V
X3.18 INI6_GND 0 V ext. (ref. to 24 V)
X3.19 I24 DS1 Pressure switch 1. Signal
A connected pressure switch signalizes that welding pressure in head 1 has been achieved.
The input is queried before the current time starts. If it is not set at this time, it waits until it is set.
This function can be deactivated in basic settings menu if no pressure switch is provided or if this function is not required.
The unit indicates “error” if the input changes to “low” during the welding time (error 61).
ISQ20 Connections
76609605EN-ISQ20-V1.2.docx 31/63
Pin I/O Function Note
X3.20 DS1_+24V Supply voltage +24 V
X3.21 DS1_GND 0 V ext. (ref. to 24 V)
X3.22 I25 DS2 Pressure switch 2. Signal
A second connected pressure switch signalizes that welding pressure in head 2 has been achieved.
The input is queried before the current time starts. If it is not set at this time, it waits until it is set.
This function can be deactivated in basic settings menu if no pressure switch is provided or if this function is not required.
The unit indicates “error” if the input changes to “low” during the welding time (error 61).
X3.23 DS2_+24V Supply voltage +24 V
X3.24 DS2_GND 0 V ext. (ref. to 24 V)
X3.25 PE Protective earth
ISQ20 Connections
76609605EN-ISQ20-V1.2.docx 32/63
4.3.4 X4: Valves
DSUB 15 - socket
Pin I/O Function Note
X4.1 O15 VV1 Valve triggering 1 +24 V Function depends on control mode, see chap. 5.3.1
X4.2 VV1_GND 0 V ext. (ref. to 24 V)
X4.3 VV1_PE Protective earth
X4.4 O16 VV2 Valve triggering 2, +24 V Function depends on control mode, see chap. 5.3.1
X4.5 VV2_GND 0 V ext. (ref. to 24 V)
X4.6 VV2_PE Protective earth
X4.7 O17 VV3 Valve triggering 3, +24 V Function depends on control mode, see chap. 5.3.1
X4.8 VV3_GND 0 V ext. (ref. to 24 V)
X4.9 VV3_PE Protective earth
X4.10 O18 VV4 Valve triggering 4, +24 V Function depends on control mode, see chap. 5.3.1
X4.11 VV4_GND 0 V ext. (ref. to 24 V)
X4.12 VV4_PE Protective earth
X4.13 O19 VV5 Valve triggering 5, +24 V The valve output can be chronologically programmed.
On current changeover the valve comes after the first current program and remains until end of second hold time.
X4.14 VV5_GND 0 V ext. (ref. to 24 V)
X4.15 VV5_PE Protective earth
4.3.5 X5: Start
Binder 6 + PE - socket
Pin I/O Function Note
X5.1 +24 V External supply voltage
X5.2 I15 Start head 1+2
min. 35 mA at 24 V Unit has to be “ready” before start is set (i.e. Quick Stop is set and unit is in a welding menu).
A program has to be selected in case of external program selection (not program “0”).
For a sequential program (e. g. lower stroke cylinder), the cylinder initiators have to be in basic position.
This input is used for automatic sequential run in twin-head mode (parallel with current changeover or consecutive sequence):
head 1 –head 2 - FK – end.
Setting this input starts welding.
X5.3 I16 Start head 1
min. 35 mA at 24 V Start signal for head 1 in twin head mode.
X5.4 I17 Start head 2
min. 35 mA at 24 V Start signal for head 2 in twin head mode.
X5.5 0 V ext. (ref. to 24 V)
X5.PE PE Protective earth
ISQ20 Connections
76609605EN-ISQ20-V1.2.docx 33/63
4.3.6 X6: Proportional Valve Head 1
Binder 7 - socket
Pin Function Note
X6.1 PVV_OUT Input actual value 1 From pressure sensor on the welding head (“actual value”) (0..10 V) or from proportional valve “actual value” (no pressure sensor).
If this input is used, the toggle switch S1 must point in the direction of X6.
X6.2 PVV_+24V +24 V continuous voltage
X6.3 PVV_INGND 0 V set value 1
X6.4 PVV_IN 0..10 V (0-10 bar) output set value 1
Control voltage for proportional valve („set value “)
X6.5 PVV_GND 0 V ext. (ref. to 24 V)
X6.6 PVV_+24V +24 V supply voltage; max. 1 A
Voltage only when start on; supply proportional valve
X6.7 frei
4.3.7 X7: Pressure Sensor Head 1
Binder 4 - socket
Pin Function Note
X7.1 PS_+24V +24 V supply voltage Supply pressure sensor
X7.2 PS_GND 0 V ext. (ref. to 24 V)
X7.3 PS_OUT Input actual value 1 From pressure sensor on the welding head (“actual value”) (0..10 V) or from proportional valve “actual value” (no pressure sensor).
If this input is used, the toggle switch S1 must point in the direction of X7.
