Page 1: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.
Page 2: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.

Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way

to improve safety and efficiency, allowing for seamless operation. Take your

systems into the future with a touch. Operate from almost anywhere. Focus on

what matters most. Experience the Power Xpert Dashboard. Power. Empowered.

Page 3: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.

ONE-LINE

ELEVATION

DOCUMENTS

TIMELINE

BREAKER SET POINTS

BE SAFE

HOME

User-friendly operation and

advanced functionality increases

your productivity and uptime.

Page 4: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.

Control20cal/cm2

ARMS Off

One-line

Elevation

TransferAutomatic

Timeline3 Alarms

Docs

Settings

Help

02:32:34 PM02/17/2017

adminLogout - 15:00

Lab Demo Gear10.130.14.247

4D - C4

Trip U...

Senso...

Type

Locat...

120 V...

800 A

Digitr...

4D

Main M1

2D - C2

Trip U...

Senso...

Type

Locat...

120 V...

800 A

Digitr...

2D

Main M1

3C - Tie Bkr

Stat

PF

la

lb

Open

--

0 A

0A

Main M1, DT11...

20 cal/cm217 cal/cm2

20 cal/cm2 20 cal/cm2

2C- Main Bkr 1

Stat

PF

la

lb

Closed

1

398 A

393 A

Main M1, DT11...

4C - Main Bkr 2

Stat

PF

la

lb

Closed

1

401A

393 A

Main M1, DT11...

Source 1

Bus 1 Bus 2

4D Feeder2D Feeder

Source 2

One-line

The One-Line Diagram allows you to see device alarms.

You can also see if the breaker is opened or closed.

Page 5: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.

Control20cal/cm2

ARMS Off

One-line

Elevation

TransferAutomatic

Timeline3 Alarms

Docs

Settings

Help

02:32:34 PM02/17/2017

adminLogout - 15:00

Lab Demo Gear10.130.14.247

4D - C4

Trip U...

Senso...

Type

Locat...

120 V...

800 A

Digitr...

4D

Main M1

2D - C2

Trip U...

Senso...

Type

Locat...

120 V...

800 A

Digitr...

2D

Main M1

3C - Tie Bkr

Stat

PF

la

lb

Open

--

0 A

0A

Main M1, DT11...

20 cal/cm217 cal/cm2

20 cal/cm2 20 cal/cm2

2C- Main Bkr 1

Stat

PF

la

lb

Closed

1

398 A

393 A

Main M1, DT11...

4C - Main Bkr 2

Stat

PF

la

lb

Closed

1

401A

393 A

Main M1, DT11...

Source 1

Bus 1 Bus 2

4D Feeder2D Feeder

Source 2

One-line

4C - Main Bkr 2

Stat

PF

la

lb

Closed

1

401A

393 A

Main M1, DT11...

Status

Main M1, DT 11 50_M2Main Bkr 2

Closed

PF Apparent 1

la 401 A

lb 394 A

lc 394 A

Vab 209 A

Vbc 206 A

Vca 207 A

Real Power 140 kW

Cp Count 54

Temp Maximum 97.3 ˚F

CF la 1.300

CF lb 1.400

CF lc 1.400

Trip Unit P/S 120VAC

Sensor/Plug 3200 A

Type Digitrip 1150

Location 1C

Breaker Code 2XIM

OffARMS

More

Page 6: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.

Control20Off

02:32:34 PM02/17/2017

adminLogout - 15:00

Lab Demo...10.130.14.247

Closed - Low Voltage Drawout Breaker4C - Main Bkr 2 - Main M1, DT 1150_M2

Communication Port INCOM

PF Apparaent 1

la 399 A

lb 396 A

lc 394A

Status Closed

Health Trends Channels

Docs

Status Normal

INST SDT Faults 9

LDT GFT Faults 7

Temperature Maximum 97.3 ℉

Operations Count 54

Last Trip

IL70C1036 EN IL DT 1150 Check Auxiliary Switch4C - Main Bkr 2 (Device) - Check Auxiliary Switch

04 PM 12 AM 08 AM334.3

334.4

334.5

334.6

334.7

Current Phase B (A)

Current Phase A (A)

Current Phase C (A)

Power Factor Apparent

334.8

334.9

334.3

334.4

334.5

334.6

334.7

334.8

334.9

334.3

334.4

334.5

334.6

334.7

334.8

334.9

1.0

1.0

1.0

1.0

1.0

1.0

1.0

PDF

02/16/201710:10:46 PM

Control

All ChannelsView Trendviewer

All Docs All Timeline Events

Choose an Action

Long Delay4C - Main Bkr 2 (Device) - Long Delay

Check Auxiliary Switch4C - Main Bkr 2 (Device) - Summary Alarm

Check Auxiliary Switch4C - Main Bkr 2 (Device) - Short Delay

Check Auxiliary Switch4C - Main Bkr 2 (Device) - Trip Event

02/16/20175:12:50 PM

02/16/20175:03:51 PM

02/16/20175:03:57 PM

02/16/20174:48:33 PM

02/16/20174:48:13 PM

Timeline

Acknowledge

Acknowledge

Acknowledge

Acknowledge

Acknowledge

Page 7: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.

Control20cal/cm2

ARMS Off

One-line

Elevation

TransferAutomatic

Timeline3 Alarms

Docs

Settings

Help

02:32:34 PM02/17/2017

adminLogout - 15:00

Lab Demo Gear10.130.14.247

Section 1

Compartment 1A Compartment 2A Compartment 3A Compartment 4A

Compartment 2D Compartment 3D Compartment 4D

1A 2A 3A 4ACompartment 1B Main Meter 1 Compartment 3B Meter Bus 2

HRG Tie Bkr Tie Bkr

Bus 2

Source 1 Source 2

2D Feeder 4D Feeder

Bus 1

Meter Bus 2

1B 2B 3A 4B

2C 3C 4C

2D1C 3D 4D

Section 2 Section 3 Section 4

20 cal/cm2

15 cal/cm2

10 cal/cm2

17 cal/cm2

Elevation

Elevation View allows you to see device alarms.

Page 8: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.

