    Models: ATI66& ATI50INSTALLATION AND OPERATINGINSTRUCTIONS

    Please read this manual carefully prior to installation.

  • 8/6/2019 Integrated Heat Pump Water Heater

    2/13

    2

    CONTENTS

    A. IMPORTANT REMARKS 4

    B. DESCRIPTION OF HEAT PUMP 5

    C. INSTALLATIONINSTRUCTIONS 6-

    7

    D. PCB PANEL: OPTIONS & INSTRUCTIONS 8-10

    E. MAINTENANCE AND SERVICE 11-12

    F. UNIT CIRCUIT DIAGRAM 13

  • 8/6/2019 Integrated Heat Pump Water Heater

    3/13

    3

    WARNINGS:

    1. This unit must be installed byAUTHORIZED personnel only. Manufacturer cannot be heldliable for accident or injuryresulting from incorrect installation or operation of the unit.

    2. Do not have the power supply to the unit on during installation or servicing of the unit.3. Unit must not be installed near flammable objects.WATER TEMPERATURE ADJUSTMENT

    Safety and energy conservation are factors to be considered when selecting the water temperature setting via the waterheaters user interface. Water temperatures above 125F can cause severe burns or death from scalding. Be sure to readand follow the warnings outlined on the label pictured below. This label is also located on the water heater near the top ofthe tank.

    Foryoursafety,theinformationinthismanualmustbe

    followedtominimizetheriskoffireorexplosion,electric

    shock,ortopreventpropertydamage,personalinjury,or

    lossoflife.Besuretoreadandunderstandtheentire

    OwnersManualbeforeattemptingtoinstalloroperatethis

    waterheater.Itmaysaveyoutimeandcost.PayparticularattentiontotheSafetyInstructions.Failuretofollowthese

    warningscouldresultinseriousbodilyinjuryordeath.

    Shouldyouhaveproblemsunderstandingtheinstructions

    inthismanual,orhaveanyquestions,STOPandgethelp

    fromaqualifiedservicetechnicianorthelocalelectric

    utility.

  • 8/6/2019 Integrated Heat Pump Water Heater

    4/13

    4

    A. Important remarksPlease note the following before installing the unit:

    1. This unit is for indoor installation only.

    2. Ambient temperature range for operating theheat pumpis35~110.3. The air vent (for exhaust air) of the unit needs a minimum clearance of3feet from the ceiling. Do not

    insert your hand or any object into the vent.

    4. Ensure that the unit is installed on a flat surface. Unit should be secured properly to the base and

    should stand in an upright position.

    5. While moving or installing the unit, ensure that the unit does not incline more than 30degrees.6. To let the unit run efficiently, install the unit at a place with properventilation.7. Ensure that the unit is installedon a dry surface. Water inflow and outflow lines should be sealed to

    prevent leaks. Condensate water should be drained.

    8. Ensure that the unit is wired to a 220V power outlet that is rated for at least 30amperes.9. Do not change wiring scheme. Ensure wiring safety standards are met. Ensure earthing.

    10. Before turningon the unit, ensure the unitis full with water.

  • 8/6/2019 Integrated Heat Pump Water Heater

    5/13

    5

    B. Description of heat pump parts

    Unit constructions (outside):

    -2

    -1

    Decoration Bar

    Top CoverAir Outlet

    ScreenPanel

    ondensate Overflow

    Back-up Heater 2

    Hot Water Outlet

    Primary electric heater

    Cold Water Inlet

    Supporting frame

    Hand Grip

    Vent Pipe

    Upper Rim

    Ventilation Fan

    Electric Board

    Compressor

    Thermostat Controller

    Electric Heater Cover

    Anode opening

    Decoration Panel

    Left/Right Decoration Bar

    Evaporator

    Tank Cover

    Condensate DrainHole

    Host Chassis

    hassis Installation board

    Drainage hole

    Safety /T&P valve

  • 8/6/2019 Integrated Heat Pump Water Heater

    6/13

    6

    C. Installation instructions

    Note:

    1. Unit should be installed indoors in an unobstructed space. Minimum clearance space (in millimeters) is

    highlighted in the figures below. Air outlet vent maybe connected to a 6-inch (diameter) air duct.

