Transmission & Distribution Program
Introduction to Substation DesignTADP 542
Introduction
Instructor: Mike Nissley
![Page 2: Introduction to Substation Design TADP 542web02.gonzaga.edu/orgl/TADP542FINAL/542W1P1V1/542W1P1V1/5… · zPrimary voltages can range from 2 - 50 kV zTypical voltage classes are 15](https://reader033.fdocuments.in/reader033/viewer/2022051909/5ffdf0fbda06551ca027815d/html5/thumbnails/2.jpg)
Module 1 Outline
Presentation 1: General System Overview
Presentation 2: Definitions
Presentation 3: Components
Presentation 4: Components (cont.)
Presentation 5: Utilization of Substation Equipment and Glossary
![Page 3: Introduction to Substation Design TADP 542web02.gonzaga.edu/orgl/TADP542FINAL/542W1P1V1/542W1P1V1/5… · zPrimary voltages can range from 2 - 50 kV zTypical voltage classes are 15](https://reader033.fdocuments.in/reader033/viewer/2022051909/5ffdf0fbda06551ca027815d/html5/thumbnails/3.jpg)
General System Overview
Generation Systems– Fuels & Philosophy
Transmission Systems– Voltages & Fundamentals
Distribution Components– Fundamentals & Utilization
![Page 4: Introduction to Substation Design TADP 542web02.gonzaga.edu/orgl/TADP542FINAL/542W1P1V1/542W1P1V1/5… · zPrimary voltages can range from 2 - 50 kV zTypical voltage classes are 15](https://reader033.fdocuments.in/reader033/viewer/2022051909/5ffdf0fbda06551ca027815d/html5/thumbnails/4.jpg)
Generation Types
Thermal Generation: Burns fuel to create heat which either boils
water for steam (to spin a turbine), or burns to directly spin a generator.
Nonthermal Generation: Fuel mechanically powers a turbine to generate
electricity.
![Page 5: Introduction to Substation Design TADP 542web02.gonzaga.edu/orgl/TADP542FINAL/542W1P1V1/542W1P1V1/5… · zPrimary voltages can range from 2 - 50 kV zTypical voltage classes are 15](https://reader033.fdocuments.in/reader033/viewer/2022051909/5ffdf0fbda06551ca027815d/html5/thumbnails/5.jpg)
Thermal Generation
Nuclear, coal, diesel, natural gas, landfill gas, and biomass are considered thermal fuel resources.
Thermal resources characterized by fuel consumption and associated generation of heat and waste by-products.
![Page 6: Introduction to Substation Design TADP 542web02.gonzaga.edu/orgl/TADP542FINAL/542W1P1V1/542W1P1V1/5… · zPrimary voltages can range from 2 - 50 kV zTypical voltage classes are 15](https://reader033.fdocuments.in/reader033/viewer/2022051909/5ffdf0fbda06551ca027815d/html5/thumbnails/6.jpg)
Natural Gas Fired Plant
![Page 7: Introduction to Substation Design TADP 542web02.gonzaga.edu/orgl/TADP542FINAL/542W1P1V1/542W1P1V1/5… · zPrimary voltages can range from 2 - 50 kV zTypical voltage classes are 15](https://reader033.fdocuments.in/reader033/viewer/2022051909/5ffdf0fbda06551ca027815d/html5/thumbnails/7.jpg)
Thermal Power Plant
![Page 8: Introduction to Substation Design TADP 542web02.gonzaga.edu/orgl/TADP542FINAL/542W1P1V1/542W1P1V1/5… · zPrimary voltages can range from 2 - 50 kV zTypical voltage classes are 15](https://reader033.fdocuments.in/reader033/viewer/2022051909/5ffdf0fbda06551ca027815d/html5/thumbnails/8.jpg)
Nonthermal Generation
Hydro, wind, solar, and wave energy are considered nonthermal fuel sources.
Nonthermal fuels are characterized by the fact that the fuel that enters the generator system leaves it unaltered -using mechanical methods to generate electricity.