X7.4 PS_RESET OPERATE-signal inverted Reset signal force measuring (0 V – Operate, 24 V – Reset)
4.3.8 X8: Proportional Valve Head 2
Binder 7 - socket
Pin Function Note
X8.1 PVV_OUT Input actual value 2 From pressure sensor on the welding head (“actual value”) (0..10 V) or from proportional valve “actual value” (no pressure sensor).
If this input is used, the toggle switch S2 must point in the direction of X8.
X8.2 frei +24 V continuous voltage
X8.3 PVV_INGND 0 V set value 2
X8.4 PVV_IN 0..10V output set value 2 Control voltage for proportional valve („set value “)
X8.5 PVV_GND 0 V ext. (ref. to 24 V)
X8.6 PVV_+24V +24 V supply voltage max. 1 A
Voltage only when start on; supply proportional valve
X8.7 frei
ISQ20 Connections
76609605EN-ISQ20-V1.2.docx 34/63
4.3.9 X9: Pressure Sensor Head 2
Binder 4 - socket
Pin Function Note
X9.1 PS_+24V +24 V supply voltage
X9.2 PS_GND 0 V ext. (ref. to 24 V)
X9.3 PS_OUT Input actual value 2 From pressure sensor on the welding head (“actual value”) (0..10 V) or from proportional valve “actual value” (no pressure sensor).
If this input is used, the toggle switch S2 must point in the direction of X9.
X9.4 PS_RESET OPERATE-signal inverted Reset signal force measuring (0 V – Operate, 24 V – Reset)
4.3.10 X10: Voltage Measurement 1
Binder 5 - socket
Pin Function Note
X10.2 U- Voltage measuring negative electrode
Connect voltage monitor for head 1 to X10. The voltage must be recorded at the electrodes near the deposit. X10.4 U+ Voltage measuring positive
electrode
4.3.11 X11: Voltage Measurement 2
Binder 5 - socket
Pin Function Note
X11.2 U - Voltage measuring negative electrode
Connect voltage monitor for head 2 to X11. The voltage must be recorded at the electrodes near the deposit. X11.4 U + Voltage measuring positive
electrode
4.3.12 X12: Binary I/O
DSUB 15 - pin
Pin I/O Function
X12.1 E16 Start head 1 min. 35 mA at 24 V
X12.2 E17 Start head 2 min. 35 mA at 24 V
X12.3 Enable input Quick stop safety relay (see. X1.30)
X12.4 INT1/1 Current breakdown pulse 1 head 1
X12.5 INT1/2 Current breakdown pulse 2head 1
X12.6 INT2/1 Current breakdown pulse 1 head 2
X12.7 INT2/2 Current breakdown pulse 2 head 2
X12.8 E64 Programmable input*
X12.9 +24V +24 V voltage output
X12.10 GND 0 V ext. (ref. to 24 V)
X12.11 A64 Programmable output* head 1 2.5 mA at 24 V
X12.12 A65 Programmable output * head 2 2.5 mA at 24 V
X12.13 A66 Programmable output * 2.5 mA at 24 V
X12.14 A67 Programmable output * 2.5 mA at 24 V
X12.15 A68 Programmable output * 2.5 mA at 24 V
* E64; A64 – A68 are only programmable with AWS3 system, otherwise A64 head 1 and A65 head 2. In this case A66 – A68 are not connected.
ISQ20 Connections
76609605EN-ISQ20-V1.2.docx 35/63
4.3.13 X30: Welding Transformer
Terminals
Pin Function
X30.1 + Positive primary voltage
X30.2 - Negative primary voltage
X30.3 PE
4.3.14 X31: Temperature Sensor Transformer
Terminals
Pin Function
X31.3 TH1 Thermo safety plug 1
X31.4 TH2 Thermo safety plug 2
4.3.15 X32: Current Measuring Coil
Terminals
Pin Function
X32.1 Current measuring contact 1
X32.2 Current measuring contact 2
ISQ20 Commissioning
76609605EN-ISQ20-V1.2.docx 36/63
5 Commissioning
5.1 Preconditions for Commissioning Stand-alone devices have to be placed firmly and stable on a table or a rack.
Built-in devices have to be mounted firmly and stable in a control cabinet or on a table rack.
Welding heads have to be mounted firmly and stable on a table or a rack.
Pay attention to the instructions on commissioning.
Make sure that all connections are made accordingly.
Caution
5.2 Electrical Connections
Electrical connections must be done only by qualified and trained personnel (electrician).
Warning
Applicable codes and regulations must be obeyed for dimensioning of the mains power cable, fuse protection and earthing. In case of long distance to the mains transformer, the cross section will eventually have to be increased to avoid a considerable drop of the mains voltage. It can be assumed as a guideline, that at max. short circuit current the voltage drop on the whole voltage line should not be higher than 5 %.
In order to compensate mains feedback, welding systems using their own power supplies must be operated at the main transformer. Sensitive units nearby should be protected using mains input filters.
