Introduction to Phasor Measurements Units (PMUs)
Wei-Jen Lee, Ph.D., PEDirector and ProfessorEnergy Systems Research CenterUniversity of Texas at Arlington
November 16, 2012
1
![Page 2: Introduction to Phasor Measurements Units (PMUs )](https://reader033.fdocuments.in/reader033/viewer/2022061313/56812b8d550346895d8faa22/html5/thumbnails/2.jpg)
Introduction
•Classical Definition of a Phasor▫A pure sinusoidal waveform can be
represented by a unique complex number known as a ‘phasor’. A sinusoidal signal
The phasor representation of this sinusoid is given by
2
![Page 3: Introduction to Phasor Measurements Units (PMUs )](https://reader033.fdocuments.in/reader033/viewer/2022061313/56812b8d550346895d8faa22/html5/thumbnails/3.jpg)
Introduction
•Classical Definition of a Phasor▫The RMS cosine-reference voltage and
current phasors are.
3
ij
vj
IeII
VeVVi
v
||||
||||
![Page 4: Introduction to Phasor Measurements Units (PMUs )](https://reader033.fdocuments.in/reader033/viewer/2022061313/56812b8d550346895d8faa22/html5/thumbnails/4.jpg)
Introduction
4
(a) Sinusoidal signal (b) Phasor representation
•Classical Definition of a Phasor
![Page 5: Introduction to Phasor Measurements Units (PMUs )](https://reader033.fdocuments.in/reader033/viewer/2022061313/56812b8d550346895d8faa22/html5/thumbnails/5.jpg)
Introduction
•Classical Definition of a Phasor▫If the sinusoid is not a pure sine wave, the
phasor is assumed to represent its fundamental frequency component.
▫The most commonly used method of calculating phasors from sampled data is that of Discrete Fourier Transform (DFT).
5
![Page 6: Introduction to Phasor Measurements Units (PMUs )](https://reader033.fdocuments.in/reader033/viewer/2022061313/56812b8d550346895d8faa22/html5/thumbnails/6.jpg)
Introduction
•Important of the Phasor Measurement
6
sin* 21
L
TT
X
EEP
![Page 7: Introduction to Phasor Measurements Units (PMUs )](https://reader033.fdocuments.in/reader033/viewer/2022061313/56812b8d550346895d8faa22/html5/thumbnails/7.jpg)
Introduction
•Important of the Phasor Measurement
7
![Page 8: Introduction to Phasor Measurements Units (PMUs )](https://reader033.fdocuments.in/reader033/viewer/2022061313/56812b8d550346895d8faa22/html5/thumbnails/8.jpg)
Introduction
•Modern EMS systems started from 1965▫Data refresh rate is around 2 to 5 seconds▫Measurement signals are not synchronized▫People relies upon power flow and state estimation to
estimate the angles among buses.▫It is an offline estimation and the results are not
reliable.
8
![Page 9: Introduction to Phasor Measurements Units (PMUs )](https://reader033.fdocuments.in/reader033/viewer/2022061313/56812b8d550346895d8faa22/html5/thumbnails/9.jpg)
Introduction
•Modern phasor measurement systems can trace origin to the development of the Symmetrical Component Distance Relay (SCDR) in the early 1970s.
• In early 1980s, measurement system started using GPS to synchronize the sampling clocks, which offering a common reference.
•The first experimental PMUs were developed at Virginia Tech in 1988, and Macrodyne built the first PMU in 1992.
9
![Page 10: Introduction to Phasor Measurements Units (PMUs )](https://reader033.fdocuments.in/reader033/viewer/2022061313/56812b8d550346895d8faa22/html5/thumbnails/10.jpg)
Introduction
•The modern PMUs use one pulse per second signals provided by the GPS satellite receivers.▫The accuracy of the GPS timing pulse is better than 1
µs.▫For a 60 Hz system corresponds to about 0.02 degrees.▫Current PMU records data at the rate of 30 samples per
second (This number can be adjusted).
10
![Page 11: Introduction to Phasor Measurements Units (PMUs )](https://reader033.fdocuments.in/reader033/viewer/2022061313/56812b8d550346895d8faa22/html5/thumbnails/11.jpg)
Introduction
•Functional block diagram of the elements in a PMU.