Control20cal/cm2

ARMS Off

One-line

Elevation

TransferAutomatic

Timeline3 Alarms

Docs

Settings

Help

02:32:34 PM02/17/2017

adminLogout - 15:00

Lab Demo Gear10.130.14.247

Elevation

Section 1

Compartment 1A Compartment 2A Compartment 3A Compartment 4A

Compartment 2D Compartment 3D Compartment 4D

1A 2A 3A 4ACompartment 1B Main Meter 1 Compartment 3B Meter Bus 2

HRG Tie Bkr Tie Bkr

Bus 2

Source 1 Source 2

2D Feeder 4D Feeder

Bus 1

Meter Bus 2

1B 2B 3A 4B

2C 3C 4C

2D1C 3D 4D

Section 2 Section 3 Section 4

20 cal/cm2

15 cal/cm2

10 cal/cm2

17 cal/cm2

4C - Main Bkr 2

Stat

PF

la

lb

Closed

1

401A

393 A

Main M1, DT11...

Status

Main M1, DT 11 50_M2Main Bkr 2

Closed

PF Apparent 1

la 401 A

lb 394 A

lc 394 A

Vab 209 A

Vbc 206 A

Vca 207 A

Real Power 140 kW

Cp Count 54

Temp Maximum 97.3 ˚F

CF la 1.300

CF lb 1.400

CF lc 1.400

Trip Unit P/S 120VAC

Sensor/Plug 3200 A

Type Digitrip 1150

Location 1C

Breaker Code 2XIM

OffARMS

More

Page 9: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.

Control20Off

02:32:34 PM02/17/2017

adminLogout - 15:00

Lab Demo...10.130.14.247

Closed - Low Voltage Drawout Breaker4C - Main Bkr 2 - Main M1, DT 1150_M2

Communication Port INCOM

PF Apparaent 1

la 399 A

lb 396 A

lc 394A

Status Closed

Health Trends Channels

Docs

Status Normal

INST SDT Faults 9

LDT GFT Faults 7

Temperature Maximum 97.3 ℉

Operations Count 54

Last Trip

IL70C1036 EN IL DT 1150 Check Auxiliary Switch4C - Main Bkr 2 (Device) - Check Auxiliary Switch

04 PM 12 AM 08 AM334.3

334.4

334.5

334.6

334.7

Current Phase B (A)

Current Phase A (A)

Current Phase C (A)

Power Factor Apparent

334.8

334.9

334.3

334.4

334.5

334.6

334.7

334.8

334.9

334.3

334.4

334.5

334.6

334.7

334.8

334.9

1.0

1.0

1.0

1.0

1.0

1.0

1.0

PDF

02/16/201710:10:46 PM

Control

All ChannelsView Trendviewer

All Docs All Timeline Events

Choose an Action

Long Delay4C - Main Bkr 2 (Device) - Long Delay

Check Auxiliary Switch4C - Main Bkr 2 (Device) - Summary Alarm

Check Auxiliary Switch4C - Main Bkr 2 (Device) - Short Delay

Check Auxiliary Switch4C - Main Bkr 2 (Device) - Trip Event

02/16/20175:12:50 PM

02/16/20175:03:51 PM

02/16/20175:03:57 PM

02/16/20174:48:33 PM

02/16/20174:48:13 PM

Timeline

Acknowledge

Acknowledge

Acknowledge

Acknowledge

Acknowledge

Page 10: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.

Control20cal/cm2

ARMS Off

One-line

Elevation

TransferAutomatic

Timeline3 Alarms

Docs

Settings

Help

02:32:34 PM02/17/2017

adminLogout - 15:00

Lab Demo Gear10.130.14.247

Device is in Alarm Status4C - Main Bkr 2 (Device) - Summary Alarm

02/16/20175:12:50 PMAcknowledge

Device is in Alarm Status4C - Main Bkr 2 (Device) - Summary Alarm

02/16/20175:12:50 PMAcknowledge

Device is in Alarm Status4C - Main Bkr 2 (Device) - Summary Alarm

02/16/20175:12:50 PMAcknowledge

Device is in Alarm Status4C - Main Bkr 2 (Device) - Summary Alarm

02/16/20175:12:50 PMAcknowledge

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Device is in Alarm Status4C - Main Bkr 2 (Device) - Long Delay

02/16/20175:12:50 PMAcknowledge

Device is in Alarm Status4C - Main Bkr 2 (Device) - Check Auzilary Switch

02/16/20175:12:50 PMAcknowledge

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Export Alarms Export Events Last 12 Months 23

Nothing Selected

Timeline3 Alarms

Page 11: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.

Control20cal/cm2

ARMS Off

One-line

Elevation

TransferAutomatic

Timeline3 Alarms

Docs

Settings

Help

02:32:34 PM02/17/2017

adminLogout - 15:00

Lab Demo Gear10.130.14.247

Device is in Alarm Status4C - Main Bkr 2 (Device) - Summary Alarm

02/16/20175:12:50 PMAcknowledge

Device is in Alarm Status4C - Main Bkr 2 (Device) - Summary Alarm

02/16/20175:12:50 PMAcknowledge

Device is in Alarm Status4C - Main Bkr 2 (Device) - Summary Alarm

02/16/20175:12:50 PMAcknowledge

Device is in Alarm Status4C - Main Bkr 2 (Device) - Summary Alarm

02/16/20175:12:50 PMAcknowledge

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Device is in Alarm Status4C - Main Bkr 2 (Device) - Long Delay

02/16/20175:12:50 PMAcknowledge

Device is in Alarm Status4C - Main Bkr 2 (Device) - Check Auzilary Switch

02/16/20175:12:50 PMAcknowledge

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Export Alarms Export Events Last 12 Months 23

Nothing SelectedTrip4C - Main Bkr 2 (Device) - Waveform Available

Trip4C - Main Bkr 2 (Device) - Wavef...

02/16/20175:12:50 PMAUTO-ACK

Cleared Cleared

Acknowledged Auto

Updates 1

Update Interval 0 Seconds

Priority Not Priority

Alarm ID 1270

Closed Closed

Device DT1150_M2

Compartment ID 4C

Last Update Time 02/16/2017

Trigger(On Value)

/waveforms/PXG900-Digitrip-1150-003-Trip-

20170216.221046.00.tgz

CurrentValue

/waveforms/PXG900-Digitrip-1150-003-Trip-

20170216.221046.00.tgz

5:10:46 PM

Trigger Time 02/16/20175:10:46 PM

View Alarm Details

View Alarm Details

View Device Details

Timeline3 Alarms

Page 12: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.