Ensure that the units are adequately earthed. The unit housing should be included in safety measures. For this use the earth connection on the rear of the ISQ20.
When connecting auxiliary voltage the mains voltage should also be compared with the nominal voltage on the type label.
Read the connection diagram carefully before connecting a separate controller. Take care of phase balance for connection cables from the same mains.
Potentially lethal high voltage is present in the inverter during operation.
The housing may only be opened after disconnecting the unit from the mains power supply and awaiting the capacitors discharge period (approx. 3 min.).
Only trained and instructed personnel may be entrusted with service work.
Any unauthorized modifications are prohibited.
The welding current source may only be used for its intended purpose.
Warning
ISQ20 Commissioning
76609605EN-ISQ20-V1.2.docx 37/63
5.2.1 Mains Supply
Note mains voltage!
Warning
First compare the existing connection voltage to the voltage stated on the type label of the equipment.
An intermediate power circuit of approx. 560V is created from the 3 phase 230/400 VAC / 50/60 Hz mains power supply in the inverter.
Due to the varying requirements in different countries the unit is delivered without a mains plug. A suitable plug should be fitted or the unit should be connected to a terminal box.
If the unit is part of a system, the mains connection must be made via the main switch of the system.
In this case the red/yellow main switch on the unit has to be replaced by a black switch. Please contact our service department for further information. Warning
ISQ20 Commissioning
76609605EN-ISQ20-V1.2.docx 38/63
5.2.2 Connecting Secondary Cables
Use secondary cables with 95 mm² cross-section and a length of at least 500 mm. Use M8 x 16 mm fixing screws.
Connect one secondary cable with the
(+) pole of the ISQ20 (resp. the transformer) and the active electrode (at the corresponding connection behind the current band on the welding head).
Connect the other secondary cable to the (-) pole of the ISQ20 (resp. the transformer) and the corresponding connection on the holder of the passive electrode.
Fig. 8: Secondary cable connection ISQ20-3/ISQ20-6
Please ensure the following to maintain as low a current resistance in the secondary circuit as possible:
The cable lugs should make contact with the mounted component over as great a surface area as possible
Secondary cables should be laid as closely as possible and bound with cable ties to maintain a limited secondary window
Secondary cables should not be in contact with other conducting parts and should not form shunt circuits
Contact surfaces should be clean
Contact surfaces should not be corroded
Screw connections should not loosen during operation
Attention
The attachment of a second (third) secondary cable to each pole increases the cable cross section, thus reducing the current resistance. The shorter the secondary cable, the lower the conducting loss. A considerable loss should be expected with cables longer than 1.5 m.
Reversed pole connection can be advantageous, depending on the application involved. Voltage is created by the Peltier effect when welding materials which are widely disparate in the electrical voltage sequence. This voltage is added to the voltage of the welding power control (recommended) or acts against it, depending on the secondary cable pole configuration. A secondary cable pole configuration which suits your particular application should therefore always be selected.
ISQ20 Commissioning
76609605EN-ISQ20-V1.2.docx 39/63
5.2.3 Connecting Current Measurement
A current measuring coil must be integrated in the secondary circuit for all inverters with external transformer (ISQ20-8, ISQ20-10, ISQ20-20). (Standard: Toroidal ring coil ø 70 mm, no. 770.60 152).
The current measuring coil is part of the power control or oft he measuring unit (if used).
Always make sure that only the supply cable of the secondary current is enclosed by the coil. The coil may never enclose both the supply and the return cable of the secondary current Attention
Abb. 9: Flap toroidal coil (example) with (+) side marking
Abb. 10: Ring toroidal coil (example) with (+) side marking
Install the coil on the (+) line of the power source. Ensure that the (+) side of the
coil points in the direction of the (+)connection of the power source. Ensure that all secondary cables of one pole are enclosed.
Connect the cable of current measurement with the coil and X32 on the ISQ20 (resp. when using an external measuring device with the corresponding input).
In order to ensure correct current indication the direction of current and, consequently,
the coil installation direction are important.
Ensure that the (+) side of the coil points to the direction of the (+) power source connection.
Ensure that all secondary cables of one pole are enclosed.
Attention
ISQ20 Commissioning
76609605EN-ISQ20-V1.2.docx 40/63
5.3 Mechanical Connections
5.3.1 Connection Possibilities Heads / Valves etc.
The most common connection types for different welding tasks are listed in the following tables.
