The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local JohnsonControls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 03/01 Johnson Controls, Inc
1/1
300s_ductdetect 1900126 9thcc:na Rev:02/22/01logo:
left ft:
right ft:standardSect# = 0seQ# = 1
300 Series
Intelligent Duct Smoke DetectorsDH300RP.tif
DescriptionThe DH300 Series photoelectric air duct smoke detectors feature an efficient housing design that samples air passing through an air handling system duct and detects if there is a developing smoke hazard. When sufficient levels of smoke are sensed, an alarm signal is initiated, which may be connected to a fire control panel monitoring the detector, and appropriate action can be taken to shut off fans and blowers, change over air handling systems, etc. This can isolate toxic smoke and fire gases or prevent their distribution throughout the areas served by the duct system.
The 300 Series modules will operate with both FlashScan and non-FlashScan systems; however, some of their features can only be utilized with FlashScan capable control panels.
Features• addressable, analog communication
• dual light-emitting diodes (LEDs)
• remote alarm output
To OrderSpecify the code number in the following selection chart
Selection Chart
Accessories
Inlet Tube Selection
Code Number Description
DH300P Intelligent Photoelectric Smoke Detector in Duct Housing
DH300RPIntelligent Photoelectric Smoke Detector with DPDT Relay in Duct Housing
Code Number Description
RA400Z Remote Alarm Annunciator LED
RTS451 Remote Test Station
RTS451KEY Key-activated Remote Test Station
Outside Duct Width Inlet Tube Required
Up to 2 Feet ST-1.5
2 to 4 Feet ST-3
4 to 8 Feet ST-5
8 to 10 Feet ST-10
! WARNING: Duct smoke detectors are life safety devcies used to prevent the spread of smoke within a building. They should not be considered fire detection devices, even though they may be required to be connected to the building’s fire alarm system per NFPA 90A.
Specifications
Electrical Characteristics
300 Series Intelligent Duct Smoke Detectors
Operating Temperature Range 0 to 55°C (32 to 131°F)
Humidity Range 10 to 93% (non-condensing)
Duct Air Velocity152.4 to 1219.2 meters/min(500 to 4,000 ft/min)
Dimensions (H x W x D)13.97 x 365.13 x 69.85 cm(5.50 x 14.38 x 2.75 in.)
Description Electrical Rating
Operating Voltage Range 15 to 32 VDC (SLC communication line voltage)
Auxiliary Power Input
DH300RP 24 VAC/DC or 120/240 VAC (separate source)
SLC Standby Current300 µA @ 24 VDC (one SLC communication every 5 seconds with LED blink enabled)
Device Current Draw
DH300 6.5 mA in alarm
RA400Z10 mA maximum (DH300P), 12 mA maximum (DH300RP)
RTS451/RTS451KEY
7.5 mA maximum (DH300P), 10 mA maximum (DH300RP)
PA400Z 15 mA maximum (DH300RP)
Auxiliary Power Current Draw
DH300RP
26 mA @ 20-30 VDC (standby), 87 mA @ 20-30 VDC (alarm),65 mA @ 24 VAC (standby), 182 mA @ 24 VAC (alarm),44 mA @ 120 VAC (standby), 52 mA @ 120 VAC (alarm),25 mA @ 220/240 VAC (standby), 30 mA @ 220/240 VAC (alarm)
Alarm Auxiliary Contact Ratings
Form-C, DPDT (alarm activated Auxiliary Relay A and B), 10 amperes @ 30 VDC (resistive), 10 amperes @ 277 VAC (0.75 power factor), 240 VA @ 249 VAC (0.40 power factor);minimum switching current for auxiliary contact must be 500 mA @ 24 VDC
Supervisory Contact Ratings
Form-C SPDT Supervisory Relay, 2.0 amperes @ 30 VDC (resistive)