![Page 9: Introduction to Substation Design TADP 542web02.gonzaga.edu/orgl/TADP542FINAL/542W1P1V1/542W1P1V1/5… · zPrimary voltages can range from 2 - 50 kV zTypical voltage classes are 15](https://reader033.fdocuments.in/reader033/viewer/2022051909/5ffdf0fbda06551ca027815d/html5/thumbnails/9.jpg)
Hoover Dam
![Page 10: Introduction to Substation Design TADP 542web02.gonzaga.edu/orgl/TADP542FINAL/542W1P1V1/542W1P1V1/5… · zPrimary voltages can range from 2 - 50 kV zTypical voltage classes are 15](https://reader033.fdocuments.in/reader033/viewer/2022051909/5ffdf0fbda06551ca027815d/html5/thumbnails/10.jpg)
Box Canyon Dam
![Page 11: Introduction to Substation Design TADP 542web02.gonzaga.edu/orgl/TADP542FINAL/542W1P1V1/542W1P1V1/5… · zPrimary voltages can range from 2 - 50 kV zTypical voltage classes are 15](https://reader033.fdocuments.in/reader033/viewer/2022051909/5ffdf0fbda06551ca027815d/html5/thumbnails/11.jpg)
Renewable Fuels
Renewable fuels are not easily classified, with many states developing their own definition. For example, some states consider landfill gas as renewable because it uses a by-product of a waste stream to generate electricity even though the waste stream itself is not renewable in the natural sense.
![Page 12: Introduction to Substation Design TADP 542web02.gonzaga.edu/orgl/TADP542FINAL/542W1P1V1/542W1P1V1/5… · zPrimary voltages can range from 2 - 50 kV zTypical voltage classes are 15](https://reader033.fdocuments.in/reader033/viewer/2022051909/5ffdf0fbda06551ca027815d/html5/thumbnails/12.jpg)
Stateline Wind Farm
![Page 13: Introduction to Substation Design TADP 542web02.gonzaga.edu/orgl/TADP542FINAL/542W1P1V1/542W1P1V1/5… · zPrimary voltages can range from 2 - 50 kV zTypical voltage classes are 15](https://reader033.fdocuments.in/reader033/viewer/2022051909/5ffdf0fbda06551ca027815d/html5/thumbnails/13.jpg)
Generation Size & Role
Plants can range in size from 0.25 MW’s to over 2000 MW’s.
Size determined by individual utility needs and operational efficiencies gained by appropriately sizing the plant.
Base Load plants provide constant power output to meet minimum needs.
Peaking Plants vary power output to follow load.
![Page 14: Introduction to Substation Design TADP 542web02.gonzaga.edu/orgl/TADP542FINAL/542W1P1V1/542W1P1V1/5… · zPrimary voltages can range from 2 - 50 kV zTypical voltage classes are 15](https://reader033.fdocuments.in/reader033/viewer/2022051909/5ffdf0fbda06551ca027815d/html5/thumbnails/14.jpg)
![Page 15: Introduction to Substation Design TADP 542web02.gonzaga.edu/orgl/TADP542FINAL/542W1P1V1/542W1P1V1/5… · zPrimary voltages can range from 2 - 50 kV zTypical voltage classes are 15](https://reader033.fdocuments.in/reader033/viewer/2022051909/5ffdf0fbda06551ca027815d/html5/thumbnails/15.jpg)
Transmission System
Used to transport large quantities of electricity efficiently over long distances.
Operates at very high voltages (as high as 750 kV) to reduce line losses associated with current flow.– As current increases the energy dissipated as
heat due to conductor line resistance increases.
![Page 16: Introduction to Substation Design TADP 542web02.gonzaga.edu/orgl/TADP542FINAL/542W1P1V1/542W1P1V1/5… · zPrimary voltages can range from 2 - 50 kV zTypical voltage classes are 15](https://reader033.fdocuments.in/reader033/viewer/2022051909/5ffdf0fbda06551ca027815d/html5/thumbnails/16.jpg)
Transmission Rule of Thumb
Calculating transmission voltage efficiency:
– Generally; 10 MW of electricity can be transported 10 Miles for every 10 kV.
– Example: A 115 kV line could efficiently move 115 MW of energy approximately 115 miles.
![Page 17: Introduction to Substation Design TADP 542web02.gonzaga.edu/orgl/TADP542FINAL/542W1P1V1/542W1P1V1/5… · zPrimary voltages can range from 2 - 50 kV zTypical voltage classes are 15](https://reader033.fdocuments.in/reader033/viewer/2022051909/5ffdf0fbda06551ca027815d/html5/thumbnails/17.jpg)
AC vs DC
Transmission lines typically operate with AC due to its low operating costs. However, there are situations where DC may be a better solution.