Legend (alphabetical) of abbreviations in the following tables: 0 Option, can be connected KV ZU Compacting unit closed PV Proportional valve
SLD Closing pressure SLH Closing stroke SWD Welding pressure SWZ Welding pincers SWZ ENT Welding pincers, unlocked SV Safety valve UHZ Lower stroke cylinder USV Change-over valve X Connect at all times ZSZ Adjustment cylinder
ISQ20 Commissioning
76609605EN-ISQ20-V1.2.docx 41/63
5.3.2 Connection with One Head and Start 1
x x x x x x x x x x x x
x x x x x x x x x x x x
x x x x x x x x
x x x x x x x x
0 0 0 0 0 0 0 0
x x x x x x x x x x x x x x x xx x xx x x
SL
D
SL
D
SL
D
SL
D
SV
SV
SV
SV
ZS
Z
ZS
Z
ZS
Z
ZS
Z
ZS
Z
ZS
Z
ZS
Z
ZS
Z
SW
D
SW
D
SW
D
SW
D
0 0 0 0 0 00 00 00 0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
SLD
/ S
WD
SLD
/ S
WD
SLD
/ S
WD
SLD
/ S
WD
SW
D
SW
D
SW
D
SW
D
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
UH
Z
UH
Z
UH
Z
UH
Z
SW
Z E
NT
SW
Z E
NT
SW
Z E
NT
SW
Z E
NT
KV
ZU
KV
ZU
KV
ZU
KV
ZU
x x x x x x x x x x x x x x x x
X5.2, X1.15
X5.3, X1.16
X2
.15
X4
.1X
2.16
X4.
4X
2.17
X4.
7X
2.18
X4.
10X
2.19
X4.
13X
6X
7X
8X
9
Clo
sin
g s
tro
ke
Pro
po
rtio
na
l val
ve
Ad
just
men
t cy
lind
er
Ad
just
men
t cy
lind
er w
ith
Pro
po
rtio
nal
val
ve
Ad
just
men
t cy
lind
er w
ith
Pro
p.
valv
e w
eld
ing
pin
cers
and
Ad
just
men
t cy
lind
er w
ith
lo
wer
str
oke
cyl
. P
rop
. va
lve
and
Ad
just
men
t cy
lind
er w
ith
Pro
p.
valv
e co
mp
acti
ng
dev
ice
and
Clo
sin
g s
tro
ke w
ith
low
er s
tro
ke
cyl
ind
er
Pro
po
rtio
na
l val
ve w
ith
wel
din
g p
ince
rs
Pro
po
rtio
na
l val
ve w
ith
co
mp
act
ing
dev
ice
Init
iato
rs
Pro
po
rtio
na
l val
ve w
ith
low
er s
tro
ke
cylin
der
Ad
just
men
t cy
lind
er w
ith
lo
wer
str
oke
cy
lind
er
Clo
sin
g s
tro
ke w
ith
co
mp
act
ing
dev
ice
Ad
just
men
t cy
lind
er w
ith
co
mp
act
ing
dev
ice
Clo
sin
g s
tro
ke w
ith
we
ldin
g p
ince
rs
Ad
just
men
t cy
lind
er w
ith
wel
din
g p
ince
rs
Start 1
Start 2
Start 3
Head 1
Stroke 1 back
Stroke 1 ahead
Head 2
Stroke 2 back
Stroke 2 ahead
Pressure switch 1
Pressure switch 2
Stepping contact
Val
ve 1
Val
ve 2
valv
e 3
Val
ve 4
Va
lve
5P
rop
ort
ion
al-
valv
e 1
Pro
po
rtio
nal
-va
lve
2
Co
nn
ecti
on
po
ssib
iliti
es(S
elec
tio
n)
wit
h o
ne
hea
d
ISQ20 Commissioning
76609605EN-ISQ20-V1.2.docx 42/63
5.3.3 Connection with Two Heads and Start 1, 2 or 3
X5.2, X1.15
X5.3, X1.16
X2.
15X
4.1
X2.
16X
4.4
X2
.17
X4
.7X
2.18
X4.
