Integrated Control System(ICS)
1
( )
Chapter 9.0B&W Cross-Training Course
R-326C
![Page 2: Integrated Control System (ICS) ()Integrated Control System • Basic function is to match generated electrical megawatts with demanded electrical megawatts. • ICS helps maintain](https://reader035.fdocuments.in/reader035/viewer/2022081615/5fe37b25539d3b58b67802d4/html5/thumbnails/2.jpg)
OBJECTIVES
1. Explain the function of the following ICS subassemblies:
a. Unit Load Demand (ULD)b. Integrated Master (IM)c. Feedwater Demand
2
d. Reactor Demand
2. Define the following terms:a. Trackb. Runbackc. Cross limits
![Page 3: Integrated Control System (ICS) ()Integrated Control System • Basic function is to match generated electrical megawatts with demanded electrical megawatts. • ICS helps maintain](https://reader035.fdocuments.in/reader035/viewer/2022081615/5fe37b25539d3b58b67802d4/html5/thumbnails/3.jpg)
OBJECTIVES
3. With the use of a block diagram of the ICS, discuss the following:a. Normal power increase & decrease.
b. Runbacks.
c Cross limits
3
c. Cross limits.
d. Placing an ICS hand/auto station in manual (hand).
e. Turbine trip.
![Page 4: Integrated Control System (ICS) ()Integrated Control System • Basic function is to match generated electrical megawatts with demanded electrical megawatts. • ICS helps maintain](https://reader035.fdocuments.in/reader035/viewer/2022081615/5fe37b25539d3b58b67802d4/html5/thumbnails/4.jpg)
Integrated Control System (ICS)
• Provides simultaneous control of:Turbine load (MWe)
Turbine bypass valves & atmospheric dump valves.
Feedwater control valves
4
MFP speed
Control rod position
• Allows plant to automatically maneuver from 15% - 100%.
Up to 5% per min.
![Page 5: Integrated Control System (ICS) ()Integrated Control System • Basic function is to match generated electrical megawatts with demanded electrical megawatts. • ICS helps maintain](https://reader035.fdocuments.in/reader035/viewer/2022081615/5fe37b25539d3b58b67802d4/html5/thumbnails/5.jpg)
Integrated Control System
• Basic function is to match generated electrical megawatts with demanded electrical megawatts.
• ICS helps maintain a balance between heat generation & heat removal.
5
• Many “adjusting” features:RCS can be operated with unequal loop flows.OTSGs do not have moisture separation equipment and must superheat steam sufficiently.
![Page 6: Integrated Control System (ICS) ()Integrated Control System • Basic function is to match generated electrical megawatts with demanded electrical megawatts. • ICS helps maintain](https://reader035.fdocuments.in/reader035/viewer/2022081615/5fe37b25539d3b58b67802d4/html5/thumbnails/6.jpg)
Simplified Integrated
Control System Fig. 9-1
![Page 7: Integrated Control System (ICS) ()Integrated Control System • Basic function is to match generated electrical megawatts with demanded electrical megawatts. • ICS helps maintain](https://reader035.fdocuments.in/reader035/viewer/2022081615/5fe37b25539d3b58b67802d4/html5/thumbnails/7.jpg)
• Runback – an automatic reduction in plant load when necessary power generation equipment is lost or its capacity is reduced.
Reduces load to a preset value at a predetermined rate.
• Cross Limits –
Definitions
Act to help maintain a balance between heat generation (Rx Power) & heat removal (FW Flow).
Normally only a factor during rapid load changes or transients.
If Rx demand signal differs from Rx power by >5%, FW demand is adjusted. If FW demand exceeds total FW flow by >5%, then Rx demand is reduced.
• Track – a condition in which actual generated MWe is substituted for the demanded MWesignal
![Page 8: Integrated Control System (ICS) ()Integrated Control System • Basic function is to match generated electrical megawatts with demanded electrical megawatts. • ICS helps maintain](https://reader035.fdocuments.in/reader035/viewer/2022081615/5fe37b25539d3b58b67802d4/html5/thumbnails/8.jpg)
Integrated Control System (Fig. 9-2)
![Page 9: Integrated Control System (ICS) ()Integrated Control System • Basic function is to match generated electrical megawatts with demanded electrical megawatts. • ICS helps maintain](https://reader035.fdocuments.in/reader035/viewer/2022081615/5fe37b25539d3b58b67802d4/html5/thumbnails/9.jpg)
9
TBVs/ADVs Setpoints Fig. 9-3
![Page 10: Integrated Control System (ICS) ()Integrated Control System • Basic function is to match generated electrical megawatts with demanded electrical megawatts. • ICS helps maintain](https://reader035.fdocuments.in/reader035/viewer/2022081615/5fe37b25539d3b58b67802d4/html5/thumbnails/10.jpg)
10Response of Steam Pressure on a Reactor Trip (Fig. 9-4)
![Page 11: Integrated Control System (ICS) ()Integrated Control System • Basic function is to match generated electrical megawatts with demanded electrical megawatts. • ICS helps maintain](https://reader035.fdocuments.in/reader035/viewer/2022081615/5fe37b25539d3b58b67802d4/html5/thumbnails/11.jpg)
Feedwater Temperature
vs. Steam Flow
11
Fig. 9-5
![Page 12: Integrated Control System (ICS) ()Integrated Control System • Basic function is to match generated electrical megawatts with demanded electrical megawatts. • ICS helps maintain](https://reader035.fdocuments.in/reader035/viewer/2022081615/5fe37b25539d3b58b67802d4/html5/thumbnails/12.jpg)
12Feedwater Regulating Valve Sequence (Fig. 9-6)
![Page 13: Integrated Control System (ICS) ()Integrated Control System • Basic function is to match generated electrical megawatts with demanded electrical megawatts. • ICS helps maintain](https://reader035.fdocuments.in/reader035/viewer/2022081615/5fe37b25539d3b58b67802d4/html5/thumbnails/13.jpg)
Rod Motion VS.