    (Fig.1) (Fig.2)

    2. Unit should stand vertical at 90degreesdo not let the unit lean against a wall or another object.3. Ensure proper ventilation in the area where the unit is installed.

    5. Ensure both condensate water pipes are drained.

    6. For water inlet and outlet connections, please refer to Fig.3below.7. Water pressure inside the tank must not exceed 0.7MPa. Ensure T&P valve is operational.

    8. Inlet water must have a minimum pressure of0.1MPa.9. Ensure the water tank is full with water before turning on the system.

    600mm

    500mm

    800mm

    MODETIMER

    CLOCK ON/OFF

    600mm

    800mm

    ON/OFFCLOCK

    T I M E R M O D E

  • 8/6/2019 Integrated Heat Pump Water Heater

    7/13

    7

    Installation diagram:

    (Fig. 3)

    MODETIMER

    CLOCK ON/OFF

    ()

    ()

    Safety Valve Three-port ValveFilterWater Inlet

    Water Supply

    Ball

    Air Outlet

    Drainage Pipe

    Hot Water Outlet

    (Hot Water

    Vent

    Air Inlet

    Condensate Overflow drain

    Condensatewaterdrainage

  • 8/6/2019 Integrated Heat Pump Water Heater

    8/13

    8

    D. PCB panel: Options & Instructions

    1. Panel -Operation:

  • 8/6/2019 Integrated Heat Pump Water Heater

    9/13

    9

    2. Panel -Display:

    :55,""

    Set Temperature

    High Temperature

    Alarm

    Auxiliary Heater

    StatusHTG: HeatingDEF: Defrost

    WARM

    Working Mode

    Time adjustment

    Time

    Timer On

    Timer Off

    Timer Period

    Water Temperature

    Temperature Gradient

    Note:When the water temperature exceeds 131,this indicator will be lighted.

  • 8/6/2019 Integrated Heat Pump Water Heater

    10/13

    10

    3. FactorySettings:

    Type Code Parameter Name Range Factory Setting Unit Remark

    Temperature

    Control

    F11 Set temperature 90-135 135

    F12 On/off temp differential 154 10 F13

    Heat pump stop highestambient temp.

    42130 110 F14 Heat pump stop lowest ambient

    temp.040 32

    F15Temp differential to re-start the

    heat pump120 9

    Compressor F21 Compressor start delay 010 3 minuteDefrost

    F31 Defrost start temp. -2077 28 F32 Defrost finish temp. 0 122 77

    F33 Defrost start time 1999 20 minuteF34 Max. defrost time Off, 199 5 minute

    4. Error Handling:

    ERROR CODE ERROR STATUS REASONS ERROR HANDLINGA1 Thermal sensor alarm

    Water temp. sensor

    malfunction.

    1. Check the water temp. sensorconnection.

    2. Change the water temp. sensor.

    A2Condenser coil sensor

    alarmCondenser coil temp.sensor

    malfunction.

    1. Check the condenser coil temp.

    sensor connection.

    2. Change the coil sensor.

    A3 Exhaust sensor alarmExhaust temp. sensor

    malfunction.

    1. Check the exhaust temp. sensorconnection.

    2. Change the exhaust temp. sensor.

    A4Ambient temp. sensor

    alarmAmbient temp. sensor

    malfunction.

    1. Check the Ambient temp. sensorconnection.

    2. Change the ambient temp. sensor.

    A5Low /High pressure

    alarm

    1.1. High pressure protectionswitch on.

    1.2. Ambient temp. too high.

    2.1. Low pressure protectionswitch on.

    2.2. Refrigerantleak.

    1.1Check or change the high pressure

    protector.1.2. Check if the surround temp. is too

    high.2.1. Check or change the low

    pressure protector.2.2.Check refrigerant level.