Control20Off

02:32:34 PM02/17/2017

adminLogout - 15:00

Lab Demo...10.130.14.247

Control20cal/cm2

ARMS Off

One-line

Elevation

TransferAutomatic

Timeline3 Alarms

Docs

Settings

Help

02:32:34 PM02/17/2017

adminLogout - 15:00

Lab Demo Gear10.130.14.247

Device is in Alarm Status4C - Main Bkr 2 (Device) - Summary Alarm

02/16/20175:12:50 PMAcknowledge

Device is in Alarm Status4C - Main Bkr 2 (Device) - Summary Alarm

02/16/20175:12:50 PMAcknowledge

Device is in Alarm Status4C - Main Bkr 2 (Device) - Summary Alarm

02/16/20175:12:50 PMAcknowledge

Device is in Alarm Status4C - Main Bkr 2 (Device) - Summary Alarm

02/16/20175:12:50 PMAcknowledge

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Device is in Alarm Status4C - Main Bkr 2 (Device) - Long Delay

02/16/20175:12:50 PMAcknowledge

Device is in Alarm Status4C - Main Bkr 2 (Device) - Check Auzilary Switch

02/16/20175:12:50 PMAcknowledge

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Export Alarms Export Events Last 12 Months 23

Nothing SelectedTrip4C - Main Bkr 2 (Device) - Waveform Available

Trip4C - Main Bkr 2 (Device) - Wavef...

02/16/20175:12:50 PMAUTO-ACK

Cleared Cleared

Acknowledged Auto

Updates 1

Update Interval 0 Seconds

Priority Not Priority

Alarm ID 1270

Closed Closed

Device DT1150_M2

Compartment ID 4C

Last Update Time 02/16/2017

Trigger(On Value)

/waveforms/PXG900-Digitrip-1150-003-Trip-

20170216.221046.00.tgz

CurrentValue

/waveforms/PXG900-Digitrip-1150-003-Trip-

20170216.221046.00.tgz

5:10:46 PM

Trigger Time 02/16/20175:10:46 PM

View Alarm Details

View Alarm Details

View Device Details

Time-Stamped Event Data

03/10/2017

07:01:30 PM

03/10/2017

07:01:45 PM

03/10/2017

07:02:00 PM

03/10/2017

07:02:15 PM

03/10/2017

07:02:30 PM

03/10/2017

07:02:45 PM

03/10/2017

07:03:00 PM

CURRENT

15k

10k

5k

0k

-5k

-10k

-15k

2C - Main Bkr 1 (Device) - Waveform AvailableTrip

Trip Details Waveform

IA 5343.00

IB 3996.00

IC 0.00

IG 0.00

IN 120.0

VAB 117.0

VBC 119.0

VCA 0.0

Power 0.0

Power Demand 23234

Energy --

Frequency 0.0

Reactive Power +1.0

pf --

THD IA --

THD IB --

Trip2C - Main Bkr 1 (Device)- Waveform Available

NoActive

NoCritical

0/waveforms/PXG900-

Digitrip-1150-001-Trip-20170310.190122.00.tgzSequence

YesClosed

Alarm Value

AutoACK

Control

View Trendviewer Documentation

IL70C1036 EN IL DT 1150 PDF

All Docs

Choose an Action Device Details

02/16/20175:12:50 PM

History

Page 13: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.

Control20Off

02:32:34 PM02/17/2017

adminLogout - 15:00

Lab Demo...10.130.14.247

Device is in Alarm Status4C - Main Bkr 2 (Device) - Summary Alarm

02/16/20175:12:50 PMAcknowledge

Device is in Alarm Status4C - Main Bkr 2 (Device) - Summary Alarm

02/16/20175:12:50 PMAcknowledge

Device is in Alarm Status4C - Main Bkr 2 (Device) - Summary Alarm

02/16/20175:12:50 PMAcknowledge

Device is in Alarm Status4C - Main Bkr 2 (Device) - Summary Alarm

02/16/20175:12:50 PMAcknowledge

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Device is in Alarm Status4C - Main Bkr 2 (Device) - Long Delay

02/16/20175:12:50 PMAcknowledge

Device is in Alarm Status4C - Main Bkr 2 (Device) - Check Auzilary Switch

02/16/20175:12:50 PMAcknowledge

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Trip4C - Main Bkr 2 (Device) - Waveform Available

02/16/20175:12:50 PMAUTO-ACK

Export Alarms Export Events Last 12 Months 23

Nothing SelectedTrip4C - Main Bkr 2 (Device) - Waveform Available

Trip4C - Main Bkr 2 (Device) - Wavef...

02/16/20175:12:50 PMAUTO-ACK

Cleared Cleared

Acknowledged Auto

Updates 1

Update Interval 0 Seconds

Priority Not Priority

Alarm ID 1270

Closed Closed

Device DT1150_M2

Compartment ID 4C

Last Update Time 02/16/2017

Trigger(On Value)

/waveforms/PXG900-Digitrip-1150-003-Trip-

20170216.221046.00.tgz

CurrentValue

/waveforms/PXG900-Digitrip-1150-003-Trip-

20170216.221046.00.tgz

5:10:46 PM

Trigger Time 02/16/20175:10:46 PM

View Alarm Details

View Alarm Details

View Device Details

Closed - Low Voltage Drawout Breaker4C - Main Bkr 2 - Main M1, DT 1150_M2

Communication Port INCOM

PF Apparaent 1

la 399 A

lb 396 A

lc 394A

Status Closed

Health Trends Channels

Docs

Status Normal

INST SDT Faults 9

LDT GFT Faults 7

Temperature Maximum 97.3 ℉

Operations Count 54

Last Trip

IL70C1036 EN IL DT 1150 Check Auxiliary Switch4C - Main Bkr 2 (Device) - Check Auxiliary Switch

04 PM 12 AM 08 AM334.3

334.4

334.5

334.6

334.7

Current Phase B (A)

Current Phase A (A)

Current Phase C (A)

Power Factor Apparent

334.8

334.9

334.3

334.4

334.5

334.6

334.7

334.8

334.9

334.3

334.4

334.5

334.6

334.7

334.8

334.9

1.0

1.0

1.0

1.0

1.0

1.0

1.0

PDF

02/16/201710:10:46 PM

Control

All ChannelsView Trendviewer

All Docs All Timeline Events

Choose an Action

Long Delay4C - Main Bkr 2 (Device) - Long Delay

Check Auxiliary Switch4C - Main Bkr 2 (Device) - Summary Alarm

Check Auxiliary Switch4C - Main Bkr 2 (Device) - Short Delay

Check Auxiliary Switch4C - Main Bkr 2 (Device) - Trip Event

02/16/20175:12:50 PM

02/16/20175:03:51 PM

02/16/20175:03:57 PM

02/16/20174:48:33 PM

02/16/20174:48:13 PM

Timeline

Acknowledge

Acknowledge

Acknowledge

Acknowledge

Acknowledge

Page 14: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.