11
![Page 12: Introduction to Phasor Measurements Units (PMUs )](https://reader033.fdocuments.in/reader033/viewer/2022061313/56812b8d550346895d8faa22/html5/thumbnails/12.jpg)
PMU and Smart Grid Development
•The electrical power system is one of the most sophisticated man-made infrastructures.
•While the power system is a technological marvel, it is also reaching the limit of its ability to meet the nation's electricity needs.
•The modernization of the electricity infrastructure leads to the concept of smart grid.
•The smart grid as defined here is based upon the description found in the Energy Independence and Security Act 2007.
12
![Page 13: Introduction to Phasor Measurements Units (PMUs )](https://reader033.fdocuments.in/reader033/viewer/2022061313/56812b8d550346895d8faa22/html5/thumbnails/13.jpg)
PMU and Smart Grid Development
•The term “Smart Gird” refers to a modernization of the electricity delivery system so that it monitors, protect, and automatically optimizes the operation of its interconnected elements.
• In general, a comprehensive smart grid design should take holistic approaches and cover both top-down and bottom-up approaches.
•Many smart grid related activities have been carried out all over the world.
13
![Page 14: Introduction to Phasor Measurements Units (PMUs )](https://reader033.fdocuments.in/reader033/viewer/2022061313/56812b8d550346895d8faa22/html5/thumbnails/14.jpg)
Desired Features of Smart Grid
•Advanced monitoring, control, and demand management.
•Advanced components & operating concepts.•Robust modeling & simulation tools.•Seamless interconnection of low environmental impact
new generation technologies.•Standardized architecture & secure communication
standards.
14
![Page 15: Introduction to Phasor Measurements Units (PMUs )](https://reader033.fdocuments.in/reader033/viewer/2022061313/56812b8d550346895d8faa22/html5/thumbnails/15.jpg)
Potential Areas of Smart Grid Development and Applications
15
![Page 16: Introduction to Phasor Measurements Units (PMUs )](https://reader033.fdocuments.in/reader033/viewer/2022061313/56812b8d550346895d8faa22/html5/thumbnails/16.jpg)
PMU for Wide Area Monitoring and Control•Deployment of Phasor Measurement Unit (PMU)
▫ In 2007, the organization of U.S Department of Energy (DOE) and the North American Electric Reliability Corporation (NERC), along with involved electric utility companies and other organizations, formed the North American SynchroPhasor Initiative (NASPI)
▫With funding from The American Recovery and Reinvestment Act of 2009, several smart investment grant and demonstration projects have been awarded to advance the synchrophsor technology.
16
![Page 17: Introduction to Phasor Measurements Units (PMUs )](https://reader033.fdocuments.in/reader033/viewer/2022061313/56812b8d550346895d8faa22/html5/thumbnails/17.jpg)
PMU for Wide Area Monitoring and Control•Deployment of Phasor Measurement Unit (PMU)
17
![Page 18: Introduction to Phasor Measurements Units (PMUs )](https://reader033.fdocuments.in/reader033/viewer/2022061313/56812b8d550346895d8faa22/html5/thumbnails/18.jpg)
PMU for Wide Area Monitoring and Control•Potential PMU Applications
• Wide-Area Visualization and Monitoring;• Angle and Frequency Monitoring;• Interarea Oscillation Detection & Analysis;• Proximity to Voltage Collapse;• State Estimation;• Fast Frequency Regulation;• Transmission Fault Location Estimation;• Dynamic Model Validation.
18
![Page 19: Introduction to Phasor Measurements Units (PMUs )](https://reader033.fdocuments.in/reader033/viewer/2022061313/56812b8d550346895d8faa22/html5/thumbnails/19.jpg)
PMU for Wide Area Monitoring and Control•Though the above applications are from the view of
ISO, the PMUs-based applications also benefit generator owners and other market participants.
•PMUs are able to continuously record several different signals which are the requirements of ancillary services like spinning reserve, frequency control and voltage control.
•Once the infrastructure is permanently installed at the power plant, the online tests such as voltage step-change can be easily applied and recorded.