N t E
13
Neutron ErrorFig. 9-7
![Page 14: Integrated Control System (ICS) ()Integrated Control System • Basic function is to match generated electrical megawatts with demanded electrical megawatts. • ICS helps maintain](https://reader035.fdocuments.in/reader035/viewer/2022081615/5fe37b25539d3b58b67802d4/html5/thumbnails/14.jpg)
Reactor Demand
14
Subassembly Interlocks
Fig. 9-8
![Page 15: Integrated Control System (ICS) ()Integrated Control System • Basic function is to match generated electrical megawatts with demanded electrical megawatts. • ICS helps maintain](https://reader035.fdocuments.in/reader035/viewer/2022081615/5fe37b25539d3b58b67802d4/html5/thumbnails/15.jpg)
BTU LimitsFig. 9-9
15
![Page 16: Integrated Control System (ICS) ()Integrated Control System • Basic function is to match generated electrical megawatts with demanded electrical megawatts. • ICS helps maintain](https://reader035.fdocuments.in/reader035/viewer/2022081615/5fe37b25539d3b58b67802d4/html5/thumbnails/16.jpg)
Table 9-1Runback Conditions
Condition Runback Rate Maximum Load Value
Loss of an RCP 50%/minute 75% generated Mw
Loss of 2 RCPs 50%/minute 50% generated Mw
Loss of a MFP 50%/minute 60% generated Mw
Asymmetric Rod 30%/minute 60% generated Mw
16
RCS Flow(Total Core Flow)
20%/minute Value required to maintaincorrect power/flow ratio
![Page 17: Integrated Control System (ICS) ()Integrated Control System • Basic function is to match generated electrical megawatts with demanded electrical megawatts. • ICS helps maintain](https://reader035.fdocuments.in/reader035/viewer/2022081615/5fe37b25539d3b58b67802d4/html5/thumbnails/17.jpg)
Table 9-2 (Item 1) Unit Load Demand Tracking Relay
17
![Page 18: Integrated Control System (ICS) ()Integrated Control System • Basic function is to match generated electrical megawatts with demanded electrical megawatts. • ICS helps maintain](https://reader035.fdocuments.in/reader035/viewer/2022081615/5fe37b25539d3b58b67802d4/html5/thumbnails/18.jpg)
Integrated Master Tracking Relay: T2
Item 2
18
![Page 19: Integrated Control System (ICS) ()Integrated Control System • Basic function is to match generated electrical megawatts with demanded electrical megawatts. • ICS helps maintain](https://reader035.fdocuments.in/reader035/viewer/2022081615/5fe37b25539d3b58b67802d4/html5/thumbnails/19.jpg)
Table 9-2, Item 3TBV/Atmospheric Dump Valve Bias Selection
19
![Page 20: Integrated Control System (ICS) ()Integrated Control System • Basic function is to match generated electrical megawatts with demanded electrical megawatts. • ICS helps maintain](https://reader035.fdocuments.in/reader035/viewer/2022081615/5fe37b25539d3b58b67802d4/html5/thumbnails/20.jpg)
Table 9-2, Item 4
20
![Page 21: Integrated Control System (ICS) ()Integrated Control System • Basic function is to match generated electrical megawatts with demanded electrical megawatts. • ICS helps maintain](https://reader035.fdocuments.in/reader035/viewer/2022081615/5fe37b25539d3b58b67802d4/html5/thumbnails/21.jpg)
FW Demand Reactor Trip Transfer: T10 & T11
Item 5
21
![Page 22: Integrated Control System (ICS) ()Integrated Control System • Basic function is to match generated electrical megawatts with demanded electrical megawatts. • ICS helps maintain](https://reader035.fdocuments.in/reader035/viewer/2022081615/5fe37b25539d3b58b67802d4/html5/thumbnails/22.jpg)
FW Demand Low-Level Limit Selection Transfer: T12 & T13, Item 6
22
![Page 23: Integrated Control System (ICS) ()Integrated Control System • Basic function is to match generated electrical megawatts with demanded electrical megawatts. • ICS helps maintain](https://reader035.fdocuments.in/reader035/viewer/2022081615/5fe37b25539d3b58b67802d4/html5/thumbnails/23.jpg)
Rx Demand Tave Transfer T14, Item 7
23