Control20cal/cm2

ARMS Off

One-line

Elevation

TransferAutomatic

Timeline3 Alarms

Docs

Settings

Help

02:32:34 PM02/17/2017

adminLogout - 15:00

Lab Demo Gear10.130.14.247

Docs

Documentation and Drawings related to the Assembly

Documentation, Guides and Videos related to devices

pdf

pdf

pdf pdf pdf

Switchgear Assembly

L00G45l-N

IL70C1036 EN ILDT1150

L00G45l-S L00G45l-S1 L00G45L-R

Manuals

Edit View:

The Docs menu allows access to all saved documents, drawings, and studies

Page 15: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.

Control20Off

02:32:34 PM02/17/2017

adminLogout - 15:00

Lab Demo...10.130.14.247

ManualIL70C1036 EN IL DT1150.pdf

07/25/2014 01:10:09 PM Last Updated

Communication Port INCOM

PF Apparaent 1

la 399 A

lb 396 A

lc 394A

Status Closed

Health Trends Channels

Docs

Status Normal

INST SDT Faults 9

LDT GFT Faults 7

Temperature Maximum 97.3 ℉

Operations Count 54

Last Trip

IL70C1036 EN IL DT 1150 Check Auxiliary Switch4C - Main Bkr 2 (Device) - Check Auxiliary Switch

04 PM 12 AM 08 AM334.3

334.4

334.5

334.6

334.7

Current Phase B (A)

Current Phase A (A)

Current Phase C (A)

Power Factor Apparent

334.8

334.9

334.3

334.4

334.5

334.6

334.7

334.8

334.9

334.3

334.4

334.5

334.6

334.7

334.8

334.9

1.0

1.0

1.0

1.0

1.0

1.0

1.0

PDF

02/16/201710:10:46 PM

Control

All ChannelsView Trendviewer

All Docs All Timeline Events

Long Delay4C - Main Bkr 2 (Device) - Long Delay

Check Auxiliary Switch4C - Main Bkr 2 (Device) - Summary Alarm

Check Auxiliary Switch4C - Main Bkr 2 (Device) - Short Delay

Check Auxiliary Switch4C - Main Bkr 2 (Device) - Trip Event

02/16/20175:12:50 PM

02/16/20175:03:51 PM

02/16/20175:03:57 PM

02/16/20174:48:33 PM

02/16/20174:48:13 PM

Timeline

Acknowledge

Acknowledge

Acknowledge

Acknowledge

Acknowledge

21 220%of 80

21

Instructional Leaflet IL70C1036H06Effective October 2009

Digitrip models 1150, 1150i, 1150+, and 1150i+ trip units for use only in Magnum and Magnum DS circuit breakers

eaton corporation www.eaton.com

Data resets in meter screen

a Reset pushbutton operation will reset data values or group of values if the Reset pushbutton is depressed when screen value is displayed (see page 44 METER menu) .

Program settings PGM SET

Current curve type selection and pickup/time settings

General

Before placing any circuit breaker in operation, set each trip unit protection setting to the values specified by the engineer responsible for the installation . Each setting is programmed using the front panel pushbuttons and Save when the desired settings are selected . a few settings are interdependent (the LonG PU (Ir) rating will indirectly affect the SHoRT PU value) . Therefore, always verify these settings after programming by entering VIEW SETTINGS menu.

The installed rating plug must match the current sensors that establish the maximum continuous current rating of the circuit breaker (In) . Instantaneous and ground current settings are defined in multiples of (In) .

To illustrate the effect of each protection setting, simulated time-current curves are pictured on the face of the trip unit . Should an automatic trip occur (as a result of the current exceeding the pre-selected value), the LED in the appropriate segment of the simulated time-current curve will flash red, indicating the reason for the trip .

all Digitrip 1150 and Digitrip 1150i offer the LSI(G) curve as the standard factory default . The five-segment straight line curve of LonG PU and Time, SHoRT PU and Time, and InSTantaneous PU are depicted on the nameplate of the product . The GRoUnD (EaRTH) element is shown also on styles with ground fault protection . The LSIa style has ground alarm only function (see page 56 andpage 57) .

a second curve selection is also possible for UL/anSI styles . an IEEE curve that accurately follows the Inverse-Time characteristic equations can be selected (IEEE draft PC37 .112-11/95) . Curve shapes of MoDerately InVerse, VERY InVerse or ExTremely InVerse are available under PHaSE SLoPE . Each of these curve shapes have a PICKUP and TimeDIaL selection to position the curve . The short delay function is included as part of IEEE curve .

For the Digitrip 1150i, a second curve type is also possible for the international styles . an IEC curve type that accurately follows the IEC255 curve equations can be selected . The curve shapes of IEC-a (normal inverse), IEC-B (very inverse), and IEC-C (extremely inverse) are available under PHaSE SLoPE . Each of these curve shapes have a PICKUP and TimeDIaL selection to position the curve . The short delay function is included as part of IEC curve .

The available settings, for the LSIG standard curve along with the effects of changing the settings, are described below and in Figure 23 through Figure 30 . Sample settings are represented in boxes (e .g . )

LONG SLOPE setting

There is a I2t or I4t curve shape selection possible for LonG SLoPE .

LONG PU setting

There are 13 available long delay settings as illustrated in Figure 23 . Each setting, called (Ir), is expressed as a multiple (ranging from 0 .4 to 1 .0) of the current (In) .

otee:N (Ir) is also the basis for the short delay current setting (see Section 4) .

Figure 23. Long PU Settings

LongTIME setting

There are 45 available Long Delay Time settings I2t, as illustrated in Figure 24, ranging from 2 to 24 seconds . For the I4t slope, there are nine settings ranging from 1 to 5 seconds . These settings represent the total clearing times when the current value equals six times (Ir) .