    A6

    (Auxiliary) electric

    heater protection

    overheat alarm

    1. Electric heater protectionswitch on.

    2. Tank water temp. too high.

    1.Check if the water temp. is as LCDdisplay, or if water temp. is too high.

    2. Change the Electric heater.

    A7Exhaust temperature

    too high1.Refrigerantleak. 1.Check refrigerant level.2. Change lubricating oil in

    compressor.

    -- Blank screen 1. No power.2. Panel wiring problem.

    1. Check the power line and voltage.2. Check panel wiring. Change panel

    if needed.

  • 8/6/2019 Integrated Heat Pump Water Heater

    11/13

    11

    E. Maintenanceand serviceExamination before trial run

    1. Check the water tank is filled with water, and open the water outlet tap till water flow out.

    2. Check the water pressure is normal (0.15Mpa~0.7Mpa).

    3. Check the air inlet oroutlet is well connected; and the air outlet pipe heat insulation is completed.

    4. Check the power supply voltage is normal, whether according with the nameplate requirement. (Range

    10%).

    5. Check whether the equipped parts are screwed /locked well.

    6. Check whether the wirings are according with the Circuit diagram, and the earth-wire is connected.

    7. Check whether the wind inlet and outlet has been cleaned up and no obstacle.

    8. Check whether the condensate drain pipe is connected well and no blockage.

    9. After power-ON, check the control panel display is normal.

    Trial running

    1. After the machine starts, to hear and determine whether there is abnormal sound or collision during

    operation, if there is abnormal sound, stop the unit immediately and check for it until there is no

    abnormal sound to continue operation.

    2. For the first time power on, the compressor will have 3minutes delay protection function.3. Observe whether the drainage of condensate water is smooth, prevent the chassis stagnant or spill

    water.

    4. For the first time discharge hot water or start the units after a long time closure, the water tap of outlet

    pipe may flow muddy water, this is a normal phenomenon, and continue to drain for a period of time can

    be cleared.

    5. After stop operation for a long time, there may have condensation water hereabout the air outlet or pipe(especial in humidity weather), this is a normal phenomenon, use a dry washcloth to clean it or by air

    dry.

    6. The advance setting parameters of the operation panel has been set at the factory, users no need toreset it, the maintenance person should be carefully set if needed.

  • 8/6/2019 Integrated Heat Pump Water Heater

    12/13

    12

    E. Maintenanceand service

    Heat Pump main unit disassembly

    Follow the steps in Figures 4 & 5 to disassemble the unit.

    (Fig.4) (Fig.5)

    1.Slideout Control panel along the slot.

    2. Loosen the PCB panel wire.

    3. Unfasten the decorative plate screwand removethe decorative panel.4. Loosen thescrewson this metal bar.5. Loosen the bottom screws of the top cover.

    6. Remove the power line from the top cover

    4

    5

    7

    6

    3

    2

    1

    MODETIMER

    CLOCK ON/OFF

  • 8/6/2019 Integrated Heat Pump Water Heater

    13/13

    13

    F. Unit circuitdiagramHeat pump WITH auxiliary electric heater:

    L1 Line1

    L2 Line2

    NG Neutral / Ground

    *Note: Back-Up Heater will only activate when Primary Heater fails.

    Elect Valve FanComp

    1 2

    3OPERATION PANELWATER TEMP.SENSOR 2

    COIL TEMP.SENSORAMBIENT TEMP.SENSOR EXHAUST TEMP.SENSOR

    PRESURE PROTECTOR

    LN

    YELLOW/GREEN

    YELLOW/GREEN

    YELLOW/GREEN

    ELECTRIC HEATER-1TEMP.SENSOR

    YELLOW/GREENELECTRIC.HEATER-2

    901251502

    4231

    /

    ELECTRIC.HEATER-1

    YELLOW/GREENC

    S R

    COMPRESSOR ELECTRIC HEATER-1 PROTECTOR

    4-WAY VALVEFAN MOTOR

    L1 NGL2 L1 NGL2

    Primary Heater Back-Up Heater