10X
2.1
9X
4.1
3X
6X
7X
8X
9
x x x x x xx x xx x x
x x x x x xx x xx x x
x x xx x x
x x x x x xx x xx x x
x x x x x xx x xx x x
x x xx x x
x x x x
x x x x
x x x x x x x x x x x x x x x x x xx x xx x xx x xx x x
x
x x x x x x x x x x
x x x x x x x x x x
x x x x x x x x x
Co
nn
ecti
on
po
ssib
ilit
ies
(Sel
ecti
on
)w
ith
tw
o s
imil
ar
hea
ds
SLD
1S
WD
1S
LD
2S
WD
2
SL
D 1
/ S
WD
1S
LD 2
/ S
WD
2
SLD
2 /
SW
D 2
SLD
2 /
SW
D 2
SLD
2 /
SW
D 2
SLD
2 /
SW
D 2
SLD
2 /
SW
D 2
SW
D 2
SW
D 2
SW
D 2
SW
D 2
SW
D 2
SW
D 2
SL
D 1
/ S
WD
1
SL
D 1
/ S
WD
1
SL
D 1
/ S
WD
1
SL
D 1
/ S
WD
1
SL
D 1
/ S
WD
1
SW
D 1
SW
D 1
SW
D 1
SW
D 1
SW
D 1
SW
D 1
(US
V)
(US
V)
(US
V)
(US
V)
(US
V)
(US
V)
(US
V)
(US
V)
(US
V)
(US
V)
(US
V)
(US
V)
(US
V)
(US
V)
(US
V)
(US
V)
(US
V)
(US
V)
(US
V)
(US
V)
SL
D 2
SV
2
SV
2
SZ
S 2
SZ
S 2
SW
D 2
UH
Z 1
UH
Z 2
UH
Z 2
UH
Z 2
UH
Z 2
UH
Z 2
UH
Z 2
UH
Z 1
UH
Z 1
UH
Z 1
UH
Z 1
UH
Z 1
SW
Z
1 E
NT
SW
Z
1 E
NT
SW
Z
1 E
NT
SW
Z
1 E
NT
SW
Z
1 E
NT
SW
Z
1 E
NT
SW
Z
2 E
NT
SW
Z
2 E
NT
SW
Z
2 E
NT
SW
Z
2 E
NT
SW
Z
2 E
NT
SW
Z
2 E
NT
SLD
1S
WD
1
0 0 0 0 SV
2
SV
2
SV
2
SV
2
SV
1
SV
1
SV
1
SV
1
SV
1
SV
1
ZS
Z 1
ZS
Z 2
ZS
Z 2
ZS
Z 2
ZS
Z 2
ZS
Z 2
ZS
Z 2
ZS
Z 2
ZS
Z 2
ZS
Z 2
ZS
Z 1
ZS
Z 1
ZS
Z 1
ZS
Z 1
ZS
Z 1
ZS
Z 1
ZS
Z 2
ZS
Z 1
ZS
Z 1
ZS
Z 1
ZS
Z 1
ZS
Z 1
Clo
sin
g s
tro
ke
Clo
sin
g s
tro
ke
Clo
sin
g s
tro
ke
Pro
po
rtio
na
l val
ve
Pro
po
rtio
na
l val
ve
Pro
po
rtio
na
l val
ve
Ad
just
men
t cy
lind
er
Ad
just
men
t cy
lind
er
Ad
just
men
t cy
lind
er
Ad
just
men
t cy
lind
er w
ith
pro
po
rtio
na
l val
ve
Ad
just
men
t cy
lind
er w
ith
pro
po
rtio
na
l val
ve
Ad
just
men
t cy
lind
er w
ith
pro
po
rtio
na
l val
ve
Ad
just
men
t cy
lind
er w
ith
lo
wer
str
oke
cy
lind
er
Ad
just
men
t cy
lind
er w
ith
lo
wer
str
oke
cy
lind
er
Ad
just
men
t cy
lind
er w
ith
lo
wer
str
oke
cy
lind
er
Ad
just
men
t cy
lind
er w
ith
pro
p. v
alve
an
d lo
we
r st
roke
cyl
.
Ad
just
men
t cy
lind
er w
ith
pro
p. v
alve
an
d lo
we
r st
roke
cyl
.
Ad
just
men
t cy
lind
er w
ith
pro
p. v
alve
an
d lo
we
r st
roke
cyl
.
Ad
just
men
t cy
lind
er w
ith
wel
din
g p
ince
rs
Ad
just
men
t cy
lind
er w
ith
wel
din
g p
ince
rs
Ad
just
men
t cy
lind
er w
ith
wel
din
g p
ince
rs
Ad
just
men
t cy
lind
er w
ith
pro
p. v
alve
an
d w
eld
ing
pin
cers
Ad
just
men
t cy
lind
er w
ith
pro
p. v
alve
an
d w
eld
ing
pin
cers
Ad
just
men
t cy
lind
er w
ith
pro
p. v
alve
an
d w
eld
ing
pin
cers
Init
iato
rs
Pro
po
rtio
na
l val
ve w
ith
low
er s
tro
ke
cylin
der
Pro
po
rtio
na
l val
ve w
ith
low
er s
tro
ke
cylin
der
Pro
po
rtio
na
l val
ve w
ith
low
er s
tro
ke
cylin
der
Pro
po
rtio
na
lve
nti
l w
ith
we
ldin
g p
inc
ers
Pro
po
rtio
na
lve
nti
l w
ith
we
ldin
g p
inc
ers
Pro
po
rtio
na
lve
nti
l w
ith
we
ldin
g p
inc
ers
Start 1
Start 2
Start 3
Head 1
Stroke 1 back
Stroke 1 ahead
Head 2
Stroke 2 back
Stroke 2 ahead
Pressure switch 1
Pressure switch 2
Stepping contact
Val
ve 1
Val
ve
2V
alve
3V
alv
e 4
Va
lve
5P
rop
ort
ion
al-
valv
e 1
Pro
po
rtio
nal
-va
lve
2
ISQ20 Commissioning
76609605EN-ISQ20-V1.2.docx 43/63
5.4 Insulation Test
We use power supply filters in our units to meet European EMC regulations. These filters have a discharge resistance to earth in each phase which is illustrated below. The resistance value is 1 M in each case. This results in an effective resistance of 333 k for a cumulative insulation resistance measurement (L1-L2-L3 to earth).