Figure 24. Long Delay Time Settings

otee:N In addition to the standard Long Delay Protection element, the Digitrip 1150 trip units using LonG SLoPE settings of I2t or I4t also have a Long Time Memory (LTM) function, which protects load circuits from the effects of repeated overload conditions . If a circuit breaker is closed soon after a long delay trip, and the current again exceeds the long delay setting, (Ir), the LTM automatically reduces the time to trip to allow for the fact that the load circuit temperature is already higher than normal because of the prior overload condition . Each time the overload condition is repeated, the LTM causes the circuit breaker to trip in a progressively shorter time . When the load current returns to normal, the LTM begins to reset; after about ten minutes it will have reset fully, so the next long delay trip time will again correspond to the setting value .

otee:N In certain applications and field testing, it may be desirable to disable the LTM function by disabling this function in program settings .

The action of the LTM must be considered when performing multiple long delay time tests (see Section 5) .

Long PU Setting lr

1 x ln = lr

lr

available Settings

0 .4, 0 .45, 0 .5, 0 .55, 0 .6, 0 .65, 0 .7, 0 .75, 0 .8, 0 .85,

0 .9, 0 .05, 1 .0 In Multiples of amperes (ln)

lr

Long Time

2 Seconds at 6 x lr

available Settings

2 .0, 2 .5, 3 .0, 3 .5, 4 .0, 4 .5 . . .

22 .0, 22 .5, 23 .0, 23 .5, 24 .0

Seconds at

6 Times Long PU Setting (lr)

6 x lr

Device Details view allows access to documents for the specific device you are viewing.

Page 16: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.

Control20cal/cm2

ARMS Off

One-line

Elevation

TransferAutomatic

Timeline3 Alarms

Docs

Settings

Help

02:32:34 PM02/17/2017

adminLogout - 15:00

Lab Demo Gear10.130.14.247

4D - C4

Trip U...

Senso...

Type

Locat...

120 V...

800 A

Digitr...

4D

Main M1

2D - C2

Trip U...

Senso...

Type

Locat...

120 V...

800 A

Digitr...

2D

Main M1

3C - Tie Bkr

Stat

PF

la

lb

Open

--

0 A

0A

Main M1, DT11...

20 cal/cm217 cal/cm2

20 cal/cm2 20 cal/cm2

2C- Main Bkr 1

Stat

PF

la

lb

Closed

1

398 A

393 A

Main M1, DT11...

4C - Main Bkr 2

Stat

PF

la

lb

Closed

1

401A

393 A

Main M1, DT11...

Source 1

Bus 1 Bus 2

4D Feeder2D Feeder

Source 2

One-line

Choose an Action

Setpoints

View Setpoints

Edit Setpoints

Page 17: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.

02:32:34 PM02/17/2017

adminLogout - 15:00

Lab Demo...10.130.14.247

20Off

02:32:34 PM02/17/2017

adminLogout - 15:00

Lab Demo...10.130.14.247

in EditMode

Current Protection

Enabled

Curve type

Phase Slope

Pickup Ir (xln) 720.00A

Time Dial

Short Delay Pickup (xlr)

12t

External CT

1440.00A

Short Delay Time (S)

Instantaneous Pickup (xln) 3200.00A

Ground Pickup (xln) 320.00A

Ground Slope

Ground Time

Ground Current Sensing

Device ConfigurationDT1150_M2 Choose an Action

IEEE

Moderate Inverse

2.0

2.0

2.0

2.0

2.0

2.0

2.0

M1

Flat

Residual

The Setup Screen you can manage device from the Setup Screen.

Page 18: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.

REMOTE

BE EFFICIENT

HOME

ARC REDUCTION

PPE

Find information, receive safety prompts, and perform

operations remotely for innovations that will get you

through the day and back home safer than ever.

Page 19: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.

Control20cal/cm2

ARMS Off

One-line

Elevation

TransferAutomatic

Timeline3 Alarms

Docs

Settings

Help

02:32:34 PM02/17/2017

adminLogout - 15:00

Lab Demo Gear10.130.14.247

4D - C4

Trip U...

Senso...

Type

Locat...

120 V...

800 A

Digitr...

4D

Main M1

2D - C2

Trip U...

Senso...

Type

Locat...

120 V...

800 A

Digitr...

2D

Main M1

3C - Tie Bkr

Stat

PF

la

lb

Open

--

0 A

0A

Main M1, DT11...

20 cal/cm217 cal/cm2

20 cal/cm2 20 cal/cm2

2C- Main Bkr 1

Stat

PF

la

lb

Closed

1

398 A

393 A

Main M1, DT11...

4C - Main Bkr 2

Stat

PF

la

lb

Closed

1

401A

393 A

Main M1, DT11...

Source 1

Bus 1 Bus 2

4D Feeder2D Feeder

Source 2

One-line

Page 20: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.

One-line

Elevation

TransferAutomatic

Timeline3 Alarms

Docs

Settings

Help

02:32:34 PM02/17/2017

adminLogout - 15:00

Lab Demo Gear10.130.14.247

20cal/cm2

ARMS Off

4D - C4

Trip U...

Senso...

Type

Locat...

120 V...

800 A

Digitr...

4D

Main M1

2D - C2

Trip U...

Senso...

Type

Locat...

120 V...

800 A

Digitr...

2D

Main M1

3C - Tie Bkr

Stat

PF

la

lb

Open

--

0 A

0A

Main M1, DT11...

20 cal/cm217 cal/cm2

20 cal/cm2 20 cal/cm2

4C - Main Bkr 2

Stat

PF

la

lb

Closed

1

401A

393 A

Main M1, DT11...

Source 1

Bus 1 Bus 2

4D Feeder2D Feeder

Source 2

2C- Main Bkr 1

Stat

PF

la

lb

Closed

1

398 A

393 A

Timeout In: 14:59In Control Mode

Control mode is confirmed by striped background.

Page 21: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.

One-line

Elevation

TransferAutomatic

Timeline3 Alarms

Docs

Settings

Help

02:32:34 PM02/17/2017

adminLogout - 15:00

20cal/cm2

ARMS Off

Lab Demo Gear10.130.14.247

4D - C4

Trip U...

Senso...

Type

Locat...

120 V...

800 A

Digitr...

4D

Main M1

2D - C2

Trip U...