DC lines have lower line losses and therefore are most efficient at distances in excess of 500 miles (verify).
![Page 18: Introduction to Substation Design TADP 542web02.gonzaga.edu/orgl/TADP542FINAL/542W1P1V1/542W1P1V1/5… · zPrimary voltages can range from 2 - 50 kV zTypical voltage classes are 15](https://reader033.fdocuments.in/reader033/viewer/2022051909/5ffdf0fbda06551ca027815d/html5/thumbnails/18.jpg)
Transmission Costs
Higher voltage lines are more expensive per mile.
– Typical 115-kV line on wood poles approximately$250,000/mile.
– Typical 345-kV line on lattice steel in excess of $1,000,000/mile
![Page 19: Introduction to Substation Design TADP 542web02.gonzaga.edu/orgl/TADP542FINAL/542W1P1V1/542W1P1V1/5… · zPrimary voltages can range from 2 - 50 kV zTypical voltage classes are 15](https://reader033.fdocuments.in/reader033/viewer/2022051909/5ffdf0fbda06551ca027815d/html5/thumbnails/19.jpg)
A Substation with a View
![Page 20: Introduction to Substation Design TADP 542web02.gonzaga.edu/orgl/TADP542FINAL/542W1P1V1/542W1P1V1/5… · zPrimary voltages can range from 2 - 50 kV zTypical voltage classes are 15](https://reader033.fdocuments.in/reader033/viewer/2022051909/5ffdf0fbda06551ca027815d/html5/thumbnails/20.jpg)
Distribution Voltages
Primary voltages can range from 2 - 50 kV
Typical voltage classes are 15 kV (12.47 kV, 13.2 kV, or 13.8 kV) and 25 kV. The different values have a lot of history behind them.
Secondary voltages are 120/240 V for residential, and 120/208 V or 480 V for commercial.
![Page 21: Introduction to Substation Design TADP 542web02.gonzaga.edu/orgl/TADP542FINAL/542W1P1V1/542W1P1V1/5… · zPrimary voltages can range from 2 - 50 kV zTypical voltage classes are 15](https://reader033.fdocuments.in/reader033/viewer/2022051909/5ffdf0fbda06551ca027815d/html5/thumbnails/21.jpg)
Distribution Construction
Can be overhead or underground.
Includes components for transformation of voltage, regulation of voltage, protection from overvoltage excursions, and isolation of faults.
![Page 22: Introduction to Substation Design TADP 542web02.gonzaga.edu/orgl/TADP542FINAL/542W1P1V1/542W1P1V1/5… · zPrimary voltages can range from 2 - 50 kV zTypical voltage classes are 15](https://reader033.fdocuments.in/reader033/viewer/2022051909/5ffdf0fbda06551ca027815d/html5/thumbnails/22.jpg)
Distribution Customer Classes
Residential – single or multi-family housing regardless of size.
Small Commercial – less than 50 kW and single phase.
Large Commercial – larger than 50 kW and possibly three-phase
Industrial – Usually in excess of 3000 kW
Irrigation – Can be divided by size
![Page 23: Introduction to Substation Design TADP 542web02.gonzaga.edu/orgl/TADP542FINAL/542W1P1V1/542W1P1V1/5… · zPrimary voltages can range from 2 - 50 kV zTypical voltage classes are 15](https://reader033.fdocuments.in/reader033/viewer/2022051909/5ffdf0fbda06551ca027815d/html5/thumbnails/23.jpg)
Load Types
Heating/Cooling/Refrigeration – typically simple motor loads
Lighting/Cooking – Typically resistive load
Manufacturing/Irrigation – can be simple motors or variable frequency drives (non-linear)
Each load type has different electrical characteristics
![Page 24: Introduction to Substation Design TADP 542web02.gonzaga.edu/orgl/TADP542FINAL/542W1P1V1/542W1P1V1/5… · zPrimary voltages can range from 2 - 50 kV zTypical voltage classes are 15](https://reader033.fdocuments.in/reader033/viewer/2022051909/5ffdf0fbda06551ca027815d/html5/thumbnails/24.jpg)
Project Scope
Who is the customer?– Organizations receiving electrical service from a
Substation
What is the scope of a project?– Function, location, etc.
Purpose of a Project Scope: – Communication