Abb. 11: Circuit structure for mains filter
We recommend disconnecting the unit for measuring insulation resistances of a system, as this will enable an insulation test under even this technical restriction.
5.5 Switching-on
Crushing Hazard!
During switching on the welding head can move.
Ensure that a safe distance is maintained to the welding head.
Plant set-up should only be carried out by qualified personnel and with extreme care.
Fundamental functions of the controller can be protected with a PIN, which should be fixed by the set-up personnel. Caution
For switching-on turn the main switch from „0“ to „1“.
Status display “01” indicates that the unit is “Ready”.
L1
L1
L1
L1’
L2
L1
R
R
R
RC3 R C3
C1
C1
C1R C3 C2 C2 C2
L2’
L3 L3’
PE PE
Mains
each with 1 MOhm
Device
ISQ20 Sequence
76609605EN-ISQ20-V1.2.docx 44/63
6 Sequence
The chronological sequence of signals and functions is illustrated in the diagrams. The following diagrams are examples and cover a broad application range.
6.1 Standard Diagram with One Head
Dia-ISQ20-1K.cdr
P
P
P
I
START 1release
10 ms or as longas start 1
2 impulsesoff-time
1 2
closing time squeezetime
current program
hold timeset pointactual
start interlocking
steppingcontact
pressure contactcloses (option);head cushioned withadjustment cylinder
current program(option)
valve 2welding pressurewith closing stroke
valve 1 closing stroke;safety relief valve withproportional valve control;adjustment pressure withadjustment cylinder
proportionalvalve (PV)
proportional valve;welding pressure spring-biased with adjustment cylinder
ISQ20 Sequence
76609605EN-ISQ20-V1.2.docx 45/63
6.2 Diagram for One Head with Stroke Cylinder
Dia-ISQ20-Hub-1K.cdr
P
P
P
I
START 1release
10 ms or as longas start 1
2 impulses
off-time
1 2
closing time squeezetime
current program
hold timeset pointactual
start interlocking
steppingcontact
proportioanal valve;welding pressure spring biased withadjustment cylinder
pressure contact closes (option);head cushioned withadjustment cylinder
current program(option)
valve 2 welding pressurewith closing stroke
valve 1 closing stroke;safety relief valve withproportional valve control;adjustment pressure with adjustment cylinder
proportionalvalve (PV)
proximity switchstroke cylinder back(bottom)
proximity switch head back
Valve 3stroke cylinder
stroke cylinder ahead(top)
ISQ20 Sequence
76609605EN-ISQ20-V1.2.docx 46/63
6.3 Diagram for Pincers resp. Locking Cylinder
Dia-ISQ20-Zange-1K.cdr
P
P
P
I
START 1release
10 ms or as longas start 1
2 impulses
off-time
1 2
closing time squeeze t. current program
hold timeset pointactual
start interlocking
stepping contact
proportioanal valve;welding pressurespring-biased withadjustment cylinder
pressure contact closes(option); head cushioned with adjustment cylinder
current program(option)
valve 1 closing stroke;safety relief valve withproportioan valve control;adjustment pressure withadjustment cylinder
proportionalvalve (PV)
proximity switch head back
valve 3pliers unlocked
Valve 2 welding pressurewith closing stroke
proximity switchlocked
ISQ20 Error Messages
76609605EN-ISQ20-V1.2.docx 47/63
7 Error Messages Each error is displayed twice: As digits in the 2-position Status display and additionally
on the display of the operating terminal with number and plain text.
7.1 Unit Errors (#10 – #59)
No. Message Cause 10 SQC3: EMERGENCY STOP active 11 SQC3: Undervoltage intermediate
circuit UZK < 450V ; Undervoltage, mains or fuses defective
12 SQC3: Overvoltage intermediate circuit
UZK > 650V ; Mains overvoltage
13 SQC3: Charging contactor defective Mains undervoltage or fuses defective 14 SQC3: Main contactor defective
15 SQC3: Over temperature cooling element
Over temperature at the cooler (power section) caused by defective fan or excessive ambient temperature
16 SQC3: Over temperature TGB Over temperature on the transformer block due to a lack of air cooling or overload
17 SQC3: Overcurrent - Reverse polarity of measuring connections or - low ohmic output load or - wrong direction of current measuring coil Sporadically occuring: Voltage fluctuations in mains line. Please contact our service department.