Senso...

Type

Locat...

120 V...

800 A

Digitr...

2D

Main M1

3C - Tie Bkr

Stat

PF

la

lb

Open

--

0 A

0A

Main M1, DT11...

20 cal/cm217 cal/cm2

20 cal/cm2 20 cal/cm2

Source 1

Bus 1 Bus 2

4D Feeder2D Feeder

Source 2

4C - Main Bkr 2

Stat

PF

la

lb

Closed

1

401A

393 A

Main M1, DT11...

2C- Main Bkr 1

Stat

PF

la

lb

Closed

1

398 A

393 A

Main M1, DT11...

Timeout In: 14:59In Control Mode

Status

Main M1, DT 11 50_M2Main Bkr 2

Closed

PF Apparent 1

la 399 A

lb 395 A

lc 397 A

Vab 208 A

Vbc 206 A

Vca 208 A

Real Power 140 kW

Cp Count 54

Temp Maximum 97.3 ˚F

CF la 1.300

CF lb 1.400

CF lc 1.400

Trip Unit P/S 120VAC

Sensor/Plug 3200 A

Type Digitrip 1150

Location 1C

Breaker Code 2XIM

OffARMS

More

Open Breaker

Enable ARMS

Page 22: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.

One-line

Elevation

TransferAutomatic

Timeline3 Alarms

Docs

Settings

Help

02:32:34 PM02/17/2017

adminLogout - 15:00

20cal/cm2

ARMS Off

Lab Demo Gear10.130.14.247

4D - C4

Trip U...

Senso...

Type

Locat...

120 V...

800 A

Digitr...

4D

Main M1

2D - C2

Trip U...

Senso...

Type

Locat...

120 V...

800 A

Digitr...

2D

Main M1

3C - Tie Bkr

Stat

PF

la

lb

Open

--

0 A

0A

Main M1, DT11...

20 cal/cm217 cal/cm2

20 cal/cm2 20 cal/cm2

Source 1

Bus 1 Bus 2

4D Feeder2D Feeder

Source 2

4C - Main Bkr 2

Stat

PF

la

lb

Closed

1

401A

393 A

Main M1, DT11...

2C- Main Bkr 1

Stat

PF

la

lb

Closed

1

398 A

393 A

Main M1, DT11...

Timeout In: 14:59In Control Mode

Status

Main M1, DT 11 50_M2Main Bkr 2

Closed

PF Apparent 1

la 399 A

lb 395 A

lc 397 A

Vab 208 A

Vbc 206 A

Vca 208 A

Real Power 140 kW

Cp Count 54

Temp Maximum 97.3 ˚F

CF la 1.300

CF lb 1.400

CF lc 1.400

Trip Unit P/S 120VAC

Sensor/Plug 3200 A

Type Digitrip 1150

Location 1C

Breaker Code 2XIM

OffARMS

More

Open Breaker

Enable ARMS

Cancel Open Breaker

PPE 3 17 cml/cm2 4’41” ARMS OnMain Bkr 2 (Device)Open Breaker

Before approaching the Assembly be sure to wear all requiredPersonal Protection Equipment and Activate Arcflash ReductionMaintenance (ARMS)

Voltage

ArcFlash Hood(25cal/cm2)

25 cal/cm2

Safety Glassesor Goggles

Current

Feeding

I am wearing required PPE or controlling remotely

207 3 V

396.7 A

Main Bkr 2 (Device)

This action will Open Breaker on Main Bkr2 (Device) and affect downstream devices.

You must confirm that you are wearing the proper PPE, before opening the breaker.

Pop-up screen will inform you of the arc energy, PPE requirements, & which downfield devices will be affected.

Page 23: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.

One-line

Elevation

TransferAutomatic

Timeline3 Alarms

Docs

Settings

Help

02:32:34 PM02/17/2017

adminLogout - 15:00

Lab Demo Gear10.130.14.247

20cal/cm2

ARMS Off

4D - C4

Trip U...

Senso...

Type

Locat...

120 V...

800 A

Digitr...

4D

Main M1

2D - C2

Trip U...

Senso...

Type

Locat...

120 V...

800 A

Digitr...

2D

Main M1

3C - Tie Bkr

Stat

PF

la

lb

Open

--

0 A

0A

Main M1, DT11...

20 cal/cm217 cal/cm2

20 cal/cm2 20 cal/cm2

4C - Main Bkr 2

Stat

PF

la

lb

Closed

1

401A

393 A

Main M1, DT11...

Source 1

Bus 1 Bus 2

4D Feeder2D Feeder

Source 2

2C- Main Bkr 1

Stat

PF

la

lb

Closed

1

398 A

393 A

Timeout In: 14:59In Control Mode

Page 24: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.

One-line

Elevation

TransferAutomatic

Timeline3 Alarms

Docs

Settings

Help

02:32:34 PM02/17/2017

adminLogout - 15:00

20cal/cm2

ARMS Off

Lab Demo Gear10.130.14.247

4D - C4

Trip U...

Senso...

Type

Locat...

120 V...

800 A

Digitr...

4D

Main M1

2D - C2

Trip U...

Senso...

Type

Locat...

120 V...

800 A

Digitr...

2D

Main M1

3C - Tie Bkr

Stat

PF

la

lb

Open

--

0 A

0A

Main M1, DT11...

20 cal/cm217 cal/cm2

20 cal/cm2 20 cal/cm2

Source 1

Bus 1 Bus 2

4D Feeder2D Feeder

Source 2

4C - Main Bkr 2

Stat

PF

la

lb

Closed

1

401A

393 A

Main M1, DT11...

2C- Main Bkr 1

Stat

PF

la

lb

Closed

1

398 A

393 A

Main M1, DT11...

Timeout In: 14:59In Control Mode

Status

Main M1, DT 11 50_M2Main Bkr 2

Closed

PF Apparent 1

la 399 A

lb 395 A

lc 397 A

Vab 208 A

Vbc 206 A

Vca 208 A

Real Power 140 kW

Cp Count 54

Temp Maximum 97.3 ˚F

CF la 1.300

CF lb 1.400

CF lc 1.400

Trip Unit P/S 120VAC

Sensor/Plug 3200 A

Type Digitrip 1150

Location 1C

Breaker Code 2XIM

OffARMS

More

Open Breaker

Enable ARMS

Page 25: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.