19
![Page 20: Introduction to Phasor Measurements Units (PMUs )](https://reader033.fdocuments.in/reader033/viewer/2022061313/56812b8d550346895d8faa22/html5/thumbnails/20.jpg)
Sample PMU Applications
•PMU applications in CAISO: Wide area visualization and monitoring
20
Source: EPG
![Page 21: Introduction to Phasor Measurements Units (PMUs )](https://reader033.fdocuments.in/reader033/viewer/2022061313/56812b8d550346895d8faa22/html5/thumbnails/21.jpg)
Sample PMU Applications
•Recording of Actual Event
21
![Page 22: Introduction to Phasor Measurements Units (PMUs )](https://reader033.fdocuments.in/reader033/viewer/2022061313/56812b8d550346895d8faa22/html5/thumbnails/22.jpg)
Sample PMU Applications
•Comparison between Actual response and Simulation Results
22
WSCC (WECC) System Blackout on August 10, 1996
![Page 23: Introduction to Phasor Measurements Units (PMUs )](https://reader033.fdocuments.in/reader033/viewer/2022061313/56812b8d550346895d8faa22/html5/thumbnails/23.jpg)
Sample PMU Applications
•State Estimation▫State estimation techniques were developed in 1970s
Obtain an approximation to averaged system state from scanned data (seconds to minutes)
It is referred as “Static State Estimates”.
▫PMUs enable synchronized phasor measurement bus voltages & currents. Make significant improvement on state estimation or state
measurement applications Install PMU in the system could be a smart move to improve the
accuracy and efficiency of state estimation.
23
![Page 24: Introduction to Phasor Measurements Units (PMUs )](https://reader033.fdocuments.in/reader033/viewer/2022061313/56812b8d550346895d8faa22/html5/thumbnails/24.jpg)
Sample PMU Applications
•PMU Based On-Line generator parameter identification system.
. . . . .
GPS
Ethernet
PMU
PMU
PMU
hp Workstation i2000
hp Workstation i2000
Phasor Data Concentrator
EMS Database
ApplicationsCommunication StandardsIEEE C37.118.2IEC 61850-90-5ICCP
24
![Page 25: Introduction to Phasor Measurements Units (PMUs )](https://reader033.fdocuments.in/reader033/viewer/2022061313/56812b8d550346895d8faa22/html5/thumbnails/25.jpg)
Sample PMU Applications
•PMU Based On-Line generator response and parameter identification system.
25
Original System Reduced System
![Page 26: Introduction to Phasor Measurements Units (PMUs )](https://reader033.fdocuments.in/reader033/viewer/2022061313/56812b8d550346895d8faa22/html5/thumbnails/26.jpg)
Sample PMU Applications
•PMU Based On-Line generator response and parameter identification system.• The Reliability Standards relate to generator model
verification are:• MOD-026-1 — Verification of Models and Data for Generator
Excitation System Functions• MOD-027-1 — Verification of Generator Unit Frequency Response
• Once these Reliability Standards are approved, the standards become mandatory and enforceable requirements
26
![Page 27: Introduction to Phasor Measurements Units (PMUs )](https://reader033.fdocuments.in/reader033/viewer/2022061313/56812b8d550346895d8faa22/html5/thumbnails/27.jpg)
Sample PMU Applications
•Fault Location in the Transmission Network.
27
![Page 28: Introduction to Phasor Measurements Units (PMUs )](https://reader033.fdocuments.in/reader033/viewer/2022061313/56812b8d550346895d8faa22/html5/thumbnails/28.jpg)
Relevant PMU Standards
•C37.111-1999▫A general transient data recording file format standard
•C37.118.1-2011▫Covers synchrophasor measurements for power systems▫Adds frequency & rate of change of frequency (ROCOF)
and dynamic operation •C37.118.2-2011
▫Defines real-time synchronized phasor measurement data exchange method
28
![Page 29: Introduction to Phasor Measurements Units (PMUs )](https://reader033.fdocuments.in/reader033/viewer/2022061313/56812b8d550346895d8faa22/html5/thumbnails/29.jpg)
Conclusion and Discussion
•PMU is a matured technology.• In addition to the original intended applications on
“Phasor Measurement”, PMUs offer attractive options for improving protection and control actions on modern power systems.
•Future power systems will have to face more stressful regimes; improved protection and control offered by the wide area measurement systems based on PMUs will become even more important.
29
![Page 30: Introduction to Phasor Measurements Units (PMUs )](https://reader033.fdocuments.in/reader033/viewer/2022061313/56812b8d550346895d8faa22/html5/thumbnails/30.jpg)
30