18 SQC3: Error, branch U Activation defective or critical closed-loop controller settings
19 SQC3: Error, branch V Activation defective or critical closed-loop controller settings
20 SQC3: I2t too large i2t limit reached: excessive current and current duration too long
21 SQC3: Wire breakage NTC-KK 22 SQC3: Pulse rest time too short Current rest time too short 23 SQC3: Pulse duration too long 24 Error Inverter Erroneous link to inverter (MFC only) 25
AW
S3-
Sys
tem
on
ly
internal CAN error 26 internal CAN error 27 welding active without
current
28 internal CAN error 29 internal CAN error
ISQ20 Error Messages
76609605EN-ISQ20-V1.2.docx 48/63
No. Message 30 Wrong answer from SQC3 31 No communication with SQC3 32 Error when deleting flash 33 Error while writing on flash sector 1 34 Error while writing on flash sector 2 35 Error during transfer to terminal 36 Current too high! (> maximum current) 37 Current too low! (< minimum current) 38 Error during DSP booting 39 Error LCA (SPI)
40 Error LCA (SGC) 41 No communication with terminal 42
AW
S3-
Sys
tem
onl
y
internal CAN error 43 internal CAN error 44 internal CAN error 45 internal CAN error 46 AC-Stop is active (AC = action counter) 47 Program ready is missing 48 Display ready (AWS) is missing 49 Wrong start at 2 head-AC 50 Undervoltage 15V 51 Overvoltage 15V 52 Undervoltage –15V 53 Overvoltage -15V 54 Undervoltage 24 V 55 Overvoltage 24 V 56 Failure 24V external 57 Undervoltage 5V 58 Overvoltage 5V 59 Defective interlocking, or Start < 10 ms or no external supply voltage at X2.
ISQ20 Error Messages
76609605EN-ISQ20-V1.2.docx 49/63
7.2 Sequence Errors (#60 – #95) No. Message Cause 60 Contact cylinder 1 not ahead (X3.7) 61 Error pressure switch 1 62 Head not back (X3.1) 63 Contact cylinder 1 not back (X3.13) 64 Current greater than maximum current 65 Start set when switching on 66 Pressure deviation 1 too big 67 Stroke cylinder 1 not in initial position 68 Head 1 not down (X3.1) 69 Progr. no. for changeover position incorrect
70 No external program selected 71 Part detection input 1 missing 72 Part detection input 2 missing 73 Error thermal switch 74 Mains compressed air error 75 Quick stop error 76 Error pressure switch 2 77 Contact cylinder 2 not ahead (X3.10) 78 Head 2 not up (X3.4) 79 Contact cylinder 2 not back (X3.16) 80 Pressure deviation 2 too big 81 Stroke cylinder 2 not in initial position 82 Head 2 not down (X3.4) 83 No program section AC chosen (AC = action counter) 84 Contact cylinder 1 back (X3.13) 85 Contact cylinder 2 back (X3.16) 86 Contact cylinder 1 ahead (X3.7) 87 Contact cylinder 2 ahead (X3.10) 88 Inputs DK1 and DK2 are missing 89 Inputs DK1 and TK1 are missing 90 Inputs DK2 and TK2 are missing 91 Inputs TK1 and TK2 are missing 92 Set point deviation – check
connections Transformer or coil polarity is reversed (with AC inverter)
93 External interlocking active
94 Voltage measuring cable not or wrong connected
Check voltage measuring cable; beware correct polarity I/U
ISQ20 Connection Variants (Examples)
76609605EN-ISQ20-V1.2.docx 50/63
8 Connection Variants (Examples)
In the following drawings the article numbers for cables always refer to cable with standard length (3 m).
