INTERNAL EROSIONAssociated with Conduits
through Embankments
by
Hal Van AllerMaryland Dam Safety
![Page 2: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/2.jpg)
Embankment Dam Schematic
![Page 3: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/3.jpg)
![Page 4: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/4.jpg)
Medford Quarry Wash Pond CMP failure
![Page 5: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/5.jpg)
Velvet Hills sinkhole
![Page 6: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/6.jpg)
Sinkhole in crest of new MD dam
![Page 7: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/7.jpg)
![Page 8: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/8.jpg)
WCC (Joe Kula) Testpit along pond CMP spillway
![Page 9: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/9.jpg)
AACounty CMP with void
![Page 10: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/10.jpg)
Loveton Dam Failure (1989) Breach
![Page 11: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/11.jpg)
![Page 12: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/12.jpg)
![Page 13: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/13.jpg)
Anti-seep collars do
not prevent seepage failures!
![Page 14: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/14.jpg)
Loveton 78” CMP viewed from downstream
78 inch CMP viewed from downstream
![Page 15: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/15.jpg)
Failed PVC pipe with anti-seep collar
![Page 16: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/16.jpg)
Annap Mall collapsed CMP d.s. of Riser
![Page 17: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/17.jpg)
Annap Mall u.s. view
![Page 18: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/18.jpg)
What caused these failures?• Design• Construction• Inspection• All of the
above??
![Page 19: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/19.jpg)
Spillways are “Confined Space”
![Page 20: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/20.jpg)
Ray Martin cave
![Page 21: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/21.jpg)
Typical Problems schematic
![Page 22: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/22.jpg)
![Page 23: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/23.jpg)
Compaction in Haunches
![Page 24: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/24.jpg)
Pipe Installation in DamDam Embankment
Filter Diaphragm
Flowable FillPipe in vertical trench
![Page 25: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/25.jpg)
![Page 26: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/26.jpg)
![Page 27: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/27.jpg)
Excavation through dam
• Side slopes must be 2(H):1(V) or flatter
15 ft
![Page 28: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/28.jpg)
![Page 29: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/29.jpg)
![Page 30: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/30.jpg)
FILTER DIAPHRAGM
![Page 31: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/31.jpg)
Centennial Park dam chimney drain construction
![Page 32: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/32.jpg)
Filter Diaphragmflooding with water for
compaction
![Page 33: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/33.jpg)
Merkle Filter Diaphragm with vibrator
![Page 34: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/34.jpg)
![Page 35: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/35.jpg)
CONSTRUCTIONExperienced contractor desired
• must realize that ponds are different from roads and utilities
• must work with design engineer• compaction along spillway is critical--
don’t construct embankment and then cut trench
• spillway joints must be watertight
![Page 36: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/36.jpg)
Alternative Designs• Avoid large diameter CMP• User weir or drop box structure• If pipes unavoidable, use:
– Concrete pressure pipe (min. ASTM C-361)– Complete concrete cradle or flowable fill– Watertight joints with o-ring gaskets– Filter diaphragm
• Avoid combining pond with road embankment
![Page 37: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/37.jpg)
Chute Spillways
![Page 38: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/38.jpg)
Concrete flumes on embankment have problems too
![Page 39: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/39.jpg)
![Page 40: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/40.jpg)
CMP spillway on steep slope through dam embankment
![Page 41: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/41.jpg)
Tasker’s Chance concrete weir
![Page 42: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/42.jpg)
Crooksville, OHIO-COMPLETED WEIR
![Page 43: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/43.jpg)
![Page 44: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/44.jpg)
Parker Pond new sheet pile spillway
![Page 45: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/45.jpg)
Do's and Don’ts for Pond Design and Construction
• Don’t use anti-seep collars to “stop” leakage• Do use filter diaphragms• Don’t allow spillway installation in trench• Do require watertight joints• Do inspect each pipe joint as it is put together
so it can be redone if necessary• Do consider alternative spillway design that
eliminates pipe through dam or foundation
![Page 46: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/46.jpg)
InspectionMore than just testing Compaction!
• Inspector should:! work for the design engineer, not the
contractor! understand design assumptions and effects
of unanticipated conditions! not allow deviation from design without
design engineer’s approval! observe and document: pipe mfg marks, joint
type, gasket material and size, and installation procedure
![Page 47: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/47.jpg)
Foundation
• Proof rolling• Inspection by Geotechnical Engineer
![Page 48: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/48.jpg)
Compaction
• Use STANDARD Proctor (ASTM D-698 or AASHTO T-99)
• Do Not use MODIFIED Proctor (ASTM D-1557 or AASHTO T-180)
• Nuclear gage readings need to be corrected to match lab moisture & density
![Page 49: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/49.jpg)
Utility Conduits(water, sewer, gas)
• Pipes through the dam must meet spillway requirements
• No granular backfill for pipes parallel to the dam axis
![Page 50: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/50.jpg)
Pre-cast riser structures
![Page 51: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/51.jpg)
Anchor Plates
Movement
![Page 52: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/52.jpg)
Leaky Joints
![Page 53: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/53.jpg)
Concrete Pipe Installation
• Pipe supports• Clean and Lubricate joints• Lubricate Gasket• Tension Gasket• Full concrete cradle, not just bedding• If not o-ring gaskets then owner and
engineer must approve
![Page 54: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/54.jpg)
![Page 55: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/55.jpg)
![Page 56: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/56.jpg)
![Page 57: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/57.jpg)
Prepare foundation and supports
![Page 58: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/58.jpg)
Mudmat is a good idea
![Page 59: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/59.jpg)
Clean joints
![Page 60: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/60.jpg)
Lubricate joints
![Page 61: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/61.jpg)
Lubricate o-ring
![Page 62: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/62.jpg)
Tension o-ring withround-shaft screwdriver
![Page 63: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/63.jpg)
Mis-aligned o-ring ...
![Page 64: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/64.jpg)
...causes broken bell
![Page 65: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/65.jpg)
Gaskets for Concrete PipeTraditional O-ring joint
•Deep joint allows for substantial extensibility
•Symmetric design accommodates internal or external pressure
![Page 66: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/66.jpg)
Newer “Profile Gaskets”
Press-Seal Gasket Company states these “advantages” over o-rings:
•Stepped joint is cheaper to manufacture than groove for confined o-ring gasket
•Easier to install, less force needed to “home” joint
•Less bell breakage
![Page 67: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/67.jpg)
Gaskets for Concrete PipeNew style “Profile Joint”
•Smaller joint separation allowance
•Designed for internal pressure
![Page 68: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/68.jpg)
Gaskets for Concrete PipeNew style “Profile Joint”
![Page 69: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/69.jpg)
Formed concrete cradle
![Page 70: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/70.jpg)
Cradle poured against
soil
![Page 71: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/71.jpg)
Poor installation
![Page 72: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/72.jpg)
![Page 73: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/73.jpg)
![Page 74: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/74.jpg)
![Page 75: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/75.jpg)
![Page 76: INTERNAL EROSION Associated with Conduits through Embankments](https://reader030.fdocuments.in/reader030/viewer/2022020700/61f5da49f7a048254552982b/html5/thumbnails/76.jpg)
Dam on Soft Foundation