One-line

Elevation

TransferAutomatic

Timeline3 Alarms

Docs

Settings

Help

02:32:34 PM02/17/2017

adminLogout - 15:00

20cal/cm2

ARMS Off

Lab Demo Gear10.130.14.247

4D - C4

Trip U...

Senso...

Type

Locat...

120 V...

800 A

Digitr...

4D

Main M1

2D - C2

Trip U...

Senso...

Type

Locat...

120 V...

800 A

Digitr...

2D

Main M1

3C - Tie Bkr

Stat

PF

la

lb

Open

--

0 A

0A

Main M1, DT11...

20 cal/cm217 cal/cm2

20 cal/cm2 20 cal/cm2

Source 1

Bus 1 Bus 2

4D Feeder2D Feeder

Source 2

4C - Main Bkr 2

Stat

PF

la

lb

Closed

1

401A

393 A

Main M1, DT11...

2C- Main Bkr 1

Stat

PF

la

lb

Closed

1

398 A

393 A

Main M1, DT11...

Timeout In: 14:59In Control Mode

Status

Main M1, DT 11 50_M2Main Bkr 2

Closed

PF Apparent 1

la 399 A

lb 395 A

lc 397 A

Vab 208 A

Vbc 206 A

Vca 208 A

Real Power 140 kW

Cp Count 54

Temp Maximum 97.3 ˚F

CF la 1.300

CF lb 1.400

CF lc 1.400

Trip Unit P/S 120VAC

Sensor/Plug 3200 A

Type Digitrip 1150

Location 1C

Breaker Code 2XIM

OffARMS

More

Open Breaker

Enable ARMS

Cancel Enable ARMS

Choose Breakers to Enable ARMS ModeEnable ARMS

Main Bkr 1Main Bkr 1 (Device)

Tie Bkr 1Tie Bkr (Device)

Main Bkr 2

Enabling ARMS will result in

Main Bkr 2 (Device)

Enable ARMSon

For work on

12cal/cm2 at 2’ Working Distance on Main Bkr 2

7cal/cm2 at 2’ Working Distance on DownstreamDevices

2C

3C

4C

Main Bkr 2

Downstream Devices

Indicates the Breaker & down stream devices that will have ARMS enabled.

Page 26: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.

One-line

Elevation

TransferAutomatic

Timeline3 Alarms

Docs

Settings

Help

02:32:34 PM02/17/2017

adminLogout - 15:00

20cal/cm2

ARMS Off

Lab Demo Gear10.130.14.247

4D - C4

Trip U...

Senso...

Type

Locat...

120 V...

800 A

Digitr...

4D

Main M1

2D - C2

Trip U...

Senso...

Type

Locat...

120 V...

800 A

Digitr...

2D

Main M1

3C - Tie Bkr

Stat

PF

la

lb

Open

--

0 A

0A

Main M1, DT11...

20 cal/cm217 cal/cm2

20 cal/cm2 20 cal/cm2

Source 1

Bus 1 Bus 2

4D Feeder2D Feeder

Source 2

4C - Main Bkr 2

Stat

PF

la

lb

Closed

1

401A

393 A

Main M1, DT11...

2C- Main Bkr 1

Stat

PF

la

lb

Closed

1

398 A

393 A

Main M1, DT11...

Timeout In: 14:59In Control Mode

Status

Main M1, DT 11 50_M2Main Bkr 2

Closed

PF Apparent 1

la 399 A

lb 395 A

lc 397 A

Vab 208 A

Vbc 206 A

Vca 208 A

Real Power 140 kW

Cp Count 54

Temp Maximum 97.3 ˚F

CF la 1.300

CF lb 1.400

CF lc 1.400

Trip Unit P/S 120VAC

Sensor/Plug 3200 A

Type Digitrip 1150

Location 1C

Breaker Code 2XIM

OffARMS

More

Open Breaker

Enable ARMS

On

20cal/cm2

ARMS On

Status Closed

PF Apparent 1

la 399 A

lb 395 A

lc 397 A

Vab 208 A

Vbc 206 A

Vca 208 A

Real Power 140 kW

Cp Count 54

Temp Maximum 97.3 ˚F

CF la 1.300

CF lb 1.400

CF lc 1.400

Trip Unit P/S 120VAC

Sensor/Plug 3200 A

Type Digitrip 1150

Location 1C

Breaker Code 2XIM

OnARMS

Open Breaker

Disable ARMS

Once ARMS has been engaged, the One Line Diagram will provide graphical indication of affected circuits & devices as well as energy levels.

Page 27: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.

Elevation

One-line

TransferAutomatic

Timeline3 Alarms

Docs

Settings

Help

02:32:34 PM02/17/2017

adminLogout - 15:00

20cal/cm2

ARMS Off

Lab Demo Gear10.130.14.247

One-line

Timeout In: 14:59In Control Mode20cal/cm2

ARMS On

Section 1

Compartment 1A Compartment 2A Compartment 3A Compartment 4A

Compartment 2D Compartment 3D Compartment 4D

1A 2A 3A 4ACompartment 1B Main Meter 1 Compartment 3B Meter Bus 2

HRG Main Bkr 1 Tie Bkr

Bus 2

Source 2

2D Feeder 4D Feeder

Bus 1

Meter Bus 2

1B 2B 3A 4B

2C 3C 4C

2D1C 3D 4D

Section 2 Section 3 Section 4

On

15 cal/cm2

10 cal/cm2

17 cal/cm2

Once ARMS has been engaged, the Elevation View will provide graphical indication of affected circuits & devices as well as energy

Page 28: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.

Control20cal/cm2

ARMS Off

One-line

Elevation

TransferAutomatic

Timeline3 Alarms

Docs

Settings

Help

02:32:34 PM02/17/2017

adminLogout - 15:00

Lab Demo Gear10.130.14.247

Section 1

Compartment 1A Compartment 2A Compartment 3A Compartment 4A

Compartment 2D Compartment 3D Compartment 4D

1A 2A 3A 4ACompartment 1B Main Meter 1 Compartment 3B Meter Bus 2

HRG Tie Bkr Tie Bkr

Bus 2

Source 1 Source 2

2D Feeder 4D Feeder

Bus 1

Meter Bus 2

1B 2B 3A 4B

2C 3C 4C

2D1C 3D 4D

Section 2 Section 3 Section 4

20 cal/cm2

15 cal/cm2

10 cal/cm2

17 cal/cm2

Elevation

Page 29: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.