8.1 ISQ20 - pneumatic 1-Head w/o Distance Measurement
ISQ20 Connection Variants (Examples)
76609605EN-ISQ20-V1.2.docx 51/63
8.2 ISQ20 - pneumatic 1-Head w/o Distance Measurement
ISQ20 Connection Variants (Examples)
76609605EN-ISQ20-V1.2.docx 52/63
8.3 AWS3 - pneumatic 1-Head
ISQ20 Connection Variants (Examples)
76609605EN-ISQ20-V1.2.docx 53/63
8.4 AWS3 - pneumatic 2-Head
ISQ20 Connection Variants (Examples)
76609605EN-ISQ20-V1.2.docx 54/63
8.5 AWS3 – pneumatic with Profibus
ISQ20 Connection Variants (Examples)
76609605EN-ISQ20-V1.2.docx 55/63
8.6 AWS3 – pneumatic with Ethernet IP
ISQ20 Connection Variants (Examples)
76609605EN-ISQ20-V1.2.docx 56/63
8.7 AWS3 - motorized 1-Head
ISQ20 Connection Variants (Examples)
76609605EN-ISQ20-V1.2.docx 57/63
8.8 AWS3 - motorized 2-Head
ISQ20 Connection Variants (Examples)
76609605EN-ISQ20-V1.2.docx 58/63
8.9 AWS3 - motorized 1-Head with Profibus
ISQ20 Connection Variants (Examples)
76609605EN-ISQ20-V1.2.docx 59/63
8.10 AWS3 - motorized 1-Head with Ethernet IP
ISQ20 Connection Variants (Examples)
76609605EN-ISQ20-V1.2.docx 60/63
8.11 AWS3 – motorized 1-Head with Router (Remote Service)
ISQ20 Connection Schemes
76609605EN-ISQ20-V1.2.docx 61/63
9 Connection Schemes
9.1 Binary Connections 1
ISQ20 Connection Schemes
76609605EN-ISQ20-V1.2.docx 62/63
9.2 Binary Connections 2
ISQ20 Index
76609605EN-ISQ20-V1.2.docx 63/63
10 Index
10.1 Illustration Index Fig. 1: Standard device ................................................................................................................... 8 Fig. 2: Maximum duty ratio ........................................................................................................... 16 Fig. 3 Front panel......................................................................................................................... 17 Abb. 4 Display ............................................................................................................................... 17 Abb. 5: Rear panel ISQ20-3 / ISQ20-6 .......................................................................................... 18 Abb. 6: Rear panel ISQ20-8 / ISQ20-10 ........................................................................................ 19 Abb. 7: Rear panel ISQ20-20 ......................................................................................................... 20 Fig. 8: Secondary cable connection ISQ20-3/ISQ20-6 ................................................................ 38 Abb. 9: Flap toroidal coil (example) with (+) side marking ............................................................. 39 Abb. 10: Ring toroidal coil (example) with (+) side marking ............................................................ 39 Abb. 11: Circuit structure for mains filter .......................................................................................... 43
10.2 Headword Index
B Baud rate ..................................................................................... 23 Binary Connections 1 ................................................................... 61 Binary Connections 2 ................................................................... 62
C Commissioning ............................................................................. 36 Connecting Current Measurement ............................................... 39 Connecting Secondary Cables ..................................................... 38 Connection ................................................................................... 42 Connection Possibilities Heads / Valves etc. ................................ 40 Connection Schemes ................................................................... 61 Connection Variants ..................................................................... 50 Connection with One Head and Start 1 ........................................ 41 Connections ................................................................................. 21
D Data Transfer ............................................................................... 21 Declaration of Conformity ............................................................... 7 Design and Mode of Action .......................................................... 17 Device Types ................................................................................. 9 Diagram for One Head with Stroke Cylinder ................................. 45 Diagram for Pincers resp. Locking Cylinder .................................. 46 Displacement Sensor ................................................................... 15
E Electrical Connections .................................................................. 36 Error Messages ............................................................................ 47
F Front Panel ISQ20 ....................................................................... 17
G General Information ....................................................................... 5
I Installation Notes ............................................................................ 6 Insulation Test .............................................................................. 43 ISQ20-10-DC Technical Data ....................................................... 12 ISQ20-20-DC Technical Data ....................................................... 13 ISQ20-3-DC Technical Data ......................................................... 10 ISQ20-6-DC Technical Data ......................................................... 11 ISQ20-8-AC Technical Data ......................................................... 14
M Mains Supply ............................................................................... 37 Maximum Duty Ratio .................................................................... 16 Mechanical Connections .............................................................. 40
O Operation ..................................................................................... 15
P Plug assignments ........................................................................ 24 Preconditions for Commissioning ................................................ 36 Pressure/Force Measuring .......................................................... 15
R Rear Panel ISQ20-20 .................................................................. 20 Rear Panel ISQ20-3 / ISQ20-6 .................................................... 18 Rear Panel ISQ20-8 / ISQ20-10 .................................................. 19 RS232 AWS3 mode .................................................................... 22 RS232 Classic mode ................................................................... 23 RS232 Data output format ..................................................... 22, 23 RS232 serial interface ................................................................. 21
S Safety Notes .................................................................................. 5 Sequence .................................................................................... 44 Software update .......................................................................... 23 Sound Pressure Level ................................................................. 15 Standard Diagram with One Head ............................................... 44 Status messages ......................................................................... 17 Switching-on ................................................................................ 43
T Technical Description .................................................................... 8 Toggle switches S1, S2, S3 ......................................................... 21
X X1: Binary inputs ......................................................................... 24 X10: Voltage Measurement 1 ...................................................... 34 X11: Voltage Measurement 2 ...................................................... 34 X12: Binary I/O ............................................................................ 34 X2: Binary Outputs ...................................................................... 27 X3: Initiators ................................................................................ 30 X30: Welding Transformer ........................................................... 35 X31: Temperature Sensor Transformer ....................................... 35 X32: Current Measuring Coil ....................................................... 35 X4: Valves ................................................................................... 32 X5: Start ...................................................................................... 32 X6: Proportional Valve Head 1..................................................... 33 X7: Pressure Sensor Head 1 ....................................................... 33 X8: Proportional Valve Head 2..................................................... 33 X9: Pressure Sensor Head 2 ....................................................... 34