Control20cal/cm2

ARMS Off

One-line

Elevation

TransferAutomatic

Timeline3 Alarms

Docs

Settings

Help

02:32:34 PM02/17/2017

adminLogout - 15:00

Lab Demo Gear10.130.14.247

PPE 4 27 cml/cm2 4’41” OnDisplaying Highest Safety Levels in SwitchgearSafety Panel

Source 1

Arc Flash Boundary

Incident Energy 27 cal/cm2

--

4

3

--

10 cal/cm2

PPE Level

Arc Flash Boundary

Incident Energy

PPE level

2

--

7 cal/cm2

Arc Flash Boundary

Incident Energy

PPE level

Line Side of Main Bkr 1 (Device)The following items are required for PPE Level 2

Balaclava

Safety Glasses or Goggles

Flame ResistantCoveralls

In-Ear Protection

Voltage Rated Gloves

Leather Boots

Required Personal Protective Equipment

Bus 1Load Side of Main Brkr 1 (Device)

Bus 2Load Side of Main Brkr 2 (Device)

PPE 4 27 cml/cm2 4’41” OnDisplaying Highest Safety Levels in SwitchgearSafety Panel

Source 1

Arc Flash Boundary

Incident Energy 27 cal/cm2

--

4

3

--

10 cal/cm2

PPE Level

Arc Flash Boundary

Incident Energy

PPE level

2

--

7 cal/cm2

Arc Flash Boundary

Incident Energy

PPE level

Line Side of Main Bkr 1 (Device)The following items are required for PPE Level 2

Balaclava

Safety Glasses or Goggles

Flame ResistantCoveralls

In-Ear Protection

Voltage Rated Gloves

Leather Boots

Required Personal Protective Equipment

Bus 1Load Side of Main Brkr 1 (Device)

Bus 2Load Side of Main Brkr 2 (Device)

PPE Level, Arc Incident Energy & Arc Flash Boundary of each device is shown

Page 30: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.

Control20cal/cm2

ARMS Off

One-line

Elevation

TransferAutomatic

Timeline3 Alarms

Docs

Settings

Help

02:32:34 PM02/17/2017

adminLogout - 15:00

Lab Demo Gear10.130.14.247

PPE 4 27 cml/cm2 4’41” OnDisplaying Highest Safety Levels in SwitchgearSafety Panel

Source 1

Arc Flash Boundary

Incident Energy 27 cal/cm2

--

4

3

--

10 cal/cm2

PPE Level

Arc Flash Boundary

Incident Energy

PPE level

2

--

7 cal/cm2

Arc Flash Boundary

Incident Energy

PPE level

Line Side of Main Bkr 1 (Device)The following items are required for PPE Level 2

Balaclava

Safety Glasses or Goggles

Flame ResistantCoveralls

In-Ear Protection

Voltage Rated Gloves

Leather Boots

Required Personal Protective Equipment

Bus 1Load Side of Main Brkr 1 (Device)

Bus 2Load Side of Main Brkr 2 (Device)

PPE 4 27 cml/cm2 4’41” OnDisplaying Highest Safety Levels in SwitchgearSafety Panel

Source 1

Arc Flash Boundary

Incident Energy 20 cal/cm2

--

3

3

--

10 cal/cm2

PPE Level

Arc Flash Boundary

Incident Energy

PPE level

3

--

15 cal/cm2

Arc Flash Boundary

Incident Energy

PPE level

Line Side of Main Bkr 1 (Device)The following items are required for PPE Level 2

ArcFlash Hood (25cal/cm2)

Safety Glasses or Goggles

Arc Rated Coveralls

In-Ear Protection

Voltage Rated Gloves

Leather Boots

Required Personal Protective Equipment

Bus 1Load Side of Main Brkr 1 (Device)

Bus 2Load Side of Main Brkr 2 (Device)

25cal/cm2

25 cal/cm2

Page 31: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.

Control20cal/cm2

ARMS Off

One-line

Elevation

TransferAutomatic

Timeline3 Alarms

Docs

Settings

Help

02:32:34 PM02/17/2017

adminLogout - 15:00

Lab Demo Gear10.130.14.247

PPE 4 27 cml/cm2 4’41” OnDisplaying Highest Safety Levels in SwitchgearSafety Panel

Source 1

Arc Flash Boundary

Incident Energy 27 cal/cm2

--

4

3

--

10 cal/cm2

PPE Level

Arc Flash Boundary

Incident Energy

PPE level

2

--

7 cal/cm2

Arc Flash Boundary

Incident Energy

PPE level

Line Side of Main Bkr 1 (Device)The following items are required for PPE Level 2

Balaclava

Safety Glasses or Goggles

Flame ResistantCoveralls

In-Ear Protection

Voltage Rated Gloves

Leather Boots

Required Personal Protective Equipment

Bus 1Load Side of Main Brkr 1 (Device)

Bus 2Load Side of Main Brkr 2 (Device)

PPE 4 27 cml/cm2 4’41” OnDisplaying Highest Safety Levels in SwitchgearSafety Panel

Source 1

Arc Flash Boundary

Incident Energy 27 cal/cm2

--

4

3

--

10 cal/cm2

PPE Level

Arc Flash Boundary

Incident Energy

PPE level

3

--

15 cal/cm2

Arc Flash Boundary

Incident Energy

PPE level

Line Side of Main Bkr 1 (Device)Example of Boundaries and Definitions

Zero Distance

Prohibited Space

Restricted Space

Limited Space

Individual

Arc Flash Boundary (Outer Boundary)

Arc Flash Boundary Diagram

Bus 1Load Side of Main Brkr 1 (Device)

Bus 2Load Side of Main Brkr 2 (Device)

Restricted Approach Boundary

Limited Approach Boundary

Arc Flash Boundary

Page 32: Introducing the Eaton · 2019-12-24 · Introducing the Eaton® Power Xpert Dashboard. An intuitive, innovative way to improve safety and efficiency, allowing for seamless operation.

Eaton is a registered trademark.

All other trademarks are property of their respective owners.

Eaton1000 Eaton BoulevardCleveland, OH 44122United StatesEaton.com

© 2017 EatonAll Rights ReservedPrinted in USAPublication No. MZ145001ENMarch 2017